Karnataka State Police Housing And Infrastructure Development Corporation Limited Tender

Karnataka, also known as Karunadu, is a state in the southwestern region of India. Karnataka was formed originally as Mysore State on 1st November 1956 and currently is the biggest state in south India. Its capital and largest city is Bengaluru. It covers an area of 191,791 km2 (74,051 sq mi) and is the sixth largest state by area comprising 31 districts. Karnataka is also a state of multiple languages; Kannada being the official and most widely spoken language in Karnataka. Other languages spoken in the state include Tamil, Telugu, Malayalam, Kodava, Konkani and much more.Karnataka tenders are issued by the government of Karnataka, public & private sector organisations. The state government issues majority of the Karnataka tenders, which are for goods and services including construction, road and bridge construction, IT services, engineering services, medical services, educational services amongst many others. Bidassist is one of the largest eprocurement portals, which offers all government tenders from across the world in one place. Bidassist offers information on all Karnataka tenders and other state and authority tenders in no time. Bidassist is a platform where users can look for various Karnataka tenders as well as other tenders.

Karnataka State Police Housing And Infrastructure Development Corporation Limited - KSPHCL Tender

Building Construction
Opening Date4 Oct 2021
Closing Date21 Oct 2021
Tender Amount₹ 11,10,56,557 
This is an estimated amount, exact amount may vary.
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Supplying And Fixing Metal Fan Box with Round Hook. ---- as per directions of engineer incharge of work.

95

-

8075

... More
Supplying heavy gauge PVC Conduit Pipe .... dia ....... mm thick with suitable size bends, metal junction boxes adhesive paste etc., by groove cutting in the wall and fixing by bracing U or J hooks and cement plastering up to the wall surface and run with 18 SWG GI fish wire run throughout the conduit wherever necessary. - 19/20mm dia 2mm thick ---- as per directions of engineer incharge of work.

2500

-

127500

... More
Supplying heavy gauge PVC Conduit Pipe .... dia ....... mm thick with suitable size bends, metal junction boxes adhesive paste etc., by groove cutting in the wall and fixing by bracing U or J hooks and cement plastering up to the wall surface and run with 18 SWG GI fish wire run throughout the conduit wherever necessary. - 25mm dia 2mm thick ---- as per directions of engineer incharge of work.

2500

-

135000

... More
Supplying heavy gauge PVC Conduit Pipe .... dia ....... mm thick with suitable size bends, metal junction boxes adhesive paste etc., by groove cutting in the wall and fixing by bracing U or J hooks and cement plastering up to the wall surface and run with 18 SWG GI fish wire run throughout the conduit wherever necessary. - 32mm dia 2.5mm thick ---- as per directions of engineer incharge of work.

500

-

40500

... More
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall - 1-3Way ---- as per directions of engineer incharge of work.

150

-

14250

... More
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall - 4-5Way ---- as per directions of engineer incharge of work.

200

-

21000

... More
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall - 6Way ---- as per directions of engineer incharge of work.

250

-

31250

... More
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall - 8Way ---- as per directions of engineer incharge of work.

200

-

29000

... More
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall - 10-12Way ---- as per directions of engineer incharge of work.

50

-

8250

... More
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. - 1 to 3 Module ---- as per directions of engineer incharge of work.

150

-

16500

... More
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. - 4 Module ---- as per directions of engineer incharge of work.

200

-

25000

... More
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. - 6 Module ---- as per directions of engineer incharge of work.

250

-

43750

... More
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. - 8 Module ---- as per directions of engineer incharge of work.

200

-

40000

... More
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. - 10-12 Module ---- as per directions of engineer incharge of work.

50

-

11500

... More
Point wiring using Copper wire without switch. Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box, the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each outlet. - Short point upto 3Mtr from tapping point to out let via switch box ---- as per directions of engineer incharge of work.

100

-

16000

... More
Point wiring using Copper wire without switch. Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box, the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each outlet. - Medium point above 3Mtr upto 6Mtr from tapping point to out let via switch box ---- as per directions of engineer incharge of work.

150

-

37500

... More
Point wiring using Copper wire without switch. Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box, the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each outlet. - Long point above 6Mtr upto 10Mtr from tapping point to out let via switch box ---- as per directions of engineer incharge of work.

250

-

93750

... More
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments.The following additional tests are compulsory either to be conducted at works or independent lab with witness by inspecting authority.Additional Tests for FRLS-Applicable Standard Oxygen Index -IS 694-1990, Clause 16.8 Temperature Index -IS 694-1990, Clause 16.13 Smoke Density -IS 694-1990, Clause 16.14 Test for Halogen Acid Gas evaluation -IS 694-1990, Clause 16.12 - 1.5 sqmm ---- as per directions of engineer incharge of work.

8200

-

168100

... More
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments.The following additional tests are compulsory either to be conducted at works or independent lab with witness by inspecting authority.Additional Tests for FRLS-Applicable Standard Oxygen Index -IS 694-1990, Clause 16.8 Temperature Index -IS 694-1990, Clause 16.13 Smoke Density -IS 694-1990, Clause 16.14 Test for Halogen Acid Gas evaluation -IS 694-1990, Clause 16.12 - 2.5 sqmm ---- as per directions of engineer incharge of work.

6000

-

192000

... More
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments.The following additional tests are compulsory either to be conducted at works or independent lab with witness by inspecting authority.Additional Tests for FRLS-Applicable Standard Oxygen Index -IS 694-1990, Clause 16.8 Temperature Index -IS 694-1990, Clause 16.13 Smoke Density -IS 694-1990, Clause 16.14 Test for Halogen Acid Gas evaluation -IS 694-1990, Clause 16.12 - 4 sqmm ---- as per directions of engineer incharge of work.

4000

-

180000

... More
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments.The following additional tests are compulsory either to be conducted at works or independent lab with witness by inspecting authority.Additional Tests for FRLS-Applicable Standard Oxygen Index -IS 694-1990, Clause 16.8 Temperature Index -IS 694-1990, Clause 16.13 Smoke Density -IS 694-1990, Clause 16.14 Test for Halogen Acid Gas evaluation -IS 694-1990, Clause 16.12 - 6 sqmm ---- as per directions of engineer incharge of work.

2800

-

196000

... More
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. - 6Amps one way Switch ---- as per directions of engineer incharge of work.

450

-

31500

... More
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. - 6Amps Two way Switch ---- as per directions of engineer incharge of work.

25

-

2375

... More
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. - 6Amps 3way socket ---- as per directions of engineer incharge of work.

285

-

29925

... More
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. - 6/16Amps universal socket ---- as per directions of engineer incharge of work.

150

-

24300

... More
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. - Stepped Fan Regulator. ---- as per directions of engineer incharge of work.

95

-

27550

... More
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. - TV/Telephone socket ---- as per directions of engineer incharge of work.

10

-

790

... More
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. - 6Amps Bell push ---- as per directions of engineer incharge of work.

10

-

960

... More
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. - 32Amps DP switch ---- as per directions of engineer incharge of work.

60

-

10920

... More
Supplying and fixing one of 230 volts Ding dong bell and a flush type bell push with gang box fixed on necessary wooden or rawl plugs using NF screws with Remote. - Ding Dong Bell ---- as per directions of engineer incharge of work.

12

-

2640

... More
Supplying capacitor type ceiling fan complete with down rod blades, shackle, canopies etc, for operation on 230 volts, 50 cycles. Single phase AC supply conforming to ISS-374- 1979 and with double ball bearing system. - 48" Sweep (1200mm) Regular model ---- as per directions of engineer incharge of work.

100

-

209000

... More
Fixing a ceiling / Wall mounting fan of all capacities and all types to the existing 'S'' hook with fan regulator to the existing board together with supplying and fixing 5 amps. ceiling rose, necessary length of 23 / 0.0076 inch PVC insulated twin twisted copper wire and wiring. ---- as per directions of engineer incharge of work.

100

-

15000

... More
Supplying exhaust fan of 1440 RPM of 300mm (12") size with bracket blades complete for light duty suitable to operate on 230V 50Hz, AC Supply. ---- as per directions of engineer incharge of work.

20

-

24000

... More
Fixing one exhaust fan in the nitch already left in the wall with bolts and nuts and 5 amps. ceiling rose with sufficient length of 23/0.0076 inch PVC insulated twin core wire. ---- as per directions of engineer incharge of work.

20

-

8000

... More
Supplying of .....feet -PVC Batten with integrated LED tube .... W with high quality diffuser with Life of 25000 burning hours & 70% lumen maintenance with CRI > 80. Power Input: 220-240V@ 50/60Hz & Power factor >0.9 along with CE approved. 2 years Warranty against any manufacturing defect working under standard electrical condition. - LED light fitting 1 x 4'- 20/22 w ---- as per directions of engineer incharge of work.

60

-

22500

... More
Fixing all types and all capacities of fluorescent /false ceiling / spot light / CFL / LED fittings indoor on the wall/ ceiling / rafters / girders using 23/0.0076" twin twisted PVC insulated wires, required Nos of round blocks and clamps. - On wall/ ceiling / Rafter / Girders ---- as per directions of engineer incharge of work.

50

-

5500

... More
Supplying of recess mounting non integral type ........ LED w luminaire comprising of pressure decast/extruded aluminium housing, with spring loaded false ceiling clamps, Power LEDs with CCT 6500 degree K, CRI> 70%. efficacy > 100 lumen per watt, 120degree beam spread, life> 25000 burning hours and Compliance to IS 10322/IEC 60598, LM 79 & LM 80. The lamp compartment is enclosed with anti glare opal diffuser which enhances the lighting level LEDs are driven by HF electronic driver integrated in a separate control gear assembly., with PF > 0.95, power loss should< 5% of lamp wattage., short circuit & open circuit protection to be integrated in the circuit, THD less than 20%, Life as per LM 79. The operating input voltage should be between 130 to 275 volts. BIS Approved and Tested by NABL/CPRI accredited laboratory with 2 years Warranty against any manufacturing defect working under standard electrical condition. - LED modular down light 2'x2' /1' X 4' 34 -36watt ---- as per directions of engineer incharge of work.

200

-

1040000

... More
Supplying & fixing of retrofit type - LED bulb ...... W with OPAL acrylic diffuser comprising of LED source with CCT 6500 degree K, CRI> 70%. efficacy >80 lumen per watt, life> 25000 burning hours and Compliance to IS 10322/IEC 60598, LM 79 & LM 80. The LED are driven by HF electronic driver integrated in the system, with PF > 0.95, power loss should < 5% of lamp wattage., short circuit & open circuit protection to be integrated in the circuit, THD less than 20%, Life as per LM 79. The operating input voltage should be between 130 to 275 volts. BIS Approved and Tested by NABL/CPRI accredited laboratory with 2 years Warranty against any manufacturing defect working under standard electrical condition. - 12W, 6500K ---- as per directions of engineer incharge of work.

125

-

20625

... More
LED Down light :Supplying of recess mounting non integrated type LED down light...... W luminaire comprising of pressure decast/ extruded aluminium housing, with spring loaded false ceiling clamps, LED of Power/COB with CCT 6500 degree K, CRI> 70%. efficacy >100 lumen per watt, 120degree beam spread, life> 25000 burning hours and Compliance to IS10322/IEC 60598, LM 79 & LM 80. The lamp compartment is enclosed with anti glare opal diffuser which enhances the lighting level. LED's are driven by HF electronic driver integrated in a separate control gear assembly., with PF > 0.95, power loss should< 5% of lamp wattage, short circuit & open circuit protection to be integrated in the circuit, THD less than 20%, Life as per LM 79. The operating input voltage should be between 130 to 275 volts. BIS Approved and Tested by NABL/CPRI accredited laboratory with 2 years Warranty against any manufacturing defect working under standard electrical condition. - 10-12W ---- as per directions of engineer incharge of work.

75

-

102000

... More
Supply of round/square recess/surface mounted rolling type LED Down light with ...... W GU 10 LED Lamp Rib Fabricated from diecast aluminium with white powder coated prewired to mains connector & has swivelling unit of aluminium die cast eye ball & LED Lamp position retained by circular wire spring, with Life of 25000 burning hours & 70% lumen maintenance with CRI > 80. Power Input: 220-240V @50/60Hz & Power factor >0.9 along with CE approved. 2years Warranty against any manufacturing defect working under standard electrical condition - LED square or round down light 15-18W ---- as per directions of engineer incharge of work.

120

-

138000

... More
Supplying and fixing regular MCB distribution boards on wall/ood board / flush mounting using required clamps, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase/3 phase/single door with powder coated painting Made out of 14 SWG MS enclosure. 1- Single Door II -Double Door Ill -Double Door - 8Way SP &N ---- as per directions of engineer incharge of work.

13

-

18850

... More
Supplying and fixing regular MCB distribution boards on wall/ood board / flush mounting using required clamps, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase/3 phase/single door with powder coated painting Made out of 14 SWG MS enclosure. 1- Single Door II -Double Door Ill -Double Door - 6Way TP &N ---- as per directions of engineer incharge of work.

6

-

19980

... More
Supplying and fixing regular MCB distribution boards on wall/ood board / flush mounting using required clamps, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase/3 phase/single door with powder coated painting Made out of 14 SWG MS enclosure. 1- Single Door II -Double Door Ill -Double Door - 12Way TP &N ---- as per directions of engineer incharge of work.

8

-

46800

... More
Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898. - 6-32Amps SP ---- as per directions of engineer incharge of work.

100

-

43400

... More
Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898. - 6-32Amps DP ---- as per directions of engineer incharge of work.

100

-

90900

... More
Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898. - 6-32Amps TPN ---- as per directions of engineer incharge of work.

20

-

34300

... More
Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898. - 40 Amps TPN ---- as per directions of engineer incharge of work.

12

-

28488

... More
Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898. - 50-63Amps TPN ---- as per directions of engineer incharge of work.

4

-

9588

... More
Supplying, fixing and wiring Earth Leakage Miniature Circuit Breaker (ELMCB) 240/450V up to 300mA sensitivity on existing wood/panel board. - 16-25 Amps 2 pole ---- as per directions of engineer incharge of work.

16

-

36800

... More
Fabricating supplying and mounting MS box made out ....SWG suitable for floor /wall mounting, fully weather proof with provision for better heat dissipation, provided with hinged front cover, equipped with tamper proof locking arrangements, with suitable size clamps with necessary cable entry pipe with gland and box should be finished with 7tanks treatment with powder coated paint and finally finished with approved colour etc., complete. - 16SWG ---- as per directions of engineer incharge of work.

325000

-

113750

... More
Supplying and fixing angle iron frame work fabricated out of M.S. angle iron.. and M.S. Flat......with bolts, washers etc., and painted with 2 coats of red oxide and then two coats of approved paint. - 50x50x6mm ---- as per directions of engineer incharge of work.

50

-

16500

... More
Supplying ......... amps rated 3phase with neutral bus bar using required capacity electrolytic aluminium strips covered with heat shrinkable coloured PVC sleeve, mounted on phenolic/FRP/DMC insulator which are mounted on powder coated 40x6mm M.S.flat frame work in existing panel board. The bus bar shall have suitable holes for termination of incoming and outgoing cables as per IS specification with necessary bolts, nuts and washers etc., complete. - 100Amps 4x30x6mm Aluminium Strips ---- as per directions of engineer incharge of work.

8

-

16400

... More
Supplying ......... amps rated 3phase with neutral bus bar using required capacity electrolytic aluminium strips covered with heat shrinkable coloured PVC sleeve, mounted on phenolic/FRP/DMC insulator which are mounted on powder coated 40x6mm M.S.flat frame work in existing panel board. The bus bar shall have suitable holes for termination of incoming and outgoing cables as per IS specification with necessary bolts, nuts and washers etc., complete. - 400Amps 4x50x10mm Aluminium Strips ---- as per directions of engineer incharge of work.

8

-

29600

... More
Supplying ......... amps rated 3phase with neutral bus bar using required capacity electrolytic aluminium strips covered with heat shrinkable coloured PVC sleeve, mounted on phenolic/FRP/DMC insulator which are mounted on powder coated 40x6mm M.S.flat frame work in existing panel board. The bus bar shall have suitable holes for termination of incoming and outgoing cables as per IS specification with necessary bolts, nuts and washers etc., complete. - 1000Amps double run of 4x60x10mm Aluminium Strips ---- as per directions of engineer incharge of work.

16

-

140800

... More
Supplying of on load change over switches 4 poles, AC-23A Duty, 415V, 50Hz, AC Supply. (Open Execution) - 800Amps ---- as per directions of engineer incharge of work.

1

-

41100

... More
Supplying of on load change over switches 4 poles, AC-23A Duty, 415V, 50Hz, AC Supply. (Open Execution) - 400Amps ---- as per directions of engineer incharge of work.

1

-

23600

... More
Supplying and fixing Moulded Case Circuit Breaker (MCCB) over the existing wood/panel board using necessary screws, bolts, nuts, necessary phase separators, handle and wiring complete. Protection of Overload and Short circuit with thermal Magnetic/Micro processor release and Earth Fault as per IS-13947. (Icu=lcs) THREE POLE FOUR POLE - 700-800Amps 50kA ---- as per directions of engineer incharge of work.

2

-

80600

... More
Supplying and fixing Moulded Case Circuit Breaker (MCCB) over the existing wood/panel board using necessary screws, bolts, nuts, necessary phase separators, handle and wiring complete. Protection of Overload and Short circuit with thermal Magnetic/Micro processor release and Earth Fault as per IS-13947. (Icu=lcs) THREE POLE FOUR POLE - 400-500Amps 50kA ---- as per directions of engineer incharge of work.

2

-

54400

... More
Supplying and fixing Moulded Case Circuit Breaker (MCCB) over the existing wood/panel board using necessary screws, bolts, nuts, necessary phase separators, handle and wiring complete. Protection of Overload and Short circuit with thermal Magnetic/Micro processor release and Earth Fault as per IS-13947. (Icu=lcs) THREE POLE FOUR POLE - 320-400Amps 50kA ---- as per directions of engineer incharge of work.

2

-

52000

... More
Supplying and fixing Moulded Case Circuit Breaker (MCCB) over the existing wood/panel board using necessary screws, bolts, nuts, necessary phase separators, handle and wiring complete. Protection of Overload and Short circuit with thermal Magnetic/Micro processor release and Earth Fault as per IS-13947. (Icu=lcs) THREE POLE FOUR POLE - 100Amps 25kA ---- as per directions of engineer incharge of work.

10

-

64000

... More
Supplying, fixing and wiring 3 Phase Digital Ammeter / Voltmeter ---- as per directions of engineer incharge of work.

12

-

14220

... More
Supplying, fixing and wiring 50/5 to 400/5Amps 5VA burden Current Transformer Class 0.5 accuracy with Tape Wound. ---- as per directions of engineer incharge of work.

8

-

3744

... More
Supplying and fixing of LED type panel board indicating lamp with required colour suitable for 230/440VAC. 50 Hz 12/24V D.C. ---- as per directions of engineer incharge of work.

18

-

7740

... More
Supplying, fixing and wiring earth leakage relay with core balanced current transformer suitable for single phase 50 Hz AC with latest microcontroller based, digital readout of percentage leakage current, programmable delay/auto/ manual reset facility suitable to mount on DIN rail/ flush mounting on panel board. ---- as per directions of engineer incharge of work.

10

-

77000

... More
Supplying & fixing of Porcelain fuse channel with cut out on existing wooden/panel using necessary nuts, bolts and washers. - 32Amps ---- as per directions of engineer incharge of work.

30

-

5220

... More
Supplying & fixing of Porcelain fuse channel with cut out on existing wooden/panel using necessary nuts, bolts and washers. - 63Amps ---- as per directions of engineer incharge of work.

36

-

8172

... More
Supplying tinned copper lugs and crimping and wiring to terminal point for wire of the following sizes. - 400 sqmm Long Barrel ---- as per directions of engineer incharge of work.

8

-

7576

... More
Supplying tinned copper lugs and crimping and wiring to terminal point for wire of the following sizes. - 240 sqmm Long Barrel ---- as per directions of engineer incharge of work.

20

-

9260

... More
Supplying tinned copper lugs and crimping and wiring to terminal point for wire of the following sizes. - 185 sqmm Long Barrel ---- as per directions of engineer incharge of work.

4

-

1308

... More
Supplying tinned copper lugs and crimping and wiring to terminal point for wire of the following sizes. - 50 sqmm Long Barrel ---- as per directions of engineer incharge of work.

6

-

360

... More
Supplying tinned copper lugs and crimping and wiring to terminal point for wire of the following sizes. - 25 sqmm Long Barrel ---- as per directions of engineer incharge of work.

2

-

40

... More
Supplying tinned copper lugs and crimping and wiring to terminal point for wire of the following sizes. - 16 sqmm ---- as per directions of engineer incharge of work.

22

-

273.68

... More
Supplying tinned copper lugs and crimping and wiring to terminal point for wire of the following sizes. - 10 sqmm ---- as per directions of engineer incharge of work.

16

-

128

... More
Supplying and fixing of heavy duty cable glands suitable for UG cable of 1.1 KV class (metal only) - 32mm dia ---- as per directions of engineer incharge of work.

2

-

234

... More
Supplying PVC/GI flexible conduit pipe .... mm dia fixing on surface over inverted tapered wooden plugs or phill plugs or rawl plugs and clamped using heavy gauge saddles at an interval of 300mm using NF screws and on either end of the pipe terminated completely - 20mm ---- as per directions of engineer incharge of work.

50

-

1100

... More
Supplying of 1.1 KV LT UG cable XLPE or Heat resistant PVC insulated, PVC extruded Inner sheath armoured UG LT cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armouring strip thickness in average +5% and resistivity 14 Ohms/Kms (Max) as per IS-3975 - 3.5 core 150 sqmm ---- as per directions of engineer incharge of work.

130

-

93600

... More
Supplying of 1.1 KV LT UG cable XLPE or Heat resistant PVC insulated, PVC extruded Inner sheath armoured UG LT cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armouring strip thickness in average +5% and resistivity 14 Ohms/Kms (Max) as per IS-3975 - 3.5 core 400 sqmm ---- as per directions of engineer incharge of work.

150

-

264000

... More
Labour charges for laying of 1.1 KV class UG cable in existing trench GI pipe/ stoneware pipe /on wall / on pole as required. In existing trench/duct. On wall/Structure - 300 sqmm to 400 sqmm ---- as per directions of engineer incharge of work.

150

-

4800

... More
Supplying of 1.1 KV LT UG cable XLPE or Heat resistant PVC insulated, PVC extruded Inner sheath armoured UG LT cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armouring strip thickness in average +5% and resistivity 14 Ohms/Kms (Max) as per IS-3975 - 3.5 core 240 sqmm ---- as per directions of engineer incharge of work.

180

-

203400

... More
Labour charges for laying of 1.1 KV class UG cable in existing trench GI pipe/ stoneware pipe /on wall / on pole as required. In existing trench/duct. On wall/Structure - 185 sqmm to 240 sqmm ---- as per directions of engineer incharge of work.

180

-

6300

... More
Supplying of 1.1 KV LT UG cable XLPE or Heat resistant PVC insulated, PVC extruded Inner sheath armoured UG LT cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armouring strip thickness in average +5% and resistivity 14 Ohms/Kms (Max) as per IS-3975 - 3.5 core 240 sqmm ---- as per directions of engineer incharge of work.

75

-

84750

... More
Labour charges for laying of 1.1 KV class UG cable in existing trench GI pipe/ stoneware pipe /on wall / on pole as required. In existing trench/duct. On wall/Structure - 185 sqmm to 240 sqmm ---- as per directions of engineer incharge of work.

75

-

2625

... More
Supplying of 1.1 KV LT UG cable XLPE or Heat resistant PVC insulated, PVC extruded Inner sheath armoured UG LT cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armouring strip thickness in average +5% and resistivity 14 Ohms/Kms (Max) as per IS-3975 - 3.5 core 95 sqmm ---- as per directions of engineer incharge of work.

50

-

24250

... More
Labour charges for laying of 1.1 KV class UG cable in existing trench GI pipe/ stoneware pipe /on wall / on pole as required. In existing trench/duct. On wall/Structure - 95 sqmm to 150 sqmm ---- as per directions of engineer incharge of work.

200

-

4200

... More
Supplying of 1.1 KV LT UG cable XLPE or Heat resistant PVC insulated, PVC extruded Inner sheath armoured UG LT cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armouring strip thickness in average +5% and resistivity 14 Ohms/Kms (Max) as per IS-3975 - 3.5 core 25 sqmm ---- as per directions of engineer incharge of work.

50

-

9000

... More
Labour charges for laying of 1.1 KV class UG cable in existing trench GI pipe/ stoneware pipe /on wall / on pole as required. In existing trench/duct. On wall/Structure - 25 sqmm to 75 sqmm ---- as per directions of engineer incharge of work.

50

-

775

... More
Supplying of 1.1 KV LT UG cable XLPE or Heat resistant PVC insulated, PVC extruded Inner sheath armoured UG LT cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armouring strip thickness in average +5% and resistivity 14 Ohms/Kms (Max) as per IS-3975 - 4 core 16 sqmm ---- as per directions of engineer incharge of work.

250

-

37500

... More
Labour charges for laying of 1.1 KV class UG cable in existing trench GI pipe/ stoneware pipe /on wall / on pole as required. In existing trench/duct. On wall/Structure - 6 sqmm to 16 sqmm ---- as per directions of engineer incharge of work.

250

-

2970

... More
Supplying of 1.1 KV LT UG cable XLPE or Heat resistant PVC insulated, PVC extruded Inner sheath armoured UG LT cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armouring strip thickness in average +5% and resistivity 14 Ohms/Kms (Max) as per IS-3975 - 4 core 10 sqmm ---- as per directions of engineer incharge of work.

100

-

13000

... More
Labour charges for laying of 1.1 KV class UG cable in existing trench GI pipe/ stoneware pipe /on wall / on pole as required. In existing trench/duct. On wall/Structure - 6 sqmm to 16 sqmm ---- as per directions of engineer incharge of work.

100

-

1188

... More
Digging of trench of 0.6m deep x 0.50 mtr wide refilling the trench to the required ground level and consolidating etc. complete.(As per Civil SR KSRB 1-2, P-7) - In soil (ordinary) ---- as per directions of engineer incharge of work.

200

-

15200

... More
Supplying and fixing of class A (medium duty) GI pipe of wall thickness not less than 3.25mm on pole/wall/drain crossing with necessary clamping arrangements for UG cable of 1.1KV - 40mm ---- as per directions of engineer incharge of work.

15

-

5025

... More
Providing and laying in position 100mm dia stone ware pipe in existing trench. ---- as per directions of engineer incharge of work.

100

-

21500

... More
Supplying and fixing LT cast Iron pot heads suitable for 1.1KV class UG cable filled with necessary bitumen/insulating compound complete with terminals, clamps, bolts, nuts and washers etc. - 50Sqmm ---- as per directions of engineer incharge of work.

2

-

1236

... More
Supplying fixing and wiring earth electrode for grounding of lifts, transformers, DG sets etc. using 40mm dia 2.9mm thick 2.5 mtr long GI pipe with GI funnel with mesh and suitable size reducer fixed on the top of the earth electrode.The funnel should be enclosed in a CC chamber of 400x400x400mm with a cast iron cover. The earth electrode shall have staggered holes of 12mm dia and the electrode should be covered 150mm all-round with alternate layers of salt and charcoal from the bottom of the CC chamber. The connection from the electrode is to be established through GI strip using GI bolts and nuts. ---- as per directions of engineer incharge of work.

12

-

49800

... More
Supplying & Fixing Chemical earthling for grounding. Conduits, IC cut-outs & other equipments backfill compound which is non-corrosive, thermally conductive, potential to permissible limits, superior Fault conduction capacity, non toxic, weather resistance & capable of achieving ohmic value less than one ohm - Using 6ft. Copper bonded rod with backfill compound ---- as per directions of engineer incharge of work.

4

-

21300

... More
Supplying and running of GI/Copper strips for grounding connections, using necessary fixing materials as required. - 25x3mm GI strip ---- as per directions of engineer incharge of work.

60

-

4500

... More
Supplying and running of GI/Copper strips for grounding connections, using necessary fixing materials as required. - 600x600x3mm Copper plate ---- as per directions of engineer incharge of work.

8

-

55200

... More
Supplying and fixing 2mm thick perforated cable GI tray with on existing MS angle support using necessary GI bolts/nuts and washer or welding as required. - 150x50mm ---- as per directions of engineer incharge of work.

150

-

63750

... More
Supplying and fixing 2mm thick perforated cable GI tray with on existing MS angle support using necessary GI bolts/nuts and washer or welding as required. - 300x50mm ---- as per directions of engineer incharge of work.

100

-

53000

... More
Supplying and fixing 2mm thick perforated cable GI tray with on existing MS angle support using necessary GI bolts/nuts and washer or welding as required. - 750x50mm ---- as per directions of engineer incharge of work.

100

-

110000

... More
Supplying, fixing and wiring Automatic Power Factor controller circuit unit fully, static units controlled by 14 stage microprocessor operation, relays LED display, self programming function for power stages and operating logic checking facility for healthy and efficient of each individual capacitor bank, measurement of network harmonics with indication when limit values are exceeded, Comprehensive displays with large, three phase LED display, Long term memory for settings, protection for over voltage, power factor correction fault and no voltage, to connect/ disconnect banks, with automatic recognition or with standard programs ---- as per directions of engineer incharge of work.

1

-

18000

... More
Supplying, fixing and wiring heavy duty low voltage capacitors conforming to IS 2834. 3 phase, 400/440 volts grade, for power factor improvement of rotating machineries like induction motor. ---- as per directions of engineer incharge of work.

125

-

50000

... More
Supply and fixing of 4pole power contactor with NO/NC contacts on existing wood/panel board using necessary bolts, nuts, washers and wiring etc., complete with AC-3 Rating and as per IS-13947. - 40 Amps ---- as per directions of engineer incharge of work.

30

-

55200

... More
Supplying and drawing UTP-CAT 6E LAN cable. ---- as per directions of engineer incharge of work.

4000

-

116000

... More
Supplying & Fixing of switch mounting rack with power manager & Cable manager. - 9U with 450mm depth ---- as per directions of engineer incharge of work.

20

-

124000

... More
Supplying fixing of Network Switches - 24 port 10/100/1000 Switch ---- as per directions of engineer incharge of work.

20

-

136000

... More
Supplying & Fixing of Patch panel for LAN cabling - 24 Port 10/100/1000 patch panel ---- as per directions of engineer incharge of work.

20

-

140000

... More
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. - RJ45/I.O.outlet Cat-6 ---- as per directions of engineer incharge of work.

300

-

58500

... More
Supplying and fixing of MDF krone junction box with KRONE Module / Telephone cable termination. - 50 pair ---- as per directions of engineer incharge of work.

6

-

3300

... More
Supplying and fixing of MDF krone junction box with KRONE Module / Telephone cable termination. - 20 Pair ---- as per directions of engineer incharge of work.

6

-

2100

... More
Supplying and drawing PVC insulated gas injected physical foam jelly flooded co-axial TV cable.RG-6. ---- as per directions of engineer incharge of work.

150

-

5250

... More
Supplying and drawing PVC flexible one pair telephone unarmoured tinned copper cable. - 5Pair ---- as per directions of engineer incharge of work.

150

-

7200

... More
Supplying and drawing PVC flexible one pair telephone unarmoured tinned copper cable. - 20pair ---- as per directions of engineer incharge of work.

200

-

30000

... More
Supplying erection, testing and commissioning of 11 kV Load Break Switch with 4 wire - (3 PT and 3 CT with Neutral) Metering cubicle and connected accessories, hardware's etc. suitable for outdoor type complete as per latest IS standard and ESCOM approved technical specification. Metering cubicle with LBS. ---- as per directions of engineer incharge of work.

1

-

288627.9

... More
HT Cable: Supplying and laying of high tension 11KV cable, Dry Curing & Dry Cooling with true triple extrusion, simultaneously through a single common head, 3 core under ground XLPE (E) cable having stranded compact circular aluminium conductor, screened insulated, insulation screened with extruded semiconducting compound in combination with copper tape, core laid up extruded inner sheathed of GI flat strip armoured and overall PVC sheathed with specified IS 7098/11/85 with latest amendments. - 3Cx95sqmm ---- as per directions of engineer incharge of work.

100

-

104000

... More
Supply & Making of 11KV (E) Extruded "X" linked for tubing & moulded & cross-linked components using Heat Shrink Stress Control tube having High Permittivity XLPE Terminations- STRAIGHT THROUGH JOINTING KIT. - 3Cx95/120Sqmm ---- as per directions of engineer incharge of work.

1

-

18487

... More
Supplying and making 11KV (E) Extruded "X" linked for tubing & moulded & cross-linked components using Heat Shrink Stress Control tube having High Permittivity XLPE Terminations- INDOOR & OUTDOOR JOINTING KIT latest amendments. - 3Cx95/120sqmm OUTDOOR ---- as per directions of engineer incharge of work.

2

-

19710

... More
Supplying fixing and wiring earth electrode for grounding of lifts, transformers, DG sets etc. using 40mm dia 2.9mm thick 2.5 mtr long GI pipe with GI funnel with mesh and suitable size reducer fixed on the top of the earth electrode.The funnel should be enclosed in a CC chamber of 400x400x400mm with a cast iron cover. The earth electrode shall have staggered holes of 12mm dia and the electrode should be covered 150mm all-round with alternate layers of salt and charcoal from the bottom of the CC chamber. The connection from the electrode is to be established through GI strip using GI bolts and nuts. ---- as per directions of engineer incharge of work.

4

-

16600

... More
Supplying and running of GI/Copper strips for grounding connections, using necessary fixing materials as required. - 25x3mm GI strip ---- as per directions of engineer incharge of work.

40

-

3000

... More
Supplying and running of GI/Copper strips for grounding connections, using necessary fixing materials as required. - 600x600x3mm GI Plate ---- as per directions of engineer incharge of work.

4

-

3040

... More
Supplying and fixing of class A (medium duty) GI pipe of wall thickness not less than 3.25mm on pole/wall/drain crossing with necessary clamping arrangements for UG cable of 1.1KV - 80mm ---- as per directions of engineer incharge of work.

15

-

10320

... More
Supplying, installing, testing and commissioning of Diesel Generator set with following specifications. Power rating as per standard reference condition as per-BS 5514/ISO 3046/ ISO 8528 & IS 1002/ISO 3046 Generator set specifications. Engine: Diesel generating set are rated at 1500RPM and conform to ISO 8528 specifications. The engines are radiator cooled, four stroke and multi cylinder, conforming to ISO 3046. The scope of supply includes: Electrical starter motor12V DC Battery charging alternator, Bosch fuel system with mechanical governor, A1 Class. Spin-on lube oil filter, Spin-on dual fuel filter with water separator, Turbocharger, Charge air cooler, Silencer (Hospital grade), Dry type air cleaner, Shutoff coil, Flywheel and flywheel housing, First fill of lube oil and coolant, Safety for low lube oil pressure, Safety for high water temperature, Permissible overload of 10% for one hour in 12 hours of operation Capacity of Fuel Tank: Fuel tank suitable for 8 hours of operation Alternator: Alternator is suitable for operation at 1500 RPM, 415 Volts, 0.8 pf (lag) suitable for 50 Hz, 3 phase, 4 wire systems, conforming to IS/IEC 60034-1. The Alternator is brush less type, screen protected, revolving field, self excited, self regulated through an AVR. The alternator shall have± 1.0% Voltage regulation (max) in static conditions- IP: 23 protections with insulation class F&H. Mounting arrangement: Engine and alternator are mounted on a common MS fabricated base frame with AVM pads. Control Panel: The control panel is manufactured with 14/16 gauge CRCA sheet and is powder coated for weather-proof and long lasting finish. The control panel consists of the following parts:- PS0500 Controller, Aluminium bus bars with suitable capacity within/outgoing terminals, Indicating lamps for 'Load On' and 'Set Running', Instrument fuses duly wired and ferruled, MCCB of suitable rating with overload and short circuit protections.Genset Controller: microprocessor based generator set monitoring and control system. The control provides a simple operator interface to the generator set, manual and remote start/ stop control, shutdown fault indication, and an LCD hour counter. The integration of all functions into a single control system provides enhanced reliability and performance compared to conventional generator set control systems. This control has been designed and tested to meet harsh environment in which gensets are typically applied. Features, Functions, protections 16 character x 2 line alphanumeric LCD display with LED Backlight Operator interface, Provide a record of most recent fault conditions. Fault history stored in the control non volatile memory, Provide Alternator Data. Voltage (1 ph or 3 ph line to line and line to neutral voltage, Current (1 ph or 3 ph), kVA (3 ph and total), Frequency, Provide Engine Data, Starting battery voltage, Engine running hours, Engine Temp, Engine oil pressure, Control includes provision for Service adjustment and calibration of DG control functions, Voltage, frequency selection, Configurable input and output set up, Meter calibration, Engine controls, Power Start operates on 12 VDC batteries,-Auto start mode accepts a ground signal from remote devices to automatically start the DG set The remote start will also wake up the control system from sleep mode. Engine Starting -The control system supports automatic engine starting, Primary and back up start disconnects are achieved by battery charging alternator feedback or main alternator output frequency. Controller provide configurable time delay of 0-300 sees to start after remote start signal and time delay of 0-600secs prior to shut down after stop signal. Sleep mode increase battery life. Configurable current settings from low to minimize current draw when genset is not working. Engine Protective functions include, Configurable alarm output, Emergency stop: Annunciated whenever an emergency stop signal is received by the control. Low lube oil pressure warning and Shutdown, High engine water temp warning / Shutdown, Low coolant temp warning, Sensor failure indication, Low and high battery voltage warning, Weak battery warning, Fail to start shut down, Cracking lockout: Control will not allow the starter to engage or to crank the running engine Cyclic cranking: Configurable for the number of starting cycle, (1 to 7) and duration of crank and rest periods. Alternator Protective functions includes, - High and Low AC voltage shut down, Under and Over frequency shutdown / warning, Loss of sensing voltage input shut down. Acoustic enclosure: The acoustic enclosure shall be made of 1.6 mm thick CRCA sheets in suitable approved shade and a structural/ sheet metal base frame painted in black. The walls of the enclosure are insulated with fire retardant foam so as to comply with the 75dBA at 1 mtr sound levels specified by Ministry of Environment & Forest The enclosure has the following features: Specially designed to meet stringent MOEF/CPCB norms of 75dBA @ 1mtr at 75% load under free field conditions, Two point lifting for easy handling at customer site, Designed to have optimum serviceability, Air inlet louvers specially designed to operate at rated load made on special purpose CNC machines for consistency in quality and workmanship, Powder coated for long lasting service life and superior finish, With UV resistant powder coating, can withstand extreme environment, Use of special hardware for longer life, Insulation material meets exacting IS 8183 specifications for better sound attenuation, Flush styling - no projections, Fluid drains for lube oil and fuel, Fuel filling point inside the enclosure. The complete set shall have sufficient safety and adhere to NEC, NBC 2016, IEC, CPWD specifications, PCB norms and KSGEI Acts and Rules. - 250 KVA/200 kw ---- as per directions of engineer incharge of work.

1

-

1723600

... More
Supply, Erection, testing and commissioning of AMF panel suitable for .....KVA DG set. The panel is of cubical type base/floor mounting control panel with hinged doors, undrilled bottom gland plate, aluminium Bus Bar with the accommodation for .....amps 4 pole contactor for alternator with thermal O/L relay,..... Amps 4 pole contactor for mains, HRC fuse for short circuit protection, Microprocessor based AMF module with supply failure timer, Restoration timer, 3 impulse automatic engine start/stop logic, Mains/generator voltage, ....capacity bypass switch and frequency sensing, PCC 1301controller with water temperature/Lube oil pressure/ engine speed, Voltage/ampere/Frequency/ KVA, Running-hour count, No of starts, Fault indication, over / under speed, Fails to start, Low oil pleasure, High engine temperature, Under/over voltage, over current, Earth fault relay, with indications for Mains on, Load on Mains, Battery charger on Push buttons AMF module by pass Mode, Battery charger unit with inbuilt Auto/Manual and Flat/Boost facility. The complete set shall have sufficient safety and adhere to NEC, NBC 2016, IEC, CPWD specifications, PCB norms and KSGEI Acts and Rules. - Above 180 KVA upto 250 KVA ---- as per directions of engineer incharge of work.

1

-

291000

... More
Supplying and drawing Flexible Multicore Cable manufactured with electrolytic grade flexible copper with low conductor confirming to IS 8130-1984 and (Virgin) PVC insulation sheathed suitable for working voltage upto 1100 Volts as per IS-694:1990 - 10C X 2.5Sq. mm ---- as per directions of engineer incharge of work.

100

-

36200

... More
Extra for Fabrication supply and fixing of Stand fabricated using slotted angle /L angle of size 6mm x 50mm for mounting out door/indoor A.C. unit/ Batteries. ---- as per directions of engineer incharge of work.

3

-

6645

... More
Supplying and drawing Flexible Multicore Cable manufactured with electrolytic grade flexible copper with low conductor confirming to IS 8130-1984 and (Virgin) PVC insulation sheathed suitable for working voltage upto 1100 Volts as per IS-694:1990 - 4C X 2.5Sq.mm ---- as per directions of engineer incharge of work.

150

-

17250

... More
Supplying of .. TR Invertor type split Air conditioners suitable for operation on A/C supply single phase 50 Hz 230 Volts with hermetically sealed inverter compressor with air cooled condenser, latest R410A / R-32 refrigerant fan motor, start & run capacitors, relay & over load protector internal unit, with one indoor & one outdoor unit The condenser unit will be placed outside the room avoid noise including standard length of suitable size copper tubing covered with nitrile rubber insulation tube. suitable capacity 3 core sheathed/ PVC copper cable and a battery operated wireless remote unit. - 1 ton capacity 3 star ---- as per directions of engineer incharge of work.

1

-

37000

... More
Supplying of .. TR Invertor type split Air conditioners suitable for operation on A/C supply single phase 50 Hz 230 Volts with hermetically sealed inverter compressor with air cooled condenser, latest R410A / R-32 refrigerant fan motor, start & run capacitors, relay & over load protector internal unit, with one indoor & one outdoor unit The condenser unit will be placed outside the room avoid noise including standard length of suitable size copper tubing covered with nitrile rubber insulation tube. suitable capacity 3 core sheathed/ PVC copper cable and a battery operated wireless remote unit. - 1.5 ton capacity 3 star ---- as per directions of engineer incharge of work.

1

-

42000

... More
Supplying of .. TR Invertor type split Air conditioners suitable for operation on A/C supply single phase 50 Hz 230 Volts with hermetically sealed inverter compressor with air cooled condenser, latest R410A / R-32 refrigerant fan motor, start & run capacitors, relay & over load protector internal unit, with one indoor & one outdoor unit The condenser unit will be placed outside the room avoid noise including standard length of suitable size copper tubing covered with nitrile rubber insulation tube. suitable capacity 3 core sheathed/ PVC copper cable and a battery operated wireless remote unit. - 2 ton capacity 3 star ---- as per directions of engineer incharge of work.

1

-

58000

... More
Supply erection, testing, commissioning of Cassette type split Air conditioners suitable for operation on single/three phase AC supply, hermetically sealed compressor with air cooled condenser motor capacitor start, capacitors run relay and over load protection, one ceiling mounted indoor unit and one outdoor condenser unit including standard accessories covered with insulation tube including battery operated cordless unit - 3.0 TR Cassette 3 Ph ---- as per directions of engineer incharge of work.

2

-

228800

... More
Supply erection, testing, commissioning of Cassette type split Air conditioners suitable for operation on single/three phase AC supply, hermetically sealed compressor with air cooled condenser motor capacitor start, capacitors run relay and over load protection, one ceiling mounted indoor unit and one outdoor condenser unit including standard accessories covered with insulation tube including battery operated cordless unit - 4.0 TR Cassette 3 Ph ---- as per directions of engineer incharge of work.

2

-

253800

... More
Installation charges for split type air conditioner with allied works for one indoor and one outdoor unit is to be mounted on suitable Angle Iron support up to 3.0 ton split/cassette type A/C. ---- as per directions of engineer incharge of work.

7

-

20300

... More
Supplying and installation of insulated refrigerant copper tubing of 5/8" and 3/8" with polythene foam insulation 3 core 80 stand copper wiring between indoor and outdoor unit Leak testing oil and gas charging for additional piping length of tube. - Split ---- as per directions of engineer incharge of work.

60

-

69300

... More
Supplying and installation of insulated refrigerant copper tubing of 5/8" and 3/8" with polythene foam insulation 3 core 80 stand copper wiring between indoor and outdoor unit Leak testing oil and gas charging for additional piping length of tube. - Cassette ---- as per directions of engineer incharge of work.

60

-

96000

... More
Supplying, erecting, testing and commissioning of voltage stabilizer suitable for 170 to 270 V input and load variation from no load to full load, with over load protection, spike suppression, operating at 00 C to 400 C. Range etc., complete. - 3KVA Capacity ---- as per directions of engineer incharge of work.

3

-

11520

... More
Extra for Fabrication supply and fixing of Stand fabricated using slotted angle /L angle of size 6mm x 50mm for mounting out door/indoor A.C. unit/ Batteries. ---- as per directions of engineer incharge of work.

7

-

15505

... More
Open Conduit System :Supplying heavy gauge PVC conduit pipe ....... dia ....... mm thick confirming to IS 2509 with suitable size bends, junction boxes, adhesive paste etc , and fixing using inverted wood plugs in case of RCC ceiling and RCC wall/ stone structure or rawl plugs in case of brick walls and cement plastering the damaged portion using heavy gauge saddles at an interval of 700mm using NF screws. - 25mm dia 2mm thick ---- as per directions of engineer incharge of work.

60

-

3900

... More
Supplying and drawing 3 core flat PVC sheathed submersible pump cable manufactured with electrolytic grade copper with flexible copper with low resistance conductor confirming to13:8130-1984 and virgin grade PVC insulation and powder coating extruded PVC sheathed suitable for working voltage upto 1100 Volts as per IS-694:1990. - 3C X 4.0Sq.mm ---- as per directions of engineer incharge of work.

600

-

84000

... More
Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898. - 6-32Amps TPN ---- as per directions of engineer incharge of work.

1

-

1715

... More
Supplying push button operated direct online starter with an antiweld silver cadmium oxide contactor with replaceable fixed and moving contacts and bimetallic thermal overload relay help in anticorrosion treated sheet steel or iron clad enclosure and fixing the same to suitable capacity wires for 230/440 volts 1/3 phase motor upto 5 HP. ---- as per directions of engineer incharge of work.

2

-

2760

... More
Supplying of 1.1 KV LT UG cable XLPE or Heat resistant PVC insulated, PVC extruded Inner sheath armoured UG LT cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armouring strip thickness in average +5% and resistivity 14 Ohms/Kms (Max) as per IS-3975 - 3.5 core 25 sqmm ---- as per directions of engineer incharge of work.

100

-

18000

... More
Labour charges for laying of 1.1 KV class UG cable in existing trench GI pipe/ stoneware pipe /on wall / on pole as required. In existing trench/duct. On wall/Structure - 25 sqmm to 75 sqmm ---- as per directions of engineer incharge of work.

100

-

1550

... More
Digging of trench of 0.6m deep x 0.50 mtr wide refilling the trench to the required ground level and consolidating etc. complete.(As per Civil SR KSRB 1-2, P-7) - In soil (ordinary) ---- as per directions of engineer incharge of work.

100

-

7600

... More
Supplying and fixing of class A (medium duty) GI pipe of wall thickness not less than 3.25mm on pole/wall/drain crossing with necessary clamping arrangements for UG cable of 1.1KV - 40mm ---- as per directions of engineer incharge of work.

5

-

1675

... More
Supplying, fixing, wiring, earth electrode for grounding conduits, I.C. cutouts and other equipment's on the meter board using 40mm dia 2.90mm thick GI pipe 2.5 mtr long buried in a pit . The pit should be filled with equal proportion of salt and charcoal 150mm all-round the pipe to complete depth. The connection from the pipe to the conduit etc., is to be established through GI wire of size as per lSI specification 7.3.3. of IS 732 using 12mm dia bolts, nuts, washers and check nuts etc., the pipe shall have 16 through holes of 12 mm dia ---- as per directions of engineer incharge of work.

2

-

5999.4

... More
Supplying and running of GI/Copper strips for grounding connections, using necessary fixing materials as required. - 25x3mm GI strip ---- as per directions of engineer incharge of work.

20

-

1500

... More
Supplying, fixing, wiring, earth electrode for grounding conduits, I.C. cutouts and other equipment's on the meter board using 40mm dia 2.90mm thick GI pipe 2.5 mtr long buried in a pit . The pit should be filled with equal proportion of salt and charcoal 150mm all-round the pipe to complete depth. The connection from the pipe to the conduit etc., is to be established through GI wire of size as per lSI specification 7.3.3. of IS 732 using 12mm dia bolts, nuts, washers and check nuts etc., the pipe shall have 16 through holes of 12 mm dia ---- as per directions of engineer incharge of work.

10

-

29997

... More
Supplying and fixing 2mm thick GI floor Raceway with on existing MS angle support using necessary GI bolts/nuts and washer or welding as required. 50mm wide as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

50

-

27700

... More
Supplying and fixing 2mm thick GI floor Raceway with on existing MS angle support using necessary GI bolts/nuts and washer or welding as required. 70mm wide as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

20

-

14260

... More
Supplying and fixing of Height adjustable floor junction box with base & cover plate complete 150X150X65 - 90mm as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

40

-

64000

... More
Supply & Installation of IP65 , 50 m radius Lighting arrestor with all accessories including spikes, spot lights, copper cable etc of Single core 70 sqmm etc all complete as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

1

-

75000

... More
Supplying of OFC cable 12 core with armoured as per direction of engineer incharge of the work. ---- as per directions of engineer incharge of work.

150

-

37500

... More
Supplying and fixing EPABX system 3 Analog Trunk and 8 Analog system etc complete as per the directions of engineer in charge of the work. ---- as per directions of engineer incharge of work.

1

-

28180

... More
Supplying telephones KX -AT7730SX/SXB as per the directions of engineer in charge of the work. ---- as per directions of engineer incharge of work.

8

-

33984

... More
Supplying, Installation & commissioning telephones Anolog basic as per the directions of engineer in charge of the work. ---- as per directions of engineer incharge of work.

20

-

13920

... More
Supplying and laying pvc trunking 100x50 mm, Make - Group "A" materials and as per the directions of Engineer in charge of the work ---- as per directions of engineer incharge of work.

50

-

31000

... More
Annual Maintainance Cost DG set, pump, ac, wiring, panel boards. ---- as per directions of engineer incharge of work.

1

-

550000

... More
"Supplying erection, testing and commissioning of 3 Way RMU, 2OD + 1VL (One Incomer + One Breakers +One Outgoing). DAS Specification Compact RMU (VCB/SF6 Type) as per IEC-62271 The DAS RMUs shall have the following in addition to the Standards: • DC motors, Numerical Relays, Multifunctional meters, fault passage indicator (FPI), Metering CTs, Protection CTs, Auxiliary transformers, Potential transformer, Batteries, Battery chargers (12V & 24V), AC power socket and light for illumination of Control panel. • Control cable from each panel shall be wired and terminated to suitable 24 pin connectors in the control panel. • Suitable space for fixing the Remote Terminal Unit (RTU) and Radio Modem in Control panel. • Suitable clamps for fixing Antenna Pipe. Supplying erection, testing and commissioning of 3 Way RMU, 2OD + 1VL (One Incomer + One Breakers +One Outgoing)" as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

1

-

609600

... More
TRANSFORMER: Supplying, erection, Testing and Commissioning of 500 KVA transformer 5 star rated Aluminum Wound Distribution Transformer tap switch, Butchholtz relay winding Temperature indicator, oil temperature indicator,marshalling box with wiring , magnetic oil level indicator with +5% to -10% steps of 2.5% with HT and LT cable end boxes including all standard accessories as per latest IS Standard Technical Specification. 500 KVA. As per BEE standard/norms with cable entry box (Indoor type) as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

1

-

722300

... More
LT Distribution Box suitable for 500 KVA Transformer with 1No 800Amps 50kA 4Pole MCCB, suitable capacityAluminium bus bar mounted in 16SWG powder coatedM.S.Box suitable to mount at Transformer Centre as per BESCOM. as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

1

-

321381

... More
LT Metering Box for housing the ETV Meters without CT's busbar wiring as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

1

-

3664

... More
Modem charges as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

1

-

10000

... More
LT Electronic Tri - Vector Meter 5A, Class-0.5 accuracy as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

1

-

2061

... More
Supplying and erection of LT Kiosk consisting of 2 MCCB's with accessories.( Data rate enclosed) as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

1

-

90778

... More
"Construction of platform with size stone, cement concert for erection of 500 kVA Transformer/Metering cubicle/Heavy Equipment. Construction of platform (1.5x1.5x1.2) mtr in size stone, for erection of transformers/Heavy equipment including all materials, labour. Excavation of (1.5x1.5x1) mt pit for foundation providing and laying cement concrete 1:4:8 for foundation laid in 10 cm thick layers, well compacted curing etc., complete providing and construction of stone masonary 0.9m below ground level and 1.2m above ground level neatly hammer dressed in cement morter 1:6.Providing and Laying cement concrete slab 1.5x1.5x0.10Mtr with cement concrete of 1:2:4 mix forming & cutting complete, providing pointing to stone masonary in cement morter 1:3 after racking joint & nisely lining curing etc., plastering the concrete surfaces in cement morter 1:4 including smooth randering curing etc., curing at every stages completely. " as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

3

-

75576

... More
FENCING: Supplying & fixing M.S rectangular pole made of 2 equal angles 65 x 65 x 6 mm welded together & fixed in C.C (1:2:4) with 2 nos 16 mm dia MS welded fost rods equal of length 25 mm including cost of all materials cutting, bending, scarffolding where ever n as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

40

-

34360

... More
Providing Chain link fencing 50 mm size of 8 gauage properly streched between rectangular poles and fixed with sutable bolt & nuts, the free ends shall be welded to the pole & black pipe at top & bottom as required including cost of all materials, labour, as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

70

-

50050

... More
Route & joint indicating stone with MS Anchor rod as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

40

-

5200

... More
Supplying & Fixing of DANGER / No Admission / No Smoking board made out of MS sheet metal with two coats of non corrosice enameled paint… as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

8

-

1168

... More
Providing ABC Powder based MAP 50, 6Kg Providing 6kg Fire Extinguisher Mono Ammonium Phosphate Powder 50, Stored Pressure Type, Pressure Gauge, Gross Weight 9.5 Kg, empty weight 3.5 Kg, Can Height 435MM, Diameter 160MM, Discharge Time less than 9 Secs, Controllable discharge mechanism (Squeeze grip with easy snap safety seal), Range minimum 4 meters, applicable on Class A,B,C and electrically started Fire, A Rating 3A, B Rating 21B, Can construction : Deep drawn & Co., Mig welded, valve Construciton and as per the directions of Engineer in charge of the work. ---- as per directions of engineer incharge of work.

1

-

5819

... More
Fire Bucket with stand - 2 Buckets with stand Bucket of round bottom, painted red, marked 'FIRE' and duly filled with fire river sand. as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

8

-

4504

... More
DG Set foundation 3x2x1.5 mtr for 250 KVA DG set as per direction of engineer incharge of the work ---- as per directions of engineer incharge of work.

1

-

29411.76

... More
Exhaust System : Supply, receive at site, store, unpack, assemble and connect exhaust pipe with Class B MS pipe with flanges, fire fly gaskets, hardware, glass wool and aluminium sheet cladding etc., as per specification inclusive of all structural supports etc., complete as required. Individual Exhaust pipe including flexibles from set with glass wool and Alu. clading etc., as required complete for 250 KVA DG set (diameter of the pipe shall be specified by the vendor) as per BESCOM norms. as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

15

-

36000

... More
Silencer with painting glass wool insulation / Al. clading etc., as required complete for 250 KVA DG set as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

10

-

28992

... More
Supplying, erecting, testing & commissioning of 1x25kVA 3phase Input/output ON-LINE UPS system with one hour back up including 84 AH batteries each 38 Nos,Suitable for parallel operation,inbuilt,static changeover witch, high input voltage band, DSP control based system, with unity power factor, with 0.99 input power factor. suitable for operation on 230V, 50Hz, A/C supply, with isolation transformer,BCB all accessories complete and including batteries and wiring complete including 3 years maintainance as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

1

-

645200

... More
Supplying and Delivery at Site 12.5 HP / 9.3KW, 25 Stage Submersible Pump set of approved make ISI with Motor. Suitable for operation of 3 Phase 50 HZ 440 Volts A.C supply fitted with required accessories complete and as per the directions of Engineer in charge of the work. ---- as per directions of engineer incharge of work.

1

-

56414

... More
KSRB13-6.3 : Providing and fixing in position brass gate valve with C.I wheel of approved quality ( screwed end ) 50 mm nominal bore including cost of all materials, labour and HOM with all leads complete as per specifications. Specification No.KBS 13.2.6 / 13.3 KSRB13-6.3-6 - do - 50 mm dia nominal and as per the directions of Engineer in charge of the work. ---- as per directions of engineer incharge of work.

1

-

1739

... More
KSRB13-7.1 : Providing and fixing in position nominal bore gun metal non-return valve horizontal type of approved make including cost of all materials, labour and HOM with all leads complete as per specifications. Specification No.KBS 13.2.10 / 13.13 KSRB13-7.1-4 - do - 50 mm dia nominal bore and as per the directions of Engineer in charge of the work. ---- as per directions of engineer incharge of work.

1

-

1330

... More
Out door type control panel Borad : Supplyinbg and Delivery Site brand new best indigenous make combined energy meter cum control panel borad of size 1200*600*350mm suitable for aperation on 3 Phase Hz 440 Volts meter, ammeter, single phase preventor etc conplete set Make - Group "A" materials and as per the directions of Engineer in charge of the work. ---- as per directions of engineer incharge of work.

1

-

8750

... More
Erection of panel and Meter Borad : Erection of combined panel borad and meter borad unit with necessary materials and labour charges Inculuding providing cement concrete foundation bed ect complete. as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

1

-

369

... More
Erection, Electrification and commissioning Work of Pump Sets : eraction of pumpset including aligning and balancing with all necessary erection materials and labour including supply and erection of two pair of supporting clamps, bore-well, cap, cable protector bolts, nuts, valve and gauges ect., as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

1

-

1478

... More
"Providing and fixing in trenches galvanised/ mildsteel tubes 50mm dia nominal bore with all fittings including cost of all materials and labour charges and HOM of equipments and testing complete as per specifications Make - Group ""A"" materials and as per the directions of Engineer in charge of the work. " ---- as per directions of engineer incharge of work.

250

-

128000

... More
Supplying of Mono sub pump set 5 HP suitable for operation on 230 volts 2880 RPM Three phase AC supply Make- Using group "A" materials. And as per the directions of engineer incharge of the work. ---- as per directions of engineer incharge of work.

2

-

44460

... More
Fixing charges of pumpset after aligning, leveling & assembling etc, inclusive of transportation charges to work spot. as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

2

-

2000

... More
Supply and laying double walled corrugated (DWC) HDPE Pipe including all necessary connecting Sockets/Couplings/Tees/Bends/End-caps of same materials in exisiting trench as per IS 14930 part -II suitable for drawing under ground cables.90mm OD / 76mm ID as per the directions of the engineer in charge of the work. ---- as per directions of engineer incharge of work.

10

-

3310



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.