Indian Institute Of Science Tender

Karnataka, also known as Karunadu, is a state in the southwestern region of India. Karnataka was formed originally as Mysore State on 1st November 1956 and currently is the biggest state in south India. Its capital and largest city is Bengaluru. It covers an area of 191,791 km2 (74,051 sq mi) and is the sixth largest state by area comprising 31 districts. Karnataka is also a state of multiple languages; Kannada being the official and most widely spoken language in Karnataka. Other languages spoken in the state include Tamil, Telugu, Malayalam, Kodava, Konkani and much more.Karnataka tenders are issued by the government of Karnataka, public & private sector organisations. The state government issues majority of the Karnataka tenders, which are for goods and services including construction, road and bridge construction, IT services, engineering services, medical services, educational services amongst many others. Bidassist is one of the largest eprocurement portals, which offers all government tenders from across the world in one place. Bidassist offers information on all Karnataka tenders and other state and authority tenders in no time. Bidassist is a platform where users can look for various Karnataka tenders as well as other tenders.

Indian Institute Of Science - IISC Tender

Works
Civil And Construction
Building Construction
Eprocure
Opening Date12 Jan 2024
Closing Date28 Feb 2024
Tender Amount₹ 1,17,46,07,470 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Supplying and filling in plinth with sand under floors, foundation of Bridges including watering, ramming, consolidating and dressing complete. As per the direction of Engineer-In-Charge

1315

-

-

... More
Providing and injecting chemical emulsion for Pre-constructional Anti-Termite Treatment, creating continuous chemical barrier under and around the column pits, walls, trenches, basement excavation, top surface of the plinth filling, junction of wall and floor, along the external perimeter of building, expansion joints, over the top surface of consolidated earth on which apron is to be laid, surrounding of pipes and conduits with Chlorpyriphos 20% E.C. / Lindane 20% E.C. @ 3.19 l/m2 including cost of chemical, diluting in water to one percent concentration, labour, usage charges of machinery, complete as per specifications. As per the direction of Engineer-In-Charge

3655

-

-

... More
Providing and laying in position plain cement concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machineries, curing, and all the other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement & formwork shall be paid separately) Mix 1:3:6 (M10) Using 20 mm nominal size graded crushed coarse aggregates As per the direction of Engineer-In-Charge

766

-

-

... More
Providing and laying in position Reinforced cement concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement & formwork to be paid separately) Mix 1:2:4 (M15) Using 20 mm nominal size graded crushed coarse aggregates As per the direction of Engineer-In-Charge

722

-

-

... More
Construction of Granular Sub-Base of required grading as per design mixing in a mechanical mix plant at OMC, carriage of mixed Material to work site, spreading in uniform layers with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per clause 401 As per the direction of Engineer-In-Charge For Grading -I Material

366

-

-

... More
Construction of Granular Sub-Base of required grading as per design mixing in a mechanical mix plant at OMC, carriage of mixed Material to work site, spreading in uniform layers with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per clause 401 As per the direction of Engineer-In-Charge For Grading -II Material

366

-

-

... More
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth. As per the direction of Engineer-In-Charge

321

-

-

... More
Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 12.5mm nominal size derived from natural sources) As per the direction of Engineer-In-Charge

100

-

-

... More
Providing & applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7kg per square meter on damp proof course after cleaning the surface with brushes and finally with apiece of cloth lightly soaked in kerosene oil. As per the direction of Engineer-In-Charge

100

-

-

... More
Providing Thermo-Mechanically Treated bars of grade Fe-500D or more Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position, binding and anchoring to adjacent members whereever necessary complete as per Design including cost of material, labour, usage charges complete as per specifications. (The laps and wastages shall not be measured separately) As per the direction of Engineer-In-Charge

2203357

-

-

... More
Providing and laying in position Reinforced cement concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement to be paid separately but inclusive of centering & Shuttering) As per the direction of Engineer-In-Charge M35 Design Mix Using 20 mm nominal size graded crushed coarse aggregates Isolated Footings

934

-

-

... More
Providing and laying in position Reinforced cement concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement to be paid separately but inclusive of centering & Shuttering) M35 Design Mix Using 20 mm nominal size graded crushed coarse aggregates As per the direction of Engineer-In-Charge Other type of Foundation

3664

-

-

... More
Providing and laying in position Reinforced cement concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement & formwork to be paid separately but inclusive of centering & Shuttering) M35 Design Mix Using 20 mm nominal size graded crushed coarse aggregates As per the direction of Engineer-In-Charge Plinth Beam/Beams

220

-

-

... More
Providing and laying in position Reinforced cement concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement to be paid separately but inclusive of centering & Shuttering) M35 Design Mix Using 20 mm nominal size graded crushed coarse aggregates As per the direction of Engineer-In-Charge Walls

913

-

-

... More
Providing and laying in position Reinforced cement concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement to be paid separately but inclusive of centering & Shuttering) M35 Design Mix Using 20 mm nominal size graded crushed coarse aggregates As per the direction of Engineer-In-Charge Grade Slab

413

-

-

... More
Providing and laying in position Reinforced cement concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcemen to be paid separately but inclusive of centering & Shuttering) As per the direction of Engineer-In-Charge M35 Design Mix Using 20 mm nominal size graded crushed coarse aggregates Slab

532

-

-

... More
Providing and laying in position Reinforced cement concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcemen to be paid separately but inclusive of centering & Shuttering) As per the direction of Engineer-In-Charge M35 Design Mix Using 20 mm nominal size graded crushed coarse aggregates Stair

47

-

-

... More
Providing and laying in position Reinforced cement concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcemen to be paid separately but inclusive of centering & Shuttering) As per the direction of Engineer-In-Charge M40 Design Mix Using 20 mm nominal size graded crushed coarse aggregates Column

291

-

-

... More
Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement to be paid separately but inclusive of centering & Shuttering) As per the direction of Engineer-In-Charge M35 Design Mix Using 20 mm nominal size graded crushed coarse aggregates Lintel

296.84

-

-

... More
Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement to be paid separately but inclusive of centering & Shuttering) As per the direction of Engineer-In-Charge M35 Design Mix Using 20 mm nominal size graded crushed coarse aggregates Slab Level Beams

2172.24

-

-

... More
Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement to be paid separately but inclusive of centering & Shuttering) As per the direction of Engineer-In-Charge M35 Design Mix Using 20 mm nominal size graded crushed coarse aggregates Slab

2427.49

-

-

... More
Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement to be paid separately but inclusive of centering & Shuttering) As per the direction of Engineer-In-Charge M35 Design Mix Using 20 mm nominal size graded crushed coarse aggregates Walls

420.53

-

-

... More
Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement to be paid separately but inclusive of centering & Shuttering) As per the direction of Engineer-In-Charge M35 Design Mix Using 20 mm nominal size graded crushed coarse aggregates Stair

332

-

-

... More
Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement to be paid separately but inclusive of centering & Shuttering) As per the direction of Engineer-In-Charge M40 Design Mix Using 20 mm nominal size graded crushed coarse aggregates Columns (all Level)

1562

-

-

... More
Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement to be paid separately but inclusive of centering & Shuttering) As per the direction of Engineer-In-Charge M40 Design Mix Using 20 mm nominal size graded crushed coarse aggregates PT Beam

2103

-

-

... More
Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement to be paid separately but inclusive of centering & Shuttering) As per the direction of Engineer-In-Charge M40 Design Mix Using 20 mm nominal size graded crushed coarse aggregates PT Slab

478

-

-

... More
Providing and laying cinder concrete in cement 1:15 ( 1 cement : 15 cinder of 12.5mm nominal gauge) on terraced roof or sunken slabs, laid to slope compacting, including cost of materials, labour, curing complete as per specifications. As per the direction of Engineer-In-Charge

315

-

-

... More
Providing and fixing in position 200mm wide Stainless steel Grade 304 plate-1.0 mm thick as per design for expansion joints. As per the direction of Engineer-In-Charge Floor Joint of 50-100 mm gap

318

-

-

... More
Designs & Execution of Post Tensioning works including de coiling the strands, cutting to the required lengths, supplying and laying of HT strands, sheathing(GI corrugated ducts 0.30 mm thick) jointing and inserting the strands, profiling, fixing live end anchorages including the supply of stressing anchorages suitable for 2/3/4/5/7/12/19 strand Tendons, grout vents, making dead end anchorages including flowering the strands, fixing tendon support bars, supervising the fixing of anti bursting reinforcement, stressing the cables, end trimming, grouting the cables with cement and admixtures, with required Plant & Machineries, tools and tackles, consumables etc., works including PT designs and drawings & obtaining approval from client/consultant for the work done as per the requirement of Engineer-In charge at site.

73

-

-

... More
Providing & Laying non-shrink, free-flowing and high strength cementitious grout meeting the requirements of ASTM –C-1107, for depths up to 60 mm. As per the direction of Engineer-In-Charge

5

-

-

... More
Providing and laying water proofing treatment to the Roof with PU based single component elastomeric pure polyurethane based coating on New terrace/Chajjas/Sunken portion of WC:Bathroom, cold applied PU waterproofing membrane that is highly elastic with elongation greater than 400% and tensile strength greater than 2MPa as per ASTM D412. The waterproofing membrane to be applied in 2coats @ 1.6kg per m2 to achieve final DFT (dry film thickness) of 1mm including prime coat of epoxy primer @150 g per m2 and protection with 120gsm Geo-textile over the waterproofing membrane. The finished cost to include surface preparation, making coving at Junction, Bore Packing, treatment of construction joints completely as per specification & with a 10 years warranty on product & work from certified manufacturers as per the direction of the Engineer In charge.

1946

-

-

... More
Providing and fixing polyurethane foam (PUF) slab 60mm thick average with PU slab density 36+/-2 kg/m³ insulation for over deck covered with two layers of 40mm thick cement concrete screed with mix proportion 1:1.5:3 (M20grade) smooth finished with floating coat of neat cement, including necessary polymerized plaster reinforced with glass fibre mesh for PUF slab, epoxy bases bonding adhesive etc., complete As per the direction of Engineer-In-Charge

1946

-

-

... More
Providing and Applying PU based Elastomeric Liquid Applied PU Waterproofing Membrane single component, cold applied, water based acrylic PU dispersion with highly elastic and UV resistant water proofing treatment to the Existing Roof surface/Chajjas/Sunken portion of WC:Bathroom applied @ 1.2L/per m2,having tensile strength greater than 1.5N/mm2, elongation greater than 300% with solid content not less than 60% in 2 coats including surface preparation, priming the surface with water based acrylic primer @0.1 L/m2, and spreading 60 gsm geotextile between two top coats completely as per specification. The finished cost to include surface preparation, making coving at Junction, Bore Packing, treatment of construction joints completely as per specification & with a 10 years warranty on product & work from certified manufacturers as per the direction of the Engineer In charge.

2021

-

-

... More
Providing and laying water proofing treatment to the Retaining wall area with PU Elastomeric Single component liquid applied, cold applied, moisture cured high tensile elastomeric PU waterproofing membrane having elongation of more than 400% and having solid content of above 90% @ 1.6kg per m2 in 2 coats to achieve final DFT (dry film thickness) of 1mm including prime coat of epoxy primer @150 g/ m2. The cost is inclusive of surface preparation, crack filling, repair of loose mortar etc. completely as per specification & with a 10 years warranty on product & work from certified manufacturers as per the direction of the Engineer In charge.

3268

-

-

... More
Providing and laying water proofing treatment to the Rafts, Below grade slab, Lift pits, water retaining structures with fully bonded High Density Polyethlene Membrane (HDPE) of 1.2mm composite thickness and having tensile strength of 25 MPa (as per ASTM D 412), elongation of 500% (as per ASTM D 412), puncture resistance of 1000N (as per ASTM E 154), peel adhesion to concrete 1200N/m (as per ASTM D 903), hydrostatic head resistance 70m (as per ASTM D 5385). The system should be fully bonded to the RCC thereby conforming to IS 16471:2017 requirements of UG waterproofing structures. The membrane should be minimum 2.4m wide to reduce the number of joints with minimum 75mm factory made selvedge’s and comprising of an HDPE layer and a pressure sensitive adhesive layer which is covered by a weather proof protective and trafficable granular layer to protect self-adhesive polymer layer, etc, including surface preparation completely as per specification & with a 10 years warranty on product & work from certified manufacturers as per the direction of the Engineer In charge.

3692

-

-

... More
Providing and laying water proofing treatment to the Water tanks & Liquid Retaining structures with two component acrylic polymer modified cementitious waterproofing membrane with minimum elongation of 50% applied @ 1.5 kg/m2 for internal side waterproofing in two layers with waiting period of 4-6 hrs per layer and food grade epoxy coating in two coats certified by CFTRI Mysuru, including surface preparation completely as per specification & with a 10 years warranty on product & work from certified manufacturers as per the direction of the Engineer In charge.

425

-

-

... More
Providing and laying waterproofing treatment by chemical injection grout process on retaining walls and raft of basement using 25mm dia M.S nozzles inserted minimum 1/3 thickness of walls,and 1/3 thickness of basement raft & U.G Sump raft placed and fixed @ 0.7 m C/C distance in both directions and @ 0.75 m C/C along construction joints,consisting of injecting cement slurries of different viscosities under pressure by pump using water proofing grout @ 225 gm/50 kg of cement or approved equivalent make conforming to IS: 2645 and as per manufacturer's specification and sealing of nozzles after the injection operation with suitable admixture. All complete As per the direction of Engineer-In-Charge

425

-

-

... More
Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge.

338

-

-

... More
Supplying, filling, spreading &leveling coarse sand of size range 1.5 mm to 2 mm in recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per direction of Engineer -in-charge.

169

-

-

... More
Gravel packing in tube well construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in-charge.

169

-

-

... More
Providing & Laying geotextile 120 GSM over horizontal/sloped surfaces Cost is inclusive of overlapping, only applicable area will be measured for payment. As per the direction of Engineer-In-Charge

1688

-

-

... More
Providing, jointing and fixing perforated uPVC drainage system conforming to IS : 13592 - Type B and UPVC fittings (moulded as well as fabricated) like bends, tees, Y-tees, crosses, boss connections, access pieces, saddle pieces, cleanouts, adaptors for connections to other materials, plugs, reducers, cowls, offsets,cleanout plug and other specials. Jointing shall be done with pushfit EPDM ring jointing technique in general. Solvent cement joints may be provided for fittings and specials which are not manufactured with pushfit rubber joints. As per the direction of Engineer-In-Charge 110 mm dia

225

-

-

... More
Providing Brick work with common burnt clay Non Modular bricks of class designation 3.5 in foundation and plinth in Cement mortar 1:6 (1 cement : 6 coarse sand) including cost of all materials, labour, scaffolding and usage charges of machinery & other incidental charges complete as per the direction of engineer incharge of work. As per the direction of Engineer-In-Charge

1133

-

-

... More
Providing and laying autoclaved aerated cement blocks masonry with 150mm/230mm/300 mm thick AAC blocks as per IS 2185 (Part III) in super structure above plinth level up to floor I level with RCC band at sill level and lintel level with approved block laying polymer modified adhesive mortar including cost of all materials, labour, scaffolding and usage charges of machinery & other incidental charges complete As per the direction of Engineer-In-Charge Cement mortar 1:6 (1 cement : 6 coarse sand)

2486

-

-

... More
Extra for brick work/ AAC block masonry/ Tile brick masonry in superstructure above floor V level, for each four floors or part thereof by mechanical means. As per the direction of Engineer-In-Charge

1106

-

-

... More
Providing Half brick masonry with common burnt clay Non Modular bricks of class designation 3.5 in superstructure above plinth level up to floor 1 level cement mortar 1:4 (1 cement :4 coarse sand) including cost of all materials, labour, scaffolding and usage charges of machinery & other incidental charges complete As per the direction of Engineer-In-Charge

100

-

-

... More
Extra for providing and placing in position 2 Nos 6mm dia. M.S. bars at every third course of half brick masonry As per the direction of Engineer-In-Charge.

100

-

-

... More
Providing cement plaster with cement mortar 1:4 (1 cement: 4 fine sand) to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge. 12 mm average thickness

8853

-

-

... More
Providing cement plaster with cement mortar 1:4 (1 cement: 4 fine sand) to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge. 15mm average thickness

13940

-

-

... More
Providing 18 mm cement plaster in two coats under layer 12 mm thick cement plaster with cement mortar 1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster with cement mortar 1:6 (1 cement : 6 fine sand) to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge.

10455

-

-

... More
Providing 6 mm cement plaster with cement mortar 1:3 (1 cement : 3 fine sand) including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge.

1496

-

-

... More
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete as per specifications and as per directions of Engineer in charge.

24289

-

-

... More
Providing & applying Exterior grade texture paint non-pigmented stone finish with Natural mineral aggregates combined with adhesives and resins. The Finish to be water repellent, anti-fungal, breathes out trapped moisture, having unique property of elasticity & flexibility (due to temperature variation no hairline cracks to appear) protective and decorative coating on exterior surfaces such as, concrete & plastered Surface (as per approved) in colour and pattern as per direction of engineer-in-charge. The works include providing and laying one coat of primer and sealer mixed in equal ratio followed by one coat of basecoat with steel trowel made of natural stone crushed powder, 2nd coat to be applied with steel trowel and finished by acrylic trowel or spray gun of natural stone crushed powder added with granite chips. Final coat of ultra protect shall be applied with roller/spray diluted with water, (as per manufacturer's specification and approval of E-I-C) including cost and conveyance of all material, labour, sundries, tools and machinery etc. all complete. (The base preparation with putty shall be included & will not be paid separately) As per the direction of Engineer-In-Charge

4705

-

-

... More
Finishing walls with water proofing cement paint of required shade :Old work (one coats applied @ 2.20 kg/10 m²) over priming coat of primer applied @ 0.80 litrs/10 m² complete including cost of Priming coat including preparing the surface after thoroughly cleaning the surface to remove all dirt, dust and foreign matter, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge.

500

-

-

... More
Finishing walls with Acrylic Smooth exterior paint of required shade :New work (Two coat applied @ 1.67 ltr/10 m² over and including priming coat of exterior primer applied @ 2.20 kg/10 m²) with paint of approved quality to give an even shade, after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge.

3500

-

-

... More
Acrylic Emulsion Paint:- Finishing walls with 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives, New work (Two coats applied @ 1.43 litre/ 10 m². Over and including priming coat of exterior primer applied @ 0.90 litre/10 m² with paint of approved quality to give an even shade, after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge.

64147

-

-

... More
Ceramic glazed wall tile:- Providing and fixing 1st quality rectified ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer- in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per m2, including pointing in white cement mixed with pigment of matching shade complete. As per the direction of Engineer-In-Charge

3202

-

-

... More
Providing & Fixing of 6mm thick lacquered toughened glass of approved shade and colour, fixed with compatible alkoxy neutral core silicon over levelled surface in design and pattern as per drawings fixed over available strata. The Lacquered glass shall be highly durable, humid resistance, polyurethane lacquer glass. Lacquered glass must be made industrially (via curtain coating process); opaque (if viewed against a support wall), coated with PU lacquer (50 micron thick); color consistency (measured by Minolta spectrophotometer CM5081); highly durable (passes PERSOZ hardness test for minimum 220 oscillations); humid resistant (conforms to BS EN 1036 1999); environmentally friendly (no lead, no arsenic, no copper, no formaldehyde); appropriate recycled content (12% post industrial / 6% post consumer); compressive strength (1000 MPa) & tensile strength (40 MPa),same as float glass. Silicone used should not react with lacquer coating (compatible, alkoxy neutral core), low VOC content 100g/l, low sag, curing time 36 hrs, medium to high modulus. cost is inclusive of provision of Aluminium base frame & base ply to recieve the 6mm thick lacquered glass. Complete in all respect as per the direction of the Engineer-in-charge. Cost is inclusive of all necessary scaffolding. As per the direction of Engineer-In-Charge

216

-

-

... More
Supply and Fixing of Slim Glass partition of 10mm Toughened Glass with insertion of Thermoplastic gasket to adhere the glass firm & airtight. The sound reduction Value is from 32 to 35 Db, using System Anodized Aluminium Frames to a height of maximum 3m or as per drawing.The Fixed glass to be fixed using Aluminum Profiles at Top & Bottom & end at sides. The profile size to be 45-50x25-30MM to be fixed on to the floor/wall/ ceiling as per the architect design. H Junction profile to be used at all Glass to Glass vertical joints, 90 Deg L Junction Profiles and T Junction profiles necessary as per design. Aluminium profiles should be suitable for Glass thickness of 10/12/13.52mm.The Profile should be matt desired coloured anodized, the Profile Manufacturer to supply all the necessary clips, seals and fixing accessories for the system. All Profiles to be with 2 mm Gauge thickness Excluding 20-25 Micron of Anodizing. As per the direction of Engineer-In-Charge

648

-

-

... More
Frosting Film:- Providing and applying 3M frosting film over the glass surface as per approved pattern. (Base rate 1500/- per Sqm). Complete in all respect as per the direction of the Engineer-in-charge. Cost is inclusive of all necessary scaffolding.

200

-

-

... More
Providing, Making and Fixing up to 600 mm. deep Back storage cabinets with shutters and drawers made out of 19 mm thk. water proof ply with back of 6 mm thk. water proof ply finished with 1.5 mm. thk. Laminate and 0.6 mm thick backing laminate on all internal surfaces as per the design and approval of the Architect including providing PVC edging at all junctions and all exposed surface and edges (including fixing SS hinges, Hardware & modular accessories as approved & required.). Shutter are framed 1.5mm thick laminate cold pressed over 19mm board as per design. Front area to be measured for payment. Complete in all respect as per the direction of Architect/Engineer-in-charge.

148

-

-

... More
Providing and applying Water dispersed polyurethane dustproof, easily cleanable and resistant to penetration of oils and liquids, resistant to corrosion, chemicals and abrasion coating and sealer to provide a pigmented sealing coat onto cementitious and concrete surfaces. It is contractor responsibilty to protect all surrounding Flooring, Wall, Window, Door etc. during the process of application. As per the direction of Engineer-In-Charge

5922

-

-

... More
Soft pad panelling ertical poles to be covered with a 19mm foam padding up to 10 feet in height to protect players from injury. Foam Padding for fencing poles up to 10 feet in height. with 12mm waterproof treated plywood over wooden base framing 19mm thermo foam and waterproof fabric As per the direction of Engineer-In-Charge

543

-

-

... More
Providing & Fixing in position Acoustical wall panelling with Integral Densified Square/Butt edged Fully Perforated Eco Friendly Lightweight Calcium Silicate panels/tiles with fabricated galvanised mild steel frame work for Auditoriums, Community halls, Offices, Institutions, Airports, Meeting halls, Indoor Stadiums and Studios. The Eco Friendly Lightweight Calcium Silicate wall panels/tiles shall be made from Non Cementitious Hydrated Calcium Silicate Slurry/Mixture, Reinforced recycled material with fibers and natural fillers. Free from Formaldehyde and other harmful materials. Doesn't contain any toxic ingrediants. The wall panels/tiles size of 595x595mm and 15mm thick should have Humidity Resistance (RH) of 100%, Water Resistance, Non Combustible: as per BS:476 Part-4, Fire Performance: as per BS:476 Part-6 for Fire Propagation, as per BS:476 Part-7 for Surface Spread of Flame, As per UK standards Fire Performace A1-S1-d0, Thermal Conductivity K= 0.048 to 0.050 w/m K as per ECBC code 2007, NRC (Noise Reductions Coefficient) 0.65 to 0.85 (Fully Perforated wall panels/Tiles) as per IS 8225:1987, Sound Attenuation (STA) 30-32dB,Thickness of tile should be 15mm thick with 450 kg/m3 density all around on edge resting portion with Integral Densified edge and 10mm thick with 350 kg/m3 density in the center of the body, Light Reflectance 85%, Weight of material is 5-5.5 kg/m2 and Suitable for Green Building application with InOrganic Recycled content of 46- 50% out of which 18-20% should be FLYASH and meets the GRIHA & SVAGRIHA norms under the categories: GRIHA V.2015 criterion:11&12, GRIHA V.3 criterion: 17&29 and SVAGRIHA criterion:12. The frame work comprising of a frame made especially fabricated galvanised mild steel sheet of 0.50 mm thick pressed section (galvanizing @ 120 grams per m2 including both sides) i.e. vertical studs of size 48x34x36mm are placed at 600mm centre to centre in a floor and ceiling channel section of size 50x32mm fixed to the floor and soffit at 600mm centres using 12mm dia, 40mm long wedge type expanded zinc alloy dash fastner with 10mm bolt. This same channel is then to be fixed in horizontal direction at 600mm centre to centre so as to form a grid of 600x600mm. Glass wool of 50mm thickness with density of 16 kg/m3 is then to be inserted in the slots and finally Lightweight calcium silicate wall panels/tiles are to be screw fixed with self-tapping pan head nickle coated mild steel screws of size 13x3.2mm on to this grid leaving an even groove of 1 mm between the panels. The joints between the panels are to be duly jointed and finished using recommended jointing calcium silicate based compound and fibre joint tape roll 50mm wide (90metre) roll and two coats of premier suitable for panelling as per manfacturer's specification as per direction of engineer-in-charge all complete.

1986

-

-

... More
Providing & fixing perforated 19mm thick MDF board over hardwood frame of 50mm x 50mm section with thermal insulation with Resin Bonded Fibre glass wool conforming to IS: 8183 having density of 32 kg/m3, 50 mm thick, wrapped in 200G Virgin Polythene Bags fixed with screw, rawl plug & washers and held in position by criss-crossing GI wires etc complete as per directions of Engineer-in-Charge. Perforrated MDF board will be finished in approved shade of Automotive paint. As per the direction of Engineer-In-Charge

489

-

-

... More
Providing and fixing Structural Steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge.

108905

-

-

... More
Providing and fixing Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. Hot finished welded type tubes including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge.

67468

-

-

... More
Providing and fixing Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge.

50466

-

-

... More
Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters. 80x1.25 mm M.S. laths with 1.25 mm thick top cover including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge.

32

-

-

... More
Providing and fixing ball bearing for rolling shutters including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge.

8

-

-

... More
Extra for providing mechanical device chain and crank operation for operating rolling shutters: Exceeding 10.00 m² and upto 16.80 m² in the area including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge.

32

-

-

... More
Finishing with Epoxy paint (two coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete. On steel work including preparing the surface after thorougly cleaning oil, grease, dirt and foreign matter, cost of materials, labour complete as per specifications and as per directions of Enginer-in-charge.

3675

-

-

... More
Applying 50 micron powder coating over MS work as per IS code 13871. As per the direction of Engineer-In-Charge

1056

-

-

... More
Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in- charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.) including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge.

200

-

-

... More
Deck Sheeting Providing and fixing roofing consist of 0.8 mm thick galvanized steel deck sheet conforming to IS 277:1992 used as permanent shuttering over which MS wire mesh 3mm laid at 100x100 mm grid including edge trim covered with concrete. This metal deck will be supported on structural steel beam with shear studs. (Structural steel like beam, column, joists etc. & concrete of different grade as per design will be paid separately). As per the direction of Engineer-In-Charge

850

-

-

... More
Fire Paint Supplying and Installing by airless spray method 3 coat fire paint system (Water based), fully compliance with GRIHA rating with a combined VOC (Volatile Organic Content) of not more than 250GMS/LTR. Water based single pack Intumescent coating applied on –site after steel erection to a DFT for fire protection of steel structure upto 1 hour as per NBC. The fire proof materials to be independently tested, assessed and approved to ASTM-E119 ,or BS -476/21.Test standards; at NAMAS and NATA approved laboratories such as WFRC,BRE,IFC ,BRANZ, Underwriters Laboratories (UL) . All packaging should be stamped with a Testing Lab Label, confirming accredited Third Party Certification of the contents to comply with requirements stipulated in test reports. All applications to be only by specialist companies certified by manufacturer. All applications to be checked/audited by Manufacturers Q/A representative, and Warranties for 15 years to be provided by the Contractor. All work shall be carried out as per manufacturer's specification and direction of engineer-in-charge.

2350

-

-

... More
Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. (Made of G.I. wire of dia. 4 mm, PVC coated to achieve outer dia not less than 5 mm in required colour and shade)

100

-

-

... More
Top sheet - Supply and Installation of colour coated 0.45mm base metal thickness 0.50mm TCT KLIP-LOK concealed fix profile of 700 mm effective cover width, with four major deep corrugation, 43mm deep rib spaced at 233mm c/c along with micro stiffeners perpendicular to ribs for strength. The male and female rib shall have anti-capillary groove. The steel sheet is having yield strength 550MPa (Fy=550Mpa), metallic coated with Zinc-Aluminium alloy (i.e. 55% Al, 43.4% Zinc, 1.6% Si - Zincalume), AZ150 (min 150 gm/m2 total on both side), pre-painted with Super Durable Polyester quality paint includes inorganic infrared reflective pigment of 20μm exterior coat on top surface and 5μm reverse coat on back surface over 5μm primer coat on both surfaces of approved color shade by concern authority. The sheet conforms to general requirement of AS/NZS 2728 type 4 / IS 15965 class 3 durability and gloss value of 25% - 40%. The "Concealed fix" sheets shall be fixed to every purlin by means of patented clips having spurs which will securely hold the sheets in position and lock-in the side-lap and both centre ribs. The clip shall be fastened with 40μm zinc coated or nominal 25μm zinc-tin alloy coated, Hex head, self-drilling screw as per AS 3566-2002 Class 3 fasteners of approved make with EPDM washer as per the requirement considering the profile shape and design load. The profile sheet, fastener size etc. needs to be approved by the concern authority. All the accessories like gutter/ flashing / capping shall be made from the same material used for main cladding. Bottom sheet - Supply of colour coated 0.45mm base metal thickness 0.50mm TCT trapezoidal profile of 1015 mm effective cover width, with five major corrugation, 28mm high rib spaced at 203mm c/c with subtle square fluting in the pan. The end rib shall have anti-capillary groove and return leg. The steel sheet is having yield strength 550MPa (Fy=550Mpa), metallic coated with Zinc-Aluminium alloy (i.e. 55% Al, 43.4% Zinc, 1.6% Si - Zincalume), AZ150 (min 150 gm/m2 total on both side), pre-painted with Super Durable Polyester quality paint includes inorganic infrared reflective pigment of 20μm exterior coat on top surface and 5μm reverse coat on back surface over 5μm primer coat on both surfaces of approved color shade by concern authority. The sheet conforms to general requirement of AS/NZS 2728 type 4 / IS 15965 class 3 durability and gloss value of 25% - 40%. The sheet shall have brand marking of the manufacturer giving product details on the back of the sheet at every 1 meter c/c for confirming genuinity of the material. The steel sheet shall be fastened with 25 μm zinc-tin alloy coated, Hex head, self-drilling screw as per AS 3566 Class 3 fasteners of approved make with EPDM washer as per the requirement considering the profile shape and design load. The fastener size shall be calculated as per the design or manufacturers recommendations. All the accessories like gutter/ flashing / capping shall be made from the same material (or manufacturer’s recommendation) which is used for main cladding application. Two Layer of 50mm Thk. 48kg/m3 density Glasswool Insulation with one side FSK facing Insulation – Insulation – In between top and bottom sheet Supply and application The galvanised Z120 sub-girts (as per design requirement) depth shall be fixed above the bottom sheet & Purlin using suitable fastener. The panel shall be 15-17% perforated backed with Non woven acoustic tissue paper, for acoustic properties. As per the direction of Engineer-In-Charge

2165

-

-

... More
All the accessories like flashing / capping /Gutter, Downspouts/Ridge shall be made from the material specifications (0.42MM BMT /0.47 MM TCT, mentioned as above in approved colour shade & as per manufacturers’ recommendation. As per the direction of Engineer-In-Charge 306 to 610mm Girth

258

-

-

... More
All the accessories like flashing / capping /Gutter, Downspouts/Ridge shall be made from the material specifications (0.42MM BMT /0.47 MM TCT, mentioned as above in approved colour shade & as per manufacturers’ recommendation. As per the direction of Engineer-In-Charge 611 to 900mm Girth

250

-

-

... More
All the accessories like flashing / capping /Gutter, Downspouts/Ridge shall be made from the material specifications (0.42MM BMT /0.47 MM TCT, mentioned as above in approved colour shade & as per manufacturers’ recommendation. As per the direction of Engineer-In-Charge 901 to 1220 mm Girth

258

-

-

... More
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. As per the direction of Engineer-In-Charge 110 mm diameter

410

-

-

... More
Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion. As per the direction of Engineer-In-Charge Coupler 110 mm diameter

12

-

-

... More
Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion. As per the direction of Engineer-In-Charge Bend 87.5° 110mm

12

-

-

... More
Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion. As per the direction of Engineer-In-Charge Shoe (Plain) 110mm

12

-

-

... More
Providing and applying two coats of PU coating with minimum thickness of 200 microns with approved make on steel surfaces of gutters within an interval of 6-8 hrs over one coat of Epoxy Zinc Primer including preparation of surface by removing and cleaning the surface to ensure it free form dust, loose material, paint, oil or any other material by wire brushing etc. and filling all joint gaps with single component PU sealant. complete as per specifications and direction of engineer-in-charge.

1032

-

-

... More
Providing and fixing unglazed, uncoated, metal pressed, full body homogeneous anti-algal, all weather resistant ready to install step tile with built-in- bull nose and anti skid strip, smooth and anti skid surface confirming to IS: 4457-2007 and having water absorption of 0.05% in 12mm thickness in sizes as required as per site condition in treads of stairs. These anti skid tiles are to be laid on 20mm thick cement mortar of mix 1:4 (1 cement: 4 coarse sand) and joints filled with polymer based cement grout with all labour, material, cement, tile, sand, grout etc as a complete job & as per direction of Engineer-in-charge.

1436

-

-

... More
Providing and fixing unglazed, uncoated, metal pressed, full body homogeneous anti-algal, all weather resistant tile with smooth and anti skid surface confirming to IS: 4457-2007 and having water absorption of 0.05% in 12mm thickness in sizes as required as per site condition in riser and skirting of stairs. These anti skid tiles are to be laid on 12mm thick cement mortar of mix 1:3 (1 cement: 3 coarse sand ) and joints filled with polymer based cement grout with all labour, material, cement, tile, sand, grout etc as a complete job & as per direction of Engineer-in-charge.

412

-

-

... More
Providing and laying tactile tile (for vision impaired persons as per standards) of size 300x300x9.8mm having with water absorption less than 0.5% and conforming to IS:15622 of approved make in all colours and shades in for outdoor floors such as footpath, court yard, multi modals location etc., laid on 20mm thick base of cement mortar 1:4 (1 cement : 4 coarse sand) in all shapes & patterns including grouting the joints with white cement mixed with matching pigments etc. complete as per direction of Engineer-in-Charge.

600

-

-

... More
Deduct for not using 20 mm thick cement mortar 1:4 (1 cement : 4 coarse sand) bedding in laying of floor tiles and jointing with grey cement slurry @ 3.3 kg/ m2. As per the direction of Engineer-In-Charge

500

-

-

... More
Fixing glazed/ Ceramic/ Vitrified floor tiles with cement based high polymer modified quick-set tile adhesive (Water based) conforming to IS: 15477, in average 3mm thickness. As per the direction of Engineer-In-Charge

500

-

-

... More
Providing and laying Matt/ Antiskid finish vitrified tiles in floor in 600mm x 600mm size (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only. Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily. (Vitrified tile with at least 10% recycled content by weight. Preference should be given to GRIHA certified Vitrified tiles). As per the direction of Engineer-In-Charge

1922

-

-

... More
Grouting the joints of flooring/ wall tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing complete as per direction of Engineer-in-charge. Size of Tile 300x600 mm

3202

-

-

... More
Grouting the joints of flooring/ wall tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing complete as per direction of Engineer-in-charge. Size of Tile 600x600 mm

1922

-

-

... More
Providing and laying Shot Blasted finish Granite stone flooring of approved & required design, shade and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand)/ Adhesive laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-charge. Polished Granite stone slab will be as per approved colour/shade by Engineer-in-charge.

206

-

-

... More
Providing and installing 18 mm thick gang saw cut, mirror polished, pre-moulded and pre-polished granite counter, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) / adhesive, joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc., complete in all respects as per the direction of the Engineer-in-charge.

874

-

-

... More
Providing and laying Polished Granite stone flooring as per approved colour/shade by Engineer-in-charge. in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-charge.

1297

-

-

... More
Making 3nos. Grooves 3mm x 3mm in treads of Granite/ Kota Stone/ Marble stone as direction of Engineers-in-charge/Architect.

59

-

-

... More
Providing and laying Rectified Glazed Ceramic floor/Wall tiles of size 300x300 mm or more (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in colours White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement: 4 Coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. As per the direction of Engineer-In-Charge

561

-

-

... More
Vitrified Tile Flooring:- Providing and laying Fullbody vitrified floor tiles in floor/Skiting in required size thickness as per maufacturers specification with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand). Tiles will be laid with 3mm thick spacer joint which will be filled the epoxy grout matching with tile colour/ as approved by Architect or Engineer-incharge. The tiles must be cut with the zero chipping diamond cutter only. Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily. Cost is inclusive of Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing complete as per direction of Engineer-in-charge. In tiles size 600mm x 600mm

1592

-

-

... More
Vitrified Tile Flooring:- Providing and laying Fullbody vitrified floor tiles in floor/Skiting in required size thickness as per maufacturers specification with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand). Tiles will be laid with 3mm thick spacer joint which will be filled the epoxy grout matching with tile colour/ as approved by Architect or Engineer-incharge. The tiles must be cut with the zero chipping diamond cutter only. Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily. Cost is inclusive of Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing complete as per direction of Engineer-in-charge. In tiles size 800mm x 800mm

1592

-

-

... More
Vitrified Tile Flooring:- Providing and laying Fullbody vitrified floor tiles in floor/Skiting in required size thickness as per maufacturers specification with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand). Tiles will be laid with 3mm thick spacer joint which will be filled the epoxy grout matching with tile colour/ as approved by Architect or Engineer-incharge. The tiles must be cut with the zero chipping diamond cutter only. Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily. Cost is inclusive of Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing complete as per direction of Engineer-in-charge. In tiles size 600mm x 1200mm

4776

-

-

... More
Providing and laying Vitrified tiles in 600mm x 600mm (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ m2 including grouting the joint with white cement & matching pigments etc. complete. As per the direction of Engineer-In-Charge

805

-

-

... More
Providing and laying C.C. pavement of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator , vacuum dewatering process and finally finished by floating, brooming with wire brush etc. complete as per specifications and directions of Engineer-incharge. (The panel shuttering work shall be paid for separately). (Note:- Cement content considered in this item is @ 330 kg/cum. Excess/less cement used as per design mix is payable/ recoverable separately).

341

-

-

... More
Extra for providing and mixing hardening compound of sodium silicate based transparent surface hardener, dust proofer, sealing and curing compound for concrete. As per the direction of Engineer-In-Charge

1311

-

-

... More
Extra for providing and mixing Glass fibre reinforcement in VDF Flooring. As per the direction of Engineer-In-Charge

341

-

-

... More
Extra for providing and mixing high performance superplasticiser in conretre intended to high water reduction and long workability retention are required. As per the direction of Engineer-In-Charge

341

-

-

... More
Providing and applying Acrylic emulsion cement modified and water based concrete bonding agent. Adhesion to concrete substrate:- 20N/mm2(BS6319) The bonding agent shall be an acrylic based emulsified solution containing a minimum of 43% solids and compatible with cementitious materials. The bonding agent shall provide adequate bond strength when directly applied on concrete and also mixed with neat cement As per the direction of Engineer-In-Charge

5243

-

-

... More
Cutting of Control/Cold joint Groove in cement concrete flooring. As per the direction of Engineer-In-Charge Groove Size 4mm x 10mm

1250

-

-

... More
Cutting of Control/Cold joint Groove in cement concrete flooring. As per the direction of Engineer-In-Charge Groove Size 8mm x 18mm

1250

-

-

... More
Filling of Control/Cold joint Groove with Epoxy urethane joint Sealer with suitable backer rod. As per the direction of Engineer-In-Charge 4mm x 4mm groove with 6mm dia backer rod.

1250

-

-

... More
Filling of Control/Cold joint Groove with Epoxy urethane joint Sealer with suitable backer rod. As per the direction of Engineer-In-Charge 8mm x 8mm groove with 10mm dia backer rod.

1250

-

-

... More
Providing & fixing of anodized aluminium skirting & end profile with plastic corners and rubber gasket and connnectors. Aluminium screw on skirting, are ideal to cover any types of wall base to protect from foot scratches and any type of floor covering thereby providing a neat finish on the joint. It is installed using a screw for neat fixing. As per the direction of Engineer-In-Charge 100mm Wide

6000

-

-

... More
Providing & fixing of anodized aluminium skirting & end profile with plastic corners and rubber gasket and connnectors. Aluminium screw on skirting, are ideal to cover any types of wall base to protect from foot scratches and any type of floor covering thereby providing a neat finish on the joint. It is installed using a screw for neat fixing. As per the direction of Engineer-In-Charge 50mm wide

6000

-

-

... More
Painting road surface marking with adequate nos. of coats to give uniform finish with ready mixed road marking paint conforming to IS : 164, on bituminous/RCC surface in white/ yellow shade, including cleaning the surface of all dirt, scales, oil, grease and foreign material etc. complete. New work (Two or more coats)

150

-

-

... More
Providing & Laying Cementitious Self-Leveling Underlay Screed upto 15mm thickness under the flooring to achieve a smooth finish even surface. Compressive Strength should not be less than 35N/Sqmm, Flexural Strength should not less than 7 N/Sqmm, Adhesion Strength not less than 2.5-2.8 N/Sqmm in 28 days. Abration class complies with AR 2(as per BS 8204) As per the direction of Engineer-In-Charge

3427

-

-

... More
Badminton & Table Tennis Flooring:- Supply & Installation of Wooden flooring system consisting of a polythene sheet on top of concrete to act as vapour barrier followed 10mm rubber cushion pad followed by pine wood runner of thickness 32mm/45mm treated and placed at 350mm interval with hard wood flooring made of Maple wood of 20mm thick and give a sanding / grinding finish assembled using Tongue and Groove joint. The wood manufacturer should be associated with BWF / ITTF approved product. Work shall be executed all Complete as per direction of Engineer-incharge/Architect. SURFACE BOARD: - Maple Wood Sports Flooring “Certified by the BWF according to BWF standards – Approved Level 1A & 1B with 20 mm thick, 55 to 85mm wide and in random length in tongue and groove shape. The edges of the boards will have a finger lock groove and the bottom side with air pass groove and treated with special anti-termite and water-resistant lacquer. THE UNDER FRAME: - Resilient SPF Pine Wood sleeper subfloor of 70 mm x 45 mm, treated with anti-termite solution and fixed on the bottom side with 19 mm thick EPDM rubber pads, stapled through the two wings at 350 mm x 350 mm. INSTALLATION: - IPS subfloor treated with a vapour barrier to be placed on the levelled IPS sub-floor before laying the under frame. The runners having air cushion pads to be placed on the vapour barrier in perfect level at 350 mm in 1 direction. The surface board to be screwed to the runner through the tongue only and will lock the screwed tongue by the groove of adjoining board. Ends of the boards will be locked by inserting the wooden fingers through the edge grooves and fixed with suitable adhesive. The expansion of 12-15 mm will be left open between the wooden flooring and the surrounding tiled area / walls. FINISHING: - After installation the floor will be machine sanded in uniform level and finished with P. U. Polishing water based polyurethane lacquer. Game line marking to be carried out in required colours before applying the finish coat. As per the direction of Engineer-In-Charge

2019

-

-

... More
On top of the wooden sub floor the PVC rolls of thickness 4.5mm Approved by Badminton World Federation And Certified by Labosport Grade 1 – EN 14904 As Per Badminton World Federation Standards should be installed with game line marking. PVC roll fixed with Welding Cord & Tape. Work shall be executed all Complete as per direction of Engineer-incharge/Architect.

2019

-

-

... More
Multi Purpose Hall Wooden Flooring:- Supply & Installation of Wooden flooring system consisting of a polythene sheet on top of concrete to act as vapour barrier followed 10mm rubber cushion pad followed by pine wood runner of thickness 32mm/45mm treated and placed at 350mm interval with hard wood flooring made of Maple wood of 20mm thick and give a sanding / grinding finish assembled using Tongue and Groove joint with polishing. Work shall be executed all Complete as per direction of Engineer-incharge/Architect.

599

-

-

... More
Basketball Court Flooring- Supply & Installation of Wooden flooring systm consisting of 10mm rubber cushion pad followed by pine wood runner of thickness 32mm/45mm treated and placed at 350mm interval with hard wood flooring made of Maple wood of 20mm thick and give a Polished finish. The wood manufacturer should be associated with MFMA and FIBA lab test report shoud be submitted and confirms to FIBA approved product. The polish which is suppose to be used should also be FIBA approved. Work shall be executed all Complete as per direction of Engineer-incharge/Architect. SURFACE BOARD: - Maple Sports Flooring “Certified by the MFMA /FIBA standards - Grade 1” LABO SPORTS Test Certify EN 14904 Standard finished with 20 mm thick, 55 to 85mm wide and in random length in tongue and groove shape. The edges of the boards will have a finger lock groove and the bottom side with air pass groove and treated with special anti-termite and water-resistant lacquer. THE UNDER FRAME: - Resilient SPF Pine Wood sleeper subfloor of 70 mm x 45 mm, treated with anti-termite solution and fixed on the bottom side with 10 mm thick EPDM rubber pads, stapled through the two wings at 350 mm x 350 mm. INSTALLATION: - IPS subfloor treated with a vapour barrier to be placed on the levelled IPS sub-floor before laying the under frame. The runners having air cushion pads to be placed on the vapour barrier in perfect level at 350 mm in 1 direction. The surface board to be screwed to the runner through the tongue only and will lock the screwed tongue by the groove of adjoining board. Ends of the boards will be locked by inserting the wooden fingers through the edge grooves and fixed with suitable adhesive. The expansion of 12-15 mm will be left open between the wooden flooring and the surrounding tiled area / walls. FINISHING: - After installation the floor will be machine sanded in uniform level and finished with P. U. Polishing water based polyurethane lacquer. Game line marking to be carried out in required colors before applying the finish coat As per the direction of Engineer-In-Charge

922

-

-

... More
Providing and fixing Heat Resistant Terrace Tiles (300 mm x 300 mm x 20 mm) with SRI (solar refractive index) 78, solar reflection 0.70 and initial emittance 0.75 on waterproof and sloped surface of terrace, laid on 20 mm thick cement sand mortar in the ratio of 1:4 (1 cement : 4 coarse sand) and grouting the joints with mix of white cement & marble powder in ratio of 1:1, including rubbing and polishing of the surface upto 3 cuts complete, including providing skirting upto 150 mm height along the parapet walls in the same manner as per direction of incharge.

2618

-

-

... More
Carpet Flooring Providing & Fixing of Flocked textile floor covering of 100% Nylon 6.6 face fiber completely water proof resilient backing. The flooring should be Anti static with thickness of 4.3 mm and approximate weight of 1.8 k.g./sqm of roll form. The carpet should be completely stain resistant and of a density approx. 80 million fibers/sq.mtr (70 million fiber/sq.yd) in the width of 2 mtr .The floor covering should have Fire Test EN-13501, Appearance Retention Hexapod ISO 140-8, Friction Slip Resistance Test EN 14041 Class DS, with resilient waterproof backing, anti allergic which is certified by British allergy foundation. The carpet should have permanent static contro. The work should be carried out by the authorized installer of the Company in India. Carpet should be laid on zero leveled surface. Carpet should be stick with SR 998/ Floor Fix on the floor. Work shall be executed all Complete as per direction of Engineer-incharge/Architect.

556

-

-

... More
Volley ball Court Flooring:- Supply & Installation of PU Flooring having thickness of 7mm (5+2) 5mm SBR rolls / Insitu smoothened with a Sealer/ self leveller followed by a 2mm PU Coating. FIVB Recommended Game line marking Work shall be executed all Complete as per direction of Engineer-incharge/Architect.

1245

-

-

... More
PU Flooring for General Sports areas :- Providing & Laying PU Sports Flooring System – PU Sports Flooring to be installed on Cement Base smooth leveled surface. Cleaning and moisture checking should be done during the sub-base preparation. Adhesive layer will be laid followed by Primer Layer. 5mm Rubber Mat/Cast in situ (SBR granules with PU Binder & Laid evenly) will be laid over primer layer followed with Pore filler coat. Two Layers of 1mm liquid will applied over PU layer followed by one coat of color on top Surface with Game Line Marking. Work shall be executed all Complete as per direction of Engineer-incharge/Architect.

434.66

-

-

... More
Supply & Instalation of 13mm turf manufactured by FIFA preferred producer. Work shall be executed all Complete as per direction of Engineer-incharge/Architect.

114

-

-

... More
Supply & Installation of Rubber flooring having thickness of 15mm of tile size 500mm x 500mm of interlocking type. Work shall be executed all Complete as per direction of Engineer-incharge/Architect.

1212

-

-

... More
Wrestling mat - Of size 2mt x 1mt made of material JSR PVC Cover of thickness 70mm. Work shall be executed all Complete as per direction of Engineer-incharge/Architect.

293.55

-

-

... More
Judo mat of density 220 - 240 of mat size 2mts x 1mt with material of high quality bonded foam 1000 dernier cover of thickness 50mm. Work shall be executed all Complete as per direction of Engineer-incharge/Architect.

155

-

-

... More
Kabbadi mat - Each mat of size 1mt x 1mt made up of Material EVA & JSR of density 130 kg.cum (Tolerence +/- 10%) and hardness of 30 degree (Tolerence +/- 15%) having thickness 40mm. Work shall be executed all Complete as per direction of Engineer-incharge/Architect.

303

-

-

... More
Squash Court Flooring: - Providing & laying Squash Court Wooden Flooring as per following steps a. Polythene Sheet on top of Concrete b. Cushion pads nailed to Pine Wood (10mm) c. Pine wood of 32mm/45mm thick treated placed at 350mm intervals d. Hard Wood .Maple installed over the pine wood (20 mm) should be WSF approved e. Sanding/Grinding to be done on the Hardwood once installed Providing and laying of hard plaster consist of plaster (4 mm), fiber reinforced, cement based and resin modified. Marking lines in red colour and painting with epoxy paint. Approved by WSF. Work shall be executed all Complete as per direction of Engineer-incharge/Architect.

146.26

-

-

... More
Squash Court Glass:- Providing & fixing rear 4 panel glass wall with a door 12mm thick with 15mm fins inclusive of all required accessories & hardwares approved by WSF. Size of Glass wall ( 21 ft. X 7 ft). Work shall be executed all Complete as per direction of Engineer-incharge/Architect.

2

-

-

... More
Squash Hard Plaster:- Providing and laying of hard plaster consist of plaster 4mm thick, fiber reinforced, cement based and resin modified. Marking lines in red colour and painting with epoxy paint. Approved by WSF. Work shall be executed all Complete as per direction of Engineer-incharge/Architect.

200

-

-

... More
Providing & fixing Tin Board approved by WSF. Work shall be executed all Complete as per direction of Engineer-incharge/Architect.

2

-

-

... More
Providing & fixing in position Phenol bonded Bamboowood flooring with planks of sizes 14mm thick, minimum 1800mm length and minimum 100 mm wide, in approved colour, texture and finish, having Performance Appraisal Certificate (PAC) issued by Building Materials & Technology Promotion Council (BMTPC). The flooring shall be fixed with tongue and groove interlocking system, with underlayment of 4mm thick expanded polyethylene foam sheets having density 40kg/cum, over prepared surface with necessary quarter round planks of size 1900mm x 18mm and door reducer of size 1900mm x 44mm, wherever required. The bamboowood planks shall have minimum density of 1000 Kg/cum & minimum Hardness 1000 Kgf. with Eco friendly UV coating, all complete as per direction of the Engineer in-charge.

150

-

-

... More
Providing & fixing in position Phenol bonded Bamboowood wall cladding at all height with planks of sizes 10mm thick, minimum 1800mm length and minimum 100 mm wide, in approved colour, texture and finish, having Performance Appraisal Certificate (PAC) issued by Building Materials & Technology Promotion Council (BMTPC), with necesasary profiled edges fixed with 40mm SS screws 5 nos in each tile to frame work made of second class teak wood of size 20x15 mm in centre of each tile and bottom and top of work height, 40x15mm placed at ends of each tile. The cladding shall be laid over backlayment of 1.00 mm thick expanded polyethylene foam of density 40kg/cum in two layers, first layer on wall surface before fixing wooden frame and second layer on frame under cladding. The bamboowood planks shall have minimum density of 1000 Kg/cum & minimum Hardness 1000 Kgf. with Eco friendly UV coating, all complete as per direction of the Engineer in-charge.

75

-

-

... More
Providing and laying 9100 Terra Z web Heavy Duty matt made of flexible vinyl (Virgin PVC) open mesh structure. The open mesh structure allows water to run through the matting so the surface stays drier than the surrounding area. Suitable for high Foot traffic application overall provide comfortable walking surface which scrap, trap & stop being enter in to a building. Z Element Gap Minimum Avg is 11 +/-1mm/1 Waves. Mass per sq mtrs Minimum Avg is 7800 gm. With Z Web Waves design. Total Thickness Minimum Avg is 10.8 mm (ASTM 3767 with precondition at 60 degree Temperature for 2 hour and COOL IT measure at 25 degree Temperature). Anti Skid Minimum Avg is Yes dry 0.91 and wet 0.57 Product should be certified from NFSI (National Floor Safety Institute) for anti skid properties Flexible Z Web Waves material. Must qualify for Partial LEEDs points and come along with authorisation certificate from 3M India. As per the direction of Engineer-In-Charge

15

-

-

... More
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm center to center, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm center to center, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm center to center, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm center, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes, finishing with jointing compound in 3 layers covering up to 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer-in-charge but excluding the cost of painting with :12.5 mm thick tapered edge gypsum plain board conforming to IS: 2095- (Part I) :2011 (Board with BIS certification marks) As per the direction of Engineer-In-Charge

470

-

-

... More
Extra over & above the respective items of gypsum board ceiling for cove up to a width of 750 mm. As per the direction of Engineer-In-Charge

100

-

-

... More
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm center to center, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm center to center, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm center to center, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm center, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes, finishing with jointing compound in 3 layers covering up to 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer-in-charge but excluding the cost of painting with :Fully Perforated Gypsum Plaster Board of size 1200 x 2400x12.5 mm having approx. 15 % perforated area with perforation size and pattern as approved by the Engineer- in-charge and as per manufacturer's specification, with all 4 side tapered and backed by acoustical tissue with NRC value not less than 0.60

200

-

-

... More
Calcium Silicate Board Ceiling Providing & fixing false ceiling at all height including providing & fixing of framework made of special section, power pressed from M.S. sheets and galvanised with zinc coating of 120 gms/ m2 (both side inclusive) as per IS : 277 and consisting of angle cleat of size 25mm wide x 1.6mm thick with flanges of 27mm and 37mm, at 1200mm c/c, one flange fixed to the ceiling with dash fastener 12.5mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25 x10 x0.50mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I chanels 45 x15 x 0.90mm running at the spacing of 1200 mm c/c, to which the ceiling section 0.5mm thick bottom wedge of 80mm with tapered flanges of 26 mm each having lips of 10.5mm, at 450mm c/c, shall be fixed in 'a direction perpendicular to As per the direction of Engineer-In-Charge

750

-

-

... More
Providing & Fixing of Integral Densified Tegular/Butt edged Eco Friendly Lightweight Calcium Silicate Suspended Ceiling System in Module Size of 600x600x15mm with Exposed GI Plain T24 Grid for Offices, Hospitals, Institutions, Airports, Banking Sector, Auditoriums, Community halls, laboratories, Factories and All buildings in high humidity or coastal Areas. The Eco Friendly Lightweight Calcium Silicate Ceiling tiles shall be made from Non Cementitious Hydrated Calcium Silicate Slurry/ Mixture, Reinforced recycled material with fibers and natural fillers. Free from Formaldehyde and other harmful materials. Doesn't contain any toxic ingredients.The Tiles should have Humidity Resistance (RH) of 100%, Water Resistance, Non Combustible: as per BS:476 Part-4, Fire Performance: as per BS:476 Part-6 for Fire Propagation, as per BS:476 Part-7 for Surface Spread of Flame, As per UK standards Fire Performace A1-S1-d0, Thermal Conductivity K= 0.048 to 0.050 w/m K as per ECBC code 2007, NRC (Noise Reductions Coefficient) 0.5 to 0.75 (Semi Perforated & Fully Perforated Tiles) as per IS 8225:1987, Sound Attenuation (STA) 30-32dB,Thickness of tile should be 15mm thick with 450 kg/m3 density all around on edge resting portion with Integral Densified edge and 10mm thick with 350 kg/m3 density in the center of the body, Light Reflectance 85%, Weight of material is 5-5.5 kg/m2 and Suitable for Green Building application with InOrganic Recycled content of 46- 50% out of which 18-20% should be FLYASH and meets the GRIHA & SVAGRIHA norms under the categories: GRIHA V.2015 criterion:11&12, GRIHA V.3 criterion: 17&29 and SVAGRIHA criterion:12 The tiles Shall be laid on 24mm Wide T-Sections Flanges colour white having rotary stitching on all T sections i.e. the Main runner with a web height of 38mm and 1200mm & 600mm Cross Tees with a web height of 32mm having thickness of 0.33mm and Wall angle of 24*24mm with 0.4 mm thickness , having load carrying capacity of 15 kg/m2. The T sections should have Galvanizing of 120 grams per m2 and need to be installed with Suspension system. As per the direction of Engineer-In-Charge

937

-

-

... More
Providing & Fixing of Mineral Fibre Acoustical Suspended Ceiling System in module size of 600 x 600 x 16mm with Exposed Grid for Hospitals, Shopping malls, Commercial establishments and office complexes. The tiles should have Humidity Resistance (RH) of 99%, NRC 0.5, Light Reflectance o87%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Colour White, Fire Performance UK Class 0 I Class 1 (BS 476 pt- 6 &7) and suitable for Green Building application with Recycled content of 30%. The tile shall be laid on 24 mm wide T - section flanges colour white having rotary stitching on all T sections i.e. the Main Runner, 1200 mm & 600 mm Cross Tees with a web height of 38mm and a load carrying capacity of 15 kg/m2 &pull out strength of minimum 100 kg The T Sections should have a Galvanizing of 90 grams per m2 and need to be installed with Suspension system. As per the direction of Engineer-In-Charge

282

-

-

... More
Providing & fixing Hinge able open cell ceiling with cell size of 100mm made out of 0.3mm thick coil coated GMS. The assembled cell ceiling panels shall be in size of 600x1200 made out of blades in 9mm (W) x 40mm (H). The assembled cell ceiling panels are then clipped into type-1 U shaped carriers in GMS, coated in black enamelled finished at 1200mm c/c. Wire clips shall hold the cell ceiling panels into the type-1 U shaped carriers. Once the type-1 U shaped carriers are installed then primary angles made out of GMS, type-2 U are cross connected to the type-1 U carriers at 1200mm c/c. for lateral bracing The whole ceiling shall be suspended by M6 threaded rods installed 1200mm c.c. All panel modules must be hinge able through wire clips. The panels are fully downward demountable / hinged from the proprietary type-1 U carrier section using spring panels. The system should be in accordance with Material class as per the Direction of the Engineer-in-charge. The system will meet fire retardant standards of BS 476: Part 6 & Part 7 tolerance. Finish: As per approved shade.

2506

-

-

... More
Providing & fixing 75 mm Hinge able open cell ceiling with cell size of 75mm made out of 0.3mm thick coil coated GMS. The assembled cell ceiling panels shall be in size of 600x1200 made out of blades in 9mm (W) x 40mm (H). The assembled cell ceiling panels are then clipped into type-1 U shaped carriers in GMS, coated in black enamelled finished at 1200mm c/c. Wire clips shall hold the cell ceiling panels into the type-1 U shaped carriers. Once the type-1 U shaped carriers are installed then primary angles made out of GMS, type-2 U are cross connected to the type-1 U carriers at 1200mm c/c. for lateral bracing The whole ceiling shall be suspended by M6 threaded rods installed 1200mm c.c. All panel modules must be hinge able through wire clips. The panels are fully downward demountable / hinged from the proprietary type-1 U carrier section using spring panels. The system should be in accordance with Material class as per the Direction of the Engineer-in-charge. The system will meet fire retardant standards of BS 476: Part 6 & Part 7 tolerance. Finish: As per approved shade.

408

-

-

... More
Acoutical Ceiling Supply and Installation of Acoustical ceiling, Square edge, magnesite-bonded pinewood fibre core, factory prepainted, fully encapsulated with texture finish,GreenPro certified, ceiling tile of size 600x2400x20mm/600x1200x20mm, volume density 400Kgs/m3, weight 8kg/m2 which is installed by using non-visible fasteners using suitable Strut & Fasteners. Acoustical ceiling framework system shall include Type-1 Strut, fully knurled, sectional thickness 0.55mm, length 3600mm, unequal flanges of 20 & 30mm and web of 25mm, fixed along the perimeters of the wall with nylon sleeves and suitable fasteners at every 300mm centers.Then suspend Type-2 Strut, fully knurled, sectional thickness 0.8mm, length 3600mm, equal flanges of 15mm and web 45mm from the soffit at 1200mm centers fastened to the Strut perpendicularly at 600mm centers. Strut having sectional thickness 2mm and length 2400mm to be fixed perpendicular to the Strut Cross Channel at 600mm centers. The system is backlined with the acoustical infill Anutone Synth PF 10x50 Technical Parameters • Fire (Class) – 1 & P • Acoustics – NRC 0.91 (For 50mm thk E250* Mounting) • Thermal conductivity (W/mk)– 0.09 • Climate (°C, RH) – 50, 91 • Light reflectance (%) – 76 • Green (VOC, RC %) – Low, 30 As per the direction of Engineer-In-Charge

50

-

-

... More
Acoustical Baffle Panels Providing & insallation of Acoustical Baffle of size 1200 length, thickness 40 mm with drop height 200/300 as options. Easily demountable. Manufactured from high density glass wool , with finished surface on both the sides. Edges are straight cut and painted. Acoustics-Sound absorption - 0.9 at 1000 Hz at 600 mm o.d.s as per EN ISO 354:2003 Humidity Resistance -Permanent ambient RH upto 95% at 30 * C without sagging , warping or delaminating. Fire Safety-Tested and classified as non combustible according to EN ISO 1182 with reaction to fire classification. Light Reflectance - 85% light reflectance Indoor Health & Well-being as per Indian standards. Cost is inclusive of hanging arrangement with suitable SS wire with locking arrangement. As per the direction of Engineer-In-Charge

1560

-

-

... More
Acoustical Spray plaster Providing & Proccessing Acoustic Spray Installation using 25mm board + 3mm Plaster: 0.8 NRC in white finish, an inorganic acoustic plaster that is sanded to an ultra-smooth finish to be applied on the ceiling, or any curved and angled walls or any surface with light reflectance 93.3/-0.1% with Class A fire rating, NRC up to 0.80 and Alpha w of 0.80, cradle to cradle silver certified, UV-light resistant as per ISO 18314-1, 2015 and A+ against French VOC regulations. As per the direction of Engineer-In-Charge Acoustic plaster is sprayed directly onto a substrate either glued or mechanically fixed to concrete substrate to a total thickness of 28mm and trowel it nicely. For completely smooth surface sand the entire surface. The Measurement to be considered entire surface area of Horizontal and vertical including beams and pillars." PERFORMANCE CRITERIA A. NRC as high as 0.8 B. Fire testing as per EN 13501-1:2002 + EN 13238:2001: A2-s1,d0 C. Fire testing as per ASTM E84-11a: Class A E. 93% Light Reflectance as per ISO 18314-1, 2015: 83 F. VOC (0.014 mg/m2h) 0,02 g/L as per the M1 Protocol for Chemical and Sensory Testing of Building Materials as per IS. G. Internal stress as per ASTM D6991-17: 1.8 Mpa H. Resistance to Mold: Meets ASTM D3273-16 mold specification requirements. I. Resistance to UV-light exposure as per ASTM G 154-16 & ISO 18314-1, 2015: No visible changes after 1000 hours J. Determination of resistance to humidity as per DS/EN ISO 6270-2, 2005, 40°C (104.00°F)/95%RH: No visible changes K. Cradle to Cradle version 3.1: Must have achieved the Cradle to Cradle version 3.1 certification on Silver Level. (LEED CERTIFICATION) L. EPD Certified (Environment product declaration)

720

-

-

... More
Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length. Second class teak wood. As per the direction of Engineer-In-Charge

2.8

-

-

... More
Providing and fixing flush door shutter made out of solid core block board type, well seasoned , chemicaly treated hard wood battens and internal frame with minimum 45 mm wide wooden frame alround door shutters covered with cross bonded wooden sheets (core veneer) hot pressed and fastened on both sides of the door useing liquid phenol formaldehyde resin as per IS specifications 2202 (part-I) 1991. from manufacturer complete as per spcification. As per the direction of Engineer-In-Charge 40 mm thick both side commercial

53

-

-

... More
Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured). As per the direction of Engineer-In-Charge

53

-

-

... More
Extra for providing rectangular/ square vision panel not exceeding 0.1 sqm in all type of flush doors (cost of glass excluded) (overall area of door shutter to be measured): As per the direction of Engineer-In-Charge

10

-

-

... More
Extra if louvers (not exceeding 0.2 sqm) are provided in flush door shutters (overall area of door shutters to be measured). As per the direction of Engineer-In-Charge

53

-

-

... More
Providing & fixing 1mm thick decorative high pressure laminated sheet of plain / wood grain in gloss / matt/ suede finish with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality. As per the direction of Engineer-In-Charge

106

-

-

... More
Providing & fixing 1mm thick SS Kick Plate as per design & drawing. As per the direction of Engineer-In-Charge

13

-

-

... More
Providing and fixing IS : 12817 marked stainless steel butt hinges 125x64x1.90mm with stainless steel screws etc. complete As per the direction of Engineer-In-Charge

84

-

-

... More
Providing and fixing SS hanging floor single rubber door stopper. As per the direction of Engineer-In-Charge

21

-

-

... More
Providing and fixing SS Tower Bolt 300mm As per the direction of Engineer-In-Charge

21

-

-

... More
Providing and fixing SS Handle 125mm As per the direction of Engineer-In-Charge

21

-

-

... More
Providing and fixing Mortise cylinder lock case, 55mm backset, 72mm center distance, 24mm square forend, SS matt double cylinder, 40+40 = 80mm, non-master keyed, matt nickel hollow and SS lever handle with cylinder escutcheon. Complete in all respect as per the direction of the Engineer-in-charge.

21

-

-

... More
Providing and fixing Alumninum channel arrangement for sliding door with all required accessories. As per the direction of Engineer-In-Charge

21

-

-

... More
Providing and fixing of Aluminium Z Louvre Casement Door on Hinge with suitable outer frame. The fixing shall be done in masonary / RCC by drilling holes inserting PVC sleeve and stainless steel counter-sunk screws of appropriate size, anchoring in the masonary. The periphery of frame shall be sealed by application of weather sealant with backer rod of colour as approved, both outside and inside between aluminium member and masonary/ RCC. The fabrication shall be done with joints mitred. including providing masking tape on the profile for safety against external scratches (masking tape to be removed only at the time of hand over). As per the direction of Engineer-In-Charge

191

-

-

... More
Insulated Fire rated doorset FD 120 with 30 minutes insulation Double Leaf doorset - Insulated Fire rated doorset (FD 120) - Staircase / exit pathway application / Refuge area. Providing and fixing of ISI marked fire doors as per IS 3614:2021, 120 minutes fire rating with 30 minutes insulation double leaf doorset tested to IS/ISO 3008. Doorset shall include grooved step frame profile of 125x75mm, made of 1.2mm GI (120GSM) and 60mm thick shutter made of 1.2mm GI (120GSM) with infill of 120kg density mineral wool. Grooved frame shall include EPDM smoke seal. Include hardwares, minimum 6nos SS ball bearing hinges of SS304 100x89x3mm, 1no of Single point Panic device and external trim with key cylinder on active leaf and 1no two point Panic device on the inactive leaf, tested as per EN1125 and CE marked. 2no of Door closer with spring size of EN 3-5, as per EN1154 and CE marked. 1no door coordinator for sequencing. 2nos vision panel 200 x 300 with 6mm clear fire rated glass and finished in desired colour of powder coating not less than 50microns including suitable anchors & fire rated puff grouting all inclusive for fixing of doorset - for staircase / exit pathway / Refuge area applications. As per the direction of Engineer-In-Charge

212

-

-

... More
General Steel Doors Single leaf door - General steel doors Providing and fixing of single leaf hollow metal steel door. Doorset shall include grooved frame profile of 125x55mm made of 1.2mm GI conforming to IS 277 (120GSM) and 46mm thick shutter made of 1.2mm GI (120GSM) with infill of honeycomb core. Grooved frame shall include PVC smoke seal.Vision lite should be minimum 5mm toughned glass on shutter, Include hardwares, 3Nos SS ball bearing hinges of SS304 of size 100x75x3mm, 1no mortise dead lock, 55mm BS, 20 mm2 forend, including escutheion, sss with euro profile cylinder both side key, 1pair Pull handle D type, 22dia, CTC 300mm, back to back, with spindle, SS 304, SSS finish. 1nos of Door closer with spring size of EN 2-4, as per EN1154. vision panel 150 x 750 with 5mm clear glass and finished in desired colour of powder coating not less than 50microns including suitable anchors & puff grouting all inclusive for fixing of doorset - for all utility and all general application. As per the direction of Engineer-In-Charge

73

-

-

... More
Double leaf door - General Steel doors Providing and fixing of double leaf hollow metal steel door. Doorset shall include grooved frame profile of 125x55mm made of 1.2mm GI conforming to IS 277 (120GSM) and 46mm thick shutter made of 1.2mm GI (120GSM) with infill of honeycomb core. Grooved frame shall include PVC smoke seal.Vision lite should be minimum 5mm toughned glass on shutter, Include hardwares, 6Nos SS ball bearing hinges of SS304 grade of size 100x75x3mm, 1no mortise dead lock, 55mm BS, 20mm sq. forend, including escutheion, sss with both side key cylinder on active leaf, 2pairs Pull handle D type, 22dia, CTC 300mm, back to back, with spindle, SS 304, SSS finish. 2nos of Door closer with spring size of EN 2-4, as per EN1154. 2nos flush bolt on the inactive leaf, 1no dust proof socket. 2Nos vision panel 150 x 750 with 5mm clear glass and finished in desired colour of powder coating not less than 50microns including suitable anchors & puff grouting all inclusive for fixing of doorset - for all utility and all general application. As per the direction of Engineer-In-Charge

542

-

-

... More
Insulated Galzed fire door - Double leaf Providing and fixing of double leaf insulated glazed fire door as per IS 16947 for integrity (E/EW 120) & Insulation (EI 30). Glazed door shall be tested to IS/ISO 834-1, IS/ISO 3009-1 for integrity & insulation (E/ EW 120). Glazed door shall be tested from CBRI for maximum rating of 120min, Door frames and partitions shall be single rebate frame profile of size 125 x 60mm made out of 1.60mm GI (120GSM). Door leaf shall be fully glazed with minimum 60 x 100mm profile step box section for taking glass elements. Door leaf shall be manufactured from 1.2mm GI (120GSM). For doors and partitions, beeding shall be minimum 1.2 mm GI with 25mm height, with screws 6 x 19mm. The infill material shall be mineral wool 96kg density. The glass shall be fire rated, ultra clear, interlayered minimum 13mm thick, for (E) 120 minutes integrity & (EI 30) 30minutes insulation with light transmission of minimum 89% as per EN1363 and EN1364. Glass shall have a impact resistance of 1B1 as per EN 12600 and sound insulation of 37db including ceramic tape. Cost of single leaf doorset shall include following hardware and accessories as a complete assembly, 6nos SS ball bearing hinges of SS304 grade of size 100x75x3mm, 1no Fire rated mortise dead lock, 55mm BS, 20mm sq. forend, including escutheion, sss as per EN 12209 with both side key cylinder on active leaf, 2pairs Pull handle D type, 22dia, CTC 300mm, back to back, with spindle, SS 304, SSS finish. 2nos of Door closer with spring size of EN 2-4, as per EN1154 and CE marked. 2nos flush bolt on the inactive leaf, 1no dust proof socket. Suitable anchor fastners for fixing on different type of wall construction as per manufacturer recommendation. All doors and frames shall be finished Pure Polyster Powder coated and shall have passed minimum 500 hours of salt sprey test. Once frame installed should be filled with PUF as recomended by the manufacturer or engineer. As per the direction of Engineer-In-Charge

116

-

-

... More
Providing & fixing Toilet Cubicle ( Bottom Colsed with Skirting) of following standard dimension which includes 600mm door size width made of heat, bacteria, water, chemical, scratch and impact resistant 12mm thick solid compact laminate panels including doors, pilasters & intermediate panels finished with approved texture/shade as per the detail drawings & as per IS 2046 (Indian Standard) and as per fire retardant BS-476/97 standard. The product should have Green Guard Certificate. This also includes providing and fixing in position necessary hardware made out of Stainless steel (Grade 304) as per manufacturer’s specifications & Engineer-in-charge's instructions like (1) Door Knob, (2) Gravity Hinges, (3) Thumb turn lockset with Occupancy indicators, (4) Coat hooks with Door stopper (5) U- Channels, (6) Adjustable foot/pedestal, (7) Top rail with Corner connector (8) Rubber noise deafening tape, (9) Screws & wall Plugs. The top fitting should consist of SS round top rail which will get fixed with pilasters, with SS panel tube holder, SS corner bend (connected with top rail) will be used on the corner of cubicle in absence of brick wall, SS wall fixing is used only on the wall which will hold the ss top rail. All screws will of 304 Grade in stainless steel with satin finish. All pilasters are supported by stainless steel Bottom Cladding.Toilet Cubicle with dimension as drawing, which includes 600mm door size width. As per the direction of Engineer-In-Charge

175

-

-

... More
Accoustic door Providing and fixing of Medium duty accoustic door as per IS 16074 & IS 4351 made of pressed galvanized steel confirming to IS 277 with the following specification. Door shall be suitable for 39db, STC rating and manufcatured in ISO 9001: 2015 certfied company for quality management. Door frame shall be single rebate step grooved profile of size 125 x 75mm made out of 1.60mm (16gauge) minimum thick galvanized steel sheet. Frames shall be mitered and field assembled with self tabs. Frames to have inbuild grooved sealing system and shall be site fitted with PVC gasket as standard. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Permimeter seal of approved make Athmer/Legancy to be provided on all three sides of the frame jamb. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Frames shall be filled with puff. Door leaf shall be 60mm thick step design fully flush double skin door, insulated without vision lite. Door leaf shall be manufactured from 1.2mm (18guage) minimum thick galvanised steel sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware. The infill material shall be 120kg/sq.mt. high density rockwool/mineral wool material. All doors shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The edges should be interlocked with a bending radius of 1.4mm. For pair of doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. Door shall be equiped with additional seals like auto door bottom All doors and frames shall be finished Pure Polyster Powder coated and shall have passed minimum 500 hours of salt sprey test. Rate shall include supply and installation of frame, shutter as a complete assembly, hardware & accessories. As per the direction of Engineer-In-Charge

26

-

-

... More
Reception Table:- (Size L:- 3000mm x W:- 750mm x H:- 1050mm & 750mm) Providing, making & fixing two level (1050mm & 750mm) Reception Table made out of 19 mm thick water proof ply structure. Granite stone to be pasted on top and vertical face as per drawing with resin hardener adhesive over 19+19mm thick waterproof ply base. Table consists of drawer unit, storage pedestal, CPU trolly and keyboard tray as per drawing. The keyboard tray and drawer shall run on powder coated M.S. channels. All other surfaces shall be finished with 1.5 mm palstic laminate. As per the direction of Engineer-In-Charge

1

-

-

... More
Reception Back Drop (L:-5890mm x H:-3050mm) Providing, making & fixing 200mm thick reception back drop with Signage, logo, Green plant wall made over the MS structure as detailed in drawing. Cost is inclusive of all accessories & lighting fixtures to illuminate the reception back drop. Provision of lighting arrangement will be paid in relevant head. As per the direction of Engineer-In-Charge

1

-

-

... More
Supply and Installation of Blockout fabric made up of 100% Polyester with Acrylic coated of 0.32mm (PVC free) of thickness 0.50mm ±5% and wieghing 270-295gsm with openess factor of 0%. Shrinkage % Warp0.5 & Weft 0.5,Color fastness5-6. The Roller blind system consists of 38mm OD extruded out of Aluminium alloy with silver anodized to provide an everlasting finish and luster, the rotary unit shall be 36mm in OD incorporating a clutch mechanism composed of low – flexing braided polyster cord with nylon core, Control Ball chain shall be composed of braided nylon cord with high engineering grade plastic beads mounted co-axially on the cord. Bottom rail should be powder coated Aluminium flat bottom rail of 290 gm to finish it from the ends it should have rail end caps. The clutch will be at the tube. The return end cap bracket shall incorporate snap spring design to facilitate easy installation and removal for maintenance activities. The bracket shall be finished with a flush mounting cover on each side providing an aesthetic finish. It should handle up to 5 Kgs of material. The clutch should mount flush to the face of the bracket which minimize the light gap between the shade and the window frame. As per the direction of Engineer-In-Charge

1030

-

-

... More
Providing and supplying aluminium extruded tubular and other aluminium sections as per the architectural drawings and approved drawings of Chief Architect, GoK.The aluminium quality shall be as per grade 6063 T5 or T6 as per BS 1474,including super durable powder coating of 60-80 microns conforming to AAMA 2604 of required colour and shade as approved by the Engineer-in-Charge. ( The item includes cost of material such as cleats, sleeves, screws etc. necessary for fabrication of extruded aluminium frame work. Nothing extra shall be paid on this account).The weight of aluminium extruded section shall be taken for purpose of payment. As per the direction of Engineer-In-Charge

19572

-

-

... More
SEMI UNITIZED STRUCTURAL GLAZING Designing, fabricating, testing, protection, installing and fixing in position semi (grid) unitized system of structural glazing (with open joints) for linear as well as curvilinear portions of the building for all heights and all levels, including:(a) Structural analysis & design and preparation of shop drawings for the specified design loads conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind pressure without any failure), including functional design of the aluminum sections for fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather silicone sealants, flashings, fire stop (barrier)-cum-smoke seals, microwave cured EPDM gaskets for water tightness, pressure equalisation & drainage and protection against fire hazard including:(b) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect verticality and fixing structural glazing system rigidly to the RCC/ masonry/structural steel framework of building structure using stainless steel anchor fasteners/ bolts, nylon seperator to prevent bimetallic contacts with nuts and washers etc. of stainless steel grade 316, of the required capacity and in required numbers. (c) Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone sealant compatible with the structural silicone sealant of required bite size in a clean and controlled factory / work shop environment, including double sided spacer tape, setting blocks and backer rod, all of approved grade, brand and manufacture, as per the approved sealant design, within and all around the perimeter for holding glass.(d)Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes, shapes and profiles, as required as per the site conditions, to seal the gap between the building structure and all its interfaces with curtain glazing to make it watertight. (e) Making provision for drainage of moisture/ water that enters the curtain glazing system to make it watertight, by incorporating principles of pressure equalization, providing suitable gutter profiles at bottom (if required), making necessary holes of required sizes and of required numbers etc. complete. This item includes cost of all inputs of designing, labour for fabricating and installation of aluminium grid, installation of glazed units, T&P, scaffolding and other incidental charges including wastages etc., enabling temporary structures and services, cranes or cradles etc. as described above and as specified. The item includes the cost of getting all the structural and functional design including shop drawings checked by a structural designer, dully approved by Engineer-incharge. The item also includes the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working structural glazing as specified, cleaning and protection till the handing over of the building for occupation. In the end, the Contractor shall provide a water tight structural glazing having all the performance characteristics etc. all complete as required, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer- in-Charge. Note:- 1. The cost of providing extruded aluminium frames, shadow boxes, extruded aluminium section capping for fixing in the grooves of the curtain glazing and vermin proof stainless steel wire mesh shall be paid for separately under relevant items under this sub- head. However, for the purpose of payment, only the actual area of structural glazing (including width of grooves) on the external face shall be measured in m2 . up to two decimal places. Note:-2. The following performance test are to be conducted on structural glazing system if area of structural glazing exceeds 2500 m2 from the certified laboratories accreditated by NABL(National Accreditation Board for Testing and Calibration Laboratories), Department of Science & Technologies, India. Cost of testing is payable separately. The NIT approving authority will decide the necessity of testing on the basis of cost of the work, cost of the test and importance of the work. Performance Testing of Structural glazing system Tests to be conducted in the NABL accredited lab or by any other accreditation body which operates in accordance with ISO / IEC 17011 and accredits labs as per ISO/ IEC 17025. 1. Performance Laboratory Test for Air Leakage Test (-50pa to - 300pa) & (+50pa to +300pa) as per ASTM E-283-04 testing method for a range of testing limit 1 to 200 mVhr 2. Static Water Penetration Test. (50pa to 1500p) as per ASTME- 331- 09 testing method for a range up to 2000 ml. 3. Dynamic Water Penetration (50pa to 1500pa) as per AAMA 501.01- 05 testing method for a range upto 2000 ml 4. Structural Performance Deflection and deformation by static air pressure test (1.5 times design wind pressure without any failure) as per ASTME-330-10 testing method for a range upto 50 mm 5. Seismic Movement Test (upto 30 mm) as per AAMA 501.4-09 testing method for Qualitative test, Tests to be conducted on site. 6. Onsite Test for Water Leakage for a pressure range 50 kpa to 240 kpa (35psi) upto 2000 ml

1631

-

-

... More
INFILL MATERIAL IN SEMI UNITIZED STRUCTURAL GLAZING Providing, assembling and supplying vision glass panels (IGUs) comprising of hermetically-sealed 6-12- 6 mm insulated glass (double glazed) vision panel units of size and shape as required and specified, comprising of an outer heat strengthened float glass 6mm thick, of approved colour and shade with reflective soft coating on surface # 2 of approved colour and shade, an inner Heat strengthned clear float glass 6mm thick, spacer tube 12mm wide, dessicants, including primary seal and secondary seal (structural silicone sealant) etc. all complete for the required performances, as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer-in-Charge. The IGUs shall be assembled in the factory/ workshop of the glass processor.(Payment for fixing of IGU Panels in the curtain glazing is included in cost of item No.18.2)For payment, only the actual area of glass on face # 1 of the glass panels (excluding the areas of the grooves and weather silicone sealant) provided and fixed in position, shall be measured in m2.(i)Neutral toughened glass 6mm thick substrate with High performance soft Low-E coating on face # 2, + 12mm Airgap + 6mm Toughened clear Glass of approved make having properties as visible Light transmittance (VLT) of 41%, Light reflection internal 15%, light reflection external 20%, Solar Factor 0.24 SHGC/SF, shading coefficient 0.27 and U value of less than 1.5-1.6 W/m2 degree K, etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement. As per the direction of Engineer-In-Charge

1631

-

-

... More
Aluminum hinge door with Accesson Entrance Design, Fabrication, Supply, installation, protection, cleaning & handover of Aluminum hinge doors . The door shall accomodate 6mm Clear FT glass with Aluminium frame profile with 35 - 40 micron PVDF Finish. The door shall have door closer / floor spring function as directed by PMC. Hold open for exit requirement door shall have possibilitiy of remaining fully open . Door shall have required seals on all four sides of the door to keep the air and water seal requirement . Door shall be from SYSTEM company, of approved brand only. All Material make/ Glass processing plant / coating plant / etc shall be as per Annexure 1 The quote rate shall include all design, engineering & shop drawing approval from architect & consultant. The quote rate shall include all Taxes, duties, statutory obligations and safety code compliance as per PMC.12mm thk. Clear FT Shutter Size : as per requirement As per the direction of Engineer-In-Charge

10

-

-

... More
Patch Fitting Door Design, Fabrication, Supply, installation, Testing (Onsite & Off site), protection, cleaning & handover of Single leaf aluminum frame swing door made with 6mm thick clear float fully tempered glass with Dorma make stainless floor spring. Complete with latch , handle -30mm dia SS handle 1200mm long , Door lock at bottom of each shutter and BTS 75 V 90 deg with EN 1-4 spring capacity floor spring. Floor spring covers shall be SS satin finish. as per Architect's approved shop drawings. Door glass of 6 mm thk clear float fully tempered size as per requirement. Provide SS threshold of 10mm at bottom of door to prevent water entering thru floor level. The door glass shall have brush pile at bottom to act as weather seal. Cost shall be included all design, engineering & shop drawing approval from architect & consultant. The quote rate shall include all Taxes, duties, statutory obligations and safety code compliance as per PMC. As per the direction of Engineer-In-Charge

10

-

-

... More
Providing, fabricating and supplying shadow box of required size and shape, for fixing in the spandrel portion of the structural glazing, in linear as well as curvilinear portions of the building by providing semi -rigid, inorganic, non-combustible fibre glass wool insulation 50 mm thick, conforming to IS: 8183 and BS: 3958 Part 5. The insulation layer shall have facing (factory bonded on surface # 1 of the fibre glass insulationlayer), of black non-woven fibre glass tissue of nominal thickness 0.5 mm and nominal mass not less than 60 g/m2,made of randomly oriented glass fibres distributed in a binder by a wet-lay process including fixing 1.5 mm thick solid aluminum sheet backing using, 6 mm thick cement board including SS rivets, nuts, bolts, washers etc complete. As per the direction of Engineer-In-Charge

84

-

-

... More
Providing and supplying Spandrel Glass Panels comprising of 6 mm thick heat strengthened monolithic float glass of approved colour and shade with reflective soft coating on surface # 2 of approved colour and shade so as to match the colour and shade of the IGUs in the vision panels etc. ,all complete for the required performances as specified, as per the Architectural drawings, as per the approved shop drawings, as specified, and as directed by the Engineer- in- Charge. For payment, only the actual area of glass on face # 1 of the glass panels (but excluding the area of grooves and weather silicone sealant) provided and fixed in position, shall be measured in m2. (Payment for fixing of Spandrel Glass Panels in the curtain glazing is included in cost of relevent Item*).“(i) Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 K etc. . The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement. As per the direction of Engineer-In-Charge

84

-

-

... More
Extra for openable side / top hung vision glass panels (IGUs) including providing and supplying at site all accessories and hardwares for the openable panels as specified and of the approved make such as heavy duty stainless steel friction hinges, min 4 -point cremone locking sets with stainless steel plates, handles, buffers etc. including necessary stainless steel screws/ fasteners, nuts, bolts, washers etc. all complete as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer- in-Charge.

30

-

-

... More
Providing and fixing dry cladding upto 10 metre heights with 30mm thick gang saw cut stone with (machine cut edges) of uniform colour and size upto 1mx1m, fixed to structural steel frame work and/ or with the help of cramps, pins etc. and sealing the joints with approved weather sealant as per Architectural drawing and direction of Engineer-in-charge. (The steel frame work, stainless steel cramps and pins etc. shall be paid for separately).Red sand stone - 30mm thick gang saw cut stone As per the direction of Engineer-In-Charge

2250

-

-

... More
Additional charges for using 30mm thick unpolished Granite of approved Shade. As per the direction of Engineer-In-Charge

2250

-

-

... More
STONE WORK DRY CLADDING Providing and fixing structural steel frame (for dry cladding with 30 mm thick gang saw cut with machine cut edges sand stone) on walls at all heights using M.S. square/ rectangular tube in the required pattern as per architectural drawing, including cost of cutting, bending, welding etc. The frame work shall be fixed to the wall with the help of M.S. brackets/ lugs of angle iron/ flats etc. which shall be welded to the frame and embedded in brick wall with cement concrete block 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 20 mm nominal size) of size 300x230x300 mm, including cost of necessary centering and shuttering and with approved expansion hold fasteners on CC/RCC surface, including drilling necessary holes. Approved cramps/ pins etc. shall be welded to the frame work to support stone cladding, the steel work will be given a priming coat of Zinc primer as approved by the Engineer-in-charge and painted with two or more coats of epoxy paint (Shop drawings shall be submitted by the contractor to the Engineer-in-charge for approval before execution). The frame work shall be fixed in true horizontal & vertical lines/planes. (Only structural steel frame work shall be measured for the purpose of payment, stainless steel cramps shall be paid for separately and nothing extra shall be paid). As per the direction of Engineer-In-Charge

33750

-

-

... More
Providing and fixing adjustable stainless steel cramps of approved quality, required shape and size, adjustable with stainless steel nuts, bolts and washer (total weight not less than 260 gms), for dry stone cladding fixed on frame work at suitable location, including making necessary recesses in stone slab, drilling required holes etc complete as per direction of the Engineer-in-charge.

6750

-

-

... More
GRC Jali:- Design, engineer, furnish, fabricate, package, deliver (to jobsite) and install: facade consisting of GRC at location as shown in elevation, supported on MS substructure , and GRC panels to mimic look of JAALI AS PER DESIGN, custom designed to with stand design wind pressure of 190 kg/sq.mtr confirming to IS -875 part III. (The system must pass the proof test at 1.5 times design wind pressure i.e. 285 kg/sq.mtr without any failure) . The system shall have drainage gutter profile with the possibility of drain container wherever exposed, for weather protection and complete air seal. The facade shall be designed as in architectural intent, supported with structural calculations to ensure stability under deflection . Panels shall be fixed as per design drawings. MS substructure to be designed as per drawing provided (architectural, sectional and detailed) . Intent to be maintained- the grid consistes of vertical members CHS 105 mm 2.5mm thick and interspersed by RHS 150 2.5 thick RHS at required interval meters, placed at groove intervals such that they are in tune with all the performance requirements. Form an interface between the Main structure through welded joints at roof level and come down to bear the GRC and the glass as per architectural intent.Further the structure shall carry a continous substructure made of MS to carry GRC panels in formation of a ring beam as shown in intent. This floating facade to have all the relevant drainage and water non- infiltration capacities in system inbuild. All extruded Mild steel section/brackets shall comply to IS 2062 Grade A and shall be coated with antirust paint of 275 microns comprising primer of 75 microns and two topcoat epoxy high performance architectural paint (Colour as per architect intent) of 100 microns each after shot blasting as per BS standards. The fastening materials like Anchors, Nuts, Bolts, Rivets, washers, clamps, straps etc required for fixing the framing members to the mild steel structure shall be of stainless steel 316 grade and corrosion resistant of approved make as per Architects/Consultants Specification. Provide exterior perimeter sealants where GRC cladding systems abutt adjacent materials including, but not limited to concrete shear walls, slab on grade and penetrations for ancillary equipment and accessories. he quote rate shall include all design, engineering & shop drawing approval FOR GRC JAALI AS DETAILED ABOVE from architect & consultant. The quote rate shall include all Taxes, duties, statutory obligations and safety code compliance as per PMC.(wt-06) As per the direction of Engineer-In-Charge

518

-

-

... More
Expanded Metal Mesh Jali Providing & fixing pwoder coated expanded metal mesh (Grid remains same while skin shall be matal exoanded mesh with eyelets as per approved by Architect and thickness of metal shall be 2.0mm) in place of jaali as detailed above from architect & consultant. The quote rate shall include all Taxes, duties, statutory obligations and safety code compliance as per PMC.(wt-02) As per the direction of Engineer-In-Charge

196

-

-

... More
Extruded Fin System Complete unitised system as mentioned Below Design, Supply and Install Extruded aluminum coated fin system custom designed to with stand the design wind pressure of 190 kg/sq.mtr confirming to IS -875 part III. (The system must pass the proof test at 1.5 times design wind pressure i.e.285 kg/sq.mtr without any failure) , Bracketing system with MS hot dip galvanized bracket system designed to accommodate three dimensional movements with serrations in bracket and washers, SS 316 grade fasteners and anchor bolts of approved make, nylon separators to prevent bi-metallic contacts, 2.0 mm thk aluminium trims and flashings to seal the gaps between curtain wall and the building structure all complete required to perform as per specification and drawing in conjunction with BOQ. The system design shall be based on system and design that shall include MS horizontal load bearing coated member running continously at the slab periphery, and the fins installed with custom brackets on and below . The system shall incorporate details required to fix top flashing as shown in perspective with termination detail. The system shall be designed considering surface temperatures of 80-90 deg Cel and temperature differential of 25 deg cel without creating excess stress in the system. The system shall be designed of floor height units spanning between the floors with slab/steel mounted bracket with provision to accommodate movement at all floor levels and at every grid panels horizontally. The system performance test shall be mandatory to verify the design performance meeting the requirement as per technical specification including all material tests. The price shall be seperately shown in the BOQ. The design to accommodate building movements, thermal expansions and the seismic movementsshould have performaning air seal and water seal alongwith fulfilling windload serviceability requirement . Performance Requirements: 1. Wind Loads: Completed system shall withstand wind pressure loads normal to wall plane indicated above. 2. Deflection: Maximum allowable deflection in any member when tested in accordance with AAMA Specifications for Aluminum Structures. a. For spans up to and including 4.1m deflection shall be limited to L/175. b. For spans greater than 4.1m, but less than12.2m, deflection shall be limited to L/175 or L/240 + 1/4” (6.4mm). MS horizontal load bearing coated member running continously at the slab periphery, grouted / fastened into slab face surface .Bracketing system designed to accommodate three dimensional movements with serrations in bracket and serrated washers, SS 316 grade fasteners and anchor bolts of approved make, nylon separators to prevent bi-metallic contacts, mechanism to be able to maintain line and level . The extruded aluminium sections of Alloy 6063 T5 / T6 and tolerances confirming to DIN standard from approved extruder. The structual profiles shall have minimum 2.5mm wall thickness. All the external visible surfaces shall have minimum 35 microns PVDF finish in solid color or as per architect approval. The non visible aluminium surfaces shall have minimum chromatizing treatment. Termination / interface of curtainwall façade with civil surface shall be treated with 2.0 mm thk aluminium trims and flashings to seal the gaps between curtain wall and the building structure all complete required to perform as per specification and drawing in conjunction with BOQ. The colour will follow the same as that with the fin members . All flashings to be in two layers (one with non metallic membrane ) and have movement capacities to accomodate building movements and thermal expansion without gaps.The floor closure shall be provided continuously at beam top level with 1mm thk GI flashing closing gap between curtain wall and building line. Mock-up installation as per the sequence specified above shall be carried till system finally passes . The performance criteria for the system shall be as per the guidelines laid down in the tender specification or as suggested by the façade consultant for the project. The Mock-up width of the sample shall be not less than of three typical adjoining wall panels/units. The height of the sample shall be not less than 2 storey high and must contain full height modules of thefin system. The std. performance test shall be : • Structural test at 50% and 100% of inward design pressure (or) structural performance @50% and 100% Design wind pressure – As per ASTM E 330-10. • Structural test at 50% and 100% of outward design pressure (or) Structural performance @50% and 100% Design wind pressure –As per ASTM E 330-10. • Structural test at 150% of inward design pressure(or) Structural performance @ 1.5 X Design wind pressure at two directions – As per ASTM E 330-10. • Structural test at 150% of outward design pressure Structural performance @ 1.5 X Design wind pressure at two directions – As per ASTM E 330-10. Cost shall be inclusive to carry out all of the above mentioned test sequence including the complete mock up fabrication,transportation, installation cost. Also visit of 4 persons i.e client representative, architect and consultant to witness the test shall be included in the quote rate. As per the direction of Engineer-In-Charge

1567

-

-

... More
POWDER COATED SHEET BENT FIN system: (4.8M WIDTH) Including FINS for glazing mentioned Below Design, Supply and Install Extruded aluminum coated fin system custom designed to with stand the design wind pressure of 190 kg/sq.mtr confirming to IS -875 part III. (The system must pass the proof test at 1.5 times design wind pressure i.e.285 kg/sq.mtr without any failure) , Bracketing system with MS hot dip galvanized bracket system designed to accommodate three dimensional movements with serrations in bracket and washers, SS 316 grade fasteners and anchor bolts of approved make, nylon separators to prevent bi-metallic contacts, 2.0 mm thk aluminium trims and flashings to seal the gaps between curtain wall and the building structure all complete required to perform as per specification and drawing in conjunction with BOQ. The system design shall be based on system and design that shall include MS horizontal load bearing coated member running continously at the slab periphery, and the fins installed with custom brackets on and below . The system shall incorporate details required to fix top flashing as shown in perspective with termination detail. The system shall be designed considering surface temperatures of 80-90 deg Cel and temperature differential of 25 deg cel without creating excess stress in the system. The system shall be designed of floor height units spanning between the floors with slab/steel mounted bracket with provision to accommodate movement at all floor levels and at every grid panels horizontally. The system performance test shall be mandatory to verify the design performance meeting the requirement as per technical specification including all material tests. The price shall be seperately shown in the BOQ. The design to accommodate building movements, thermal expansions and the seismic movementsshould have performaning air seal and water seal alongwith fulfilling windload serviceability requirement . Performance Requirements: 1. Wind Loads: Completed system shall withstand wind pressure loads normal to wall plane indicated above. 2. Deflection: Maximum allowable deflection in any member when tested in accordance with AAMA Specifications for Aluminum Structures. a. For spans up to and including 4.1m deflection shall be limited to L/175. b. For spans greater than 4.1m, but less than12.2m, deflection shall be limited to L/175 or L/240 + 1/4” (6.4mm). MS horizontal load bearing coated member running continously at the slab periphery, grouted / fastened into slab face surface .Bracketing system designed to accommodate three dimensional movements with serrations in bracket and serrated washers, SS 316 grade fasteners and anchor bolts of approved make, nylon separators to prevent bi-metallic contacts, mechanism to be able to maintain line and level . The extruded aluminium sections of Alloy 6063 T5 / T6 and tolerances confirming to DIN standard from approved extruder. The structual profiles shall have minimum 2.5mm wall thickness. All the external visible surfaces shall have minimum 35 microns PVDF finish in solid color or as per architect approval. The non visible aluminium surfaces shall have minimum chromatizing treatment. Termination / interface of curtainwall façade with civil surface shall be treated with 2.0 mm thk aluminium trims and flashings to seal the gaps between curtain wall and the building structure all complete required to perform as per specification and drawing in conjunction with BOQ. The colour will follow the same as that with the fin members . All flashings to be in two layers (one with non metallic membrane ) and have movement capacities to accomodate building movements and thermal expansion without gaps.The floor closure shall be provided continuously at beam top level with 1mm thk GI flashing closing gap between curtain wall and building line. Mock-up installation as per the sequence specified above shall be carried till system finally passes . The performance criteria for the system shall be as per the guidelines laid down in the tender specification or as suggested by the façade consultant for the project. The Mock-up width of the sample shall be not less than of three typical adjoining wall panels/units. The height of the sample shall be not less than 2 storey high and must contain full height modules of thefin system. The std. performance test shall be : • Structural test at 50% and 100% of inward design pressure (or) structural performance @50% and 100% Design wind pressure – As per ASTM E 330-10. • Structural test at 50% and 100% of outward design pressure (or) Structural performance @50% and 100% Design wind pressure –As per ASTM E 330-10. • Structural test at 150% of inward design pressure(or) Structural performance @ 1.5 X Design wind pressure at two directions – As per ASTM E 330-10. • Structural test at 150% of outward design pressure Structural performance @ 1.5 X Design wind pressure at two directions – As per ASTM E 330-10. Cost shall be inclusive to carry out all of the above mentioned test sequence including the complete mock up fabrication,transportation, installation cost. Also visit of 4 persons i.e client representative, architect and consultant to witness the test shall be included in the quote rate. As per the direction of Engineer-In-Charge

342

-

-

... More
Aluminium Louvered System with Plain Panels Providing and fixing Aluminium Louvers with Plain Panel of approved colour consisting of panel 84 mm wide x 16mm deep x 0.6mm thick with round edges panel length upto 5mtrs coil coated on a continuous paint line double baked and roll formed from enameled corrosion Resistance Aluminum Alloy for higher strength and good Roll forming characteristics. Panels shall be clipped at a distance of 69mm to baked enameled Aluminium panel stringer 33mm wide and 65mm deep x 0.95 mm thick in a standard length of 5mtrs made of double baked enameled Aluminium Alloy to hold the panel in a module of 69.4mm centre to centre. The prongs on stringers shall be to accommodate an angle of 24 Degrees between two panels as per enclosed profile details. Stringers shall be fixed at 150 mm from panel ends and at a distance of maximum 900 mm center to center across the panel span. The carrier shall be fixed to a suitable structure by means of rigid fixing details. Cladding manufacturer should have in-house testing lab in India. The manufacturer should have inhouse roll forming machine to achieve the roll formed edges of Panels. All Panels shall be factory made. No site fabrication & cutting of panels is allowed. Paint Finish: -Panel shall be stove enamelled and finished with SDP of the approved colour on the exposed side and the reverse side with epoxy. Louver Panel Color -As approved by Architect/ Engineer-in-charge. Stringer Color - Black

451

-

-

... More
ACP Cladding For Verticle straight portions Providing and fixing of Aluminium composite panel of approved make and colour for wall cladding for Brick/Rcc/stone walls & coloumns/ beams with necessary aluminium frame works at required level made out of 50x25x4mm C section or equivalent. The panel should consist of 3mm thick non-halogenated FR grade mineral based polymer ( 2 hrs fire resistance as per ASTM E119-12 and clause B, S1, do as per ENT 13501-1sandwiched between 0.50 skins thick aluminium sheet making a total panel thickness of 4mm. The surfaces will be finished with PVDF based coating on topsides and service coating on reverse sides would be in polyester paint. The system shall be fixed using GI brackets, aluminium L cleats and stainless steel bolts and nuts complete with spring washer and cap nuts and all other necessary accessories, sealing shall be done with necessary rods etc., complete As per the direction of Engineer-In-Charge

224

-

-

... More
ACP Cladding For Roof & Parapet coping Providing and fixing of Aluminium composite panel of approved make and colour for wall cladding for Brick/Rcc/stone walls & coloumns/ beams with necessary aluminium frame works at required level made out of 50x25x4mm C section or equivalent. The panel should consist of 3mm thick non-halogenated FR grade mineral based polymer ( 2 hrs fire resistance as per ASTM E119-12 and clause B, S1, do as per ENT 13501-1sandwiched between 0.50 skins thick aluminium sheet making a total panel thickness of 4mm. The surfaces will be finished with PVDF based coating on topsides and service coating on reverse sides would be in polyester paint. The system shall be fixed using GI brackets, aluminium L cleats and stainless steel bolts and nuts complete with spring washer and cap nuts and all other necessary accessories, sealing shall be done with necessary rods etc., complete As per the direction of Engineer-In-Charge

1604

-

-

... More
Providing & Installing invisible SS wire grill system. The System Includes Alumninium track channel with 3 or 2 inch spacing with double pad SS 304 bolts. Grill will be developed in Nylon coated marine grade SS316 wire of 2mm thickness (12+1 wire construction). Channel will be fixed with SS anchor faseners for streching the grill. SS316 garde stiffeners will be used for horizontal & verticle intersection as per approved pattern & design. System cost is inclusive of all neccessory arrangements & accessories to fix & develope the SS Grill System. As per the direction of Engineer-In-Charge

350

-

-

... More
Removal of Unserviceable Soil with Disposal upto a suitable distance as directed by the Engineer incharge of work As per the direction of Engineer-In-Charge

900

-

-

... More
Construction of sub-grade and earthen shoulders with approved material obtained from borrow pits with all lifts & leads, transporting to site, spreading, grading to required slope and compacted to meet requirement of table No. 300-2 As per the direction of Engineer-In-Charge

900

-

-

... More
Preparation and surface treatment of formation by removing mud and slurry, watering to the extent needed to maintain the desired moisture content, trimming to the required line, grade, profile and rolling with 8-10 t smooth wheeled roller, complete as per clause 310. As per the direction of Engineer-In-Charge

3000

-

-

... More
Construction of Granular Sub-Base of required grading as per design mixing in a mechanical mix plant at OMC, carriage of mixed Material to work site, spreading in uniform layers with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per clause 401For Grading -I Material As per the direction of Engineer-In-Charge

450

-

-

... More
Construction of Granular Sub-Base of required grading as per design mixing in a mechanical mix plant at OMC, carriage of mixed Material to work site, spreading in uniform layers with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per clause 401 For Grading -II Material As per the direction of Engineer-In-Charge

450

-

-

... More
Providing, laying, spreading and compacting graded stone aggregate to wet mix macadam specification including premixing the Material with water at OMC in mechanical mix plant carriage of mixed Material by tipper to site, laying in uniform layers with paver/grader in sub-base / base course on well prepared surface and compacting with vibratory roller to achieve the desired density. As per the direction of Engineer-In-Charge

300

-

-

... More
Construction of M40 grade un-reinforced, dowel jointed, plain cement concrete pavement over a prepared sub base with Cement @ 315 kg/m3 and GGBS@ 105 kg/m3, coarse and fine aggregate conforming to IS 383:2016, maximum size of coarse aggregate not exceeding 25 mm, mixed in a batching and mixing plant as per approved mix design transported to site, laid with a paver finisher, spread, compacted and finished in a continuous operation including provision of contraction, expansion, construction and longitudinal joints, joint filler, separation membrane, sealant primer, joint sealant, debonding strip, dowel bar, tie rod, admixtures as approved, curing compound, finishing to lines and grades as per drawing As per the direction of Engineer-In-Charge

11

-

-

... More
Filling of Control/Cold joint Groove with Epoxy urethane joint Sealer with suitable backer rod. 4mm x 4mm groove with 6mm dia backer rod. As per the direction of Engineer-In-Charge

30

-

-

... More
Filling of Control/Cold joint Groove with Epoxy urethane joint Sealer with suitable backer rod. 8mm x 8mm groove with 10mm dia backer rod. As per the direction of Engineer-In-Charge

30

-

-

... More
Providing and fixing factory made precast RCC perforated drain covers 100mm thick, having concrete of strength not less than M-35, of required size, reinforced with 8 mm dia 100mm c/c both ways with cross sectional T.M.T. hoop bars, including providing 50 mm dia perforations @ 100 mm c/c, including providing edge binding with M.S. flats of size 50 mm x 1.6 mm complete, all as per direction of Engineer-in-charge.

500

-

-

... More
Providing and laying 60mm thick factory made cement concrete paver block of approved shape and colour of M -30 grade made of C&D waste by block making machine with vibratory compaction laid in required pattern and including over 50mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge.

662

-

-

... More
Providing and laying Machine cut shot blasted granite cobbles (30mm thick) stone flooring in required design and patterns, in linear as well as curvilinear portions. all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge.

600

-

-

... More
Supplying and fixing M15 grade precast cement concrete Kerb stones for Roadway, Sidewalls and gutters fixed with CM 1:3 fixed and finsihed in line as per direction of Engineer in charge. (The cost of PCC shall be paid extra) 300 x 250 x 100 mm Kerb Stone

1000

-

-

... More
Providing & Fixing Precast Saucer Drain as par requirement As per the direction of Engineer-In-Charge

350

-

-

... More
Providing and laying 80mm thick faciory made cement concrete interlocking paver block of M -40 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50mm thick compacted bed of coarse sand, filling the joints with line sand etc. all complete as per the direction of Engineer-in-charge.

1020

-

-

... More
Providing, laying and rolling of bituminous cold mix on prepared base consisting of a mixture of unheated mineral aggregate and emulsified or cutback bitumen, including mixing in a plant of suitable type and capacity, transporting, laying, compacting and finishing to specified grades and levels. Using SS1 bitumen emulsion and 9.5 mm or 13.2 mm size aggregate. As per the direction of Engineer-In-Charge

55

-

-

... More
BUILDING SIGNAGE Providing, Carving and fixing of 3D Black Granite Stone Logo & lettering thickness as per drawing 30 mm ,height 400 mm Cost is inclusive of all neccessory fixture hardware in Stainless steel, Scaffolding etc. , all complete as per direction of Engineer-in-charge & Architect.

1

-

-

... More
STAINLESS STEEL NAME PLATE WITH PICTOGRAM Providing and fixing of Steel Name plate,304 Grade,16 Guage with engraved texts and cutout pictograms .Fixing provision using 3M VHP double sided tape as required. Signage Size 14 "x 14" inch, all complete as per direction of Engineer-in-charge & Architect.

311

-

-

... More
STEEL DIRECTIONAL HANGING SIGNAGE Providing and fixing of Steel directional hanging Signage,304 Grade ,16 Guage with engraved texts and cutout pictograms .Fixing provision SS Wires as required. Signage Size 48 "x 10" inch, all complete as per direction of Engineer-in-charge & Architect.

32

-

-

... More
FLOOR DIRECTORY Providing and fixing of Steel directory wall mounted Signage,304 Grade ,16 Guage with engraved texts and cutout pictograms,directions signs .Fixing provision SS Studs/ 3M VHP Tape as required. Signage Size 14 "x 14" inch all complete as per direction of Engineer-in-charge & Architect.

40

-

-

... More
FIRE EVACUATION MAP / SIGN. Providing and fixing of Clear Acrylic sandwich frame of 3mm & 2mm acrylic with Evacuation Plan Printed on photoluminescent media and inserted between the two frames. Should be fixed on the wall using 4 Screw/ SS studs. Size 12 inch x 17 all complete as per direction of Engineer-in-charge & Architect.

16

-

-

... More
FIRE SAFETY SIGNAGE Providing fabricating and fixing of Steel signage sheet at base with engraved plan Complete including fixing on wall with screws and washerS. all complete as per direction of Engineer-in-charge & Architect.Photoluminescent, Fire Hose Reel - 10"x8"

64

-

-

... More
FIRE SAFETY SIGNAGE Providing fabricating and fixing of Steel signage sheet at base with engraved plan Complete including fixing on wall with screws and washerS. all complete as per direction of Engineer-in-charge & Architect.Photoluminescent, Fire Exit / Escape Sign - 18"x6"

64

-

-

... More
FIRE SAFETY SIGNAGE Providing fabricating and fixing of Steel signage sheet at base with engraved plan Complete including fixing on wall with screws and washerS. all complete as per direction of Engineer-in-charge & Architect.Photoluminescent, Floor Level - 18"x6"

48

-

-

... More
FIRE SAFETY SIGNAGE Providing fabricating and fixing of Steel signage sheet at base with engraved plan Complete including fixing on wall with screws and washerS. all complete as per direction of Engineer-in-charge & Architect. Photoluminescent, Fire Alarm Call Point - 10"x8"

16

-

-

... More
FIRE SAFETY SIGNAGE Providing fabricating and fixing of Steel signage sheet at base with engraved plan Complete including fixing on wall with screws and washerS. all complete as per direction of Engineer-in-charge & Architect.Photoluminescent, Fire do not use lift- 10"x8"

16

-

-

... More
FIRE SAFETY SIGNAGE Providing fabricating and fixing of Steel signage sheet at base with engraved plan Complete including fixing on wall with screws and washerS. all complete as per direction of Engineer-in-charge & Architect.Photoluminescent Signs, Fire Extinguishers - 10"x8"

48

-

-

... More
Demolition of Existing Buildings including disposal of unserviceable materials and crediting of Serviceable materials of Distressed/dilapidated building of RCC Two storey framed structure building with slopped roof at IISc, Bangalore, including upto 1500mm below the ground level completely and allied structures such as walkway, UG sump, walls, Drains,Stone slab Flooring etc., including disposal of building rubbish/malba/similar unserviceable, dismantled or waste materials from the site by mechanical means, including all operation i.e leveling, dressing, loading, transporting, unloading at approved municipal dumping ground for all leads including all lifts involved complete as per direction of Engineer-in-charge.(Bid is exclusive of land below & surrounding of the buildings). (Total Plinth Area = 2860 sqm) As per the direction of Engineer-In-Charge (Amount will be deducted from the bill)

2861

-

-

... More
Barricading Work Hire charges for providing temporary barricading around the site using GI corrugated sheet to a height of 6m. The GI corrugated /plain sheets of 0.35mm thick shall be fixed to the framework made out of 50mm dia MS pipe for vertical strut placed at about 3m center to center with required bracing using 40mm dia MS pipe placed about 2m center to center and fixing diagonal middle braces using 25mm dia MS pipe forming a rigid frame work as per the architectural drawing and direction of Engineer-in-charge. The barricade shall remain in the same location till the completion of the new work construction project. No additional charges shall be paid for the extended period of contract. The rate quoted shall be including cost of conveyance of all required materials to work site, erecting, removing and disposing the same after completion of work, cost of J bolts washers, cement concrete bed 45cm x 45cm x 75cm in CC 1:2:4 and labour charges etc., complete as per direction of Engineer-in-charge. (Note :- One time payment shall be made for providing barricading from start of work till completion of work i/c shifting. The barricading provided shall remain to be the property of the contractor on completion of the work).

3100

-

-

... More
Cleaning/clearing of land Clearing of land by cutting of thick and sparse growth plants(0.25 mt thickness plants and clearing of bushes along with roots( throwing away to 1.5mtr height and 50 mtr far) As per the direction of Engineer-In-Charge

1000

-

-

... More
Planting of trees Digging pits of size 0.75 x 0.75x 0.75m, filling 50% of the pit with top soil and remaining 50% of pit with 1:2:3 proportion of sand (0.035cum) FYM (0.070cum) Red earth (0.105 cum) and planting of well grown tree saplings (excluding cost of plants) Normal soil As per the direction of Engineer-In-Charge

225

-

-

... More
Planting of Shrubs Digging pits of size 0.45 x 0.45 x0.45m filling 50% of the pit with top soil and remaining 50% of pit with1:2:3 proportion of sand (0.007), FYM (0.014cm) red earth (0.021cm) and and planting of well grown tree saplings (excluding cost of plants) Normal soil As per the direction of Engineer-In-Charge

450

-

-

... More
Planting of Creepers Digging pits of size 0.45 x 0.45 x0.45m filling 50% of the pit with top soil and remaining 50% of pit with1:2:3 proportion of sand (0.007), FYM (0.014cm) red earth (0.021cm) and planting of well grown (excluding cost of plants) Normal soil As per the direction of Engineer-In-Charge

150

-

-

... More
Planting of Ground cover plants Digging of 1.0mx1.0mx0.45m area and filling 50% of the area with top soiland remaining 50% area with 1:2:3 proportion of sand (0.0375 cum),FYM (0.075 cum) red earth (0.0112 cum) and planting of well grown saplings/plants (excluding cost of plants) Normal soil As per the direction of Engineer-In-Charge

50

-

-

... More
Rose garden/growing of rose plants Digging pits of 0.6x 0.6 x0.6m size and filling 50% of the pit with top soil and remaining 50% of pit with 1:6:6 proportion of sand (0.008), FYM (0.048cm) red earth (0.048cm), Neem oil cake (200 gram), Bone meal (100gram), Gingali oil (100gram),Suphala (10 gms), Rose mix (5 gms) and other plant protection chemicals and planting of different varieties of rose plants etc. (excluding cost of plants) Normal soil

100

-

-

... More
Growing of Flower beds Digging of 1.0mx1.0mx0.45m area and filling 50% of the area with top soil and remaining 50% area with 1:2:3 proportion of sand (0.0375 cum),FYM (0.075 cum) red earth (0.0112 cum) and planting of well grown saplings/plants (excluding cost of plants) Normal soil

50

-

-

... More
Growing of Flower beds using corms/bulbs (Cana,Tuberose,Gladiolus etc) Digging of 1.0mx1.0mx0.45m area and filling 50% of the area with top soil and remaining 50% area with 1:2:3 proportion of sand (0.0375 cum),FYM (0.075 cum) red earth (0.0112 cum) and planting of corms/bubs/tubers in the following spacing. Cana and tuberose-0.2mx0.3m,gladiolus and others-02mx0.2m((excluding cost of planting materail) Normal soil

100

-

-

... More
Growing of Hedges Digging trench of size 1mx0.30mx0.45m and filling 50% of the trench with top soil and remaining 50% trench with1:2:3 proportion of sand (0.0112), FYM (0.0224cum) red earth (0.0336cum) and planting of well grown plants (excluding cost of plants) Normal soil

500

-

-

... More
Lawn development : SCRAPPING AND REMOVING TOP SOIL :-Scrapping the area by removing 0.15m soil and removing of unwanted plants,grass along with roots.25km initial transport, including lead, lift loading and unloading charges. (1x1x0.15mt) As per the direction of Engineer-In-Charge

150

-

-

... More
Lawn development : 1ST DIGGING:-Digging of the area for developing lawn including removing weeds, debris if any and breaking of clumps, watering etc. (1x1x0.45mt) As per the direction of Engineer-In-Charge

450

-

-

... More
Lawn development : 2ND DIGGING:- Digging of soil by removing grass etc if any and levelling of the soil etc .. (1x1x0.45mt) As per the direction of Engineer-In-Charge

150

-

-

... More
Lawn development : procurement of quality red earth/soil and heap around pit (1x1x0.15mt) As per the direction of Engineer-In-Charge

150

-

-

... More
Lawn development : Supply of inputs such as sand, FYM, Red earth in 1:3:6 ratio.mixing and spreadingthe mixture to 7.50cm thickness wherever required with Red soil As per the direction of Engineer-In-Charge

1000

-

-

... More
Lawn development : Supply of inputs such as sand, FYM, Red earth in 1:3:6 ratio.mixing and spreadingthe mixture to 7.50cm thickness wherever required with Farm Yard manure As per the direction of Engineer-In-Charge

22.5

-

-

... More
Lawn development : Supply of inputs such as sand, FYM, Red earth in 1:3:6 ratio.mixing and spreadingthe mixture to 7.50cm thickness wherever required with Sand As per the direction of Engineer-In-Charge

45

-

-

... More
Supply of Fertiliser Super Phosphate As per the direction of Engineer-In-Charge

250

-

-

... More
Supply of Fertiliser Neem oilcake As per the direction of Engineer-In-Charge

100

-

-

... More
Supply of Fertiliser Bone meal As per the direction of Engineer-In-Charge

100

-

-

... More
Supply of Fertiliser Potash As per the direction of Engineer-In-Charge

250

-

-

... More
Supply of Fertiliser Furadan As per the direction of Engineer-In-Charge

100

-

-

... More
Supply of Fertiliser Ammonium Sulphate As per the direction of Engineer-In-Charge

250

-

-

... More
Supply of Fertiliser Chlorophyriphos As per the direction of Engineer-In-Charge

50

-

-

... More
Designing, providing and installing vector art work (Base rate of Rs. 600 per sqft.) as per approved theme. The artwork shall be printed on 3M Scotchcal IJ40 / IJ220 vinyl with graphic cum UV protective layer 3M matte finish laminate. The approved artwork digitally reproduced using water-based inks certified to have no hazardous air pollutants. Self-adhesive, bubble-free installation to be done on a smooth, dust free putty surface that has a coat of oil-based primer, Printed on Latex technology by Authorised printer only. All complete as per design, drawing and approval of Architect. ( Base Rate Rs. 450 Sft) As per the direction of Engineer-In-Charge

90

-

-

... More
Design, Research & Painting art work over the available external wall surfaces. Art work will be done by exterior grade paints incldues base preperation with suitable exterior grade putty to get even suface. All complete as per the approval of the Architect/ Engineer-in-charge. For Single Height ( Base rate for complete process Rs. 200/ Sft)

396

-

-

... More
Design, Research & Painting art work over the available external wall surfaces. Art work will be done by exterior grade paints incldues base preperation with suitable exterior grade putty to get even suface. All complete as per the approval of the Architect/ Engineer-in-charge. For Additional Height ( Base rate for complete process Rs. 350/ Sft)

240

-

-

... More
Mural Work in Approved Design and pattern with Selected mateial by IISC & Engineer Incharge. (Basic Rate Rs. 2000 per Sft)

40

-

-

... More
Metal Art Work in Façade Supply and fixing of screen panel cladding fixed system manufactured. The Screen panels of maximum sizes say 1000 mm X 2500 mm as per design requirement shall be manufactured from Aluminium material of 2mm thick. Screen panels shall have customized perforation/Pattern/foramtion as per architects design. Combination of perforations to be provided to suite the design Panels. The panels of required length and height shall be fixed to sub structure by means of screen panel guide clamps of 20x43x2mm. Panels shall be bent from all four sides and shall have extended flanges to accommodate clamps. Installer or Client shall provide sub frame made from Aluminium Steel. The Panels shall be fixed to a suitable structure by means of rigid fixing details, taking into account the relevant live loads and a dead load. Installation shall be carried out as per manufacturer recommendation/ as per Direction of Engineer-in-charge. The manufacturer should have inhouse roll forming /Bending machine to achieve the roll formed edges o. All Panels shall be factory made. No site fabrication & cutting of panels is allowed. Dimensional Tolerances: Gauge: The tolerance in thickness is ±0.03 mm Width: The tolerance in the width of the strip is ±0.2 mm. Cost is inclusive of all Substructure required to fix screen facade.

150

-

-

... More
Water Closet Providing and fixing white vitreous china extended wall mounting water closet of size 780x370x690 mm of approved shape including providing & fixing white vitreous china cistern with dual flush fitting, of flushing capacity 3 litre/ 6 litre (adjustable to 4 litre/ 8 litres), including seat cover, and cistern fittings, nuts, bolts and gasket etc complete. As per the direction of Engineer-In-Charge

125

-

-

... More
Health Faucet Providing and fixing of Health faucet with regulator with flexible pipe 1.0 m long, wall hooked complete as required with flow rate of 3.8 LPM complying to Green Building requirements. . As per the direction of Engineer-In-Charge

125

-

-

... More
Bib Cock Providing and fixing of 15 mm dia CP brass bib cock with CP wall flange of approved quality with flow rate of 3.8 LPM complying to Green Building requirements.As per the direction of Engineer-In-Charge

125

-

-

... More
Providing and fixing toilet paper holder : C.P. brass As per the direction of Engineer-In-Charge

125

-

-

... More
Coat Hook Providing and fixing of C.P. brass twin coat hook with PVC rawl plug & C.P. brass screw complete as required.As per the direction of Engineer-In-Charge

125

-

-

... More
Infrared sensor operated urinal Providing and fixing white vitreous china battery based infrared sensor operated urinal of approx. size 610 x 390 x 370 mm having pre & post flushing with water (250 ml & 500 ml consumption), having water inlet from back side, including fixing to wall with suitable brackets all as per manufacturers specification and direction of Engineer-in-charge.

53

-

-

... More
Providing and fixing granite stone slab with table rubbed, edges rounded and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in- charge and finished smooth.

12.89

-

-

... More
Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Wash basin size 630x450 mm with a single 15 mm C.P. brass pillar tap As per the direction of Engineer-In-Charge

127

-

-

... More
Providing and fixing CP Brass 32mm size Bottle Trap of approved quality & make and as per the direction of Engineer-in-charge.

127

-

-

... More
Supply, Receiving, Storing & Fixing of ABS plastic body liquid soap dispenser with push lever assembly complete with soap refill.As per the direction of Engineer-In-Charge

72

-

-

... More
Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.

127

-

-

... More
Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 g.

24

-

-

... More
Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931

280

-

-

... More
Providing and fixing unplasticised PVC connection pipe with brass unions : 45 cm length 15 mm nominal bore

125

-

-

... More
Supply of solid state, no touch operting, fully hygienic hand drier of approved shade with single blower, with time delay, summer & winter control, music while drying, volume ON/OFF controls complete as required.

35

-

-

... More
Providing and fixing of CP Brass Shower Mixer with provision of overhead shower with 115mm long bend pipe, in built spout, spout / shower selector with wall flange complete with all accessories as required and making good the walls wherever required. with flow rate of 6.0 LPM complying to Green Building requirements.

77

-

-

... More
Providing and fixing of CP Brass 115mm long Shower Arm with wall flange and pressure adjustable 100 mm dia Shower Rose complete with all accessories as required and making good the walls wherever required .

77

-

-

... More
Providing & fixing of CP brass soap dish with brackets fixed to wooden cleats with CP brass screws with approved design and make.

77

-

-

... More
Providing and fixing of 600 mm long Nickel Chromium Plated towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour, of approved brand & manufacture complete as per direction of Engineer in Charge.

77

-

-

... More
Providing and fxing of one no. hinged rail 76 cm & 4 nos. of grab bar 60 cm for handicap toilet & Hadicap shower complete as required.

42

-

-

... More
Providing and fixing of Storage type water heater/ Geyser with required accessories like 15 mm CP angle valve on inlet & outlet line, heavy duty reinforced flexible PVC connector for cold water line and flexible CP brass connector with CP checkout for hot water line, CPVC line connection, MS bracket with two coats of enamel paint, anchor fastners etc to hang the units, providing and fixing of 16 A 3 Pin plug of Anchor make, etc complete as required. Make:-Jaquar VERSA VERTICAL or equivalent Capacity 40 Liters

14

-

-

... More
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 15 mm nominal outer dia Pipes

1765

-

-

... More
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 20 mm nominal outer dia Pipes

45

-

-

... More
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 25 mm nominal outer dia Pipes

245

-

-

... More
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall 15 mm dia nominal bore

815

-

-

... More
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall 20 mm dia nominal bore

665

-

-

... More
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall 25 mm dia nominal bore

260

-

-

... More
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall 32 mm dia nominal bore

270

-

-

... More
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall 40 mm dia nominal bore

550

-

-

... More
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall 50 mm dia nominal bore

235

-

-

... More
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall 65 mm nominal bore

180

-

-

... More
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall 80 mm nominal bore

30

-

-

... More
Providing, fixing, jointing and testing in position the following U-PVC pressure threaded Pipes as per ASTM D 1785 Schedule 40 and threaded conforming to IS:554. Cut to required lengths including all necessary fittings and specials such as bends, tees, unions, reducers, flanges and plugs etc. Cost shall be inclusive of excavation, dewatering, backfilling, ramming surrounding the pipe all round with minimum 150 mm thick all round compacted silver sand and providing thrust block. (Pipe shall be provided with anti crossive protective treatment confirming to AWWA C 203 / IS 10221 standard complete as per specification). All work complete as per specification and satisfaction of the Engineer in Charge. (For Municipal / Tanker water supply) 25mm dia

50

-

-

... More
Providing, fixing, jointing and testing in position the following U-PVC pressure threaded Pipes as per ASTM D 1785 Schedule 40 and threaded conforming to IS:554. Cut to required lengths including all necessary fittings and specials such as bends, tees, unions, reducers, flanges and plugs etc. Cost shall be inclusive of excavation, dewatering, backfilling, ramming surrounding the pipe all round with minimum 150 mm thick all round compacted silver sand and providing thrust block. (Pipe shall be provided with anti crossive protective treatment confirming to AWWA C 203 / IS 10221 standard complete as per specification). All work complete as per specification and satisfaction of the Engineer in Charge. (For Municipal / Tanker water supply) 32mm dia

175

-

-

... More
Providing, fixing, jointing and testing in position the following U-PVC pressure threaded Pipes as per ASTM D 1785 Schedule 40 and threaded conforming to IS:554. Cut to required lengths including all necessary fittings and specials such as bends, tees, unions, reducers, flanges and plugs etc. Cost shall be inclusive of excavation, dewatering, backfilling, ramming surrounding the pipe all round with minimum 150 mm thick all round compacted silver sand and providing thrust block. (Pipe shall be provided with anti crossive protective treatment confirming to AWWA C 203 / IS 10221 standard complete as per specification). All work complete as per specification and satisfaction of the Engineer in Charge. (For Municipal / Tanker water supply) 40mm dia

35

-

-

... More
Providing, fixing, jointing and testing in position the following U-PVC pressure threaded Pipes as per ASTM D 1785 Schedule 40 and threaded conforming to IS:554. Cut to required lengths including all necessary fittings and specials such as bends, tees, unions, reducers, flanges and plugs etc. Cost shall be inclusive of excavation, dewatering, backfilling, ramming surrounding the pipe all round with minimum 150 mm thick all round compacted silver sand and providing thrust block. (Pipe shall be provided with anti crossive protective treatment confirming to AWWA C 203 / IS 10221 standard complete as per specification). All work complete as per specification and satisfaction of the Engineer in Charge. (For Municipal / Tanker water supply) 50mm dia

115

-

-

... More
Providing, fixing, jointing and testing in position the following U-PVC pressure threaded Pipes as per ASTM D 1785 Schedule 40 and threaded conforming to IS:554. Cut to required lengths including all necessary fittings and specials such as bends, tees, unions, reducers, flanges and plugs etc. Cost shall be inclusive of excavation, dewatering, backfilling, ramming surrounding the pipe all round with minimum 150 mm thick all round compacted silver sand and providing thrust block. (Pipe shall be provided with anti crossive protective treatment confirming to AWWA C 203 / IS 10221 standard complete as per specification). All work complete as per specification and satisfaction of the Engineer in Charge. (For Municipal / Tanker water supply) 80mm dia

60

-

-

... More
Providing, fixing, jointing and testing in position the following U-PVC pressure threaded Pipes as per ASTM D 1785 Schedule 40 and threaded conforming to IS:554. Cut to required lengths including all necessary fittings and specials such as bends, tees, unions, reducers, flanges and plugs etc. Cost shall be inclusive of excavation, dewatering, backfilling, ramming surrounding the pipe all round with minimum 150 mm thick all round compacted silver sand and providing thrust block. (Pipe shall be provided with anti crossive protective treatment confirming to AWWA C 203 / IS 10221 standard complete as per specification). All work complete as per specification and satisfaction of the Engineer in Charge. (For Municipal / Tanker water supply) 100mm dia

60

-

-

... More
Supply and delivery at site GM (copper alloy) gate valves confirming to Class-I as per IS 778 with latest amendments, 1 No. screwed in bonnet inside screw, rising spring spindle integral seat screwed females ends confirming to IS 554/ 1990 body hydraulically tested 1.5HP seat standard tested 1 HP with IS mark. For 15 mm dia GM (Copper alloy) Gate valves

11

-

-

... More
Supply and delivery at site GM (copper alloy) gate valves confirming to Class-I as per IS 778 with latest amendments, 1 No. screwed in bonnet inside screw, rising spring spindle integral seat screwed females ends confirming to IS 554/ 1990 body hydraulically tested 1.5HP seat standard tested 1 HP with IS mark. For 20 mm dia GM (Copper alloy) Gate valves

27

-

-

... More
Supply and delivery at site GM (copper alloy) gate valves confirming to Class-I as per IS 778 with latest amendments, 1 No. screwed in bonnet inside screw, rising spring spindle integral seat screwed females ends confirming to IS 554/ 1990 body hydraulically tested 1.5HP seat standard tested 1 HP with IS mark. For 25 mm dia GM (Copper alloy) Gate valves

17

-

-

... More
Supply and delivery at site GM (copper alloy) gate valves confirming to Class-I as per IS 778 with latest amendments, 1 No. screwed in bonnet inside screw, rising spring spindle integral seat screwed females ends confirming to IS 554/ 1990 body hydraulically tested 1.5HP seat standard tested 1 HP with IS mark. For 32 mm dia GM (Copper alloy) Gate valves

26

-

-

... More
Supply and delivery at site GM (copper alloy) gate valves confirming to Class-I as per IS 778 with latest amendments, 1 No. screwed in bonnet inside screw, rising spring spindle integral seat screwed females ends confirming to IS 554/ 1990 body hydraulically tested 1.5HP seat standard tested 1 HP with IS mark. For 40 mm dia GM (Copper alloy) Gate valves

6

-

-

... More
Supply and delivery at site GM (copper alloy) gate valves confirming to Class-I as per IS 778 with latest amendments, 1 No. screwed in bonnet inside screw, rising spring spindle integral seat screwed females ends confirming to IS 554/ 1990 body hydraulically tested 1.5HP seat standard tested 1 HP with IS mark. For 50 mm dia GM (Copper alloy) Gate valves

5

-

-

... More
BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water / hot water circulation as specified. 80 mm dia

2

-

-

... More
BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water / hot water circulation as specified. 65 mm dia

1

-

-

... More
Providing and fixing in position of approved quality high pressure rated Gun Metal Float Valve with copper ball float and brass rods of required length suitable for test pressure of not less than 15 Kg/sqcm of the following sizes: 40mm nominal bore

2

-

-

... More
Constructing brick masonry chamber of internal dimension 600x600mm and depth of 600mm (inner dimensions) with modular bricks of CD 75 in cement mortar 1:6, bed concrete 150mm thick with 1:3:6, plastering 12 mm thick with cement mortar 1:4, CC 1:2:4 coping 75mm thk for fixing CI cover & frame etc. excluding the cost of CI frame and cover..

8

-

-

... More
Constructing masonry Chamber 120x120x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) , i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design bricks of class designation 7.5

1

-

-

... More
Providing & fixing Auto Air vent for cold water supply risers, suitable for pressure not less than 15 Kg/Sq.cm. 15 mm dia

17

-

-

... More
Providing & fixing in position 25 mm dia lawn hydrants consisting of 25 mm dia Ball valve, GI nipple and quick release coupling / threaded hose receiver complete as required.

7

-

-

... More
Providing and fixing enclosed type water meter (bulk type) conforming to IS : 2373 and tested by Municipal Board complete with bolts, nuts, rubber insertions etc. (The tail pieces if required will be paid separately) : 100 mm dia nominal bore

1

-

-

... More
Providing & fixing on line turbine type flow meter with preamplifier & microprocessor based electronic flow meter mounted in plumbing plant room electrical control panel with the following features. Monitoring the total flow, Flow rate, high low arm batching and blending etc. Including electrical wiring from preamplifier to microprocessor based flow meter. Complete with all type of Plumbing & Electrical connections, accessories, wiring, conduits & supports complete with all respect. The signal from read out shall be 4-20 m.amps to be received on BAS. 40 mm dia

2

-

-

... More
Providing & fixing on line turbine type flow meter with preamplifier & microprocessor based electronic flow meter mounted in plumbing plant room electrical control panel with the following features. Monitoring the total flow, Flow rate, high low arm batching and blending etc. Including electrical wiring from preamplifier to microprocessor based flow meter. Complete with all type of Plumbing & Electrical connections, accessories, wiring, conduits & supports complete with all respect. The signal from read out shall be 4-20 m.amps to be received on BAS. 50 mm dia

1

-

-

... More
Providing, fixing and effecting connection from Existing Water Supply line including necessary excavation & making good the same including cutting, boring and tapping the Existing line by providing and installing ferrule / Tee connections with necessary fittings as required and making good the same. The rate for this item also includes complete services from the contractor for liasoning works such as filing necessary applications, submission of forms for approval to the municipal authorities, depositing the fees / other amounts as required for getting the premises / installations, inspected and approved and all other formalities required till the water connection is obtained. All the expenses incurred in this regard shall be borne by the Contractor except for the official payments to be made for any security deposit etc which will be reimbursed on production of original voucher.

1

-

-

... More
Providing, jointing and fixing UPVC Soil, Waste & Vent system conforming to IS : 13592 - Type B and UPVC fittings (moulded as well as fabricated) like bends, tees, Y-tees, crosses, boss connections, access pieces, saddle pieces, cleanouts, adaptors for connections to other materials, plugs, reducers, cowls, offsets and other specials. Jointing shall be done with pushfit EPDM ring jointing technique in general. Solvent cement joints may be provided for fittings and specials which are not manufactured with pushfit rubber joints. Pipes may be laid / fixed in sunken floors, under slung from ceiling. The pipes laid in sunken floor shall be encased with 75 mm thick cement concrete (1:2:4) all around. The installation shall be complete in all respects including cutting chases / holes in walls, slabs and making good the same as per specifications. 75 mm dia

190

-

-

... More
Providing, jointing and fixing UPVC Soil, Waste & Vent system conforming to IS : 13592 - Type B and UPVC fittings (moulded as well as fabricated) like bends, tees, Y-tees, crosses, boss connections, access pieces, saddle pieces, cleanouts, adaptors for connections to other materials, plugs, reducers, cowls, offsets and other specials. Jointing shall be done with pushfit EPDM ring jointing technique in general. Solvent cement joints may be provided for fittings and specials which are not manufactured with pushfit rubber joints. Pipes may be laid / fixed in sunken floors, under slung from ceiling. The pipes laid in sunken floor shall be encased with 75 mm thick cement concrete (1:2:4) all around. The installation shall be complete in all respects including cutting chases / holes in walls, slabs and making good the same as per specifications. 110 mm dia

1550

-

-

... More
Providing, fixing, jointing, testing and commissioning PVC (Class III) of pressure rating 6.0 kg/sqcm Rain water downtake pipe conforming to IS:4985 cut to required lengths including all necessary fittings and specials. Fixing at wall/ceiling level supported by galvanized steel clamps & hangers etc. as required for proper seismic loading as per the calculations. Making proper connection with cement solvent joint as per BIS / manufacturer. Cutting chases/holes in floors / walls / slab. All Down take RWP pipe only). 110 mm dia.

235

-

-

... More
Providing, fixing, jointing, testing and commissioning PVC (Class III) of pressure rating 6.0 kg/sqcm Rain water downtake pipe conforming to IS:4985 cut to required lengths including all necessary fittings and specials. Fixing at wall/ceiling level supported by galvanized steel clamps & hangers etc. as required for proper seismic loading as per the calculations. Making proper connection with cement solvent joint as per BIS / manufacturer. Cutting chases/holes in floors / walls / slab. All Down take RWP pipe only). 160 mm dia.

265

-

-

... More
Providing, fixing, jointing, testing and commissioning PVC (Class III) of pressure rating 6.0 kg/sqcm Rain water downtake pipe conforming to IS:4985 cut to required lengths including all necessary fittings and specials. Fixing at wall/ceiling level supported by galvanized steel clamps & hangers etc. as required for proper seismic loading as per the calculations. Making proper connection with cement solvent joint as per BIS / manufacturer. Cutting chases/holes in floors / walls / slab. All Down take RWP pipe only). 210 mm dia.

125

-

-

... More
Providing, fixing, jointing and testing of UPVC Floor Traps formed out of bore 'P' trap with 50 mm water seal, setting in 1:2:4 mix cement concrete block or clamping to the wall or suspending with the ceiling including cutting and making good the walls and floors wherever required. 110 mm inlet and 110 mm outlet.

191

-

-

... More
Providing and fixing floor drain points formed out of 110 x 63 mm PVC dia elbow with suitable extension piece, setting in 1:2:4 mix cement concrete block or clamping to the wall or suspending with the ceiling including cutting and making good the walls and floors wherever required

125

-

-

... More
Providing and fixing EXTENTION PIECE for floor trap, formed out of 110 mm PVC pipe with multiple side inlets formed with saddle pieces, suitable for 32, 40, 50 and 63 mm dia side connections as per standard detail and support through galvanized steel support from slab or set in cement concrete mix 1:2:4 complete as required.

191

-

-

... More
Providing and fixing Heavy class CP grating with Cockroach proof SS strainer of approved design including setting in floor with cement motor to match with floor finish as per architect requirement suitable for waster and Floor drain. Size 127 mm x 127 mm

316

-

-

... More
Providing and fixing cast iron gratings for Rain Water Pipes. 225x225mm

14

-

-

... More
Providing and fixing uPVC clean out plug with opening arrangements for soil / waste pipe and other necessary fittings inlcuding jointing, all complete as per standard detail. For 110 mm dia pipe

78

-

-

... More
Providing and fixing uPVC clean out plug with opening arrangements for soil / waste pipe and other necessary fittings inlcuding jointing, all complete as per standard detail. For 160 mm dia pipe

2

-

-

... More
Providing, fixing, jointing and testing UPVC soil, waste, vent pipework comprising UPVC pipe conforming to IS :4985-1983 and of required class as specified below and fittings (moulded as well as fabricated) like elbows, bends, reducers, threaded tail pieces, caps, suitable elbow with suitable extension piece for drain point and other specials jointing with cement solvent, chasing, cutting and making good the walls & floors pipes laid in floors shall be encased with 40 mm thick concrete all around, complete in all respects including testing of complete installation. 40 mm dia 6 kg/cm2 (Class III )

225

-

-

... More
Providing, fixing, jointing and testing UPVC soil, waste, vent pipework comprising UPVC pipe conforming to IS :4985-1983 and of required class as specified below and fittings (moulded as well as fabricated) like elbows, bends, reducers, threaded tail pieces, caps, suitable elbow with suitable extension piece for drain point and other specials jointing with cement solvent, chasing, cutting and making good the walls & floors pipes laid in floors shall be encased with 40 mm thick concrete all around, complete in all respects including testing of complete installation. 50 mm dia 6 kg/cm2 (Class III )

105

-

-

... More
Providing, fixing, jointing and testing UPVC soil, waste, vent pipework comprising UPVC pipe conforming to IS :4985-1983 and of required class as specified below and fittings (moulded as well as fabricated) like elbows, bends, reducers, threaded tail pieces, caps, suitable elbow with suitable extension piece for drain point and other specials jointing with cement solvent, chasing, cutting and making good the walls & floors pipes laid in floors shall be encased with 40 mm thick concrete all around, complete in all respects including testing of complete installation. 63 mm dia 6 kg/cm2 (Class III )

130

-

-

... More
Providing and fixing floor clean out on soil & waste pipes, with opening arrangements for soil / waste pipe and other necessary fittings inlcuding jointing, to the satisfaction of the Project Manager / Consultants. For 110 mm dia pipe

8

-

-

... More
Supplying, laying and jointing HDPE pipes of specified grade and conforming to IS 4984-2016 with latest ammendments and conveying to work site including loading and unloading at both destinations and rolling and lowering into trenches, laying true to line and jointing of pipes and specials with electrofusion welding, giving hydraulic test as per relevant ISS with all lead and lifts including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excation, testing and commissioning. The rate is exclusive of required specials and fittings wherever necessary like saddle Tee, stub ends, flanged sets, bedns, reducers etc. complete (Contractor will make his own arrangements for procuring water for testing) etc Note: Upto 110mm dia Coil shall be used. For Grade PE80 PN6.0 : HDPE Grade PE80-PN6.0, 90mm dia

235

-

-

... More
Supplying and installation of Class SN8 Double Wall Corrugated HDPE pipe outer wall corrugated and inner wall smooth piping system in accordance with IS 16098 part 2 and conveying to work site and lowering into trenches, laying true to line and level and perfect linking at joints with the help of two “O” rings and a coupler of suitable size, including loading and unloading at both destination and cutting of pipes where ever necessary including jointing with all labour, all lead and lift including encasing the pipe around to a depth of not less than 15 cm with screened soft soil available from the excavated soil. The testing commissioning including necessary hydraulic test to the required pressure as per ISS shall be done the contractor shall have to make his own arrangement for procuring water for testing SN8 Double Wall Corrugated HDPE pipe sizes of 200 mm dia

240

-

-

... More
Supplying and installation of Class SN8 Double Wall Corrugated HDPE pipe outer wall corrugated and inner wall smooth piping system in accordance with IS 16098 part 2 and conveying to work site and lowering into trenches, laying true to line and level and perfect linking at joints with the help of two “O” rings and a coupler of suitable size, including loading and unloading at both destination and cutting of pipes where ever necessary including jointing with all labour, all lead and lift including encasing the pipe around to a depth of not less than 15 cm with screened soft soil available from the excavated soil. The testing commissioning including necessary hydraulic test to the required pressure as per ISS shall be done the contractor shall have to make his own arrangement for procuring water for testing SN8 Double Wall Corrugated HDPE pipe sizes of 250 mm dia

560

-

-

... More
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete as per standard design: 150mm dia SW /RCC pipepipe

240

-

-

... More
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete as per standard design: 250mm dia SW /RCC pipepipe

110

-

-

... More
Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design: 180x150 mm size P type With common burnt clay F.P.S. (non modular) bricks of class designation 7.5

3

-

-

... More
Constructing brick masonry road gully chamber 50x45x60 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast R.C.C. horizontal grating with frame complete as per standard design : With common burnt clay F.P.S. (non modular) bricks of class designation 7.5

1

-

-

... More
Providing, supplying and fixing in position of High density poly ethylene Machinehole of 1200 mm internal diameter for all depths with top opening of 600mm, PE Machinehole chambers shall be on the basis of EN13598- 2:9009 shall meet relevant BIS/ASTM standards and specifications. All chambers shall be of a solid single wall 100mm or greater thickness construction made of 100% virgin PE material without recycling or foam content. All chambers shall come with a prefabricated integrated base with apprpriate benching with a gredient of 1-2%. The Machinehole shall be seated on M10 cement concrete (1:3:6) of 200mm depth. The inlet pipes to be connected with elastomer seal for a flexible connection of pipes according to EN 681-1. The Machinehole shall have straight channel DN 200 with four extra inlets DN 200/160/110, 45o and 90o right and left and drop arrangement if required and Outlet DN 200/160/110 including steps. The Machinehole shall also be designed to receive house connection at shaft level as per requirement. In case the system is made of midular parts then triple safety (three sided lip/element) seal according to standard practices to be used to connect the parts. Machinehole shall have corrossion resistance steps vertical step distance 25 cms in order to safe guard against uplift pressure, Machinehole should have solid horizontal re-inforcement ribs of appropriate thickness and width. These ribs should be stratagically placed at regular intervals all along the outside of the shaft of the Machinehole. During installation, special care must be taken to ensure proper compaction of the excavated earth with proctar density of 95%, below and around the Machinehole, suitably anchored over concrete to take traffic load without settlement. HDPE Machinehole of 1200mm dia and upto 1.0 m height

38

-

-

... More
Supplying and fixing SFRC frame and cover conforming to IS 12592 (part-I)-1988 and IS 12592 (part-II)- 1991 with latest amendment, including cutting slabs to the required size for the opening and fixing the covering C.C. 1:2:4 and C.M. 1:3 plastering 20 mm thick to all exposed faces, curing for 10 days with all lead and lift with appurtenances. complete. Medium Duty

38

-

-

... More
Providing and fixing medium duty circular manhole cover with frame size 525 mm dia, total weight 50 kg complete in all respects. (For overhead tanks)

3

-

-

... More
Providing and fixing medium duty circular manhole cover with frame size 525 mm dia, total weight 116 kg complete in all respects. (For Underground tanks)

4

-

-

... More
Providing and fixing 700mm long puddle flanges fabricated out of 6mm thick M.S. plates along with flanges of suitable size properly fixed in walls and top slabs of (for Underground & overhead tanks). 32mm dia

1

-

-

... More
Providing and fixing 700mm long puddle flanges fabricated out of 6mm thick M.S. plates along with flanges of suitable size properly fixed in walls and top slabs of (for Underground & overhead tanks). 40mm dia

4

-

-

... More
Providing and fixing 700mm long puddle flanges fabricated out of 6mm thick M.S. plates along with flanges of suitable size properly fixed in walls and top slabs of (for Underground & overhead tanks). 50mm dia

4

-

-

... More
Providing and fixing 700mm long puddle flanges fabricated out of 6mm thick M.S. plates along with flanges of suitable size properly fixed in walls and top slabs of (for Underground & overhead tanks). 65mm dia

1

-

-

... More
Providing and fixing 700mm long puddle flanges fabricated out of 6mm thick M.S. plates along with flanges of suitable size properly fixed in walls and top slabs of (for Underground & overhead tanks). 80mm dia

11

-

-

... More
Providing and fixing 700mm long puddle flanges fabricated out of 6mm thick M.S. plates along with flanges of suitable size properly fixed in walls and top slabs of (for Underground & overhead tanks). 100mm dia

13

-

-

... More
Providing and fixing 700mm long puddle flanges fabricated out of 6mm thick M.S. plates along with flanges of suitable size properly fixed in walls and top slabs of (for Underground & overhead tanks). 150mm dia

13

-

-

... More
Providing and fixing 700mm long puddle flanges fabricated out of 6mm thick M.S. plates along with flanges of suitable size properly fixed in walls and top slabs of (for Underground & overhead tanks). 250mm dia

2

-

-

... More
Providing and fixing 80mm dia G.I. vent pipe on Under ground and over head tank inlcuding cost of 2 Nos. 900 bend and painting with enamel paint complete with in all respect.(for underground tanks & overhead tanks).

12

-

-

... More
Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS : 10910, on 12 mm dia steel bar conforming to IS: 1786, having minimum cross section as 23 mmx25 mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture's permanent identification mark to be visible even after fixing, including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design.

54

-

-

... More
Providing & installation of Water cooler with RO system having Capacity to purify water @ 80 liter /hours.

14

-

-

... More
Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required : (a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. (b) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. d) Suitable cement concrete foundation duly plastered with anti vibration pads. 2280 lpm at 88 m Head Note: *The head of the pump is selected in a manner so as to give a minimum 3.5kgf/cm2 pressure at the highest/farthest point.

2

-

-

... More
Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. 2280 lpm at 88 m Head Note: * The head of the pump is selected in a manner so as to give a minimum 3.5kgf/cm2 pressure at the highest/farthest point.

1

-

-

... More
Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520. Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325. M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. 180 lpm at 88 m Head

2

-

-

... More
Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump) (a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. 900 lpm at 35 m Head

1

-

-

... More
Providing, fixing, testing andcommissioning of precharged air vessel (size 450 mm dia & 2000 mm height) for pressurization of hydrant / sprinkler system complete with adequate pressure switches (as per design / requirement) with valves to operate as per operating sequences including 25 mm dia drain valve, air release valve with stop cock on the top, 25 mm dia inlet with isolating valve duly painted from inside and outside complete as required. Note:Contractor shall include in his rates for providing level controllers, pressure switches, wiring, cabling from level controller / pressure switch to panel etc. complete as required to operate the system automatic/manual. Pump shall be protected against running dry.

2

-

-

... More
Providing & fixing dial type (100 mm) pressure gauge with isolation ball valve suitable for working pressure of 250 PSI. Cost shall be inclusive of providing any short pieces, nipples, elbows etc as required.

5

-

-

... More
Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required.

5

-

-

... More
Providing & installing Galvanized Iron Pipe 5.40mm thick @ 21.20 Kg/m, Such as Tees elbows check nuts unions, Flanger, Nipples etc. including cutting welding, Trending fixing on walls, ceiling (Using 41- Tech pipe/M.S.angle supports work includes two coats of metal primer and two coats of Red enamel paint etc. including cost of materials, labour, usage charges of machinery complete as per specifications. Galvanized Iron Pipes 65 mm dia. complete

5

-

-

... More
Providing & installing Galvanized Iron Pipe 5.40mm thick @ 21.20 Kg/m, Such as Tees elbows check nuts unions, Flanger, Nipples etc. including cutting welding, Trending fixing on walls, ceiling (Using 41- Tech pipe/M.S.angle supports work includes two coats of metal primer and two coats of Red enamel paint etc. including cost of materials, labour, usage charges of machinery complete as per specifications. Galvanized Iron Pipes 80 mm dia. complete

7.5

-

-

... More
Providing & installing Galvanized Iron Pipe 5.40mm thick @ 21.20 Kg/m, Such as Tees elbows check nuts unions, Flanger, Nipples etc. including cutting welding, Trending fixing on walls, ceiling (Using 41- Tech pipe/M.S.angle supports work includes two coats of metal primer and two coats of Red enamel paint etc. including cost of materials, labour, usage charges of machinery complete as per specifications. Galvanized Iron Pipes 100 mm dia. complete

7.5

-

-

... More
Providing & installing Galvanized Iron Pipe 5.40mm thick @ 21.20 Kg/m, Such as Tees elbows check nuts unions, Flanger, Nipples etc. including cutting welding, Trending fixing on walls, ceiling (Using 41- Tech pipe/M.S.angle supports work includes two coats of metal primer and two coats of Red enamel paint etc. including cost of materials, labour, usage charges of machinery complete as per specifications. Galvanized Iron Pipes 150 mm dia. complete

10

-

-

... More
Providing & installing Galvanized Iron Pipe 5.40mm thick @ 21.20 Kg/m, Such as Tees elbows check nuts unions, Flanger, Nipples etc. including cutting welding, Trending fixing on walls, ceiling (Using 41- Tech pipe/M.S.angle supports work includes two coats of metal primer and two coats of Red enamel paint etc. including cost of materials, labour, usage charges of machinery complete as per specifications. Galvanized Iron Pipes 200 mm dia. complete

25

-

-

... More
Providing & installing Galvanized Iron Pipe 5.40mm thick @ 21.20 Kg/m, Such as Tees elbows check nuts unions, Flanger, Nipples etc. including cutting welding, Trending fixing on walls, ceiling (Using 41- Tech pipe/M.S.angle supports work includes two coats of metal primer and two coats of Red enamel paint etc. including cost of materials, labour, usage charges of machinery complete as per specifications. 250 NB (IS: 3589, 6.0 mm thick)

25

-

-

... More
Providing & fixing heavy duty double flanged flexicon rubber expansion joint (suitable for system test pressure) of standard length as per manufacturers specs including rubber gaskets, flanges, nuts, bolts and washers complete as required. 150 mm dia

3

-

-

... More
Providing & fixing heavy duty double flanged flexicon rubber expansion joint (suitable for system test pressure) of standard length as per manufacturers specs including rubber gaskets, flanges, nuts, bolts and washers complete as required. 80 mm dia

1

-

-

... More
Providing & fixing heavy duty double flanged flexicon rubber expansion joint (suitable for system test pressure) of standard length as per manufacturers specs including rubber gaskets, flanges, nuts, bolts and washers complete as required. 65 mm dia

2

-

-

... More
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 65 mm dia

2

-

-

... More
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 80 mm dia

5

-

-

... More
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 150 mm dia

9

-

-

... More
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 200 mm dia

4

-

-

... More
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 250 mm dia

4

-

-

... More
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : 65 mm dia

2

-

-

... More
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : 80 mm dia

3

-

-

... More
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : 150 mm dia

3

-

-

... More
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : 200 mm dia

1

-

-

... More
Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. 250mm dia

2

-

-

... More
Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required.

6

-

-

... More
Providing & fixing dial type (100 mm) pressure gauge with isolation ball valve suitable for working pressure of 250 PSI. Cost shall be inclusive of providing any short pieces, nipples, elbows etc as required.

44

-

-

... More
5.40mm thick @ 21.20 Kg/m, Such as Tees elbows check nuts unions, Flanger, Nipples etc. including cutting welding, Trending fixing on walls, ceiling (Using 41- Tech pipe/M.S.angle supports work includes two coats of metal primer and two coats of Red enamel paint etc. including cost of materials, labour, usage charges of machinery complete as per specifications. Galvanized Iron Pipes 25 mm dia. complete

105

-

-

... More
5.40mm thick @ 21.20 Kg/m, Such as Tees elbows check nuts unions, Flanger, Nipples etc. including cutting welding, Trending fixing on walls, ceiling (Using 41- Tech pipe/M.S.angle supports work includes two coats of metal primer and two coats of Red enamel paint etc. including cost of materials, labour, usage charges of machinery complete as per specifications. Galvanized Iron Pipes 80 mm dia. complete

115

-

-

... More
5.40mm thick @ 21.20 Kg/m, Such as Tees elbows check nuts unions, Flanger, Nipples etc. including cutting welding, Trending fixing on walls, ceiling (Using 41- Tech pipe/M.S.angle supports work includes two coats of metal primer and two coats of Red enamel paint etc. including cost of materials, labour, usage charges of machinery complete as per specifications. Galvanized Iron Pipes 100 mm dia. complete

130

-

-

... More
5.40mm thick @ 21.20 Kg/m, Such as Tees elbows check nuts unions, Flanger, Nipples etc. including cutting welding, Trending fixing on walls, ceiling (Using 41- Tech pipe/M.S.angle supports work includes two coats of metal primer and two coats of Red enamel paint etc. including cost of materials, labour, usage charges of machinery complete as per specifications. Galvanized Iron Pipes 150 mm dia. complete

1045

-

-

... More
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 150 mm dia

7

-

-

... More
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : 150 mm dia

7

-

-

... More
Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. 150 mm dia

1

-

-

... More
Providing and fixing tamper switch on butterfly valve / sluice valve / isolation valve for remote mointing of the valve open / close position. The tamper switch shall be provided with potential free contact with 2 No. NONC. The valve shall also be provided with manual lock & chain arrangement.

7

-

-

... More
Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required : Single headed Stainless steel

44

-

-

... More
Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required : Single headed Stainless steel

6

-

-

... More
Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : Stainless Steel (Grade 304)

88

-

-

... More
Providing & fixing controlled percolation fire hose pipe (as per IS:8423) of 63 mm dia and 15 meter length rated for brust pressure of 35.7 Kg/sqcm. The hose shall be tested for flame resistance test in accordance to IS:8423. Hose shall be complete with ISI marked brass male & female coupling (IS:903) bound & riveted to hose pipe with copper rivets & 1.5 mm copper wire (Location : External fire hydrant)

12

-

-

... More
Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 30 m

44

-

-

... More
Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : Stainless Steel (Grade 304)

50

-

-

... More
Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : 2 way-100 mm dia M.S. Pipe

1

-

-

... More
Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : 4 way-150 mm dia M.S. Pipe

2

-

-

... More
Providing and fixing standard firemans axe with heavy rubber handle.

44

-

-

... More
Supplying Installing, testing and commissioning of Hose reel cabin

44

-

-

... More
Providing and fixing heavy duty SS Floor grating with frame of approved design including setting in floor with cement motor to match with floor finish as per architect requirement. (for FHC drain pipe) Size 100 mm x 100 mm

44

-

-

... More
Supplying Installing, testing and commissioning of Hose cabinet made out of 18 gauge M.S.sheet with double glass door with lacing arrangement and painted with two coats of Fire red Enamel paint at outer ise of the Box and two coats of white enamel paint at inner side of the box is to accomodated 2 Nos. of Fire hose box size 20"x24"x10" complete including cost of materials, labour, usage charges of machinery complete as per specifications.

6

-

-

... More
Providing & fixing MS cabinet (to enclose above FB connection and draw out connection) fabricated from 16g MS sheet with full front glass door and locking arrangement duly painted with one coat of primer and two or more coats of synthetic enamel paint of approved make and shade and suitably mounted on a raised masonry platform as required (Approx 0.6m x 0.6m x 0.45m)

3

-

-

... More
Providing laying, testing & commissioning of 'C' class heavy duty GI Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. 100 mm. Dia

10

-

-

... More
Providing laying, testing & commissioning of 'C' class heavy duty GI Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. 150 mm. Dia

15

-

-

... More
Supplying Installing, testing and commissioning of Gun metal AIR RELEASE VALVE SIZE OF 25mm dia including cost of materials, labour, usage charges of machinery complete as per specifications. Complete

2

-

-

... More
5.40mm thick @ 21.20 Kg/m, Such as Tees elbows check nuts unions, Flanger, Nipples etc. including cutting welding, Trending fixing on walls, ceiling (Using 41- Tech pipe/M.S.angle supports work includes two coats of metal primer and two coats of Red enamel paint etc. including cost of materials, labour, usage charges of machinery complete as per specifications. Galvanized Iron Pipes 25 mm dia. complete

5920

-

-

... More
5.40mm thick @ 21.20 Kg/m, Such as Tees elbows check nuts unions, Flanger, Nipples etc. including cutting welding, Trending fixing on walls, ceiling (Using 41- Tech pipe/M.S.angle supports work includes two coats of metal primer and two coats of Red enamel paint etc. including cost of materials, labour, usage charges of machinery complete as per specifications. Galvanized Iron Pipes 32 mm dia. complete

355

-

-

... More
5.40mm thick @ 21.20 Kg/m, Such as Tees elbows check nuts unions, Flanger, Nipples etc. including cutting welding, Trending fixing on walls, ceiling (Using 41- Tech pipe/M.S.angle supports work includes two coats of metal primer and two coats of Red enamel paint etc. including cost of materials, labour, usage charges of machinery complete as per specifications. Galvanized Iron Pipes 40 mm dia. complete

2415

-

-

... More
5.40mm thick @ 21.20 Kg/m, Such as Tees elbows check nuts unions, Flanger, Nipples etc. including cutting welding, Trending fixing on walls, ceiling (Using 41- Tech pipe/M.S.angle supports work includes two coats of metal primer and two coats of Red enamel paint etc. including cost of materials, labour, usage charges of machinery complete as per specifications. Galvanized Iron Pipes 50 mm dia. complete

370

-

-

... More
5.40mm thick @ 21.20 Kg/m, Such as Tees elbows check nuts unions, Flanger, Nipples etc. including cutting welding, Trending fixing on walls, ceiling (Using 41- Tech pipe/M.S.angle supports work includes two coats of metal primer and two coats of Red enamel paint etc. including cost of materials, labour, usage charges of machinery complete as per specifications. Galvanized Iron Pipes 65 mm dia. complete

640

-

-

... More
5.40mm thick @ 21.20 Kg/m, Such as Tees elbows check nuts unions, Flanger, Nipples etc. including cutting welding, Trending fixing on walls, ceiling (Using 41- Tech pipe/M.S.angle supports work includes two coats of metal primer and two coats of Red enamel paint etc. including cost of materials, labour, usage charges of machinery complete as per specifications. Galvanized Iron Pipes 80 mm dia. complete

1345

-

-

... More
5.40mm thick @ 21.20 Kg/m, Such as Tees elbows check nuts unions, Flanger, Nipples etc. including cutting welding, Trending fixing on walls, ceiling (Using 41- Tech pipe/M.S.angle supports work includes two coats of metal primer and two coats of Red enamel paint etc. including cost of materials, labour, usage charges of machinery complete as per specifications. Galvanized Iron Pipes 100 mm dia. complete

775

-

-

... More
5.40mm thick @ 21.20 Kg/m, Such as Tees elbows check nuts unions, Flanger, Nipples etc. including cutting welding, Trending fixing on walls, ceiling (Using 41- Tech pipe/M.S.angle supports work includes two coats of metal primer and two coats of Red enamel paint etc. including cost of materials, labour, usage charges of machinery complete as per specifications. Galvanized Iron Pipes 150 mm dia. complete

815

-

-

... More
Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories : Pendent Sprinkler

2371

-

-

... More
Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories : Upright Sprinkler

2269

-

-

... More
Providing & fixing Flow Switch in following sizes M.S. pipe including connection etc as required. 150mm dia

15

-

-

... More
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 150 mm dia

17

-

-

... More
Providing, fixing, testing & commissioning of installation control valve of cast iron body,brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required : 150mm dia

1

-

-

... More
Providing, installation, testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required.

1250

-

-

... More
Providing and fixing inspectors test assembly complete with test valve, sight glass sectional drain valve, 25mm and 50mm dia medium class (Class B) G.I. pipes conforming to IS:1239 cut to required lengths including threaded fittings,union with corrosion resistant orifice all complete strictly as per drawing.

15

-

-

... More
Supply, installation, testing and commissioning of 4.5Kg CO2 Gas Type Fire Extinugisher, Trolley Mounted, 2 Easy Weight Management used Unused Mechanism, Squeeze Grip, Gross Weight 19.1 Kg. empty Weight 14.6 Kg. Can Height 860MM Diameter 140MM, Discharge Time less than13 Sees, Controllable discharge mechanism, Applicable on Class 8&C Fire, 8 Rating 138, Can Constuctin : Hot spinning/Forging, Valve Construction : Forging & Machining, Internal Coating of Can : Not Applicable, External coating of Can : Spray Painting, Sheet metal thickness : 4.5M M lSI Approved 1Year Warranty. with instalert system with Superior quality EPDM Rubber Hosepipe etc., including cost of materials, labour, usage charges of machinery complete as per specifications. complete

44

-

-

... More
Supply, installation, testing and commissioning of ABC Powder based MAP 50, 6Kg Providing 6kg Fir e Ex tinguisher Mono Ammonium Phos phate Powder 50, Stored Pressure Type, Pressure Gauge, Gross Weight 9.5 Kg, empty weight 3.5 Kg, Can Height 435MM, Diameter 160MM, Discharge Time less than 9 Sees, Controllable discharge mechanism (Squeeze grip with easy snap safety seal), Range minimum 4 meters, applicable on Class A,8,C and electrically started Fire, A Rating 3A, 8 Rating 218, Can construction : Deep drawn & Co., Mig welded, valve Construciton : Forging and Mechining, Internal Coating of Can: Epoxy powder coating, External Coating of Can: Epoxy PoIyster power coating, Sheet metal thickness: 1.60MM, 5 years Warranty with instalert system with Superior quality EPDM Rubber Hosepipe etc., including cost of materials, labour, usage charges of machinery complete as per specifications. complete. IS 15683 Approved, CE Marked

44

-

-

... More
Supply, installation, testing and commissioning of ABC Powder based MAP 50, 9Kg Providing 9kg Fire Extinguisher Mono Ammonium Phosphate Powder 50, Stored Pressure Type, Pressure Gauge, Gross Weight 14.90 Kg, empty weight 5.90 Kg, Can Height 615MM, Diameter 175M M, Discharge Time less than 13Secs, Controllable discharge mechanism (Squeeze grip with easy snap safety seal), Range minimum 4 meters, applicable on Class A,8, C and electrically started Fire, A Rating 4A, 8 Rating 348, Can construction : Deep drawn & Co., Mig welded, valve Construciton : Forging and Mechining, Internal Coating of Can: Epoxy powder coating, External Coating of Can: Epoxy Polyster power coating, Sheet metal thickness: 2.00MM, 5 years Warranty with instalert system with Superior quality EPDM Rubber Hosepipe etc., including cost of materials, labour, usage charges of machinery complete as per specifications. complete IS 15683, CE Marked

2

-

-

... More
Supply, installation, testing and commissioning of Aqueous Film-Forming Foam - 50 Ltr Providing 50 Ltr Fire Extinugisher Aqueous Film-Forming Foam Type, External Cartridge Type, Pressure Gauge, Gross Weight 102kg. empty weight 52kg Can Height 1192MM, Diameter 300 MM, Discharge Time less than 180 Sees, Controllable discharge mechanism (Squeeze grip with easy snap safety seal), Range minimum 10 Meters, applicable on Class A,B,Can Construction; Deep drawn & C02, Mig welded, Valve Construction: Forging & Machining, Internal Coating of Can : Epoxy Powder coating, External Coating of Can : Epoxy Polyster Powder coating, Sheet metal thickness: 4.0MM, 1 Years Warranty with instalert system with Superior quality EPDM Rubber Hosepipe etc., including cost of materials, labour, usage charges of machinery complete as per specifications. complete.

1

-

-

... More
Supply, installation, testing and commissioning of four bucket stand alongwith buckets. Complete

1

-

-

... More
Supply, installation, testing and commissioning of "FIRE EXIT " Autoglow ,fixed on the exit door(SINGLE SIDE)

30

-

-

... More
Supply, installation, testing and commissioning of "EXTINGUISHER Signages" - Autoglow, with suspension chains

44

-

-

... More
Supply, installation, testing and commissioning of "EMERGENCY EXIT "Autoglow, with suspension chains(SINGLE SIDE)

55

-

-

... More
Supply, installation, testing and commissioning of "EMERGENCY EXIT "Autoglow, with suspension chains(DOUBLE SIDE)

21

-

-

... More
Supply, installation, testing and commissioning of "MCP Signages" - Autoglow, with suspension chains

33

-

-

... More
Preparation of drawing and providing, Autoglow Fire escape route map in clear acrylic glass and required glass studs supports etc. Indicating direction, Key plan, contact numbers etc. (The sample of the same need to be presented for approval before execution)…. (Maximum size of the board A2)

16

-

-

... More
Supply & Installation of Nylon net: sides Nets of 50mmx50mm (In Millimeters) Color of nets - green. Size - 50 X 50mm. For Basketball, Cricket, Volleyball All complete as per direction of Engineer-in-charge/Architect.

1209.7

-

-

... More
Supply & Installation of Nylon Nets- Top covered from the top. Color of top net - white. Size - 50 X 50mm All complete as per direction of Engineer-in-charge/Architect.

24674.43

-

-

... More
Supply & Installation of Manual flipping scoreboard with 2 digits from 0 to 30 and 2 digits from 0 to 9, can be used for badminton. All complete as per direction of Engineer-in-charge/Architect.

13

-

-

... More
Supply & Installation of badminton poles and net as per BWF standard. All complete as per direction of Engineer-in-charge/Architect.

10

-

-

... More
Supply & Installation of Volleyball Post, Antenna & Net as per FIVB standard.All complete as per direction of Engineer-in-charge/Architect.

2

-

-

... More
Supply & Installation of Benches for players. All complete as per direction of Engineer-in-charge/Architect.

50

-

-

... More
Supply & Installation of Free standing Volleyball referee stand as per FIVB standard. All complete as per direction of Engineer-in-charge/Architect.

2

-

-

... More
Supply & Installation of Badminton umpire chairs as per BWF standard. All complete as per direction of Engineer-in-charge/Architect.

10

-

-

... More
Supply & Installation of Ball cart as per FIVB standard. All complete as per direction of Engineer-in-charge/Architect.

2

-

-

... More
Supply & Installation of Fixed type basketball post as per FIVB standard. All complete as per direction of Engineer-in-charge/Architect.

2

-

-

... More
Supply & Installation of Indoor multisport scoreboard for Volleyball as per FIVB standard. All complete as per direction of Engineer-in-charge/Architect.

2

-

-

... More
Supply & Installation of Fixed Type wall mounted Stadium PVC Chairs. Complete with all neccessory hardware & accessories. All complete as per direction of Engineer-in-charge/Architect.

400

-

-

... More
Supply & Installation of Cricket Net Nylon net: sides Nets of 50mmx50mm (In Millimeters) Color of nets - green. Size - 50 X 50mm. Cricket Net should cover the all neccessory area as per requirement. All complete as per direction of Engineer-in-charge/Architect.

1

-

-

... More
Supply & Installation of Metal Lockers Size 380mm(W) x 450mm(D) x 1830mm(H). Each with 6 doors. Finished in epoxy polyester powder coated to the thickness of 50 microns. Handle/Label holder shall be Aesthetically appealing Snap fit ABS plastic handle. Ventilation shall be attractive punched pattern. All complete as per direction of Engineer-in-charge/Architect.

350

-

-

... More
SEWAGE TREATMENT PLANT (50 KLD) Design, Engineering, supplying, installation, testing and commissioning of aerobic Sewage Treatment Plant based on MBBR Technology process (with air diffuser system), completely at basement level with total effluent handling capacity of 50 KLD. The Plant shall be complete with a central Electrical Power and Control panel fully pre/site wired and with all power and control cables to all pumps and equipment including all instrumentation, water level controllers and other controls. All the equipment, piping, pumps, blowers and electrical are to be housed in a plant room to be built below grade level. MS (hot dipped galvanized) puddle flange, inlet, outlet, overflow, vent, M.S. cover, drain channel with M.S. gratings, rungs, sump to house pumps will be included. Nature of Effluent : Domestic sewage from Public toilet use and pantry/kitchen waste etc. The rates will include all pumps, piping, valves, controls, reactor and tube settler media, blowers, diffusers, all power and control cables to all pumps and equipment including all instrumentation, water level controllers, electronic type water level indicator, Sight tube and other controls. BASIC DATA ON INFLUENT RAW WASTE WATER Total Suspended Solids (TSS) : 250 - 450 mg/lit, BOD5 : 250 - 400 mg/lit, COD : 500 - 700 mg/lit, pH : 6.0 - 8.5, Oil / Grease : up to 50 mg/lit, Inflow time : 16 HRS, Peak factor : 3 Temperature : Ambient TREATED EFFLUENT WASTE WATER QUALITY As stipulated by State Pollution Control Board (PCB), the treated effluent quality shall be within the following values for various parameters, for both present and future. The treated water quality should be fit for Flushing, Softening (after softening) and Landscaping & Construction purpose – pH : 7 - 8, Total Suspended Solids (TSS) : 10 mg/lit, COD : 50 mg/lit, BOD5 : 10 mg/lit, Oil / Grease : 10 mg/lit, Color : Colorless, Odor : unobjectionable, E.coli : Nil, NH4-N : 5 mg/litN , Total : 10 mg/lit, PO4-P : 2 mg/lit The STP shall be designed based on the attached details and parameters. The capacities of various tanks and pumps are guidelines to the vendor. The contractor has to submit detailed calculations of system and equipment he proposes to install. Taking Approval from pollution board at initial & various other stages of works including preparation of report / drawings as per pollution board requirement, arrangement of raw sewage for testing & commissioning. Contractor shall include the cost of all chemicals consumed during testing & commissioning and the cost of such items of works which are not explicitly mentioned above, but are mandatory to have pollution board approval. (All relevant fee for PCB Approval shall be paid by client). The STP should follow all the concern Indian and local norms. The Contractor shall have to submit detailed GA drawings (Plan & Section), P & I diagram, Electrical SLD, Schematic diagram and Shop drawings of the plant indicating all sleeves etc. for the various component and additional component if so required for the complete working of the STP also indicating all components in plant room required. The drawings will have to submit for approval before start of work.Bypass arrangement shall be provided so that raw sewage transfer pumps can be used to pump out sewage to external sewer line incase of maintenance of STP (Battery Limit = From Raw Sewage Transfer Pumps to up to 2 meters outside from STP unit). Arrangement shall be provided so that balance treated water transfer pumps can be used to pump out to external sewer line on a regular basis. (Battery Limit = From Treated water Transfer Pumps to up to 2 meters outside from STP unit).The scope of work includes design, drawings, coordinating during construction, erection, commissioning, trial run and obtaining test results of completely below ground sewage treatment plant with electrical, mechanical, piping and controls. The work is required to be carried out on a turnkey basis covering a guarantee of satisfactory performance as per the standards laid for a minimum of One year. The contractor will be solely responsible for smooth running of the sewage treatment plant and overall functioning of STP. In case it is found in the later stage that some additional fixtures / equipment are required to be added in order to achieve desired quality, the contractor would be liable to provide without any extra charges. Ventilation of the plant room / tanks including exhaust fans, ducts etc. shall be coordinated with the Ventilation Consultant. Ventilation work shall be carried by ventilation vendor. The STP shall consist of following units but not limited to these unit as may be required by the manufacturer's design to achieve the desired quality parameters in treated effluent. a. Bar Screen chamber with suitable lifting arrangements complete as required. b. Oil / Grease removal chamber complete in all respect. c. Raw sewage Collection cum Equalization tank for housing of submersible sewage lifting pumps. Provision for aeration of sump will be kept with adequate numbers of coarse air bubble air diffusers to avoid any smell and sedimentation problems.d. Anoxic tank with all required inlet, outlet & other necessary provisionse. e. MBBR tanks with air diffusion system and piping complete of adequate capacity. f. Secondary settling tank having hopper bottom, baffle wall, outlet launders with arrangement of lifting sludge from the bottom complete as required. g. Filter Feed Tank with suitable inlets, outlets, drain, overflow facility complete as required. h. Softener Feed Tank with suitable inlets, outlets, drain, overflow facility complete as required. i. Sludge Holding tank with provision of inlet, outlet, drain, overflow, supernatant withdrawal arrangement with provision of air diffusers for aeration. j. Treated water storage tank to collect treated water with inlet, outlet, drain, overflow facility complete. k. UF water storage tank to collect treated water with inlet, outlet, drain, overflow facility complete. l. Plant room drainage sump to collect the waste water from the back washes, drains etc. m. Stairs, Railing, Sheds, Foot rests, Manhole covers, Maintenance Platform, equipment's foundation etc. ELECTRO MECHANICAL WORKS: Supply, installation, testing and commissioning of following electro mechanical works and equipment's - 2 Nos S.S. 304 bar screen having 10 mm opening with suitable lifting arrangements complete as required. 2 Nos S.S. 304 bar screen having 10 mm opening with suitable lifting arrangements complete as required.

2

-

-

... More
Air diffuser system with Twin type rotary air blowers capable of delivering min. 60 cum/hr. of free air at 0.5 kg/cm2 driven through "V" belt or directly coupled through flexible coupling to a TEFC motor of suitable HP Suitable for 415 + 10% volts, 3 phase, 50 cycles A/C supply fine bubble membrane type diffusers complete with valves & air distribution grid complete as required. Qty : 2 Nos (1W+1S)

2

-

-

... More
Non clog type air dispersion system capable of handling required 3-5 cfm of air with oxygen transfer efficiency 3-4% per meter water depth. Air dispersion grid shall be assembled in modular form so that they can be replaced / repaired easily from platform at the top. Air dispersion system shall be provided coarse air bubble type diffusers for raw sewage equalization tank & sludge holding tank and fine bubble type diffusers for MBBR Tanks.

1

-

-

... More
Non clogging type submersible raw sewage pumps for transfer of equalization tank to Anoxic tank capable of handling solids minimum 32/35 mm, in CI casing and impeller, SS shaft, IP 68, Class F / B insulation, mechanical seal complete with all accessories, motor of required capacity, Pressure gauge on delivery line with isolation valve, NRV of resin ball type suitable for sewergae application, level controller,level switch (with wiring) to control the level of sump automatically including bypass line from pump outlet to external sewer line as per site with all valves. (for Bypass connection, battery limit of STP vendor is From Raw Sewage Transfer Pumps to up to 10 meters outside from STP unit). Flow rate : 2.5 cum/hr. at 12 meter head. Qty : 2 Nos (1W+1S).

2

-

-

... More
Non clogging type horizontal centrifugal Sludge transfer / disposal / recirculation pumps capable of handling solids up to 8 mm, having C.I. casing, C.I. impeller, SS shaft, chrome steel shaft sleeve, IP 55, Class B insulation, mechanical seal complete with all accessories, motor of required capacity, Pressure gauge on delivery line with isolation valve, NRV of resin ball type suitable for sewergae application, level controller (with wiring) to control the level of sump automatically. Flow rate : 2 cum/hr. at 10 meter head. Qty : 2 Nos (1W+1S).

2

-

-

... More
Supply, installation, testing & commissioning of Non Clogging type Horizontal Centrifuge Feed Pumps capable of handling 10mm solids having CI Casing, CI Impeller, SS Shaft, Crome Steel Shaft, IP 55 Class B Insulation with Mechnical Seal complete with all accessories, motor of required capacity, pressure gauge on delivery with isolation cock, controller (with wiring). Duty - 1 Cu-m/Hr; 10 Meter Head.

2

-

-

... More
Providing ,fixing testing and commissioning of basket type centrifuge shall have the holding cap of 30 kg dry solid , having MOC of CI casing & base frame and wetted parts in SS304 construction with complete with the electronic motor of suitable KW ,2950 rpm suitable for 451 (± 10%) , 50 Hz operation with centrifuge v-belt pulley , motor v-belt pulley ,1 set of V-belt protection box, rubber buffers with all required spares and fitting complete in all respect Poly Dosing PUMP - 0-6 LPH , & Poly Dosing Tank - 200 L

1

-

-

... More
Providing, fixing, testing and commissioning of single stage, horizontal, centrifugal, 2 pole, 50 HZ, AC, Monoblock pumps (as per IS : 9079) incorporating C.I. casing and frame, stainless steel shaft, bronze / SS impeller, TEFC induction motor directly coupled to the pump, IP44 protection, class B insulated, C.I. body, hydraulically and dynamically balanced to give vibration free operation, with mechanical seal arrangement, fixed on a base plate with suitable vibration eliminator pads complete with PCC foundation, bolts grouted in CC blocks of 1:2:4, suitably rated DOL / star-delta starter fixed inside main electrical panel complete with level controller, necessary wiring, pressure gauge on the delivery side and strainer on suction side, including non-return valve and isolating valves on suction and delivering sides as required, including suction and delivery headers complete in all respects. (i) Filter Feed Pumps - 2 Nos (1W+1S), having discharge : 3 cum/hr. (each) at 30 meter head

2

-

-

... More
Providing, fixing, testing and commissioning of single stage, horizontal, centrifugal, 2 pole, 50 HZ, AC, Monoblock pumps (as per IS : 9079) incorporating C.I. casing and frame, stainless steel shaft, bronze / SS impeller, TEFC induction motor directly coupled to the pump, IP44 protection, class B insulated, C.I. body, hydraulically and dynamically balanced to give vibration free operation, with mechanical seal arrangement, fixed on a base plate with suitable vibration eliminator pads complete with PCC foundation, bolts grouted in CC blocks of 1:2:4, suitably rated DOL / star-delta starter fixed inside main electrical panel complete with level controller, necessary wiring, pressure gauge on the delivery side and strainer on suction side, including non-return valve and isolating valves on suction and delivering sides as required, including suction and delivery headers complete in all respects. (ii) Softener Feed Pumps - 2 Nos (1W+1S), having discharge : 2.6 cum/hr. (each) at 30 meter head

2

-

-

... More
Plant room drainage sump with 2 Nos. submersible dewatering pumps having 18 cum/hr. discharge at 12 meter head in CI casing and impeller, SS shaft, 12 mm min particle size, 50 Hz, 400 volts, IP68, F / B class insulation with float valve / level controller, piping, valves, nerve etc. complete. The outlet pipe from dewatering pumps to be connected to Equalization Tank. In case of excess inflow into the sump, both pumps shall start automatically with magnetic water level controllers, audio, visual & alarm Including all standard accessories for pumps auto On/ Off Lights, dry running protection etc. complete in all respect.

2

-

-

... More
Supply, installation, testing & commissioning of Random Media for attached growth process (MBBR Technology) MOC = PP, Specific Gravity = 0.93 - 0.95, Surface Area = 400 sq.mtr / cum.mtr. (Note : Volumetric check of MBBR Media to be done at site. Also STP Vendor should provide the Test Certificate of MBBR Media.).

3.5

-

-

... More
Supply, installation, testing and commissioning of PVC tube deck settling media to be installed in secondary settling tank. VH-750 mm, Angle of Inclination - 60° slope, Shape - Hexagonal Chevron.

1.5

-

-

... More
Supply, installation & testing and commissioning of vertical floor mounted FRP type Multi Grade filter of suitable size for required flow and head, provided with an inlet distributor. The vessel is provided frontal piping & valves, back wash system & filter media etc. complete with standard fittings like pressure gauge at inlet & outlet, sampling cock,MPV, air vent valve with piping, bolts, nuts & rubber gaskets. Flow rate = 3 M3 / hr at 16 hrs operation, Vessel Dia = 550 mm, HOS = Min. 1600 mm, Filteration rate = 18 M3/M2/Hr, Working pressure = 3.5 Kg/Sq.cm., Test pressure = 5.5 Kg/Sq.cm. Qty. = 1 Set

1

-

-

... More
Supply, installation & testing and commissioning of vertical floor mounted FRP type Activated Carbon filter of suitable size for required flow and head, provided with an inlet distributor. The vessel is provided with frontal piping & valves, back wash system & filter media etc. complete with standard fittings like, pressure gauge at inlet & outlet, sampling cock,MPV, air vent valve with piping, bolts, nuts & rubber gaskets. Flow rate =3 M3 / hr at 16 hrs operation, Vessel Dia = 550 mm, HOS = Min. 1600 mm, Filteration rate = 15 M3/M2/Hr, Working pressure = 3.5 Kg/Sq.cm., Test pressure = 5.5 Kg/Sq.cm., Qty. = 1 Set

1

-

-

... More
Supply, installation, testing & commissioning of water Softening Plant (FRP) comprising HDPE brine tank of 300 liters capacity with brine ejector, MSFRP/SS mixer with plastic pipng complete with fitting like manhole cover, legs, filter pressure gauges, sampling cock, MPV, and brine filtering media and complete charge of cation exchange resin as per specification for the capacity as given below. Flow rate =2.6 M3 / hr at 16 hrs operation, Incoming hardness 345 ppm (approx), Outgoing harness less than 50 ppm, Working pressure 3.0 Kg/Sq cm, Testing pressure 4.5 Kg/Sq cm, OBR- 50 cum, Approx resin =320 ltrs, Diameter 650mm x 1800mm height, Further to be confirmed by vendor calculation.

1

-

-

... More
Supply, Installation of hollow UF Filtration system with fully automatic 90 % recovery.PVDF Membrane area in each module 40 sqm minimum. Cost shall includes all required piping , automatic valves manual basket strainer back wash line with suitable SS screen and other accessories required within the system for automatic operation without harming the UF membrane. Acid ,alkali and hypo dosing with tank and pump with metering. Providing and fixing single/multi stage, monobloc vertical/ horizontal in-line pumps stainless steel, head and base in cast iron, pump shaft and impeller in stainless steel AISI 304, mechanical seal coupled to a TEFC electric motor, 2900 RPM. Each pump should be operate to a curve required by the operating conditions connected to a TEFC induction motor suitable for 400/440 volts, 3 phase 50 cycles A.C. supply having IP 55 protection enclosure, vibration eliminating pads etc. complete with base and frame, nuts and bolts and necessary RCC foundations as per requirement and as per instructions UF Feed Pump - 2 Nos (1W +1S) Capacity : 2.5 cum/hr Head : 30 Mts or as per OEM recommendation backwash Pump - 2Nos (1W +1S) Capacity : 3 cum/hr Head : 30 Mts or as per OEM recommendation Manual Basket Strainer in feed line - 1 No Flow : 2.5 cum/hr Size : 100 micron size MAKE = IMPEL Acid Dosing pumps with mechanical diaphragm with PP pump head including FRP tank of 100 liters. - 1 No Capacity : 20 LPH Head : 35 Mts PUMP TANK Alkali Dosing pumps with mechanical diaphragm with PP pump head including FRP tank of 100 liters. - 1 NoCapacity : 20 LPH Head : 35 Mts TANK Hypo Chlorite dosing pumps with mechanical diaphragm with PP pump head including FRP tank of 200 liters.- 1 No Capacity : 20 LPH Head : 35 Mts TANK Interconnecting Piping and valvingUPVC piping with sch 40 rating and Solenoid/Motorised Vales with actuators as required and compressor to operate the valves. Including water flowmeter of rotameter type diameter :32 mm, flow range 0-5 m3/h .UF unit Skid and Membrane . No. of Membrane shall be atleast 1 nos or as per OEM. OEM to submit all technical details with flux not exceeding 45-50LMH, datasheets, Electrical Panel and P & I with PLC details for review and approval. MS epoxy : Air grid piping-non submergedGI Piping coated (Class 'C') : All non submerged piping before filter feed tank. GI Piping (Class 'C') : All piping after filter feed tank. uPVC (Sch 80) : Pipe for Dewatering Pumps uPVC (Sch 80) : Pipe for By pass line to the first manhole

1

-

-

... More
The various pipe sizes should be selected that the maximum velocity in any pipe should not exceed 1.50 mps. Minimum 65 mm pipe dia is required in individual line of raw sewage transfer pumps and minimum 80 mm uPVC Sch 40 pipe to be considered for each dewatering pumps outlet and common header will be 100 mm dia.

1

-

-

... More
Design, Providing, Fixing of heavy class MS (hot dipped galvanized) puddle flanges as required to be provided of various diameters.

1

-

-

... More
Supply, Installation, testing & commissioning of electro-magnetic type flow meter to be installed at raw sewage pump outlet line. 65 mm dia.

1

-

-

... More
Supply, Installation, testing & commissioning of Bulk Water meter in Flushing, Softneing and Horticulture Feeder Line. 40 mm dia.

1

-

-

... More
Providing, fixing, testing & commissioning of Chlorine dozing pump with 100 lits. HDPE/ FRP solution tank, injection fitting assembly, suction and delivery hose upto the point of injection, capacity 2.5 ml/hr to 7.5 l/h at 3 kg/sq.cm injection pressure, complete in all respects for treated water tank.Dosing pump shall be with powerful variable-speed stepper motor with internal stoke speed control and the turndown ratio of pump shall not below 1:3000. Accuracy of repeatability shall be +/- 1%.Pump shall be compatible to handle the liquid temperature range between -10 °C to 45°C. ,

1

-

-

... More
Supply, installation, testing & commissioning of multi tubes Disinfection system (UV) comprising of U.V Reactor in a close circuit chamber suitable for waste water application. The system should be provided with self cleaning mechanism. Max. operating pressure at 120 psig, electronic ballast type operating frequency 30 kHz - 50 kHz, cabinet safety standard rating IP54, material of treatment chamber SS 316L and uv dosage (uW-sec/cm2) = 60000. Flow rate of 1.5 cum/hr. Qty. = 1 Set

1

-

-

... More
Supply Installation, Testing & Commissioning of Agitator for Anoxic Tank.The Mixer shall be in PP/SS with suitable RPM and power to provide proper agitation in anoxic tank complete in all respect.

1

-

-

... More
Non clogging type horizontal centrifugal Sludge recirculation pumps (between MBBR tank to Anoxic Tank) capable of handling solids upto 8 mm, having C.I. casing, C.I. impeller, SS shaft, chrome steel shaft sleeve, IP 55, Class B insulation, mechanical seal complete with all accessories, motor of required capacity, Pressure gauge on delivery line with isolation cock, level controller (with wiring) to control the level of sump automatically. Flow rate : 10 cum/hour at 10M head. Qty : 2 Nos (1W+1S)

2

-

-

... More
The prefabricated structure for STP shall be constructed of MS FRP plates with necessary supports and base frame. The structure shall be constructed of minimum 5mm vertical plate and 6mm bottom plate. The structure shall be painted internally with epoxy and externally with enamel paint. All tanks shall have manhole cover of 560 dia and Lifting lugs @300 C/c for maintenance purpose. Screen Chamber (Volume- 0.5 KL +free Board)1No Equalization Tank (Volume- 18 KL + free Board)1No Oil and Grease Tank(Volume- 1.25 KL + free Board)1No Anoxic Tank (Volume- 7.5 KL + free Board)1No MBBR cum Aeartion tank ( Volume- 7.5KL + free Board)2Nos. Tube Settler Water Tank (Area 1.6 x1.6 Sqm + height as requied )1No Sludge Holding Tank (Volume- 10 KL + free Board)1No Clear Water Tank (Volume- 5KL + free Board)1No Treated Water Tank (Volume- 5 KL + free Board)1No. Flushing Water Tank/ UF Permeate Tank (Volume- 5 KL + free Board)2No Soft Water Tank (Volume- 10 KL + free Board)2Nos. Foundation for MS tanks and equipments1Lot

1

-

-

... More
ONLINE MONITORING SYSTEM Providing & fixing of online monitoring system comprising of following : Analyzer type : Cabinet type & multiparameter Measuring principal a) COD/BOD/TSS : UV light absorption (scan between 180nm and 800nm) b) pH : External sensor. Measuring range a) COD : 0-1000 mg/l b) BOD : 0-1000 mg/l c) TSS : 0-1000 mg/l d) pH : 0-14 Operating pressure : 0.5 bars | Operating temperature : 0-80°C | Operating flow : 5 LPM | Encloser protection : IP 65 Communication a) RS 485 for communication b) USB Port for USB communication c) Capable of operation on Wifi / Lan based Internet network. Memory : Upto 16 GB with date & time | Display : 8.5" TFT screen 16/9 (LED backlight) [minimum 7"] | Power supply : 10-240 VAC (50-60 Hz) or 24 VDC. Calibration requirement a) Zero calibration : An auto zero is performed at every cleaning cycle b) Span :Factory calibrated Online monitoring system shall include all instrument, fitting & accessories to make the system function. Data transmission to CPCB server - 1st Year Installation Charges Extended Warranty : 12 Months including Comprehensive AMC 3 Years Comprehensive AMC for Online Monitoring System (After Warranty Period) Scope of Spares Covered : (Flow cell, Flow lamp, Electronic card, Sample pumps ) ; Excluding pH SensorData transmission to CPCB server - After 1st Year 4 TB  Hard Disk (Seagate/Eqt Hard Disk) (Including Remote Monitoring Feature) Connectivity  with CPCB Server Per Year

1

-

-

... More
STP Panel Supply, Installation, testing and commissioning of motor control centre shall be fabricated out of 14 gauge CRCA sheet steel in form in 3b formation with reinforcement of suitable size angle iron, channel ‘T’ sections irons and/or flats wherever necessary. Cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before painting as per specifications with 2 coats of red oxide primer and final approved shade of powder coated paint. 2 Nos. earthing terminals shall be provided for 3 phase, 4 wire, 50 Hz supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel before fabrication. Galvanised hardware with zinc passivation shall be used in fabrication of panels. Incoming (1 No.) 200 amps 4P MCCB Thermal magnetic - 1 No. Bus Bars 250 amps TPN, 10 KA, aluminium bus bars with heat shrinkable insulation sleeve. Outgoings as per STP Equipments required - 1 Lot Power & Control Cables - 1 Lot Perforated Type Cable Tray Supply and fixing of factory fabricated MS powder coated Perforated type cable trays with radial bends, reducers, Tee etc. complete with all accessories. As per the involving sizes are required.

1

-

-

... More
Supplying, installing, testing and commissioning of vertical inline type centrifugal pump with SS-304 casing, SS-304 impeller & SS shaft suitable for operation 400/440 volts, 3 phase, 50 Hz, 2900 rpm, TEFC electric motor with efficiency class of min. IE-3 mounted on common channel base plate with coupling guard. Pump shall have pressure gauge with isolation cock, Isolation valve, NRV on delivery line, strainer (with by-pass) at suction which will be paid separately under respective items. Pump shall be provided with mechanical seal, suitable vibration elimination pads of approved design, drain pipe with valve (25 dia). The pump shall be suitable for auto/ manual operation. The installation shall be complete with all necessary ancillaries & accessories including base plate complete as required. It shall be mounted on MS channel common base plate & fixed with suitable bolts grouted in PCC foundation in PCC (1:2:4) type B-1 using 20 mm graded stone aggregate 30 cm above floor level including making connection of inlet & outlet with fittings including nut, bolts, packing etc.Cost for Antivibration arrangement of cushy foot mountings is deemed to be included in this item cost. Vendor to submit proposed pump model with duty curve. The entire work shall be complete as per specifications & as per directions of E-I-C. Flow rate : 1.5 LPS each Head : 65 Mts No. of pumps : 2 (1 Working + 1 Standby) Required for : Domestic water Transfer / Liftting pump

1

-

-

... More
Supplying, installing, testing and commissioning of vertical inline type centrifugal pump with SS-304 casing, SS-304 impeller & SS shaft suitable for operation 400/440 volts, 3 phase, 50 Hz, 2900 rpm, TEFC electric motor with efficiency class of min. IE-3 mounted on common channel base plate with coupling guard. Pump shall have pressure gauge with isolation cock, Isolation valve, NRV on delivery line, strainer (with by-pass) at suction which will be paid separately under respective items. Pump shall be provided with mechanical seal, suitable vibration elimination pads of approved design, drain pipe with valve (25 dia). The pump shall be suitable for auto/ manual operation. The installation shall be complete with all necessary ancillaries & accessories including base plate complete as required. It shall be mounted on MS channel common base plate & fixed with suitable bolts grouted in PCC foundation in PCC (1:2:4) type B-1 using 20 mm graded stone aggregate 30 cm above floor level including making connection of inlet & outlet with fittings including nut, bolts, packing etc.Cost for Antivibration arrangement of cushy foot mountings is deemed to be included in this item cost. Vendor to submit proposed pump model with duty curve. The entire work shall be complete as per specifications & as per directions of E-I-C. Flow rate : 1.5 LPS each Head : 65 Mts No. of pumps : 2 (1 Working + 1 Standby) Required for : Flushing water Transfer / Liftting pump

1

-

-

... More
Supplying, installing, testing and commissioning of vertical inline type centrifugal pump with SS-304 casing, SS-304 impeller & SS shaft suitable for operation 400/440 volts, 3 phase, 50 Hz, 2900 rpm, TEFC electric motor with efficiency class of min. IE-3 mounted on common channel base plate with coupling guard. Pump shall have pressure gauge with isolation cock, Isolation valve, NRV on delivery line, strainer (with by-pass) at suction which will be paid separately under respective items. Pump shall be provided with mechanical seal, suitable vibration elimination pads of approved design, drain pipe with valve (25 dia). The pump shall be suitable for auto/ manual operation. The installation shall be complete with all necessary ancillaries & accessories including base plate complete as required. It shall be mounted on MS channel common base plate & fixed with suitable bolts grouted in PCC foundation in PCC (1:2:4) type B-1 using 20 mm graded stone aggregate 30 cm above floor level including making connection of inlet & outlet with fittings including nut, bolts, packing etc.Cost for Antivibration arrangement of cushy foot mountings is deemed to be included in this item cost. Vendor to submit proposed pump model with duty curve. The entire work shall be complete as per specifications & as per directions of E-I-C. Irrigation water hydropneumatic system as follows: No. of pumps 2 (1 Working + 1 Standby) Water Flow Rate 2.0 LPS each Head 50 MR PM 2900

1

-

-

... More
Submersible Centrifugal Non-clog Drainage Pump Supply, installation, testing and commissioning of continuous duty submersible centrifugal single stage single suction non-clogging drainage mono block pumps with stator frame of cast iron casing, bronze or equivalent non -clogging impeller, high tensile stainless steel shaft complete with 3 phase tottaly water & dust proof motor suitable for operation 400/440 volts, 3 phase, 50 Hz, 2900 rpm, class -F isulation, IP 68 protection as per IS 2147 of electric motor with efficiency class of min. IE-3 (tested for leak proof operation) with all necessary protection and double mechanical seal, gland packed etc. complete with all ancillaries including float type level controllers, float switch, electrical control panels fabricated from 14 gauge CRCA sheet volt meter ammeter with selector switch, TPMCB, 5 VA CL : CTs, phase indicating lamps protected by 2 amp SP MCB, DOL starter of suitable capacity (H.P), necessary wiring, cable alleys, nclusive of all terminations, earthing, interlocking, starter with Automatic float type level controller, providion of high level alarm, sequence timer, potential free contact to starter for connection to BAS, both pumps may run simultaneously at pre determind level. (1Working + 1Standby). The submersible pump shall be protected for dry run operation & with suitable foundation. The pump shall be suitable for auto/ manual operation. Flow rate : 4.0 LPS each Head : 7 Mts Solid Handling : 10 – 12 MM Location : Plumbing & Fire Plant Room No. of pumps : 2 (1 set=1 Working + 1 Standby)

1

-

-

... More
Submersible Centrifugal Non-clog Drainage Pump (Spec same as above) with following requirement:- Flow rate : 4.0 LPS each Head : 7 Mts Solid Handling : 10-12 MM Location : Basement Purpose : Basement Drainage (ramp-1 & 2) No. of pumps : 2 (1 set=1 Working + 1 Standby)

2

-

-

... More
Submersible Centrifugal Non-clog Drainage Pump (Spec same as above) with following requirement:- Flow rate : 4.0 LPS each Head : 7 Mts Solid Handling : 10-12 MM Location : Basement Purpose : Basement Drainage for AHU area No. of pumps : 2 (1 set=1 Working + 1 Standby)

1

-

-

... More
Submersible Centrifugal Non-clog Drainage Pump (Spec same as above) with following requirement:- Flow rate : 15.0 LPS each Flow rate : 4.0 LPS each Head : 10 Mts Solid Handling : 10-12 MM Location : Basement Purpose : Basement Drainage No. of pumps : 2 (1 set=1 Working + 1 Standby)

1

-

-

... More
Supplying, installing, testing and commissioning of annunciation and indication panel with interlocking arrangement complete in accordance to specification with level controller (In Fire Water, Raw Water, Treated Water and Flushing Water Tank : High / Low Level Controller) etc with control cabling from field to MCC as required. The system shall be complete to ensure automatic quotation of pump in accordance to water level in respective tanks.

1

-

-

... More
Providing & fixing level controllers for water pumps to start/stop the pump at set level. Including wiring, cabling from pump to panel & all other accessories as required to operate the system automatically.

6

-

-

... More
Providing & fixing pressure switch for water pumps to start/stop the pump at set pressure. Including wiring, cabling from pump to panel & all other accessories as required to operate the system automatically.

3

-

-

... More
Providing & fixing full way lever operated forged brass ball valve of brass body with forged brass hard chrome-plated steel ball tested to a pressure not less than 15 Kg / sq.cm with threaded / flanged joints complete with nuts, bolts, gaskets, washers etc. 32mm nominal bore

10

-

-

... More
BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating as specified 40 mm dia

10

-

-

... More
BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating as specified 50 mm dia

3

-

-

... More
BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating as specified 65 mm dia

2

-

-

... More
BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating as specified 80 mm dia

2

-

-

... More
Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified. suction). 40 mm dia

2

-

-

... More
Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified. suction). 80 mm dia

1

-

-

... More
Providing & fixing flanged ends CI horizontal lift check valve tested to a pressure of PN-16. Including rubber gasket, flanges, union, nuts, bolts, washers & painting complete as required 32 mm dia

6

-

-

... More
Providing & fixing dual plate CI wafer type check valve tested to a pressure of 15 Kg/sqcm. Including rubber gasket, flanges, union, nuts, bolts, washers & painting complete as required 50 mm dia

2

-

-

... More
Providing and fixing Heavy class GI header complete for pump suction / discharge manifold comprising of flanges, unions, check nuts, expansion bellows, tee elbow and two coat enamel painting,etc. including all flanged connections as per drawing / site requirement. Supports from wall, floor and ceiling etc. Including dead end flanged connection complete as required. The header size shall also include tee connections with blank flanges for the future connections. 32 mm dia

70

-

-

... More
Providing and fixing Heavy class GI header complete for pump suction / discharge manifold comprising of flanges, unions, check nuts, expansion bellows, tee elbow and two coat enamel painting,etc. including all flanged connections as per drawing / site requirement. Supports from wall, floor and ceiling etc. Including dead end flanged connection complete as required. The header size shall also include tee connections with blank flanges for the future connections. 40 mm dia

50

-

-

... More
Providing and fixing Heavy class GI header complete for pump suction / discharge manifold comprising of flanges, unions, check nuts, expansion bellows, tee elbow and two coat enamel painting,etc. including all flanged connections as per drawing / site requirement. Supports from wall, floor and ceiling etc. Including dead end flanged connection complete as required. The header size shall also include tee connections with blank flanges for the future connections. 50 mm dia

10

-

-

... More
Providing and fixing Heavy class GI header complete for pump suction / discharge manifold comprising of flanges, unions, check nuts, expansion bellows, tee elbow and two coat enamel painting,etc. including all flanged connections as per drawing / site requirement. Supports from wall, floor and ceiling etc. Including dead end flanged connection complete as required. The header size shall also include tee connections with blank flanges for the future connections. 65 mm dia

10

-

-

... More
Providing and fixing Heavy class GI header complete for pump suction / discharge manifold comprising of flanges, unions, check nuts, expansion bellows, tee elbow and two coat enamel painting,etc. including all flanged connections as per drawing / site requirement. Supports from wall, floor and ceiling etc. Including dead end flanged connection complete as required. The header size shall also include tee connections with blank flanges for the future connections. 80 mm dia

20

-

-

... More
Providing & fixing heavy duty double flanged flexicon rubber expansion joint (suitable for system test pressure) of standard length as per manufacturers specs including rubber gaskets, flanges, nuts, bolts and washers complete as required. 32 mm dia

6

-

-

... More
Providing & fixing heavy duty double flanged flexicon rubber expansion joint (suitable for system test pressure) of standard length as per manufacturers specs including rubber gaskets, flanges, nuts, bolts and washers complete as required. 40 mm dia

6

-

-

... More
Providing & fixing heavy duty double flanged flexicon rubber expansion joint (suitable for system test pressure) of standard length as per manufacturers specs including rubber gaskets, flanges, nuts, bolts and washers complete as required. 50 mm dia

2

-

-

... More
Providing & fixing heavy duty double flanged flexicon rubber expansion joint (suitable for system test pressure) of standard length as per manufacturers specs including rubber gaskets, flanges, nuts, bolts and washers complete as required. 65 mm dia

2

-

-

... More
Supply, installation, testing and commissioning of sight tube (of 3.5 to 4 m length) with isolation valve at top / bottom, demarcation on tube for making the installation of level indication on the RCC water tank complete.

4

-

-

... More
Providing & fixing Electric control panel to operate a 24 V DC, 50Hz Solenoid to open / close the solenoid valve at low / high water level through level controller in over head water tanks. Including wiring, level controller probes, solenoid valves, float valves & other accessories as required to operate the system automatically.

2

-

-

... More
Providing and fixing electronic type level indicator for water tanks mounting in panel with the following features, level display, alarm when water level is low or high, full range from one level to four level display and manual reset for alarm etc. with electrical wiring conduit supports from wall & ceiling probs and all other accessories complete as required.

4

-

-

... More
Supply, installation, testing and commissioning of the UV unit consisting of reactor, cabinet housing, cabinet cooling, treatment chamber, electrical panel, temperature safety control, lampout alert, UV radiometer along with UV monitoring system and UV monitoring readout panel. The UV Dosage should be 30,000 uW – Sec / sq.cm. The lamps should be selected based upon the flow requirement of respective unit. The unit shall be complete with temperature safety control, lamp out alert circuit & UV radiometer with 4 – 20 mA output.The treatment chamber shall be SS3162 Flowrate : 1.0 LPS

1

-

-

... More
Providing and fixing MS structural work fabricated from structural steel sections M.S. rounds, angles, channels, tees, square bars, plates including cutting to size, drilling, welding fixing and welding to insert plates in RCC structural works, as directed by Architects. M.S. ladders and tank covers & frame etc. cutting and making good the wall and floor where ever required including two coats of synthetic enamel paint / epoxy paint over a coat of primer.

800

-

-

... More
Providing & complete testing kit with all chemicals complete suitable for conducting test on water quality. The test kit shall be suitable to measure TDS, pH, Hardness, Iron content and other parameters

1

-

-

... More
Supply, installation, testing and commissioning of tanker inlet connection complete with 100 mm dia GI (heavy) inlet piping, hose inlet connection, MS cabinet enclosure (epoxy painted after fabriction), pad locking arrangement, inlet flexible hose complete with all necessary arrangement.

1

-

-

... More
LT PANELS & DISTRIBUTION BOARDS MAIN LT PANEL (LT PANEL ROOM) (GROUND FLOOR) Refer Technical Specifications (Section No : __) before quoting

1

-

-

... More
MAIN HVAC PANEL (TERRACE FLOOR) MAIN HVAC PANEL (TERRACE FLOOR) Panel described as Below Incomer comprising of : 630 TPN MCCB with Microprocessor release for over current, short circuit & earth fault protection etc. - 2 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 600/5 15 VA, CL 0.5, 3 No. CTs- 2 Set ON / OFF / TRIP indicating lights with control MCB -2 Set Phase indicating light protected by 2 amps MCB’s - 2 Set. Bus Bar comprising of : 800 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable steeve - 1 set Bus Coupler 630 TPN MCCB with Microprocessor release for over current, short circuit & earth fault protection etc. - 1 Set Outgoing comprising of : 250 TPN MCCB with Microprocessor release for over current, short circuit & earth fault protection etc. - 5 Set 63 amps 4 Pole MPCB - 8 Set 16 amps 4 Pole MPCB - 7 Set Notes:- All Outgoing feeders shall be provided with ON/OFF/TRIP Indications and shall be protected by 2 amps SP MCBs. All breakers shall be minimum 10 kA rating with Icu = Ics. All incoming breakers shall be electrically/ mechanically interlocked. Design, fabrication, assembling, wiring and supply, installation, testing and commissioning of LT Panel, Distribution Panels, fabricated out of (load bearing member of 2mm and non load bearing member 1.6 mm thick) CRCA sheet steel in cubicle compartmentised modular 3b construction, free standing floor mounted with bottom cable entry, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels.

1

-

-

... More
315 kVAR Capacitor Panel (LT Panel Room) described as Below Incomer comprising of : 630 TPN MCCB with Microprocessor release for over current, short circuit & earth fault protection etc. - 1 Set Microprocessor APFC controller shall continuously monitor all three phases and displays various Electrical Parameters like voltage, input current, capacitive current, KVA demand, KW, Power Factor, self diagnostic error code indication with printout facility of the above with RS 232C port. Controller should mounted on the front side of the panel. It shall have data logging for minimum 2 months, it shall provide output for maximum 8 stages. Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 630/5 15 VA, CL 0.5, 3 No. CTs- 1 Set Breaker ON / OFF / TRIP indicating lights with control MCB - 1 Set Phase indicating light protected by 2 amps MCB’s. - 1 Set Bus Bar comprising of : 800 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable steeve - 1 set Outgoing comprising of : 50 kVAR Capacitor Bank - 5 Set each comprising of following: 125 Amps TPN MCCB - 1 Set AHF duty 525 volts 50Hz Thyrister for online control - 1 Set “ON” /”OFF” push buttons and indicating lamps. - 1 Set 50 kVAR, 525 volts capacitor unit as specified - 1 Set 25 kVAR Capacitor Bank - 2 Set each comprising of following: 80 Amps TPN MCCB - 1 Set AHF duty 525 volts 50Hz Thyrister for online control - 1 Set “ON” /”OFF” push buttons and indicating lamps. - 1 Set 25 kVAR, 525 volts capacitor unit as specified - 1 Set 15 kVAR Capacitor Bank - 1 Set each comprising of following: 40 Amps TPN MCCB - 1 Set AHF duty 525 volts 50Hz Thyrister for online control - 1 Set “ON” /”OFF” push buttons and indicating lamps. - 1 Set 15 kVAR, 525 volts capacitor unit as specified - 1 Set Notes: All incoming and outgoing breakers shall be minimum 25 kA rating with Icu = Ics. Heavy duty exhaust fans to be provided for cooling Capacitors, Thyristers & AHF. LED indication for number of capacitor banks ‘ON’. LED indication of Power Factor lagging or leading. APFC system shall comprise of following: i. Over Voltage ii. Voltage Imbalance iii. Earth Leakage 50% Active & 50% Passive Harmonic filter Capacity shall be computed by vendor as per Manufacturer standard and requirement as per feeder load requirement.

1

-

-

... More
Lighting, Power & AHU MDB Panel LGF-1 (Lower Ground Floor) Incomer comprising of : 160 amps 4 Pole MCCB with Thermal magnetic release for SC and OL protections - 1 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 160/5 15 VA, CL 0.5, 3 No. CTs- 1 Set ON / OFF / TRIP indicating lights with control MCB -1 Set RYB Phase indicating light protected by 2 amps MCB’s - 1 Set. Bus Bar comprising of : 200 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable steeve - 1 set Outgoing comprising of : 63 amps 4 Pole MCB - 4 Set 40 amps 4 Pole MCB - 2 Set 32 amps 4 Pole MCB - 4 Set Notes:- All breakers shall be minimum 10 kA rating with Icu = Ics. Lighting, Power & AHU MDB Panel LGF-1 (Lower Ground Floor) described as above

1

-

-

... More
MDB-VENT.-GF/1 (Ground Floor) (Ventilation Panel) Incomer comprising of : 250 TPN MCCB with Microprocessor release for OL, SC & EF protection etc. - 1 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 250/5 15 VA, CL 0.5, 3 No. CTs- 1 Set ON / OFF / TRIP indicating lights with control MCB -1 Set Phase indicating light protected by 2 amps MCB’s - 1 Set. Bus Bar comprising of : 630 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable steeve - 1 set Outgoing comprising of : 63 amps TPN MCCB with Thermal magnetic release for SC and OL protections - 1 Set 63 amps 4 Pole MCB - 16 Set 40 amps 4 Pole MCB - 8 Set 32 amps 4 Pole MCB - 3 Set Notes:- All breakers shall be minimum 16 kA rating with Icu = Ics. MDB-VENT.-GF/1 (Ventilation Panel) described as above

1

-

-

... More
MDB-VENT.-2F/1 Ventilation Panel Incomer comprising of : 250 TPN MCCB with Microprocessor release for over current, short circuit & earth fault protection etc. - 1 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 250/5 15 VA, CL 0.5, 3 No. CTs- 1 Set ON / OFF / TRIP indicating lights with control MCB -1 Set Phase indicating light protected by 2 amps MCB’s - 1 Set. Bus Bar comprising of : 300 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable steeve - 1 set Outgoing comprising of : 63 amps 4 Pole MCB - 8 Set 32 amps 4 Pole MCB - 6 Set Notes:- All breakers shall be minimum 10 kA rating with Icu = Ics. MDB-VENT.-3F/1 Ventilation Panel described as above

1

-

-

... More
MDB-VENT.-4F/1 Ventilation Panel Incomer comprising of : 125 TPN MCCB with Thermal magnetic based release for OL & SC protection etc. - 1 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 120/5 15 VA, CL 0.5, 3 No. CTs- 1 Set ON / OFF / TRIP indicating lights with control MCB -1 Set Phase indicating light protected by 2 amps MCB’s - 1 Set. Bus Bar comprising of : 200 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable steeve - 1 set Outgoing comprising of : 63 amps 4 Pole MCB - 6 Set 25 amps 4 Pole MCB - 3 Set Notes:- All breakers shall be minimum 10 kA rating with Icu = Ics. MDB-VENT.-4F/1 Ventilation Panel described as above

1

-

-

... More
Main Lift Power Panel (Lift Machine Room) Incomer comprising of : 125 amps TPN MCCB with Thermal magnetic release for SC and OL protections - 2 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 120/5 15 VA, CL 0.5, 3 No. CTs- 2 Set ON / OFF / TRIP indicating lights with control MCB - 2 Set Phase indicating light protected by 2 amps MCB’s - 2 Set. 125 amp 4pole contactor - 2sets Bus Bar comprising of : 200 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable steeve - 1 set Outgoing comprising of : 63 amps 4 Pole MCCB with Thermal magnetic release for SC, OL protection - 6 Set 40 amps 4P MCB - 3 Set Notes:- All breakers shall be minimum 16 kA rating with Icu = Ics. All incoming breakers shall be electrically/ mechanically interlocked. Main Lift Power Panel (Lift Machine Room) described as above

1

-

-

... More
UPS Input Panel (Ground Floor) (Elec. ROOM) Incomer comprising of : 100 amps 4 Pole MCCB with Thermal magnetic release for SC, OL protection - 2 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 100/5 15 VA, CL 0.5, 3 No. CTs- 2 Set ON / OFF / TRIP indicating lights with control MCB -2 Set Phase indicating light protected by 2 amps MCB’s - 2 Set. 100 amp 4 pole contactor - 2 Set Bus Bar comprising of : 200 Amps TPN Copper Bus Bar with colour coded heat shrinkable sleeves Outgoing comprising of : 63 amps 4 Pole MCCB with Thermal magnetic release for SC, OL protection - 5 Set UPS Input Panel (Ground Floor) (Elec. ROOM) described as above 63 amps 4 Pole MCB - 1 Set Notes:- All breakers shall be minimum 16 kA rating with Icu = Ics. All incoming breakers shall be electrically/ mechanically interlocked.

1

-

-

... More
MDB-E1 EMERGENCY LIGHTING PANEL (LOWER GROUND FLOOR) Incomer comprising of : 63 amps 4 Pole MCCB with Thermal magnetic release for SC and OL protections - 2 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 60/5 15 VA, CL 0.5, 3 No. CTs- 2 Set ON / OFF / TRIP indicating lights with control MCB -2 Set Phase indicating light protected by 2 amps MCB’s - 2 Set. Bus Bar comprising of : 100 Amps TPN Copper Bus Bar with colour coded heat shrinkable steeve - 1 set Outgoing comprising of : 25 amps 4 Pole MCB - 25 Set Notes:- All breakers shall be minimum 10 kA rating with Icu = Ics. MDB-E1 EMERGENCY LIGHTING PANEL (LOWER GROUND FLOOR) described as above

1

-

-

... More
MDB- GYM EQUIPMENTS PANEL (ELEC. ROOM) GROUND FLOOR Incomer comprising of : 160 amps 4 Pole MCCB with Thermalmagnetic release for SC and OL protections - 2 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 160/5 15 VA, CL 0.5, 3 No. CTs- 1 Set ON / OFF / TRIP indicating lights with control MCB -1 Set Phase indicating light protected by 2 amps MCB’s - 1 Set. Bus Bar comprising of : 200 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable steeve - 1 set Outgoing comprising of : 63 amps 4 Pole MCCB with Thermalmagnetic release for SC and OL protections - 2 Set 40 amps 4 Pole MCB WITH 40 amp RCCB 30mA - 2 Set 32 amps 4 Pole MCB WITH 40 amp RCCB 30mA - 2 Set 25 amps 4 Pole MCB WITH 25 amp RCCB 30mA - 4 Set 63 amps 4 Pole MCB - 2 Set Notes:- All breakers shall be minimum 10 kA rating with Icu = Ics. MDB- GYM EQUIPMENTS PANEL (ELEC. ROOM) GROUND FLOOR described as above

1

-

-

... More
MDB- KITCHEN/CAFE PANEL (ELEC. ROOM) GROUND FLOOR Incomer comprising of : 100 amps 4 Pole MCCB with Thermalmagnetic release for SC and OL protections - 2 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 with 200/5 15 VA, CL 0.5, 3 No. CTs- 1 Set ON / OFF / TRIP indicating lights with control MCB -1 Set Phase indicating light protected by 2 amps MCB’s - 1 Set. Bus Bar comprising of : 200 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable steeve - 1 set Outgoing comprising of : 63 amps 4 Pole MCCB with Thermalmagnetic release for SC and OL protections - 4 Set 40 amps 4 Pole MCB WITH 40 amp RCCB 30mA - 2 Set 25 amps 4 Pole MCB WITH 25 amp RCCB 30mA - 18 Set 63 amps 4 Pole MCB - 3 Set Notes:- All breakers shall be minimum 10 kA rating with Icu = Ics. MDB- KITCHEN/CAFE PANEL (ELEC. ROOM) GROUND FLOOR described as above

1

-

-

... More
LIGHTING,POWER & AHU PANEL-GF1 (GROUND FLOOR) Incomer comprising of : 125 amps TPN MCCB with Thermalmagnetic release for SC and OL protections - 1 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 100/5 15 VA, CL 0.5, 3 No. CTs- 1 Set ON / OFF / TRIP indicating lights with control MCB -1 Set Phase indicating light protected by 2 amps MCB’s - 1 Set. Bus Bar comprising of : 200 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable steeve - 1 set Outgoing comprising of : 63 amps 4 Pole MCB - 3 Set 32 amps 4 Pole MCB - 3 Set 25 amps 4 Pole MCB - 3 Set Notes:- All breakers shall be minimum 10 kA rating with Icu = Ics. LIGHTING,POWER & AHU PANEL-GF1 (GROUND FLOOR) described as above

1

-

-

... More
LIGHTING,POWER & AHU PANEL-1F1 (1ST FLOOR) Incomer comprising of : 125 amps TPN MCCB with Thermalmagnetic release for SC and OL protections - 1 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 120/5 15 VA, CL 0.5, 3 No. CTs- 1 Set ON / OFF / TRIP indicating lights with control MCB -1 Set Phase indicating light protected by 2 amps MCB’s - 1 Set. Bus Bar comprising of : 200 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable steeve - 1 set Outgoing comprising of : 63 amps 4 Pole MCB - 4 Set 32 amps 4 Pole MCB - 5 Set 25 amps 4 Pole MCB - 6 Set Notes:- All breakers shall be minimum 10 kA rating with Icu = Ics. LIGHTING,POWER & AHU PANEL-1F1 (1ST FLOOR) described as above

1

-

-

... More
LIGHTING,POWER & AHU PANEL-2F1 (2ND FLOOR) Incomer comprising of : 200 amps TPN MCCB with Thermalmagnetic release for SC and OL protections - 1 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 200/5 15 VA, CL 0.5, 3 No. CTs- 1 Set ON / OFF / TRIP indicating lights with control MCB -1 Set Phase indicating light protected by 2 amps MCB’s - 1 Set. Bus Bar comprising of : 300 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable steeve - 1 set Outgoing comprising of : 63 amps 4 Pole MCB - 6 Set 40 amps 4 Pole MCB - 3 Set 32 amps 4 Pole MCB - 6 Set 25 amps 4 Pole MCB - 3 Set Notes:- All breakers shall be minimum 10 kA rating with Icu = Ics. LIGHTING,POWER & AHU PANEL-2F1 (2ND FLOOR) described as above

1

-

-

... More
LIGHTING,POWER & AHU PANEL-3F1 (3RD FLOOR) C16:C17 Incomer comprising of : 125 amps TPN MCCB with Thermal magnetic release for SC and OL protections - 1 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 120/5 15 VA, CL 0.5, 3 No. CTs- 1 Set ON / OFF / TRIP indicating lights with control MCB -1 Set Phase indicating light protected by 2 amps MCB’s - 1 Set. Bus Bar comprising of : 200 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable steeve - 1 set Outgoing comprising of : 63 amps 4 Pole MCB - 3 Set 32 amps 4 Pole MCB - 5 Set 25 amps 4 Pole MCB - 5 Set Notes:- All breakers shall be minimum 10 kA rating with Icu = Ics. LIGHTING,POWER & AHU PANEL-3F1 (3RD FLOOR) described as above

1

-

-

... More
LIGHTING,POWER & AHU PANEL-4F1 (4TH FLOOR) Incomer comprising of : 250 amps TPN MCCB with Thermalmagnetic release for SC and OL protections - 1 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 250/5 15 VA, CL 0.5, 3 No. CTs- 1 Set ON / OFF / TRIP indicating lights with control MCB -1 Set Phase indicating light protected by 2 amps MCB’s - 1 Set. Bus Bar comprising of : 300 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable steeve - 1 set Outgoing comprising of : 63 amps 4 Pole MCB - 7 Set 32 amps 4 Pole MCB - 5 Set 25 amps 4 Pole MCB - 3 Set Notes:- All breakers shall be minimum 10 kA rating with Icu = Ics. LIGHTING,POWER & AHU PANEL-4F1 (4TH FLOOR) described as above

1

-

-

... More
LIGHTING,POWER & AHU PANEL-5F1 (5TH FLOOR) Incomer comprising of : 125 amps TPN MCCB with Thermalmagnetic release for SC and OL protections - 1 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 120/5 15 VA, CL 0.5, 3 No. CTs- 1 Set ON / OFF / TRIP indicating lights with control MCB -1 Set Phase indicating light protected by 2 amps MCB’s - 1 Set. Bus Bar comprising of : 200 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable steeve - 1 set Outgoing comprising of : 63 amps 4 Pole MCB - 4 Set 32 amps 4 Pole MCB - 4 Set 25 amps 4 Pole MCB - 3 Set Notes:- All breakers shall be minimum 10 kA rating with Icu = Ics. LIGHTING,POWER & AHU PANEL-3F1 (3RD FLOOR) described as above

1

-

-

... More
LIGHTING,POWER & AHU PANEL-6F1 (6TH FLOOR) Incomer comprising of : 160 amps TPN MCCB with Thermalmagnetic release for SC and OL protections - 1 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 160/5 15 VA, CL 0.5, 3 No. CTs- 1 Set ON / OFF / TRIP indicating lights with control MCB -1 Set Phase indicating light protected by 2 amps MCB’s - 1 Set. Bus Bar comprising of : 200 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable steeve - 1 set Outgoing comprising of : 63 amps 4 Pole MCB - 8 Set 40 amps 4 Pole MCB - 2 Set 32 amps 4 Pole MCB - 4 Set 25 amps 4 Pole MCB - 3 Set Notes:- All breakers shall be minimum 10 kA rating with Icu = Ics. LIGHTING,POWER & AHU PANEL-6F1 (6TH FLOOR) described as above

1

-

-

... More
MDB -PRESUREIZATION PANEL (TERRACE) Incomer comprising of : 100 amps TPN MCCB with Thermalmagnetic release for SC and OL protections - 1 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 100/5 15 VA, CL 0.5, 3 No. CTs- 1 Set ON / OFF / TRIP indicating lights with control MCB -1 Set Phase indicating light protected by 2 amps MCB’s - 1 Set. Bus Bar comprising of : 200 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable steeve - 1 set Outgoing comprising of : 63 amps 4 Pole MCB - 3 Set 25 amps 4 Pole MCB - 6 Set Notes:- All breakers shall be minimum 10 kA rating with Icu = Ics. LIFT & PRESUREIZATION PANEL described as above

1

-

-

... More
PLUMBING PUMP PANEL Incomer comprising of : 100 amps TPN MCCB with Thermalmagnetic release for SC and OL protections - 1 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 100/5 15 VA, CL 0.5, 3 No. CTs- 1 Set ON / OFF / TRIP indicating lights with control MCB -1 Set Phase indicating light protected by 2 amps MCB’s - 1 Set. Bus Bar comprising of : 200 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable steeve - 1 set Outgoing comprising of : 6.3 - 10 amps TPN MPCB with 25 amp contactor - 7 Set 2.5 - 4 amps TPN MPCB with 12 amp contactor - 3 Set 11 - 18 amps TPN MPCB with 25 amp contactor - 1 Set Notes:- All breakers shall be minimum 10 kA rating with Icu = Ics. PLUMBING PUMP PANEL described as above

1

-

-

... More
FIRE PUMP PANEL (LOWER GROUND FLOOR) Incomer comprising of : 400 TPN MCCB with Microprocessor release for over current, short circuit & earth fault protection etc. - 2 Set Multifunction meter for VAF, PF, Power & eneregy with RS - 485 port with 400/5 15 VA, CL 0.5, 3 No. CTs- 2 Set ON / OFF / TRIP indicating lights with control MCB -2 Set Phase indicating light protected by 2 amps MCB’s - 2 Set Bus Bar comprising of : 600 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable steeve - 1 set Bus Coupler 400 TPN MCCB with Microprocessor release for over current, short circuit & earth fault protection etc. - 1 Set Outgoing comprising of : 160 amps TPN MCCB with Thermalmagnetic release for SC and OL protections - 3 Set 40 amps TPN MPCB with 70 amp contactor - 2 Set 25 amps TPN MPCB with 40 amp contactor - 2 Set Notes:- All Outgoing feeders shall be provided with ON/OFF/TRIP Indications and shall be protected by 2 amps SP MCBs. All breakers shall be minimum 10 kA rating with Icu = Ics. All incoming breakers shall be electrically/ mechanically interlocked. FIRE PUMP PANEL (LOWER GROUND FLOOR) Panel described as above

1

-

-

... More
DISTRIBUTION BOARD Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898. 6-32 A SP

1462

-

-

... More
DISTRIBUTION BOARD Supplying and fixing regular MCB distribution boards on wall/ood board / flush mounting using required clA, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase/3 phase/single door with powder coated painting Made out of 14 SWG MS enclosure. I - Single Door 8 Way SP & N

2

-

-

... More
DISTRIBUTION BOARD Supplying and fixing regular MCB distribution boards on wall/ood board / flush mounting using required clA, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase/3 phase/single door with powder coated painting Made out of 14 SWG MS enclosure. I - Single Door 12 Way SP & N

6

-

-

... More
DISTRIBUTION BOARD Supplying and fixing regular MCB distribution boards on wall/ood board / flush mounting using required clA, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase/3 phase/single door with powder coated painting Made out of 14 SWG MS enclosure. 6 Way SP & N

4

-

-

... More
DISTRIBUTION BOARD Supplying and fixing regular MCB distribution boards on wall/ood board / flush mounting using required clA, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase/3 phase/single door with powder coated painting Made out of 14 SWG MS enclosure. 8 Way SP & N

8

-

-

... More
DISTRIBUTION BOARD Supplying and fixing regular MCB distribution boards on wall/ood board / flush mounting using required clA, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase/3 phase/single door with powder coated painting Made out of 14 SWG MS enclosure. III - Double Door 8 Way TP & N

26

-

-

... More
DISTRIBUTION BOARD Supplying and fixing regular MCB distribution boards on wall/ood board / flush mounting using required clA, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase/3 phase/single door with powder coated painting Made out of 14 SWG MS enclosure. III - Double Door 12 Way TP & N

28

-

-

... More
Supplying, fixing and wiring Residual current circuit breaker (RCCB) 240/450V upto 300mA sensitivity on existing wood/ panel board. 32-40A 4 pole

78

-

-

... More
Supplying, fixing and wiring Residual current circuit breaker (RCCB) 240/450V upto 300mA sensitivity on existing wood/ panel board. 63 A 4 pole

81

-

-

... More
Supplying, fixing and wiring Earth Leakage Miniature Circuit Breaker (ELMCB) 240/450V upto 300mA sensitivity on existing wood/panel board. 16-25 A 2 pole

20

-

-

... More
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40A

26

-

-

... More
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A

28

-

-

... More
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions. 3.5 core 300 sq.mm Al arm.

610

-

-

... More
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions. 3.5 core 240 sq.mm Al arm.

290

-

-

... More
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions. 3.5 core 150 sq.mm Al arm.

270

-

-

... More
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions. 3.5 core 185 sq.mm Al arm.

410

-

-

... More
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions. 3.5 core 95 sq.mm Al arm.

210

-

-

... More
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions. 3.5 core 70 sq.mm Al arm.

180

-

-

... More
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions. 3.5 core 50 sq.mm Al arm.

50

-

-

... More
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions. 4 core 25 sq.mm Al arm.

70

-

-

... More
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions. 4 core 16 sq.mm Cu arm.

2100

-

-

... More
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions. 4 core 10 sq. mm. Cu arm.

700

-

-

... More
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions. 4 core 6 sq.mm Cu arm.

1500

-

-

... More
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions. 4 core 4 sq.mm Cu arm.

1600

-

-

... More
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions. 3 core 6 sq.mm Cu arm.

50

-

-

... More
Supplying of following sizes of 600V/1000V Grade Fire Survival galvanised steel wire Armoured cable in the strandard aluminium/Copper conductor,constructed / designed as per BS 7846.as required complete in all respect as per site requirement. 3.5 core 240 sq.mm Al arm.

150

-

-

... More
Supplying of following sizes of 600V/1000V Grade Fire Survival galvanised steel wire Armoured cable in the strandard aluminium/Copper conductor,constructed / designed as per BS 7846.as required complete in all respect as per site requirement. 3.5 core 185 sq.mm Al arm.

70

-

-

... More
Supplying of following sizes of 600V/1000V Grade Fire Survival galvanised steel wire Armoured cable in the strandard aluminium/Copper conductor,constructed / designed as per BS 7846.as required complete in all respect as per site requirement. 3.5 core 120 sq.mm Al arm.

30

-

-

... More
Supplying of following sizes of 600V/1000V Grade Fire Survival galvanised steel wire Armoured cable in the strandard aluminium/Copper conductor,constructed / designed as per BS 7846.as required complete in all respect as per site requirement. 3.5 core 95 sq.mm Al arm.

90

-

-

... More
Supplying of following sizes of 600V/1000V Grade Fire Survival galvanised steel wire Armoured cable in the strandard aluminium/Copper conductor,constructed / designed as per BS 7846.as required complete in all respect as per site requirement. 3.5 core 70 sq.mm Al arm.

90

-

-

... More
Supplying of following sizes of 600V/1000V Grade Fire Survival galvanised steel wire Armoured cable in the strandard aluminium/Copper conductor,constructed / designed as per BS 7846.as required complete in all respect as per site requirement. 3.5 core 50 sq.mm Al arm.

260

-

-

... More
Supplying of following sizes of 600V/1000V Grade Fire Survival galvanised steel wire Armoured cable in the strandard aluminium/Copper conductor,constructed / designed as per BS 7846.as required complete in all respect as per site requirement. 4 core 25 sq.mm Al. arm.

720

-

-

... More
Supplying of following sizes of 600V/1000V Grade Fire Survival galvanised steel wire Armoured cable in the strandard aluminium/Copper conductor,constructed / designed as per BS 7846.as required complete in all respect as per site requirement. 4 core 10 sq.mm Cu. arm.

1485

-

-

... More
Supplying of following sizes of 600V/1000V Grade Fire Survival galvanised steel wire Armoured cable in the strandard aluminium/Copper conductor,constructed / designed as per BS 7846.as required complete in all respect as per site requirement. 4 core 6 sq.mm Cu arm.

565

-

-

... More
Supplying of following sizes of 600V/1000V Grade Fire Survival galvanised steel wire Armoured cable in the strandard aluminium/Copper conductor,constructed / designed as per BS 7846.as required complete in all respect as per site requirement. 4 core 4 sq.mm Cu arm.

420

-

-

... More
Supplying of following sizes of 600V/1000V Grade Fire Survival galvanised steel wire Armoured cable in the strandard aluminium/Copper conductor,constructed / designed as per BS 7846.as required complete in all respect as per site requirement. 3 core 4 sq.mm Cu arm.

2100

-

-

... More
Supplying of following sizes of 600V/1000V Grade Fire Survival galvanised steel wire Armoured cable in the strandard aluminium/Copper conductor,constructed / designed as per BS 7846.as required complete in all respect as per site requirement. 1 core 16 sq.mm Cu Unarm. for UPS Connectivity

320

-

-

... More
Supplying of following sizes of 600V/1000V Grade Fire Survival galvanised steel wire Armoured cable in the strandard aluminium/Copper conductor,constructed / designed as per BS 7846.as required complete in all respect as per site requirement. 2 core 10 sq.mm Cu Unarm. for UPS Connectivity

130

-

-

... More
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Upto 35 sq. mm (clamped with 1mm thick saddle)

11210

-

-

... More
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)

860

-

-

... More
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)

780

-

-

... More
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)

900

-

-

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)

20

-

-

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. Above 95 sq. mm and upto 185 sq. mm (clamped with 40x3mm MS flat clamp)

100

-

-

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)

90

-

-

... More
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 300 sq. mm (70mm)

40

-

-

... More
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 240 sq. mm (62mm)

10

-

-

... More
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 185 sq. mm (50mm)

12

-

-

... More
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 150 sq. mm (45mm)

6

-

-

... More
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 95 sq. mm (45mm)

6

-

-

... More
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 70 sq. mm (38mm)

8

-

-

... More
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 25sq. mm (28mm)

2

-

-

... More
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 50 sq. mm (38mm)

2

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of bimettalic crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 4 core 16 sq.mm Cu arm.

72

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of bimettalic crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 4 core 10 sq. mm. Cu arm.

22

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of bimettalic crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 4 core 6 sq.mm Cu arm.

72

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of bimettalic crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 4 core 4 sq.mm Cu arm.

44

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of bimettalic crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 3 core 6 sq.mm Cu arm.

2

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured fire returant cables of 1100 volt grade including supplying and fixing of bimettalic crimping flame proof lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 3.5 core 240 sq. mm Al arm.

4

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured fire returant cables of 1100 volt grade including supplying and fixing of bimettalic crimping flame proof lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions.3.5 core 185 sq. mm Al arm.

4

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured fire returant cables of 1100 volt grade including supplying and fixing of bimettalic crimping flame proof lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 3.5 core 120 sq. mm Al arm.

2

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured fire returant cables of 1100 volt grade including supplying and fixing of bimettalic crimping flame proof lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 3.5 core 95 sq. mm Al arm.

2

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured fire returant cables of 1100 volt grade including supplying and fixing of bimettalic crimping flame proof lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 3.5 core 70 sq. mm Al arm.

2

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured fire returant cables of 1100 volt grade including supplying and fixing of bimettalic crimping flame proof lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 3.5 core 50 sq. mm Al arm.

6

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured fire returant cables of 1100 volt grade including supplying and fixing of bimettalic crimping flame proof lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 4 core 25 sq.mm Al. arm.

22

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured fire returant cables of 1100 volt grade including supplying and fixing of bimettalic crimping flame proof lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 4 core 10 sq.mm Al. arm.

42

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured fire returant cables of 1100 volt grade including supplying and fixing of bimettalic crimping flame proof lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 4 core 6 sq.mm Cu arm.

16

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured fire returant cables of 1100 volt grade including supplying and fixing of bimettalic crimping flame proof lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 4 core 4 sq.mm Cu arm.

10

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured fire returant cables of 1100 volt grade including supplying and fixing of bimettalic crimping flame proof lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 3 core 4 sq.mm Cu arm.

80

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured fire returant cables of 1100 volt grade including supplying and fixing of bimettalic crimping flame proof lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 1 core 16 sq.mm Cu Unarm. for UPS Connectivity

12

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured fire returant cables of 1100 volt grade including supplying and fixing of bimettalic crimping flame proof lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 1 core 10 sq.mm Cu Unarm. for UPS Connectivity

6

-

-

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 50 mm width X 50 mm depth X 1.6 mm thickness

1080

-

-

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 150 mm width X 50 mm depth X 1.6 mm thickness

1650

-

-

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 300 mm width X 50 mm depth X 1.6 mm thickness

870

-

-

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 450 mm width X 50 mm depth X 2.0 mm thickness

290

-

-

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 600 mm width X 50 mm depth X 2.0 mm thickness

22

-

-

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 750 mm width X 75 mm depth X 2.0 mm thickness

150

-

-

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 900 mm width X 75 mm depth X 2.0 mm thickness

35

-

-

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 100 mm width X 50 mm depth X 1.6 mm thickness

100

-

-

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 300 mm width X 50 mm depth X 1.6 mm thickness

40

-

-

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 450 mm width X 50 mm depth X 2.0 mm thickness

15

-

-

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 600 mm width X 50 mm depth X 2.0 mm thickness

3

-

-

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 900 mm width X 75 mm depth X 2.0 mm thickness

2

-

-

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, paintingsuspenders etc as required. 100 mm width X 50 mm depth X 1.6 mm thickness

20

-

-

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, paintingsuspenders etc as required. 300 mm width X 50 mm depth X 1.6 mm thickness

20

-

-

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, paintingsuspenders etc as required. 450 mm width X 50 mm depth X 2.0 mm thickness

8

-

-

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, paintingsuspenders etc as required. 600 mm width X 50 mm depth X 2.0 mm thickness

2

-

-

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, paintingsuspenders etc as required. 750 mm width X 75 mm depth X 2.0 mm thickness

3

-

-

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, paintingsuspenders etc as required. 900 mm width X 75 mm depth X 2.0 mm thickness

4

-

-

... More
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 150 mm width X 50 mm depth X 1.6 mm thickness

30

-

-

... More
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 300 mm width X 50 mm depth X 1.6 mm thickness

20

-

-

... More
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 450 mm width X 50 mm depth X 2.0 mm thickness

20

-

-

... More
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "bends" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 150 mm width X 50 mm depth X 1.6 mm thickness

5

-

-

... More
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "bends" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 300 mm width X 50 mm depth X 1.6 mm thickness

4

-

-

... More
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "bends" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 450 mm width X 50 mm depth X 2.0 mm thickness

3

-

-

... More
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Tee" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 150 mm width X 50 mm depth X 1.6 mm thickness

2

-

-

... More
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Tee" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 300 mm width X 50 mm depth X 2.0 mm thickness

2

-

-

... More
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Tee" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 450 mm width X 50 mm depth X 2.0 mm thickness

3

-

-

... More
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 300mm dia

440

-

-

... More
Earthing System:Supply, Testing & Commissioning, fixing of following bare Copper / GI tapes / wires including all necessary fixing accessories, insulators and effecting connections as per specifications. 32 x 6 mm thick Copper tape with heat shrinkable sleeves

132

-

-

... More
Providing and fixing 25 mm X 5 mm Copper. strip on surface or in recess for connections etc. as required.

88

-

-

... More
Supply, Testing & Commissioning, fixing of following bare Copper / GI tapes / wires including all necessary fixing accessories, insulators and effecting connections as per specifications. 50 x 6 mm thick GI tape

400

-

-

... More
Supply, Testing & Commissioning, fixing of following bare Copper / GI tapes / wires including all necessary fixing accessories, insulators and effecting connections as per specifications. 50 x 10 mm thick GI tape

90

-

-

... More
Supply, Testing & Commissioning, fixing of following bare Copper / GI tapes / wires including all necessary fixing accessories, insulators and effecting connections as per specifications. 32 x 6 mm thick GI tape

90

-

-

... More
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.

1364

-

-

... More
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.

1100

-

-

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm

50

-

-

... More
Providing and fixing Earth Bus of 50mm X 5mm copper strip on surface for connections etc. as required.

10

-

-

... More
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.

22

-

-

... More
Earthing with copper earth plate 600 mm X 600 mm X 3 mm hick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.

10

-

-

... More
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 100mm dia

10

-

-

... More
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 150mm dia

20

-

-

... More
Lightning Protection System:Supply, Installation, testing & Commissioning of interception Aluminium Rod of 3 mtr length including bi-metallic connection witth the strip with all accessories as required complet in all respects.

3

-

-

... More
Jointing copper / G.I . Tape (with aother copper / G.I tape ,base of the final or any other mettalic object ) by riveting / nut bolting / sweating and soldering etc as required.

10

-

-

... More
Providing and fixing G.I Tape 20 x 3 mm thick on Parapet or surface of wall for lightning conductor complete as required(for horizental run)

525

-

-

... More
Providing and fixing G.I Tape 32 x 3 mm thick lightning conductor complete as required(For Vertical run)

210

-

-

... More
Providing and fixing testing joint,made of 20 mm x 3 mm thick G.I strip,125 mm long with 4 nos of G.I bolts,nuts,chuck nuts and spring washers etc.complete as required.

12

-

-

... More
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.

8

-

-

... More
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 100 mm dia

10

-

-

... More
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 150 mm dia

40

-

-

... More
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 250 mm dia

10

-

-

... More
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 300 mm dia

200

-

-

... More
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C

351

-

-

... More
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C

1264

-

-

... More
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments. 1.5 mm2

1820

-

-

... More
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments. 2.5 mm2

1400

-

-

... More
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments. 4 mm2

1650

-

-

... More
Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments. 6 mm2

350

-

-

... More
Supplying 6A flush type socket and 6 A flush type SP switch either surface/flush mounting in existing gang box or in 4mm thick plastic sheet and fixing over a flush mounted wooden box and wiring using necessary capacity wires as required as per IS 1293 and IS 3654 6A 2 Way

40

-

-

... More
Supplying and mounting 2 Nos. of 2Way 6 A flush type switches either surface/flush mounted on existing gang box or in 4mm thick plastic sheet and mounted on a flush mounted wooden box and wiring as per IS 1293

2

-

-

... More
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 1-3 Way

50

-

-

... More
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 4-5 Way

30

-

-

... More
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 6 Way

30

-

-

... More
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 8 Way

20

-

-

... More
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 10-12 Way

50

-

-

... More
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. 1 to 3 Module

100

-

-

... More
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. 4 Module

70

-

-

... More
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. 6 Module

60

-

-

... More
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. 8 Module

20

-

-

... More
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. 10-12 Module

10

-

-

... More
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. 6A One Way Switch

48

-

-

... More
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. 6A Three Way socket

48

-

-

... More
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. 16A One Way Switch

237

-

-

... More
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. 32A DP Switch

3

-

-

... More
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. 6/16A Universal Socket

237

-

-

... More
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. TV/Telephone Socket

3

-

-

... More
Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. RJ45/I.O Outlet Cat-6

15

-

-

... More
Supplying and fixing 32A security and energy saving DP switch with key tag suitable to operate on 230 V, 50Hz AC supply & completely wired on existing box.

2

-

-

... More
Supplying and fixing suitable size GI box with modular plate and cover infront on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings).

3

-

-

... More
Supplying and fixing of metal clad industrial plugs and sockets. 2pole+earth 250V PLUG 10A

3

-

-

... More
Supplying and fixing of metal clad industrial plugs and sockets. 2pole+earth 250V PLUG 20A

10

-

-

... More
Internal lighting fixtures: Supplying of .....feet -PVC Batten with integrated LED tube .... W with high quality diffuser with Life of 25000 burning hours & 70% lumen maintenance with CRI 80. Power Input: 220-240V@ 50/60Hz & Power factor 0.9 along with CE approved. 2 years Warranty against any manufacturing defect working under standard electrical condition. LED light fitting 1 x 2' - 9/10 W

92

-

-

... More
Supplying of .....feet -PVC Batten with integrated LED tube .... W with high quality diffuser with Life of 25000 burning hours & 70% lumen maintenance with CRI 80. Power Input: 220-240V@ 50/60Hz & Power factor 0.9 along with CE approved. 2 years Warranty against any manufacturing defect working under standard electrical condition. LED light fitting 1 x 4' - 20/22 W

91

-

-

... More
Supplying of .....feet -PVC Batten with integrated LED tube .... W with high quality diffuser with Life of 25000 burning hours & 70% lumen maintenance with CRI 80. Power Input: 220-240V@ 50/60Hz & Power factor 0.9 along with CE approved. 2 years Warranty against any manufacturing defect working under standard electrical condition. LED light fitting 1 x 4' - 36/40 W

30

-

-

... More
Supplying of recess mounting non integrated type LED down light...... W luminaire comprising of pressure decast/ extruded aluminium housing, with spring loaded false ceiling clA, LED of Power/COB with CCT 6500 degree K, CRI 70%. efficacy 100 lumen per W, 120degree beam spread, life 25000 burning hours and Compliance to IS10322/IEC 60598, LM 79 & LM 80. The lamp compartment is enclosed with anti glare opal diffuser which enhances the lighting level. LED's are driven by HF electronic driver integrated in a separate control gear assembly., with PF 0.95, power loss should 5% of lamp Wage, short circuit & open circuit protection to be integrated in the circuit, THD less than 20%, Life as per LM 79. The operating input voltage should be between 130 to 275 V. BIS Approved and Tested by NABL/CPRI accredited laboratory with 2 years Warranty against any manufacturing defect working under standard electrical condition. 10-12W

150

-

-

... More
Supplying of recess mounting non integrated type LED down light...... W luminaire comprising of pressure decast/ extruded aluminium housing, with spring loaded false ceiling clA, LED of Power/COB with CCT 6500 degree K, CRI 70%. efficacy 100 lumen per W, 120degree beam spread, life 25000 burning hours and Compliance to IS10322/IEC 60598, LM 79 & LM 80. The lamp compartment is enclosed with anti glare opal diffuser which enhances the lighting level. LED's are driven by HF electronic driver integrated in a separate control gear assembly., with PF 0.95, power loss should 5% of lamp Wage, short circuit & open circuit protection to be integrated in the circuit, THD less than 20%, Life as per LM 79. The operating input voltage should be between 130 to 275 V. BIS Approved and Tested by NABL/CPRI accredited laboratory with 2 years Warranty against any manufacturing defect working under standard electrical condition. 15-18W

1043

-

-

... More
10 Watt Bulkhead LED light fixture with minimum luminaire system efficacy of 100 lm/w having a color temperature of 5700K and housing should made up of pressure die cast aluminium with high efficiency diffuser with driver, accessories wiring etc.

60

-

-

... More
Volley Ball court light Supply, Installation, Testing and Commissioning of 195W LED Flood light made of High Pressure Die Cast Aluminium Alloy hosuing with anti-dust exposed lenses. High power LED with efficacy of 120lm/w at source and lumen output upto 24000 lumen. The product should come with Compnay LOGO Engraved, Corelated Color Temp 5700k, CRI≥70,Maintenance of lumen L70 (Hrs) 50K@L70,Ambient temperature (Ta) 35Degree, the product should be AMB. Protection of Fixture:- IP66,IK08, servicability Class B, power factor≥0.95, THD≤10%. The driver should be equipped with protection like 440V (P2P) Protection for 8 Hrs., High cut off @ 325±15V, Auto Restart, Surge protection 4KV internal and 10KV external. Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters. Both the fixture and Driver should have separate BIS approval.

32

-

-

... More
Badminton Court, Basketball Court Supply, Installation, Testing and Commissioning of 175W LED Flood light made of High Pressure Die Cast Aluminium Alloy hosuing with anti-dust exposed lenses. High power LED with efficacy of 120lm/w at source and lumen output upto 21000 lumen. The product should come with Compnay LOGO Engraved, Corelated Color Temp 5700k, CRI≥70,Maintenance of lumen L70 (Hrs) 50K@L70,Ambient temperature (Ta) 35Degree, the product should be AMB. Protection of Fixture:- IP66,IK08, servicability Class B, power factor ≥0.95, THD≤10%. The driver should be equipped with protection like 440V (P2P) Protection for 8 Hrs., High cut off @ 325±15V, Auto Restart, Surge protection 4KV internal and 10KV external. Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters. Both the fixture and Driver should have separate BIS approval.

96

-

-

... More
Badminton Court Supply, Installation, Testing and Commissioning of led Light 4 feet, 108W fixer badminton court with clamps. Length: 1220 mm Width: 260 mm Height: 62 mm Lumen: 120LM/W CRI 80 PF: 0.9 CCT: 6000K Rated Volt: AC85-240V Frequency: 50-60HZ

59

-

-

... More
Entrance Porch Lighting Supply, Installation, Testing and Commissioning of Suspended Light 15W made of Pressure die-cast aluminium heat sink for effective thermal management, sturdiness and excellent corrosion resistant fitted in white/Black finish Powder coated housing. PC Clear diffuser for glare free uniform light distribution along with Aluminum reflector to enhance the lumen output of the fixture. Powered by built-in, isolated, electronic LED driver (SMPS based constant current supply) with Output Short-circuit protection, Surge Voltage protection & other safety test as per IS:15885Part 2/Sec 13. Operating voltage range: 140 V - 270 V, Average life L70B50: 35000 hours, UGR19@CCT 4000K. Beam angle 36Deg, Suystem Lumen 1200Lm, Dia 75MM, Height 150MM.

10

-

-

... More
Supply, Installation, Testing and Commissioning Lobby & Seating area Downlighter of LED indoor surface downlighter suitable for general lighting. Luminaire should have pressure die-cast Al housing with diffused optics. The luminaire should have CRI ≥ 80 and CCT of 6500K. The luminaire shall be compliant with IP20, IK02 classification.The fixture should have a minimum system efficacy of 110 lumen/Watt and a minimum system lumen output of 1500 lumens and maximum system wattage of 14 Watts. The luminaire shall be designed so as to ensure lumen depreciation of up to 30% over 30k burning hours @ design ambient temp 45 deg C. The electronic driver used shall have a power factor≥0.95 , THD ≤10%. Luminaire manufacture shall provide LM79 report from NABL/UL accredited lab & LM80 report issued by LED manufacturer. Both the fixture and Driver should be of same make & must have separate BIS approval.

590

-

-

... More
Supply of LED indoor surface downlighter suitable for general lighting. Luminaire should have pressure die-cast Al housing with diffused optics. The luminaire should have CRI ≥ 80 and CCT of 6500K. The luminaire shall be compliant with IP20, IK02 classification.The fixture should have a minimum system efficacy of 110 lumen/Watt and a minimum system lumen output of 1500 lumens and maximum system wattage of 14 Watts. The luminaire shall be designed so as to ensure lumen depreciation of up to 30% over 30k burning hours @ design ambient temp 45 deg C. The electronic driver used shall have a power factor≥0.95 , THD ≤10%. Luminaire manufacture shall provide LM79 report from NABL/UL accredited lab & LM80 report issued by LED manufacturer. Both the fixture and Driver should be of same make & must have separate BIS approval.

420

-

-

... More
Reccessed Downlighters Supply, Installation, Testing and Commissioning recessed mounted 12W Round Shape Downlighter with high performance LEDs, suitable for mounting with Armstrong/Grid ceiling. pressure die-cast aluminium heat sink & PC diffuser in white powder coated finish with integral electronic low THD (10%) LED driver. High efficiency long life LED package in integral module with lumen efficacy of 110 lm/W. Powered by an integrated driver, SELV Output electronic LED driver (SMPS based constant current supply) with Output Short-circuit protection, Surge protection & other reliability test. . CRI 80, SDCM5, Color temperature 4000K, PF 0.95, IP20, IK03. Life class of 50,000 hrs @ L70, Operating Temperature: -10 TO +45 DEG.C; Input Supply Voltage Range:140-270 V, Frequency :50-60 HZ; Internal Surge Protection:3.5 KV; Protection: Reverse Polarity, Open & Short Circuit. DRIVER SAFETY REQUIREMENT STANDARDS: IS 15885-2-13, TEST REPORT TO BE SUBMITTED; PHOTO BIOLOGICAL SAFETY NORMS: IS 16108, TEST CERTIFICATE TO BE SUBMITTED; CERTIFICATION: LM 79 FOR LUMINAIRE LM 80 FOR LED SOURCE

50

-

-

... More
Reccessed 2' x 2' panel Supply, Installation, Testing and Commissioning of 36w 2x2 Panel recess mounting luminaire with high performance LEDs, suitable for Armstrong/Grid ceiling.CRCA powder coated white after phosphochromate treatment and High transmittance polystyrene opal diffuser.High efficiency long life LED package in integral module with System lumen efficacy of 115 lm/W and viewing angle of 120° to ensure better uniformity.Powered by an independent Isolated, SELV Output electronic LED driver (SMPS based constant current supply) with Output Short-circuit protection, Surge protection & other reliability test. Lumen Output of 4100 lm lumens.CRI 80, Color temperature 5700K, THD 10%, SDCM5 and PF 0.95,IP20,Life class of 50,000 hrs @ L70, Operating Temperature:-10 TO +40 DEG.C; Input Supply Voltage Range:140-270 V, Frequency :50-60 HZ; Internal Surge Protection:3 KV; Protection : Reverse Polarity, Open & Short Circuit. DRIVER SAFETY REQUIREMENT STANDARDS :IS 15885-2-13 & CISPR15, TEST REPORT TO BE SUBMITTED; PHOTO BIOLOGICAL SAFETY NORMS: IS 16108, TEST CERTIFICATE TO BE SUBMITTED; CERTIFICATION: LM 79 FOR LUMINAIRE LM 80 FOR LED SOURCE.

579

-

-

... More
Surface mounted 2'x 2 panel Supply, Installation, Testing and Commissioning of 36w 2x2 Panel Surface mounting luminaire with high performance LEDs, suitable for Armstrong/Grid ceiling.CRCA powder coated white after phosphochromate treatment and High transmittance polystyrene opal diffuser.High efficiency long life LED package in integral module with System lumen efficacy of 100 lm/W and viewing angle of 120° to ensure better uniformity.Powered by an independent Isolated, SELV Output electronic LED driver (SMPS based constant current supply) with Output Short-circuit protection, Surge protection & other reliability test. Lumen Output of 4100 lm lumens.CRI 80, Color temperature 5700K, THD 10% and PF 0.95,IP20,Life class of 50,000 hrs @ L70, Operating Temperature:-10 TO +40 DEG.C; Input Supply Voltage Range:140-270 V, Frequency :50-60 HZ; Internal Surge Protection:3 KV; Protection : Reverse Polarity, Open & Short Circuit. DRIVER SAFETY REQUIREMENT STANDARDS :IS 15885-2-13 & CISPR15, TEST REPORT TO BE SUBMITTED; PHOTO BIOLOGICAL SAFETY NORMS: IS 16108, TEST CERTIFICATE TO BE SUBMITTED; CERTIFICATION: LM 79 FOR LUMINAIRE LM 80 FOR LED SOURCE

600

-

-

... More
Suspended Lighting Supply, Installation, Testing and Commissioning Pendent mounted Dayspace LED sidelit 2X2 panel with hollow space,made of CRCA housing with high efficiency single piece PC Diffuser. LED Used shall be SMD type and fixture should have minimum efficacy at System level ≥=90 lumens/watt with Minimum system Lumens 3600 & System wattage of 40W, Life of fixture : 50000 burning Hrs. @ L70B50 Lumen maintenance, CCT of 6500K (SDCM≤=5), CRI Ra ≥=80, THD≤10%, PF ≥0.95. Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. The product should be able to integrate into the ceiling to deliver soft and etheareal yet brilliant environment with very good vertical illuminance.The product should have provision of customizable back plate for creative freedom if required. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters. Both the fixture and Driver should have separate BIS approval.

50

-

-

... More
Squash court light Supply, Installation, Testing and Commissioning 36W LED with Linear with, minimum 3800 lumens Downligher luminaire made of Aluminum extruded housing in white powder coated finish and snap fit plastic moulded end caps, High transmittance PMMA opal profiled diffuser, control gear accessible and serviceable from bottom, suitable for standalone and continuous row mounting for endless line of light, High efficiency long life LED package in integral module with lumen efficacy 110 Lm/W and viewing angle of 120° to ensure better uniformity.Powered by an integral isolated low THD electronic LED driver ( SMPS based constant current supply) with output short circuit protection, surge protection. Fixture Efficacy 100Lm/W, CRI 80, Color temperature 5700K, THD 10% and PF 0.90,IP20,IK03.Life class of 50,000 hrs @ L70, Operating Temperature:-10 TO +45 DEG.C; Input Supply Voltage Range:140-270 V, Frequency :50-60 HZ; Internal Surge Protection:3.5 KV; Protection : Reverse Polarity, Open & Short Circuit. DRIVER SAFETY REQUIREMENT STANDARDS :IS 15885-2-13, TEST REPORT TO BE SUBMITTED; PHOTO BIOLOGICAL SAFETY NORMS: IS 16108, TEST CERTIFICATE TO BE SUBMITTED; CERTIFICATION: LM 79 FOR LUMINAIRE LM 80 FOR LED SOURCE.

113

-

-

... More
Snooker Suspended light Supply, Installation, Testing and Commissioning Wide 120mm x 33mm height Suspended 4ft continuous LED Channel Fixture Flatline Linear in rectangle form with hollow curved edges & high efficiency diffuser. LED Used shall be SMD type with Minimum system Lumens 2200 @19W/4ft length & efficacy upto 120lm/W,Life of fixture : 50000 burning Hrs. @ L70B50 Lumen maintenance, CCT of 4000K (SDCM≤=5), CRI Ra ≥=80, PF ≥0.95, UGR≤19, an Operating working temp range - 0°C ≤ Ta ≤ 45°C & operating Voltage Range of 140-270 V AC. Minimum Internal Surge Protection 4.0KV. The fixture design should be with flicker free operations ripple ≤5%, comply to IEC61000-3-2 ed.3.2, 2009 for Harmonics, IEC61347 -2 -13, 2006 in Conjunction with IEC61347-1 ed.2.0, 2007 for Electrical Safety, IEC62384 ed.1.1, 2011 for performance and IEC61547 ed.2.0, 2009, CISPR-15 for EMI/EMC. Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters. Both the fixture and Driver should have separate BIS approval. Dimension should be LBH = Multiple of 1200mm (As per design reqiurement) x 120mm x 33mm

10

-

-

... More
Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.

72

-

-

... More
supply ,installation, testing and commissioning of 1200 mm dia BLDC fan

30

-

-

... More
Supplying installation,testing and commissioning of Passive Infrared(PIR) technology based occupancy sensor having high preformance, non regulating programmable type, suitable for connected load upto 10Amp, for mounting height up to 2.8 mtr and for 5 m diameter coverage area along with necessary fixing arrangements Vc programming at site etc. complete as required.

20

-

-

... More
Data, voice & TV system: Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. 25mm

200

-

-

... More
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. 32mm

100

-

-

... More
Supplying and drawing UTP-CAT 6E LAN cable.

5500

-

-

... More
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. 1 or 2 Module (75 mmX75 mm)

50

-

-

... More
Supplying and drawing PVC flexible one pair telephone unarmoured tinned copper cable. 2 Pair

150

-

-

... More
Supplying fixing of Network Switches 24 Port 10/100 Switch

1

-

-

... More
Supplying fixing of Network Switches 8 Port 10/100 Switch

1

-

-

... More
Supplying & Fixing of Patch panel for LAN cabling 24 Port 101100 patch panel

1

-

-

... More
Supply, laying, including termination testing & commissioning of RG-11 co-axial cable of approved make for TV in existing conduit complete in all respect as required.

180

-

-

... More
Fire Alarm System: Supply, install, test and commissioning of addressable peer to peer Networkable analogue addressable type fire alarm control panel with minimum 1500 Character / 240X64 Pixel / 7inch Touchscreen graphic LCD display. The panel should be equipped with sufficient numbers of loop with 20% spare capacity, with each networkable intelligent fire alarm Control Panel having SLC with capacity of min 126 /240 detectors/ devices in any combination with key pad, dual flash-based microprocessor technology, inbuilt USB Port for upload and down load the configuration tools, RS232 serial port for direct PC or modem connection, inbuilt NAC's, min 20 programmable Zonal LEDs and operates on 240V AC + 10% with 50 Hz with built in charger. The panel shall have fire, fault relays, option of BMS integration MODBUS/ BACKNET, graphical software for provision of TCP/ IP modules, Remote Access, Class 'X' wiring with provision of both class 'A' and class 'B' wiring in the SLC circuit, user friendly with communication facility to monitor & control the FACPs from a single window. The panel shall be suitable for minimum of 5000 event record facility, event fetch from FACP facility and the single panel shall be suitable for min 2000 fire zones and 200 Panels/ Nodes in one network with all other accessories required to successfully run the system. (The System cost shall be included of all necessary cards, modules, Panel enclosure, CPU and associated accessories to complete the system design). Approval: VDS/UL/EN-54 Std. 8 LOOP Panel.

1

-

-

... More
Supply, Installation , Testing & Commissioning† of Network Active Repeater Panel with 1500 Character / 240X64 Pixel / 7inch Touchscreen. The LCD shall Display all events / detectors, devices status of complete systems in the networked.† Approval: UL/VDS/EN54.

3

-

-

... More
Supply, install, test and commissioning of† analogue addressable Smoke Sensor detector and standard base (For Detectors/Device without inbuilt isolator, Fault Isolator or Isolator base to be provided with each detector/device) Approval: VDS/UL/EN54.

300

-

-

... More
Supplying, installation, testing & commissioning of fault isolator complete with base as required.

28

-

-

... More
Supply, install, test and commissioning of analogue addressable dual heat detector and standard base, It shall have multiple modes with min five different heat sensitivity adjustment from 57 Degree to 90 Degree for static response while working on Rate of Rise response. 360° Visible Tri-coloured led for Normal, Fault and alarm condition, addressing shall be by means of Soft addressing or dip switches or decade switches, or suitable punched cards. (For Detectors/Device without inbuilt isolator, Fault Isolator or Isolator base to be provided with each detector/device) Approval: UL/VDS/EN54.

5

-

-

... More
Supplying, installation, testing & commissioning of addressable beam detector with short circuit isolator (inbuilt or seperate) complete with emitter and receiver including connections with remote test features etc complete as required.

8

-

-

... More
Supplying, installation, testing & commissioning of addressable fire control module complete as required.

55

-

-

... More
Supply, install, test and commissioning of Analogue addressable Manual Call Point (Resettable Type) with inbuilt† isolator and LED indicator, designed for IP44 requirements and approved to operate in –10°C to +55°C temperature, complies with the essential requirement of the EMC Directive to be supplied with Barriers, Junction Box, Glands and other mounting accessories for proper installation. (For Detectors/Device without inbuilt isolator, Fault Isolator or Isolator base to be provided with each detector/device) Approval: VDS.

40

-

-

... More
Supply, Installation, Testing & Commissioning of Analogue Addressable loop powered Sounder & Beacon† with inbuilt isolator and† having Min 15 distinct sound patterns/ multitone to indicate Exit doors and direct occupants for safe and fast evacuation and 100dB output with minimum 1Hz Frequency flash rate designed for IP65 requirements and approved to operate in –10°C to +55°C temperature, complies with the essential requirement of the EMC Directive to be supplied with Junction Box, Glands and other mounting accessories for proper installation. (For Detectors/Device without inbuilt isolator, Fault Isolator or Isolator base to be provided with each detector/device) Approval: VDS/UL/EN54.

40

-

-

... More
Supplying, installation, testing & commissioning of fire fighter telephone handset complete as required.

40

-

-

... More
Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required.

400

-

-

... More
Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required.

5500

-

-

... More
Supply & Laying of Speaker Cable 2 Pair ,2core -1.5Sqmm

4000

-

-

... More
Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required.

1000

-

-

... More
Supply, installation, testing and commissioning of the Analog addresable Photoelectric Multicriteria detector with mounting based LED, address switch to programme the detectors complete as required.

5

-

-

... More
Supply, install, test and commissioning of Analogue addressable Monitor Cum Control (Input/Output) module (1+1) with inbuilt relay and isolator with LED indicator, approved to operate in –10°C to +55°C temperature, complies with the essential requirement of the EMC Directive to be supplied with Junction Box, Glands and other mounting accessories for proper installation. In case of Manufacturer with single Input or Output module need to supply One quantity of each for line item. (For Detectors/Device without inbuilt isolator, Fault Isolator or Isolator base to be provided with each detector/device) Approval: EN54.

50

-

-

... More
UPS System: Supplying, erecting, testing & commissioning of ON-LINE UPS system suitable for operation on 230V, 50Hz, A/C supply, with isolation transformer all accessories complete and Excluding batteries and wiring complete. 10 kVA ON LINE UPS

4

-

-

... More
Supplying, installation, testing & commissioning of 12V DC, AH batteries in poly propylene container for U.P.S. Sealed maintenance free batteries. 26 AH capacity

32

-

-

... More
Supplying, installation, testing & commissioning of 12V DC, AH batteries in poly propylene container for U.P.S. Sealed maintenance free batteries. 42 AH capacity

40

-

-

... More
External and facade lighting system: Projector Light The housing in light weight, made of high strength die cast aluminium and coated by static powder making it weather resistant.Protection screen in clear tempered glass with high impact resistance 25-30W, LED,3000k, IP 66. High precision dial ensures precision angle adjustment.Premium thermal management by high heat conductivity aluminum alloy and thermal fins. Pure Polyester powder coating in Standard Grey Colour. Precise structure and multi-protection silicon rubber seal guarantees the fixture IP66 rated. Height – 122mm, Dia.-170mm, Weight - 2Kgs. Power LED Module with high efficacy LED's,on Printed Circuit Board with metal core plate.,Electronic Power Supply for LED Module,which offers Protection against Short Circuit, Over- Voltage & Over- Current, with in-built surge protection.Lens made of PC which should offer wide range of narrow,medium & wide beam angles. Estimated LED Lifetime is L70-100,000 hours minimum.LM80 report from LED Manufacturer should be submitted. BIS test report with Name of Manufacturer should be same as the brand proposed,as per IS10322 from Intertek/UL lab & BIS Certificate with Name of Manufacturer should be same as the brand proposed, should be submitted. Minimum Light fixture Lumen output is 2200Lumens. Sample Should be submitted for concerned engineer incharge for approval of light fixture.

21

-

-

... More
Circular Ground Buried Uplight Body made made of die cast aluminium using pressure die casting process.Protection screen in clear tempered glass with high impact resistance 15-20W,LED,3000k, IP 67. Pure Polyester powder coating in Standard Grey Colour. Precise structure and multi-protection silicon rubber seal guarantees the fixture IP67 rated. Dia.–210mm, Height.-120mm, Weight - 2.4Kgs. Power LED Module with high efficacy LED's, on Printed Circuit Board with metal core plate. Lens made of PC which should offer wide range of narrow,medium & wide beam angles. Estimated LED Lifetime is L70-50,000 hours minimum.LM80 report from LED Manufacturer should be submitted.Minimum Light fixture Lumen output is 1200Lumens. Sample Should be submitted for concerned engineer incharge for approval of light fixture.

44

-

-

... More
Linear Wall Washer The housing in light weight, made of high strength aluminium and coated by static powder making it weather resistant.Protection screen in clear tempered glass with high impact resistance 25-30W,LED,3000k, IP 66. High precision dial ensures precision angle adjustment. Pure Polyester powder coating in Standard Grey Colour. Precise structure and multi-protection silicon rubber seal guarantees the fixture IP66 rated. Length-1000mm,Height – 66mm, Width.-64mm, Weight - 3.95Kgs. Power LED Module with high efficacy LED's, on Printed Circuit Board with metal core plate. Lens made of PC which should offer wide range of narrow,medium & wide beam angles. Estimated LED Lifetime is L70-100,000 hours minimum.LM80 report from LED Manufacturer should be submitted.BIS safety test report with manufacturer name same as brand proposed, as per IS10322 from Intertek/UL lab & BIS Certificate with manufacturer name same as brand proposedshould be submitted. Minimum Light fixture Lumen output is 1600Lumens. Sample Should be submitted for concerned engineer incharge for approval of light fixture.

40

-

-

... More
Landscape Lighting Pole Top Light Light fixture body made of Die cast aluminium using pressure die-casting process 115-125W, Power Module LED, 3000K. Protective Screen in PC(IK08).Hole for coupling on pipes Ø 60 mm, for lateral installation.Pure Polyester Powder Coating in Grey Colour. Silicone gasket enusures the IP protection. IP Rating - IP 66. Height – 87mm,Length-567mm,Width -233mm,Weight – 2.35Kgs. Power LED Module with high efficacy LED's on Printed Circuit Board with metal core plate.Colour Rendering Index: Ra 70. Electronic Power Supply for LED Module, which offers Protection against Short Circuit, Over- Voltage & Over- Current, with in-built surge protection. Estimated LED Lifetime is L70 @ 100,000 hours@Ts 85°C minimum. LM80 report from LED manufaturer should be submitted.The Light fixture shall be in compliance with IEC 60598/IS 10322-Supporting Test Report from UL/UL Authorised/3rd party NABL aboratory should be submitted along with BIS Certificate with manufacturer name same as brand proposed.Light Fixture Sample should be submitted for approval from concerned engineer-in charge.

15

-

-

... More
6M HEIGHT DOUBLE ARM ARCHITECTURAL POLE 6M Height Twin arm pole made in combination of mild steel pipe sections of 89mm dia. and Bracket of 60mm dia with horizontal length of 500mm. The pole to be provided with a suitable size steel base plate. This mounting steel base plate along with foundation bolts of suitable size to be used for ensuring firm grouting into the specially designed RCC foundation. After Fabrication, Entire Pole is hot dip galvanized (60 microns Minimum) for the effective corrosion resistance. The hot dip Galvanised pole should be provided with an inbuilt junction box to fix 32A connectors and 6A MCB, at the bottom - the inbuilt box should have a flush door of suitable size. wind pressure calculation as per IS 875(part-3) & structural calculation report as per EN40 should be submitted to verify the pole strength. Entire pole shall be made to provide pleasing aesthetics as approved by Concerned Engineer in-charge. Pole & it's parts are painted in 3 layer coating(coating thickness-100 microns minimum) in which 1st layer with etch primer, 2nd layer with epoxy primer & 3rd final layer with PU paint.

15

-

-

... More
ARCHITECTURAL 4M POST TOP POLE 4M height post top Pole Made of mild steel pipe sections 114mm dia. & 76mm dia. Entire pole shall be made to provide pleasing aesthetics as approved by Concerned Engineer in-charge. After Fabrication, Entire Pole is hot dip galvanized(60 microns Minimum ) for the effective corrosion resistance . The hot dip Galvanised pole should be provided with an inbuilt junction box to fix 32A connectors and 6A MCB, at the bottom - the inbuilt box should have a flush door of suitable size. The pole to be provide with suitable size base plate. This base plate along with foundation bolts of suitable size to be used for ensuring firm grouting into the specially designed RCC foundation. wind pressure calculation as per IS 875(part-3) & structural calculation report as per EN40 should be submitted to verify the pole design. Pole and its parts are painted in 3 layer coating(coating thickness-100 microns minimum) in which 1st layer with etch primer, 2nd layer with epoxy primer & 3rd final layer with PU paint - customised colour Metallaic NERI Grey. ARCHITECTURAL 4M POST TOP POLE/DW Windsor/GHM

20

-

-

... More
LIGHT FIXTURE 20-30W Power Module LED, 3000K Upper part in circular shape & Lower part in "V" shape,both are in single piece made of die-cast aluminum using pressure die casting process 20-30W Power Module LED, 3000K. manufacturer name/logo should be embosed on the body. Prismatic screen in Flat tempered glass. Pure polyester powder coating in customised colour Metallaic Grey. Silicone gasket ensures the IP Rating - IP 66. Height – 500mm,Diameter - 420mm,Weight -8Kgs., Area Exposed to Wind(S) - 0.08 m2 Power LED Module with Company /brand name printed on PCB with the metal core plate, in compliance with IEC 62031.LED Chips of CREE/NICHIA/OSRAM/LUMILEDS make- same should be supported by LED manufacturer's tech sheet . Colour Rendering Index: Ra 70. Electronic Power Supply for LED Module, which offers Protection against Short Circuit, Over- Voltage & Over- Current, with in-built surge protection a minimum of 4kV (an additional surge protection device of 10kV also provided in-built the fixture). Optics with refractive lens in PMMA which offers Type II/III/IV/V distribtuion.LED Lifetime @L90 1,00,000hours@Ts 85°C. LM 80 report & TM 21 calculation should be submitted to support the same.The Light fixture shall be in compliance with IEC 60598/IS 10322(Supporting Test Report from UL/UL Authorised/Intertek Laboratory should be submitted. Sample should be submitted for approval from concerned engineer-in charge.

20

-

-

... More
BOLLARD- The Bollard suitable for on ground installation,is made of 3mm thick(minimum) extruded aluminium pipe 10-15W,LED Module, 3000K, IP65. Top cover(156mm dia.,8mm thick & weight-0.7Kgs.) with company name/logo engraved is made of die cast aluminium in single piece. It's screen made of acrylic with high impact resistance,in single piece. Pure polyester powder coating in Standard Grey Colour. IP Rating - IP 65. Height – 1000mm, Dia - 127mm LED Module on Printed Circuit Board with metal core plate.Colour Rendering Index: Ra 70.Electronic Power Supply for LED Module, which offers Protection against Short Circuit, Over- Voltage & Over- Current. Estimated LED Lifetime L80 @50,000 hours minimum.

24

-

-

... More
Wall Recessed Light, 8-10W,LED,3000k, Body-Die-casting aluminium Body with screen in tempered glass.Body colour-RAL 9005 Matt, Dimension-260mm(L)x245mm(H)x60mm(D),Weight-0.8kg. Electronic Driver which offers Protection against Short Circuit, Over-Voltage & Over- Current, IP 65 protection,CRI 70,Estimated Lifetime-L70 @ 50,000hours minimum.LM80 report from LED Manufacturer should be submitted.Sample should be submitted for approval from concerned engineer-in charge.

10

-

-

... More
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions. 4 core 6 sq.mm Cu arm.

200

-

-

... More
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions. 3 core 6 sq.mm Cu arm.

400

-

-

... More
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions. 3 core 4 sq.mm Cu arm.

150

-

-

... More
Supplying of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification complete in all respect as required as per site conditions. 3 core 2.5 sq.mm Cu arm.

350

-

-

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm

1100

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of bimettalic crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 4 core 6 sq.mm Cu arm.

15

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of bimettalic crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 3 core 10 sq.mm Cu arm.

15

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of bimettalic crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 3 core 4 sq.mm Cu arm.

20

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed Aluminium / copper conductor armoured cables of 1100 volt grade including supplying and fixing of bimettalic crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 3 core 2.5 sq.mm Cu arm.

40

-

-

... More
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 100 mm dia

20

-

-

... More
Feeder Pillar (For External Landscape lighting) IP 55 for outdoor Protection Incomer 63 Amps 4 pole MCB, Photocell Sensor Bus Bars 100 Amps TPN Aluminium bus bars with heat shrinkable insulation sleeve. - 1 Set Outgoing 40 Amps 4 pole MCB incomer with 40 Amps TP contactor 0-24 hours timer auto / manual and outgoings including 10 No. 10/16/20 Amps SP MCB with 3 Nos. 32 Amps DP RCCB’s of 30 mA leakage current with separate neutral link of each phase- 1 set (33%) 40 Amps 4 pole MCB incomer with 40 Amps TP contactor 0-24 hours timer auto / manual and outgoings including 10 No. 10/16/20 Amps SP MCB with 3 Nos. 32 Amps DP RCCB’s of 30 mA leakage current with separate neutral link of each phase- 1 set (33%) 40 Amps DP MCB - 3 set 63 Amps 4 Pole MCB - 3 set Design, fabrication, assembling, wiring and supply, installation, testing and commissioning of Distribution Panels fabricated out of (load bearing member of 2mm and non load bearing member 1.6 mm thick) CRCA sheet steel in cubicle compartmentised modular 3b construction, free standing floor mounted with bottom cable entry, dust and vermin proof with reinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided at the bottom of the panels with appropriate stand etc. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminals shall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in case of large panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels.

1

-

-

... More
Supply, installation, testing and commissioning of 63 Amps 4 Pole Industrial socket outlet with MCB including Outdoor duty Polycarbonate enclosure of approved make (IP 68).

2

-

-

... More
Supply, installation, testing and commissioning of 40 Amps DP Industrial socket outlet with MCB including Outdoor duty Polycarbonate enclosure of approved make (IP 68).

2

-

-

... More
IP CCTV System: Supply, installation, testing and commissioning of indoor UL Listed IP N/W colour dome camera, 1/3'' CCD / CMOS sensor, 1.3 MP resolution, varifocal 3-10 mm lens, Auto Iris, Day Night cameras, Vandal Proof & Motion detection, POE, (high resolution cameras / 4CIF / 25 FPS) ONVIF compliant complete with IP 55 Dome Housing, Connectors, Lens, Camera Mounts, Power Supply, I/O and all Ancillary Equipment & all accessories.

135

-

-

... More
Supply, installation, testing and commissioning of Outdoor (IP 66) UL Listed IP PTZ type colour camera,1/3'' CCD/CMOS sensor, 1.3 MP resolution, varifocal 3-10 mm lens , Auto Iris, Day Night cameras, Vandal Proof & Motion detection,ONVIF compliant POE, complete with IP 55 Dome Housing, Connectors, Lens, Camera Mounts, Power Supply, I/O and all Ancillary Equipment & all accessories.

3

-

-

... More
Supply, installation, testing and commissioning of Layer 2 managed switch with 24 ports (RJ-45), POE as to support all cameras 15% spare ports complete with supply. The switch shall have 1 GB port to communicate with other switches including Passive components inbuilt 2 SFP ports including SFP modules, POE compliant ports, rack mountable, SMPS power supply & other termination accessories (Like Pigtails/ LIUs/Convertors/Splicing equipment , Patch panel, Patch Cord Etc) complete as per specifications and as required.

3

-

-

... More
Supply, installation, testing and commissioning of Layer 3 managed switch with 24 ports (RJ-45), POE as to support all cameras 15% spare ports complete with supply. The switch shall have 1 GB port to communicate with other switches including Passive components inbuilt 2 SFP ports including SFP modules, POE compliant ports, rack mountable, SMPS power supply & other termination accessories (Like Pigtails/ LIUs/Convertors/Splicing equipment , Patch panel, Patch Cord Etc) complete as per specifications and as required.

3

-

-

... More
Supply, Installation, Testing and Commissioning of UL listed Network Video Recorder including data base server for recording real time audio - video and data applications for 140 Cameras, of suitable Raw Capacity, capability to eliminate Single Points of Failure, redundant Power Supplies, redundant fans, .The NVR storage should store all cameras at 1.3 MP resolution for minimum 30 days backup @25 FPS,complete as per specifications and as required. The NVR shall be compatible with ONVIF compliant cameras. the required hardware and the software with operating system, video management client viewing license for 3 User for monitoring of all camera simultaneously complete as per specifications and as required.

1

-

-

... More
Supply, installation, testing and commissioning 21" LCD Screen including all required accessories complete as per specifications and as required.

10

-

-

... More
Supply, installation, testing and commissioning of video management client workstations as required including 21" LCD, keyboard, mouse, and all required accessories complete as per specifications and as required. The licence support shall be for life time.

2

-

-

... More
Supply, laying, connecting , testing and commissioning of un-armoured 6C Single Mode Optic Fibre Communication Cable including required terminations, Junction Box, Connectors, LIU, SFP, Pigtails, Cable tie`s & Tags including MS conduit as per specification and as required.

60

-

-

... More
Supply and fixing of following sizes of steel conduit alongwith the accessories in surface/recess including painting in case of surface conduit or cutting the wall and making good the same incase of recessed conduit as required. 20mm dia

500

-

-

... More
Supply and fixing of following sizes of steel conduit alongwith the accessories in surface/recess including painting in case of surface conduit or cutting the wall and making good the same incase of recessed conduit as required. 25mm dia

500

-

-

... More
Supplying and drawing Flexible Multicore Cable manufactured with electrolytic grade flexible copper with low conductor confirming to IS 8130-1984 and (Virgin) PVC insulation sheathed suitable for working voltage upto 1100V as per IS- 694:2010 2C X 1.5 mm2

1800

-

-

... More
Solar PV Plant: Supply, Installation, Testing and Commissioning of ongrid Solar Photovoltaic Power Plant conforming to MNRE specifications as amended, consisting of Mono/Poly Crystalline silicon solar cells, net metering facility, necessary protections, earthing, mounted on Aluminium/GI structure of suitable strength with following components complete as required:- a) Solar Photovoltaic Module of capacity 330 Wp or above , manufactured in India, conforming to IS 14286/IEC 61215, IS/IEC 61730-Part-1, IS/IEC 61730-Part-2. Solar Photovoltaic Module conversion efficiency shall not be less than 16.5%. PV modules used in solar power plants/ systems must be warranted for their output peak watt capacity, which should not be less than 90% at the end of 10 years and 80% at the end of 25 years. b) Power Conditioning Unit (PCU) of 350-800 V DC Input voltage range and 400 V AC, three phase, 4 wire, 50Hz +/- 2.5 Hz, output voltage suitable to generate AC Power with efficiency not less than 97%, total harmonic distortion less than 3% and suitable for ambient temperature from 0 to 50 degree C. The PCU shall adjust the voltage and frequency level to suit the Grid Voltage Frequency. c) Data Monitoring System complete with accessories. d) Fixing of Array junction box & Main junction box with IP 65 protection and termination arrangement for incoming and outgoing cable along with glands, lugs and other accessories etc. as required. e) Lightning and surge voltage protection. f) Connections & Interconnections by supplying & fixing required size XLPE insulated copper conductor 1.1 kV grade armoured power and control cables between solar modules, main power cable to grid supply PCU unit along with supplying & fixing of necessary channel/conduit lugs and other accessories etc. as required.

200

-

-

... More
Compact Substation (CSS) for 1250 KVA Transformer Design, manufacture and supply, unloading and shifting to store, installation in correct aligned position, testing and commissioning of 11 / 0.415 KV compact package sub station comprising : - 1 No 11 KV 630 A compact SF6 RMU (2 No cable isolating switch & one tap off VCB) -1 No. 1250 kVA 11 / 0.415 KV Dry type transformer, percentage impedance Z= 5%, copper wound with Dyn11 connection and neutral brought out for earthing. The transformer shall be provided with (–) 15% and (+) 5% OFF load tap changer with RTCC Panel on HT side. HT side cable termination box shall be suitable for 11 KV, 3C x 240mm2 XLPE cable and LT side terminal box shall be suitable for terminating cables / Busduct. The transformer shall be supplied all standard fitting viz dial type oil and winding temperature indicator, all alarm contacts, thermistors for Alarm and Trip, winding temperature relay unit with Alarm and trip, Provision for remote metering for winding temperature, indications for all units, lifting lugs, earthing studs and marshlling box including some spare parts etc. complete in all respect as required as per specification. Transformer's 'No load losses' & 'Full Load Losses" shall be as per latest ECBC. '-LT panel consisting of 1 no. 2000 Amp 4 Pole ACB as incomer Package sub-station shall be complete in all respect as required as per site requirements. Note : The rate shall also include the following : Supporting rigid frame work. All fixing accessories such as foundation bolts, nuts and bolts etc as required. Touching up all damaged paint with approved paint shade. Interlocking shall be provided between transformer and VCB HT breaker panel. When transformer open respective HT breaker shall be tripped. Degree of protection for transformer enclosure shall be outdoor duty Provision shall be made to be hooked up with BAS for status indication. All protection relays shall be microprocessor based.

1

-

-

... More
HT Cable: Supplying of following 11 kV grade XLPE insulated Aluminium conductor armoured cables as per specifications complete in all respect as required as per site condition. 3 core 240 sq. mm Al arm (E)

1000

-

-

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. 3 core 240 sq. mm Al arm (E)

1000

-

-

... More
Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 3 core 240 sq. mm Al arm (E)

2

-

-

... More
Supplying and making Straight Through cable Jointing with heat shrinkable jointing kit complete with all accessories including ferrules suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 3 core 240 sq. mm Al arm (E)

2

-

-

... More
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like sockets ,bends coupler etc. conforming to IS 14930 part II Complete with fitting & cutting ,jointing etc.direct in ground (75cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc complete as required (for HT Line 900mm below ground level & 20% extra cost included in DSR Rate) 200 mm Dia (OD -200mm & ID -175 mm nominal)

1000

-

-

... More
Supply, installation, testing and commissioning of 100AH capacity 24 volts DC hermetically sealed maintenance free lead acid batteries duly charged including battery charger unit with provisions of Boost Charing, and Float charging. Suitable for 240 V, including DC DB single phase + 10% AC, 50 Hz supply as per specifications .

1

-

-

... More
Supply & Laying of non skid Electro mat 1mtr wide and 2.5 mm thick 11KV grade IS 15652 as required including cutting to required length complete as per requirement of local electricity authorities.

30

-

-

... More
Supply and fixing in position the approved “Shock Treatment Charts” written in English and Local Language. These charts shall be framed in teak wood frame and covered with glass.

20

-

-

... More
Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.

4

-

-

... More
Supply and fixing position the approved single line diagram framed in 1000 x 100 mm size glass frame and installed in main LT Panel Room.

1

-

-

... More
Supply of tool kit, first aid box with all accessories required for operation and maintainence for 415 volt & 11 kV equipment with 1 pair 11 kV rubber hand gloves of approved make.

1

-

-

... More
Supply and fixing cable route marker with 10cm X 10cm X 5mm thick G.I plate with iscription there bolted / welded to 35mm X 35mm X 6mm angle iron, 60cm long and fixing same in ground as required

25

-

-

... More
DG Set and Accesories: Supplying, installing, testing and commissioning of Diesel Generator set 500 kVA/400 kW with following specifications. Power rating as per standard reference condition as per-BS 5514/ISO 3046/ ISO 8528 & IS 1002/ISO 3046 Generator set specifications. Engine: Diesel generating set are rated at 1500RPM and conform to ISO 8528 specifications. The engines are radiator cooled, four stroke and multi cylinder, conforming to ISO 3046. The scope of supply includes: Electrical starter motor12V DC Battery charging alternator, Bosch fuel system with mechanical governor, A1 Class. Spin-on lube oil filter, Spin-on dual fuel filter with water separator, Turbocharger, Charge air cooler, Silencer (Hospital grade), Dry type air cleaner, Shutoff coil, Flywheel and flywheel housing, First fill of lube oil and coolant, Safety for low lube oil pressure, Safety for high water temperature, Permissible overload of 10% for one hour in 12 hours of operation Capacity of Fuel Tank: Fuel tank suitable for 8 hours of operation Alternator: Alternator is suitable for operation at 1500 RPM, 415 V, 0.8 pf (lag) suitable for 50 Hz, 3 phase, 4 wire systems, conforming to IS/IEC 60034-1. The Alternator is brush less type, screen protected, revolving field, self excited, self regulated through an AVR. The alternator shall have± 1.0% Voltage regulation (max) in static conditions- IP: 23 protections with insulation class F&H. Mounting arrangement: Engine and alternator are mounted on a common MS fabricated base frame with AVM pads. Control Panel: The control panel is manufactured with 14/16 gauge CRCA sheet and is powder coated for weather-proof and long lasting finish. The control panel consists of the following parts:- PS0500 Controller, Aluminium bus bars with suitable capacity within/outgoing terminals, Indicating lA for 'Load On' and 'Set Running', Instrument fuses duly wired and ferruled, MCCB of suitable rating with overload and short circuit protections. Genset Controller: microprocessor based generator set monitoring and control system. The control provides a simple operator interface to the generator set, manual and remote start/ stop control, shutdown fault indication, and an LCD hour counter. The integration of all functions into a single control system provides enhanced reliability and performance compared to conventional generator set control systems. This control has been designed and tested to meet harsh environment in which gensets are typically applied. Features, Functions, protections 16 character x 2 line alphanumeric LCD display with LED Backlight Operator interface, Provide a record of most recent fault conditions. Fault history stored in the control non volatile memory, Provide Alternator Data. Voltage (1 ph or 3 ph line to line and line to neutral voltage, Current (1 ph or 3 ph), kVA (3 ph and total), Frequency, Provide Engine Data, Starting battery voltage, Engine running hours, Engine Temp, Engine oil pressure, Control includes provision for Service adjustment and calibration of DG control functions, Voltage, frequency selection, Configurable input and output set up, Meter calibration, Engine controls, Power Start operates on 12 VDC batteries,-Auto start mode accepts a ground signal from remote devices to automatically start the DG set The remote start will also wake up the control system from sleep mode. Engine Starting -The control system supports automatic engine starting, Primary and back up start disconnects are achieved by battery charging alternator feedback or main alternator output frequency. Controller provide configurable time delay of 0-300 sees to start after remote start signal and time delay of 0- 600secs prior to shut down after stop signal. Sleep mode increase battery life. Configurable current settings from low to minimize current draw when genset is not working. Engine Protective functions include, Configurable alarm output, Emergency stop: Annunciated whenever an emergency stop signal is received by the control. Low lube oil pressure warning and Shutdown, High engine water temp warning / Shutdown, Low .coolant temp warning, Sensor failure indication, Low and high battery voltage warning, Weak battery warning, Fail to start shut down, Cracking lockout: Control will not allow the starter to engage or to crank the running engine Cyclic cranking: Configurable for the number of starting cycle, (1 to 7) and duration of crank and rest periods. Alternator Protective functions includes, - High and Low AC voltage shut down, Under and Over frequency shutdown / warning, Loss of sensing voltage input shut down. Acoustic enclosure: The acoustic enclosure shall be made of 1.6 mm thick CRCA sheets in suitable approved shade and a structural/ sheet metal base frame painted in black. The walls of the enclosure are insulated with fire retardant foam so as to comply with the 75dBA at 1 m sound levels specified by Ministry of Environment & Forest The enclosure has the following features: Specially designed to meet stringent MOEF/CPCB norms of 75dBA @ 1 m at 75% load under free field conditions, Two point lifting for easy handling at customer site, Designed to have optimum serviceability, Air inlet louvers specially designed to operate at rated load made on special purpose CNC machines for consistency in quality and workmanship, Powder coated for long lasting service life and superior finish, With UV resistant powder coating, can withstand extreme environment, Use of special hardware for longer life, Insulation material meets exacting IS 8183 specifications for better sound attenuation, Flush styling - no projections, Fluid drains for lube oil and fuel, Fuel filling point inside the enclosure. The complete set shall have sufficient safety and adhere to NEC, NBC 2016, IEC, CPWD specifications, PCB norms and KSGEI Acts and Rules.

1

-

-

... More
Supplying, installing, testing and commissioning of Diesel Generator set 750 KVA/ 600 KW with following specifications. Power rating as per standard reference condition as per-BS 5514/ISO 3046/ ISO 8528 & IS 1002/ISO 3046 Generator set specifications. Engine: Diesel generating set are rated at 1500RPM and conform to ISO 8528 specifications. The engines are radiator cooled, four stroke and multi cylinder, conforming to ISO 3046. The scope of supply includes: Electrical starter motor12V DC Battery charging alternator, Bosch fuel system with mechanical governor, A1 Class. Spin-on lube oil filter, Spin-on dual fuel filter with water separator, Turbocharger, Charge air cooler, Silencer (Hospital grade), Dry type air cleaner, Shutoff coil, Flywheel and flywheel housing, First fill of lube oil and coolant, Safety for low lube oil pressure, Safety for high water temperature, Permissible overload of 10% for one hour in 12 hours of operation Capacity of Fuel Tank: Fuel tank suitable for 8 hours of operation Alternator: Alternator is suitable for operation at 1500 RPM, 415 V, 0.8 pf (lag) suitable for 50 Hz, 3 phase, 4 wire systems, conforming to IS/IEC 60034-1. The Alternator is brush less type, screen protected, revolving field, self excited, self regulated through an AVR. The alternator shall have± 1.0% Voltage regulation (max) in static conditions- IP: 23 protections with insulation class F&H. Mounting arrangement: Engine and alternator are mounted on a common MS fabricated base frame with AVM pads. Control Panel: The control panel is manufactured with 14/16 gauge CRCA sheet and is powder coated for weather-proof and long lasting finish. The control panel consists of the following parts:- PS0500 Controller, Aluminium bus bars with suitable capacity within/outgoing terminals, Indicating lA for 'Load On' and 'Set Running', Instrument fuses duly wired and ferruled, MCCB of suitable rating with overload and short circuit protections. Genset Controller: microprocessor based generator set monitoring and control system. The control provides a simple operator interface to the generator set, manual and remote start/ stop control, shutdown fault indication, and an LCD hour counter. The integration of all functions into a single control system provides enhanced reliability and performance compared to conventional generator set control systems. This control has been designed and tested to meet harsh environment in which gensets are typically applied. Features, Functions, protections 16 character x 2 line alphanumeric LCD display with LED Backlight Operator interface, Provide a record of most recent fault conditions. Fault history stored in the control non volatile memory, Provide Alternator Data. Voltage (1 ph or 3 ph line to line and line to neutral voltage, Current (1 ph or 3 ph), kVA (3 ph and total), Frequency, Provide Engine Data, Starting battery voltage, Engine running hours, Engine Temp, Engine oil pressure, Control includes provision for Service adjustment and calibration of DG control functions, Voltage, frequency selection, Configurable input and output set up, Meter calibration, Engine controls, Power Start operates on 12 VDC batteries,-Auto start mode accepts a ground signal from remote devices to automatically start the DG set The remote start will also wake up the control system from sleep mode. Engine Starting -The control system supports automatic engine starting, Primary and back up start disconnects are achieved by battery charging alternator feedback or main alternator output frequency. Controller provide configurable time delay of 0-300 sees to start after remote start signal and time delay of 0- 600secs prior to shut down after stop signal. Sleep mode increase battery life. Configurable current settings from low to minimize current draw when genset is not working. Engine Protective functions include, Configurable alarm output, Emergency stop: Annunciated whenever an emergency stop signal is received by the control. Low lube oil pressure warning and Shutdown, High engine water temp warning / Shutdown, Low .coolant temp warning, Sensor failure indication, Low and high battery voltage warning, Weak battery warning, Fail to start shut down, Cracking lockout: Control will not allow the starter to engage or to crank the running engine Cyclic cranking: Configurable for the number of starting cycle, (1 to 7) and duration of crank and rest periods. Alternator Protective functions includes, - High and Low AC voltage shut down, Under and Over requency shutdown / warning, Loss of sensing voltage input shut down. Acoustic enclosure: The acoustic enclosure shall be made of 1.6 mm thick CRCA sheets in suitable approved shade and a structural/ sheet metal base frame painted in black. The walls of the enclosure are insulated with fire retardant foam so as to comply with the 75dBA at 1 m sound levels specified by Ministry of Environment & Forest The enclosure has the following features: Specially designed to meet stringent MOEF/CPCB norms of 75dBA @ 1 m at 75% load under free field conditions, Two point lifting for easy handling at customer site, Designed to have optimum serviceability, Air inlet louvers specially designed to operate at rated load made on special purpose CNC machines for consistency in quality and workmanship, Powder coated for long lasting service life and superior finish, With UV resistant powder coating, can withstand extreme environment, Use of special hardware for longer life, Insulation material meets exacting IS 8183 specifications for better sound attenuation, Flush styling - no projections, Fluid drains for lube oil and fuel, Fuel filling point inside the enclosure. The complete set shall have sufficient safety and adhere to NEC, NBC 2016, IEC, CPWD specifications, PCB norms and KSGEI Acts and Rules.

1

-

-

... More
Supply, installation, testing and commissioning of following MS piping heavy duty, along with bends as per thickness mentioned for exhaust system as per IS: 3589 and 1239 (Part-I) amended and revised to date including all accessories as required at site. 200 mm NB ERW MS pipe Heavy duty type

60

-

-

... More
Supply, installation, testing and commissioning of following MS piping heavy duty, along with bends as per thickness mentioned for exhaust system as per IS: 3589 and 1239 (Part-I) amended and revised to date including all accessories as required at site. 300 mm NB ERW MS pipe Heavy duty type

45

-

-

... More
Supply and fixing of SS Bellows including flanges, nut, bolts as required for following sizes 200 mm dia

2

-

-

... More
Supply and fixing of SS Bellows including flanges, nut, bolts as required for following sizes 300 mm dia

1

-

-

... More
Supplying, laying, tesing & commissioning of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification in cable trays / ducts clamped to wall with suitable clamps including, saddles fixing bolts, connecting testing and commissioning complete in all respect as required as per site conditions. 12 core 2.5 sq.mm shielded Cu. Cable

30

-

-

... More
Supplying, laying, tesing & commissioning of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification in cable trays / ducts clamped to wall with suitable clamps including, saddles fixing bolts, connecting testing and commissioning complete in all respect as required as per site conditions. 4 core 2.5 sq.mm Cu arm.

60

-

-

... More
Supplying, laying, tesing & commissioning of following 1100 volt grade XLPE insulated PVC sheathed Aluminium/Copper conductor armoured/Unarmored cables as per specification in cable trays / ducts clamped to wall with suitable clamps including, saddles fixing bolts, connecting testing and commissioning complete in all respect as required as per site conditions. 2 core 4 sq.mm Cu arm.

60

-

-

... More
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Upto 35 sq. mm (clamped with 1mm thick saddle)

200

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed copper conductor armoured cables of 1100 volt grade including supplying and fixing of Copper crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 4 core 2.5 sq.mm Cu arm.

10

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed copper conductor armoured cables of 1100 volt grade including supplying and fixing of Copper crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 12 core 2.5 sq.mm Cu arm.

10

-

-

... More
Supplying and making Cable end termination of the following XLPE insulated PVC sheathed copper conductor armoured cables of 1100 volt grade including supplying and fixing of Copper crimping lugs, double compression glands with earthing testing and commissioning complete in all respect as required as per site conditions. 2 core 4 sq.mm Cu arm.

10

-

-

... More
Supplying all the material for fabrication of 30 mtr High lattice tower for supporting 2 Nos. Chimmnies for 750 KVA & 500KVA DG Sets complete with suitable size M.S channel, M.S angle, nut, bolt etc. complete including 1 coat of red-oxide & 2 coat of enamel paint and other Accessories as required at the site of work. Lightning arrestor & 40 x 6 mm GI strip including 2 Nos. earthing stations with GI plate, also to be included in the item. Note :- supporting structure for horizontal exhaust pipes is included here. Lightening Arrstor Non steamer type-- 2 Nos. Aviation light 2 Nos. 25x3 mm GI strip 100 mtr. Isolator switch 2 Nos. Insualtors @ 0.5 mtrs 70 Nos. Chemical earthing 2 Nos. 50x6 mm GI strip 30 Mtr 30 mtr high supporting structure for DG chimnies described as above

22000

-

-

... More
HVAC:Supplying, installing, testing and commissioning of single/multi compressor AHRI Certified Water Cooled Screw Water Chilling Machines (along with VFD) The delivered capacity of each machine shall be 200 TR Actual at the specified conditions under Basis of Design and comprise of machine mounted motor with closed transition star delta starter, water cooled condenser, refrigerant piping and control wiring, first charge of refrigerant & oil and accessories including safety controls mounted in central micro-processor based console panel, sockets, flow switches, sensors, cable termination adopter box with suitable rating of 4 pole MCCB/ACB. Refrigerant used as shall be Ozone friendly HFC. vibration isolators shall be provided for the chiller and included in price. Evaporator shall be factory insulated with 25 mm Thick black cloth faced Nitrile Rubber/Elastomeric Foam as per OEM standard. Flow switch shall be provided at evaporator and condenser duly interlocked for safe operation of chiller.Condenser & Evaporator shell shall be constructed with ASME certifited rolled carbon steel. Unit mounted/Floor mounted VFD to be provided. In case of floor mounted VFD, the cost of cabling & cable trays from VFD to chiller shall be included in the chiller price. Sound level should not be more than 75 dB(A) at 6 m distance from the unit. Water marine boxes shall be provided at Condensers. Cable terminal box shall be suitable for receiving incoming Aluminium Cabling. Grooved coulping for chiller and condenser at inlet & outlet. BMS card shall be included in the price and vendor shall provide open protocol and suitable to connect with Modbus/ Lonwork/ Bacnet. Motor suitable for 415±10%, 50 cycles, 3 phase AC supply. a) Testing point at site/design Condition at any single point are following .1) 100 % Load 2) 50% Load 3) 25% Load 4) 100% Load (Design plus 5 Deg °F at condenser entering water temerature) Chiller should also be capable to run at minimum 60° F. condenser inlet temp. The Evaporator performance shall be as follows: Chilled Water Temperature- Inlet - 54 °F, Chilled Water Temperature- Outlet - 44 °F,Fouling factor- 0.0005 FPS Chilled water flow 480 USGPM, Pressure drop Max 10 ft, The Condenser performance shall be as follows:Condenser Water Temperature- Inlet - 80 °F Condenser Water Temperature- Outlet - 90 °F, Fouling factor - 0.001 FPS, Condenser water flow - 600 USGPM, Pressure drop - Max 15 ft, Chiller sequencing and operation should be designed in such a way that one chiller starts with minimum capacity initially and load to the maximum and enable the next chiller to start on demand through Building Management. Anti-freeze  & communication card etc. Micro-processor based controls with alpha-numeric display in English for all operating parameters such as supply voltage, frequency, load current, chilled water inlet, chilled water outlet, condenser inlet and outlet temperature parameters, operating pressures etc., It should be compatible to be be integrated with BMS / chiller plant manager of any make communicating on any one of the standard protocols such as BACNET / MODBUS. The required hardware and software with all accessories complete for communication. Co-ordination with low side HVAC contractor for chiller commissioning, Power control termination, testing etc. The bidder shall submit a computerized selection sheet of the chiller offered as obtained from the manufacturer along with their offer from the latest AHRI listed software version. Non-submittal of the computerized selection sheet shall be liable for bid rejection. The cooler and condenser shall have applicable pressure code vessel stamping on the nameplate as a standard, without which the machines will be rejected. Clearing the goods including customs clearance for all items as described under supply Loading to the transport vehicle Local transport by road including transit insurance. Interaction and clearance at various local points Unloading at site Shifting of material to the point of installation including lifting using mechanical means to the designated area of Building  Note : 1.   Vendor to study the methodology to lift/shift  the chillers to Plant Room and only consultant/client approval approved methodology to be adopted.   2.  Necessary permissions from authorities to be taken by the contractor before lifting / shifting the chillers 3. Necessary Insurance for the workmen, material and third party liability. Installation, leveling, testing and commissioning charges including all consumables, tools and equipment. Any items and works not specifically mentioned above but as required for the works. (contractor to specify the nature of work / item)Minimum COP at AHRI conditions shall be as per ECBC Plus Maximum IkW/ TR at full load - 0.7 max, mini NPLV 0.38 Water Chilling Machines as described above

3

-

-

... More
Single testing point of Water Chilling Machine as described above (For one Chiller)

1

-

-

... More
Supplying, installation, testing and commissioning of Automatic Tube Cleaning System suitable for Chillers, capacity as mentioned above along with the following size of Condenser Nozzle connection and configuration of Chilling Unit(s).All above and as mentioned in Specifications.(200 mm for condenser )

1

-

-

... More
Supplying, installing, testing and commissioning of Long coupled Vertical Inline Pumps duly factory mounted on a base with electric motor. The pump motor shall be IE-3 efficiency (minimum 90%) and suitable for 415 +10% volts, 50 cycles, 3 phase power supply. Pumps will adhere to following performance characteristics : The pump performance shall meet the criterion laid down under ASHRAE 90.1-2019 and with minimum efficiency as specified. Thermal insulation & cladding of the chilled water pumps will be included. Secondary Pump shall operate through variable frequency drives. The rating of pumps shall be as follows: Primary Chilled Water Pumps- Water flow rate : 480 USGPM Head : 40 ft of water Motor HP not to exceed : 10 HP Efficiency : 75% or more Primary Chilled Water pump as described above including 1 No. standby.

3

-

-

... More
Supplying, installing, testing and commissioning of Long coupled Vertical Inline Pumps duly factory mounted on a base with electric motor. The pump motor shall be IE-3 efficiency (minimum 90%) and suitable for 415 +10% volts, 50 cycles, 3 phase power supply. Pumps will adhere to following performance characteristics : The pump performance shall meet the criterion laid down under ASHRAE 90.1-2019 and with minimum efficiency as specified. Thermal insulation & cladding of the chilled water pumps will be included. Secondary Pump shall operate through variable frequency drives. The rating of pumps shall be as follows: Secondary Chilled Water Pumps- Water flow rate : 480 USGPM Head : 80 ft of water Motor HP not to exceed : 15 HP Efficiency : 75% or more Secondary Chilled Water pump as described above including 1 No. standby.

3

-

-

... More
Supplying, installing, testing and commissioning of Long coupled Vertical Inline Pumps duly factory mounted on a base with electric motor. The pump motor shall be IE-3 efficiency (minimum 90%) and suitable for 415 +10% volts, 50 cycles, 3 phase power supply. Pumps will adhere to following performance characteristics : The pump performance shall meet the criterion laid down under ASHRAE 90.1-2019 and with minimum efficiency as specified. Thermal insulation & cladding of the chilled water pumps will be included. Secondary Pump shall operate through variable frequency drives. The rating of pumps shall be as follows: Condenser Water Pumps- Water flow rate : 600 USGPM Head : 70 ft of water Motor HP not to exceed : 25 HP Efficiency : 75% or more Condenser Water pump as described above including 1 No. standby.

3

-

-

... More
Supplying, installing, testing and commissioning of Variable Speed Pumping System (Sensor based) consisting of following: Variable Frequency Drive suitable for Secondary Chilled Water Pumps described above. Pump controller (micrprocessor based) with licensed software capable of operating the system with Modbus/Lon Works/Bacnet protocol. Quoted price shall include control/power wiring for daisy chain linking of pumps and providing signals at one point within the room. Pump controller shall be capable of controlling numbers of SCHW pumps mentioned above under item no. 2.4.2 Suitable No. Differential pressure sensor / transmitters control along with control cabling running in 25 mm dia MS conduit from sensor/transmitter to VFD Panel. Pressure sensing elements shall be installed at farthest end of zone circuit Digital display shall be provided on Pump Controller which will display all critical parameters. All wiring to complete the installation shall be included as part of this item. Secondary variable speed pumping system as described above

1

-

-

... More
Supplying, installing, testing and commissioning of 50 mm thick double skin construction Air Handling Units comprising of following: (Floor Mounted ) Backward curved fan inside double skin housing with efficiency not less than 75% . Pre filter (MERV 8) and bag filter (MERV-14) in supply air stream. Velocity across filter section shall not exceed 500 FPM. All AHU with 6 row deep cooling coil unless specified otherwise. SS 304 construction end plates to be provided. UVGI to be provided across the coil. Coil shall be provided with hydrophilic coating. All AHU shall be provided with mixing box & thermal break profile as per specifications. TEFC Motors suitable for 415 ± 10% volts, 50 Hz, AC supply and IE 3 efficiency. The maximum rating is specified below and contractor can select a lower rating motor incase the desired performance is being met. Motor shall be suitable to operate on VFD. Fan shall be plug type Fan outlet velocity not exceeding 10 mps. Minimum 20-30 mm (WC) external static pressure shall be considered. However, actual total static pressure shall be calculated and confirmed by the vendor at the time of bidding. All AHU which is placed outside shall be provided with rain protection canopy. All AHU's will be with DOL or S/D starter, if VFD starter not mentioned. General From electrical panel there shall be single input to Single AHU terminal box. All necessary internal wiring from Terminal Box to multiple direct drive motors provided by AHU vendor. Supply and Installation of 19 mm thick Neoprene Rubber Waffle Type Pads to be installed between the floor and the Air Handling Units. The neoprene pads shall be in accordance with the manufacturer's instructions for the size and weight distribution of the equipment supported. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen the AHU and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The rating shall be as follows: FM AHU 01,02, Capacity (CFM) - 25000, Required TR - 50, Total static pressure(mmwg) - 40-50, Motor Rating (kW) - 15

2

-

-

... More
Supplying, installing, testing and commissioning of 50 mm thick double skin construction Air Handling Units comprising of following: (Floor Mounted ) Backward curved fan inside double skin housing with efficiency not less than 75% . Pre filter (MERV 8) and bag filter (MERV-14) in supply air stream. Velocity across filter section shall not exceed 500 FPM. All AHU with 6 row deep cooling coil unless specified otherwise. SS 304 construction end plates to be provided. UVGI to be provided across the coil. Coil shall be provided with hydrophilic coating. All AHU shall be provided with mixing box & thermal break profile as per specifications. TEFC Motors suitable for 415 ± 10% volts, 50 Hz, AC supply and IE 3 efficiency. The maximum rating is specified below and contractor can select a lower rating motor incase the desired performance is being met. Motor shall be suitable to operate on VFD. Fan shall be plug type Fan outlet velocity not exceeding 10 mps. Minimum 20-30 mm (WC) external static pressure shall be considered. However, actual total static pressure shall be calculated and confirmed by the vendor at the time of bidding. All AHU which is placed outside shall be provided with rain protection canopy. All AHU's will be with DOL or S/D starter, if VFD starter not mentioned. General From electrical panel there shall be single input to Single AHU terminal box. All necessary internal wiring from Terminal Box to multiple direct drive motors provided by AHU vendor. Supply and Installation of 19 mm thick Neoprene Rubber Waffle Type Pads to be installed between the floor and the Air Handling Units. The neoprene pads shall be in accordance with the manufacturer's instructions for the size and weight distribution of the equipment supported. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen the AHU and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The rating shall be as follows: FM AHU 03, Capacity (CFM) - 20000, Required TR - 40, Total static pressure(mmwg) - 40-50, Motor Rating (kW) - 11

1

-

-

... More
Supplying, installing, testing and commissioning of 50 mm thick double skin construction Air Handling Units comprising of following: (Floor Mounted ) Backward curved fan inside double skin housing with efficiency not less than 75% . Pre filter (MERV 8) and bag filter (MERV-14) in supply air stream. Velocity across filter section shall not exceed 500 FPM. All AHU with 6 row deep cooling coil unless specified otherwise. SS 304 construction end plates to be provided. UVGI to be provided across the coil. Coil shall be provided with hydrophilic coating. All AHU shall be provided with mixing box & thermal break profile as per specifications. TEFC Motors suitable for 415 ± 10% volts, 50 Hz, AC supply and IE 3 efficiency. The maximum rating is specified below and contractor can select a lower rating motor incase the desired performance is being met. Motor shall be suitable to operate on VFD. Fan shall be plug type Fan outlet velocity not exceeding 10 mps. Minimum 20-30 mm (WC) external static pressure shall be considered. However, actual total static pressure shall be calculated and confirmed by the vendor at the time of bidding. All AHU which is placed outside shall be provided with rain protection canopy. All AHU's will be with DOL or S/D starter, if VFD starter not mentioned. General From electrical panel there shall be single input to Single AHU terminal box. All necessary internal wiring from Terminal Box to multiple direct drive motors provided by AHU vendor. Supply and Installation of 19 mm thick Neoprene Rubber Waffle Type Pads to be installed between the floor and the Air Handling Units. The neoprene pads shall be in accordance with the manufacturer's instructions for the size and weight distribution of the equipment supported. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen the AHU and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The rating shall be as follows: FM AHU 04,05, Capacity (CFM) - 15000, Required TR - 30, Total static pressure(mmwg) - 40-50, Motor Rating (kW) - 7.5

2

-

-

... More
Supplying, installing, testing and commissioning of 50 mm thick double skin construction Air Handling Units comprising of following: (Floor Mounted ) Backward curved fan inside double skin housing with efficiency not less than 75% . Pre filter (MERV 8) and bag filter (MERV-14) in supply air stream. Velocity across filter section shall not exceed 500 FPM. All AHU with 6 row deep cooling coil unless specified otherwise. SS 304 construction end plates to be provided. UVGI to be provided across the coil. Coil shall be provided with hydrophilic coating. All AHU shall be provided with mixing box & thermal break profile as per specifications. TEFC Motors suitable for 415 ± 10% volts, 50 Hz, AC supply and IE 3 efficiency. The maximum rating is specified below and contractor can select a lower rating motor incase the desired performance is being met. Motor shall be suitable to operate on VFD. Fan shall be plug type Fan outlet velocity not exceeding 10 mps. Minimum 20-30 mm (WC) external static pressure shall be considered. However, actual total static pressure shall be calculated and confirmed by the vendor at the time of bidding. All AHU which is placed outside shall be provided with rain protection canopy. All AHU's will be with DOL or S/D starter, if VFD starter not mentioned. General From electrical panel there shall be single input to Single AHU terminal box. All necessary internal wiring from Terminal Box to multiple direct drive motors provided by AHU vendor. Supply and Installation of 19 mm thick Neoprene Rubber Waffle Type Pads to be installed between the floor and the Air Handling Units. The neoprene pads shall be in accordance with the manufacturer's instructions for the size and weight distribution of the equipment supported. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen the AHU and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The rating shall be as follows: FM AHU 06, Capacity (CFM) - 12000, Required TR - 25, Total static pressure(mmwg) - 40-50, Motor Rating (kW) - 5.5

1

-

-

... More
Supplying, installing, testing and commissioning of 50 mm thick double skin construction Air Handling Units comprising of following: (Floor Mounted ) Backward curved fan inside double skin housing with efficiency not less than 75% . Pre filter (MERV 8) and bag filter (MERV-14) in supply air stream. Velocity across filter section shall not exceed 500 FPM. All AHU with 6 row deep cooling coil unless specified otherwise. SS 304 construction end plates to be provided. UVGI to be provided across the coil. Coil shall be provided with hydrophilic coating. All AHU shall be provided with mixing box & thermal break profile as per specifications. TEFC Motors suitable for 415 ± 10% volts, 50 Hz, AC supply and IE 3 efficiency. The maximum rating is specified below and contractor can select a lower rating motor incase the desired performance is being met. Motor shall be suitable to operate on VFD. Fan shall be plug type Fan outlet velocity not exceeding 10 mps. Minimum 20-30 mm (WC) external static pressure shall be considered. However, actual total static pressure shall be calculated and confirmed by the vendor at the time of bidding. All AHU which is placed outside shall be provided with rain protection canopy. All AHU's will be with DOL or S/D starter, if VFD starter not mentioned. General From electrical panel there shall be single input to Single AHU terminal box. All necessary internal wiring from Terminal Box to multiple direct drive motors provided by AHU vendor. Supply and Installation of 19 mm thick Neoprene Rubber Waffle Type Pads to be installed between the floor and the Air Handling Units. The neoprene pads shall be in accordance with the manufacturer's instructions for the size and weight distribution of the equipment supported. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen the AHU and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The rating shall be as follows: FM AHU 07 to 09, Capacity (CFM) - 10000, Required TR - 26, Total static pressure(mmwg) - 40-50, Motor Rating (kW) - 5.5

3

-

-

... More
Supplying, installing, testing and commissioning of 50 mm thick double skin construction Air Handling Units comprising of following: (Floor Mounted ) Backward curved fan inside double skin housing with efficiency not less than 75% . Pre filter (MERV 8) and bag filter (MERV-14) in supply air stream. Velocity across filter section shall not exceed 500 FPM. All AHU with 6 row deep cooling coil unless specified otherwise. SS 304 construction end plates to be provided. UVGI to be provided across the coil. Coil shall be provided with hydrophilic coating. All AHU shall be provided with mixing box & thermal break profile as per specifications. TEFC Motors suitable for 415 ± 10% volts, 50 Hz, AC supply and IE 3 efficiency. The maximum rating is specified below and contractor can select a lower rating motor incase the desired performance is being met. Motor shall be suitable to operate on VFD. Fan shall be plug type Fan outlet velocity not exceeding 10 mps. Minimum 20-30 mm (WC) external static pressure shall be considered. However, actual total static pressure shall be calculated and confirmed by the vendor at the time of bidding. All AHU which is placed outside shall be provided with rain protection canopy. All AHU's will be with DOL or S/D starter, if VFD starter not mentioned. General From electrical panel there shall be single input to Single AHU terminal box. All necessary internal wiring from Terminal Box to multiple direct drive motors provided by AHU vendor. Supply and Installation of 19 mm thick Neoprene Rubber Waffle Type Pads to be installed between the floor and the Air Handling Units. The neoprene pads shall be in accordance with the manufacturer's instructions for the size and weight distribution of the equipment supported. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen the AHU and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The rating shall be as follows: FM AHU 10 to 12, Capacity (CFM) - 7000, Required TR - 14, Total static pressure(mmwg) - 40-50, Motor Rating (kW) - 3.0

3

-

-

... More
Supplying, installing, testing and commissioning of 50 mm thick double skin construction Air Handling Units comprising of following: (Floor Mounted ) Backward curved fan inside double skin housing with efficiency not less than 75% . Pre filter (MERV 8) and bag filter (MERV-14) in supply air stream. Velocity across filter section shall not exceed 500 FPM. All AHU with 6 row deep cooling coil unless specified otherwise. SS 304 construction end plates to be provided. UVGI to be provided across the coil. Coil shall be provided with hydrophilic coating. All AHU shall be provided with mixing box & thermal break profile as per specifications. TEFC Motors suitable for 415 ± 10% volts, 50 Hz, AC supply and IE 3 efficiency. The maximum rating is specified below and contractor can select a lower rating motor incase the desired performance is being met. Motor shall be suitable to operate on VFD. Fan shall be plug type Fan outlet velocity not exceeding 10 mps. Minimum 20-30 mm (WC) external static pressure shall be considered. However, actual total static pressure shall be calculated and confirmed by the vendor at the time of bidding. All AHU which is placed outside shall be provided with rain protection canopy. All AHU's will be with DOL or S/D starter, if VFD starter not mentioned. General From electrical panel there shall be single input to Single AHU terminal box. All necessary internal wiring from Terminal Box to multiple direct drive motors provided by AHU vendor. Supply and Installation of 19 mm thick Neoprene Rubber Waffle Type Pads to be installed between the floor and the Air Handling Units. The neoprene pads shall be in accordance with the manufacturer's instructions for the size and weight distribution of the equipment supported. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen the AHU and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The rating shall be as follows: FM AHU 13 to 17, Capacity (CFM) - 4000, Required TR - 10, Total static pressure(mmwg) - 40-50, Motor Rating (kW) - 2.2

5

-

-

... More
Supplying, installing, testing and commissioning of 50 mm thick double skin construction Air Handling Units comprising of following: (Floor Mounted ) Backward curved fan inside double skin housing with efficiency not less than 75% . Pre filter (MERV 8) and bag filter (MERV-14) in supply air stream. Velocity across filter section shall not exceed 500 FPM. All AHU with 6 row deep cooling coil unless specified otherwise. SS 304 construction end plates to be provided. UVGI to be provided across the coil. Coil shall be provided with hydrophilic coating. All AHU shall be provided with mixing box & thermal break profile as per specifications. TEFC Motors suitable for 415 ± 10% volts, 50 Hz, AC supply and IE 3 efficiency. The maximum rating is specified below and contractor can select a lower rating motor incase the desired performance is being met. Motor shall be suitable to operate on VFD. Fan shall be plug type Fan outlet velocity not exceeding 10 mps. Minimum 20-30 mm (WC) external static pressure shall be considered. However, actual total static pressure shall be calculated and confirmed by the vendor at the time of bidding. All AHU which is placed outside shall be provided with rain protection canopy. All AHU's will be with DOL or S/D starter, if VFD starter not mentioned. General From electrical panel there shall be single input to Single AHU terminal box. All necessary internal wiring from Terminal Box to multiple direct drive motors provided by AHU vendor. Supply and Installation of 19 mm thick Neoprene Rubber Waffle Type Pads to be installed between the floor and the Air Handling Units. The neoprene pads shall be in accordance with the manufacturer's instructions for the size and weight distribution of the equipment supported. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen the AHU and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The rating shall be as follows: FM AHU 18, Capacity (CFM) - 3500, Required TR - 10, Total static pressure(mmwg) - 40-50, Motor Rating (kW) - 1.5

1

-

-

... More
Supplying, installing, testing and commissioning of 50 mm thick double skin construction Air Handling Units comprising of following: (Floor Mounted ) Backward curved fan inside double skin housing with efficiency not less than 75% . Pre filter (MERV 8) and bag filter (MERV-14) in supply air stream. Velocity across filter section shall not exceed 500 FPM. All AHU with 6 row deep cooling coil unless specified otherwise. SS 304 construction end plates to be provided. UVGI to be provided across the coil. Coil shall be provided with hydrophilic coating. All AHU shall be provided with mixing box & thermal break profile as per specifications. TEFC Motors suitable for 415 ± 10% volts, 50 Hz, AC supply and IE 3 efficiency. The maximum rating is specified below and contractor can select a lower rating motor incase the desired performance is being met. Motor shall be suitable to operate on VFD. Fan shall be plug type Fan outlet velocity not exceeding 10 mps. Minimum 20-30 mm (WC) external static pressure shall be considered. However, actual total static pressure shall be calculated and confirmed by the vendor at the time of bidding. All AHU which is placed outside shall be provided with rain protection canopy. All AHU's will be with DOL or S/D starter, if VFD starter not mentioned. General From electrical panel there shall be single input to Single AHU terminal box. All necessary internal wiring from Terminal Box to multiple direct drive motors provided by AHU vendor. Supply and Installation of 19 mm thick Neoprene Rubber Waffle Type Pads to be installed between the floor and the Air Handling Units. The neoprene pads shall be in accordance with the manufacturer's instructions for the size and weight distribution of the equipment supported. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen the AHU and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The rating shall be as follows: FM AHU 19 to 21, Capacity (CFM) - 3000, Required TR - 7, Total static pressure(mmwg) - 40-50, Motor Rating (kW) - 1.5

3

-

-

... More
Supplying, installing, testing and commissioning of 50 mm thick double skin construction Air Handling Units comprising of following: (Floor Mounted ) Backward curved fan inside double skin housing with efficiency not less than 75% . Pre filter (MERV 8) and bag filter (MERV-14) in supply air stream. Velocity across filter section shall not exceed 500 FPM. All AHU with 6 row deep cooling coil unless specified otherwise. SS 304 construction end plates to be provided. UVGI to be provided across the coil. Coil shall be provided with hydrophilic coating. All AHU shall be provided with mixing box & thermal break profile as per specifications. TEFC Motors suitable for 415 ± 10% volts, 50 Hz, AC supply and IE 3 efficiency. The maximum rating is specified below and contractor can select a lower rating motor incase the desired performance is being met. Motor shall be suitable to operate on VFD. Fan shall be plug type Fan outlet velocity not exceeding 10 mps. Minimum 20-30 mm (WC) external static pressure shall be considered. However, actual total static pressure shall be calculated and confirmed by the vendor at the time of bidding. All AHU which is placed outside shall be provided with rain protection canopy. All AHU's will be with DOL or S/D starter, if VFD starter not mentioned. General From electrical panel there shall be single input to Single AHU terminal box. All necessary internal wiring from Terminal Box to multiple direct drive motors provided by AHU vendor. Supply and Installation of 19 mm thick Neoprene Rubber Waffle Type Pads to be installed between the floor and the Air Handling Units. The neoprene pads shall be in accordance with the manufacturer's instructions for the size and weight distribution of the equipment supported. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen the AHU and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The rating shall be as follows: FM AHU 22, Capacity (CFM) - 2500, Required TR - 5, Total static pressure(mmwg) - 40-50, Motor Rating (kW) - 1.1

1

-

-

... More
Supplying, installing, testing and commissioning of 25mm thick double skin construction Air Handling Units comprising of following: (Ceiling Mounted) Forward curved fan mounted inside double skin housing with efficiency not less than 65% Pre filter (MERV 8) and bag filter (MERV-14) in supply air stream. Velocity across filter section shall not exceed 500 FPM. All AHU with 4 row deep cooling coil unless specified otherwise. SS 304 construction end plates to be provided. UVGI to be provided across the coil. Coil shall be provided with hydrophilic coating. TEFC Motors suitable for 415 ± 10% volts, 50 Hz, AC supply and IE 3 efficiency. The maximum rating is specified below and contractor can select a lower rating motor incase the desired performance is being met. Fan shall be plug type Fan outlet velocity not exceeding 10 mps. SS 304 construction end plates to be provided. Hydrophilic coating shall be carried out on the chilled water coil. All AHU are ceiling suspended type complete with, vibration isolation & hanging arrangement with height as per the drawings Minimum 15-20 mm (WC) external static pressure shall be considered. However, actual total static pressure shall be calculated and confirmed by the vendor at the time of bidding. The desired rating of AHU shall be as follows: CS AHU 01 to 05, Capacity (CFM) - 2000, Required TR - 5, Total static pressure(mmwg) - 40-50, Motor Rating (kW) - 1.1

5

-

-

... More
Supplying, installing, testing and commissioning of 25mm thick double skin construction Air Handling Units comprising of following: (Ceiling Mounted) Forward curved fan mounted inside double skin housing with efficiency not less than 65% Pre filter (MERV 8) and bag filter (MERV-14) in supply air stream. Velocity across filter section shall not exceed 500 FPM. All AHU with 4 row deep cooling coil unless specified otherwise. SS 304 construction end plates to be provided. UVGI to be provided across the coil. Coil shall be provided with hydrophilic coating. TEFC Motors suitable for 415 ± 10% volts, 50 Hz, AC supply and IE 3 efficiency. The maximum rating is specified below and contractor can select a lower rating motor incase the desired performance is being met. Fan shall be plug type Fan outlet velocity not exceeding 10 mps. SS 304 construction end plates to be provided. Hydrophilic coating shall be carried out on the chilled water coil. All AHU are ceiling suspended type complete with, vibration isolation & hanging arrangement with height as per the drawings Minimum 15-20 mm (WC) external static pressure shall be considered. However, actual total static pressure shall be calculated and confirmed by the vendor at the time of bidding. The desired rating of AHU shall be as follows: CS AHU 06 to 10, Capacity (CFM) - 1500, Required TR - 4, Total static pressure(mmwg) - 40-50, Motor Rating (kW) - 1.1

5

-

-

... More
Supply, installing, testing and commissioning of wall mounted type Air Cooled Split AC Units (Inverter Type) as described in specifications. The unit shall be complete with Ductable type Indoor unit and external condensing unit, powered coated MS stand, gas charging and top up for extra copper length, complete in all respects, inclusive of copper refrigerant piping, PVC condensate drain piping, valves and insulation. Quoted price shall include cost of thermostat, wiring, control cooling thermostat, wiring, control wiring & earthing The unit capacities shall be after taking deration into account due to copper piping lengths. Unit shall be R407 C/ R 410a/ R-32 refrigerant based. Suitable rating Switch Socket shall be provided within 1.0 m of all IDUs (by others). The cost for Power Cable from the IDU to this Switch Socket and the power cable from the IDU to the ODU shall be included in the Quoted unit price. 1.5 TR Hi Wall type split units

3

-

-

... More
Supply, installing, testing and commissioning of wall mounted type Air Cooled Split AC Units (Inverter Type) as described in specifications. The unit shall be complete with Ductable type Indoor unit and external condensing unit, powered coated MS stand, gas charging and top up for extra copper length, complete in all respects, inclusive of copper refrigerant piping, PVC condensate drain piping, valves and insulation. Quoted price shall include cost of thermostat, wiring, control cooling thermostat, wiring, control wiring & earthing The unit capacities shall be after taking deration into account due to copper piping lengths. Unit shall be R407 C/ R 410a/ R-32 refrigerant based. Suitable rating Switch Socket shall be provided within 1.0 m of all IDUs (by others). The cost for Power Cable from the IDU to this Switch Socket and the power cable from the IDU to the ODU shall be included in the Quoted unit price. 2.0 TR Hi Wall type split units

1

-

-

... More
Supplying, installing, testing and commissioning of SILENT MIXED FLOW INLINE FANS suitable for installing in any position in vertical or horizontal ducts.Constructed with sheet steel with epoxy polyester paint, acoustic isulation within the outer shell. Two speed motor (IP 44 Rated) with removable fan body with two speed motor, single phase speed controlable class F external rotor motor with capacitor and thermal protection. All units shall be complete with duct flexible connector, speed regulator (with wiring of 3 m included between fan & regulator) and volume control damper and static pressure or to suit the system, shall be as follows: The sound level shall be measured at three metre distance. Actual static to be checked by the vendor during the shop drawings. 100-200 ( Fan capacity-CFM) 35 Dba (Max Noise Level)

2

-

-

... More
Supplying, installing, testing and commissioning of SILENT MIXED FLOW INLINE FANS suitable for installing in any position in vertical or horizontal ducts.Constructed with sheet steel with epoxy polyester paint, acoustic isulation within the outer shell. Two speed motor (IP 44 Rated) with removable fan body with two speed motor, single phase speed controlable class F external rotor motor with capacitor and thermal protection. All units shall be complete with duct flexible connector, speed regulator (with wiring of 3 m included between fan & regulator) and volume control damper and static pressure or to suit the system, shall be as follows: The sound level shall be measured at three metre distance. Actual static to be checked by the vendor during the shop drawings. 201-500 ( Fan capacity-CFM) 35 Dba (Max Noise Level)

1

-

-

... More
Supplying, installing, testing and commissioning of SILENT MIXED FLOW INLINE FANS suitable for installing in any position in vertical or horizontal ducts.Constructed with sheet steel with epoxy polyester paint, acoustic isulation within the outer shell. Two speed motor (IP 44 Rated) with removable fan body with two speed motor, single phase speed controlable class F external rotor motor with capacitor and thermal protection. All units shall be complete with duct flexible connector, speed regulator (with wiring of 3 m included between fan & regulator) and volume control damper and static pressure or to suit the system, shall be as follows: The sound level shall be measured at three metre distance. Actual static to be checked by the vendor during the shop drawings. 501-800 ( Fan capacity-CFM) 35 Dba (Max Noise Level)

3

-

-

... More
Supplying, installing, testing and commissioning of direct driven PROPELLER FANS for exhaust air . Each fan shall be complete with permanent split capacitor or shaded pole motor, mounting plate, accessories like wire guard, bird screen and fixed louvers for weather protection as required. Fan selection arrangement and Electrical characteristics shall be as follows : 300 mm dia 900 RPM fan suitable for 220±6% volts 50 cycles, 1 phase AC supply.

2

-

-

... More
Supplying, installing, testing and commissioning of direct driven PROPELLER FANS for exhaust air . Each fan shall be complete with permanent split capacitor or shaded pole motor, mounting plate, accessories like wire guard, bird screen and fixed louvers for weather protection as required. Fan selection arrangement and Electrical characteristics shall be as follows : 230 mm dia 900 RPM fan suitable for 220±6% volts 50 cycles, 1 phase AC supply.

10

-

-

... More
Supplying, installing, testing and commissioning of FRP Induced draft Cooling Towers with VFD with built in PID controller, control panel(keypad and display) for air conditioning system. Each tower shall be complete with FRP basin, casing, distribution system, filling, louvers, HDG supporters, GI ladders, steel/masonary supporting structure, anti vibration mounting etc. (VFD is considered as a seperate item in the BOQ) Cooling tower approach should not be more than 5 °C at lower WBT. Software generated curves to be submitted by manufacturer. Motors shall be for outdoor application (IP55), suitable for 415±10% volt, 50 cycle’s 3 phase power supply meeting criterion as per ASHRAE standard 90.1-2019 and high efficiency. Isolators at cooling tower enclosed in weather proof panel shall also be included. Performance required for cooling tower is minimum 50 gpm/hp when tested according CTI ATC-105 procedure. Foundation shall be under Civil Contractor's scope. Cooling tower suitable for - 200 TR Cooling Capacity Inlet Condenser Water Temperature - 90 °F Outlet Condenser Water Temperature - 80 °F Wet Bulb Temperture - 75 °F Chilled Water Flow - 525 USGPM Motor HP - 1 No. 10 HP Cell Number - 1 No. Sound level - 76 dB at 3 meter distance Cooling Tower as described above

2

-

-

... More
Supply, installation, testing and commissioning of Closed type pressurized chilled water expansion tank with PN-16 rating complete with necessary connection for piping, vent, valves and accessories. The requirement shall be as follows: The total volume of water in chilled water pipes shall be worked out by HVAC contractor and contractor will work out the total volume. Below tank capacity are indicative for quotes, any change during the execution in Tank capacity. There will be no additional claim will be acceptable. Accessories like pumps in N+1 etc.shall be included in quoted price for satisfactory operation. The tank shall be nitrogen precharged steel expansion tank with replaceable heavy duty butyl rubber bladder. The tank shall have suitable sized inlet connection, drain alongwith valves for isolation/shutdown of system connection and drain and charging valve connection to facilitate the on site charging of the tank to meet system requirement. Chilled water Expansion tank of capacity- 800 litres

1

-

-

... More
Supply, installation, testing and commissioning of Centrifugal type Air Seperator complete with necessary connection for piping, vent, valves and accessories. The requirement shall be as follows: 200 mm dia Air Seperator

1

-

-

... More
Supplying, installing, testing and commissioning of double skin construction Fan sections (made out of 25mm thick panel) complete with internally mounted motor, fan belt drive, flexible connection, vibrations isolators and complete with following: TEFC Motors suitable for 415 ± 10% volts, 50 Hz, AC supply and IE 3 efficiency. The maximum rating is specified below and contractor can select a lower rating motor incase the desired performance is being met. Forward & Backward curved fan inside double skin housing with efficiency not less than 65-70%. Minimum 20-25 mm (WC) external static pressure shall be considered. However, actual total static pressure shall be calculated and confirmed by the vendor at the time of bidding. Height of the unit shall not exceed 550mm, contractor to select the no. of fans accordingly. Fan shall be provided with pre filters of MERV-8 . The rating of fan sections shall be as follows: FS 01 to 04(Toilet Ventilation), Capacity (CFM) - 12500, External static pressure(mmwg) - 20-25, Motor Rating (kW) - 5.5, VFD-Yes

4

-

-

... More
Supplying, installing, testing and commissioning of double skin construction Fan sections (made out of 25mm thick panel) complete with internally mounted motor, fan belt drive, flexible connection, vibrations isolators and complete with following: TEFC Motors suitable for 415 ± 10% volts, 50 Hz, AC supply and IE 3 efficiency. The maximum rating is specified below and contractor can select a lower rating motor incase the desired performance is being met. Forward & Backward curved fan inside double skin housing with efficiency not less than 65-70%. Minimum 20-25 mm (WC) external static pressure shall be considered. However, actual total static pressure shall be calculated and confirmed by the vendor at the time of bidding. Height of the unit shall not exceed 550mm, contractor to select the no. of fans accordingly. Fan shall be provided with pre filters of MERV-8 . The rating of fan sections shall be as follows: FS 05 & 06 (Toilet Ventilation), Capacity (CFM) - 9000, External static pressure(mmwg) - 20-25, Motor Rating (kW) - 5.5 , VFD- Yes

2

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Smoke Exhaust air motor shall be Class H rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%.Fan and casing shall be suitable for normal & smoke exhaust application.Motor shall be mounted inside the fan casing & thermally rated for 250 Deg C for 2 hour as per [BS-7346 Part-2 : 1090] External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-01,02 , Capacity (CFM) - 36000, External static pressure(mmwg) - 20-25, Motor Rating (kW) - 22 , VFD- No

2

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Smoke Exhaust air motor shall be Class H rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%.Fan and casing shall be suitable for normal & smoke exhaust application.Motor shall be mounted inside the fan casing & thermally rated for 250 Deg C for 2 hour as per [BS-7346 Part-2 : 1090] External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-03,04 , Capacity (CFM) - 28000, External static pressure(mmwg) - 20-25, Motor Rating (kW) - 15 , VFD- No

2

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Smoke Exhaust air motor shall be Class H rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%.Fan and casing shall be suitable for normal & smoke exhaust application.Motor shall be mounted inside the fan casing & thermally rated for 250 Deg C for 2 hour as per [BS-7346 Part-2 : 1090] External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-05 , Capacity (CFM) - 26000, External static pressure(mmwg) - 20-25, Motor Rating (kW) - 15 , VFD- No

1

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Smoke Exhaust air motor shall be Class H rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%.Fan and casing shall be suitable for normal & smoke exhaust application.Motor shall be mounted inside the fan casing & thermally rated for 250 Deg C for 2 hour as per [BS-7346 Part-2 : 1090] External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-06 , Capacity (CFM) - 16000, External static pressure(mmwg) - 20-25, Motor Rating (kW) - 7.5 , VFD- No

1

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Smoke Exhaust air motor shall be Class H rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%.Fan and casing shall be suitable for normal & smoke exhaust application.Motor shall be mounted inside the fan casing & thermally rated for 250 Deg C for 2 hour as per [BS-7346 Part-2 : 1090] External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-07-09 , Capacity (CFM) - 12500, External static pressure(mmwg) - 20-25, Motor Rating (kW) - 5.5 , VFD- No

3

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Smoke Exhaust air motor shall be Class H rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%.Fan and casing shall be suitable for normal & smoke exhaust application.Motor shall be mounted inside the fan casing & thermally rated for 250 Deg C for 2 hour as per [BS-7346 Part-2 : 1090] External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-10-12 , Capacity (CFM) - 8500, External static pressure(mmwg) - 20-25, Motor Rating (kW) - 3.0 , VFD- No

3

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Smoke Exhaust air motor shall be Class H rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%.Fan and casing shall be suitable for normal & smoke exhaust application.Motor shall be mounted inside the fan casing & thermally rated for 250 Deg C for 2 hour as per [BS-7346 Part-2 : 1090] External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-13-14 , Capacity (CFM) - 6000, External static pressure(mmwg) - 20-25, Motor Rating (kW) - 2.2 , VFD- No

2

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Smoke Exhaust air motor shall be Class H rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%.Fan and casing shall be suitable for normal & smoke exhaust application.Motor shall be mounted inside the fan casing & thermally rated for 250 Deg C for 2 hour as per [BS-7346 Part-2 : 1090] External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-15-16 , Capacity (CFM) - 4500, External static pressure(mmwg) - 20-25, Motor Rating (kW) - 2.2 , VFD- No

2

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Smoke Exhaust air motor shall be Class H rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%.Fan and casing shall be suitable for normal & smoke exhaust application.Motor shall be mounted inside the fan casing & thermally rated for 250 Deg C for 2 hour as per [BS-7346 Part-2 : 1090] External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-17 , Capacity (CFM) - 2500, External static pressure(mmwg) - 20-25, Motor Rating (kW) - 1.1 , VFD- No

1

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Smoke Exhaust air motor shall be Class H rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%.Fan and casing shall be suitable for normal & smoke exhaust application.Motor shall be mounted inside the fan casing & thermally rated for 250 Deg C for 2 hour as per [BS-7346 Part-2 : 1090] External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-18-19 , Capacity (CFM) - 22000, External static pressure(mmwg) - 20-25, Motor Rating (kW) - 11, VFD- No

2

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Smoke Exhaust air motor shall be Class H rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%.Fan and casing shall be suitable for normal & smoke exhaust application.Motor shall be mounted inside the fan casing & thermally rated for 250 Deg C for 2 hour as per [BS-7346 Part-2 : 1090] External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-20-24 , Capacity (CFM) - 17000, External static pressure(mmwg) - 20-25, Motor Rating (kW) - 7.5, VFD- No

5

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Make up air motor shall be Class F rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%. External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-01 , Capacity (CFM) - 36000, External static pressure(mmwg) - 20-25, Motor Rating (kW) - 22, VFD- No

1

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Make up air motor shall be Class F rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%. External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-02,03 , Capacity (CFM) - 28000, External static pressure(mmwg) - 20-25, Motor Rating (kW) - 15, VFD- No

2

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Make up air motor shall be Class F rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%. External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-04 to 07, Capacity (CFM) - 18000, External static pressure(mmwg) - 20-25, Motor Rating (kW) - 7.5, VFD- No

4

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Make up air motor shall be Class F rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%. External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-08 ,09, Capacity (CFM) - 6000, External static pressure(mmwg) - 20-25, Motor Rating (kW) -2.2, VFD- No

2

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Make up air motor shall be Class F rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%. External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-10, Capacity (CFM) - 2500, External static pressure(mmwg) - 20-25, Motor Rating (kW) -1.1, VFD- No

1

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Make up air motor shall be Class F rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%. External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-11(Chiller Plant Roon Exhaust), Capacity (CFM) - 11000, External static pressure(mmwg) - 20-25, Motor Rating (kW) -5.5, VFD- No

1

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Make up air motor shall be Class F rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%. External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-12 (Chiller Plant Room Makeup), Capacity (CFM) - 11000, External static pressure(mmwg) - 20-25, Motor Rating (kW) -5.5, VFD- No

1

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Make up air motor shall be Class F rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%. External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-13 (Pump Room Exhaust), Capacity (CFM) - 4000, External static pressure(mmwg) - 20-25, Motor Rating (kW) -2.2, VFD- No

1

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Make up air motor shall be Class F rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%. External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-14 (Pump Room Makeup), Capacity (CFM) - 4000, External static pressure(mmwg) - 20-25, Motor Rating (kW) -2.2, VFD- No

1

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Make up air motor shall be Class F rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%. External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-15 (STP Exhaust), Capacity (CFM) - 6500, External static pressure(mmwg) - 20-25, Motor Rating (kW) -3.0, VFD- No

1

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Make up air motor shall be Class F rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%. External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-16 (STP Makeup), Capacity (CFM) - 6000, External static pressure(mmwg) - 20-25, Motor Rating (kW) -3.0, VFD- No

1

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Make up air motor shall be Class F rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%. External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-17 (Equipment store Exhaust), Capacity (CFM) - 6000, External static pressure(mmwg) - 20-25, Motor Rating (kW) -3.0, VFD- No

1

-

-

... More
Supply, installation, testing & commissioning of Axial Flow Fans suitable for installing in both Horizontal or vertical position as per site requirement and complete with totally enclosed direct driven, motor mount, fire rated flexible connection and vibration isolators. The fan shall be equipped with mounting bracket. Fan capacity shall be as follows Normal application fan shall be selected for lower noise level and shall not exceed 72 DB (A) at 3 m distance from the fan. If required contractor to add sound attenuator to meet the desired noise level. Fan shall be selected for minimum efficiency of 60-70% and also these fan will operate through Starter delta or DOL starter in case of fire can be selected for higher outlet velocity as sound is not criteria while selecting. Total static pressure shall be check by vendor. Fan will be selected on the basis of best in-class efficiency. For Make up air motor shall be Class F rating and suitable for 415±10% volts 3 phase 50 cycles, AC supply. The motor selected shall be IE3 efficiency at full load. Fan shall be selected for minimum efficiency of 65%. External static pressure shall be 20-25 mm (WC) minimum and Total static pressure shall be check by vendor. General Supply and Installation of spring hangers for all above mention Fans. The hangers should consist of a free-standing, laterally stable steel spring and elastomeric washer in series, assembled in a stamped or welded steel bracket with a Neoprene element at the top . The hanger bracket shall be designed to carry five times overload without failure and shall allow up to 30 degree rod misalignment without metal to metal contact. The spring should have a minimum deflection of 25 mm and Neoprene element minimum 4mm deflection. Supply and Installation of Fire Resistant Fabric Flexible Connection to be installed betweeen above mention all the Fans and the ducting to provide flexibilty of movement in case of a seismic event and to prevent transmission of vibration from the unit to the duct. The fabric should be of glassfiber with a silicon silicon coating and extruded metal flanges. The fabric should conform to BS 476 Part 7 Class 1 and NFPA 701. The fan capacities shall be as follows: AXF-18 (LT Panel Room Exhaust), Capacity (CFM) - 1500, External static pressure(mmwg) - 20-25, Motor Rating (kW) -1.1, VFD- No

1

-

-

... More
Supply, installing, testing and commissioning of VFD suitable for HVAC application with minimum IP 55 enclosures complying with the tender specifications and shall be complete in all respects and suitable for following motor rating and shall meet the following specifications : a) The VFD shall have a dual 5% impedance DC link reactor (Harmonic filters) on the positive and negative rails of the DC bus to minimize power line harmonics and protect the VFD from power line transients. The chokes shall be non-saturating. b) All the VFD’s should have factory fitted IP 55 enclosure protection c) EMC filters, C1 Category, Drive should support at least 2 PID loops are required d) Panel space and wiring shall be included under Electrical Panel section e) 2 No. Pressure sensor and wiring shall be included in the cost. Equipment- Floor Mounted air handling unit , Motor kW- 1.1

1

-

-

... More
Supply, installing, testing and commissioning of VFD suitable for HVAC application with minimum IP 55 enclosures complying with the tender specifications and shall be complete in all respects and suitable for following motor rating and shall meet the following specifications : a) The VFD shall have a dual 5% impedance DC link reactor (Harmonic filters) on the positive and negative rails of the DC bus to minimize power line harmonics and protect the VFD from power line transients. The chokes shall be non-saturating. b) All the VFD’s should have factory fitted IP 55 enclosure protection c) EMC filters, C1 Category, Drive should support at least 2 PID loops are required d) Panel space and wiring shall be included under Electrical Panel section e) 2 No. Pressure sensor and wiring shall be included in the cost. Equipment- Floor Mounted air handling unit , Motor kW- 1.5

3

-

-

... More
Supply, installing, testing and commissioning of VFD suitable for HVAC application with minimum IP 55 enclosures complying with the tender specifications and shall be complete in all respects and suitable for following motor rating and shall meet the following specifications : a) The VFD shall have a dual 5% impedance DC link reactor (Harmonic filters) on the positive and negative rails of the DC bus to minimize power line harmonics and protect the VFD from power line transients. The chokes shall be non-saturating. b) All the VFD’s should have factory fitted IP 55 enclosure protection c) EMC filters, C1 Category, Drive should support at least 2 PID loops are required d) Panel space and wiring shall be included under Electrical Panel section e) 2 No. Pressure sensor and wiring shall be included in the cost. Equipment- Floor Mounted air handling unit , Motor kW- 2.2

5

-

-

... More
Supply, installing, testing and commissioning of VFD suitable for HVAC application with minimum IP 55 enclosures complying with the tender specifications and shall be complete in all respects and suitable for following motor rating and shall meet the following specifications : a) The VFD shall have a dual 5% impedance DC link reactor (Harmonic filters) on the positive and negative rails of the DC bus to minimize power line harmonics and protect the VFD from power line transients. The chokes shall be non-saturating. b) All the VFD’s should have factory fitted IP 55 enclosure protection c) EMC filters, C1 Category, Drive should support at least 2 PID loops are required d) Panel space and wiring shall be included under Electrical Panel section e) 2 No. Pressure sensor and wiring shall be included in the cost. Equipment- Floor Mounted air handling unit , Motor kW- 3.7

4

-

-

... More
Supply, installing, testing and commissioning of VFD suitable for HVAC application with minimum IP 55 enclosures complying with the tender specifications and shall be complete in all respects and suitable for following motor rating and shall meet the following specifications : a) The VFD shall have a dual 5% impedance DC link reactor (Harmonic filters) on the positive and negative rails of the DC bus to minimize power line harmonics and protect the VFD from power line transients. The chokes shall be non-saturating. b) All the VFD’s should have factory fitted IP 55 enclosure protection c) EMC filters, C1 Category, Drive should support at least 2 PID loops are required d) Panel space and wiring shall be included under Electrical Panel section e) 2 No. Pressure sensor and wiring shall be included in the cost. Equipment- Floor Mounted air handling unit , Motor kW- 5.5

4

-

-

... More
Supply, installing, testing and commissioning of VFD suitable for HVAC application with minimum IP 55 enclosures complying with the tender specifications and shall be complete in all respects and suitable for following motor rating and shall meet the following specifications : a) The VFD shall have a dual 5% impedance DC link reactor (Harmonic filters) on the positive and negative rails of the DC bus to minimize power line harmonics and protect the VFD from power line transients. The chokes shall be non-saturating. b) All the VFD’s should have factory fitted IP 55 enclosure protection c) EMC filters, C1 Category, Drive should support at least 2 PID loops are required d) Panel space and wiring shall be included under Electrical Panel section e) 2 No. Pressure sensor and wiring shall be included in the cost. Equipment- Floor Mounted air handling unit , Motor kW- 7.5

2

-

-

... More
Supply, installing, testing and commissioning of VFD suitable for HVAC application with minimum IP 55 enclosures complying with the tender specifications and shall be complete in all respects and suitable for following motor rating and shall meet the following specifications : a) The VFD shall have a dual 5% impedance DC link reactor (Harmonic filters) on the positive and negative rails of the DC bus to minimize power line harmonics and protect the VFD from power line transients. The chokes shall be non-saturating. b) All the VFD’s should have factory fitted IP 55 enclosure protection c) EMC filters, C1 Category, Drive should support at least 2 PID loops are required d) Panel space and wiring shall be included under Electrical Panel section e) 2 No. Pressure sensor and wiring shall be included in the cost. Equipment- Floor Mounted air handling unit , Motor kW- 10

1

-

-

... More
Supply, installing, testing and commissioning of VFD suitable for HVAC application with minimum IP 55 enclosures complying with the tender specifications and shall be complete in all respects and suitable for following motor rating and shall meet the following specifications : a) The VFD shall have a dual 5% impedance DC link reactor (Harmonic filters) on the positive and negative rails of the DC bus to minimize power line harmonics and protect the VFD from power line transients. The chokes shall be non-saturating. b) All the VFD’s should have factory fitted IP 55 enclosure protection c) EMC filters, C1 Category, Drive should support at least 2 PID loops are required d) Panel space and wiring shall be included under Electrical Panel section e) 2 No. Pressure sensor and wiring shall be included in the cost. Equipment- Floor Mounted air handling unit , Motor kW- 15

2

-

-

... More
Supply, installation, testing and commissioning of Bipolar Air Ionizer combination of Needle point , Tube Type & Carbon Brush Type which produces a natural Bio Climate rich in equal amount of positive and negative ions. The ionizer shall be kill microorganism and pathogens, remove Odour, VOC and reduce dust particle. The Ionizer should be UL 2998 & UL 867 listed With Zero Ozone Emission.The housing material is 18G steel powder coated. Models accept 24V AC input, 120V AC to 12V DC wall pack, 120V/240V AC to 12V DC power supply and 241V/277V AC to 12V DC power supply. 25000 CFM (Capacity)

2

-

-

... More
Supply, installation, testing and commissioning of Bipolar Air Ionizer combination of Needle point , Tube Type & Carbon Brush Type which produces a natural Bio Climate rich in equal amount of positive and negative ions. The ionizer shall be kill microorganism and pathogens, remove Odour, VOC and reduce dust particle. The Ionizer should be UL 2998 & UL 867 listed With Zero Ozone Emission.The housing material is 18G steel powder coated. Models accept 24V AC input, 120V AC to 12V DC wall pack, 120V/240V AC to 12V DC power supply and 241V/277V AC to 12V DC power supply. 20000 CFM (Capacity)

1

-

-

... More
Supply, installation, testing and commissioning of Bipolar Air Ionizer combination of Needle point , Tube Type & Carbon Brush Type which produces a natural Bio Climate rich in equal amount of positive and negative ions. The ionizer shall be kill microorganism and pathogens, remove Odour, VOC and reduce dust particle. The Ionizer should be UL 2998 & UL 867 listed With Zero Ozone Emission.The housing material is 18G steel powder coated. Models accept 24V AC input, 120V AC to 12V DC wall pack, 120V/240V AC to 12V DC power supply and 241V/277V AC to 12V DC power supply. 15000 CFM (Capacity)

2

-

-

... More
Supply, installation, testing and commissioning of Bipolar Air Ionizer combination of Needle point , Tube Type & Carbon Brush Type which produces a natural Bio Climate rich in equal amount of positive and negative ions. The ionizer shall be kill microorganism and pathogens, remove Odour, VOC and reduce dust particle. The Ionizer should be UL 2998 & UL 867 listed With Zero Ozone Emission.The housing material is 18G steel powder coated. Models accept 24V AC input, 120V AC to 12V DC wall pack, 120V/240V AC to 12V DC power supply and 241V/277V AC to 12V DC power supply. 12000 CFM (Capacity)

1

-

-

... More
Supply, installation, testing and commissioning of Bipolar Air Ionizer combination of Needle point , Tube Type & Carbon Brush Type which produces a natural Bio Climate rich in equal amount of positive and negative ions. The ionizer shall be kill microorganism and pathogens, remove Odour, VOC and reduce dust particle. The Ionizer should be UL 2998 & UL 867 listed With Zero Ozone Emission.The housing material is 18G steel powder coated. Models accept 24V AC input, 120V AC to 12V DC wall pack, 120V/240V AC to 12V DC power supply and 241V/277V AC to 12V DC power supply. 10000 CFM (Capacity)

3

-

-

... More
Supply, installation, testing and commissioning of Bipolar Air Ionizer combination of Needle point , Tube Type & Carbon Brush Type which produces a natural Bio Climate rich in equal amount of positive and negative ions. The ionizer shall be kill microorganism and pathogens, remove Odour, VOC and reduce dust particle. The Ionizer should be UL 2998 & UL 867 listed With Zero Ozone Emission.The housing material is 18G steel powder coated. Models accept 24V AC input, 120V AC to 12V DC wall pack, 120V/240V AC to 12V DC power supply and 241V/277V AC to 12V DC power supply. 7000 CFM (Capacity)

3

-

-

... More
Supply, installation, testing and commissioning of Bipolar Air Ionizer combination of Needle point , Tube Type & Carbon Brush Type which produces a natural Bio Climate rich in equal amount of positive and negative ions. The ionizer shall be kill microorganism and pathogens, remove Odour, VOC and reduce dust particle. The Ionizer should be UL 2998 & UL 867 listed With Zero Ozone Emission.The housing material is 18G steel powder coated. Models accept 24V AC input, 120V AC to 12V DC wall pack, 120V/240V AC to 12V DC power supply and 241V/277V AC to 12V DC power supply. 4000 CFM (Capacity)

5

-

-

... More
Supply, installation, testing and commissioning of Bipolar Air Ionizer combination of Needle point , Tube Type & Carbon Brush Type which produces a natural Bio Climate rich in equal amount of positive and negative ions. The ionizer shall be kill microorganism and pathogens, remove Odour, VOC and reduce dust particle. The Ionizer should be UL 2998 & UL 867 listed With Zero Ozone Emission.The housing material is 18G steel powder coated. Models accept 24V AC input, 120V AC to 12V DC wall pack, 120V/240V AC to 12V DC power supply and 241V/277V AC to 12V DC power supply. 3500 CFM (Capacity)

1

-

-

... More
Supply, installation, testing and commissioning of Bipolar Air Ionizer combination of Needle point , Tube Type & Carbon Brush Type which produces a natural Bio Climate rich in equal amount of positive and negative ions. The ionizer shall be kill microorganism and pathogens, remove Odour, VOC and reduce dust particle. The Ionizer should be UL 2998 & UL 867 listed With Zero Ozone Emission.The housing material is 18G steel powder coated. Models accept 24V AC input, 120V AC to 12V DC wall pack, 120V/240V AC to 12V DC power supply and 241V/277V AC to 12V DC power supply. 3000 CFM (Capacity)

3

-

-

... More
Supply, installation, testing and commissioning of Bipolar Air Ionizer combination of Needle point , Tube Type & Carbon Brush Type which produces a natural Bio Climate rich in equal amount of positive and negative ions. The ionizer shall be kill microorganism and pathogens, remove Odour, VOC and reduce dust particle. The Ionizer should be UL 2998 & UL 867 listed With Zero Ozone Emission.The housing material is 18G steel powder coated. Models accept 24V AC input, 120V AC to 12V DC wall pack, 120V/240V AC to 12V DC power supply and 241V/277V AC to 12V DC power supply. 2500 CFM (Capacity)

1

-

-

... More
Supply, installation, testing and commissioning of Bipolar Air Ionizer combination of Needle point , Tube Type & Carbon Brush Type which produces a natural Bio Climate rich in equal amount of positive and negative ions. The ionizer shall be kill microorganism and pathogens, remove Odour, VOC and reduce dust particle. The Ionizer should be UL 2998 & UL 867 listed With Zero Ozone Emission.The housing material is 18G steel powder coated. Models accept 24V AC input, 120V AC to 12V DC wall pack, 120V/240V AC to 12V DC power supply and 241V/277V AC to 12V DC power supply. 2000 CFM (Capacity)

2

-

-

... More
Supply, installation, testing and commissioning of Bipolar Air Ionizer combination of Needle point , Tube Type & Carbon Brush Type which produces a natural Bio Climate rich in equal amount of positive and negative ions. The ionizer shall be kill microorganism and pathogens, remove Odour, VOC and reduce dust particle. The Ionizer should be UL 2998 & UL 867 listed With Zero Ozone Emission.The housing material is 18G steel powder coated. Models accept 24V AC input, 120V AC to 12V DC wall pack, 120V/240V AC to 12V DC power supply and 241V/277V AC to 12V DC power supply. 1500 CFM (Capacity)

2

-

-

... More
Supply, Installation, Testing & commissioning of IAQ Monitor to remotely measure the levels of PM 2.5, VOCs, CO2, Temperature(In / Out), Humidity on a real time basis. The IAQ Monitor shall be capable of getting connected with Wi-Fi. The Monitor should be capable of sending the indoor air quality information on display Screen/Mobile/Browser as per Client's requirement. The Monitor should indicate the quality of air through changing the colours on the display screen as per the NAAQS standards and should meet the well building standards. This monitor should be a 3 tier architecture including sensor Hardware, secure cloud infrastructure, monitoring apps including dashboard, android/IOS. Quoted price shall be inclusive of all necessary arrangement as required to make the unit proper functional.

1

-

-

... More
Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators, Rigid supports / Steel wire rope hangers and fittings such as bends,tees etc.but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. 200 mm dia

250

-

-

... More
Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators, Rigid supports / Steel wire rope hangers and fittings such as bends,tees etc.but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. 150 mm dia

80

-

-

... More
Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators, Rigid supports / Steel wire rope hangers and fittings such as bends,tees etc.but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. 125 mm dia

60

-

-

... More
Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators, Rigid supports / Steel wire rope hangers and fittings such as bends,tees etc.but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. 100 mm dia

70

-

-

... More
Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators, Rigid supports / Steel wire rope hangers and fittings such as bends,tees etc.but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. 80 mm dia

50

-

-

... More
Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators, Rigid supports / Steel wire rope hangers and fittings such as bends,tees etc.but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. 65 mm dia

20

-

-

... More
Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators, Rigid supports / Steel wire rope hangers and fittings such as bends,tees etc.but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. 50 mm dia

10

-

-

... More
BUTTERFLY VALVE (MANUAL) with CI body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified Valves of 200 mm dia

3

-

-

... More
BUTTERFLY VALVE (MANUAL) with CI body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified Valves of 150 mm dia

6

-

-

... More
BUTTERFLY VALVE (MANUAL) with CI body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified Valves of 125 mm dia

10

-

-

... More
BUTTERFLY VALVE (MANUAL) with CI body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified Valves of 65 mm dia

2

-

-

... More
BUTTERFLY VALVE (MANUAL) with CI body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified Valves of 50 mm dia

2

-

-

... More
BUTTERFLY VALVE (MANUAL) with CI body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified Valves of 25 mm dia(Ball valve)

2

-

-

... More
Supplying, fixing, testing and commissioning of following sizes Motorized Butterfly Valve with CI Body, SS Disc, O - ring and minimum PN-16 pressure rating, conforming to BS 5155, IS 13095, with IP-55 actuator, capable of accepting upto 10V DC , and upto 20 mA electric signal and providing similar transduced feedback output to control system as required Valves of 150 mm dia

6

-

-

... More
Supplying, installing and fixing in position Balancing valves of PN 16 rating and suitable for following pipe sizes: Valves of 150 mm dia

5

-

-

... More
Supplying, installing and fixing in position Y Strainers of PN 16 rating and suitable for following pipe sizes. Strainers of 150 mm dia

3

-

-

... More
Non Return Valve with dual plate of CI Body SS Plates vulcanized NBR seal flanged end & PN 16 pressure rating as specified Valves of 150 mm dia

3

-

-

... More
Supply, installing and fixing in position Flexible connections of required pressure rating ( PN 16) installed at pump & chiller suction & discharge and at pipes crossing building expansion joints. Valves of 150 mm dia

6

-

-

... More
Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required)

6

-

-

... More
Providing & fixing in position the mercury in glass industrial type thermometres.

6

-

-

... More
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, steel wire rope hangers/ vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive or Chemically cross linked polyethlyne foam of class"O"(XLPE) with Aluminium PE foil for as per given below pipe size. The joints shall be sealed with 50 mm x 1 mm thick self adhesive tape at the joints etc. & complete as per specifications including repairing of damage to building etc. and as required complete in all respect.Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. 200 mm dia.(32 mm thick insulation)

180

-

-

... More
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, steel wire rope hangers/ vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive or Chemically cross linked polyethlyne foam of class"O"(XLPE) with Aluminium PE foil for as per given below pipe size. The joints shall be sealed with 50 mm x 1 mm thick self adhesive tape at the joints etc. & complete as per specifications including repairing of damage to building etc. and as required complete in all respect.Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. 150 mm dia.(32 mm thick insulation)

130

-

-

... More
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, steel wire rope hangers/ vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive or Chemically cross linked polyethlyne foam of class"O"(XLPE) with Aluminium PE foil for as per given below pipe size. The joints shall be sealed with 50 mm x 1 mm thick self adhesive tape at the joints etc. & complete as per specifications including repairing of damage to building etc. and as required complete in all respect.Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. 125 mm dia.(32 mm thick insulation)

260

-

-

... More
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, steel wire rope hangers/ vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive or Chemically cross linked polyethlyne foam of class"O"(XLPE) with Aluminium PE foil for as per given below pipe size. The joints shall be sealed with 50 mm x 1 mm thick self adhesive tape at the joints etc. & complete as per specifications including repairing of damage to building etc. and as required complete in all respect. Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. 100 mm dia.(32 mm thick insulation)

200

-

-

... More
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, steel wire rope hangers/ vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive or Chemically cross linked polyethlyne foam of class"O"(XLPE) with Aluminium PE foil for as per given below pipe size. The joints shall be sealed with 50 mm x 1 mm thick self adhesive tape at the joints etc. & complete as per specifications including repairing of damage to building etc. and as required complete in all respect. Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. 80 mm dia.(32 mm thick insulation)

160

-

-

... More
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, steel wire rope hangers/ vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive or Chemically cross linked polyethlyne foam of class"O"(XLPE) with Aluminium PE foil for as per given below pipe size. The joints shall be sealed with 50 mm x 1 mm thick self adhesive tape at the joints etc. & complete as per specifications including repairing of damage to building etc. and as required complete in all respect. Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. 65 mm dia.(32 mm thick insulation)

80

-

-

... More
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, steel wire rope hangers/ vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive or Chemically cross linked polyethlyne foam of class"O"(XLPE) with Aluminium PE foil for as per given below pipe size. The joints shall be sealed with 50 mm x 1 mm thick self adhesive tape at the joints etc. & complete as per specifications including repairing of damage to building etc. and as required complete in all respect. Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. 50 mm dia.(32 mm thick insulation)

350

-

-

... More
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, steel wire rope hangers/ vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive or Chemically cross linked polyethlyne foam of class"O"(XLPE) with Aluminium PE foil for as per given below pipe size. The joints shall be sealed with 50 mm x 1 mm thick self adhesive tape at the joints etc. & complete as per specifications including repairing of damage to building etc. and as required complete in all respect. Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. 40 mm dia.(32 mm thick insulation)

100

-

-

... More
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, steel wire rope hangers/ vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive or Chemically cross linked polyethlyne foam of class"O"(XLPE) with Aluminium PE foil for as per given below pipe size. The joints shall be sealed with 50 mm x 1 mm thick self adhesive tape at the joints etc. & complete as per specifications including repairing of damage to building etc. and as required complete in all respect. Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. 32mm dia.(19 mm thick insulation)

180

-

-

... More
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / hot water piping inside the building (with necessary clamps, steel wire rope hangers/ vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive or Chemically cross linked polyethlyne foam of class"O"(XLPE) with Aluminium PE foil for as per given below pipe size. The joints shall be sealed with 50 mm x 1 mm thick self adhesive tape at the joints etc. & complete as per specifications including repairing of damage to building etc. and as required complete in all respect. Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. 25mm dia.(19 mm thick insulation)

400

-

-

... More
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified Valves of 200 mm dia

1

-

-

... More
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified Valves of 150 mm dia

18

-

-

... More
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified Valves of 50 mm dia

2

-

-

... More
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. Motorized Butterfly Valve with CI Body, SS Disc, O - ring and minimum PN-16 pressure rating, conforming to BS 5155, IS 13095, with IP-55 actuator, capable of accepting upto 10V DC , and upto 20 mA electric signal and providing similar transduced feedback output to control system as required Valves of 150 mm dia

6

-

-

... More
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. AHU's Valves- BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified Valves of 80 mm dia

8

-

-

... More
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. AHU's Valves- BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified Valves of 65 mm dia

12

-

-

... More
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. AHU's Valves- BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified Valves of 50 mm dia

18

-

-

... More
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. AHU's Valves- BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified Valves of 40 mm dia

6

-

-

... More
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. AHU's Valves- BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/ hot eater circulation as specified Valves of 32 mm dia

22

-

-

... More
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified Valves of 150 mm dia

6

-

-

... More
Supplying, installing and fixing in position Y Strainers of PN 16 rating and suitable for following pipe sizes. Price shall include the cost of Insulation, material and external treatment will be same as of pipe: 150 mm dia

6

-

-

... More
Supplying, installing and fixing in position Y Strainers of PN 16 rating and suitable for following pipe sizes. Price shall include the cost of Insulation, material and external treatment will be same as of pipe: 80 mm dia

4

-

-

... More
Supplying, installing and fixing in position Y Strainers of PN 16 rating and suitable for following pipe sizes. Price shall include the cost of Insulation, material and external treatment will be same as of pipe: 65 mm dia

6

-

-

... More
Supplying, installing and fixing in position Y Strainers of PN 16 rating and suitable for following pipe sizes. Price shall include the cost of Insulation, material and external treatment will be same as of pipe: 50 mm dia

9

-

-

... More
Supplying, installing and fixing in position Y Strainers of PN 16 rating and suitable for following pipe sizes. Price shall include the cost of Insulation, material and external treatment will be same as of pipe: 40 mm dia

3

-

-

... More
Supplying, installing and fixing in position Y Strainers of PN 16 rating and suitable for following pipe sizes. Price shall include the cost of Insulation, material and external treatment will be same as of pipe: 32 mm dia

11

-

-

... More
Supply, Installation, Testing and Commissioning of following sizes electronic, self- alancing, pressure independent type dynamic balancing valve with integrated 2 way modualating control valve in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20mA electric signal and shall provide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 25 Bar Minimum. The modulating valves cost included with Digital Thermostat alongwith necessary wiring. Valve suitable for 80 mm dia pipe

4

-

-

... More
Supply, Installation, Testing and Commissioning of following sizes electronic, self- alancing, pressure independent type dynamic balancing valve with integrated 2 way modualating control valve in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20mA electric signal and shall provide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 25 Bar Minimum. The modulating valves cost included with Digital Thermostat alongwith necessary wiring. Valve suitable for 65 mm dia pipe

6

-

-

... More
Supply, Installation, Testing and Commissioning of following sizes electronic, self- alancing, pressure independent type dynamic balancing valve with integrated 2 way modualating control valve in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20mA electric signal and shall provide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 25 Bar Minimum. The modulating valves cost included with Digital Thermostat alongwith necessary wiring. Valve suitable for 50 mm dia pipe

9

-

-

... More
Supply, Installation, Testing and Commissioning of following sizes electronic, self- alancing, pressure independent type dynamic balancing valve with integrated 2 way modualating control valve in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20mA electric signal and shall provide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 25 Bar Minimum. The modulating valves cost included with Digital Thermostat alongwith necessary wiring. Valve suitable for 40 mm dia pipe

3

-

-

... More
Supply, Installation, Testing and Commissioning of following sizes electronic, self- alancing, pressure independent type dynamic balancing valve with integrated 2 way modualating control valve in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20mA electric signal and shall provide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 25 Bar Minimum. The modulating valves cost included with Digital Thermostat alongwith necessary wiring. Valve suitable for 32 mm dia pipe

11

-

-

... More
NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including insulation as specified 150 mm dia ( insulated)

6

-

-

... More
Supply, installing and fixing in position flexible connections of required pressure rating ( PN 16) installed at pump suction & discharge and at pipes crossing building expansion joints. Price shall include the cost of Insulation, material and external treatment will be same as of pipe Valves of 150 mm dia

24

-

-

... More
Supply, installation, testing and commissioning of Digital cooling thermostats to be installed for controllig air handling units & fan coil units as described elsewhere in BOQ. Proportional cooling thermostat for controlling AHU.

33

-

-

... More
Supplying, installing and fixing in position Auto air vents of PN 16 rating.

60

-

-

... More
Supplying, installing and fixing in position of Drain/Bleed Valves of PN 16 rating.

80

-

-

... More
Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required

100

-

-

... More
Providing & fixing in position the mercury in glass industrial type thermometres.

100

-

-

... More
Supplying and fixing GI class ‘B’ pipes cut to required lengths and complete with threaded joints. Quoted price shall include providing and fixing in position fittings, elbows, tees, reducers, expanders, mating flanges & sockets for Building Automation System as required.. The pipes shall be of following sizes: GI pipes of 65 mm dia

20

-

-

... More
Supplying and fixing GI class ‘B’ pipes cut to required lengths and complete with threaded joints. Quoted price shall include providing and fixing in position fittings, elbows, tees, reducers, expanders, mating flanges & sockets for Building Automation System as required.. The pipes shall be of following sizes: GI pipes of 50 mm dia

15

-

-

... More
Supplying and fixing GI class ‘B’ pipes cut to required lengths and complete with threaded joints. Quoted price shall include providing and fixing in position fittings, elbows, tees, reducers, expanders, mating flanges & sockets for Building Automation System as required.. The pipes shall be of following sizes: GI pipes of 40 mm dia

50

-

-

... More
Supplying and fixing GI class ‘B’ pipes cut to required lengths and complete with threaded joints. Quoted price shall include providing and fixing in position fittings, elbows, tees, reducers, expanders, mating flanges & sockets for Building Automation System as required.. The pipes shall be of following sizes: GI pipes of 32 mm dia

130

-

-

... More
Supplying and fixing GI class ‘B’ pipes cut to required lengths and complete with threaded joints. Quoted price shall include providing and fixing in position fittings, elbows, tees, reducers, expanders, mating flanges & sockets for Building Automation System as required.. The pipes shall be of following sizes: GI pipes of 25 mm dia

40

-

-

... More
Squar / Rectangular Ducting (Factory Fabricated) Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports/steel wire hangers etc. as per approved drawings and specifications of following sheet thickness complete as required. Thickness 0.63 mm sheet

4000

-

-

... More
Squar / Rectangular Ducting (Factory Fabricated) Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports/steel wire hangers etc. as per approved drawings and specifications of following sheet thickness complete as required. Thickness 0.8 mm sheet

200

-

-

... More
Squar / Rectangular Ducting (Factory Fabricated) Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports/steel wire hangers etc. as per approved drawings and specifications of following sheet thickness complete as required. Thickness 1.00 mm sheet

50

-

-

... More
Square / Rectangular Ducting (Site Fabricated) Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required Thickness 0.63 mm sheet

200

-

-

... More
Square / Rectangular Ducting (Site Fabricated) Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required Thickness 0.80 mm sheet

80

-

-

... More
Square / Rectangular Ducting (Site Fabricated) Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required Thickness 1.00 mm sheet

10

-

-

... More
Square / Rectangular Ducting (Site Fabricated) Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required Thickness 1.25 mm sheet

60

-

-

... More
Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. Fire damper

30

-

-

... More
Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. Actuator with control panel

50

-

-

... More
Supply, installation, testing and commissioning of Motorized (ON-OFF Type) duct mounted GI volume control damper with enthalpy sensor and necessary control wire (minimum 1.5 sq. mm) for integration within AHU room Dampers.

10

-

-

... More
Supply, installation, testing and commissioning of Motorized (ON-OFF Type) duct mounted GI volume control damper with enthalpy sensor and necessary control wire (minimum 1.5 sq. mm) for integration within AHU room Actuator.

22

-

-

... More
Supply, installation and balancing of Extruded Aluminium construction Non return Damper. The NRD will be powder coated in shade approved by Client and installed as per approved shop drawings and specifications.

5

-

-

... More
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.

30

-

-

... More
Supply, installation and balancing of Extruded Aluminium construction Exhaust/Fresh Grilles without volume control dampers. The grilles will be powder coated in shade approved by Client and installed as per approved shop drawings and specifications. The grilles may be double or single louvered, adjustable or fixed as required by Client

45

-

-

... More
Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core

15

-

-

... More
Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core..

15

-

-

... More
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required.

50

-

-

... More
Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc., as per specifications.

25

-

-

... More
Supply, installation, testing and balancing of Powder coated/Anodised extruded aluminium construction inlet air louvers with bird screen for fresh air alongwith GI construction volume control damper.The louvers will be powder coated in shade approved by Client and installed as per approved shop drawings and specifications.

40

-

-

... More
Supply, installation, testing and balancing of Powder coated/Anodised extruded aluminium construction exhaust air louvers with bird screen.The louvers will be powder coated in shade approved by Client and installed as per approved shop drawings and specifications.

30

-

-

... More
Supply, installation, testing and balancing of Exhaust valves 100mm Dia

5

-

-

... More
Supply, installation, testing and balancing of Exhaust valves 125mm Dia

5

-

-

... More
Supply, installation, testing & commissioning of thermal insulated flexible duct of following sizes duly supported at regular interval as per site requirement etc. complete as required as per specifications 200 mm dia

10

-

-

... More
Supply, installation, testing and balancing of Pressure relief dampers as per the specifications Note:All exposed internal surfaces & duct shall be painted in black mat finish by the HVAC contractor. (applicable to internal ducts)

40

-

-

... More
Supply and fixing of acoustic lining of supply air duct and plenum with 25 mm thick resin bonded glass wool having density of 32 kg/m³, with 25 mm X 25 mm GI section of 1.25 mm thick, at 600 mm centre to centre covered with Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminum sheet fixed to inside surface of ducts with cadmium plated nuts, bolts, stick pins, CPRX compound etc. or anti-microbial Chemically cross linked polyethlyne foam of class"O"(XLPE)complete as required and as per specifications. - DSR:16.21 15 mm thick acoustic lining

600

-

-

... More
Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class "O") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation or anti-microbial Chemically cross linked polyethlyne foam of class"O"(XLPE) with Aluminium PE foil complete as per specifications and as required. - DSR:16.23 Insulation of 19 mm thickness

3370

-

-

... More
Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class "O") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation or anti-microbial Chemically cross linked polyethlyne foam of class"O"(XLPE) with Aluminium PE foil complete as per specifications and as required. - DSR:16.23 Insulation of 25 mm thickness for sun exposed duct

80

-

-

... More
Supplying and fixing of 13 mm thick Nitrile rubber insulation on condensate drain piping/fittings includng valves, flanges, union etc.as per the approved shop drawings and specifications. Pipe shall be finished with cladding as per specifications. Condensate drain pipes of 65 mm dia- 13mm thick insulation

20

-

-

... More
Supplying and fixing of 13 mm thick Nitrile rubber insulation on condensate drain piping/fittings includng valves, flanges, union etc.as per the approved shop drawings and specifications. Pipe shall be finished with cladding as per specifications. Condensate drain pipes of 50 mm dia- 13mm thick insulation

15

-

-

... More
Supplying and fixing of 13 mm thick Nitrile rubber insulation on condensate drain piping/fittings includng valves, flanges, union etc.as per the approved shop drawings and specifications. Pipe shall be finished with cladding as per specifications. Condensate drain pipes of 40 mm dia- 13mm thick insulation

50

-

-

... More
Supplying and fixing of 13 mm thick Nitrile rubber insulation on condensate drain piping/fittings includng valves, flanges, union etc.as per the approved shop drawings and specifications. Pipe shall be finished with cladding as per specifications. Condensate drain pipes of 32 mm dia- 13mm thick insulation

130

-

-

... More
Supplying and fixing of 13 mm thick Nitrile rubber insulation on condensate drain piping/fittings includng valves, flanges, union etc.as per the approved shop drawings and specifications. Pipe shall be finished with cladding as per specifications. Condensate drain pipes of 25 mm dia- 13mm thick insulation

40

-

-

... More
Supplying & fixing of Underdeck insulation on RCC slab ceiling with approved sample of Class "O" closed cell Nitrile Rubber Insulation with 25 mm Thickness & density 40-55 Kg/Cum .Thermal Conductivity not exceeding 0.035 W/mK at an average Temperature of 0°C. Material shall have fire performance acc. to BS 476 Part 7 & Part 6, water vapour diffusion resistance ( μ factor ) shall be greater than 7000 & tested from third party for the parameteres.Insulation material shall be factory laminated with Aluminium Foil. 25mm thick

1170

-

-

... More
MOTOR CONTROL CENTRE : Design, manufacture, supply, installation, testing and commissioning of the following cubicle type 2 mm thick sheet steel enclosed separate compartment for each feeder, front operated, rear connections indoor type LT motor control panel, dust and vermin proof, drawout/hinged and lockable doors, complete with internal wiring, colour coding with ferrules, bonding to earth and painting. Quoted price for each panel & motor control centre shall include all associated control wiring and interlocking circuitary. Each MCC shall include cost of cable, cable trays,wiring, control wiring & inter locking between chillers, primary CHW pumps, condenser water pumps, motorized valves at chillers and condensers & flow switch installed in de-coupler by-pass line, in order to execute the required sequence of operation. A separate set of CTs to be provided for BAS and wiring from CT’s and voltage transducers to be brought on to separate set of terminals. All outgoing shall be provided with Stop/Manual/ Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. Motor Control Centre- Section 01 (415 V) bus section consisting of : 1 No. Incoming each consisting of the following : 1 No. 1000 amps 4 Pole ACB with microprocessor based complete with the following : 0 - 500 volts 96 x 96 sq mm digital voltmeter with selector switch. -1Set 0 - 1000 amps 96 x 96 sq mm digital ammeter with 3 No. 1000-/ 5 amps CT’s and selector switch.-1Set Phase indicating lamps. TPN bus bars shall be of Aluminium and shall be sleeved. Phase bus bars shall be rated at 1250 amps and neutral bus bar shall be of 50% capacity. Bus Coupler # 1 Set 1 No. 1000 amps 4 Pole ACB without releases Auxillary contacts with on/off/trip indicating lights # 1 Set Control MCB # 1No. Outgoings 1 2 No. 250 amps TPN MCCB with microprocessor based O/C, S/C protection release & ROM as outgoing to 2 No. 115 KW starter of chilling unit compressor motor. The MCCB compartment shall contain CT operated digital ammeter of 0-400 amps range with selector switch and an indicating lamp with MCB for ‘ON’ status of motor. 2 No. 40 amps MCCB Suitable rating MCCB Star Delta starter for 10 HP motor overloading relay with built in single phasing protection & outgoing feeder to Primary Chilled water pump motor. Each of these compartment shall contain CT operated digital ammeter of 0-100 amps range with selector switch and indicating lamp with MCB for ‘ON / OFF’ status of pump motors. 2 No. 63 amps MCCB with outgoing feeders to variable Frequency Drive (VFD) panel of 20 HP outgoing feeders to Variable Flow Secondary Chilled Water pump motor. Each of these compartment shall contain CT operated digital ammeter of 0-100 amps range with selector switch and indicating lamp with MCB for ‘ON / OFF’ status of pump motors. VFD space provision shall be included. 2 No. 63 amps MCCB with outgoing feeders to variable Frequency Drive (VFD) panel of 25 HP outgoing feeders to Variable Flow Condenser water pump. Each of these compartment shall contain CT operated digital ammeter of 0-100 amps range with selector switch and indicating lamp with MCB for ‘ON / OFF’ status of pump motors. 1 No. 40 amps MPCB with outgoing VFD feeders to 7.5 HP Cooling Tower Fan Moter. Each of these compartment shall contain CT operated digital ammeter of 0-63 amps range with selector switch and indicating lamp with MCB for ‘ON / OFF’ status of pump motors.VFD space provision shall be included Outgoings -2 1 No. 250 amps TPN MCCB with microprocessor based O/C, S/C protection release & ROM as outgoing to 1 No. 115 KW starter of chilling unit compressor motor. The MCCB compartment shall contain CT operated digital ammeter of 0-400 amps range with selector switch and an indicating lamp with MCB for ‘ON’ status of motor. 1 No. 40 amps MCCB Suitable rating MCCB Star Delta starter for 10 HP motor overloading relay with built in single phasing protection & outgoing feeder to Primary Chilled water pump motor. Each of these compartment shall contain CT operated digital ammeter of 0-100 amps range with selector switch and indicating lamp with MCB for ‘ON / OFF’ status of pump motors. 1 No. 63 amps Suitable rating MCCB with outgoing feeders to Variable Frequency Drive (VFD) panel of 20 HP outgoing feeders to Variable Flow Secondary Chilled Water pump motor. Each of these compartment shall contain CT operated digital ammeter of 0-100 amps range with selector switch and indicating lamp with MCB for ‘ON / OFF’ status of pump motors. VFD space provision shall be included. 1 No. 63 ampsSuitable rating MCCB with outgoing feeders to Variable Frequency Drive (VFD) panel of 25 HP outgoing feeders to Variable Flow Condenser water pump. Each of these compartment shall contain CT operated digital ammeter of 0-100 amps range with selector switch and indicating lamp with MCB for ‘ON / OFF’ status of pump motors. 1 No. 40 amps Suitable rating MPCB with outgoing VFD feeders to 7.5 HP Cooling Tower Fan Moter. Each of these compartment shall contain CT operated digital ammeter of 0-63 amps range with selector switch and indicating lamp with MCB for ‘ON / OFF’ status of pump motors.VFD space provision shall be included Necessary cable alleys, space for spare switches, internal wiring, control wiring / cabling and copper earthing of all equipment shall be included. All switches and other components shall be motor duty rating. Spare feeder & space for following: 4 No. 25 HP Motor Only Space for provision, internal switchgear will be installed as per future requirement. Blank space shall be provided. Motor Control Centre No. 1 as described above.

1

-

-

... More
CONTROL PANELS FOR AHU's (IP 65) Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring, incoming, earthing & terminating into MCCB in each panel shall be provided by the electrical contractor. Space in Panel for mounting the VFD shall be included in the price All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. The panel shall include the following components & accessories. a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. b. DOL/SD starter as HP rating c. Terminal block for power distribution as required. d. Contactor, over load relay with built in single phasing protection. e. Phase indicating lights and indicating light for ON status. f. Digital voltmeter and digital ammeter. g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. h. 3 No. of Single Pole MCB's Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator & as a spare. i. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. j. The item includes providing emergeny stop button along with NO/NC contacts / control wiring or any other accessorries required to complete installation in all respects. The button shall be placed near the AHU only. k. 220 / 24 V Transformer The number of control panels shall be as follows: Suitable rating MCB for 1.1 KW motor

11

-

-

... More
CONTROL PANELS FOR AHU's (IP 65) Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring, incoming, earthing & terminating into MCCB in each panel shall be provided by the electrical contractor. Space in Panel for mounting the VFD shall be included in the price All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. The panel shall include the following components & accessories. a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. b. DOL/SD starter as HP rating c. Terminal block for power distribution as required. d. Contactor, over load relay with built in single phasing protection. e. Phase indicating lights and indicating light for ON status. f. Digital voltmeter and digital ammeter. g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. h. 3 No. of Single Pole MCB's Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator & as a spare. i. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. j. The item includes providing emergeny stop button along with NO/NC contacts / control wiring or any other accessorries required to complete installation in all respects. The button shall be placed near the AHU only. k. 220 / 24 V Transformer The number of control panels shall be as follows: Suitable rating MCB for 1.5 KW motor

4

-

-

... More
CONTROL PANELS FOR AHU's (IP 65) Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring, incoming, earthing & terminating into MCCB in each panel shall be provided by the electrical contractor. Space in Panel for mounting the VFD shall be included in the price All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. The panel shall include the following components & accessories. a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. b. DOL/SD starter as HP rating c. Terminal block for power distribution as required. d. Contactor, over load relay with built in single phasing protection. e. Phase indicating lights and indicating light for ON status. f. Digital voltmeter and digital ammeter. g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. h. 3 No. of Single Pole MCB's Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator & as a spare. i. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. j. The item includes providing emergeny stop button along with NO/NC contacts / control wiring or any other accessorries required to complete installation in all respects. The button shall be placed near the AHU only. k. 220 / 24 V Transformer The number of control panels shall be as follows: Suitable rating MCB for 2.2 KW motor

5

-

-

... More
CONTROL PANELS FOR AHU's (IP 65) Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring, incoming, earthing & terminating into MCCB in each panel shall be provided by the electrical contractor. Space in Panel for mounting the VFD shall be included in the price All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. The panel shall include the following components & accessories. a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. b. DOL/SD starter as HP rating c. Terminal block for power distribution as required. d. Contactor, over load relay with built in single phasing protection. e. Phase indicating lights and indicating light for ON status. f. Digital voltmeter and digital ammeter. g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. h. 3 No. of Single Pole MCB's Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator & as a spare. i. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. j. The item includes providing emergeny stop button along with NO/NC contacts / control wiring or any other accessorries required to complete installation in all respects. The button shall be placed near the AHU only. k. 220 / 24 V Transformer The number of control panels shall be as follows: Suitable rating MCB for 3.7 KW motor

3

-

-

... More
CONTROL PANELS FOR AHU's (IP 65) Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring, incoming, earthing & terminating into MCCB in each panel shall be provided by the electrical contractor. Space in Panel for mounting the VFD shall be included in the price All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. The panel shall include the following components & accessories. a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. b. DOL/SD starter as HP rating c. Terminal block for power distribution as required. d. Contactor, over load relay with built in single phasing protection. e. Phase indicating lights and indicating light for ON status. f. Digital voltmeter and digital ammeter. g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. h. 3 No. of Single Pole MCB's Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator & as a spare. i. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. j. The item includes providing emergeny stop button along with NO/NC contacts / control wiring or any other accessorries required to complete installation in all respects. The button shall be placed near the AHU only. k. 220 / 24 V Transformer The number of control panels shall be as follows: Suitable rating MCB for 5.5 KW motor

4

-

-

... More
CONTROL PANELS FOR AHU's (IP 65) Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring, incoming, earthing & terminating into MCCB in each panel shall be provided by the electrical contractor. Space in Panel for mounting the VFD shall be included in the price All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. The panel shall include the following components & accessories. a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. b. DOL/SD starter as HP rating c. Terminal block for power distribution as required. d. Contactor, over load relay with built in single phasing protection. e. Phase indicating lights and indicating light for ON status. f. Digital voltmeter and digital ammeter. g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. h. 3 No. of Single Pole MCB's Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator & as a spare. i. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. j. The item includes providing emergeny stop button along with NO/NC contacts / control wiring or any other accessorries required to complete installation in all respects. The button shall be placed near the AHU only. k. 220 / 24 V Transformer The number of control panels shall be as follows: Suitable rating MCB for 7.5 KW motor

2

-

-

... More
CONTROL PANELS FOR AHU's (IP 65) Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring, incoming, earthing & terminating into MCCB in each panel shall be provided by the electrical contractor. Space in Panel for mounting the VFD shall be included in the price All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. The panel shall include the following components & accessories. a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. b. DOL/SD starter as HP rating c. Terminal block for power distribution as required. d. Contactor, over load relay with built in single phasing protection. e. Phase indicating lights and indicating light for ON status. f. Digital voltmeter and digital ammeter. g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. h. 3 No. of Single Pole MCB's Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator & as a spare. i. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. j. The item includes providing emergeny stop button along with NO/NC contacts / control wiring or any other accessorries required to complete installation in all respects. The button shall be placed near the AHU only. k. 220 / 24 V Transformer The number of control panels shall be as follows: Suitable rating MCB for 11.0 KW motor

1

-

-

... More
CONTROL PANELS FOR AHU's (IP 65) Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring, incoming, earthing & terminating into MCCB in each panel shall be provided by the electrical contractor. Space in Panel for mounting the VFD shall be included in the price All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. The panel shall include the following components & accessories. a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. b. DOL/SD starter as HP rating c. Terminal block for power distribution as required. d. Contactor, over load relay with built in single phasing protection. e. Phase indicating lights and indicating light for ON status. f. Digital voltmeter and digital ammeter. g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. h. 3 No. of Single Pole MCB's Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator & as a spare. i. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. j. The item includes providing emergeny stop button along with NO/NC contacts / control wiring or any other accessorries required to complete installation in all respects. The button shall be placed near the AHU only. k. 220 / 24 V Transformer The number of control panels shall be as follows: Suitable rating MCB for 15.0 KW motor Note: All exposed panel shall be provided with IP55 protection.

2

-

-

... More
CONTROL PANELS FOR AXIAL FANS/ FAN SECTIONS Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels, including anchoring into the wall, wiring terminating into MCCB and copper earthing, in each panel shall be provided by the electrical contractor.And space in Panel for mounting the VFD. All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. The panel shall include the following components & accessories. a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. b. DOL/SD starter as HP rating c. Terminal block for power distribution as required. d. Contactor, over load relay with built in single phasing protection. e. Phase indicating lights and indicating light for ON status. f. Digital voltmeter and digital ammeter. g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. h. 3 No. of Single Pole MCB's Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator & as a spare. i. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. j. The item includes providing emergeny stop button along with NO/NC contacts / control wiring or any other accessorries required to complete installation in all respects. The button shall be placed near the fan only. k. 220 / 24 V Transformer The number of control panels shall be as follows- Suitable rating MPCB with DOL starter for upto 1.1 kW motor

3

-

-

... More
CONTROL PANELS FOR AXIAL FANS/ FAN SECTIONS Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels, including anchoring into the wall, wiring terminating into MCCB and copper earthing, in each panel shall be provided by the electrical contractor.And space in Panel for mounting the VFD. All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. The panel shall include the following components & accessories. a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. b. DOL/SD starter as HP rating c. Terminal block for power distribution as required. d. Contactor, over load relay with built in single phasing protection. e. Phase indicating lights and indicating light for ON status. f. Digital voltmeter and digital ammeter. g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. h. 3 No. of Single Pole MCB's Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator & as a spare. i. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. j. The item includes providing emergeny stop button along with NO/NC contacts / control wiring or any other accessorries required to complete installation in all respects. The button shall be placed near the fan only. k. 220 / 24 V Transformer The number of control panels shall be as follows- Suitable rating MPCB with DOL starter for upto 1.5 kW motor

2

-

-

... More
CONTROL PANELS FOR AXIAL FANS/ FAN SECTIONS Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels, including anchoring into the wall, wiring terminating into MCCB and copper earthing, in each panel shall be provided by the electrical contractor.And space in Panel for mounting the VFD. All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. The panel shall include the following components & accessories. a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. b. DOL/SD starter as HP rating c. Terminal block for power distribution as required. d. Contactor, over load relay with built in single phasing protection. e. Phase indicating lights and indicating light for ON status. f. Digital voltmeter and digital ammeter. g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. h. 3 No. of Single Pole MCB's Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator & as a spare. i. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. j. The item includes providing emergeny stop button along with NO/NC contacts / control wiring or any other accessorries required to complete installation in all respects. The button shall be placed near the fan only. k. 220 / 24 V Transformer The number of control panels shall be as follows- Suitable rating MPCB with DOL starter for upto 2.2 kW motor

8

-

-

... More
CONTROL PANELS FOR AXIAL FANS/ FAN SECTIONS Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels, including anchoring into the wall, wiring terminating into MCCB and copper earthing, in each panel shall be provided by the electrical contractor.And space in Panel for mounting the VFD. All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. The panel shall include the following components & accessories. a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. b. DOL/SD starter as HP rating c. Terminal block for power distribution as required. d. Contactor, over load relay with built in single phasing protection. e. Phase indicating lights and indicating light for ON status. f. Digital voltmeter and digital ammeter. g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. h. 3 No. of Single Pole MCB's Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator & as a spare. i. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. j. The item includes providing emergeny stop button along with NO/NC contacts / control wiring or any other accessorries required to complete installation in all respects. The button shall be placed near the fan only. k. 220 / 24 V Transformer The number of control panels shall be as follows- Suitable rating MPCB with DOL starter for upto 3.7 kW motor

6

-

-

... More
CONTROL PANELS FOR AXIAL FANS/ FAN SECTIONS Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels, including anchoring into the wall, wiring terminating into MCCB and copper earthing, in each panel shall be provided by the electrical contractor.And space in Panel for mounting the VFD. All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. The panel shall include the following components & accessories. a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. b. DOL/SD starter as HP rating c. Terminal block for power distribution as required. d. Contactor, over load relay with built in single phasing protection. e. Phase indicating lights and indicating light for ON status. f. Digital voltmeter and digital ammeter. g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. h. 3 No. of Single Pole MCB's Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator & as a spare. i. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. j. The item includes providing emergeny stop button along with NO/NC contacts / control wiring or any other accessorries required to complete installation in all respects. The button shall be placed near the fan only. k. 220 / 24 V Transformer The number of control panels shall be as follows- Suitable rating MPCB with DOL starter for upto 5.5 kW motor

6

-

-

... More
CONTROL PANELS FOR AXIAL FANS/ FAN SECTIONS Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels, including anchoring into the wall, wiring terminating into MCCB and copper earthing, in each panel shall be provided by the electrical contractor.And space in Panel for mounting the VFD. All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. The panel shall include the following components & accessories. a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. b. DOL/SD starter as HP rating c. Terminal block for power distribution as required. d. Contactor, over load relay with built in single phasing protection. e. Phase indicating lights and indicating light for ON status. f. Digital voltmeter and digital ammeter. g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. h. 3 No. of Single Pole MCB's Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator & as a spare. i. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. j. The item includes providing emergeny stop button along with NO/NC contacts / control wiring or any other accessorries required to complete installation in all respects. The button shall be placed near the fan only. k. 220 / 24 V Transformer The number of control panels shall be as follows- Suitable rating MPCB with DOL starter for upto 7.5 kW motor

10

-

-

... More
CONTROL PANELS FOR AXIAL FANS/ FAN SECTIONS Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels, including anchoring into the wall, wiring terminating into MCCB and copper earthing, in each panel shall be provided by the electrical contractor.And space in Panel for mounting the VFD. All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. The panel shall include the following components & accessories. a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. b. DOL/SD starter as HP rating c. Terminal block for power distribution as required. d. Contactor, over load relay with built in single phasing protection. e. Phase indicating lights and indicating light for ON status. f. Digital voltmeter and digital ammeter. g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. h. 3 No. of Single Pole MCB's Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator & as a spare. i. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. j. The item includes providing emergeny stop button along with NO/NC contacts / control wiring or any other accessorries required to complete installation in all respects. The button shall be placed near the fan only. k. 220 / 24 V Transformer The number of control panels shall be as follows- Suitable rating MPCB with DOL starter for upto 11 kW motor

2

-

-

... More
CONTROL PANELS FOR AXIAL FANS/ FAN SECTIONS Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels, including anchoring into the wall, wiring terminating into MCCB and copper earthing, in each panel shall be provided by the electrical contractor.And space in Panel for mounting the VFD. All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. The panel shall include the following components & accessories. a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. b. DOL/SD starter as HP rating c. Terminal block for power distribution as required. d. Contactor, over load relay with built in single phasing protection. e. Phase indicating lights and indicating light for ON status. f. Digital voltmeter and digital ammeter. g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. h. 3 No. of Single Pole MCB's Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator & as a spare. i. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. j. The item includes providing emergeny stop button along with NO/NC contacts / control wiring or any other accessorries required to complete installation in all respects. The button shall be placed near the fan only. k. 220 / 24 V Transformer The number of control panels shall be as follows- Suitable rating MPCB with DOL starter for upto 15 kW motor

5

-

-

... More
CONTROL PANELS FOR AXIAL FANS/ FAN SECTIONS Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels, including anchoring into the wall, wiring terminating into MCCB and copper earthing, in each panel shall be provided by the electrical contractor.And space in Panel for mounting the VFD. All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. The panel shall include the following components & accessories. a. MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. b. DOL/SD starter as HP rating c. Terminal block for power distribution as required. d. Contactor, over load relay with built in single phasing protection. e. Phase indicating lights and indicating light for ON status. f. Digital voltmeter and digital ammeter. g. For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation. h. 3 No. of Single Pole MCB's Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator & as a spare. i. All starters shall be provided with suitable potential free contract for connections to the Building Automation System. j. The item includes providing emergeny stop button along with NO/NC contacts / control wiring or any other accessorries required to complete installation in all respects. The button shall be placed near the fan only. k. 220 / 24 V Transformer The number of control panels shall be as follows- Suitable rating MPCB with DOL starter for upto 22 kW motor Note: All exposed panel shall be provided with IP55 protection.

3

-

-

... More
Lift: Design, supplying, erecting testing and commissioning of - passenger/ Bed-cum-passenger hospital lift with speed of 1.5 mtr per second, variable voltage variable frequency drive, with or without machine room for the available well size, operating at 415 V 3 phase 50 cycles AC supply, powder coated / Stainless Steel car entrance doors enclosures with suitable colour vinyl flooring, LED car illumination, emergency light, intercom and fan as desired by the user, central opening / side opening door with or without attendant operation, 7 segment display buttons, call register indicator, fireman drive, SS handrails inside car, full length infrared curtain in car door, automatic rescue device with batteries, voice announcing in regional / international languages, Braille buttons with one year warranty and maintenance with necessary scaffolding and minor civil works like fixing of guide rail, counter weight etc. With Machine Room-SS Finish 8 Passengers - 8 Stops

1

-

-

... More
Design, supplying, erecting testing and commissioning of - passenger/ Bed-cum-passenger hospital lift with speed of 1.5 mtr per second, variable voltage variable frequency drive, with or without machine room for the available well size, operating at 415 V 3 phase 50 cycles AC supply, powder coated / Stainless Steel car entrance doors enclosures with suitable colour vinyl flooring, LED car illumination, emergency light, intercom and fan as desired by the user, central opening / side opening door with or without attendant operation, 7 segment display buttons, call register indicator, fireman drive, SS handrails inside car, full length infrared curtain in car door, automatic rescue device with batteries, voice announcing in regional / international languages, Braille buttons with one year warranty and maintenance with necessary scaffolding and minor civil works like fixing of guide rail, counter weight etc. With Machine Room-SS Finish 20 Passenger - 8 Stops

3

-

-

... More
Design, supplying, erecting testing and commissioning of - passenger/ Bed-cum-passenger hospital lift with speed of 1.5 mtr per second, variable voltage variable frequency drive, with or without machine room for the available well size, operating at 415 V 3 phase 50 cycles AC supply, powder coated / Stainless Steel car entrance doors enclosures with suitable colour vinyl flooring, LED car illumination, emergency light, intercom and fan as desired by the user, central opening / side opening door with or without attendant operation, 7 segment display buttons, call register indicator, fireman drive, SS handrails inside car, full length infrared curtain in car door, automatic rescue device with batteries, voice announcing in regional / international languages, Braille buttons with one year warranty and maintenance with necessary scaffolding and minor civil works like fixing of guide rail, counter weight etc. With Machine Room-SS Finish 2 MT Goods Lift - 8 Stops

1

-

-

... More
BMS: BMS Computer System: Supply, installation, testing and commissioning of BMS operator workstation having intel i-5 Processor 10th Gen. with latest technology or Equivalent Server PC, 3.5 GHz, with 16 GB RAM, & 1 TB HDD, 10/100 Mbps Ethernet card, USB connection & internal modem, Microsoft(R) Windows(R) 10 OS Professional Enterprise, Web server software, with 32" colour graphics monitor as per Tender Specifications. Accessories included Mouse, Key Pad, Laserjet, Scanner colour A4 printer with the above BMS System configuration.

1

-

-

... More
BUILDING MANAGEMENT SYSTEM WEB-BASED SERVER SOFTWARE SITC of minimum 3 user web based Server Software for Building Management System with dynamic Vector graphics. The software shall have minimum upto 3 simultaneous users. The Web-Based Server software shall have unlimited users capability. Software should have license point as per I/O Summary with minimum 10-15% spare points.Building Management Software with features like 3D vector dynamic graphics with Autocad import of plan with Zoom In & Zoom Out facility, Plant Viewer, Trend Viewer, Object Viewer, Report Viewer, Alarm viewer. The Web-Based Server software shall permit use of Standard Web-Browsers such as Microsoft Internet Explorer, Netscape Navigator, etc. The software shall be capable of integration third-party systems and should supports latest IP technology (IP V4). Software shall be B-OWS profile & support all open protocols natively such as BACnet, Modbus, Lontalk etc.The Management Stations shall match the BACnet Profile B-BC as per the BTL Listing shall be Rev. 14 and above.(Properitary Protocol shall not be accepted)

1

-

-

... More
PROGRAMMABLE & APPLICATION SPECIFIC CONTROLLER (DDC) - UL LISTED (DDC controllers for Chiller Plant incl. Chillers, Primary Pumps, Secondary Pumps, Condenser Pumps & Cooling Towers) Supply, Installation, Testing & Commissioning of Standalone, Intelligent, UL listed, BTL tested Rev.12 and above, ANSI/ASHRAE approved BACnet I/P, interoperable DDC as per the specification. All the controllers are UL/BTL tested & CE certified. The controller possesses Dual 32 Bit Microprocessor both for IO Management as well as communication. It should store trend logs and event buffer. DDC Controller shall have a resident real time clock with a battery back up. DDC must support trending & scheduling at Controller level. All trend data must be created and saved to the automation station to achieve gap-free trend documentation during communication failure. For AHU's Maximum of One Controller /2 AHU Shall be used. UL Listed BACnet( BTL) B-AAC controller and communication with Expansion units to Main Controller shall be on BACnet I/P. The field controller shall be able to connect in daisy chain , RSTP network, wherein it can support min. 30 controllers in RSTP network. Consider 20% Spare. Proprietry Protocol shall not be accepted The above shall be housed in a vandal proof, lockable & secure MS Cabinets to be supplied along with the Controllers

1

-

-

... More
PROGRAMMABLE & APPLICATION SPECIFIC CONTROLLER (DDC) - UL LISTED (DDC for AHU Floor mounted (upto 2AHU /DDC) ) Supply, Installation, Testing & Commissioning of Standalone, Intelligent, UL listed, BTL tested Rev.12 and above, ANSI/ASHRAE approved BACnet I/P, interoperable DDC as per the specification. All the controllers are UL/BTL tested & CE certified. The controller possesses Dual 32 Bit Microprocessor both for IO Management as well as communication. It should store trend logs and event buffer. DDC Controller shall have a resident real time clock with a battery back up. DDC must support trending & scheduling at Controller level. All trend data must be created and saved to the automation station to achieve gap-free trend documentation during communication failure. For AHU's Maximum of One Controller /2 AHU Shall be used. UL Listed BACnet( BTL) B-AAC controller and communication with Expansion units to Main Controller shall be on BACnet I/P. The field controller shall be able to connect in daisy chain , RSTP network, wherein it can support min. 30 controllers in RSTP network. Consider 20% Spare. Proprietry Protocol shall not be accepted The above shall be housed in a vandal proof, lockable & secure MS Cabinets to be supplied along with the Controllers

6

-

-

... More
PROGRAMMABLE & APPLICATION SPECIFIC CONTROLLER (DDC) - UL LISTED (DDC for AHU Ceiling Suspended (upto 2AHU /DDC)) Supply, Installation, Testing & Commissioning of Standalone, Intelligent, UL listed, BTL tested Rev.12 and above, ANSI/ASHRAE approved BACnet I/P, interoperable DDC as per the specification. All the controllers are UL/BTL tested & CE certified. The controller possesses Dual 32 Bit Microprocessor both for IO Management as well as communication. It should store trend logs and event buffer. DDC Controller shall have a resident real time clock with a battery back up. DDC must support trending & scheduling at Controller level. All trend data must be created and saved to the automation station to achieve gap-free trend documentation during communication failure. For AHU's Maximum of One Controller /2 AHU Shall be used. UL Listed BACnet( BTL) B-AAC controller and communication with Expansion units to Main Controller shall be on BACnet I/P. The field controller shall be able to connect in daisy chain , RSTP network, wherein it can support min. 30 controllers in RSTP network. Consider 20% Spare. Proprietry Protocol shall not be accepted The above shall be housed in a vandal proof, lockable & secure MS Cabinets to be supplied along with the Controllers

5

-

-

... More
PROGRAMMABLE & APPLICATION SPECIFIC CONTROLLER (DDC) - UL LISTED (DDC for Ventilation & Exhaust Fans (upto 5 Fans/DDC) ) Supply, Installation, Testing & Commissioning of Standalone, Intelligent, UL listed, BTL tested Rev.12 and above, ANSI/ASHRAE approved BACnet I/P, interoperable DDC as per the specification. All the controllers are UL/BTL tested & CE certified. The controller possesses Dual 32 Bit Microprocessor both for IO Management as well as communication. It should store trend logs and event buffer. DDC Controller shall have a resident real time clock with a battery back up. DDC must support trending & scheduling at Controller level. All trend data must be created and saved to the automation station to achieve gap-free trend documentation during communication failure. For AHU's Maximum of One Controller /2 AHU Shall be used. UL Listed BACnet( BTL) B-AAC controller and communication with Expansion units to Main Controller shall be on BACnet I/P. The field controller shall be able to connect in daisy chain , RSTP network, wherein it can support min. 30 controllers in RSTP network. Consider 20% Spare. Proprietry Protocol shall not be accepted The above shall be housed in a vandal proof, lockable & secure MS Cabinets to be supplied along with the Controllers

11

-

-

... More
PROGRAMMABLE & APPLICATION SPECIFIC CONTROLLER (DDC) - UL LISTED (DDC for Plumbing & Firefighting System) Supply, Installation, Testing & Commissioning of Standalone, Intelligent, UL listed, BTL tested Rev.12 and above, ANSI/ASHRAE approved BACnet I/P, interoperable DDC as per the specification. All the controllers are UL/BTL tested & CE certified. The controller possesses Dual 32 Bit Microprocessor both for IO Management as well as communication. It should store trend logs and event buffer. DDC Controller shall have a resident real time clock with a battery back up. DDC must support trending & scheduling at Controller level. All trend data must be created and saved to the automation station to achieve gap-free trend documentation during communication failure. For AHU's Maximum of One Controller /2 AHU Shall be used. UL Listed BACnet( BTL) B-AAC controller and communication with Expansion units to Main Controller shall be on BACnet I/P. The field controller shall be able to connect in daisy chain , RSTP network, wherein it can support min. 30 controllers in RSTP network. Consider 20% Spare. Proprietry Protocol shall not be accepted The above shall be housed in a vandal proof, lockable & secure MS Cabinets to be supplied along with the Controllers DDC for Plumbing & Firefighting System

1

-

-

... More
PROGRAMMABLE & APPLICATION SPECIFIC CONTROLLER (DDC) - UL LISTED (DDC for Electrical system) Supply, Installation, Testing & Commissioning of Standalone, Intelligent, UL listed, BTL tested Rev.12 and above, ANSI/ASHRAE approved BACnet I/P, interoperable DDC as per the specification. All the controllers are UL/BTL tested & CE certified. The controller possesses Dual 32 Bit Microprocessor both for IO Management as well as communication. It should store trend logs and event buffer. DDC Controller shall have a resident real time clock with a battery back up. DDC must support trending & scheduling at Controller level. All trend data must be created and saved to the automation station to achieve gap-free trend documentation during communication failure. For AHU's Maximum of One Controller /2 AHU Shall be used. UL Listed BACnet( BTL) B-AAC controller and communication with Expansion units to Main Controller shall be on BACnet I/P. The field controller shall be able to connect in daisy chain , RSTP network, wherein it can support min. 30 controllers in RSTP network. Consider 20% Spare. Proprietry Protocol shall not be accepted The above shall be housed in a vandal proof, lockable & secure MS Cabinets to be supplied along with the Controllers DDC for Electrical system

1

-

-

... More
NETWORK / SUPERVISORY CONTROLLERS Supply, installation, testing and commissioning of Microprocessor based 32 Bit, UL Listed & BTL Listed B-BC profile Rev.14, Web Based Supervisory controller for connecting all field DDC controllers and 3rd party System Integration Units and for transferring data from field devices to BMS Server Software. The Network Controller shall support routing between BACnet/IP , BACnet/LonTalk and BACnet MS/TP, Modbus, Lontalk. The Router shall Supports BACnet/IP and Firmware update via Ethernet and USB Device. Proprietry Protocol shall not be accepted between Router and Management station. Supervisory controller shall be modular in nature, with dual IP. Network supervisory controller shall have cybersecurity features such as IP whitelisting, IP port disablement etc.

1

-

-

... More
SYSTEM INTEGRATION UNITS FOR 3RD PARTY SYSTEM SOFTWARE INTEGRATION - UL listed Controllers Supply, Installation, Testing & Commissioning of System Integration unit consisting of microprocessor based controller units BTL & UL Listed for third party integration. The same should support operations/ monitoring via portable operator terminal. Third Party Integrator/ Gateway shall have cybersecurity features such as IP whitelisting, IP port disablement etc.The controller shall be Native BACnet type with communication via BACnet, LonTalk, Modbus over RS-485. Integration platforms and system controllers for third-party devices and systems via Modbus, J-Bus and other protocols into the automation level via BACnet. The same shall Support operation via local or network-compatible operator units. It should store trend logs and event buffer. Third Party make controller shall not be accepted. Chiller Panel, Automatic Tube Cleaning, Chemical Dosing systemAHU/CSU/DOAS EC Fans, Pump VFD, Transfer pumps, STP Pumps, UPS Integration, DG Integration, Energy Meters, Variable Air Volume Diffusers, Fire Alarm System, Lift Integration, IAQ Sensors Integration unit as mentioned above As per the direction of Engineer In Charge

1

-

-

... More
Supplying, installing, testing and commissioning of IP 65, NTC/PTC, RTD/Themister type immersion Temp. sensor, having accuracy of ±1 deg. C. As per the direction of Engineer In Charge

4

-

-

... More
Supplying, installing, testing and commissioning of IP54, 1 SPDT NO/NC Contact relay, DP Switch -Air, having setting range from 20-300 Pa As per the direction of Engineer In Charge

73

-

-

... More
Supplying, installing, testing and commissioning of IP 65, NTC/PTC RTD/Thermister type T+Rh Sensor for outdoor application As per the direction of Engineer In Charge

1

-

-

... More
Supplying, installing, testing and commissioning of IP 65, NTC/PTC RTD/Thermister type Temp Sensor- Duct type As per the direction of Engineer In Charge

21

-

-

... More
Supplying, installing, testing and commissioning of Duct Pressure Sensor As per the direction of Engineer In Charge

11

-

-

... More
Supplying, installing, testing and commissioning of Split core type Current Relay As per the direction of Engineer In Charge

36

-

-

... More
Supplying, installing, testing and commissioning of IP65, Bi-level Switch with 2 NO/NC for indicating high & Low water level in tanks As per the direction of Engineer In Charge

12

-

-

... More
Supplying, installing, testing and commissioning of IP65, PN16, Water Pressure Sensor, giving 0-10 VDC/4-20 mA output As per the direction of Engineer In Charge

1

-

-

... More
Supplying, installing, testing and commissioning of DC Voltage Transducers As per the direction of Engineer In Charge

2

-

-

... More
Supplying, laying, termination, testing and commissioning of signal cables. (2 core 1 mm2), PVC insulated, tinned copper conductor cable unarmoured cable. As per the direction of Engineer In Charge

7656

-

-

... More
Supplying, laying, termination, testing and commissioning of communication cables. CAT 6 STP cable- unarmoured cable. As per the direction of Engineer In Charge

750

-

-

... More
Supplying and laying of 25mm of Heavy Duty PVC conduit on surface/recess including cutting/filling chases along with conduit accessories etc. complete as required. As per the direction of Engineer In Charge

6380

-

-

... More
GI Flexible conduit for termination in the DDC Panels As per the direction of Engineer In Charge

5104

-

-

... More
Supplying, laying, termination, testing and commissioning of communication cables. (2 core 1 mm2), PVC insulated, shielded tinned copper conductor cable, unarmoured cable. As per the direction of Engineer In Charge

1500

-

-

... More
Supplying, installing, testing and commissioning of 2 mm thick GI perforated cable trays of the following sizes complete with angle iron supports/hanging arrangement etc 40 x 300 x 40 As per the direction of Engineer In Charge

500

-

-

... More
NETWORKING ACCESSORIES Supply, installation, testing and commissioning of 8/16/24 port Layer 2 unmanaged switch The switch shall communicate with other switches to build a network on CAT6 cable within the building complete as per specifications with all necessary accessories As per the direction of Engineer In Charge

1

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.