Karnataka Cooperative Milk Producers Federation Limited Tender

Karnataka, also known as Karunadu, is a state in the southwestern region of India. Karnataka was formed originally as Mysore State on 1st November 1956 and currently is the biggest state in south India. Its capital and largest city is Bengaluru. It covers an area of 191,791 km2 (74,051 sq mi) and is the sixth largest state by area comprising 31 districts. Karnataka is also a state of multiple languages; Kannada being the official and most widely spoken language in Karnataka. Other languages spoken in the state include Tamil, Telugu, Malayalam, Kodava, Konkani and much more.Karnataka tenders are issued by the government of Karnataka, public & private sector organisations. The state government issues majority of the Karnataka tenders, which are for goods and services including construction, road and bridge construction, IT services, engineering services, medical services, educational services amongst many others. Bidassist is one of the largest eprocurement portals, which offers all government tenders from across the world in one place. Bidassist offers information on all Karnataka tenders and other state and authority tenders in no time. Bidassist is a platform where users can look for various Karnataka tenders as well as other tenders.

Karnataka Cooperative Milk Producers Federation Limited Tender

Electrical Generators And Transformers
Electrical and Electronics
Opening Date2 Aug 2024
Closing Date17 Aug 2024
Tender Amount₹ 72,34,597.38 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
code04 - HT TERMINATION : Installation of Heat shrinkable Type Terminations 3x95 to 3x150 Sqmm (Refer : COMMON SR 2023-24 VOL-6,Part-II, Page 52 Sl. No.22.04)

2

3136

6272.88

... More
code05 - 1.1 KV ,LT CABLE : Supply of 1.1 kV, XLPE or Heat resistant PVC insulated, PVC exutruted Inner Seath Armoured LTUG Cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armouring strip thickness and resistivity as per IS-3975300 Sqmm, 3.5 Core, (32 GI Strips - 4 x 0.8 mm) (Refer : COMMON SR 2023-24 VOL-6,Part-II, Page 14 Sl. No.32.19)

700

1257

880523

... More
code06 - 1.1 KV ,LT CABLE : Laying of cable in Existing Trench/GI pipe/Stone Ware/RCC Hume pipe using Wooden/Aluminum Rollers as directed by the departmental staff 300 to 400 Sqmm (Refer : COMMON SR 2023-24 VOL-6,Part-II, Page 52 Sl. No.177 item no.21.08)

700

40

28224

... More
code07 - 1.1KV Cable : Termination Supply and providing the end terminations with Heavy Duty aluminium/Copper lugs, double compreesion brass cable glands, taping, crimping, gland and armour earthing, etc. complete as required.( Al Cable Al. Lugs & Copper Cable Copper Lugs) 3.5 Core x 300 sqmm 1.1 KV Grade PVC sheathed XLPE Cable.-MARKET RATE

30

2891

86730

... More
code08 - 1.1KV Cable : Supply of Straight Through Jointing Kit Suitable for 1.1 kV Class LTUG Cable as per IS-13573400 Sqmm, 3.5/4 Core (Refer : COMMON SR 2023-24 VOL-6,Part-II, Page 14 Sl. No.241 item no. 34.13)

2

3829

7658.2

... More
code09 - 1.1KV Cable : Installation of Straight Through Jointing Kit Suitable for 1.1 kV Class LTUG Cable as per IS-13573 300 to 400 Sqmm (Refer : COMMON SR 2023-24 VOL-6,Part-II, Page 53 Sl. No.190 item no.22.12)

2

672

1345.18

... More
code10 - Earth work excavation for pipelines/cables by Manual means upto 600 mm trench width, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, removal of stumps and other deleterious matter, including dressing of excavated surfaces, disposing off or leveling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m. Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering and lift upto 1.5 m including cost of labour, tools, usage& other appurtenances required to complete the work. In all kinds of soils. Depth upto 1.50m (Refer : PWD SR 2023-24 VOL-1 ,Page 6 , item no. 1.6.1)

30

571

17133.6

... More
code11 - Refilling available earth around trenches/pipelines, cables in layers not exceeding 20 cms in depth, compacting each deposited layer by ramming after watering with a lead upto 50 m, and lift upto 1.5 m. Including cost of all labour complete as per specifications (Refer : PWD SR 2023-24 VOL-1,Page 7 , item no. 1.10)

25.2

188

4757.508

... More
code12 - Brick - Table Moulded Bricks (Refer : PWD SR 2023-24 VOL-1 ,Page A-38 item no. 20)

200

9

1888

... More
code13 - Sand - M-Sand (Refer : PWD SR 2023-24 VOL-1 ,Page A-40 item no. 64)

3

1741

5225.01

... More
code14 - Supplying & Fixing Chemical earthling for grounding. Conduits, IC cut-outs & other equipments backfill compound which is noncorrosive, thermally conductive, potential to permissible limits, superior Fault conduction capacity, non toxic, weather resistance & capable of achieving ohmic value less than one ohm. Using 10ft. Copper bonded rod with backfill compound (Refer : PWD SR 2023-24, Page 55 Sl. No.12.60.3)

6

10022

60137.52

... More
code15 - Supplying fixing and wiring earth electrode for grounding of lifts, transformers, DG sets etc. using 40mm dia 2.9mm thick 2.5m long GI pipe with GI funnel with mesh and suitable size reducer fixed on the top of the earth electrode.The funnel should been closed in a CC chamber of 400 x 400 x 400 mm with a castiron cover. The earth electrode shall have staggered holes of 12mm dia and the electrode should be covered 150mm all-round with alternate layers of salt and charcoal from the bottom of the CC chamber.The connection from the electrode is to be established through GI strip using GI bolts and nuts. (Refer :PWD SR 2023-24 Page 54 Sl. No.12.58 )

2

5022

10044.16

... More
code16 - GI/Copper strips for grounding connections, using necessary fixing materials as required.50 x 6 mm GI strip (Refer :PWD SR 2023-24 Page 55 Sl. No.12.58.5 )

100

257

25724

... More
code17 - GI/Copper strips for grounding connections, using necessary fixing materials as required.50 x 6 mm Copper strip (Refer :PWD SR 2023-24 Page 55 Sl. No.12.58.10 )

50

2559

127971

... More
code18 - GI/Copper strips for grounding connections, using necessary fixing materials as required.25 x 6 mm GI strip (Refer :PWD SR 2023-24 Page 54 Sl. No.12.58.3 )

50

151

7552

... More
code19 - 600 x 600 x 3 mm Copper plate (Refer :PWD SR 2023-24 Page 54 GI/Copper strips for grounding connections, using necessary fixing materials as required.Sl. No.12.58.11)

2

8756

17513.54

... More
code20 - 2mm thick perforated cable GI tray with on existing MS angle support using necessary GI bolts/nuts and washer or welding as required.600 x 50 mm (Refer :PWD SR 2023-24 Page 55 Sl. No.12.59.4)

150

1106

166026

... More
code21 - Supply, Erection, painting of steel items as required as per spec complete. Generally, steel items include trays supporting arrangements and any other steel items of schedule of qualities. Supports shall also be provided with one coat of anti corrosive epoxy coat with two coats of approved colour. (Market Price )

350

171

59885

... More
code22 - LT KIOSK (as per Attached Drawing number -PPES /DKMPUL/LTK/EL-01): LT ACB 1250 Amps (Refer : COMMON SR 2023-24 VOL-6,Part-II, Page 29 Sl. No.529,item no: 65.09 ) ( The ACB shall be MDO with O/c, S/C, S/T,&U/V, EFR Relay with RS 485 cominication port & current display (MP based),)

1

281688

281688.42

... More
code23 - Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898. 6-32 A SP (Refer : PED SR 2023-24 , Page 17 Sl. No.5.18.1)

3

489

1469.1

... More
code24 - Supplying and fixing of LED type panel board indicating lamp with required colour suitable for 230/440VAC. 50 Hz 12/24V D.C. (Refer : PWD SR 2023-24 , Page 19 Sl. No.5.38)

3

607

1823.07

... More
code25 - Supplying and fixing angle iron frame work fabricated out of M.S. angle iron.. and M.S. Flat......with bolts, washers etc., and painted with 2 coats of red oxide and then two coats of approved paint. 50 x 50 x 6 mm (Refer : PWD SR 2023-24 ,Page 20 Sl. No.5.41.2)

10

466

4660.9

... More
code26 - Supplying .........A rated 3phase with neutral bus bar using required capacity electrolytic aluminium strips covered with heat shrinkable coloured PVC sleeve, mounted on phenolic/FRP/DMC insulator which are mounted on powder coated 40x6mm M.S.flat frame work in existing panel board. The bus bar shall have suitable holes for termination of incoming and outgoing cables as per IS specification with necessary bolts, nuts and washers etc., complete1000 A double run of 4 x 60 x 10 mm Aluminium Strips (Refer : PWD SR 2023-24 , Page 20 Sl. No.5.40.5 )

3

12484

37453.2

... More
code27 - Fabricating supplying and mounting MS box made out ....SWG suitable for floor /wall mounting, fully weather proof with provision for better heat dissipation, provided with hinged front cover, equipped with tamper proof locking arrangements, with suitable size clamps with necessary cable entry pipe with gland and box should be finished with 7tanks treatment with powder coated paint and finally finished with approved colour etc., complete. 14 SWG (Refer : PWD SR 2023-24 VOL-6,Page 20 Sl. No.5.42.1 )

150000

-

88500

... More
code28 - Main LT Panel (as per Attached Drawing number -PPES /DKMPUL/MLTP /EL-03) : LT ACB 1250 Amps (Refer : COMMON SR 2023-24 VOL-6,Part-II, Page 29 Sl. No.529,item no: 65.09 ) ( The ACB shall be EDO with O/c, S/C, S/T,&U/V, EFR Relay with RS 485 cominication port & current display (MP based),)

1

281688

281688.42

... More
code29 - Main LT Panel (as per Attached Drawing number -PPES /DKMPUL/MLTP /EL-03) LT ACB 800 Amps (Refer : COMMON SR 2023-24 VOL-6,Part-II, Page 29 Sl. No.528,item no: 65.08 ) ( The ACB shall be EDO with O/c, S/C, S/T,&U/V, EFR Relay with RS 485 cominication port & current display (MP based),)

3

247650

742950.39

... More
code30 - Supplying and fixing Moulded Case Circuit Breaker (MCCB) over the existing wood/panel board using necessary screws, bolts, nuts, necessary phase separators, handle and wiring complete. Protection of Overload and Short circuitwith adjustable thermal magnetic release, Micro processor release shall have Earth Fault as per IS/IEC 60947-2 . (Icu=100% lcs). In 4P MCCB, all Poles should have protection for Short-Cicrcuit/Over Load. For Microprocessor MCCBS Facility for segregating Priority and Non-Priority loads must be available in the MCCB. MCCB shall be provided with double insulation (insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open). Multi-pole breakers shall be designed to break all the poles simultaneously and they shall have a single mechanism.500-630 A 50 kA (Refer : PWD SR 2023-24 I, Page 17 Sl. No.5.15.19 )

2

49440

98881.64

... More
code31 - Supplying and fixing Moulded Case Circuit Breaker (MCCB) over the existing wood/panel board using necessary screws, bolts, nuts, necessary phase separators, handle and wiring complete. Protection of Overload and Short circuitwith adjustable thermal magnetic release, Micro processor release shall have Earth Fault as per IS/IEC 60947-2 . (Icu=100% lcs). In 4P MCCB, all Poles should have protection for Short-Cicrcuit/Over Load. For Microprocessor MCCBS Facility for segregating Priority and Non-Priority loads must be available in the MCCB. MCCB shall be provided with double insulation (insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open). Multi-pole breakers shall be designed to break all the poles simultaneously and they shall have a single mechanism.400-500 A 50 kA (Refer : PWD SR 2023-24 , Page 17 Sl. No.5.15.18 )

1

48966

48966.46

... More
code32 - Supplying and fixing Moulded Case Circuit Breaker (MCCB) over the existing wood/panel board using necessary screws, bolts, nuts, necessary phase separators, handle and wiring complete. Protection of Overload and Short circuitwith adjustable thermal magnetic release, Micro processor release shall have Earth Fault as per IS/IEC 60947-2 . (Icu=100% lcs). In 4P MCCB, all Poles should have protection for Short-Cicrcuit/Over Load. For Microprocessor MCCBS Facility for segregating Priority and Non-Priority loads must be available in the MCCB. MCCB shall be provided with double insulation (insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open). Multi-pole breakers shall be designed to break all the poles simultaneously and they shall have a single mechanism.250 A 25 kA (Refer : PWD SR 2023-24 ,Page 17 Sl. No.5.15.13 )

1

25241

25241.37

... More
code33 - Supplying and fixing Moulded Case Circuit Breaker (MCCB) over the existing wood/panel board using necessary screws, bolts, nuts, necessary phase separators, handle and wiring complete. Protection of Overload and Short circuitwith adjustable thermal magnetic release, Micro processor release shall have Earth Fault as per IS/IEC 60947-2 . (Icu=100% lcs). In 4P MCCB, all Poles should have protection for Short-Cicrcuit/Over Load. For Microprocessor MCCBS Facility for segregating Priority and Non-Priority loads must be available in the MCCB. MCCB shall be provided with double insulation (insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open). Multi-pole breakers shall be designed to break all the poles simultaneously and they shall have a single mechanism.125 A 25 kA (Refer : PWD SR 2023-24 ,Page 17 Sl. No.5.15.10)

2

12202

24404.76

... More
code34 - Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898. 6-32 A SP (Refer : PWD SR 2023-24 ,Page 17 Sl. No.5.18.1)

9

489

4407.3

... More
code35 - Supplying and fixing of Shunt trip suitable for MCCB.CBCT (Refer : PWD SR 2023-24 , Page 17 Sl. No.5.16 )

7

2009

14066.78

... More
code36 - Numerical Over Current & Earth Fault Protecion Relay with Accessories for NJY Works(Refer : COMMON SR 2023-24 VOL-6,Part-II, Page 24 Sl. No.406 item no. 53.12)

3

12850

38550.57

... More
code37 - Supplying, fixing and wiring 50/5 to 400/5A 5VA burden Current Transformer Class 0.5 accuracy with Tape Wound. (Refer : PWD SR 2023-24 ,Page 19 Sl. No.5.34)

12

663

7957.92

... More
code38 - Supplying, fixing and wiring 1000/5A to 1600/5A 15VA Burden class 1 Current Transformer (Refer : COMMON SR 2023-24 VOL-6,Part-III, Page 19 Sl. No.5.36 )

27

991

26762.13

... More
code39 - Supplying of multi function digital meter with three line back light LCD type display for voltage, Current, frequency, Power, power factor, kVA, kWH, kVAR suitable for 3 phase, 4 wire LT network with IP 54 degree of protection and completely wired as required with communication Port and Class 0.5s accuracy (Refer : COMMON SR 2023-24 VOL-6,Part-III, Page 19 Sl. No.5.33 )

6

10991

65950.14

... More
code40 - Supplying, fixing and wiring 0 to 600V 96x96mm AC Voltmeter on existing panel/wood board. (Refer : COMMON SR 2023-24 VOL-6,Part-III, Page 18 Sl. No.5.22 )

3

533

1600.08

... More
code41 - Supplying, fixing and wiring earth leakage relay with core balanced current transformer suitable for single phase 50 Hz AC with latest microcontroller based, digital readout of percentage leakage current, programmable delay/auto/ manual reset facility suitable to mount on DIN rail/ flush mounting on panel board.(Refer : COMMON SR 2023-24 VOL-6,Part-III, Page 18 Sl. No.5.21 )

3

10920

32762.7

... More
code42 - PLC Arrangement for Interlocking System (Market Rate)

1

147500

147500

... More
code43 - Surge Protection System - T1 SPD - Market Rate

1

23600

23600

... More
code44 - Supplying and fixing angle iron frame work fabricated out of M.S. angle iron.. and M.S. Flat......with bolts, washers etc., and painted with 2 coats of red oxide and then two coats of approved paint. 50 x 50 x 6 mm (Refer : PWD SR 2023-24 ,Page 20 Sl. No.5.41.2)

15

466

6991.35

... More
code45 - Supplying A rated 3phase with neutral bus bar using required capacity electrolytic aluminium strips covered with heat shrinkable coloured PVC sleeve, mounted on phenolic/FRP/DMC insulator which are mounted on powder coated 40x6mm M.S.flat frame work in existing panel board. The bus bar shall have suitable holes for termination of incoming and outgoing cables as per IS specification with necessary bolts, nuts and washers etc., complete. 1000 A double run of 4 x 60 x 10 mm Aluminium Strips (Refer : PWD SR 2023-24 , Page 20 Sl. No.5.40.5 )

6

12484

74906.4

... More
code46 - Fabricating supplying and mounting MS box made out ....SWG suitable for floor /wall mounting, fully weather proof with provision for better heat dissipation, provided with hinged front cover, equipped with tamper proof locking arrangements, with suitable size clamps with necessary cable entry pipe with gland and box should be finished with 7tanks treatment with powder coated paint and finally finished with approved colour etc., complete. 14 SWG (Refer : PWD SR 2023-24 VOL-6,Page 20 Sl. No.5.42.1 )

300000

-

177000

... More
code47 - 275 KVAR APFCR Panel (as per Attached Drawing number -PPES /DKMPUL/APFC /EL-02) Installation, Testing & Commissiong of floor mounted Panel shall be made out of 14/16 guage sheet steel, with 630 A, capacity TPN +E, aluminium busbars with PVC sleeves with required outgoing feeders..(Size of the panel -2.0 Mts(L) x 8.0 (D) x 2.1 Mts (H) ) -MARKET PRICE

1

531000

531000

... More
code48 - Supplying and drawing Flexible Multicore Cable manufactured with electrolytic grade flexible copper with low conductor confirming to IS8130-1984 and (Virgin) PVC insulation sheathed suitable for working voltage upto 1100 Volts as per IS-694:19903C x 1.5 mm2 (Refer : PWD SR 2023-24 VOL-6,Page 6 Sl. No.2.5.2 )

150

84

12744

... More
code49 - Supplying and drawing Flexible Multicore Cable manufactured with electrolytic grade flexible copper with low conductor confirming to IS8130-1984 and (Virgin) PVC insulation sheathed suitable for working voltage upto 1100 Volts as per IS-694:19904C x 2.5 mm2 (Refer : PWD SR 2023-24 VOL-6,Page 6 Sl. No.2.5.9 )

100

174

17464

... More
code50 - Supplying and drawing Flexible Multicore Cable manufactured with electrolytic grade flexible copper with low conductor confirming to IS8130-1984 and (Virgin) PVC insulation sheathed suitable for working voltage upto 1100 Volts as per IS-694:199010C x 2.5 mm2 (Refer : PWD SR 2023-24 VOL-6,Page 6 Sl. No.2.5.13 )

100

506

50621

... More
code51 - Supplying ......... A rated 3phase with neutral bus bar using required capacity electrolytic aluminium strips covered with heat shrinkable coloured PVC sleeve, mounted on phenolic/FRP/DMC insulator which are mounted on powder coated 40x6mm M.S.flat frame work in existing panel board. The bus bar shall have suitable holes for termination of incoming and outgoing cables as per IS specification with necessary bolts, nuts and washers etc., complete 1000 A double run of 4 x 60 x 10 mm Aluminium Strips (Refer : PWD SR 2023-24 , Page 20 Sl. No.5.40.5 )

3

12484

37453.2

... More
code52 - Unloading, Storing, Erection, testing and commissioning of 11 KV /433V, 800KVA, EEL-2 Delta/Star, Copper ,Wound, Transformer with HV & LV side cable box , with OLTC ( The civil works like foundation is excluded in this scope) -MARKET PRICE

1

14160

14160

... More
code53 - Liaison with Electrical Inspectorate, approval of drawings, obtaining charging & commissioning approval from Electrtical Inspectorate (Fees for the above approvals will be reimbersed at Actuals) -MARKET PRICE

1

236000

236000

... More
code54 - Dismantling of existing foundation of size 4.25 ft Length x 4.25 ft Breadth x 4.25 ft Height. Cost of work includes shifting of debris to specified place as per direction of Engineer Incharge. Cost of work includes HOM, labour, tools & tackles,etc all complete

1

10000

10000

... More
code55 - Providing of RCC / Size stone masonry foundation for 800 KVA transformer. Scope of work includes excavation, size stone masonry work, plastering, 100mm thick. PCC on top of foundation,etc. all cpmplete with required Gi Support to OLTC of Transformer, etc complete. Cost of work is inclusive of materials, transportation, HOM, labour, tools & tackles, etc all complete. Size of transformer foundartion-1800mm(L) x 1200mm(W) x 1500mm (D)

1

35000

35000

... More
code55 - Supply , Unloading, Storing, Erection, testing and commissioning of 11 KV /433V, 800KVA, EEL-2 Delta/Star, Copper ,Wound, Transformer with HV & LV side cable box , with OLTC with RTCP

1

2419000

2419000



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.