Indian Institute Of Science Tender

Karnataka, also known as Karunadu, is a state in the southwestern region of India. Karnataka was formed originally as Mysore State on 1st November 1956 and currently is the biggest state in south India. Its capital and largest city is Bengaluru. It covers an area of 191,791 km2 (74,051 sq mi) and is the sixth largest state by area comprising 31 districts. Karnataka is also a state of multiple languages; Kannada being the official and most widely spoken language in Karnataka. Other languages spoken in the state include Tamil, Telugu, Malayalam, Kodava, Konkani and much more.Karnataka tenders are issued by the government of Karnataka, public & private sector organisations. The state government issues majority of the Karnataka tenders, which are for goods and services including construction, road and bridge construction, IT services, engineering services, medical services, educational services amongst many others. Bidassist is one of the largest eprocurement portals, which offers all government tenders from across the world in one place. Bidassist offers information on all Karnataka tenders and other state and authority tenders in no time. Bidassist is a platform where users can look for various Karnataka tenders as well as other tenders.

Indian Institute Of Science - IISC Tender

Works
Civil And Construction
Civil Works Others
Eprocure
Opening Date7 Feb 2020
Closing Date28 Feb 2020
Tender Amount₹ 85,87,60,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
KSRB 2.14-1: Extra for additional lift of 1.5m. or part thereof for excavation In loose / soft or hard soil including cost of materials, labour complete as per specifications. specification.

6571

-

-

... More
KSRB 2.14-2: Extra for additional lift of 1.5m. or part thereof for excavation in soft or hard rock including cost of materials, labour complete as per specifications.

3128

-

-

... More
Filling earth brought from outside ( excluding rock ) in sides of foundations for trenches of retaining walls, sump tanks, under ground structures etc. and else where as directed at site including breaking clods, watering ramming, consolidating and compacting in 150mm thick layers using vibratory compactors, plate compactors, rollers of different capacities and at inaccessible places with wooden/steel rammers to suit site conditions to achieve proctor density of 98% at optimum moisture content, all leads and lifts, bailing/pumping out water to keep site dry while back filling. Rate shall include conveyance of materials, labour, machinery etc., complete as per detailed specification.

535

-

-

... More
KSRB 2.7 : Providing and removing shoring and strutting for protecting the sides of foundation trenches, wherever required, including cost of all materials and labour complete as per specifications. specification. No. KBS 2.5 / 2.13

1800

-

-

... More
KSRB 2.8 : Providing and Filling in foundation with granite / trap broken metal 100mm. and down size, with approved sand including hand packing, ramming, watering, including cost of all materials and labour with lead and lift complete as per specifications. KBS 2.10.2

479

-

-

... More
KSRB 2.10 : Providing sand cement bed with all leads for all materials and lift of 1.5 m. machine mixed, laid in layers of 15cms. thick and well compacted for foundation, including curing cost of materials labour and HOM complete as per specifications. specification. No. KBS 2.10.2 KSRB 2.10 :- do - sand cement bed with 5% cement

10

-

-

... More
KSRB-3.2: Providing and injecting chemical emulsion for Pre-constructional Anti-Termite Treatment, creating continuous chemical barrier under and around the column pits, walls, trenches, basement excavation, top surface of the plinth filling, junction of wall and floor, along the external perimeter of building, expansion joints, over the top surface of consolidated earth on which apron is to be laid, surrounding of pipes and conduits,with chloropyriphos emulsifiable concentrates of 20% concentration at 3.19lit/sqm., including cost of chemical, diluting in water to one percent concentration, labour, HOM complete as per specifications. (Plinth area of the building at ground floor only shall be measured ) Specification No. KBS : 3.2.6 / 3.2.7.

3790

-

-

... More
Providing 50mm thk 1:2:1 Shotcreting using 6 mm down size aggregates with the maximum water to cement ratio of 0.4, including fasten 50mmx50mmx2.8mm weld mesh to the 20mm dia nails.

10

-

-

... More
Providing and fixing/ inserting MS Pipe (ref IS Code1161) of 100mm diameter at a spacing of 500mm c/c from natural ground level as shown in the drawing and grouted into 165 mm dia holes drilled to a depth of 1000mm below the raft or footing level. The pipe thickness is 5.0mm thick. Annular space between the pipe and drilled hole shall be grouted with cement slurry and cebex 100. Work shall be completed with M20 grade concrete.

10

-

-

... More
CEMENT CONCRETE WORKS KSRB 4.1.3: Providing and laying in position plain cement concrete of mix M 1:4:8 with OPC @180kgs with 40mm and down size graded granite metal coarse aggregates @0.85 cum and fine aggegates @ 0.57 cum machine mixed, concrete laid in layers not exceeding 15 cms. thick, well compacted, in foundation, including cost of all materials, labour, HOM curing complete as per specifications. Specification No. KBS 4.1, 4.2

674

-

-

... More
Lift Charges - LGF

275

-

-

... More
KSRB 4.2.1: Providing and laying in position reinforced cement concrete of design mix M25 with OPC @340kgs, with 20mm and down size graded granite metal coarse aggregates @0.70 cum and fine aggegates @ 0.47 cum with super plastisiser @ 3 liters confirming to IS 9103-1999 reafirmed -2008 at machine mixed, concrete laid in layers not exceeding 15cms thick, vibrated for all works in foundation for footing, pedestal, retaining walls, return walls,walls (any thick ness) including attached pilasters, coloums pillers, posts, struts, buttresses, bed blocks, anchor blocks & plinths etc., including cost of all materials, labour, HOM curing complete but excluding cost of reinforcement as per specifications. Specification No. KBS 4.1, 4.6

1871

-

-

... More
Lift Charges - LGF

899

-

-

... More
Lift Charges - FF

53

-

-

... More
Lift Charges - SF

54

-

-

... More
Lift Charges - TF

49

-

-

... More
Lift Charges - Terrace & Above

44

-

-

... More
KSRB 4.2.2: Providing and laying in position reinforced cement concrete of design mix M20 with OPC @320kgs, with 20mm and down size graded granite metal coarse aggregates @0.69 cum and fine aggegates @ 0.460 cum with super plasticisers @3 liters confirming to IS 9103-1999 reaffirmed -2008, machine mixed, concrete laid in layers not exceeding 15 cms thick,vibrated for all works in foundation for footing, pedestal, retaining walls, return walls,walls (any thick ness) including attached pilasters, coloums pillers, posts, struts, buttresses, bed blocks, anchor blocks & plinths etc., including cost of all materials, labour, HOM curing complete but excluding cost of reinforcement as per specifications. Specification No. KBS 4.1, 4.6

1238

-

-

... More
Lift Charges - LGF

250

-

-

... More
KSRB 4.2.7: Providing and laying in position reinforced cement concrete of design mix M25 with OPC @340kgs with 20mm and down size graded granite metal coarse aggregates @0.70cum and fine aggegates @ 0.47 cum with super plastisiser @3lts confirming to IS9103-1999 Reaffirmed -2008, machine mixed, concrete laid in layers not exceeding 15 cms thick, vibrated for all works in ground floor level for roof slabs, staircase, lintles and beams, retaining walls, return walls, walls (any thick ness) including attached pilasters, coloums, lintles, pillars, pillers, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window cills, fillets etc., including cost of all materials, labour, HOM curing, complete but excluding cost of reinforcement as per specifications. Specification No. KBS 4.1, 4.6

2369

-

-

... More
Lift Charges - LGF

279.07

-

-

... More
Lift Charges - FF

542.1

-

-

... More
Lift Charges - SF

396.86

-

-

... More
Lift Charges - TF

333.7

-

-

... More
Lift Charges - Terrace & Above

254.65

-

-

... More
Providing and laying in place at all levels light weight concrete using damaged / broken AAC (to be manually broken to the desired size) in the mix ratio of 1:3:6 ( 1 part cement, 3 part coarse sand and 6 part AAC block of desired size) for filling of sunken portions including all leads and lifts, curing compacting and finishing using broom of the top most layer complete as directed by Engineer Incharge.

42

-

-

... More
Providing and laying foam Concrete of density 1100Kg/Cum for deck slab mix design as recommended by engineers, including all leads and lifts, transporting, pumping, curing compacting and finishing complete as directed by Engineer Incharge.

1432

-

-

... More
SHUTTERING WORKS KSRB 4-6.1 : Providing and removing centering, shuttering, strutting, propping etc., and removal of form work for foundations, footings, bases of columns for mass concrete including cost of all materials, labour complete as per specificaitons. Specification No. KBS 4.6.2

2970

-

-

... More
Lift Charges - LGF

1078

-

-

... More
KSRB 4-6.2 : Providing and removing centering, shuttering, strutting, propping etc., and removal of form work for suspended floors, landings, balconies and likes, thickness upto 200 mm including cost of all materials, labour complete as per specificaitons for heights more than 3.50m from ground level. Specification No. KBS 4.6.2 - do - for 0 to 5 mtrs

3018

-

-

... More
Lift Charges - LGF

38

-

-

... More
Lift Charges - FF

649

-

-

... More
Lift Charges - SF

689

-

-

... More
Lift Charges - TF

594

-

-

... More
Lift Charges - Terrace & Above

691

-

-

... More
KSRB 4-6.4 : Providing and removing centering, shuttering, strutting, propping etc., and removal of form work for vertical surface such as walls at any thickness, including attached pilasters, buttresses, plinth cills and string courses cost of all materials, labour complete as per specificaitons. Specification No. KBS 4.6.2

8031

-

-

... More
Lift Charges - LGF

427

-

-

... More
Lift Charges - FF

950

-

-

... More
Lift Charges - SF

918

-

-

... More
Lift Charges - TF

923

-

-

... More
Lift Charges - Terrace & Above

1005

-

-

... More
KSRB 4-6.5 : Providing and removing centering, shuttering, strutting, propping etc., and removal of form work for columns, pillars, post and struts, square / rectangular / polygon in plan including cost of all materials, labour complete as per specificaiton. Specification No. KBS 4.6.2

2416

-

-

... More
Lift Charges - LGF

463

-

-

... More
Lift Charges - FF

418

-

-

... More
Lift Charges - SF

418

-

-

... More
Lift Charges - TF

418

-

-

... More
Lift Charges - Terrace & Above

174

-

-

... More
KSRB 4-6.6 : Providing and removing centering, shuttering, strutting, propping etc., and removal of form work for columns, pillars, post and struts, circular or curved in plan including cost of all materials, labour complete as per specificaiton. Specification No. KBS 4.6.2

23

-

-

... More
Lift Charges - FF

12

-

-

... More
KSRB 4-6.7 :Providing and removing centering, shuttering, strutting, propping etc., and removal of form work for sides and soffits of beams, beam haunchings, cantilever girders, bressumers and lintels not exceeding 1m in depth including cost of all materials, labour complete as per specificaitons. Specification No. KBS 4.6.2

1179

-

-

... More
Lift Charges - LGF

472

-

-

... More
KSRB 4-6.11 :Providing and removing centering, shuttering, strutting, propping etc., and removal of form work for Stairs (excluding landing) except spiral staircase including cost of all materials, labour complete as per specificaiton. Specification No. KBS 4.6.2

381

-

-

... More
Lift Charges - LGF

44

-

-

... More
Lift Charges - FF

77

-

-

... More
Lift Charges - SF

77

-

-

... More
Lift Charges - TF

77

-

-

... More
Providing, fabricating and erecting form work at all levels and places wherever needed / specified as per drawing including striking with 12 mm Plastic coated, marine resistant waterproof ply/Smooth finished MS plates with adjustable steel props of acceptable Staging system and with sufficient bracing as approved by consultant with repetations not more than five times subject to approval of architect. Cost to include designing of proper form work and staging system to suit the requirements, Submission of design calculations and shop drawings for approval, sealing the joints with heavy duty brown self-adhesive tape, aligning to line and levels including M.S. Ties, PVC Spacer, Providing openings/ cut outs/ pockets, applying de-shuttering chemical, De-shuttering as approved by the consultant etc., complete at all levels, double heights and profiles for payment. Note : Only plan area shall be considered. No extra shall be paid for Side shuttering.

2557

-

-

... More
STEEL REINFORCEMENT WORKS KSRB 4.9.2 : Providing TMT steel reinforcement for R.C.C work including straightening, cutting, bending, hooking, placing in position, lapping and / or welding wherever required, tying with binding wire and anchoring to the adjoining members wherever necessary complete as per design (laps, hooks and wastage shall not be measured and paid) cost of materials, labour, HOM complete as per specifications. Specification No. KBS 4.6.3. TMT Steel : For all RCC works the contractor shall purcharsed the TMT STEEl manufactured by the authorized dealers and necessary physical tests for the TMT steel so procured shall be conducted. As per IS 1786 if necessary chemical tests may also be insisted. For lapping steel reinforcement,preferably 25mm and above, only welding splices shall be done. -do- TMT Bars Fe 500

623

-

-

... More
Lift charges for steel of all diameters for additional floors over ground floor per floor height of 3.5 m or part there of cost of labour, complete as per specification. Specification No. KBS Lift Charges - LGF

189

-

-

... More
Lift Charges - FF

98

-

-

... More
Lift Charges - SF

85

-

-

... More
Lift Charges - TF

76

-

-

... More
Lift Charges - Terrace & Above

69

-

-

... More
STRUCTURAL STEEL & ROOF DECK WORKS Supplying, fabricating and erecting in position structural steel works riveted or bolted or welded in columns, beams, portals, runners, roof structural elements, trusses, purlins, bracings, sag rods, platforms, decking, railings, catwalks, ladders, stairs, hangers, monorails, jibcranes etc. as per design, drawings and details and as per specifications. Vendor to prepare shop drawings, erection schedules and obtaining consultant approvals. Rate to include consumables such as bolts, nuts, washers, surface preparation as per specifications,Water Based Intumescent Paint conforming to UL 263 or BS 476 Pt 20/21 Certifire and UL Labelled Product for 120 mins fire rating to Structural Steel. The product packaging must bear a UL certification mark. The Intumescent shall be top sealed with Polyurethane Finish 2 Coats(40 microns each) to a total of 80 microns including zinc chromate primer and surface preparation as directed by Engineer

855

-

-

... More
Supplying, fabricating and erecting in position Galvanised structural steel works riveted or bolted or welded in columns, beams, portals, runners, roof structural elements, trusses, purlins, bracings, sag rods, platforms, decking, railings, catwalks, ladders, stairs, hangers, monorails, jibcranes etc. as per design, drawings and details and as per specifications and complete as approved by engineer/ Architect. Vendor to prepare shop drawings, erection schedules and obtaining consultant approvals. Hot-dip galvanizing thickness and procedue to be as per BS EN ISO 1461. Steel sections of thickness more than 6 mm shall have a minimum galvanized coating thickness of 85 µm. Rate to include consumables such as bolts, nuts, washers, surface preparation and two coat enamel paint over etch zinc chromate primer as approved by architect/Engineer , as per specifications.

40

-

-

... More
Providing, fabricating and erecting Roof deck, with 1 mm thick GI sheet, which form the base of the composite flooring, including the cost of nut, bolt, corner bead, shear studs and other acessories for installation etc complete as directed by Engineer Incharge. concrete will be paid seperately. Rate to include shear studs etc. and all other accessories that is necessary to complete the work in accordance to the drawings & specification complete as directed by the Engineer In Charge

9082

-

-

... More
MASONRY WORKS KSRB 5.4 : Providing and constructing granite / trap / basalt size stone masonry in superstructure with cement mortar , edges of stones chistle dressed in courses not less than 15 cms high, bond stones at two m. apart in each course including cost of materials, labour, scaffolding, curing complete as per specifications. KBS 5.1.13 KSRB 5.4-3 :- do- with cement mortar 1:6

5

-

-

... More
Constructing granite / basalt size stone masonry in superstructure with cement mortar 1:6, where the granite size stones are used from the dismantled existing structure and the same is used for the construction includes edges of stones chistle dressed in courses not less than 15 cms high, bond stones at two m. apart in each course including cost of materials, labour, scaffolding, curing complete as per specifications.

360

-

-

... More
Demolishing stone rubble/size masonry manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge including cost of cleaning etc.

550

-

-

... More
Providing and constructing Exposed burnt brick masonry with approved quality of modular bricks of size 230mmX100mmX50mm of class designation 7.5 newton per sqmm ( Machine moulded Wirecut bricks ) including making horizontal and vertical grooves 10mm wide12 mm deep complete with cement mortar 1:6 for basement and superstructure including cost of materials, labour charges, scaffolding, curing complete as per specifications. - do - with cement mortar 1:6

5

-

-

... More
Provinding and constructing non load bearing wall with Light Weight Concrete (Autoclaved aerated concrete) Blocks confirmIng to IS:2185 (part-3) 1984 and IS 6441-1972 of compressive strength of 3.0N/sq mm with a thin layer of polymer based jointing solvent for super structure with neccesary scaffolding, curing including cost of all materials, labour, lead & lift etc, complete as per specifications - do - with 600x200x100mm size Blocks

681

-

-

... More
Lift Charges - LGF

55

-

-

... More
Lift Charges - FF

109

-

-

... More
Lift Charges - SF

159

-

-

... More
Lift Charges - TF

142

-

-

... More
- do - with 600x200x150mm size Blocks

119

-

-

... More
Lift Charges - LGF

6

-

-

... More
Lift Charges - FF

33

-

-

... More
Lift Charges - SF

33

-

-

... More
Lift Charges - TF

33

-

-

... More
- do - with 600x200x200mm size Blocks

6458

-

-

... More
Lift Charges - LGF

710

-

-

... More
Lift Charges - FF

1257

-

-

... More
Lift Charges - SF

1243

-

-

... More
Lift Charges - TF

1186

-

-

... More
Lift Charges - Terrace & Above

618

-

-

... More
KSRB 5-14.1: Providing and constructing load bearing wall with solid concrete blocks having block density not less than 1800kg/m3 having a minimum average compressive strength of 5.00 N/mm2 confirming to IS 2185 (Part 1):2005 and constructed with CM 1:4, as per IS 2572:2005 including cost of all materials labour charges, scaffolding, curing, hire charges of machineries etc., complete as per specifications. KBS No.5.4 - do - with solid concrete bolck of size 400X200X200mm

509.2

-

-

... More
Dismantling of existing block work and other structures for service opening and other purpose comprising of masonry, cement, concrete, wood work, steel work, including finishing the opening, scaffolding wherever necessary, sorting the dismantled materials, disposing of unserviceable materials and stacking the serviceable materials with all lifts complete as per specifications and instruction of engineer/ Architect.

10

-

-

... More
FLOORING WORKS Providing and laying MATTE FINISH STAIN RESISTANT VITRIFIED TILES in different sizes and 10 mm thick of approved make, with water absorption's less than 0.08% and confirming to IS : 15622 in all colours and shades and size for FLOORING laid on bed of 20 mm thick cement mortar 1:3 mix, to approved pattern. Rate to include applying Laticrete epoxy grout, providing spacers upto 3 mm wide, cleaning, curing etc. complete at all levels, protecting the laid tiles with POP untill completion and handing over and cleaning subsequently before handing over, including cost of all materials, labour, curing, complete HOM of equipments and machineries, all leads and lift, loading and unloading charges, transportation cost and conveyance of all matterials & and all other incidental charges at all floor levels etc., complete for successful completion of work as per drawings & specifications and as directed by the Engineer-in-charge.

5724

-

-

... More
Same as above but as 100 mm high skirting fixed flush to the wall. Rate to include chasing, fixing, and making good the wall and plaster as also making 6 x 6 groove in plaster.

1799

-

-

... More
Providing and laying ANTI - SLIP GLAZED VITRIFIED TILES in different sizes and 10 mm thick of approved make, with water absorption's less than 0.08% and confirming to IS : 15622 in all colours and shades and size for FLOORING laid on bed of 20 mm thick cement mortar 1:3 mix, to approved pattern. Rate to include applying Laticrete epoxy grout, providing spacers upto 3 mm wide, cleaning, curing etc. complete at all levels, protecting the laid tiles with POP untill completion and handing over and cleaning subsequently before handing over, including cost of all materials, labour, curing, complete HOM of equipments and machineries, all leads and lift, loading and unloading charges, transportation cost and conveyance of all matterials & and all other incidental charges at all floor levels etc., complete for successful completion of work as per drawings & specifications and as directed by the Engineer-in-charge.

525

-

-

... More
Same as above but as 100 mm high skirting fixed flush to the wall. Rate to include chasing, fixing, and making good the wall and plaster as also making 6 x 6 groove in plaster.

18

-

-

... More
Providing and laying machine cut, MIRROR POLISHED KOTA STONE of size 4'X2' IN FLOORING, LANDING ETC (SAMPLE TO BE APPROVED BY ARCHITECT / CLIENT) with minimum thickness of the stone slab being 25 mm to 35 mm over a bed of Cement Mortar 1:6 and average thickness 25 mm in shape and pattern and at all levels and all positions to proper line, level and slope as per drawings / directions by Engineer In-Charge over existing concrete bed or top of roof laid to line and level and jointed with cement slurry mixed with pigment to match the shade of the slab. Rate to include cost of all materials, labour, curing, filling of joints, machine polishing (7 rounds of tin oxide mirror polish with Vito protector sealant and Tenax Proseal sealant) , curing, acid cleaning after completion and also POP protective coat to prevent scratches, HOM of equipments and machineries, all leads and lifts, loading and unloading charges, transportation cost and conveyance of all material and all other incidental charges etc., complete for successful completion of work and as directed by the Engineer-in-charge. (Allow necessary cut-outs for pipes, waste couplings etc.)

3120

-

-

... More
Same as above but as 100 mm high skirting fixed flush to the wall. Rate to include chasing, fixing, and making good the wall and plaster as also making 6 x 6 groove in plaster.

5

-

-

... More
Providing and laying machine cut, CROSS CUT JAISALMER OR ETA GOLD IN FLOORING, LANDING ETC (SAMPLE TO BE APPROVED BY ARCHITECT / CLIENT) COMPLETE IN MIRROR POLISH with minimum thickness of the stone slab being 25 mm to 35 mm over a bed of Cement Mortar 1:6 and average thickness 25 mm in shape and pattern and at all levels and all positions to proper line, level and slope as per drawings / directions by Engineer In-Charge over existing concrete bed or top of roof laid to line and level and jointed with cement slurry mixed with pigment to match the shade of the slab. Rate to include cost of all materials, labour, curing, filling of joints, machine polishing, curing, acid cleaning after completion and also POP protective coat to prevent scratches, HOM of equipments and machineries, all leads and lifts, loading and unloading charges, transportation cost and conveyance of all material and all other incidental charges etc., complete for successful completion of work and as directed by the Engineer-in-charge. (Allow necessary cut-outs for pipes, waste couplings etc.)

1201

-

-

... More
Same as above but as 100 mm high skirting fixed flush to the wall. Rate to include chasing, fixing, and making good the wall and plaster as also making 6 x 6 groove in plaster.

2320

-

-

... More
Providing and laying machine cut, ROUGH KOTA STONE IN FLOORING with 4-6mm grout, LANDING ETC (SAMPLE TO BE APPROVED BY ARCHITECT / CLIENT) with minimum thickness of the stone slab being 25 mm to 35 mm over a bed of Cement Mortar 1:6 and average thickness 25 mm in shape and pattern and at all levels and all positions to proper line, level and slope as per drawings / directions by Engineer In-Charge over existing concrete bed or top of roof laid to line and level and jointed with cement slurry mixed with pigment to match the shade of the slab. Rate to include cost of all materials, labour, curing, filling of joints, machine polishing, curing, acid cleaning after completion and also POP protective coat to prevent scratches, HOM of equipments and machineries, all leads and lifts, loading and unloading charges, transportation cost and conveyance of all material and all other incidental charges etc., complete for successful completion of work and as directed by the Engineer-in-charge. (Allow necessary cut-outs for pipes, waste couplings etc.)

1454

-

-

... More
Same as above but as 100 mm high skirting fixed flush to the wall. Rate to include chasing, fixing, and making good the wall and plaster as also making 6 x 6 groove in plaster.

5

-

-

... More
GRANITE FLOORING- Leather / Honed Finish Granite Providing and laying machine cut Jet Black granite of approved colour and quality in in ANTIQUE finish in pattern as indicated in drawing IN FLOORING, LANDING ETC (SAMPLE TO BE APPROVED BY ARCHITECT / CLIENT) OF SIZE AS IN DRAWINGS with minimum thickness of the stone slab being 20 mm to 25 mm over a bed of Cement Mortar 1:4 and average thickness 25 mm in shape and pattern and at all levels and all positions to proper line, level and slope as per drawings / directions by Engineer In-Charge over existing concrete bed or top of roof laid to line and level and Joints in the flooring to be filled with approved grout of approved shade as per manufacturers specifications. Quoted rate to include the cost of wastages, lead and lift, chipping the floor (if required) to lay the new flooring, and catering away the debris from site, curing, protection with 3 mm Celloboard joined with Masking Tape, one coat of stone guard till hand-over & cleaning. Rate to include cost of all materials, labour, curing, filling of joints, machine polishing, curing, acid cleaning after completion and also POP protective coat to prevent scratches, HOM of equipments and machineries, all leads and lifts, loading and unloading charges, transportation cost and conveyance of all material and all other incidental charges etc., complete for successful completion of work and as directed by the Engineer-in-charge. (Allow necessary cut-outs for pipes, waste couplings etc.)

1339

-

-

... More
Same as above but as 100 mm high skirting fixed flush to the wall. Rate to include chasing, fixing, and making good the wall and plaster as also making 6 x 6 groove in plaster.

16

-

-

... More
Providing and laying machine cut Sira stone of approved colour and quality in Leather / Honed finish as cill and coping including edge finishing in pattern as indicated in drawing (SAMPLE TO BE APPROVED BY ARCHITECT / CLIENT) with minimum thickness of the stone slab being 20 mm to 25 mm over a bed of Cement Mortar 1:4 and average thickness 25 mm in shape and pattern and at all levels and all positions to proper line, level and slope as per drawings / directions by Engineer In-Charge and Joints to be filled with approved grout of approved shade as per manufacturers specifications. Quoted rate to include the cost of wastages, lead and lift, chipping (if required) and catering away the debris from site, curing, protection with 3 mm Celloboard joined with Masking Tape, one coat of stone guard till hand-over & cleaning. Rate to include cost of all materials, labour, curing, filling of joints, machine polishing, curing, acid cleaning after completion and also POP protective coat to prevent scratches, HOM of equipments and machineries, all leads and lifts, loading and unloading charges, transportation cost and conveyance of all material and all other incidental charges etc., complete for successful completion of work and as directed by the Engineer-in-charge.

384

-

-

... More
Same as above but as 100 mm high skirting fixed flush to the wall. Rate to include chasing, fixing, and making good the wall and plaster as also making 6 x 6 groove in plaster.

5

-

-

... More
Providing and laying Vacuum Dewatered Cement Flooring 100 mm thick using RCC M20 grade using 20 mm and down gauge graded granite aggregate laid in panels as per structural drawing laid to proper level, slope or fall and top surface finished smooth using mechanical float and disc, including vibrating, vacuum dewatering, mechanical troweling, cleaning of base, form work, curing etc., complete as per directions of engineer in charge

35

-

-

... More
Providing and laying as per manufactures's specification, Epoxy Underlay Nitoflor EU5 at 2.0mm + Epoxy Self Levelling: Nitoflor SL 2000 at 2.0mm. (total - 4.0mm thick) to a glossy finish

5

-

-

... More
Providing and laying of 75 mm thick screed plain cement concrete 1:2:4 with 20 mm and downgraded stone aggregates wherever to required thickness, slope in flooring including placing, compaction, curing and finished with trowel finished smooth as directed, complete. The level of the screeding has to be 8 mm below the hard floor level or as directed by Engineer In-Charge so as to obtain smooth slurry finish.(The contractor should survey the site to ensure that the level differences are within the above limits to ensure that the rates quoted would be based on the site condition).

9445

-

-

... More
Providing and laying VITRIFIED TILES in different sizes and 10 mm thick of approved make in DADO, with water absorption's less than 0.08% and confirming to IS : 15622 in all colours and shades and size for FLOORING laid on bed of 20 mm thick cement mortar 1:3 mix, to approved pattern. Rate to include applying Laticrete epoxy grout, providing spacers upto 3 mm wide, cleaning, curing etc. complete at all levels, protecting the laid tiles with POP untill completion and handing over and cleaning subsequently before handing over, including cost of all materials, labour, curing, complete HOM of equipments and machineries, all leads and lift, loading and unloading charges, transportation cost and conveyance of all matterials & and all other incidental charges at all floor levels etc., complete for successful completion of work as per drawings & specifications and as directed by the Engineer-in-charge.

1196

-

-

... More
Providing and fixing Heat Resistant Terrace Tiles of approved make and size with solar reflection 0.5 and initial emittance 0.75 on waterproof and sloped surface of terrace, laid on 20 mm thick cement sand mortar in the ratio of 1:4 (1 cement : 4 coarse sand) and grouting the joints with mix of white cement & marble powder in ratio of 1:1, including rubbing and polishing of the surface upto 3 cuts complete, including providing skirting upto 150 mm height along the parapet walls in the same manner.

1754

-

-

... More
Anti - Static Vinyl Flooring Providing and laying in position Approved make Anti-Static Vinyl flooring of 3 mm thickness as per manufacturer's specifications. Tiles / Planks may be used. Shade as per approved sample. Rate to include surface preparation, levelling using POP if required and covering of the floor by plastic sheet securley and re-covering it as required. Rate to include final cleaning before handover. Rate to also include providing suitable brushed SS transition profile as required and approved by the architects. The product should be homogeneous and single layered. Color and pattern details shall be dispersed throughout the thickness of the wear layer. It shall conform to group "T" wear resistance as per EN649, Clean Room certified with class 'A' as per ASTMF5100, static electrical charges 2KV, Flammability resistance of class Bfl-s1asperGB8624-2006, Dynamic coefficient of friction of class DSasperEN13893, Thermal Resistance of 0.072m2K/WasperEN12667, Thermal conductivity of 0.071W/mKasperEN12524, impact sound reduction of 3dBasperISO10140, Slip Resistance of class R9 as per DIN51130, Residual indentation of 0.03 mm as per GB/T4085-2005, Color fastness rating of ≥ 6 as per ISO105-B02, total weight being 2.8 kg/m2 as per EN430. The product shall be suitable for applications in class 23/34/43 areas as per EN685. Product shall exhibit antistatic behaviour, resistance to bacteria, resistance to chemical, resistance to staining, suitability to castor chair. Installation- It is important to ensure the subfloor on which the sheet is being laid is smooth, flat, hard and free from moisture, grease etc. In case of uneven subfloor the same should be levelled using selfleveling compound. IPS/Vitrified/ceramic/mosaic tiles do not provide zero leveled subfloor. The moisture present in the subfloor should be less than 8% before installation of the floor. The sheet should be installed as per recommended adhesive. The installation shall be undertaken as per manufacturers installation instructions.

291

-

-

... More
Providing and fixing 600mm removable raised/false access flooring with system and its components of approved make for different plenum height with possible height adjustment upto 50 mm, comprising of modular load bearing floor panels supported on G.I. rectangular stinger frame work and G.I. Pedestal etc. all complete, as per the architectural drawings, as specified and as directed by Engineer-incharge consisting of : a) Providing at required spacing to form modular framework, pedestals made out of GI tube of thickness minimum 2 mm and 25 mm outer diameter, fully welded on to the G.I. Base plate of size 100mmx100mmx3mm at the bottom of the pedestal tube, G.I. pedestal head of size 75mmx75mmx3.5 mm welded with GI fullythreaded stud 16mm outer diameter with two GI Check nuts screwed on the stud for level adjustment upto 50mm, locking and stabilizing the pedestal head in for level adjustment upto 50mm, locking and stabilizing the pedestal head in position at the required level. The pedestals shall be fixed to the subfloor (base)through base plate using epoxy based adhesive of approved make or the machine through base plate using epoxy based adhesive of approved make or the machine screw with rawl plug. b) Stringers system in all steel construction hot dipped galvanized of rectangular size 570x20x30x0.80 mm thick having holes at both ends for securing the stringers on to the pedestal head using fully threaded screws ensuring maximum lateral stability in all directions, the grid formed by the pedestal and stringer assembly shall receive the floor panel, this system shall provide adequate solid,rigid support for access floor panel, the system shall provide a minimum clear uninterrupted clearance between the bottom of the floor for electrical conduits and wiring etc. all complete as per the architectural drawings, as specified and as directed by the Engineer-in-charge. c) Providing and fixing Access Floor panel of 600x600x32 mm medium grade Filled Steel anti static high pressure Lamination of 800H grade (FS800H). Access Floor panel shall finished with Antistatic High Pressure laminate with Non Warp technology uptobe steel welded construction with an enclosed bottom pan with uniform pattern of 64 hemispherical cones. The top and bottom plates of Steel Gauges: top 0.6 mm and bottom 0.7 mm fused spot welded together (minimum 64 welds in each dome and 20 welds along each flange). The panel should be Corroresist epoxy coated for lifetime rust protection and cavity formed by the top and bottom plate is filled with Pyrogrip noncombustible Portland cementitious core mixed with lightweight foaming compound. The access floor shall be factory core mixed with lightweight foaming compound. The access floor shall be factory 1mm thickness for superior adhesion and Surface flatness within 0.75mm.The panel is to withstand a Concentrated Load of 363 kgs applied on area 25mm x 25mm The panel will withstand and Uniformly Distributed Load (UDL) minimum 1250 kg/sqm and an impact load of 50kg all complete as per the approved manufacturers specification and as per the direction of Engineer-in-charge. All specification must be printed on the side of the panel to ensure the quality of the product. 600 mm Finished Floor Height (FFH).

89

-

-

... More
Stone cladding - Dry 50 mm thick honed finish granite stone slab in dry cladding mechanically fixed with and including Contractor's designed galvanised (minimum 600 gms/m²) mild steel framework structure, primer coat and three or more coats of epoxy paint to steelwork's surfaces, stainless steel Grade 316: bolts, screws, washers and fixing accessories, adhesive for grouting of clamps in stone, forming grooves, filling grooves with non-staining and non-streaking silicon sealants (approved make), backer rod, drilling, anchoring, grouting, edge polishing and chamfering. Rate to include also for any necessary cutting, fittings, margins, wastages, borders, patterns, inlays, rubbing, curing and polishing etc, all complete

5

-

-

... More
STEEL & ALUMINIUM WORK KSRB 7.5 : Providing and fixing pull and push type rolling shutters of approved make out of 18 guage, 75mm wide cold rolled steel laths of convex corrugation, with side guides and bottom rail, with interlocking arrangements for steel laths by means of alternate clips, suspension shaft with High tension coil type springs two numbers, mounted on specially designed pipe shaft, with bracket plates, guide channels, ball bearing arrangements, for inside & outside locking with push & pull operations complete including pulling hooks, 4Nos. handles with all fittings and accessories, painted with a coat of red lead paint (without top cover) cost of materials, labour, HOM of machinery complete as per specifications. Shutter size 3mx2.8 m Specification No. KBS 7.10 / 7.12

27

-

-

... More
SINGLE GLAZING PARTITION Providing and fixing full height partitions with aluminium frame 25 mm x 36 mm sections anodized, powder coated (As per IS code) to be provided for partitions with necessary rubber gaskets, dry acoustic gaskets, screws fixed to underside of suspended ceiling or bulk head and to the finished floor and aluminium beadings as approved by the engineer in charge. The partition will have 12 mm thick toughened glass with glass to glass joints done in vertical ‘I’ section in aluminium in the same anodised finish. Partition systems to be of aproved make/vendor. Rate to include providing shop drawings as per archiitects approval The complete frame shall be firmly fixed to floors, wall, and ceilings. The costs must include leads, lifts, assembling, fixing and placing in position and also suitable intersection points to completed as directed by Engineer in Charge/ Architect. All color or shades as approved by engineer in charge/Architect.

1382

-

-

... More
SINGLE GLAZING PARTITION DOOR: Providing and fixing aluminium work for doors with aluminium section 25 mm x 100 mm of approved make conforming to IS: 733 and IS: 1285 fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top. bottom and sides with required EPDM rubber/ neoprene gasket etc. Partition systems to be of aproved make/vendor. Rate to include providing shop drawings as per archiitects approval. All aluminium sections to be in natural anodised / powdercoated finish (minium thickness of powder coating 50 micron). Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snab beading for glazing / panelling, stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge/ Architect. The rate to incorporate batwing acoustic seals and rebate in the back to accept the glazing. Rate to include supply and installation of single or double leaf glazed shutter as per drawing with 12 mm toughened glass fixed to door frame with two hinges with Hardware like Exposed TS 90 Door closer, Narrow stile mortise lock with 35 mm backset & lever handle with Oval roses, 70 mm EPC with one side key & one side thumb turn indicator & Half moon door stopper & dropdown seal and consealed door closure etc. complete. All ironmongery to be finished in SS.

5

-

-

... More
DOUBLE GLAZING PARTITION Providing and fixing full height double glazed partitions with anodized aluminium frame 25 mm x 36 mm sections anodized, powder coated (As per IS code) to be provided for partitions with necessary rubber gaskets, dry acoustic gaskets, screws fixed to underside of suspended ceiling or bulk head and to the finished floor and aluminium beadings as approved by the engineer in charge. The partition will have 24 mm thick DGU Glass ( 6 mm toughened glass + 12 mm air gap + 6 mm clear toughened glass) of approved make for fixed glass panels, including necessary accessories (EPDM gasket, clip angle etc) complete fitted with glazing clips and rubber beading. The complete frame shall be firmly fixed to floors, wall, and ceilings. Partition systems to be of aproved make/vendor. Rate to include providing shop drawings as per archiitects approval. The costs must include leads, lifts, assembling, fixing and placing in position and also suitable intersection points to completed as directed by Engineer in Charge/ Architect All color or shades as approved by engineer in charge/Architect.

5

-

-

... More
Double GLAZING PARTITION DOOR: Providing and fixing aluminium work for doors with aluminium section 25 mm x 100 mm of approved make conforming to IS: 733 and IS: 1285 fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top. bottom and sides with required EPDM rubber/ neoprene gasket etc. Partition systems to be of aproved make/vendor. Rate to include providing shop drawings as per archiitects approval All aluminium sections to be in natural anodised / powdercoated finish (minium thickness of powder coating 50 micron). Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snab beading for glazing / panelling, stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. The rate to incorporate batwing acoustic seals and rebate in the back to accept the glazing. Rate to include supply and installation of single or double leaf glazed shutter as per drawing with 24 mm thick DGU Glass ( 6 mm Reflective glass + 12 mm air gap + 6 mm clear toughened glass) of approved make for fixed glass panels, including necessary accessories (EPDM gasket, clip angle etc) complete fitted with glazing clips and rubber beading. fixed to door frame with two hinges with Hardware like Exposed TS 90 Door closer, Narrow stile mortise lock with 35 mm backset & lever handle with Oval roses, 70 mm EPC with one side key & one side thumb turn indicator & Half moon door stopper & dropdown seal and consealed door closure etc. complete. All ironmongery to be finished in SS.

5

-

-

... More
EXTERNAL GLAZING(WINDOWS) SINGLE GLAZED FIXED: Providing and fixing of Powder Coated / Anodized Aluminum dixed Window using sections of size as per drawing including 6 mm thick clear toughed glass for shutters & fixed glass panels for shutters fitted with glazing clips 19 mm x 17.3 mm x 11 mm and 0.9 mm thick and rubber beading using Z sections of 33 mm, web thickness 4 mm, weight 0.663 kg/m: central mullion section 59 x 33 mm with web thickness 3 mm, weight 1.123 kg/m: The shutters on aluminium hinges with approved quality of fixtures including necessary accessories such as EPDM gasket, clip angle, TPI, wheels, handles, stopper, star lock, aluminium tower bolts, handles, stays etc complete etc. All glazing and frames to be of approved make. All openable hardware will be of approved make. Rate should include all material, fixtures, labour and HOM of machinery complete for successful completion of work as per specifications including all leads and lifts, loading unloading charges and transportation cost and conveyance of all materials and all other incidental charges etc complete for successful completion of work as directed by the Engineer -in - charge labour, scaffolding, tools, tackles, silicon sealant for sealing all gaps allround the window. Aluminium sections anodised 12 to 15 microns, including cutting to required length, joints mitred subdividing the frame tenonned and rivetted in the assembled frame stiffened with end clips at corners angles etc., and fixed to the walls, lintels, floor beams / cills as the case may be with necessary steel screws, raul plugs, or teak wood gatties including cutting masonry or concrete and making good the original surface using cement mortar, as per drawings and aluminium sections pretreated for removal of any rust and protection of further rust formation and coated with the greasy materials for non-adhesion of mortar and any other sticky materials, (this coatings should be cleaned after installation). For complete details refer architectural drawing.

1107

-

-

... More
EXTERNAL GLAZING(WINDOWS) SINGLE GLAZED FIXED AND CASEMENT: Providing and fixing of Powder Coated / Anodized Aluminum Partly Fixed & Partly Casement Window/Door using sections of size as per drawing including 6 mm thick clear toughed glass for shutters & fixed glass panels for shutters fitted with glazing clips 19 mm x 17.3 mm x 11 mm and 0.9 mm thick and rubber beading using Z sections of 33 mm, web thickness 4 mm, weight 0.663 kg/m: central mullion section 59 x 33 mm with web thickness 3 mm, weight 1.123 kg/m: The shutters on aluminium hinges with approved quality of fixtures including necessary accessories such as EPDM gasket, clip angle, TPI, wheels, handles, stopper, star lock, aluminium tower bolts, handles, stays etc complete etc. All openable hardware will be of approved make. Rate should include all material, fixtures, labour and HOM of machinery complete for successful completion of work as per specifications including all leads and lifts, loading unloading charges and transportation cost and conveyance of all materials and all other incidental charges etc complete for successful completion of work as directed by the Engineer -in - charge labour, scaffolding, tools, tackles, silicon sealant for sealing all gaps allround the window. Aluminium sections anodised 12 to 15 microns, including cutting to required length, joints mitred subdividing the frame tenonned and rivetted in the assembled frame stiffened with end clips at corners angles etc., and fixed to the walls, lintels, floor beams / cills as the case may be with necessary steel screws, raul plugs, or teak wood gatties including cutting masonry or concrete and making good the original surface using cement mortar, as per drawings and aluminium sections pretreated for removal of any rust and protection of further rust formation and coated with the greasy materials for non-adhesion of mortar and any other sticky materials, (this coatings should be cleaned after installation). For complete details refer architectural drawing.

1183

-

-

... More
Same as above (8.7) single glazed with 6mm thick toughenend glass for ventilators

5

-

-

... More
EXTERNAL GLAZING(WINDOWS) SINGLE GLAZED FIXED AND CASEMENT: Providing and fixing of Powder Coated / Anodized Aluminum Partly Fixed & Partly Casement OR Top Hung Window / Door using sections of size as per drawing including with 8 mm clear toughened glass of approved make having properties as visible light transmittance (VLT) of 25 to 35 %, light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc using sections of size as per drawing for fixed glass panels, including necessary accessories (EPDM gasket, clip angle etc) complete fitted with glazing clips and rubber beading. All glazing and frames to be of approved make. All openable hardware will be of approved make. Rate should include all material, fixtures, labour and HOM of machinery complete for successful completion of work as per specifications including all leads and lifts, loading unloading charges and transportation cost and conveyance of all materials and all other incidental charges etc complete for successful completion of work as directed by the Engineer -in - charge labour, scaffolding, tools, tackles, silicon sealant for sealing all gaps allround the window. Aluminium sections anodised 12 to 15 microns, including cutting to required length, joints mitred subdividing the frame tenonned and rivetted in the assembled frame stiffened with end clips at corners angles etc., and fixed to the walls, lintels, floor beams / cills as the case may be with necessary steel screws, raul plugs, or teak wood gatties including cutting masonry or concrete and making good the original surface using cement mortar, as per drawings and aluminium sections pretreated for removal of any rust and protection of further rust formation and coated with the greasy materials for non-adhesion of mortar and any other sticky materials, (this coatings should be cleaned after installation). For complete details refer architectural drawing.

3

-

-

... More
STRUCTURAL GLAZING : Providing and fixing structural glazing of curtain wall system with 6mm thick toughened glass ET-450 H.S glass with pressure plate and pressure cap consisting of aluminium anodized to approved colour from available range, assembled in framed structure as required with mullions and transoms. Framing to include all necessary fixtures and fasteners required to fix onto masonry /RCC structure. The system design shall be based on Open joint system & design shall include pressure equalization with minimum 3 barrier gaskets for improved weather performance, drainage at all floor levels, The design to accommodate building movements, thermal expansions & the seismic movements. All metal joints in the wet area shall be small joint sealant applied to ensure water tightness. The three barrier gasket system consists of 1st ,2nd & 3rd barrier of EPDM gaskets to achieve the required compression & seal in the system. The extruded aluminium sections of Alloy 6063 T5 / T6 & tolerances confirming to DIN / EN standard. The structural profiles shall have minimum 2mm wall thickness. All the internal & externally visible surfaces shall have Powder coating of 60 - 80 microns or natural anodized finish. The quote rate shall include all design, engineering & shop drawing approval from architect & consultant. The quote rate shall include statutory obligations and safety code compliance as per client. Rate to also include providing and installing additional structural supports, ms box sections, plates etc made from MS metal plates and secured to building structure for receiving various facade elements, understructures, structural glazing members etc. The item is to be used for structural elements that are necessary to support the facade systems , apart from those that form a part of thr base building. Rates to include these supports , chemical and mechanical fasteners, providing primer coat and fnal paint coat as required.

346

-

-

... More
Same as above (8.11) single glazed with 8mm thick toughenend glass for Skylight

112

-

-

... More
Aluminium Louver System Providing and fixing frames for Aluminium Z-Louver System on shafts at required level made out of heavy duty aluminium anodized Z" shaped profile of size 105 x 50 x 2 mm thick section designed to satisfy the structural design criteria specified in the technical specification and profile and shape to be as per drawing of varying size and fixed either on the Glazing system or on the Windows and Ventilators as specified. All louvers and frames to be of approved make. The system shall be fixed using GI screws, aluminium L Cleats and all other necessary accessories, sealing shall be done using weather sealant of Dow Corning 789 with necessary Backer rods etc., Rate shall include the supply and fixing of S.S Fly Mesh.

72

-

-

... More
Aluminium Louver Enclosure Providing and fixing frames for Aluminium Z-Louver System Spacing of blades @ 70mm and height of enclosure = 4.8m.UOM is sqm, for enclosure around MEP work in ground floor and terrace, at required level made out of heavy duty aluminium anodized Z" shaped profile of size as mentioned in drawing with 2mm thick blades designed to satisfy the structural design criteria specified in the technical specification and profile and shape to be as per drawing of varying size and fixed either on the Glazing system or on the Windows and Ventilators as specified in the drawings. The system shall be fixed using GI screws, aluminium L Cleats and all other necessary accessories, sealing shall be done using weather sealant of Dow Corning 789 with necessary Backer rods etc.

1437

-

-

... More
Providing and fixing of Aluminium composite panel of approved make and colour for wall cladding for straight Brick/RcclStone walls & columns/ beams with necessary aluminium frame works at required level made out of 50x25x4mm C section or equivalent. The panel should consist of 3mm thick non-halogonated FR grade mineral based polymer core (2 hrs fire resistance as per ASTM E119-12 & clause B, SI, do as per BS476 EN 13501) sandwiched between O.50mm skin thick aluminium sheet making a total panel thickness of 4mm. The surfaces will be finished with PVDF based coating on topsides and service coating on reverse sides would be in polyester paint. The system shall be fixed using GI brackets, aluminium L cleats and stainless steel bolts and nuts complete with spring washer and cap nuts and all other necessary accessories, sealing shall be done using weather sealant of Dow Corning 789 with necessary rods etc., complete

10

-

-

... More
Providing and fixing of GRC cladding (Glass reinforced concrete) of approved make and colour for wall cladding for straight Brick/RcclStone walls & columns/ beams with necessary MS frame works at required level made out of 50x25x4mm C section or equivalent with total panel thickness of 15mm. The surfaces will be finished as instructed by engineer/Architect. The system shall be fixed using GI brackets, aluminium L cleats and stainless steel bolts and nuts complete with all other necessary accessories, sealing complete. The GRC elements should be made from ‘53 grade’ White Portland Cement, Fine graded Quartz & Silica Sand, Alkali Resistant Glass Fiber, Super Plasticizers, Polymers and U.V resistant Synthetic inorganic pigments manufactured from approved manufacturers. The GRC flexural strength average Limit of proportionality should be minimum 6 N/mm2 & Modulus of rupture should be minimum 15 N/mm2 for tests done on 28 days cured samples. The GRC elements must be classes using dry fixing methodology with S.S 304 quality screws/fasteners. The joints between the two GRC element must be filled with PU Sealent. The GRC used in this project must be produced from the company manufacturing White Cement (Ultratech or Equivalent).

3314.07

-

-

... More
Providing and fixing of Copper cladding of approved make and 0.7mm thickness for wall cladding for straight Brick/RcclStone walls & columns/ beams with necessary aluminium frame works at required level made out of 50x25x4mm C section or equivalent. The system shall be fixed using GI brackets, aluminium L cleats and stainless steel bolts and nuts complete with all other necessary accessories, sealing complete as instructed by engineer / Architect

140

-

-

... More
CEILING WORKS Providing and Fixing 15 mm thick densified tegular edged eco friendly light weight calcium silicate suspended false ceiling tiles of approved texture of size 595 x 595 mm in true horizontal level , suspended on inter locking metal grid of hot dipped galvanized steel sections frame works (galvanizing @ 120 grams persqm including both side) consisting of main T runner suitabl spaced at joints to get required length and of size 24 x 38 mm made 1from 0.33 mm thick (minimum) sheet, spaced 1200 mm centre to centre, and cross 'T' of size 24 x 28 mm made out of 0.33 mm (minimum) sheet, 1200 mm long spaced between main 'T' at 600 mm centre to centre to form a grid of 1200 x 6OO mm and secondary cross 'T' of length 600 mm and size 24 x 28 mm made of 0.33 mm thick (minimum) sheet to be inter locked at middle of the 1200 x BOO mm panel to from grid of size 600 x 600 mm, resting on periphery walls I partitions on a Perimeter wall angle pre-coated steel of size (24 x 24 x 3000 mm made of 0.40 mm thick (minimum) sheet with the help of rawl plugs at 450 mm centre to centre with 25 mm long dry wall screwes at 230 mm intervals and laying 15 mm thick densifed edges calcium silicate ceiling tiles of approved texture In the grid, including cutting I making opening for services like .diffuse, grills, fight fittings, fixtures, smoke detectors etc., wherever required.'T' runners to be suspended from ceiling using G.I. slotted cleats of size 25 x 35 x 1 mm fixed to ceiling with 12.5 mm dia and 50 mm long .dash fasteners, 4 mm G.I. adjustable rods with galvanised steel level clips of size 85 x 30 x 0.80mm spaced at 1200 mm centre to centre along bottom exposed with 24 mm of all T sections shall be pre painted with polyster baked paint for all heights, as per speCifications, and as directed by Engineer-in-charge. Note: G.I. perimeter channel and supporting materials are to be provided to make any opening for light and any others fittings/ fixtures with 300x300, 9 mm ply templates, diffusers etc. and should be supported properly to maintain the integrity of the ceiling.(Area shall be measured in plan area for measurement ).

513

-

-

... More
Providing & Fixing of true horizontal level false ceiling grid system of approved make, 19 mm BWP plywood of approved make and finished in veneer with mellamine polish of approved shade at all levels. Rate to be all inclusive of making drops and cut outs for light fixtures, AC Grills etc as per drawing issued. The tile shall be laid on grid with 15 / 20 mm wide T-section flanges colour white having rotary stitch in diagonal sections i.e. the Main Runner, 1200 mm & 600 mm Cross Tees with a web height of 38 mm and a load carrying capacity of 14 Kgs / M2 with a minimum pull out strength of 100 kgs. The T Sections have a Galvanizing of 90 grams per M2 and need to be installed with Suspension system of approved make. Main runner spaced at 1200 mm centre s securely fixed to the structurals off it using approved make suspension system at 1200 mm maximum centre. The First / Last suspension system at the end of each main runner should not be greater than 450 mm from the adjacent wall. Flush fitting 1200 mm long cross tees to be interlocked between main runners at 600 mm centre to form 1200 x 600 mm module. Cut cross tees longer than 600 mm require independent support. 600 x 600 mm module to be formed by fitting 600 mm long flush fitting cross tees centrally between the 1200 mm cross tees. Perimeter trim to be approved make wall angles of size 3000 x 19 x 19 mm, secured to walls at 450 mm maximum centres. SUSPENSION SYSTEM accessories manufactured and supplied by approved make consisting of M6 approved Fasteners with Vertical Hangers made of Galvanised steel of size 26 x 26 x 25 x 1.2 mm with a Galvanised Thickness of 80 gsm, A pre-Straightened Hanger wire of dia – 2.5 mm of 1.8 m length., thickness of 80 gsm and a tensile strength of 344 - 413 MPa, along with Adjustable hook clips of 0.8 mm thick, galvanised spring steel for 2.68 mm with a minimum pull strength of 110 kg. The adjustable clip also consists of a 3.5 mm aquiline wire to be used with the main runner.

5

-

-

... More
Providing and fixing Gypsum False Ceiling with trap door which includes G.I. Perimeter Channels of size .55 mm thick (having One Flange of 20 mm and another flange of 30 mm and a web of 27 mm) along with perimeter of ceiling, screw fixed to brick wall / partition with the help of Nylon sleeves and screws at 610 mm centres. Then suspending G.I. intermediate channels of size 45 mm (0.9 mm thick with 2 flanges of 15 mm each) from the soffit at 1220 mm centres with ceiling angle of width 25 mm X 10 mm X 0.55 mm thick fixed to soffit with G.I. cleat and steel expansion fasteners. Ceiling section of 0.55 mm thick having knurled web of 51.5 mm and 2 flanges of 26 mm each with lips of 10.5 mm are then fixed to the intermediate channel with the help of connecting clips and in direction perpendicular to the intermediate channel at 450 mm centres. IN HEAVY LOCAL GI CHANNELS. Trap door finished with 12mm Gypsum, plastered and painted same as ceiling. 12.5 mm tapered edge Gypboard (conforming to IS 2095-1982) is then screw fixed to ceiling section with 25 mm dry wall Philips screws at 230 mm centres. Screw fixing is done mechanically with drilling machine with suitable attachment. Finally tapered edges of the Gyp boards are to be jointed and finished so as to have a flush look which includes filling and finishing with jointing compound, paper tape etc complete as per the recommended practices of India Gypsum. Rate to be included all kinds of profiles and cut outs required for light fixtures, Speakers, Smoke detector, trap doors and AC grill in the ceiling. Rate to include Providing and fixing of Trap doors made with 18 mm waterproof plywood with Aluminum support structure all around and one intermediate section. Plywood to be lipped with TW lipping and finished with 1 mm laminate on ply and duco paint on lipping. Rate to include either concealed or cut hinges ( 2 pairs) dead lock, concealed aldrop, recessed handles etc all complete. Additional support in the false ceiling ot take the weight of the trap doors also to be included in the rate.

285

-

-

... More
Providing & Fixing of Mineral Fibre Acoustical Suspended Ceiling System with Tegular Edge Tiles with 15mm recessed grid. The tiles should have Humidity Resistance (RH) of 99%, NRC 0.7, Light Reflectance ≥84%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Colour White, Fire Performance UK Class 0 / Class 1 (BS 476 pt - 6 &7) with sand texture finish in module size of 600x600x20mm, suitable for Green Building application, with Recycled content of 49%. The tile shall be laid on profile grid system with 15mm white flanges incorporating a 6mm central reveal in white/black colour and with a web height of 38mm and a load carrying capacity of minimum 7.90 Kgs/M2 (as per standard installation layout mentioned below) & pull out strength of 100Kgs. Silhouette, Main Runners & Cross Tees to have mitred ends & “birdsmouth” notches to provide mitred cruciform junctions. The T Sections have a Galvanizing of 90 grams per M2 and need to be installed with Suspension system. INSTALLATION: To comprise main runner spaced at 1200mm securely fixed to the structural soffit using suspension system (specifications below) at 1200mm maximum. The First/Last suspension system at the end of each main runner should not be greater than 450mm from the adjacent wall. Flush fitting 1200mm long cross tees to be interlocked between main runners at 600mm to form 1200 x 600 mm module. Cut cross tees longer than 600mm require independent support. 600 x 600mm module to be formed by fitting 600mm long flush fitting cross tees centrally between the 1200 mm cross tees. Perimeter trim to be wall angles of size 3000x19x19mm, secured to walls at 450 mm maximum. Installation to be carried out by Trained Installation team & Installation should be carried out as per recommended procedure. SUSPENSION SYSTEM accessories manufactured and supplied by approved make World Industries approved make consisting of M6 Anchor Fasteners with hanger hole, pre Straightened Hanger wire of dia – 2.5 mm of 1.80 m length having a tensile strength of 344-413 MPa and a minimum pull strength of 110 kgs. (Adjustable hook clips of 0.7mm thick, galvanized spring steel can also be used for installation purpose as an additional accessory. The adjustable clip also consists of a 4 mm aquiline wire to be used with the main runner) Providing opening for light and any others fittings/ fixtures with 300x300, 9 mm ply templates and extra support for fixtures and any fittings and co ordinating with MEP team as directed by Engineer/ Architect.

2752

-

-

... More
Providing & Fixing of Soft Fibre Acoustical Suspended Ceiling System with Beveled Tegular Edge Tiles With 15mm recessed Grid. The tiles should have Humidity Resistance (RH) of 95%, NRC 0.9 - 1.0, Light Reflectance ≥85%, Colour White, Fire Performance UK Class 0 / Class 1 (BS 476 pt - 6 &7) in module size of 600x600x15mm, suitable for Green Building application, with Recycled content of 66% GW & 74% RW. The tile shall be laid on profile grid system with 15mm white flanges incorporating a 6mm central reveal in white/black colour and with a web height of 38mm and a load carrying capacity of minimum 7.90 Kgs/M2 (as per standard installation layout mentioned below) & pull out strength of 100Kgs. Silhouette, Main Runners & Cross Tees to have mitred ends & “birdsmouth” notches to provide mitred cruciform junctions. The T Sections have a Galvanizing of 90 grams per M2 and need to be installed with Suspension system of approved make. The Tile & Grid system used together should carry a 10 year warranty. INSTALLATION: To comprise main runner spaced at 1200mm securely fixed to the structural soffit using suspension system (specifications below) at 1200mm maximum. The First/Last suspension system at the end of each main runner should not be greater than 450mm from the adjacent wall. Flush fitting 1200mm long cross tees to be interlocked between main runners at 600mm to form 1200 x 600 mm module. Cut cross tees longer than 600mm require independent support. 600 x 600mm module to be formed by fitting 600mm long flush fitting cross tees centrally between the 1200 mm cross tees. Perimeter trim to be wall angles of size 3000x19x19mm, secured to walls at 450 mm maximum. Installation to be carried out by Trained Installation team & Installation should be carried out as per recommended procedure. SUSPENSION SYSTEM accessories manufactured and supplied by approved make consisting of M6 Anchor Fasteners with hanger hole, pre Straightened Hanger wire of dia – 2.5 mm of 1.80 m length having a tensile strength of 344-413 MPa and a minimum pull strength of 110 kgs. (Adjustable hook clips of 0.7mm thick, galvanized spring steel can also be used for installation purpose as an additional accessory. The adjustable clip also consists of a 4 mm aquiline wire to be used with the main runner).

1980

-

-

... More
Providing & Fixing of Aluminium Microlook Lay-in Standard Perforated metal ceiling consisting of 600x600mm Lay-in tiles of Aluminium in 0.7 mm thickness. The perforation shall have Micro Perforation having hole diameter as 2.5mm and open area as 16%. The tile shall be powder coated to White color having powder coat thickness ranging from 60-80 microns. Back side of the tile will have Soundtex fleece hot pressed to achieve NRC upto 0.7 and Fire Performance of Class 0/Class 1 as per BS476 Part 6 & 7 in module size of 600x600mm. The tile shall be laid on profile grid system with 15mm white flanges incorporating a 6mm central reveal in white/black colour and with a web height of 38mm and a load carrying capacity of minimum 7.90 Kgs/M2 (as per standard installation layout mentioned below) & pull out strength of 100Kgs. Silhouette, Main Runners & Cross Tees to have mitred ends & “birdsmouth” notches to provide mitred cruciform junctions. The T Sections have a Galvanizing of 90 grams per M2 and need to be installed with Suspension system of approved make. INSTALLATION: To comprise main runner spaced at 1200mm securely fixed to the structural soffit using system (specifications below) at 1200mm maximum. The First/Last system at the end of each main runner should not be greater than 450mm from the adjacent wall. Flush fitting 1200mm long cross tees to be interlocked between main runners at 600mm to form 1200 x 600 mm module. Cut cross tees longer than 600mm require independent support. 600 x 600mm module to be formed by fitting 600mm long flush fitting cross tees centrally between the 1200 mm cross tees. Perimeter trim to be wall angles of size 3000x19x19mm, secured to walls at 450 mm maximum. In case of end tiles lesser than 600mm, use lay-in end cap for installation to have a Microlook effect on perimeters. Installation to be carried out by Trained Installation team & Installation should be carried out as per recommended procedure. SUSPENSION SYSTEM accessories manufactured and supplied by approved make consisting of M6 Anchor Fasteners with hanger hole, pre Straightened Hanger wire of dia – 2.5 mm of 1.80 m length having a tensile strength of 344-413 MPa and a minimum pull strength of 110 kgs. (Adjustable hook clips of 0.7mm thick, galvanized spring steel can also be used for installation purpose as an additional accessory. The adjustable clip also consists of a 4 mm aquiline wire to be used with the main runner).

5

-

-

... More
FINISHING WORKS KSRB 15.3 Providing 12 mm thick cement plaster in single coat with cement mortar to brick masonry including rounding off corners wherever required smooth rendering, : Providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications. KSRB 15.3.1 - do - with cement mortar 1:3

9343

-

-

... More
Lift Charges - LB

1490

-

-

... More
Lift Charges - FF

1232

-

-

... More
Lift Charges - SF

1630

-

-

... More
Lift Charges - TF

1716

-

-

... More
Lift Charges - Terrace

620

-

-

... More
KSRB15-3 : Providing 12 mm thick cement plaster in single coat with cement mortar to ceiling including rounding off corners wherever required smooth rendering, : Providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications KSRB 15.3.13 - do - with cement mortar 1:3

255

-

-

... More
Lift Charges - LB

33

-

-

... More
Lift Charges - FF

49

-

-

... More
Lift Charges - SF

49

-

-

... More
Lift Charges - TF

53

-

-

... More
KSRB15-5 : Providing rough cement plastering 15mm thick in single coat with cement mortar to brick masonry for base of dadooing works with sand of approved quality, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications KSRB 15-5.1 - do - with cement mortar 1:4

1472

-

-

... More
Lift Charges - LB

132

-

-

... More
Lift Charges - FF

379

-

-

... More
Lift Charges - SF

321

-

-

... More
Lift Charges - TF

321

-

-

... More
KSRB15-7 : Providing lime rendering for plastering to wall and ceiling , including cost of materials, labour, curing complete as per specifications

9343

-

-

... More
Providing and rendering 20 mm thick cement plastering on external surfaces of brick or concrete surfaces in two layers consisting of 8 mm thick sand faced plaster in cement mortar 1:5 (1 cement : 5 fine sand) top coat mixed with integral waterproofing compound as per maufacturer's specifications and specified fibers as per maufacturer's specifications over a base coat of 12 mm thick rendering in cement mortar 1:5 (1 cement : 5 coarse sand), forming key to receive the finishing coat including necessary scaffolding and curing etc. complete at all heights.

5610

-

-

... More
KSRB 15-15.1 : Providing and applying painting in two coats with plastic emulsion paint of approved brand on wall surface to give an even approved shade after throughly brushing the surface, free from mortar drops and other foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour, complete as per specifications _do_ with primer

8301

-

-

... More
KSRB 15-15.2 : Extra over Item 15-15.1 for painting two coats with plastic emulsion paint of approved brand and shade on ceiling and / or sloping roof as per specifications

611

-

-

... More
Providing two coats of painting to Ceiling and Walls with Premium Emulsion Paint of approved shade and manufacture over a coat of primer including preparing the surface to receive the painting, putty work etc., complete.

20

-

-

... More
KSRB 15.10.1 Providing white washing to new wall surface in two coats with lime of approved quality, to give an even shade including cost of materials, labour, complete as per specifications.

1423

-

-

... More
Providing Internal wall with 2mm thick polished plaster armourcoat texture paint finish using approved brand paint appiled uniformly over two coats of putty and one coat of water based primer including of all materials, machineries, labour, transportion,loading and unloading all lead and lift and other incidental charges including scaffolding and removing stains, complete as per specification.

892

-

-

... More
Providing and applying weather proof exterior emulsion (water based 100% acrylic) grade paint to all type of cement plasters, concrete, exterior ceiling etc. or surface / sub straits (which are subjected to continuous seepage and dampness. The surface to be painted shall be made free from any loose paint, dust, grease and any fungus, algae or moss, on it shall got be removed thoroughly by vigorous wire brushing and cleaning with water. Then one coat of exterior grade wall primer be applied after which any surface imperfection such as holes, dents, fine cracks shall be corrected by filling with external wall putty. Thereafter second coat of exterior grade wall primer and again surface imperfection to be corrected. Thereafter Apex weatherproof exterior emulsion paint to be applied in two coats. The color and pattern / color combination of the paint shall be got approved from Engineer in charge. Contractor has to submit photographs of building with colour combinations for sample selection. The stock of the quantity for all material as manufacturer’s theoretical consumption (per unit of actual wall surface area) shall be made available at site before commencement of the painting work. The rate includes cost of all materials, labour, scaffolding, ladders charges, storing & safeguarding the labour in all heights (all external walls, compound walls etc.). Contractor has to provide all precautions’ and arrange safety belts, helmets to all working labours at site.

5482

-

-

... More
WALL PARTITION WORKS Providing, Fabricating and fixing full height cement board partitions for main partitions at locations as indicated, to proper line, level and plumb of overall thickness of 100 mm consisting of the following: Rate to include Cost of paneling to include making of necessary cutouts for Electrical / other conduiting and outlets.Alternate members of the framework to be anchored to the true slab. And also any modification required in frame work for laying of items like AC duct etc. and inclusive of making grooves as per design. Framework : Partition framework to be formed out of 50 X 50 mm extruded Aluminum sections for framework placed vertically and horizontally at required centre to centre fixed to the wall @ 600mm c/c both ways and crossbraced with floor and ceiling channels supported by hinges, using galvanized metal screws and wooden / PVC rawl plugs. Providing and fixing 12 mm thick Cement bonded particle board panel of approved make conforming to BIS specifications fixed with SS screws complete on both sides of the framing as instructed by Engineer-in-charge. The fastening arrangement should flush with the board and no chipping /warping should be visible. Cladding: Partition framework to be cladded with 12.5 mm thick tapered edge cement board on both sides of the partition in line and level fixed with drywall screws @ 300 mm c/c with staggered joints to avoid through joints and finished with proprietary supplied jointing tape and compound as per manufacture'rs specifications.

276

-

-

... More
Providing and fixing framework for Full Height Gypsum Partitions of 150 mm thick to be fabricated for main partitions at locations as indicated, to proper line, level and plumb, fabricated out of 50 mm x 50 mm Extruded Aluminium sections fixed to the wall @ 600mm c/c both ways with horizontal noggings at floor and soffit, on both side skinning with fire rated 12.5 mm Tapered edge gyp board (IS-2095/1982), in line and level screw fixed to either side of GI section with 25 mm long dry wall screws 300 mm c/c with joints staggered to avoid through joints finished so to have flush look with jointing compound paper tape and two coats of primer suitable for Gyp board as per recommended practices complete and firerated Glass wool insulation of 50 mm thk inside the partition filled with insulation as per drawings. All electrical / network switch boxes, niches to be boxed / packed with adequate reinforcement using plywood and also 12 mm GI channel to be provided at intersection of two materials. Rate to include Cost of paneling to include making of necessary cutouts for Electrical / other conduiting and outlets.Alternate members of the framework to be anchored to the true slab. And also any modification required in frame work for laying of items like AC duct etc. and inclusive of making grooves as per design. Rate to include Backing Material of : Fibre Glass wool of 48Kg/m3 density, 50 mm thickness, with a NRC of 0.85 minimum (LFA-031 & HFA-0.7) with a covering of Black R P Tissue, well compacted, raped in non woven tissues and tied in positionby 24 gauge x 12mm GI wire netting tied to the frame etc. complete as per acoustic consultant specifications.

76

-

-

... More
Providing and supplying ‘Optra Acoustical Wall Paneling’ with square edges made of fibre glass substrate 25mm thick and wrapped on the front side with an acoustically transparent and classified for Fire reaction Class A, as per ASTM E-84, fabric with an option of colors – Husk, Copper, Sangria, Sesame, Coffee, Charcoal, Titanium, Flame, Peanut and Shell as per the choice of the Architect of size 600x600mm, 600x1200mm & 600x1800mm providing a minimum sound absorption level of 0.85 NRC to be affixed to wall using Wall panel Impalers supplied by Solutions and construction adhesives as per the instructions laid down by the manufacturer as per the approved make. INSTALLATION: In order to fix the panels to the wall, the Impalers shall be fixed to the wall surface using self tapping screws. 3 nos. in case of 600x600mm, 4 nos in case of 600x1200mm and 5 nos in case of 600x1800mm wall panel Impalers to be used for the installation purpose. Silica based construction adhesive to be dabbed on to the projecting elements (spikes) of the impalers. Optra wall panels shall be pierced through the spikes of the impalers ensuring the line and level of the panels are maintained. Installation to be carried out by Trained Installation team & Installation should be carried out as per recommended procedure.

937

-

-

... More
Providing and fixing framework for Full Height fire rated Single Gypsum Partitions of 150 mm thick to be fabricated for main partitions at locations as indicated, to proper line, level and plumb, fabricated out of 50 mm x 50 mm Extruded Aluminium sections fixed to the wall @ 600mm c/c both ways with horizontal noggings at floor and soffit, on both side skinning with fire rated 12.5 mm Tapered edge gyp board (IS-2095/1982), in line and level screw fixed to either side of GI section with 25 mm long dry wall screws 300 mm c/c with joints staggered to avoid through joints finished so to have flush look with jointing compound paper tape and two coats of primer suitable for Gyp board as per recommended practices complete and Glass wool insulation of 50 mm thk inside the partition filled with insulation as per drawings. All electrical / network switch boxes, niches to be boxed / packed with adequate reinforcement using plywood and also 12 mm GI channel to be provided at intersection of two materials. Rate to include Cost of paneling to include making of necessary cutouts for Electrical / other conduiting and outlets.Alternate members of the framework to be anchored to the true slab. And also any modification required in frame work for laying of items like AC duct etc. and inclusive of making grooves as per design. Rate to include Backing Material of : Fibre Glass wool of 48Kg/m3 density, 50 mm thickness, with a NRC of 0.85 minimum (LFA-031 & HFA-0.7) with a covering of Black R P Tissue, well compacted, raped in non woven tissues and tied in positionby 24 gauge x 12mm GI wire netting tied to the frame etc. complete..

5

-

-

... More
WOOD WORKS Wooden laminate Doors: Providing and fixing 50 mm thick single / double leaf flush solid core flush door shutters, confirming to IS . 1659 - 1960 and 2202 part I - 1962 as modified unto date for non-decorative type, core of block board construction to aluminium frame with 1 mm thick laminate of approved make on both side of shutters as per drawings / specifications and to be part of the internal partition system of approved make/vendor. Rate to include providing shop drawings as per archiitects approval. Rate to include lipping, hardware door fitting of handle & lock complete in all respects including anti-termite treatment. Handles:- SS Handle, cylindrical lock , Hinges :- 3 Nos SS Hinges –Heavy gauge each shutter, Tower Bolts:- 2 Nos stainless steel, consealed Door closer each shutter and Stopper:- One each shutter. Hardware to be of approved make. Rate to include cost of all materials, HOM of machineries and equipments, with all leads and lifts, loading and unloading charges , transportation cost and conveyance of all materials, labour for fixing the fixtures etc., complete for successful completion of work as per specifications at all floor levels and as directed by the Engineer-in-Charge.

480

-

-

... More
TOILET DOORS: Providing and fixing 50 mm thick single / double leaf flush solid core door shutters, confirming to IS . 1659 - 1960 and 2202 part I - 1962 as modified unto date for non-decorative type, core of block board construction to frame of 1st class teak wood and well matched commercial 4 mm veneering with vertical grains approved make and shade on one side and 1 mm laminate of approved make on the other side of shutters as per drawings / specifications. Rate to include melamine polishing, fixing of 600X200mm air vents, teak wood lipping, hardware door fitting of handle & lock complete in all respects including anti-termite treatment. Handles:- SS Handle, cylindrical lock , Hinges :- 3 Nos SS Hinges –Heavy gauge each shutter, Tower Bolts:- 2 Nos stainless steel, consealed Door closer each shutter and Stopper:- One each shutter. Hardware to be of approved make. Rate to include cost of all materials, HOM of machineries and equipments, with all leads and lifts, loading and unloading charges , transportation cost and conveyance of all materials, labour for fixing the fixtures etc., complete for successful completion of work as per specifications at all floor levels and as directed by the Engineer-in-Charge.

2

-

-

... More
TOILET DOORS: Providing and fixing 40 mm thick single leaf flush solid core door shutters, confirming to IS . 1659 - 1960 and 2202 part I - 1962 as modified unto date for non-decorative type, core of block board construction to frame of 1st class Sal wood and well matched commercial 4 mm veneering with vertical grains approved make and shade on one side and 1 mm laminate of approved make on the other side of shutters as per drawings / specifications. Rate to include melamine polishing, fixing of 600X200mm air vents, teak wood lipping, hardware door fitting of handle & lock complete in all respects including anti-termite treatment. Handles:- SS Handle, cylindrical lock , Hinges :- 3 Nos SS Hinges –Heavy gauge each shutter, Tower Bolts:- 2 Nos stainless steel, consealed Door closer each shutter and Stopper:- One each shutter. Hardware to be of approved make. Rate to include cost of all materials, HOM of machineries and equipments, with all leads and lifts, loading and unloading charges , transportation cost and conveyance of all materials, labour for fixing the fixtures etc., complete for successful completion of work as per specifications at all floor levels and as directed by the Engineer-in-Charge.

147

-

-

... More
TOILET DOORS: Providing and fixing 50 mm thick single / double leaf flush solid core door shutters, confirming to IS . 1659 - 1960 and 2202 part I - 1962 as modified unto date for non-decorative type, core of block board construction to frame of 1st class Sal wood and well matched commercial 4 mm veneering with vertical grains on both side of shutters as per drawings / specifications. Rate to include melamine polishing, teak wood lipping, hardware door fitting of handle & lock complete in all respects including anti-termite treatment. Handles:- SS Handle, cylindrical lock , Hinges :- 3 Nos SS Hinges –Heavy gauge each shutter, Tower Bolts:- 2 Nos stainless steel, consealed Door closer each shutter and Stopper:- One each shutter. Hardware to be of approved make. Rate to include cost of all materials, HOM of machineries and equipments, with all leads and lifts, loading and unloading charges , transportation cost and conveyance of all materials, labour for fixing the fixtures etc., complete for successful completion of work as per specifications at all floor levels and as directed by the Engineer-in-Charge.

5

-

-

... More
UTILITY & SERVICE ROOM DOORS: Providing and fixing 50 mm thick single / double leaf flush solid core door shutters, confirming to IS . 1659 - 1960 and 2202 part I - 1962 as modified unto date for non-decorative type, core of block board construction to frame of 1st class teak wood and well matched commercial 4 mm veneering with vertical grains of approved make on one side and 1 mm laminate of approved make on the other side of shutters as per drawings / specifications. Rate to include melamine polishing, 6 mm thick toughened vision glass, teak wood lipping, hardware door fitting of handle & lock complete in all respects including anti-termite treatment. Handles:- SS Handle, Lock :- cylindrical lock , Hinges :- 3 Nos SS Hinges –Heavy gauge each shutter, Tower Bolts:- 2 Nos stainless steel Door closer each shutter and Stopper:- One each shutter. Hardware to be of approved make. Rate to include cost of all materials, HOM of machineries and equipments, with all leads and lifts, loading and unloading charges , transportation cost and conveyance of all materials, labour for fixing the fixtures etc., complete for successful completion of work as per specifications at all floor levels and as directed by the Engineer-in-Charge.

58

-

-

... More
FIRE DOORS: Providing 50mm thick 2 hr wooden fire Cum Acoustic door rated for 40db sound insulation(ARAI certfied) .The doors are duly tested for Integrity & Insulation Criteria as per the IS: 3614 Part 2 and BS: 476 part 22 specified in IS: 3809-1979 and BS: 476 part 20 & 22 1987 to achieve the required integrity and insulation (i.e. to restrict the heat radiation, temperature rise on the non fire side to the maximum of 140° C above the ambient temperature on the exposed surface of the shutter).Door Frame: Formed out of 120 mm x 60 mm hard wood ( with density of 650 kg /metre cube ) section with Promaseal® Intumescent strip (Imported) to take care of Hot and cold smoke of size 10mm X 4mm concealed in the groove of the frame for fire and smoke sealing mounted in the grooves of the frame. Intumescent Strip: For the Door Frame 2 runs and for the Shutter 1 run of Size of 10mm X 4mm . Shutter: Providing of 50 mm thick smoke check shutter of 120min fire rating tested to BS 476 part 20 & 22, IS3614 part -II & ISO 834 comprising of 2x9mm Promina ® boards, treated hard wood internal timber frame work of 100x30mm with infill 96kg/cum, total 30mm thick ceramic fiber reinforced FR silicate coating on both sides and faced with 3mm thick water proof commercial ply / teak ply with 1 run of fire and hot smoke seal strips of size 20 mm x 4mm mounted in the grooves in the shutter on all edges except bottom and externally lipped with teakwood / hardwood beading. Promaseal ® Intumescent sealant is used to seal the gaps between Promina Board and shutter beading. Proprietary acoustic drop down seals and EPDM Gasket around the frame are used to enchance acoustic property. Finish - Both Side veneer Finish with melamine polish and 2Hr Fire Rated Vision Panel:200mm x 300mm. Door to be completed with all dorma hardware- bottom seals, acoustic seals, dead lock, concealed door closer, pull handle and hinges.

41

-

-

... More
SHAFT DOORS: Providing and fixing 50 mm thick single leaf solid flush door shutters, confirming to IS . 1659 - 1960 and 2202 part I - 1962 as modified unto date for non-decorative type, core of block finished with duco paint or putty and paint on both sides and Edges of the door to have metal trim on all sides as per drawings / specifications. Rate to include Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge. Each shutter shall be fixed firmly with necessary pivot hinges at the top and a floor spring of approved make at the bottom . Shutter to be fixed with allen key locking mechanism Rate to include cost of all materials, HOM of machineries and equipments, with all leads and lifts, loading and unloading charges , transportation cost and conveyance of all materials, labour for fixing the fixtures etc., complete for successful completion of work as per specifications at all floor levels and as directed by the Engineer-in-Charge.

99

-

-

... More
WATER PROOFING WORKS KSRB 10-3 : Providing and laying integral cement based waterproofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc., consisting of following application. (a) Applying and grouting a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with proprietary water proofing compound conforming to IS:2645 over the RCC slab after cleaning the surface before treatment. (b) Laying cement concrete using broken brick bats 25mm to 100mm size with 50% of cement mortar 1:5 admixed with proprietary water proofing compound conforming IS:2645 over 20mm thick layer of cement mortar 1:5 admixed with proprietary water proofing compound to required slope and treating similarly the adjoining walls upto 300mm height including rounding off junctions of walls and slabs. (c) After two days of proper curing, applying a second coat of cement slurry admixed with proprietary water proofing compound (d) Finishing the surface with 20mm thick jointless cement mortar of mix 1:4 admixed with proprietary water proofing compound and finally finishing the surface with trowel and neat cement slurry and making of 300x300mm square. (e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test including cost of materials, labour complete as per specifications.

2534

-

-

... More
Water proofing of RCC terrace/ Podium slab/ toilet/ utilities/ water retaining structure by preparing the surface by chipping and cleaning and grouting of honey comb, voids cracks/ construction joints with cement slurry (1kg cement added in 10ltr of water) added with 100gm of inorganic accelerator followed by spraying of liquid biological modified alkaline earth silicate @ 0.4ltr per sqm on whole surface to reduce the micro porosity and allowing it to dry curing the surface for silicates to penetrate deeper into the concrete and spraying waterproofing impregnate liquid containing silane and silanol linear copolymer @ 0.5 ltr per Sqm and finally applying polymer slurry made out of cross linked acrylic/ styrene/ butadiene & cement in the ratio of 1:0.1 @ 50Kg/Sqm on the whole surface, including all labour charges tools and equipments all complete as per specifications.

2418

-

-

... More
Extra for water proofing the inside surface of tanks (OHT & UGT) applying of modified polymers soft acrylic esters coat @0.40 kg/sqm in 2 coats including all labour charges tools and equipments, all complete as per the specification.

1064

-

-

... More
Providing and fixing food grade epoxy painting to over head tank and sump tank after cleaning and drying including pumping and bailing out of water, including cost of all materials, labour lead lift etc., complete.

88

-

-

... More
Supplying and applying two coats of two component acrylic elastomeric cementetious waterproof coating POLYPLUS AC, applied @ 750 Gms/M2/Coat, over a coat of single component, in depth crystallisation waterproof coating, POLYPLUS CP, applied @ 500 Gms/M2/COAT, including ponding test, pressure grouting the leaking points, curving the corners with polymer plastering, and coating the brick/ block work area with two coats of POLYPLUS AC. Complete with approved makes. For STP and other works.

840

-

-

... More
Water Proofing Protection with plastering of 15mm thick using cement mortar 1:4 as directed by engineer.

3204.72

-

-

... More
Water Proofing Protection screed of 50mm thick as directed by engineer

574.28

-

-

... More
Providing and fixing of expansion joint system related with floor location as per drawings and direction of Engineer-In-Charge. The joints system will be of extruded aluminum base members, self aligning / self centering arrangement and support plates etc. as per ASTM B221-02. The system shall be such that it provides floor to floor /floor to wall expansion control system for various vertical location in load application areas that accommodates multi directional seismic movement without stress to it's components. System shall consist of metal profiles with a universal aluminum base member designed to accommodate various project conditions and finish floor treatments. The cover plate shall be designed of width and thickness required to satisfy projects movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered selfcentering arrangement that freely rotates / moves in all directions. The Self – centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer -in-Charge. (Material shall confirm to ASTM 6063).

194.8

-

-

... More
MS WORKS INTERNAL RAILING: Providing, fabricating and fixing 1020 mm high MS railing with TEAK WOOD Class-II HANDRAIL of size 75 x 40mm as per design and detailings as shown in the drawings is fixed on to a 40mmX12mm MS flat, assembled including making grooves for fixing and including SS screws for BALCONY, CORRIDOR, STAIR CASE RAILINGS, LADDERS,etc as per architectural drawing and instructions. The system shall be consist with MS flats 100 mm and 8 mm thick base plate fixed in RCC member with anchor bolt ( 3/8 size) c/c as per site condition and given the drawing. All the joints and sections should be cut to length,welded and grinded wherever necessary etc., complete as per specifications & drawing. The vertical and horizontal members 40mmX6mm MS flats at an approximate of 100mm C/C shall be welded properly, including necessary hardware, anchor bolt, cutting, grinding, machining, assembly, welding, jointing, drilling, grouting and cleaning etc. completed as per the instructions of EIC/ Architect. Rate also included providing and applying one coat epoxy primer and finish the railing with two coates of approved quality enamel paint complete on MS and oil based primer and polish on the wooden hand rail. The work shall include the cost of all materials, cost of labour, including applying apriming coat of red lead paint, HOM equipment and machinery,all lead and lift, loading and unloading charges, transportation cost and conveyance of all materials, and all other incidental charges at all floor levels etc., complete for successful completionof work. The work shall be carried out as per the directions of the Engineer in charge.

798

-

-

... More
EXTERNAL & TERRACE RAILING: Providing, fabricating and fixing 1020 mm high MS hand rail, assembled including making grooves for fixing and including SS screws for BALCONY, CORRIDOR, STAIR CASE RAILINGS, LADDERS,etc as per architectural drawing and instructions. The system shall be consist with MS flats 100 mm and 8 mm thick base plate fixed in RCC member with anchor bolt ( 3/8 size) c/c as per site condition and given the drawing. All the joints and sections should be cut to length,welded and grinded wherever necessary etc., complete as per specifications & drawing. The vertical and horizontal members 40mmX6mm MS flats at an approximate of 100mm C/C shall be welded properly, including necessary hardware, anchor bolt, cutting, grinding, machining, assembly, welding, jointing, drilling, grouting and cleaning etc. completed as per the instructions of EIC/ Architect. Rate also included providing and applying one coat epoxy primer and finish the railing with two coates of approved quality enamel paint complete. The work shall include the cost of all materials, cost of labour, including applying apriming coat of red lead paint, HOM equipment and machinery,all lead and lift, loading and unloading charges, transportation cost and conveyance of all materials, and all other incidental charges at all floor levels etc., complete for successful completionof work. The work shall be carried out as per the directions of the Engineer in charge.

468

-

-

... More
MS LADDER: Providing, fabricating and fixing MS Ladders (for lift & OHT) using MS Pipes/Flats/Rod/Angles etc of size/section as per detailed drawings, including painting with 2 coats of Synthetic Enamel Paint of approved colour and make over a coat of anti corrosive Zinc Chromate primer, etc., complete all as per the drawings/instructions of architects.

600

-

-

... More
CHAINLINK FENCING: Providing, fabricating and fixing Chainlink Fencing (for compound) using 50x50x6mm MS Angles for frame, panels filled with 11 gauge 50x50mm GI Chainlink Mesh as per detailed drawings, including fixing of MS frame in PCC M20, Painting of MS Angles with 2 coats of Aluminum Paint of approved make over a coat of anti corrosive Zinc Chromate primer, etc., complete all as per the drawings/instructions of architects.

288

-

-

... More
MS Gate : Providing, fabricating and fixing MS Gate using MS Pipes/Flats/Rod etc of size/section as per details–jointed mittered and electrically flash welded with Iron lugs, Mullions, projecting hinges for Side hung shutters, including locking arrangements, Painting with 2 coats of Synthetic Enamel Paint of approved colour and make over a coat of anti corrosive Zinc Chromate primer, putty work etc., complete all as per the drawings/instructions of architects. (Average Weight of steel 30 KGS/SQM)

2

-

-

... More
MS Sliding Gate : Providing, fabricating and fixing MS Gate using MS Pipes/Flats/Rod etc of size/section as per details–jointed mittered and electrically flash welded with Iron lugs, Mullions, with roller and sliding arrangements, including lock system, Painting with 2 coats of Synthetic Enamel Paint of approved colour and make over a coat of anti corrosive Zinc Chromate primer, putty work etc., complete all as per the drawings/instructions of architects. (Average Weight of steel 30 KGS/SQM)

2

-

-

... More
MISCELLANEOUS WORKS Providing & Fixing T Line Toilet Cubicle System as per approved shop drawing in SS-316 Heavy Series , Comprising of rigid SS components (1) Indicator Lock (2) Automatic Reverse Hinges (3) Height Adjustable Legs (4) Door Knob (5) Coat Hook & Aluminum (Brush Finish) (6) Top Rail (7) h Section (8) U Section (9) Silicon Strip to be inserted in h Section to provide Noise Dampening (10) Screws & Plugs with Water, Chemical, Heat, Bacteria, Fire, Impact & Scratch Resistant 12 mm T Line Compact Laminate. The Top Rail will be fixed end to end and all the mid and end pilasters will get fixed into it. The whole system will have Upto 150 mm clearance height to the floor.U Sections will be used for Board to Board Jointing and Board to Wall Fixing. Toilet Cubicle System ( L Shape ) with Standard Dimension of 1950 mm Height x 900 mm Width x 1500 mm Depth, Which Includes a 600 mm Width x 1800 mm Height Door. Front Panel ( I Shape ) with Standard Dimension of 1950 mm Height x 900 mm Width, Which Includes a 600 mm Width x 1800 mm Height Door.

68

-

-

... More
Providing & fixing Floor transition trims between the hardflooring and the carpets/vinyl flooring of Aluminium with approved profile . The preparation and fixing method to be as recommended by the Manufacturer.

37

-

-

... More
Supply and installation of high quality 6 mm polished float glass mirror of approved make, at all levels / places as directed framed in a one-piece, bright polished, wooden frame with 90° mitered corners. All edges of the mirror are protected by absorbing filler strips. Mirror has a galvanized steel back with integral horizontal hanging brackets and wall hanger for concealed mounting. Rate to include 12 mm backing with waterproof ply of approved brand and fixing with 3M double side tape.

102

-

-

... More
Providing & fixing 8 mm thick coloured Lacqured glass mounted over existing 12 mm thick commercial ply backing projected 150 mm from wall/partition face with fixed onto existing wall / partition with an anodized aluminum L angle frame in indicated locations and sizes Manet fittings of approved make complete as per the detail drawing and instruction of the Architect

18

-

-

... More
Urinal partition: Supply & installation of 8 mm thick frosted glass urinal partition of size 900X450mm including all consumable, tools, tackles, labour fixing accessories with SS clamp etc all complete as directed by the EIC.

28

-

-

... More
Urinal partition: Supply & installation of 20 mm thick jet black granite stone urinal partition of size 900X450mm including all consumable, tools, tackles, labour fixing accessories etc all complete as directed by the EIC.

2

-

-

... More
Providing and laying machine cut, ,leather finished jet black ganite in pattern as indicated in drawing in counter and facia and bullnose for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size,approved shade, colour and texture (SAMPLE TO BE APPROVED BY ARCHITECT / CLIENT) with minimum thickness of the stone slab being 18 mm to 20 mm over a bed of Cement Mortar 1:4 and average thickness 25 mm in shape and pattern and at all levels and all positions to proper line, level and slope as per drawings / directions by Engineer In-Charge over existing concrete bed or top of roof laid to line and level and Joints in the flooring to be filled with approved grout of approved shade as per manufacturers specifications. Quoted rate to include the cost of bullnosing, rounding off edges, edge-polishing etc, wastages, lead and lift, chipping (if required) to lay and catering away the debris from site curing, protection with 3 mm Celloboard joined with Masking Tape, one coat of stone guard till hand-over & cleaning. Rate to include cost of all materials, labour, curing, filling of joints, machine polishing, curing, acid cleaning after completion and also POP protective coat to prevent scratches, HOM of equipments and machineries, all leads and lifts, loading and unloading charges, transportation cost and conveyance of all material and all other incidental charges etc., complete for successful completion of work and as directed by the Engineer-in-charge. (Allow necessary cut-outs for pipes, waste couplings etc.)

89

-

-

... More
Tensile Canopy: Supply and installation of Tensile Fabric of architectural membrane PVC Polystel High Tensile Fabric, UV protected and also withstanding high temperature along with all accessories like tie down edge cables and stabilizing onto the MS frames on the façade with clamping system, fasteners and gaskets designed to withstand wind velocity and pressure of Serge Ferrari make of approved colour and code with approved perforation and protected against microbial and fungal attack all inclusive and complete as per instruction.

220

-

-

... More
GRANITE AGGREGATE: Providing, and Spreading 40mm Granite Aggretates (for Transformer & DG yard) including preparing and compacting of subgrade etc complete all as per the drawings/instructions of architects.

60

-

-

... More
BARRICADING: Providing and fixing barricading site using 22 gauge precoated metal sheet including support system embedded in concrete as per details given by structural engineer and removal of the same when no longer required

2308.5

-

-

... More
Supplying and Fixing Expandable Anchor Bolts in concrete or masonry including drilling, cleaning the holes, ramming the bolts in the holes in accordance with manufacturer’s procedures, recommendations and specifications for fixing plates or other steel members to already cast concrete surfaces. 12 mm core diameter

10

-

-

... More
16 mm core diameter

10

-

-

... More
20 mm core diameter

10

-

-

... More
25 mm core diameter

10

-

-

... More
MANHOLE COVER: Providing and fixing 600x600mm Heavy Duty Precast Cement Cover with frame for STP tank, fixed with CM 1:4 etc complete all as per instructions of architects.

15

-

-

... More
PVC rungs for Sumps (260X165X25mm)

250

-

-

... More
Provide and Laying 250micron HDPE sheet below grade slab as instructed by engineer/architect with overlap of 100mm in joints cost including material, labour and HOM complete as per specifications

10

-

-

... More
Supply and fixing of timber slats of Spacing @ 50mm c/c distance and size (50 X 25mm). with metal frame, including polish as per the drawings, specifications and approval from architect,

10

-

-

... More
Supply and installation of copper handle as per the drawings, for main doors including hardware HOM complete as instructed by architect.

20

-

-

... More
ELECTRICAL WORKS HT ELECTRICAL WORKS COMPACT DAS RING MAIN UNIT OUT DOOR TYPE (3 MODULE) Installation, testing and commissioning of 11KV Outdoor cubicle type DOS compatible Compact DAS Ring main unit as per BESCOM requirement comprising of 2 Nos. (2 incomer) 11KV 630A, 26.3kA, 3P VCB, & 1No outgoing 11KV 630A, 26.3kA, 3P draw out type VCB with earth switch with all accessories and all metering and protection for satisfactory operation to meet local EB supply authority and CEIG complacence etc., as required. Bus bar should be copper with current density of 1.3A/sqmm. AC to DC Power-pack should be provided with 230V AC input & out put DC voltage should be as per the Breaker control voltage with SMF battery of required Ah. The cubicle shall be made out of 14G MS sheet & shall confirm to IP65 (OUT DOOR) classification. The unit shall be mounted on pedestal with necessary supports. Refer Main single line diagram

1

-

-

... More
HT BREAKER PANEL OUT DOOR TYPE Installation, testing and commissioning of 11KV Outdoor cubicle type HT Panel as per BESCOM requirement comprising of 1 Nos. 11KV 630A, 26.3kA, 3P VCB 3P draw out type VCB with earth switch with all accessories and protection for satisfactory operation to meet local EB supply authority and CEIG complacence etc., as required. Bus bar should be copper with current density of 1.3A/sqmm. AC to DC Power-pack should be provided with 230V AC input & out put DC voltage should be as per the Breaker control voltage with SMF battery of required Ah. The cubicle shall be made out of 14G MS sheet & shall confirm to IP65 (OUT DOOR) classification. The unit shall be mounted on pedestal with necessary supports. Refer Main single line diagram

2

-

-

... More
HT METERING CUBICLE OUT DOOR TYPE Supply, Installation, testing and commissioning of OUT DOOR 11kV Metering cubicle. IP 65 made out of 2.5mm cold rolled, mild steel, metal clad and shall be suitable for operation on 11kV, 3 Phase, 50 Hz, AC earthed system. The panel shall contain the equipment's and components as per the SLD & BESCOM requirement & Specification Complete with bus bar interconnections, control wiring, designation label's, caution notices, EB sealing & pad locking facilities wherever required. Necessary space shall be provided for entry/exit of HT cable from the bottom through detachable gland plates. Bus bar should be copper with current density of 1.3A/sqmm. The panel shall be finished with one coat of air drying red oxide and 2 coats of epoxy paint certifying to shade RAL 631. View panel should be provided for easy meter reading notification. The unit shall be mounted on pedestal with necessary supports. Refer Main single line diagram.

1

-

-

... More
HT BREAKER PANEL WITH METERING CUBICAL OUT DOOR TYPE Installation, testing and commissioning of 11KV Outdoor cubicle type HT Panel as per BESCOM requirement comprising of 1 Nos. 11KV 630A, 3P LBS 3P .with earth switch with all accessories and protection for satisfactory operation to meet local EB supply authority and CEIG complacence etc., as required. Bus bar should be copper with current density of 1.3A/sqmm. The panel shall contain the equipment's and components as per the SLD & BESCOM requirement & Specification Complete with bus bar interconnections, control wiring, designation label's, caution notices, EB sealing & pad locking facilities wherever required. AC to DC Power-pack should be provided with 230V AC input & out put DC voltage should be as per the Breaker control voltage with SMF battery of required Ah. The cubicle shall be made out of 14G MS sheet & shall confirm to IP65 (OUT DOOR) classification. The unit shall be mounted on pedestal with necessary supports. Refer Main single line diagram 3C-400 sq.mm 11KV, Round wire armoured, earthed cable. (Assumed 250Mtr from Sources from BESCOM Will be operated with liasioning contractor based on BESCOM feasibility)

250

-

-

... More
3C-400 sq.mm 11KV, Round armoured, earthed cable. ( If BESCOM insist to use Round armoured Same to be used)

10

-

-

... More
3C-240 sq.mm 11KV, flat armoured, earthed cable.

180

-

-

... More
3C-240 sq.mm 11KV, Round armoured, earthed cable. ( If BESCOM insist to use Round armoured Same to be used)

10

-

-

... More
Supply, Installation, testing & commissioning of indoor cable end termination with Raychem heat shrinkable jointing kit complete with all accessories as recommended by cable manufacturer including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as require. All cable gland should be earthed using copper strips. 3C-400 sq.mm 11KV, Round wire armoured, earthed cable.

4

-

-

... More
3C-400 sq.mm 11KV, flat armoured, earthed cable.

4

-

-

... More
3C-240 sq.mm 11KV, Round armoured, earthed cable.

6

-

-

... More
3C-240 sq.mm 11KV, flat armoured, earthed cable.

2

-

-

... More
Supply, Installation, testing & commissioning of Outdoor cable end termination with Raychem heat shrinkable jointing kit complete with all accessories as recommended by cable manufacturer including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required. All cable gland should be earthed using copper strips. 3C-400 sq.mm 11KV, flat wire armoured, earthed cable.

1

-

-

... More
3C-240 sq.mm 11KV, flat wire armoured, earthed cable.

1

-

-

... More
TRANSFORMER - ONAN ON LOAD TAP CHANGER Supplying, erection, testing and commissioning of 1000kVA capacity Copper wound Distribution transformer 11kV/433V On load Tap Switch, Buchholtz relay, winding temperature indicator, marshalling box with wiring, oil level indicator with +5% to -10% steps of 2.5 %, HT and LT bushing with all standard accessories as per latest IS standard technical specification. The losses shall be as per IS 1180 for Level - 3 rating Provide Name Plate Details of Transformer in 2x3ft acrylic sheet in self reflective letters. No. of Phase - Three Frequency - 50 Hz Rating - 11KV/ 433V Vector group - Dyn 11 Tap Changer - OLTC of +5% to -10% taps (Percentage at 2.5 % ) RTCC - Required Duty - Continuous, Copper wound Cable entry - Cable boxes on HV side & LV side adopter box with Bus duct flange suitable for air insulated bus duct. Cooling - ONAN. Losses - As per IS 1180 for Level - 3 rating Impedance - As per IS 1180. Transformer shall be finished in Battle Ship Grey colour, Powder coated Finish as per IS/ IEC standards

1

-

-

... More
Supply, Installation, testing & commissioning of XLPE insulated, extruded PVC inner sheathed outer sheathed armoured and PVC Sheathed overall 1.1 KV grade confirming to IS 1554 (I)/1988 19 Core 2.5 Sqmm copper armoured control cable for inter locking HT Panel, Transformer OLTC to RTCC panel for 11 KV Transformer Etc.,

120

-

-

... More
10Core 2.5 Sqmm copper armoured control cable (OLTC to RTCC FOR OLTC CONTROL & HT BREAKERS CONTROL CABLING)

120

-

-

... More
14Core 2.5 Sqmm copper armoured control cable (OLTC TO RTCC FOR TAP POSITION SENSING)

120

-

-

... More
4Core 4 Sqmm copper armoured control cable

120

-

-

... More
3Core 4 Sqmm copper armoured control cable

80

-

-

... More
3Core 2.5 Sqmm copper armoured control cable

80

-

-

... More
Supply, Installation, testing & commissioning of End termination of cables using single compression brass gland & copper lugs 2 19Core 2.5 Sqmm copper armoured control cable with proper crimping.

4

-

-

... More
10Core 2.5 Sqmm copper armoured control cable with proper crimping.

4

-

-

... More
14Core 2.5 Sqmm copper armoured control cable with proper crimping.

2

-

-

... More
4Core 4 Sqmm copper armoured control cable with proper crimping.

4

-

-

... More
3Core 4 Sqmm copper armoured control cable with proper crimping.

4

-

-

... More
3Core 2.5 Sqmm copper armoured control cable with proper crimping.

4

-

-

... More
EARTHING WORKS Supply and installation of Earthing with G.I. earth pipe 3.0 metre long, 40 mm dia including accessories, and providing masonary enclosure with cover plate having locking arrangement and watering pipe etc with charcoal/coke and salt as required. (for HT equipment and transformer body to suit CEIG norms)

10

-

-

... More
Supply and installation of Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonary enclosure with cover plate having locking arrangement and watering pipe 2.7 metre long etc. with charcoal/ coke and salt as required. (for transformer neutral)

2

-

-

... More
40 x 6mm Cu. Earth flat

40

-

-

... More
MISCELLANEOUS ITEMS Supply and erection of 12 SWG GI chain link fence 2.5M high with necessary MS angle, box section, gate , lock, foundation and necessary civil works as required. The panel shall be finished with one coat of air drying red oxide and 2 coats of epoxy paint Based on Architect/client/consultant recommendation.

56

-

-

... More
Supply and erection of 12 SWG GI Gate with lock for HT yard with frame of 2.5M high with necessary MS angle, box section. The paint shall be finished with one coat of air drying red oxide and 2 coats of epoxy paint Based on Architect/client/consultant recommendation

3

-

-

... More
Providing, Laying and fixing of following dia RCC Hume Pipe of NP2 class in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) & refilling etc. as required for HT cable laying at the road crossing or wherever necessary as per site condition. Cost to include RCC collar and necessary civil works as required. 100mm Dia RCC Hume pipe

900

-

-

... More
150mm Dia RCC Hume pipe

5

-

-

... More
200mm Dia RCC Hume pipe

300

-

-

... More
300mm Dia RCC Hume pipe

5

-

-

... More
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, 2 mm thick, and vitreous enamelled white on both sides, and with inscription in single red Colour on front side as required.

2

-

-

... More
Supply and installation of HT cable route markers / joints indicating slabs as per MSB requirement with necessary excavation and concerting as required to complete the installation.

10

-

-

... More
Supply & spreading of 45mm/1.5 inch deep new blue metal Jelly 150mm filling to the HT / Transformer yard.

100

-

-

... More
Supply & installation of PCC Inspection chamber of sizes as mentioned, for laying of humepipes. The rate shall also include cost for refilling the excavated portion and consolidating etc., with heavy duty precast covers etc., all complete as required. Top cover of the chamber has to be meet landscape requirements. Chambers which are located on driveway needs to be designed for fire vehicle movement. The mentioned dimensions are of Inner side of the chamber. 1200 (L)x1200(W)x1500mm(D)

2

-

-

... More
1200 (L)x1200(W)x1200mm(D)

15

-

-

... More
1000 (L)x1200(W)x1000mm(D)

2

-

-

... More
500 (L)x500(W)x600mm(D)

45

-

-

... More
500 (L)x500(W)x750mm(D)

5

-

-

... More
750 (L)x750(W)x1000mm(D)

5

-

-

... More
Supply & fixing of shock treatment chart duly framed with 5mm thick glass required both in Hindi, English & Kannada for treating person suffering due to electric shock outdoor duty fixed to Yard Fencing -inside & outside

2

-

-

... More
Closure of retaining wall cut-outs / Chamber cutouts using fire retardant material after completing the works

25

-

-

... More
Supply and fixing of First-aid box containing medicines for 10 persons to give first-aid treatment conforming to IS 2217 -1963.

2

-

-

... More
Supply and fixing of LAMINATED Single line diagram chart duly framed with 5mm thick glass outdoor duty fixed to Yard Fencing & HT room wall.

2

-

-

... More
Supply of Rubber hand gloves suitable for 11KV.

2

-

-

... More
Fire Bucket with stand & cover - 4 buckets. Bucket of round bottom, painted red, marked 'FIRE' and duly filled with fire river sand.

2

-

-

... More
Obtaining of Power sanction, lisoning and obtaining HT drawing approval, approval for the HT installations for commissioning from Chief Electrical Inspectorate Govt. And also obtaining drawing approval, approval for the LT installations after commissioning from Chief Electrical Inspectorate Govt. of Karnataka including all necessary coordination for Phase-1

1

-

-

... More
Obtaining of Power sanction, lisoning from Chief Electrical Inspectorate Govt. And also obtaining drawing approval, approval for the LT installations after commissioning from Chief Electrical Inspectorate Govt. of Karnataka including all necessary coordination for Phase-2

1

-

-

... More
LT KIOSK-1 IP - 55 OUTDOOR PANEL

1

-

-

... More
MAIN LT PANEL (Panel shall have provision of knockout, plug for fire trace tube in each compartment with cylinder(Novec) housing assembly (Panel Fire protection as per NBC-2016 Part 4 Fire and Life Clause 3.4.6.3 )).

1

-

-

... More
EMERGENCY PANEL

1

-

-

... More
300 kVAR APFC PANEL

1

-

-

... More
MAIN LIFT PANEL

1

-

-

... More
UTILITY PANEL

1

-

-

... More
GROUND FLOOR RAW POWER PANEL

1

-

-

... More
1ST FLOOR RAW POWER PANEL

1

-

-

... More
2ND FLOOR RAW POWER PANEL

1

-

-

... More
3RD FLOOR RAW POWER PANEL

1

-

-

... More
UPS INPUT PANEL

1

-

-

... More
UPS OUTPUT PANEL

1

-

-

... More
GROUND FLOOR UPS PANEL

1

-

-

... More
GF WING-A UPS PANEL-1

1

-

-

... More
FIRST FLOOR UPS PANEL

1

-

-

... More
1F WING-A UPS PANEL-1

1

-

-

... More
SECOND FLOOR UPS PANEL

1

-

-

... More
2F WING-A UPS PANEL-1

1

-

-

... More
THIRD FLOOR UPS PANEL

1

-

-

... More
3F WING-A UPS PANEL-1

1

-

-

... More
SERVER UPS PANEL -SA & SERVER UPS PANEL -SB

2

-

-

... More
EMGERGENCY LIGHTING PANEL

1

-

-

... More
HVAC CHILLER PANEL IP - 55 OUTDOOR PANEL

1

-

-

... More
HVAC PUMP CONTROL PANEL IP - 55 OUTDOOR PANEL

1

-

-

... More
TERRACE WING-A HVAC IP - 55 OUTDOOR PANEL WITH 500MM PEDESTRIAL

1

-

-

... More
TERRACE WING-B HVAC IP - 55 OUTDOOR PANEL WITH 500MM PEDESTRIAL

1

-

-

... More
HVAC TERRACE FIRE MODE OUTDOOR PANEL IP - 55 WITH 500MM PEDESTRIAL

1

-

-

... More
PHE PUMP ROOM PANEL-1

1

-

-

... More
LANDSCAPE LIGHTING PANEL IP -55 OUTDOOR TYPE

1

-

-

... More
GF-CL-1 WET LPDB, 2F-CL-15 WET LAB LPDB (WALL MOUNTED PANEL)

2

-

-

... More
1F-SC-9 WET LPDB,2F-SC-19 WET LAB LPDB , 3F-SC-32 LPDB (WALL MOUNTED PANEL)

3

-

-

... More
3F - ELECTRICAL WORK SHOP UPS PANEL

1

-

-

... More
3F-BCW-LPDB ( BIOCHEMISTRY WORKSHOP -WALL MOUNTED PANEL)

1

-

-

... More
Air insulated Bus Duct Supply, transport, unloading, installation, testing and commissioning of L.T. Air Insulated Bus Duct for out door applicaation including vertical elbows, horizontal bends, terminal flange, fixing brackets / antivibration supports, MS Supports and with necessary expansion units as required. For all other details refer SLD and the Technical specification. 1600A, 3 Phase, 4 Wire, IP5X , 415V, Air Insulated type, Aluminium bus duct (Suitable for Out Door Type ) Straight run

10

-

-

... More
Terminal flange

2

-

-

... More
Fixing Arrangements

2

-

-

... More
Vertical elbow

2

-

-

... More
Horizontal elbow

2

-

-

... More
Cable Adopter Box

2

-

-

... More
SANDWICH BUS DUCT FOR RAISING MAIN CONNECTIVITY 1.1 kV Grade, 1600A, 3Ph, 4 Wire (4P) ALU sandwich In door type, 16kA/1sec, IP-54 bus duct with earth bus of size 2Rx40x10 Hot Dip Galvonised GI strip on both sides other complete accessories( Main LT Panel to Rising Main connectivity in the Shaft up to 5 Floor Roof Level )

16

-

-

... More
Cost for make Horizontal Bend

12

-

-

... More
Cost for to make Vertical Bend

6

-

-

... More
Set of TPN Copper Laminate Flexible connections at Termination Ends on Panels

2

-

-

... More
Bus Duct Flange End

2

-

-

... More
Mounting Brackets i) Floor Supports - Spring

8

-

-

... More
ii) Floor Supports - Fixed

8

-

-

... More
1.1 kV Grade, 800A, 3Ph, 4 Wire (4P) ALU sandwich In door type, 16kA/1sec, IP-54 bus duct with earth bus of size 2Rx40x10 Hot Dip Galvonised GI strip on both sides other complete accessories( Main LT Panel to Rising Main connectivity in the Shaft up to 5 Floor Roof Level )

154

-

-

... More
Cost for make Horizontal Bend

12

-

-

... More
Cost for to make Vertical Bend

6

-

-

... More
Set of TPN Copper Laminate Flexible connections at Termination Ends on Panels

2

-

-

... More
Bus Duct Flange End

2

-

-

... More
Wall Frame Assembly ( For Wall Crossing)

4

-

-

... More
Bus Duct end Cap Assembly

2

-

-

... More
Mounting Brackets i) Floor Supports - Spring

8

-

-

... More
ii) Floor Supports - Fixed

8

-

-

... More
With adopter box for cable termination as per cable schedule Tap-off boxes with 630A, 4P 16KA MCCB Mp Based O/L,S/C releases with RHOM , RYB indicating lamps with MCB control, with wiring complete.

2

-

-

... More
Tap-off boxes with 400A, 4P 16KA MCCB Mp Based O/L,S/C releases with RHOM , RYB indicating lamps with MCB control, with wiring complete.

6

-

-

... More
Supply and installation for MS supporting for Bus Duct & Raising Main works - the quoted rate shall include with 2 coat of primer and 2 coat of enamel paint.

656

-

-

... More
MCB DISTRIBUTION BOARDS & ENCLOSURES Design, fabrication, supply, installation, testing & commissioning of Per Phase Isolated Ready DBs, made out of CRCA sheet, duly powder coated suitable for wall mounting as required complete with necessary powder coated. DB'S shall be with MCB/RCBO as incomer and MCB's as outgoings, With Double Door Distribution Boards complete with combined bus bar. The cubicle shall be fitted with necessary components of recommended make and as mentioned below complete with copper bus bar(combed bus) & internal wiring. Enough space shall be provided for terminating incoming power cable & DB shall be properly sized to take out multiple circuits through conduits. The GA of DB with necessary components shall be got approved by consultants/Project Managers. LDB TYPE- 1 16 WAY ETPN DB Incomer - 40A, 4P, 10kA, "C" Curve, MCB - 1 No Sub Incomer - 32A, 2P, 100mA, RCCB "AC" Series - 3 Nos Outgoing - 10A, SP, 10kA, "C" Curve, MCB - 30 Nos

1

-

-

... More
ELDB TYPE-2 12 WAY SPN DB Incomer - 25A, 2P, 100mA, RCCB "AC" Series - 1 Nos Outgoing - 10A, SP, 10kA, "C" Curve, MCB - 6 Nos

4

-

-

... More
LPDB TYPE -1 6 WAY VTPN DB Incomer - 63A, 4P, 100mA, RCBO "AC" Series - 1 Nos Outgoing - 16A, SP, 10kA, "C" Curve, MCB - 9 Nos

4

-

-

... More
LPDB TYPE -2 8 WAY VTPN DB Incomer - 63A, 4P, 100mA, RCBO "AC" Series - 1 Nos Outgoing - 16A, 3P, 10kA, "C" Curve, MCB - 4 Nos Outgoing - 16A, SP, 10kA, "C" Curve, MCB - 12 Nos

34

-

-

... More
LPDB TYPE -3 8 WAY VTPN DB Incomer - 63A, 4P, 100mA, RCBO "AC" Series - 1 Nos Outgoing - 16A, 3P, 10kA, "C" Curve, MCB - 3 Nos Outgoing - 16A, SP, 10kA, "C" Curve, MCB - 15 Nos

1

-

-

... More
LPDB TYPE -4 12 WAY VTPN DB Incomer - 63A, 4P, 100mA, RCBO "AC" Series - 1 Nos Outgoing - 16A, 3P, 10kA, "C" Curve, MCB - 6 Nos Outgoing - 16A, SP, 10kA, "C" Curve, MCB - 18 Nos

12

-

-

... More
LPDB TYPE -5 8WAY VTPN DB Incomer - 63A, 4P, 100mA, RCBO "AC" Series - 1 Nos Outgoing - 16A, 3P, 10kA, "C" Curve, MCB - 2 Nos Outgoing - 16A, SP, 10kA, "C" Curve, MCB - 18 Nos

1

-

-

... More
LPDB TYPE -6 16 WAY ETPN Incomer - 63A, 4P, 10kA, "C" Curve, MCB - 1 Nos Sub Incomer - 40A, 2P, 100mA, RCCB "AC" Series - 3 Nos Outgoing - 10/16A, SP, 10kA, "C" Curve, MCB -32 Nos

5

-

-

... More
LPDB TYPE -7 12 WAY ETPN Incomer - 63A, 4P, 10kA, "C" Curve, MCB - 1 Nos Sub Incomer - 40A, 2P, 100mA, RCCB "AC" Series - 3 Nos Outgoing - 10/16A, SP, 10kA, "C" Curve, MCB - 24 Nos

2

-

-

... More
LPDB TYPE -9 6 WAY ETPN Incomer - 40A, 4P, 10kA, "C" Curve, MCB - 1 Nos Sub Incomer - 32A, 2P, 100mA, RCCB "AC" Series - 3 Nos Outgoing - 10/16A, SP, 10kA, "C" Curve, MCB -12 Nos

1

-

-

... More
UPS DB TYPE -1 16 WAY ETPN Incomer - 40A, 4P, 10kA, "D" Curve, MCB - 1 Nos Sub Incomer - 32A, 2P, 100mA, RCCB "AC" Series - 3 Nos Outgoing - 16A, SP, 10kA, "D" Curve, MCB - 30 Nos

1

-

-

... More
UPS DB TYPE -2 8 WAY ETPN Incomer - 40A, 4P, 10kA, "D" Curve, MCB - 1 Nos Sub Incomer - 32A, 2P, 100mA, RCCB "AC" Series - 3 Nos Outgoing - 16A, SP, 10kA, "D" Curve, MCB - 18 Nos

2

-

-

... More
UPS DB TYPE -3 6 WAY ETPN Incomer - 40A, 4P, 10kA, "D" Curve, MCB - 1 Nos Sub Incomer - 32A, 2P, 100mA, RCCB "AC" Series - 3 Nos Outgoing - 16A, SP, 10kA, "D" Curve, MCB - 12 Nos

4

-

-

... More
UPS DB TYPE -4 6 WAY VTPN Incomer - 32A, 4P, 100mA, RCBO "AC" Series - 1 Nos Outgoing - 16A, 3P, 10kA, D" Curve, MCB - 3 Nos Outgoing - 16A, SP, 10kA, "D" Curve, MCB - 9 Nos

56

-

-

... More
PDB TYPE- 1 12 WAY TPN DB Incomer - 63A, 4P, 10kA, "C" Curve, MCB - 1 No Sub Incomer - 40A, 2P, 100mA, RCCB "AC" Series - 3 Nos Outgoing - 10A, SP, 10kA, "C" Curve, MCB - 24 Nos

1

-

-

... More
PDB TYPE- 2 12 WAY SPN DB ( Same shall be updated as per Lift Vendor Requirement) Incomer - 63A, 4P, 10kA, "C" Curve, MCB - 1 No Sub Incomer - 32A, 4P, 100mA, RCCB "AC" Series - 1 Nos Outgoing - 10A, SP, 10kA, "C" Curve, MCB - 2 Nos

5

-

-

... More
MCB's IN WEATHER PROOF ENCLOSURE 16A, 2P, MCB isolator in IP66 Polycarbonate enclosure

1

-

-

... More
25A, 2P, MCB isolator in IP66 Polycarbonate enclosure

1

-

-

... More
32A, 2P, MCB isolator in IP66 Polycarbonate enclosure

1

-

-

... More
63A, 2P, MCB isolator in IP66 Polycarbonate enclosure

1

-

-

... More
16A, 4P, MCB isolator in IP66 Polycarbonate enclosure

1

-

-

... More
25A, 4P, MCB isolator in IP66 Polycarbonate enclosure

1

-

-

... More
32A, 4P, MCB isolator in IP66 Polycarbonate enclosure

1

-

-

... More
63A, 4P, MCB isolator in IP66 Polycarbonate enclosure

1

-

-

... More
Weather Proof / Cable termination Box IP 66 Enclosure ( Landscape)

45

-

-

... More
Weather Proof encloser IP 66 Enclosure for housing 16A Socket with Switch ( Terrace)

7

-

-

... More
Din channel energy meter with 16A 3 Pin Socket with 16A 2P SLD in Lockable weather proof encloser for Car Charging

2

-

-

... More
LIGHT FIXTURES Supply, installation, testing & commissioning of light fixtures of suitable model numbers. The quoted rate for installation shall include the following, 1. Necessary anchor fasteners, 2. Down rods / Wires / Silk Wires for Suspended lights / chains (galvanized) 3. Ceiling rose/Junction Box with Connectors 4. Assembling of light fixtures 5. Connectivity between ceiling rose and Light fixture using PVC insulated FRLS multistrand copper wires in PVC flexible conduit of suitable size. 6. Connectivity between ceiling rose and Suspended Light fixture using PVC insulated PVC sheathed braided multistrand copper cable (Silk Cable) suitable for Switching. 7. UV rays emeited form Light fixture shall compile to IEC 62471 (2006) Similar to Regent -PENDENT CHENNAL LED LF-01 20W LED Suspended Linear Light Fixture (100X1200MM )

35

-

-

... More
LF-03 40W LED Suspended Linear Light Fixture (100X2400MM ) Similar to Regent -PENDENT CHENNAL LED

410

-

-

... More
LF-04 40W LED Suspended Dimmable Linear Light Fixture (100X2400MM ) Similar to Regent -PENDENT CHENNAL LED

210

-

-

... More
LF -06 Surface mounted 18W LED downlighter, Made of Die cast aluminium body with PC diffuser & Electronic driver. Similar to Wipro - Halo Plus LD99

245

-

-

... More
LF-05 Recess mounted 15W LED downlighter, Made of Die cast aluminium body with PC diffuser & Electronic driver. Similar to Wipro - Iris LD71

125

-

-

... More
LF-07 Recess mounted 18W LED downlighter, Made of Die cast aluminium body with PC diffuser & Electronic driver. Similar to Wipro - Halo CRDL 11

485

-

-

... More
LF-08 Recess mounted 18W dimmable LED downlighter, Made of Die cast aluminium body with PC diffuser & Electronic driver with required Ballast Similar to Wipro - Halo CRDL 11

20

-

-

... More
LF-10 Recess mounted 32W (2X2) LED downlighter . Similar to Wipro - CRCO10R036HP57G1

48

-

-

... More
LF-11 Recess mounted 32W (2X2) LED downlighter with Dimmable control. Similar to Wipro - CRCO10R036HP57G1

82

-

-

... More
LF-12 Surface mounted 36W 4 Feet LED Linear Light Fixture Similar to Wipro - LE10-491-XXX-57HCSL

42

-

-

... More
LF-13 Surface mounted 36W 4 Feet LED Linear Light Fixture Similar to Wipro - WIO 922208

63

-

-

... More
LF-14 Surface mounted 40W 4 Feet LED Linear Light Fixture IP 65 Similar to Wipro - LE20-491-XXX-57-XX

44

-

-

... More
LF-15 Surface mounted 10W 2 Feet LED Linear Light Fixture Similar to Philip Endura- BN02110S

63

-

-

... More
LF-16 Surface mounted 9 W Bulk Head light fixture Similar to Philip LW07-141

48

-

-

... More
LF-17 26 W Led Surface mounted suspended type Similar to Wipro - CRDL11S033HP57

19

-

-

... More
LF-18 10W Led Floor mounted light fixture

2

-

-

... More
Similar to flos LF-19 3W Led Step Light

12

-

-

... More
Similar to LT- soo3ctw000 LF-20 47W indoor type Surface mounted Up Down light

13

-

-

... More
Similar to XAL LF-21 13W outdoor type Surface mounted Updown light

2

-

-

... More
Similar to LT- Tubus LF-22 35W LED Flood Light for out door application. Cost shall incuded all types of clamps required for mounting.

10

-

-

... More
Similar to Philip -BVP120 LED 35 CW LF-23 LED strip Light For Indoor Application- 10 Watts / Mtr

50

-

-

... More
LF-24 LED strip Light For Outdoor Application

50

-

-

... More
LF-25 Supply & installation of Twin Avation light controllerled by 24hours timer in Polycarbonate encloser.

2

-

-

... More
POINT WIRING Light Point wiring Supply, installation, Testing and Commissioning of point wiring using 2R X 1.5+1R 1.5 Sqmm for Primary & 3R x 1.5 for Secondary wiring FRLS 1100V wire of approved make drawn in 20mm dia 2mm thick FRLS PVC rigid conduit including all conduit accessories such as bends, junction boxes etc., complete. The wiring shall be complete with ceiling roses, switches and all consumables. PRIMARY LIGHT POINT I. Primary light point means wiring from first switch control to the first light outlet. The switch and all necessary accessories would be part of primary point. Sensor shall be considered separately. Cost of wiring from Switch to sensor & senor to Light point to be conisdered II. Not to include the incoming lighting circuit from MCB-DB to switch. III. But to include the sub-circuit if it is drawn from adjacent switch box. IV. Ceiling PVC flexible conduit shall be included at the drop of light fixture.

500

-

-

... More
SECONDARY LIGHT POINT I. Secondary light point means extention of light outlet from existing primary point. Same to be controlled by the existing switch of primary point. II. Ceiling PVC flexible conduit shall be included at the drop of light fixture.

920

-

-

... More
MCB Control Light Point wiring Supply, installation, Testing and Commissioning of point wiring using 2Rx2.5+1 x 1.5 sqmm for Primary & 3Rx1.5 sqmm for Secondary wiring ZHFR 1100V wire of approved make drawn in 20mm dia 2mm thick PVC FRLS conduit including all conduit accessories such as bends, junction boxes etc., complete. The wiring shall be complete with ceiling roses, switches and all consumables. PRIMARY LIGHT POINT I. Primary light point means extending the wiring till the light fixture with ceiling rose & complete accessories (wiring from the DB to first light is covered under circuit mains) II. Ceiling PVC flexible conduit shall be included at the drop of light fixture.

75

-

-

... More
SECONDARY LIGHT POINT I. Secondary light point means extention of light outlet from existing primary point with ceiling rose & complete accessories. Same to be controlled by the existing MCB in DB II. Ceiling PVC flexible conduit shall be included at the drop of light fixture.

680

-

-

... More
Lift Shaft Lighting and Power Wiring for 9W LED bulkhead light fixture with 2x2.5 Sqmm + 1x1.5 sqmm PVC FRLS copper wires in Surface mounted 25mm dia 2mm thick PVC Heavy duty conduit controlled by 1 nos. 1way switch and Wiring for 6/16A 3-pin socket controlled by 16A socket with 2x4 Sqmm + 1x2.5 sqmm PVC FRLS copper wires in Surface mounted 25mm dia 2mm thick PVC Heavy duty conduit, Including providing and fixing of 6/16A 3 Pin switched socket per floor of approved make and design in GI boxes with grid plates and earthing the third pin of socket with 2.5 Sqmm PVC copper conductor stranded flexible FRLS wire & Supply , istn of 9W LED bulkhead fixture (for each landing, lift pit & headroom) of approved make.Wiring for Lighting and power of shall be drawn through seperate conduit. This will be controlled from the lift machine DB Lift pit, Lower Ground ,GF,1F,2F,3F, Terrace & Head room

4

-

-

... More
Stair Case Lighting Set of light points for stair case having Lower, Ground + 3 floors + terrace and one light points located near each landing/ midlanding using 3R x 2.5 sqmm PVC insulated multi strand flexible copper conductors in 25mm dia PVC conduit including all accessories and controlled by 10A MCB. Each circuit shall have maximum of 6 light fixtures and not more. The complete work shall be treated as single activity. Light fixture cost shall not be part of this line item. The cost shall include wiring from lighting DB and subsequent looping between points.

8

-

-

... More
POWER RECEPTACLES Supply, installation, testing and commissioning of Switched socket outlets on workstations / furntiure, on wall, ceiling with necessary mounting boxes, front plate of approved make & along with accessories, all in conformity with specifications, drawings, as required, approved. The cost shall include 1.2mm Thick GI back Box, Front Plate & all required Accessiores. Industrial type sockets shall be of Polycarbonate body with plug top. All switch / sockets including front plate & frame which will be mounted on the metal boxes shall have removable film coat to protect from scraches & paint during installation. Safety shutters to prevent accidental contact with live parts shall be provided. With modular with out back box 1x6A Universal socket controlled by 10A switch

18

-

-

... More
1x 6/16A Universal socket controlled by 16A switch

2

-

-

... More
2x 6/13A Universal socket controlled by 16A switch

3

-

-

... More
3x 6/13A Universal socket controlled by 16A switch

26

-

-

... More
4x 6/13A Universal socket controlled by 16A switch

6

-

-

... More
With modular back box 1x6A Universal socket controlled by 10A switch

98

-

-

... More
1x 6/16A Universal socket controlled by 16A switch

298

-

-

... More
1x 6/13A Universal socket controlled by 10A switch

5

-

-

... More
2x 6/13A Universal socket controlled by 16A switch

27

-

-

... More
3x 6/13A Universal socket controlled by 16A switch

5

-

-

... More
Industrial Sockets 1Ph 16A, 2P+E 3pin Industrial socket with 16A 2P MCB "C" Curve control housed in IP-66 Polycarbonate enclosure with plug top

170

-

-

... More
1Ph 32A, 2P+E 3pin Industrial socket with 32A 2P MCB "C" Curve control housed in IP-66 Polycarbonate enclosure with plug top

1

-

-

... More
1Ph 63A, 2P+E 3pin Industrial socket with 63A 2P MCB "C" Curve control housed in IP-66 Polycarbonate enclosure with plug top

1

-

-

... More
3Ph 16A, 3P+E 3pin Industrial socket with 16A 4P MCB "C" Curve control housed in IP-66 Polycarbonate enclosure with plug top

120

-

-

... More
3Ph 32A, 3P+E 3pin Industrial socket with 32A 4P MCB "C" Curve control housed in IP-66 Polycarbonate enclosure with plug top

1

-

-

... More
3Ph 63A, 3P+E 3pin Industrial socket with 63A 4P MCB "C" Curve control housed in IP-66 Polycarbonate enclosure with plug top

1

-

-

... More
Explosion Proof Industrial Sockets 16A 3 pin 1phase Industrial type socket with male /female connector controlled by 16A 2P MCB in fire rated weather proof box

72

-

-

... More
16A 5pin 1phase Industrial type socket with male /female connector controlled by 16A 4P MCB in fire rated weather proof box

72

-

-

... More
MS Floor junction boxes with top SS finish: Note : Cost shall include Sockets, Face Plate & required accerioires Floor mounted junction box to locate 2 set of 6/16A intel socket controlled by of 16A switch in 2 rows 1 on raw power other on UPS with 8 module dummy space for socket or data ports.

280

-

-

... More
Floor mounted junction box to locate 2 rows of 4 no 6/16A intel socket controlled by of 16A switch 8 module dummy space for data ports.

20

-

-

... More
Occupancy / Sensor with Coverage area as per drawing Standalone 230V, Recess Mounted PIR Occupancy sensor

116

-

-

... More
Standalone 230V, Recess Mounted Day Light sensor with Occupancy sensor

71

-

-

... More
SITC of Ceiling fan point controlled by 1 no. of 6A switch and stepped regulator for fan. The rate shall include cost of 6 amps one way switch, stepped regulator, concealed type metal deep junction box / Required supports sutable for Metal Deck Slab, complete with necessary accessories & hook to hang fan. etc., all complete as required.

321

-

-

... More
SITC of capactior type ceiling fan complete with down rod, blades, shakles, canopies etc. for operation on 230Volts 50 Hz 1Ph supply conforming to ISS-374-1979 and with double ball bearing system. Down rod to be conisdered mi 1.2Mtrs from ture ceiling ( Contractor shall coordiante as per false ceiling height and decide the length of exxteebded mounitng rod).

321

-

-

... More
POWER & LIGHTING CIRCUIT WIRING Circuit mains using 1.1kV grade FRLS PVC insulated copper conductor (MSCC) wires / FRLS PVC insulated PVC sheathed single core cables drawn in 2mm thick FRLS PVC rigid conduit or in existing raceway. Rates quoted shall include supply of conduits, wires & other conduiting accessories.Circuit mains shall be measured from respective DB to the nearest point. All circuit terminations shall be provided with solder less crimping type copper sockets / lugs, ferrules indicating source code on load side & load code on source side. There shall not be any joints in the circuits, only looping is allowed in terminal blocks & at points. 2Runs x 2.5 Sq.mm + 1R x 1.5 Sq.mm for Phase, Neutral & Earthing in 20mm Dia 2mm thick FRLS PVC conduit - For Circuit main & Light Point controlled by MCB / switch Control

12000

-

-

... More
3Runs x 1.5Sq.mm for Phase, Neutral & Earthing in 25mm Dia 2mm thick FRLS PVC conduit - For Circuit main & Light Point controlled by MCB / switch Control

3000

-

-

... More
Supply, installation, Testing and Commissioning of Sensor power wiring using 2x2.5 Sqmm + 1x1.5 Sqmm wiring FRLS 1100V wire of approved make drawn in 20mm dia 2mm thick PVC FRLS conduit including all conduit accessories such as bends, junction boxes etc., complete.

1500

-

-

... More
Power circuits - General Power Sockets Supply & wiring of Circuit Wiring of ISI marked FRLS copper conductor wires of approved make in 2mm Thick FRLS PVC conduit including all accessories. all in conformity with specifications, drawings, as required, approved. Rate shall include wall chasing & rough plastering, clamping / fixing arrangement & cost of Conduit mentioned. 2Runs x 4.0 sq.mm + 1R x 2.5 Sq.mm for Phase, Neutral & Earthing in 25mm Dia conduit

9500

-

-

... More
2Runs x 1.5 Sq.mm for Phase, Neutral in 19mm Dia 2mm thick FRLS PVC conduit - For ON/OFF/MUSHROOM HEAD PUSH BUTTON.

100

-

-

... More
LV CABLE & CABLE END TERMINATIONS Supply, laying, end termination, testing and commissioning of following sizes of 1100V Steel/Aluminium and Wire/Strip armoured, unarmoured, sheathed Aluminium / Copper conductor cables of approved make. End termination of cables using brass type cable glands single / double compression with aluminium / copper lugs. Note : a) Hydraulic crimping tool shall be used for making the end terminations. b) Single compression glands - up to 150 sq.mm. c) Double compression glands for sizes 150 sq.mm shall be used. d) Cable identification shall be made vide details furnished in single line viz., AYFY for PVC insulated, steel strip armoured, aluminium conductor cable and with PVC outer sheath. XLPE Insulated Armoured Aluminium conductor cables 3.5C x 300 Sq.mm - A2XFY

450

-

-

... More
Cable End Termination

14

-

-

... More
3.5C x 240 Sq.mm - A2XFY

1100

-

-

... More
Cable End Termination

24

-

-

... More
3.5C x 185 Sq.mm - A2XFY

1600

-

-

... More
Cable End Termination

68

-

-

... More
3.5C x 120 Sq.mm - A2XFY

350

-

-

... More
Cable End Termination

8

-

-

... More
3.5C x 70 Sq.mm - A2XFY

250

-

-

... More
Cable End Termination

8

-

-

... More
3.5C x 35 Sq.mm - A2XFY

200

-

-

... More
Cable End Termination

4

-

-

... More
4C x 25 Sq.mm - A2XFY

4300

-

-

... More
Cable End Termination

134

-

-

... More
4C x 16 Sq.mm - A2XFY

130

-

-

... More
Cable End Termination

4

-

-

... More
4C x 10 Sq.mm - A2XFY

600

-

-

... More
Cable End Termination

25

-

-

... More
3C x 10 Sq.mm - A2XWY

370

-

-

... More
Cable End Termination

4

-

-

... More
XLPE Insulated Armoured Copper Conductor Cables 3.5C x 120 Sq.mm Copper- 2XFY

250

-

-

... More
Cable End Termination

12

-

-

... More
3.5C x 95 Sq.mm Copper- 2XFY

20

-

-

... More
Cable End Termination

2

-

-

... More
3.5C x 70 Sq.mm Copper- 2XFY

180

-

-

... More
Cable End Termination

8

-

-

... More
4C x 25 Sq.mm Copper- 2XFY

500

-

-

... More
Cable End Termination

10

-

-

... More
4C x 16 Sq.mm Copper- 2XFY

100

-

-

... More
Cable End Termination

4

-

-

... More
4C x 10 Sq.mm Copper- 2XWY

3300

-

-

... More
Cable End Termination

146

-

-

... More
4C x 6 Sq.mm Copper- 2XWY

3100

-

-

... More
Cable End Termination

76

-

-

... More
4C x 4 Sq.mm Copper- 2XWY

1100

-

-

... More
Cable End Termination

34

-

-

... More
3C x 6 Sq.mm Copper- 2XWY

350

-

-

... More
Cable End Termination

36

-

-

... More
2C x 6 Sq.mm Copper- 2XWY

310

-

-

... More
Cable End Termination

10

-

-

... More
2C x 4 Sq.mm Copper- 2XWY

65

-

-

... More
Cable End Termination

2

-

-

... More
1C x 120 Sq.mm Copper- 2XWY

260

-

-

... More
Cable End Termination

10

-

-

... More
1C x 95 Sq.mm Copper- 2XWY

175

-

-

... More
Cable End Termination

10

-

-

... More
1C x 70 Sq.mm Copper- 2XWY

345

-

-

... More
Cable End Termination

10

-

-

... More
1C x 35 Sq.mm Copper- 2XWY

650

-

-

... More
Cable End Termination

20

-

-

... More
PVC Insulated Un-Armoured Copper Flexible Multistrand Cables 1C x 95 Sq.mm Copper - YY

650

-

-

... More
Cable End Termination

54

-

-

... More
1C x 25 Sq.mm Copper- YY

510

-

-

... More
Cable End Termination

36

-

-

... More
1C x 16 Sq.mm Copper- YY

250

-

-

... More
Cable End Termination

18

-

-

... More
3C x 4 Sq.mm Copper- YY

7100

-

-

... More
Cable End Termination

114

-

-

... More
5C x 4 Sq.mm Copper- YY

3400

-

-

... More
Cable End Termination

46

-

-

... More
2C x 2.5 Sq.mm Copper flexible cable inside 25mm PVC FRLS conduit for DG power sensing (cost of conduit to be included)

2500

-

-

... More
Cable End Termination with PVC gland and CU lugs etc.

200

-

-

... More
LADDER TYPE CABLE TRAY & PERFORATED RACEWAYS Supply, fabrication, installation, testing and commissioning of following type galvanised double bended cable trays from GI sheets continuously connected including horizontal and vertical bends, reducers, tees and other accessories and duly suspended/ Mounted from the ceiling / wall supported by suitable size from reputed manufacturer. complete as per specifications, as required. Also cost shall include 2 Runs of 40 x 6 mm Hot dip galvanised GI strips clamped to adject side of cable tray of all sizs of cbale tray. Note: Installation charges shall includes the necessary hardware viz,anchor fasteners, slotted C channel supports. a) Support at an intervals of 1000mm b) Down rod/vertical support as per site conditions approved by project manager c) Slotted channel to suit width of the tray d) Spring and plate washers with locknuts (galvanised). 100mm (W) x 50mm (D) x 1.6mm (T)

320

-

-

... More
150mm (W) x 75mm (D) x 1.6mm (T)

150

-

-

... More
300mm (W) x 75mm (D) x 1.6mm (T)

240

-

-

... More
450mm (W) x 75mm (D) x 1.6mm (T)

290

-

-

... More
600mm (W) x 75mm (D) x 2mm (T)

370

-

-

... More
750mm (W) x 75mm (D) x 2mm (T)

320

-

-

... More
Supply & Installtion of Wedge type support with required accessories & supporting rod of required sizes as per selected cable tray at every 1Mtr suitable for metal deck slab

3244

-

-

... More
Supply & Installtion of wired supports with required accessories with required sizes as per selected cable tray at every 1Mtr suitable for metal structural truss work.

676

-

-

... More
Steel fabrication and installation for supporting electrical works - the quoted rate shall include two coats of Zinc primer and two coats of enamel paint.

1500

-

-

... More
PERFORATED TYPE CABLE TRAY Supply, fabrication, installation, testing and commissioning of following type galvanised cable trays from specified thickness GI sheets continuously connected including horizontal and vertical bends, reducers, tees and other accessories and duly suspended from the ceiling with min 12mm Dia vertical GI threaded rods supported by 40mm x 40mm x 5 mm Slotted frame etc. (or installed on wall supported on suitable brackets as required) complete as per specifications, as required. Note: Installation charges shall includes the necessary hardware viz,anchor fasteners, full threaded down rods and slotted C channel supports. a) Support at intervals of 750mm b) Slotted channel to suit width of the tray c) Spring and plate washers with locknuts (galvanised). 300mm (W) x 50mm (D) x 1.6mm (T)

40

-

-

... More
150mm (W) x 50mm (D) x 1.6mm (T)

40

-

-

... More
Supply & Installtion of Wedge type support with required accessories & supporting rod of required sizes as per selected cable tray at every 1Mtr suitable for metal deck slab

160

-

-

... More
Raceways for Power Supply & Installation of following size GI raceway / wire way with cover, made out of 14 SWG GI for body and 14 SWG GI for cover. Junction boxes to be provided with enough supports inside the box. Raceway installed below floor shall include necessary mounting supports, junction boxes and accessories to fix it firmly to the ground. The raceways shall be fixed to the floor with GI strips so that there is no movement of the channels when civil work (pouring of cement concrete) is being done. All edges, cut faces shall be free of burrs & shall be smooth. Chipping of floor for laying floor raceway and filling the gaps with Cement concrete, chicken wire mesh, making it for floor finishing level cost to be considered. The channels shall be earthed at the boxes and at the joints with 14 SWG bare copper wire with screws so that earth is continuous. Jointing of the race ways to be done using fisher plates ALL RACEWAY TO BE PROVIDED WITH BIFURCATION WALL BETWEEN POWER AND NETWORK CABLES ,60% AREA WILL FOR POWER & 40 % FOR NETWORK Floor raceways for 14 Guage 450 x 40mm Size

30

-

-

... More
300 x 40mm Size

300

-

-

... More
250 x 40mm Size

105

-

-

... More
150 x 40mm Size

400

-

-

... More
100 x 40mm Size

280

-

-

... More
50 x 40mm Size

450

-

-

... More
GI Floor Junction boxes 14swg 500 x 500 x 60mm size

8

-

-

... More
350 x 350 x 60mm size

84

-

-

... More
300 x 300 x 60mm size

65

-

-

... More
200 x 200 x 60mm size

136

-

-

... More
150 x 150 x 60mm size

73

-

-

... More
100 x 100 x 60mm size

196

-

-

... More
50 x 50 x 60mm size

2

-

-

... More
Ceiling Raceway Supply & Installation of following size GI raceway / wire way with cover, made out of 16 SWG GI for body and 16 SWG GI for cover. Junction boxes to be provided with enough supports inside the box. Raceway installed above false ceiling shall include necessary mounting supports, junction boxes and accessories to fix it firmly to the ceiling. All edges, cut faces shall be free of burrs & shall be smooth. The channels shall be earthed at the boxes and at the joints with 14 SWG bare copper wire with screws so that earth is continuous. Jointing of the race ways to be done using fisher plates & 'Slotted Channel' angle supports @ 1000mm interval etc., to suit site conditions. 300 x 40mm Size

150

-

-

... More
250 x 40mm Size

40

-

-

... More
150 x 40mm Size

210

-

-

... More
100 x 40mm Size

170

-

-

... More
50 x 40mm Size

10

-

-

... More
Supply & Installtion of Wedge type support with required accessories & supporting rod of required sizes as per selected cable tray at every 1Mtr

1160

-

-

... More
GI Ceiling Junction boxes 350 x 350 x 60mm Size

19

-

-

... More
300 x 300 x 60mm Size

11

-

-

... More
200 x 200 x 60mm Size

29

-

-

... More
150 x 150 x 60mm Size

46

-

-

... More
100 x 100 x 60mm Size

5

-

-

... More
Supply & Laying of following size Raceway. Supports shall be powder coated with same colour of DB. Raceway 1.6mm thick, raceway cover 1.2mm thick. For DB Drops & DB Niches 100(W) mm x 110 (D)mm ( Depth D To be equal as per Eelctrical DB depth)

650

-

-

... More
150(W) mm x 110 (D)mm ( Depth D To be equal as per Eelctrical DB depth)

450

-

-

... More
200(W) mm x 110 (D)mm ( Depth D To be equal as per Eelctrical DB depth)

80

-

-

... More
Supply & Laying of PVC adaptable trunking systems of 80 x 50 mm , with required accerioioers such as Covers, Clip on partition, Frames, bases, Angles at walls

400

-

-

... More
Supply & Laying of PVC adaptable trunking systems of 150 x 50 mm , with required accerioioers such as Covers, Clip on partition, Frames, bases, Angles at walls

400

-

-

... More
Supply & Laying of following size 2mm thick FRLS PVC conduits in floor/Wall. Rate shall include wall chasing & rough plastering, clamping / fixing arrangement. 32mm dia

80

-

-

... More
25mm dia

450

-

-

... More
Supply & Laying of following size MS conduits in floor/Wall. Rate shall include wall chasing & rough plastering, clamping / fixing arrangement. 32mm dia

250

-

-

... More
25mm dia

450

-

-

... More
EARTH ELECTRODES, EARTH CONNECTIVITY CONDUCTORS Body earthing Supply, earth excavation, back filling, chamber and fixing of 100mm DIA GI Pipe earth station in conformity with IS 3043. 2 no.s of 50x6 GI strip, CI funnel of 20 gauge, block masonry chamber of 450mm(L)x 450mm(B)x 300mm(H) (clear space), concrete base CI Man hole cover with frame painted with bitumastic paint and packing with mixture of charcoal and salt around the pipe electrode including digging upto permanent water level but not less than 3mtr back filling as required. The earth resistance shall be less than 4 ohms. All work shall be carried out in conformity with specifications, standards & Codes. Refer Single line diagram, earthing schematic diagram and fault level calculations. Rate Shall include the labelling of the earth pits as per project manager's instructions.

22

-

-

... More
Neutral earthing Supply, earth excavation, back filling, chamber and fixing of 0.6m x 0.6m x 4mm CU Plate earth station in conformity with IS 3043. 2 no.s of 50x6 Cu strip, CI funnel of 20 gauge, block masonry chamber of 450mm (L)x 450mm(B) x 300mm(H) (clear space), concrete base CI Man hole cover with frame painted with bitumastic paint and packing with mixture of charcoal and salt around the plate electrode including digging upto permanent moisture level but not less than 3mtr back filling as required. The earth resistance shall be less than 4 ohms. All work shall be carried out in conformity with specifications, standards & Codes. Refer Single line diagram, earthing schematic diagram and fault level calculations. Rate Shall include the labelling of the earth pits as per project manager's instructions.

20

-

-

... More
Maintenance Free Earthing Supply, installation, testing & commissioning of MAINTENANCE FREE chemical earthing system in 150mm dia 3mtr bore hole with Single Earthing Electrode consist of 3mtr long 25m mm dia Copper earth electrode, Brass clamp terminal flat of 175 x 50 x 3 mm , the entire construction processed with Hot Dip Galvanization, outer surface up to 250-300 microns. The entire bore area shall be filled with highly conductive and non-corrosive nature crystalline material, along with electrode Moisture Booster compound of 3 x 25 Kg bags to fill surround the electrode at the time of installation or equivalent maintenance free earthing. (Moisture Booster having its property of moisture retention, conduction and non-corrosive nature). The cost shall include RCC chamber & CI cover. The resistance to be measured & witnessed by the client/consultant less than 1 ohm. The cost of Boring 150mm dia 3mtr long in hard rock area to be considered in the installation scope. For All equipment earthing

1

-

-

... More
Supply, laying, testing and commissioning of following sizes of GI/Cu earth continuity conductor (strips/ stranded wires) for interconnection between the earthing stations, panels, DB's & equipments etc on walls/ceiling, Corrosion protection for buried, Joints, conductors with bituminous coating and covered with PVC tapes etc all in conformity with the specifications as required, approved and directed. Note : Earth Strips laid in earth shall have sleeves. The rate shall include cost of laying Earth strip in floor with PVC sleeves. Rate shall include wall / floor chasing, rough plastering, clamping, Sleeve including End termination for Cables. 40 x 10 mm Hot dip galvanised GI strips

70

-

-

... More
40 x 6 mm Hot dip galvanised GI strips

60

-

-

... More
25 x 6 mm Hot dip galvanised GI strips

50

-

-

... More
25 x 3 mm Hot dip galvanised GI strips

1000

-

-

... More
40 x 6 mm CU strips

100

-

-

... More
25mm x 6mm CU strips

1250

-

-

... More
25mm x 3mm CU strips

3640

-

-

... More
1C x 10 Sqmm Copper Earting Cable

40

-

-

... More
1C x 6 Sqmm Copper Earting Cable

150

-

-

... More
1C x 4 Sqmm Copper Earting Cable

470

-

-

... More
1C x 2.5 Sqmm Copper Earting Cable

390

-

-

... More
Busbar of 0.25 Mtr length made out of 50 x 6 mm Cu. strip with drill holes of M8 at 25mm interval mounted on insulators with lockable type Enclosure.

4

-

-

... More
Busbar of 0.5 Mtr length made out of 50 x 6 mm Cu. strip with drill holes of M8 at 25mm interval mounted on insulators with lockable type Enclosure.

57

-

-

... More
Busbar of 0.75 Mtr length made out of 50 x 6 mm Cu. strip with drill holes of M8 at 25mm interval mounted on insulators with lockable type Enclosure.

5

-

-

... More
Supply and installation of Copper Earth bus mounted on insulators for Body Earthing with bimetal washers in enclosure. Note below mentioned part detail is only for busbar type, contactor shall fix the mentioned earth bus in required MS enclosure. 300 X100 X 6.35mm similar to Erico - TMGBA12L15P (Server & Hub Room)

9

-

-

... More
LIGHTING PROTECTION Air Terminal Supply of 8mm Aluminum Solid Round Conductor for building terrace as a air terminal to meet the requirements of IS/IEC 62305 and IEC 62561-2.

610

-

-

... More
Supply of Conductor Holder for fixing Aluminium Conductor above concrete Parapet with fixing Screws/glue on parapet to meet the requirements for IS/IEC 62305

40

-

-

... More
Supply of Flat roof Conductor Holder for fixing Aluminium Conductor on terrace floor to meet the requirements for IS/IEC 62305.

610

-

-

... More
Supply of Stainless Steel cross connector for 8- 10 mm round AL conductor to meet the requirement of IS/IEC - 62305.

65

-

-

... More
Supply of Stainless steel folding clamp for interconnecting air termination part to metal structures to meet the requirement of IS/IEC - 62305

40

-

-

... More
Supply of Expansion Piece with connector to compensate the expansion and contraction of Solid Round Al. Conductor during temperature variations to be provided on conductors length over 20 meters with Expansion Piece Connector for to connect Solid Roung Al. Conductor at both ends to meet the requirements for IS/IEC 62305

25

-

-

... More
Supply of 4 metre Vertical Air terminal of dia 16-10 mm with mounting accessories on flat surface to meet the requirements of IS/IEC 62305.Tested for Electrical ,Mechanical and Chemical as per IEC 62561.

3

-

-

... More
Supply of 2 metre Vertical Air terminal of dia 16-10 mm with mounting accessories on flat surface to meet the requirements of IS/IEC 62305.Tested for Electrical ,Mechanical and Chemical as per IEC 62561.

5

-

-

... More
Supply of 1 metre Vertical Air terminal of dia 10 mm to meet the requirements of IS/IEC 62305.Tested for Electrical ,Mechanical and Chemical as per IEC 62561

21

-

-

... More
Supply, laying and testing Accessories : System consist of Fang Fix with base and clamp, on the top air terminal is erected.

19

-

-

... More
Supply, laying and testing Fang fix clamp made of SS, lightning tested for 100 KA 10/350 micro sec waveform. 16 KG stone of 365 mm diameter, high level of stability. Quick and easy mounting of interception rod using anchors. Concrete, frost-resistant, can be stacked.

19

-

-

... More
Supply of suitable straight connector for interconnecting 8mm Aluminium conductor to meet the requirement of IS/IEC 62305.Tested for Electrical , Mechanical and chemical as per IEC 62561..

64

-

-

... More
Down Conductor Supply of 8mm Aluminum Solid Round Conductor as down conductor through side wall to meet the requirements of IS/IEC 62305 and IEC 62561-2.

425

-

-

... More
Supply of Conductor Holder for fixing Aluminium Conductor on side wall for fixing down conductor to meet the requirements for IS/IEC 62305.

425

-

-

... More
Supply of suitable straight connector for interconnecting 8mm Aluminium conductor to meet the requirement of IS/IEC 62305.Tested for Electrical , Mechanical and chemical as per IEC 62561.

40

-

-

... More
Supply of Stainless steel Test Joint round to round with enclosure, suitable connector for 8 mm aluminium round conductor & 10 mm round copper coated steel round conductor to meet the requirement for IS/IEC - 62305.

20

-

-

... More
Supply, laying and testing LCD screen shows the number of lightning strikes, hour and date of lightning events. Buttons enable TIME/DATE setting and log viewing.Replaceable battery, working life minimum five years, Complies with IEC/EN 62561-6.

1

-

-

... More
Test link with flat conductor holder in encloser with

20

-

-

... More
ACTIVE HARMONICS FILTER Supply and fixing of IGBT Based Active harmonic filter of required rating , mounted in MS Sheet metal enclosure with IP31. The AHF shall have feature of Harmonic mitigation, Neutral harmonic compensation, Load balancing, PF Correction. The AHF should be designed to with for an ambient of 45Deg C without derating suitable for IT Grounding system. The cost shall include commission, programming & performance checking of Active Harmonics filter. Active harmonics filter shall be installed in below mentioned panel with mentioned Rating. The mentioned rating is indicative only. Vendor shall re-evaluate the rating at the time of supply Active Harmonic Filter & re-confirm with the below mentioned rating. Vendor shall quote entire work as single quantity and works to be carried as mentioned below. Note: PMC / Client to inform respective vendor at the time Panel Submittal Approval. The re-evaluating of Active filter ratings & panel approvals shall take parallel with each other. MAIN LT PANEL - 60 Active Harmonics Filter

1

-

-

... More
CONTROL & WIRING FOR DIMMING OF LIGHTS Supply of Eco system/DALI Dimming controller; Controls 2 independent DALI links with up to 64 DALI ballasts per link. 4 groups of sensors inputs: Occ sensor, daylight sensor and IR sensor. Requires mains/line voltage feed Similar to Lutron QSNE-2DAL-D

2

-

-

... More
Supply Power Supply Unit for supply PDUs to Antenna devices Similar to Lutron QSPS-DH -1 -75

4

-

-

... More
5/8 Button wired keyapds with master raised and lower for all meeting / conference rooms above 4 pax. The keyapd should be programmable for individual scenes based on the user requiorment. Similar to Lutron QSWE 5BRL AW

8

-

-

... More
Network interface for the coocupancy sensors simialr to QSM 5 XW C

8

-

-

... More
2Runs x 1.5 Sq.mm in 20mm Dia 2mm thick FRLS PVC conduit - For DALI dimming

500

-

-

... More
4Runs x 1.5 Sq.mm in 25mm Dia 2mm thick FRLS PVC conduit - For DALI dimming

500

-

-

... More
SECTION V - MISCELLANEOUS WORKS Supply and fixing of first-aid box containing medicines for 10 persons to give first-aid treatment.

5

-

-

... More
Supply and fixing of DANGER BOARD 415 V, vide inspectorate prescription

12

-

-

... More
Drawing display board with A1 laminated SLD at Main Electrical rooms

2

-

-

... More
Drawing display board with A2 laminated Equipment layout at Electrical rooms

5

-

-

... More
Supply 11kV grade rubber gloves

4

-

-

... More
Supply & installation of NO ADMISSION BOARD

12

-

-

... More
6mm thick MS chequered plates with 2 coats of primer and final enamel paint for electrical shaft. The Cost shall include MS support required for supporting Checker plate.

600

-

-

... More
Supply & installation of sealing the portion left between cables and chequered fire barrier mortar of 63mm thickness (HILTI or approved equivalent) with minimum 2hours fire rating when tested in accordance with UL 1479 standards, for fire rated vertical openings in floors or slabs & floors made of concrete, masonry, metal, gypsum partition, after passing service lines like cable, cable trays, metal pipes. Mortar shall be a light weight cementations product and shall carry test certificate in accordance with IEC 60068-2-57:1999-11 (environmental testing) as per part 2-57: Test for Vibration-Time-history method & VERTEQII for seismic zone 4. Products shall carry test certificate for mould resistance rating determined by ASTM G21-96. It shall be UL listed. Rate shall include the mineral wool & miscellaneous items etc.., (Ratio of Mortar to foam can be assumed as 80% & 20% respectively)

2

-

-

... More
Supply & installation of Acrylic fire stop sealant (HILTI or approved equivalent) with minimum 2 hours fire rating when tested in accordance with UL 1479 standards, shall be used along periphery of Cable trays, Conduits , Cut-outs without insulation passing through fire rated walls & floors made of concrete, masonry, metal, gypsum construction to provide up to 2 hours insulation & integrity when subject to the test conditions of UL 1479 standards. Product should be tested for mould resistance as determined by ASTM G21-96 & shall have a VOC content of approx. 75 g/l as per LEED 2009. All installations to be in full accordance with the manufacturer. The sealant should be tested in accordance with IEC 60068-2-57:1999-11 (Environmental Testing) as per Part 2-57: Test for Vibration-Time-history method and VERTEQII for seismic zone 4. Product shall bear the UL & FM approval. Rate shall include the mineral wool backing material and other miscellaneous items etc..,

4

-

-

... More
Supply and fixing of 'shock treatment charts' on wall with inside plastic sheet cover and plywood back plate framework complete.

7

-

-

... More
1100 V grade ISI marked rubber mats shall comply with latest IS for electrical rooms (1m width 2 mtrs length)

20

-

-

... More
Steel fabrication and installation for supporting electrical works - the quoted rate shall include two coats of Zinc primer and two coats of enamel paint.

900

-

-

... More
Supply of below mentioned size HDPE Pipe. The cost shall include excavating of soil, laying of HDPE pipe & Back filling of soil. 160 mm dia.

10

-

-

... More
110 mm dia.

10

-

-

... More
Providing of 1500(W) X 1000( D) masanory trance with 1000 X 1000 RCC man hole covers at requral interval of 15 Mts. Refer Master plan for datials

10

-

-

... More
Preparation of as built drawings for the complete LT Related works-5 sets

1

-

-

... More
DG WORKS Design, supply, installation, testing and commissioning of the following : Diesel Generators - Prime duty application continuous rated 24/7 to provide full & continuous output as rated. Scope of supply shall include Monitoring of engine & Alternator, necessary equipment to provide input to the automation controller shall form a part of generator supply. The vendor shall refer to the I/O list Vide annexure to enable to hook to the building Automation System. The Generator sets shall be suitable for Auto Mains failure, Load sharing & load dependent start/Stop, Suitable for Isolated/parallel operation system. The Generator shall have communication port with modbus protocol ( in case of any other protocol the vendor shall consider necessary convertor). The communication port shall be RS 485 and Ethernet. DG sets developing following capacity 3 phase, 415 volts, 50Hz, 4 wire system coupled to suitable BHP diesel engine,1500 RPM,4 stroke,Multi-Cylinder, electric start for giving power rating as per ISO 8528 Part I in KVA at the load terminals of alternator. The engine shall conform to IS 10000/ ISO 3046/BS 649/ BS 5514. Synchronous Alternator shall be of class H insulation, IP 23,brushless,self / separately excited, self regulated, SPDP enclosure, through AVR suitable to withstand tropical conditions and shall comply with BS 5000 / IS 4722. Quoted rates for each DG Sets shall include the following a. Required number of anti vibration mounting pads b. Required number of charged battery, battery stand, battery leads etc., c. Method of cooling - Engine driven radiator / Radiator with external power supply d. Duty Type - Prime Duty e. Ambient Temp - 45 Deg C (Design Ambient) f. Relative Humidity - 40% - 50% 400 KVA Diesel Generating Set is comprising Diesel engine Prime duty, Radiator Cooled Diesel Engine @ 1500RPM, Complete with standard accessories. COUPLED TO Alternator rated at 400 KVA, 415V, 50Hz, 0.8PF, Mounted on a Channel Iron Base Frame. DG set shall be supplied with machine acoustic enclosure, First fill lube oil, AVM pads, Batteries with Leads, First fill of coolant as per standards & technical specifications furnished along with BOM/ Q.

2

-

-

... More
Supply, installation, testing and commissioning of Intermediate Tank 990 Litres capacity day oil storage tank fabricated from 4 mm thick MS plates. Tank shall include 450 mm ID manhole cover, level indicator and flanged connection for inlet, outlet, overflow drain and probe provision for level controller and external glass tube fuel level indication. Tank shall be mounted on 2 m high structure support with access ladder, Dip tray to be considered below the Day tank (painted with 2 coats of red oxide primer).

1

-

-

... More
Isolator Box Design, supply, installation, testing and commissioning of Cable Adopter box made out of CRCA sheet steel of minimum 2 mm thick with necessary MS angle or channel stiffeners suitable to mount side by the alternator with extended busbare to terminated the cable. Adopter box shall be with undrilled detachable gland plate of minimum 3 mm thick. Shall be of dust & vermin proof provided with neoprene gaskets with necessary hardwares. Box shall be powder coated and shade to be matched to the alternator body colour. Adaptor box suitable to terminate 415V cables between down stream with MCCB with necessary busbar and flexible bellows to be considered for connection between the DG set and isolator. Cable connecting between the DG Set to Adopter box with UNINYVIN CABLE to be considered. This shall be got done through approved fabricator only. Adopter box of 630A,4P, 35kA, MCCB, TM based, OC-SC, Release

2

-

-

... More
Exhaust System suitable for DG sets Supplying, fixing & installing exhaust pipe fabricated out of 5 mm thick Class B ERW and all fixing accessories and hardware for the following with 22G, aluminium sheet cladding & 50 mm thick 64 kg / cu M density mineral wool insulation wrapped in chicken mesh including all supporting structure with arrangements like Supporting frames, Hooks, Clamps, Hardware & Fasteners Etc complete as required. Note : Vendor shall study the DG set layout and routing of flue gas exhaust pipe and suggest suitable size of ERW "B" class pipe and bends to achieve free flow of flue gas without developing any back pressure on turbocharger, size of the pipe shall be supported by back pressure design calculations. Individual exhaust system shall be provided. Residential type silencer with spring support, suitable thickness and density of rock wool/ mineral wool insulation, chicken mesh and 22 G Aluminium Cladding, Pipe shall be as per IS 3589,GR.330(for 200 NB & above) and IS 1239,Part I (up to 150 NB pipe) inclusive of all supports, spring isolators , SS 304 expansion bellow, Y Joints complete with other necessary accessories for above mentioned DG sets

2

-

-

... More
200 mm dia MS Exhaust pipe including all necessary long bends, Short bends, Tees Etc. complete with insulation as above, flange, hardware and painting in approved colour & MS support for exhaust pipe & residential silenced

15

-

-

... More
250 mm dia MS Exhaust pipe including all necessary long bends, Short bends, Tees Etc. complete with insulation as above, flange, hardware and painting in approved colour & MS support for exhaust pipe & residential silencer

150

-

-

... More
300 mm dia MS Exhaust pipe including all necessary long bends, Short bends, Tees Etc. complete with insulation as above, flange, hardware and painting in approved colour & MS support for exhaust pipe & residential silencer

5

-

-

... More
Flexible bellows with suitable size of the flange.(SS 304 expansion bellows and matching flanges, gaskets, galvanised fasteners.)

25

-

-

... More
Spring Loaded supports (Bottle leg supports) for MS exhaust pipes to contain the vibrations. The steel for supporting the exhaust pipe is separately covered elsewhere in this bid document

4

-

-

... More
Steel works for exhaust pipe support Steel work as required to support the exhaust system with 1 coat of red oxide & enamel paint. Related civil works shall be as per approved drawing and specifications. ( The exhaust system to carry 3x300mm dia exhaust pipe 25 Mtrs from FFL as per CPCB.)

18000

-

-

... More
Lightning spikes made out of copper rod with 5 number of spikes mounted on suitable support at the top of the DG exhaust chimney

1

-

-

... More
25 x 3 copper strip complete with insulating base provided at 600 mm interval, running between copper spike to the earth pit at the bottom

150

-

-

... More
Aviation Obstruction lights Low intensity Aviation lights with LED lamp with flasher suitable for 230V AC including all accessories, controller etc.

1

-

-

... More
FRLS 3Core 2.5Sqmm PVC insulated PVC sheathed copper conductor aroumoured cable - (For Aviation Lamp)

50

-

-

... More
Cable End termination

2

-

-

... More
Fuel Piping for DG sets Supply, laying, jointing, testing and commissioning of HSD pipe (MS ERW heavy class as per IS 1239 part I) line with necessary specials such as elbows, tees, reducers, cutting welding, anti-corrosive treatment etc. all as per detailed specifications. Cost of all piping works shall be inclusive of required quantity of MS Grip Bolts ,Anchoring plates ,pipe bends, pipe tees, pipe unions, pipe nipples etc and required hardware. Piping laid underground shall be inclusive of anti-corrosive treatment, tapes and such protective measures as required. The cost shall include required valves, float valves & other accessories & equipments required. From Intermediate tank to header line 50mm dia. HSD pipe

60

-

-

... More
From header line to day tanks 32mm dia. HSD pipe

45

-

-

... More
LT CABLES Supply and laying of cables of following sizes in cable Tray/cable trench/buried in ground/clamped to wall with suitable clamps / trefoil clamps for single core cable, saddles, and fixing bolts and including testing and commissioning of the following 1100 volt grade ,XLPE/PVC insulation cable(extruded PVC compound), PVC compound inner sheath and extruded black PVC compound outer sheath complete as per IS 7098 Part I ,IS 1554 and IS - 694 required. The costs shall include for all cables to be provided suitable cable tags,PVC ties, dressing clamps or GI strips and route marker as per specification and as required. Cable installation shall be carried out as per relevant IS codes and standards. Method of measurement:-Cables shall be measured on the basis of linear centre line measurement from gland to gland. CONTROL CABLES- All control cables shall be multi-stranded 3C X 1.5 sq.mm ,Stranded Copper, PVC Cable

250

-

-

... More
6C X 1.5 sq.mm ,Stranded Copper, PVC Cable

250

-

-

... More
12 C X 1.5 sq.mm ,Stranded Copper, PVC Cable

10

-

-

... More
2C x 2.5 sq.mm,Stranded Copper, PVC Cable

250

-

-

... More
4C x 2.5 sq.mm,Stranded Copper, PVC Cable

250

-

-

... More
10C x 2.5 sq.mm,Stranded Copper, PVC Cable

250

-

-

... More
12C x 2.5 sq.mm,Stranded Copper, PVC Cable

250

-

-

... More
4C X 4 sq.mm shielded Cu cable

250

-

-

... More
LT CABLES END TERMINATION Supply and installation of Cable termination of the above cables including the cost of crimping heavy duty tinned copper lugs, nickel plated brass double compression glands/FLP glands, providing an earth tag, insulation tape, cable tag,PVC Gland boots /Shrouds and all requisite material for completion of termination complete as required. Single compression gland with earthing tag can be used in control cables, lighting and small power(from wall mounted DB to last mile terminations only if applicable) CONTROL CABLES- All control cables shall be multi-stranded 3C X 1.5 sq.mm ,Stranded Copper, PVC Cable

6

-

-

... More
6C X 1.5 sq.mm ,Stranded Copper, PVC Cable

6

-

-

... More
12 C X 1.5 sq.mm ,Stranded Copper, PVC Cable

2

-

-

... More
2C x 2.5 sq.mm,Stranded Copper, PVC Cable

4

-

-

... More
4C x 2.5 sq.mm,Stranded Copper, PVC Cable

4

-

-

... More
10C x 2.5 sq.mm,Stranded Copper, PVC Cable

4

-

-

... More
12C x 2.5 sq.mm,Stranded Copper, PVC Cable

4

-

-

... More
4C X 4 sq.mm shielded Cu cable

4

-

-

... More
Steel fabrication and installation for supporting electrical works - the quoted rate shall include two coats of Zinc primer and two coats of enamel paint.- For ladder type cable trays.

500

-

-

... More
SWITCH BOARDS Design, fabrication, supply, installation, testing & commissioning of LT Switchgear Panels as mentioned below strictly in conformity with IS:2675/BS:214 and construction shall be class of IP4X for Indoor and IP5X/6X for outdoor. The switchboard fabrication shall confirm to FORM-4A&4B construction. The cubicle shall be of CRCA sheet steel, duly powder coated with polyester for out door and epoxy polyester for indoor. The switchboard shall be extendable type. The ACB / MCCB / MCB shall be approved make and of specified short circuit rating and suitable for breaker coordination. Suitable bus bars of high conductivity Copper/Aluminium strips and mounted on non- hygroscopic insulating supports shall be provided. All components shall be approved type of components of recommended make of switchgear components of suitable capacity as mentioned in the single line diagram and in conformity with technical specifications. Panels shall Compliance to IEC - 61439. Auto Start / Auto Stop / Auto Synchronising Panel, Complete with intelligent PLC, Manual over ride facility for start, stop, Auto synch, Auto load sharing, PLC DG Synchronising is done by PLC and Interlocking of all incoming air circuit breakers/bus coupler shall be through PLC which shall be designed as well as operation comprising suitable nos. digital inputs (24 V) and outputs (Relay) Facility for operations of Breaker control for DG Synchronising Panel. DG SYNCHRONIZATION PANEL

1

-

-

... More
LT CABLES & END TERMINATIONS Supply, Laying, Testing and Commissioning of stranded XLPE/PVC insulated, Armoured/Unarmoured/Flexible, Aluminium / Copper conductor, laid in tray / Hume pipe / in ready made trenches, with nylon cable ties / MS Clamps @ 600mm interval etc., as required. The cost of the nylon tie and overlapping GI strip shall be included in the cost of installation. Cable identification labels at both ends clearly mentioning the cable specs & also at appropriate intervals along the cable route should be provided. The labels shall be engraved / anodized aluminium with white letters on black background. Supply, Installation, Testing and Commissioning of Compression type cable gland, tinned copper lugs, insulation tape, anti corrosive paste, brass clamps for gland earthing with 14 SWG copper wire to connect to nearest earth flat. Insulation: XLPE FRLS Inner sheath: Extruded PVC only for Multicore Outer sheath: Extruded Type ST2 PVC with FRLS Voltage grade:1100Volts Armoured: Galvanized Steel strip/Wire for multicore Non Magnetic Aluminium Wire/Strip for Single core Gland type : Brass with nickel plated Compression : Double compression above 70 Sq.mm Sealing Ring : Natural rubber for indoor, Neoprene for Outdoor Only heavy duty cable ties should be used for cable dressing. FRLS XLPE Insulated & Steel Armoured Aluminium Conductor Cables 3.5 Core X 300 Sqmm

1000

-

-

... More
End terminations

34

-

-

... More
MISCELLANEOUS ITEMS Co2 Fire extinguisher 4.5 kgs

2

-

-

... More
Providing first-aid box containing medicines for 10 persons to give first-aid treatment.

2

-

-

... More
415 V Danger Board - vide inspectorate prescription

2

-

-

... More
415 V grade rubber gloves

2

-

-

... More
Shock treatment charts with inside plastic sheet cover and plywood back plate framework complete.

2

-

-

... More
415 V grade with prescribed thickness, ISI marked rubber mats (Size:2mx 1m)

3

-

-

... More
Preparation of Shop drawings for the complete DG related works

1

-

-

... More
LIAISONING WORK Professional charges towards obtaining permission for installation as well as for running of 2Nos Generator sets from both Chief Electrical Inspector to Govt.of Karnataka and any other statutory body as may be required. Professional charges towards liaison charges for obtaining drawing approval and commissioning from CEIG

1

-

-

... More
Professional charges towards liaison charges for obtaining approval from Pollution Control Board

1

-

-

... More
UPS WORKS Design, manufacture, assembly, supply, installation, testing, delivery and commissioning of 80kVA UPS of Continuous rating, SNMP Card online, double conversion mode 3 ph input and 3 ph output UPS system with IGBT rectifier, with external isolation Transformer as per technical specifications. The UPS Cabinet shall consist of a Breaker & breaker cabinet, rectifier / charger, a three-phase inverter, static transfer switch, logic, synchronizing equipment, protective devices, display module shall show clear graphical / text based overview of alarms, status data & instructional help, Top/Bottom cable entry provision, Parallel kit with necessary BMS compatibility (Hardware & software items for third party integration) with MODBUS protocol-RS 485 and accessories as required for proper operation.

3

-

-

... More
Design, manufacture, assembly, supply, installation, testing, delivery and commissioning of 80kVA Isolation Transformer 3 phase input / 3 phase output with Incomer and bypass breaker with double neutral with enclosure as per specification.

3

-

-

... More
Supply, installation, testing and commissioning of Battery banks of requisite quantity and AH rating suitable for 80kVA (Continuous rating) online, double conversion operating on Modular UPS system with one suitably rated DC circuit breaker on each string with all necessary interconnecting links/wiring for each of above UPS units with autonomy to 15 minutes at the end of Battery life span at rated load. Battery shall be of the sealed maintenance free Valve Regulated Lead Acid (VRLA) stationary type 12V blocks, Battery Rack and base frame shall be designed to cater a point load to be conformed by vendor. (2Strings), Battery life should be 5 year.

3

-

-

... More
Design, manufacture, assembly, supply, installation, testing, delivery and commissioning of 25 kVA (Continuous rating) online, double conversion mode 3 ph input and 3 ph output UPS system with IGBT rectifier with external isolation transformer as per technical specifications. The UPS Cabinet shall consist of a Breaker & breaker cabinet, rectifier / charger, a three-phase inverter, static transfer switch, logic, synchronizing equipment, protective devices, Parallel kit with necessary BMS compatibility (Hardware & software items for third party integration) with MODBUS protocol-RS 485 and accessories as required for proper operation. (For Server/Hub)

2

-

-

... More
Design, manufacture, assembly, supply, installation, testing, delivery and commissioning of 25 kVA Isolation Transformer 3 phase input / 3 phase output with Incomer and bypass breaker with double neutral with enclosure as per specification.

2

-

-

... More
Supply, installation, testing and commissioning of Battery banks of requisite quantity and AH rating suitable for 25kVA (Continuous rating) online, double conversion operating on Modular UPS system with one suitably rated DC circuit breaker on each string with all necessary interconnecting links/wiring for each of above UPS units with autonomy to 15 minutes at the end of Battery life span at rated load. Battery shall be of the sealed maintenance free Valve Regulated Lead Acid (VRLA) stationary type 12V blocks, Battery Rack and base frame shall be designed to cater a point load to be conformed by vendor. (2Strings), Battery life should be 5 year.

2

-

-

... More
Design, manufacture, assembly, supply, installation, testing, delivery and commissioning of 15 kVA (Continuous rating) online, double conversion mode 3 ph input and 3 ph output UPS system with IGBT rectifier with external isolation transformer as per technical specifications. The UPS Cabinet shall consist of a Breaker & breaker cabinet, rectifier / charger, a three-phase inverter, static transfer switch, logic, synchronizing equipment, protective devices, with necessary BMS compatibility (Hardware & software items for third party integration) with MODBUS protocol-RS 485 and accessories as required for proper operation. (For EMERGENCY LIGHTING)

1

-

-

... More
Supply, installation, testing and commissioning of Battery banks of requisite quantity and AH rating suitable for 15kVA (Continuous rating) online, double conversion operating on Modular UPS system with one suitably rated DC circuit breaker on each string with all necessary interconnecting links/wiring for each of above UPS units with autonomy to 90 minutes at the end of Battery life span at rated load. Battery shall be of the sealed maintenance free Valve Regulated Lead Acid (VRLA) stationary type 12V blocks, Battery Rack and base frame shall be designed to cater a point load to be conformed by vendor. (2Strings), Battery life should be 5 year.

1

-

-

... More
CABLING SYSTEM Supply, installation, testing and commissioning of 1100V grade multistrand, copper conductor, Uni Nyvin, unarmoured flexible cable of requisite size for interconnection between battery, battery breakers and the respective 60KVA UPS Units. The cable shall conform to IS-694.

3

-

-

... More
Supply, installation and commissioning of 1100V grade multistrand, copper conductor, Uni Nyvin, unarmoured flexible cable termination with Single compression cable gland, Ring type copper lugs and necessary steel bolts for interconnection between battery, battery breakers and the respective 60 KVA UPS Units.

3

-

-

... More
Supply, installation, testing and commissioning of 1100V grade multistrand, copper conductor, Uni Nyvin, unarmoured flexible cable of requisite size for interconnection between battery, battery breakers and the respective 25KVA UPS Units. The cable shall conform to IS-694.

2

-

-

... More
Supply, installation and commissioning of 1100V grade multistrand, copper conductor, Uni Nyvin, unarmoured flexible cable termination with Single compression cable gland, Ring type copper lugs and necessary steel bolts for interconnection between battery, battery breakers and the respective 25KVA UPS Units.

2

-

-

... More
Supply, installation, testing and commissioning of 1100V grade multistrand, copper conductor, Uni Nyvin, unarmoured flexible cable of requisite size for interconnection between battery, battery breakers and the respective 15KVA UPS Units. The cable shall conform to IS-694.

1

-

-

... More
Supply, installation and commissioning of 1100V grade multistrand, copper conductor, Uni Nyvin, unarmoured flexible cable termination with Single compression cable gland, Ring type copper lugs and necessary steel bolts for interconnection between battery, battery breakers and the respective 15KVA UPS Units.

1

-

-

... More
Supply, installation and commissioning of 1100V grade multistrand, copper conductor, FRLS insulated, 4C x 2.5Sq.mm unarmoured flexible cable & termination with Single compression cable gland, Ring type copper lugs and necessary steel bolts for interconnection between UPS & Battery breaker.

6

-

-

... More
Battery open cabinet Supply and installation of Open Battery cabinet of epoxy painted sheet steel suitable for 60KVA UPS with separate compartment for circuit breaker for Item No.3. Each open cabinet shall be supplied with 600mm high MS base stand with powder coated. The design of supporting structure shall ensure uniform distribution of weight

3

-

-

... More
Supply and installation of Open Battery cabinet of epoxy painted sheet steel suitable for 25KVA UPS with separate compartment for circuit breaker for Item No.6. Each open cabinet shall be supplied with 600mm high MS base stand with powder coated. The design of supporting structure shall ensure uniform distribution of weight

2

-

-

... More
Supply and installation of Open Battery cabinet of epoxy painted sheet steel suitable for 15KVA UPS with separate compartment for circuit breaker for Item No.9. Each open cabinet shall be supplied with 600mm high MS base stand with powder coated. The design of supporting structure shall ensure uniform distribution of weight

1

-

-

... More
MS SUPPORTING STRUCTURES Supply & installation of fabricated MS frame approximately 600mm height suitable for 60KVA UPS. Exact height should be matched with the false flooring height. The design of stool shall ensure uniform distribution of weight

3

-

-

... More
Supply & installation of fabricated MS frame approximately 600mm height suitable for 25KVA UPS.Exact height should be matched with the false flooring height. The design of stool shall ensure uniform distribution of weight

2

-

-

... More
Supply & installation of fabricated MS frame approximately 600mm height suitable for 15KVA UPS.Exact height should be matched with the false flooring height. The design of stool shall ensure uniform distribution of weight

1

-

-

... More
TESTING & COMMISSIONING Site testing of individual 60 kVA online, double conversion UPS systems including load testing with all necessary cables, Load bank of 60kVA resistive Load @ site for testing etc. complete for 3 UPS Systems of 180 kVA in parallel as per technical specification.

1

-

-

... More
Site testing of individual 25 kVA online, double conversion UPS systems including load testing with all necessary cables, Load bank of 50kVA resistive Load @ site for testing etc. complete for 2 UPS Systems of 50 kVA as per technical specification

1

-

-

... More
Site testing of individual 15 kVA online, double conversion UPS systems including load testing with all necessary cables, Load bank of 15kVA resistive Load @ site for testing etc. complete for 1 UPS Systems of 15kVA as per technical specification

1

-

-

... More
REMOTE ALARM PANEL Supply, installation, testing and commissioning of Remote Alarm Panel with buzzer and display for group of 3 nos of 80kVA, 2nos of 25kVA 1No of 15 kVA UPS/Invertor units as required with interconnecting signal cables drawn in MS conduit and flexible MS conduits, fixing of conduit with necessary accessories, supports etc. Complete as per technical specification. The quoted rate shall be inclusive of metal conduits, flexible metal conduits and necessary fixing accessories, supports etc. Remote Alarm Panel with hooter and 100 meter cable for monitoring each group (3 Nos of 80KVA, 2Nos of 25kVA & 1 No of 15kVA) of UPS units.

1

-

-

... More
CCTV WORKS DOME CAMERA - Supply, Installation, Testing & Commissioning of IP Network TDN Low-Light IR Dome Camera, 1/3" CMOS, 2 MP @ 25fps or better, triple stream, Min. Illumination required 0.2 lux @ F1.4 (colour), 120dB True WDR, Min. Pixels 1920×1080p, triple stream, 3mm - 12 mm motorized focus & zoom lens, Intelligent Video Analytics such as Tripwire, Object Removed, Object Left Behind, etc Backlight Compensation, 3DNR, Privacy Mask, 3 IR LEDs Smart IR with upto 20m IR distance, H.264& MJPEG, Dual channel Audio G.711a/G.711u/AAC, 128GB SD card support, IP 54 & IK10, Alarm: 1 In & 1out, PoE, H.264 High Profile and MJPEG, PoE Class 3/ 12V DC/24VAC, Die-Cast Aluminium Construction, Having Operating temp range : –30°C to 60° C. Certifications: ONVIF Profile S & Profile G compliant. Safety Certification : UL, CE, EN, FCC &RoHS compliant. Cyber security Certification : UL-CAP

84

-

-

... More
DOME CAMERA - Supply, Installation, Testing & Commissioning of IP Network TDN Low-Light IR Dome Camera, 1/3" CMOS, 2 MP @ 25fps or better, triple stream, Min. Illumination required 0.2 lux @ F1.4 (colour), 120dB True WDR, Min. Pixels 1920×1080p, triple stream, 3mm - 12 mm motorized focus & zoom lens, Intelligent Video Analytics such as Tripwire, Object Removed, Object Left Behind, etc Backlight Compensation, 3DNR, Privacy Mask, 3 IR LEDs Smart IR with upto 50m IR distance, H.264& MJPEG, Dual channel Audio G.711a/G.711u/AAC, 128GB SD card support, IP 54 & IK10, Alarm: 1 In & 1out, PoE, H.264 High Profile and MJPEG, PoE Class 3/ 12V DC/24VAC, Die-Cast Aluminium Construction, Having Operating temp range : –30°C to 60° C. Certifications: ONVIF Profile S & Profile G compliant. Safety Certification : UL, CE, EN, FCC &RoHS compliant. Cyber security Certification : UL-CAP

18

-

-

... More
DOME CAMERA - Supply, Installation, Testing & Commissioning of IP Network TDN Low-Light IR Dome Camera FOR LIFT APPLICATION, 1/3" CMOS, 2 MP @ 25fps or better, triple stream, Min. Illumination required 0.2 lux @ F1.4 (colour), 120dB True WDR, Min. Pixels 1920×1080p, triple stream, 3mm - 12 mm motorized focus & zoom lens, Intelligent Video Analytics such as Tripwire, Object Removed, Object Left Behind, etc Backlight Compensation, 3DNR, Privacy Mask, 3 IR LEDs Smart IR with upto 20m IR distance, H.264& MJPEG, Dual channel Audio G.711a/G.711u/AAC, 128GB SD card support, IP 54 & IK10, Alarm: 1 In & 1out, PoE, H.264 High Profile and MJPEG, PoE Class 3/ 12V DC/24VAC, Die-Cast Aluminium Construction, Having Operating temp range : –30°C to 60° C. Certifications: ONVIF Profile S & Profile G compliant. Safety Certification : UL, CE, EN, FCC &RoHS compliant. Cyber security Certification : UL-CAP

3

-

-

... More
OUTDOOR BOX CAMERA - Supply, Installation, Testing & Commissioning of IP Network TDN Low-Light IR Outdoor Box/Bullet type fixed Camera, 1/3" CMOS, 2 MP @50fps, triple stream, Min. Illumination required 0.01 lux @ F1.4 (colour), 120dB True WDR, Min. Pixels 1920×1080p, triple stream, 5mm - 50mm variable focus & zoom lens, Intelligent Video Analytics such as Tripwire, Object Removed, Object Left Behind, etc. Backlight Compensation, Highlight Compensation, 3DNR, Privacy Mask, Internal/External Smart IR LEDs with upto 50m IR distance, H.264& MJPEG, Dual channel Audio G.711a/G.711u/AAC, 128GB SD card support, IP 54 & IK10, Alarm: 1 In & 1out, PoE, H.264 High Profile and MJPEG, PoE Class 3/ 12V DC/24VAC, Die-Cast Aluminium Construction, Having Operating temp range : –30°C to 60° C. Certifications: ONVIF Profile S & Profile G compliant, UL, CE, EN, FCC &RoHS compliant. Cyber security Certification : UL-CAP

30

-

-

... More
PTZ CAMERA - Supply, Installation, Testing & Commissioning of IP Network TDN Low-Light IP PTZ Camera, 1/2.3" CMOS, 2MP@25fps,H.264, MJPEG, Min. Illumination required 0.2 lux @ F1.6 (colour), 120dB True WDR, Min. Pixels 1920 × 1080p, triple stream, 4.3mm - 129mm OR 4.5mm - 135mm OR 6mm - 180mm lens, 30X motorized focus & zoom lens, Backlight Compensation, 3DNR, Defog, Electronic Image Stabilization, Privacy Mask, Internal / External Smart IR with upto 200m IR distance, Dual channel Audio G.711a/G.711u/AAC, 32GB SD card support, Alarm: 5 In/ 2out, PoE, H.264 High Profile and MJPEG, High-PoE and 12V DC/24VAC, IP 66, IK 10 vandal proof, Having Operating temp range : –40°C to 60° C. Certifications: ONVIF Profile S compliant, UL, CE, EN, FCC & RoHS compliant.

2

-

-

... More
SERVER - Supply, Installation, Testing & Commissioning of Management Server Processor Intel Xeon E5 26xx or higher Speed 2.5 GHz or Higher 8 Core Cache 10 MB L3 Cache System Bus/QPI 5 GTS/Sec Chipset Intel C600 or better on Intel or Equivalent OEM Mother Board Original Intel or OEM manufactured Memory 32 GB ECC DDR-III @ 1333 MHz or higher RAM

1

-

-

... More
VIDEO MANAGEMENT SOFTWARE - Supply, Installation, Testing & Commissioning of Video Management Software for 160 Cameras.

1

-

-

... More
Supply Installation Testing & Commissioning of Network Storage Manager(NSM) supporting ONVIF Profile S & G, PSIA, real time streaming protocol (RTSP) standards, emerging technologies in the industry, like 4K resolution, H.265 video compression codec, 3D PTZ control, 360° Fisheye camera and multi-imager/lens camera support, and intelligence events. System proposed shall have scalability of 4 to 128 cameras per NSM with sufficient licenses to record all the cameras in this requirement. NSM shall support simultaneous recording, live monitoring, playback/search of recorded video for up to 4K resolution on all cameras, taking snapshots and viewing presets for PTZ cameras and system management. NSM shall have integrated Dashboard to easily monitor the health and recording status, Flexible retention time / archive time for cameras, Smart Motion detection, Role-based operator privileges supporting Windows and local users, Video Archiving, Multi-stream support, Advanced security features with encryption support for communication between desktop client to NSM and secure https login for Web Client and Mobile apps, Event history and operator log reporting with export to PDF, Crystal Reports, MS Excel/MS Word. NSM Shall support scheduled backfilling of the recordings from the edge storage/SD card of cameras to the NSM using ONVIF Profile G NVR should support 160 camera license and 30 days of recording based on 1.3 MP, 25fps on higher native resolution. NVMMS Client shall be running on workstation/PC with minimum Intel Core i7-6700, 3.4GHz, 8GB RAM, Windows 10 (64 Bit) OS, DVD R/W, Integrated Intel HD graphics 530 and NVIDIA Quadro NVS 315 1 GB PCIE x 16 LP supporting 6 Monitors. The NVMMS shall be complete system including server for satisfactory surveillance operations with all necessary software's, licenses, required PC Hardware, Storage, accessories etc., civil, electrical works & peripheral items, as required as per specification in Annexure A at site of work inline with the Engineer in Charge instructions. PTZ JOYSTICK - Supply, Installation, Testing & Commissioning of POE based Joystick Controller having Touch wheel for camera & NVR/ Suitable Hardware control, Multiple connectivity options (RS232/422/485 and TCP/IP),Web browser for easy upgrading and configuring, Backlit Keys with pleasant adjustable blue or white LED, Laser cut ergonomic keys which shall be fade free, Min. two nos. Quick Monitor section keys, should have camera function keys for View, Tour, PTZ Call, Alt, Undo, Set, Iris, Focus. Etc. with Touch Pad for Fast Fwd, Reverse, Play actions etc. with all necessary accessories like AC Plug Adaptor, LAN Patch/Crossovers etc. Certification: UL, CE, FCC.

2

-

-

... More
LED - Supplying, Installation, Testing & Commissioning of 55" LED TV with 1920x1080 full HD resolution and as per specifications attached suitable for mounting on wall including connection etc.

6

-

-

... More
WORK STATION - Supply, Installation, Testing & Commissioning of Client WorkStation with CPU of Intel Core i7 Processor, With 8GB RAM, 1 GB Graphic Card, and 500 GB HDD.

2

-

-

... More
HARD DISK - Supply, Installation, Testing & Commissioning of 150nos. Cameras at 25 FBS at 30Day storage capacity (1200 TB) Hard Disk. Calculation to be submitted.

1

-

-

... More
POLE - Supply, Installation, Testing & Commissioning of 6 Meter long hexagonal GI POLE with suitable cement concrete foundation including excavation, including supply and fixing of foundation & all civil work suitable for outdoor camera including connection etc. complete as per specifications :

18

-

-

... More
Specification - Supply of 80mm Dia GI Pipe pole B class 6 Mtr length duly painted complete with accessories required for installation of CCTV equipments. box mounted up to 1.25 meter from ground level for switch with lock & various cable arrangements for camera & network equipment i/c anti climbing arrangement for protection of system from monkey etc. Vendor should supply all the mounting accessories. as per specifications i/c Erection of 6 mtr. length GI pole in cement concrete 1:3:6 (1 cement: 3 coarse sand: 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc i/c Providing and making collar with cement concrete (1 cement: 3 coarse sand: 6 stone aggregate 20 mm) of specified size and shape including from work, plastering if required, curing etc. as required POWER CABLE- Supply and fixing/laying of Power Cable 3 Core, Conductor size: 1.5 sq mm, multi strand with standard annealed electrolytic copper conductor suitable for single phase 230V AC supply/ DC supply in existing PVC Conduit/surface etc as reqd.

3600

-

-

... More
32MM HDPE PIPE - Supply, Installation, Testing & Commissioning of 32mm HDPE Pipe in the existing trench.

200

-

-

... More
STP CAT 6 CABLE - Supply, Installation, Testing & Commissioning of STP CAT 6 Cable

50

-

-

... More
Laying of HDPE pipe in ground etc. (Through Trenchless where as required) Size- 32mm

200

-

-

... More
25mm dia PVC CONDUIT - Supply, Installation, Testing & Commissioning of PVC Conduit On Surface

4000

-

-

... More
ACCESS CONTROL SYSTEM Supply, of access control system complete with all accessories, components, Access control Software having features like Web Based Client for Badging, Reporting, Alarm and Event Server support including Windows® Server 2012/2012R2, SQL Server 2012/ 2014/ 2016, Windows 7/8/8.1/ 10 (32-bit and 64-bit) . Single user interface for multiple security and business functions , Certification Management Virtualization support for VMWare and Microsoft® Hyper-V ,Database partitioning , definable operator permissions ,Support for Microsoft Azure are ibasic features comes inbuilt with package . Along with above , dedicated time & attendance software is requires to manage required number of doors. required to make the system full functional and consisting of the following equipments all as specified. Supply, installation, testing and commissioning Access Control System Server Software consisting of Access Control system ,2 client License , Graphical layout .All these along with high end security features consist in single package as per specification.Approve Make:-ONGUARD7.0(LENEL),CCURE9000(SOFTWAREHOUSE);Honeywell -(Pro-watch)

1

-

-

... More
Supply, installation, testing & commissioning of Main IP Based Access Intelligent Controller capable of controlling the reader interface modules / door controllers connected to it on RS485 multidrop, with suitable PSU, battery back up, tamper alarm , provision to accept fire trip signal fro FAS modules and enclosures.

1

-

-

... More
Supply, installation, testing & commissioning of 2 Door controller with door status module, I/O relays for interface unit to connect FACP with necessary power supply module including powdercoated MS enclosure.

8

-

-

... More
Supply, installation, testing & commissioning of 4 Door controller with door status module, I/O relays for interface unit to connect FACP with necessary power supply module including powdercoated MS enclosure.

13

-

-

... More
Supply, installation, testing & commissioning of 8 Door controller with door status module, I/O relays for interface unit to connect FACP with necessary power supply module including powdercoated MS enclosure.

10

-

-

... More
Supply, installation, testing & commissioning of Multi technology Smart card Readers (2”-3") complete as per specification.

125

-

-

... More
Supply, installation, testing & commissioning of Smart card proximity reader (AptiQ Multitechnology Reader-operating in13.56 Mhz-Mifare Technology) with suitable GI back box for mounting.

500

-

-

... More
Supply, installation, testing and commissioning, of Electromagnetic locks, suitable for single leaf door with magnetic contacts as per specification.

70

-

-

... More
Supply, installation, testing and commissioning, of Electromagnetic locks, suitable for double leaf door with magnetic contacts as per specification.

47

-

-

... More
Supply, installation, testing and commissioning of Exit Push Button, Green Mush Domed with NO/NC & SS Plate with Signage

109

-

-

... More
Supply, installation, testing and commissioning, of Break Glass unit complete in all respects.

112

-

-

... More
Supply, installation, testing and commissioning, of Magnetic Contacts Complete in all respects.

164

-

-

... More
Supply, installation, testing and commissioning, of Panic Bar complete in all respects.

12

-

-

... More
Supply, installation, testing and commissioning of Surface mount door Buzzer

112

-

-

... More
Supply, installation, testing and commissioning of Battery - 12 Volt DC - for controllers

31

-

-

... More
Supply, of PVC insulated and PVC sheathed 8 core (4 pair) 0.5 sq.mm. twisted pair standard cable with PVC/steel conduit as required as per specification

4440

-

-

... More
Supply, installation, testing and commissioning, of PVC insulated and PVC sheathed 4 core 1.5 sq.mm. copper condcutor cable with PVC/steel conduit as required as per specification

4440

-

-

... More
Supply, installation, testing and commissioning of 2 Core , 22 AWG Screened Shielded Cable

4440

-

-

... More
Supply, installation, testing and commissioning, of CAT 6 cable with PVC/steel conduit as required as per specification

500

-

-

... More
Supply, installation, testing and commissioning, of Access Control and Monitoring WORK STATION station complete as specified including all the required OS, Antivirus as per the given specification

1

-

-

... More
Supply, installation, testing and commissioning, of Access Control and Monitoring SERVER station complete as specified including all the required OS, Antivirus as per the given specification

1

-

-

... More
SITC of 50-55'' Flat Screen HD Profesional LED with remote control and wall mount unit / floor stand complete with making connections etc as per list of approved makes.

1

-

-

... More
SOLAR PLANT WORKS PV Solar Module : 320Wp,Poly crystalline70 cells as per IEC 61215 & IEC 61730. Module efficiency – 17.4%

228

-

-

... More
Solar Module Mounting structure: Aluminummounting structure or in suitable angle frame/ C-channels. IS 2062:1992, IS 4759, Seismic load cal.

1

-

-

... More
Grid Tile Inverters: 50KVA three phase, 415V AC string Inverter with remote monitoring facility, Dual MPPT. Inverter efficiency – 98.8%

1

-

-

... More
25KVA three phase, 415V AC string Inverter with remote monitoring facility, Dual MPPT. Inverter efficiency – 98.8%

1

-

-

... More
Supply and instalation of DCDB with (Consisting 8 Array and each array will have 21 PV panel serius connected) CRCA sheet enclosures have IP54 or above with double door protection with MCB, & Fuse. Should cater to Phase-2 also.

2

-

-

... More
CRCA sheet enclosures have IP54 or above with double door protection with MCB, AC SPD & Energy meter.Should cater to Phase-2 also.

1

-

-

... More
MCCB : TPN63 Amps, 36kA, 415VLL

1

-

-

... More
AC SPD: 415 AC, 20KVA , Type-II

1

-

-

... More
Solar meter panel at LT side: CRCA sheet enclosures have IP54 or above with double door protection with MCCB, & Energy meter

1

-

-

... More
Energy Meter: Class 0.5 Unidirectional Energy Meter (Multifunction Meter with 3 current transformers)

1

-

-

... More
MCCB : 400 A TPN 36KA, 415VLL

1

-

-

... More
DC Cable red & Black: 1 C x 6 SQ.mm PVC insulatedtinned Cu. Cable

4000

-

-

... More
AC cable from Inverter to ACDB box (AC cable) : 5C x 16 SQ.mm PVC insulated flexible Cu. Cable

250

-

-

... More
AC cable from ACDB to combiner box : 3.5 C x 35 sq.mm Aluminum cable

400

-

-

... More
AC cable from combiner panel Tosolar meter LT Panel (AC Cable) : 3.5 Cx 150 Sq.mm Aluminum cable

200

-

-

... More
Lightening Arrester: As per IEC 62305 Franklinglightning rod

1

-

-

... More
Earthing Rod with BFC chemical: As per IS 3043(1987), 3.0meters, Copper bonded, ¾ inches diameter

4

-

-

... More
G.I STRIP /wire for Earthing : GI strip 25 X 3 sq. mm or GI wire 10 SWG or copper wire/ copper cable 16 sq.mm

400

-

-

... More
Surge arrestor: Supply, Installation, Testing & commissioning of Outdoor type IP 65 protected Surge protection device with protective fuse and other necessary accessories as per ISI Standards

1

-

-

... More
Cable tray: ISI, rustproof and Industrial standard 450 mm W x 100 mm H

15

-

-

... More
300 mm W x 50 mm H

45

-

-

... More
150 mm W x 50 mm H

50

-

-

... More
Net Meter: Supply, Installation, Testing & commissioning of Bi-Directional, Multifunction Digital Meter, Class 0.2S and other necessary accessories as per IS Standards.

1

-

-

... More
Monitoring system : Supply, Installation, Testing & commissioning of Wireless/ Cloud based Data logging system with display unit including Weather monitor system with RS 485 port as per the specifications of this tender and directions of Engineer-in-Charge.

1

-

-

... More
Safety Items Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, 2 mm thick, and vitreous enamelled white on both sides, and with inscription in single red Colour on front side as required.

3

-

-

... More
Supply and fixing of 1.1 KV grade nominal 2.0 mm +/- 10% thick insulated Synthetic Mat conforming to IS 15652: 2006 and meeting the requirements of IS 5216 (Part1,2&3), IS 8437, IEC-479 Pub-1, along-with suitable adhesive/ chemibound, Pu resin, waterproofing compound and sealing material as per in service recommendation.

8

-

-

... More
Supply of Rubber hand gloves suitable for 1.1KV.

2

-

-

... More
Supply & fixing of shock treatment chart duly framed with 5mm thick glass required both in Hindi, English & Kannada for treating person suffering due to electric shock mounted on wall hooks.

1

-

-

... More
Providing & fixing of 4 No's 9.0 Litter capacity GI bucket painted in post office red Colour with prior coat of red - oxide paint and written with white paint 'Fire' and mounted on MS angle iron frame with bracket of appropriate size and capacity including filling sand.

2

-

-

... More
Supply of First Aid box conforming to IS 2217 -1963.

1

-

-

... More
Providing of Single line diagram chart duly framed.

2

-

-

... More
Supply and fixing of 4.5 Kg capacity Carbon Dioxide fire extinguisher with mounting hook and discharge horn.

2

-

-

... More
Supply and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm

600

-

-

... More
Providing and fixing of 20mm dia sizes of heavy duty GI Flexible Conduits suitable along with connectors complete with conduit gland & all accessories required.

150

-

-

... More
Liasoning and approvals (including net-metering) : BESCOM+CIG+PCB ETC

1

-

-

... More
Project documentation and reporting : As per USGBC guidelines

1

-

-

... More
Operation and Maintenance for 5 years (Except module cleaning): As per USGBC and MNRE guidelines

1

-

-

... More
Training to maintenance engineer :As per guidelines

1

-

-

... More
Plant insurance (Optional): General Insurance

1

-

-

... More
MISCELLANEOUS ITEMS · Flexible pipe · HDPE Pipe · Cable tie · Metal Cable Glands · MC4 Connectors (male-female set) · G.I. Saddle · PVC Taps · Conduit Pipe · Conduit Bend

1

-

-

... More
NETWORK IT Network Passive Cabling CAT6A Information IO Work Area Data- Blue

585

-

-

... More
CAT6 Information IO Work Area Voice -Yellow

84

-

-

... More
CAT6A RJ45 Rev Connector- Cam End

128

-

-

... More
CAT 6A 1 Mtr patch cord Data - Blue Color Rack end

585

-

-

... More
CAT 6A 1 mtr patch cord for voice rack end - Yellow

84

-

-

... More
CAT 6A 1 mtr patch cord for Camera - red color

128

-

-

... More
CAT 6A UTP Cable 305 Mts Roll 23 AWG

211

-

-

... More
1-port British Style faceplate, WHITE

220

-

-

... More
2-port British Style faceplate, WHITE

82

-

-

... More
4-port British Style faceplate, WHITE

28

-

-

... More
24-port unloaded, straight Jack Panel, SL-Series, 1U

33

-

-

... More
24-port unloaded, straight Jack Panel, SL-Series, 1U

5

-

-

... More
CAT 6A Information IO Rack End Data- Blue

585

-

-

... More
CAT 6A Information IO Rack Voice -Yellow

84

-

-

... More
CAT 6A Information IO Camera Rack end -Red

128

-

-

... More
CAT 6A 2 Meter patch cord Data - Blue Color user end

585

-

-

... More
CAT 6A 2 Meter patch cord userend - Yellow

84

-

-

... More
POE signal booster for CAT -  6 Cables

1

-

-

... More
12 Core SM OFC , Indoor Gel Free cable

980

-

-

... More
1U fiber LIU 24 Port with Duplex LC coupler with splice tray

12

-

-

... More
SM Pigtail 2 mtr

96

-

-

... More
SM OFC Patch cord LC to LC - 2mtr

32

-

-

... More
Labels for Patch cords pack of 2500

1

-

-

... More
Labels for Face Plate

1

-

-

... More
Cable Ties , Plastic Wrap and accessories

1

-

-

... More
L Type Ladder for wall mount

1

-

-

... More
Floor Mount 42U Rack Server rack with PDU 5x15AMP with 10 Socket, Earthing Kit

1

-

-

... More
24U 19 Network Rack 2 Post Aluminium

9

-

-

... More
Telecommunication Grounding Main Bus

8

-

-

... More
Rack Grounding Kit

4

-

-

... More
Rack Equipment ground kit

20

-

-

... More
STI Make Fire Stopping Box for Data cable entry and exit

8

-

-

... More
Cable Tray 100x40mm Ceiling Raceway With all Fittings And Threaded Rod For Ceiling.

480

-

-

... More
50x40mm floor Raceway With all Fittings And Threaded Rod For Ceiling.

400

-

-

... More
1" Ceiling Conduit Pipe With all Fittings

1410

-

-

... More
1" Floor Conduit Pipe With all Fittings

1670

-

-

... More
325 X 325 Junction Box

26

-

-

... More
HDPE pipe from main Entry to ISP

500

-

-

... More
IT Active Compontents 48 ports 10/100/1000 Base T and 4x 10G SFP+ ports , All copper ports should support 802.3at PoE + Standard, 1 x Out of Band IP based management Port , 1 Console Port, USB Port / External Flash , support stacking for upto 8 switches with minimum 32 Gbps stacking., Have Redundant Power Supply support and variable speed fan to adjust to varying weather conditions in campus

6

-

-

... More
Supply, installation, testing & commissioning of`Minimum of 24 ports  10/100/1000 Base T and 2x 10G SFP+ ports All copper ports should support POE+, 1 x Out of Band IP based management Port , 1 Console Port, USB Port / External Flash support stacking for upto 8, support stacking for upto 8 switches with minimum 32 Gbps stacking. switches with minimum 32 Gbps stacking.Have  Redundant Power  Supply support and variable speed fan to adjust to varying weather conditions in campus

1

-

-

... More
Supply, installation, testing & commissioning of Minimum of 12 ports  10/100/1000 Base T and 2x 10G SFP+ ports All copper ports should support POE+, 1 x Out of Band IP based management Port , 1 Console Port, USB Port / External Flash support stacking for upto 8, support stacking for upto 8 switches with minimum 32 Gbps stacking. switches with minimum 32 Gbps stacking.Have  Redundant Power  Supply support and variable speed fan to adjust to varying weather conditions in campus

2

-

-

... More
48 ports Non PoE 10/100/1000 Base T and 4x 10G SFP+ ports 1 x Out of Band IP based management Port , 1 Console Port, USB Port / External Flash support stacking for upto 8 switches with minimum 32 Gbps stacking. Have Redundant Power Supply support and variable speed fan to adjust to varying weather conditions in campus

9

-

-

... More
24 ports Non PoE 10/100/1000 Base T and 2 x 10G SFP+ ports 1 x Out of Band IP based management Port , 1 Console Port, USB Port / External Flash support stacking for upto 8 switches with minimum 32 Gbps stacking. Have Redundant Power Supply support and variable speed fan to adjust to varying weather conditions in campus

4

-

-

... More
12 ports Non PoE 10/100/1000 Base T and 2 x 10G SFP+ ports 1 x Out of Band IP based management Port , 1 Console Port, USB Port / External Flash support stacking for upto 8 switches with minimum 32 Gbps stacking. Have Redundant Power Supply support and variable speed fan to adjust to varying weather conditions in campus

2

-

-

... More
10Gig SFP SM Modules

36

-

-

... More
Wireless Access Point controller with minimum 100 Access point controling capability. Virtualized Software-Based WLAN Controller, The controller should support the following hypervisors and cloud environments Microsoft Hyper-V and Amazon EC2 cloud should have scalaibility upto 2000, All necessary hardware/server and the OS required for the installation.

1

-

-

... More
The wireless access point shall be dual radio; The 802.11AC Access Point should be 2x2 MIMO, dual-radio (concurrent 802.11 a/b/g/n/ac) wireless access points ;Data rates supported: 802.11b/g: 1,2,5.5,11,6,9,12,18,24,36,48 and 54 Mbps;802.11a: 6,9,12,18,24,36,48, and 54 Mbps 802.11n: MCS 0-23 up to 300 Mbps;

60

-

-

... More
Firewall The appliance based security platform should be capable of providing minimum 2 Gbps of Multiprotocol real world FW, IPS and Application Visibility throughput in a single appliance from day one.The appliance should have minimum 6 no. of 10/100/1000 Base-T Gigabit Ethernet ports and 1:1 redundant internal power supply.The appliance hardware should be a multicore CPU architecture with a hardened 64-bit operating system to support higher memory Firewall should have minimum 8 GB RAM and 8 GB Flash/250 GB HDD from day 1. Firewall should support stateful failover of sessions in Active/Standby and Active/Active mode Firewall Should support DES, 3DES, AES IPSec VPN throughput of minimum 150 Mbps Firewall should support at least 10,000 connections per second Firewall should support static Routes, OSPFv2, OSPFv3 and BGP4 Firewall should support PIM Multicast routing Firewall should support for Layer 3 and Layer 4 stateful firewall features, including access control, network address translation, and stateful inspection. Firewall should support creating access-rules with IPv4 & IPv6 objects simultaneously Firewall should provide application inspection for DNS, FTP, HTTP, SMTP, ESMTP, LDAP, MGCP, RTSP, SIP, SCCP, SQLNET, TFTP, H.323, SNMP etc. Firewall should be able to create access policies based on the User/group info from the Active Directory either through clientless or agent based mechanism. The Firewall should have an inbuilt URL filtering functionality with minimum of 75 pre-defined categories. The solution should support creation of custom URL categories for allowing/blocking specific destinations as required by the organization Should be able to enforce access policy with 500 commonly used applications while providing granular access control. Application recognition should be based on signatures, heuristics, and content scanning, removing the need to tie applications to ports. Firewall should support RFC 6379 based Suite-B Cryptography Suites/algorithms like AES- GCM/GMAC support (128-, 192-, and 256-bit keys), ECDH support (groups 19, 20, and 21), ECDSA support (256-, 384-, and 521-bit elliptic curves) for enhanced VPN security. Firewall should support SSHv2, SNMPv2c, SNMPv3 and NTP Firewall should support AAA using RADIUS and TACACS+ Firewall/ Firewall’s Operating System should be tested and certified for EAL 4/NDPP or above under Common Criteria Certification or FIPS Level 2 Certifications 3 Years onsite OEM Warranty

1

-

-

... More
IP EPABX expandable with 200 SIP IP Extensions by adding license keys of 8/16/32/128 / 256 IP licenses 04 FXO Ports (to connect 04 Analog trunk lines) 02 FXS Ports Multi level Auto Attendant with IVR functionality IVR designer Voice Mail System Voice Mail to email Fax to email , 3rd party audio conference Integration with MS Outlook Direct Click to Dial, Multiple locations connectivity, SIP Surveillance Router should have at least 2 open slots for additional LAN/ WAN modules other then asked ports.

1

-

-

... More
Video IP Phone, 4.3” capacitive colour Touch Screen, Built-in camera, Web browsing, 6 SIP accounts, HD audio, Skype, Microsoft Lync, sales force compatible, Gigabit Ethernet Ports, Power on Ethernet (PoE), Wi-fi, Bluetooth, 2 USB Port, SD Card slot, Mini HDMI port for LCD/LED TV connectivity, Android based 3 Year warranty

84

-

-

... More
Audio & Video Works 86 Inch 4K Multi touch up to 10 touch display with 4 HDMI inputs, USB (touch) x 3, with inbuilt media player USB port, LAN, RS232, Anti-Glare Tempered Glass, Pen or Finger touch, with Intelligent Light Detector, intelligent Thermo protector, with inbuilt Android system, whiteboard operation, On screen annotation Etc., with Necessary Mounting Bracket Approved Makes : Newline, Panasonic, Samsung, Sharp or Approved equilvalents

2

-

-

... More
55 Inch LED LCD 4K professional display with 2 x HDMI 1.4 , 1 x HDMI 2.0 , Display port x 1, DVI-D x 1, VGA x 1, LAN, RS232, with in-built speaker, with Brightness 400cd/m2 & Necessary Mounting Bracket Approved Makes : Panasonic, Samsung, Sharp or Approved equilvalents

11

-

-

... More
109" Diagonal Motorized Projection screen (16:10 format) Approved Makes : Logic, Elite, EIS or Approved Equivalent

3

-

-

... More
5500 ANSI Lumens WXGA projector with HDMI, VGA, RS232 & LAN Approved Makes : Epson, Panasonic, Benq or Approved Equivalent

3

-

-

... More
Wireless Presentation Systems with single USB Dongle, with 1 x HDMI output, Windows 7/8/8.1/10 32 & 64 bit, macOS 10.12/10.13/10.14 (Mojave), Android v7; v8 & 8.1 (app), iOS 10; 11 &12 (app) Approved Makes : Barco, Latentech or Approved equivalents

9

-

-

... More
Wireless Collar/ Lapel with wearable hearworn Mic for the presenter Approved Make : Shure/ AKG/ Sennheiser

3

-

-

... More
Wireless Handheld Mic for the Audience Approved Make : Shure/ AKG/ Sennheiser

6

-

-

... More
4" Recessed Ceiling Mount Speakers with 102 degree coverage angle with 40W @ 6/2 Ohms Approved Makes : Tannoy, Bose, JBL, Extron or Approved Equivalents

28

-

-

... More
Digital Audio server with 12 analog inputs, 8 analog outputs, with inbuilt AEC, VOIP and telephone interface with LAN, RS232 Approved Make : Biamp, BSS, QSC or Approved equivlent

3

-

-

... More
Dual Channel Power Amplifier 60W @ 8x/4/2 ohms Approved Makes - Labgruppen / Bose / JBL

9

-

-

... More
4x4 HDMI Matrix Switcher 4K60 4:2:0 with Audio Embedding & Deembedding, Max. Data Rate — 8.91Gbps data rate (2.97Gbps per graphics channel), with Active source detection for priority, last–connected automatic and manual switching, Selectable HDCP Off per Input, Approved Makes: Kramer , Crestron, Extron, or Approved Equivalents

9

-

-

... More
Media Link wall Mount inbuilt Controller with Ethernet Control , with RS232, IR, IO, Approved Make : Crestron, Extron, Kramer or Approved Equivalent

9

-

-

... More
Multiformat HDMI TwistedPair Transmitter upto 70Mtr Approved Make : Kramer, Extron, Crestron, or Approved Equivalent

19

-

-

... More
Multiformat HDMI TwistedPair Transmitter upto 70Mtr Approved Make : Kramer, Extron, Crestron, or Approved Equivalent

10

-

-

... More
HDMI TwistedPair Receiver with inbuilt scaler up to 70Mtr Approved Make : Kramer, Extron, Crestron, or Approved Equivalent

9

-

-

... More
USB based 12X PTZ Camera & Microphone with interfacing Hub for Video Conferencing and Audio Conferencing application Approved Make : Konftel, Panasonic or Approved Equivalent

4

-

-

... More
Expansion MIC pods for the above USB Microphones Approved Make : Konftel, Panasonic or Approved Equivalent

6

-

-

... More
Cable Cubby with 2 power, 2 LAN, HDMI, ports Approved Make : Logic, EIS or Approved Equivalent

12

-

-

... More
1.8 Mtr HDMI Moulded Cable Approved Make : Logic, EIS or Approved Equivalent

59

-

-

... More
10 Mtr HDMI Moulded Cable Approved Make : Logic, EIS or Approved Equivalent

13

-

-

... More
Audio Visual Face plate as required to provide AV Connectivity at the Table / Rack side Aprroval: Sample to be submitted for approval before fabricating the same

10

-

-

... More
Video Conference Codec with one cameras and 4 MIC pods for Conferencing application with HD resolution license and multipaty license Approved Make : Polycom , Cisco, Lifesize or approved equivalent

1

-

-

... More
AV Equipment Rack/ AV Storage with necessary leuvers which will be provided inside the room to house AV the backend equipments

16

-

-

... More
Necessary Cables & Connectors to complete the installtion and commisioning

1

-

-

... More
Installtion / Labour Cost

1

-

-

... More
PHE WORKS SANITARY FIXTURES Supplying, installing, testing and commissioning of approved colour Wall mounted - European water closet with concealed flush tank, dual flush (close coupled, 3 / 6 lts capacity as per LEED requirement, with all internal parts of the cistern for efficient functioning), with back inlet P or S trap by using conversion bend. The closet is mounted with GI Rag bolts and nuts, with 110 mm dia straight type syphon UPVC WC pan connector with neoprene rubber ring, 15 mm necessary valves, solid duroplast or scratch resistant seat and cover with special polythene buffer and flap, hinges to suit Floor mounting water closet complete etc., all of approved make .

71

-

-

... More
Supplying, installing, testing and commissioning of approved colour & size of Rectangle/Oval/Circular type wash basin with pillar cock/Basin Mixer. The basin is mounted over GI rag bolts and the basin is fitted with the following CP brass fittings like 32 mm CP brass waste coupling, CP brass bottle trap of casted type with 300 mm extension pipe, 40 mm OD PVC waste pipe concealed in wall and taken up to floor trap with necessary specials, 15 mm x 450 mm long PVC flexible hose inlet connecting pipe with end nuts for the Cold connections etc., complete all of approved make. Supply and fixing of granite counter shall be done by the external agency. (For all toiets)

61

-

-

... More
Supplying, installing, testing and commissioning of approved colour & size of Rectangle/Oval/Circular type wash basin with pillar cock/Basin Mixer. The basin is mounted over GI rag bolts and the basin is fitted with the following CP brass fittings like 32 mm CP brass waste coupling, CP brass bottle trap of casted type with 300 mm extension pipe, 40 mm OD PVC waste pipe concealed in wall and taken up to floor trap with necessary specials, 15 mm x 450 mm long PVC flexible hose inlet connecting pipe with end nuts for the Cold connections etc., complete all of approved make. Supply and fixing of granite counter shall be done by the external agency. (For all Handicap Toilet)

10

-

-

... More
Supplying, installing, testing and commissioning of 15 mm CP health faucet of approved make with necessary CP flexible hose 1000 mm long & nozzle, CP wall flange, CP angle cock etc., complete.

71

-

-

... More
Supplying, installing, testing and commissioning of approved make white colour glazed back inlet type glazed urinals with SS bolts and nuts to fix the urinal with all hangers and brackets, including dome type waste coupling, 32 mm bottle trap, CP spreader, CP connecting tube complete. with wall flanges, 15 mm dia CP flush valve with flexile hose, CP wall flange etc, Complete

40

-

-

... More
Supplying, installing, testing and commissioning of approved make & coloured urinal division plate of size 810 x 390 and fixed to wall by using CP brass screws etc . complete as per specifications.

40

-

-

... More
Supplying, installing, testing and commissioning of CP toilet paper holder fixed with counter sunk SS screws complete. (For VIP toilet)

1

-

-

... More
Supplying, installing, testing and commissioning of CP twin coat hook fixed with necessary ss screws, and clamps etc ., complete. Toilet door . (For All VIP Toilet)

1

-

-

... More
Supplying, installing, testing and commissioning of liquid Soap dispenser of approved make of suitable capacity of with necessary fixing materials etc . Complete (For VIP toilet)

1

-

-

... More
Supplying, installing, testing and commissioning of approved make CP towel ring fixed on to wall by using with SS screws (For VIP toilet)

1

-

-

... More
Supplying, installing, testing and commissioning of CP 20 mm dia 600 mm long grab bar with CP flanges, fixed with SS screws complete . Location : Handicap Toilet

10

-

-

... More
Supplying, installing, testing and commissioning of stainless steel sink with Single bowl of approved size manufactured from 1mm thick stainless steel, 18 G high grade indestructible chrome nickel steel with top quality polish, 40 mm dia CP waste coupling with extension flexible pipe of suitable dia. 15 mm dia angle cock etc., complete. Supply and fixing of granite counter shall be done by the external agency.

10

-

-

... More
Supplying, installing, testing and commissioning of 15mm dia CP Sink Cock with swinging spout (table mounted model) for Kitchen sink with CP wall flange etc

10

-

-

... More
Supplying, installing, testing and commissioning of storage vertical/Horizontal type water heater of 25Ltrs capacity. Approved make high rated pressure withstand capacity including all fittings & fixture inside, polypropylene cover, with 3 core heavy duty copper cable with 3 pin plug, automatic pressure release valve adjustable thermostat, angle valve,thermal cutout, puf insulation, tested for 7Kg pressure, etc.complete, & bracket painted with two coats of enamel paints. (Incusive of all fittings.)(with 2no's of angle valve)

1

-

-

... More
Supplying, installing, testing and commissioning of approved make CP Hot & cold mixer shower unit with hand shower rose, CP wall flanges for mixer etc., complete. (For VIP toilet)

1

-

-

... More
Supplying, installing, testing and commissioning of approved make of 15 mm dia CP angle cocks for washbasin, etc., Complete (For Wet labs)

6

-

-

... More
Supplying, installing, testing and commissioning of 125 mm x 125 mm floor grating of CP ring and grate with two SS screw with necessary fixing materials and cement concrete all - round the trap for collection of Waste water etc., complete.

124

-

-

... More
Supplying, installing, testing and commissioning of approved make hand drier of approved colour having twin blower integrated with timer cum infrared sensing system fully automatic which can work on 230 volts, single phase, 50 cycles etc., complete .

21

-

-

... More
INTERNAL & EXTERNAL WATER SUPPLY SYSTEM Supplying, installing, fixing, jointing, testing and commissioning of approved make Chlorinated Polyvinyl Chloride pipes (CPVC) up to 50 mm dia shall be SDR . 11 with ASTM CTS fittings, and above 50 mm dia shall be CPVC schedule 40 ASTM IPS with SCHD 80 ASTM F 439 fittings . The fittings and specials for SDR 11 such as tees, elbows, couplers, bends, enlargers etc., with CPVC brass threaded combination / transition specials such as male adapters brass threaded female adapters, brass FPT Tee, elbows, bends etc., The specials & fittings for Sch 40 pipe such as couplers, elbows, tees, unions, hex adaptor, end plug & caps, pipe clip & bend 90 etc., where connection with metal is to be made including necessary drilling holes, chasing walls and making the same good in cement mortar 1:1 restore the same original condition neatly as directed by the Engineer in-charge . Joints to be made with CPVC solvent cement up to 50 mm dia as per ASTM D - 2846 and above 50 mm dia primer P - 70, and solvent confirming to ASTM F - 493/724 . Including hanger supports, grip bolts & Clamps etc., 20mm nominal OD pipes

850

-

-

... More
25mm nominal OD pipes

290

-

-

... More
32mm nominal OD pipes

160

-

-

... More
Supplying, installing, testing and commissioning of approved make uPVC Pipes as per ASTM D 1785 Schedule 40 with sch 80 fittings pasted with solvent cement joints. The fittings and specials such as tees, elbows, couplers, bends, enlargers etc., with uPVC brass threaded combination / transition specials such as male adapters brass threaded female adapters, brass FPT Tee, elbows, bends etc., The specials & fittings for Sch 80 pipe such as couplers, elbows, tees, unions, hex adaptor, end plug & caps, pipe clip & bend 90 etc., where connection with metal is to be made including necessary drilling holes, chasing walls and making the same good in cement mortar 1 : 1 restore the same original condition neatly as directed by the Engineer in - charge . Including hanger supports, grip bolts & Clamps etc., Terrace & Vertical piping Quantity 25mm nominal OD pipes

80

-

-

... More
32mm nominal OD pipes

80

-

-

... More
40mm nominal OD pipes

30

-

-

... More
50mm nominal OD pipes

140

-

-

... More
65mm nominal OD pipes

485

-

-

... More
100mm nominal OD pipes

95

-

-

... More
Providing and fixing 9mm to 19mm thick nitrile rubber insulation with FR cloth wrap and UV paint for all terrace level exposed piping. Refer technical specificaiton for detailed description. Only considered terrace water supply piping. Pipe Size (mm) - Thickness of Nitrile Rubber Insulation 15 mm to 25 mm - 9mm thickness

50

-

-

... More
32 mm to 50 mm - 13mm thickness

80

-

-

... More
65 mm to above - 19mm thickness

400

-

-

... More
Supplying, installing, testing and commissioning of approved make Brass ball valves PN 10 conforming to IS 1703 with unions etc., complete. 25 mm dia (Screwed ends)

7

-

-

... More
32 mm dia (Screwed ends)

21

-

-

... More
40 mm dia (Screwed ends)

1

-

-

... More
Supplying, installing, testing and commissioning of CI butterfly valves PN 10 with standard lever confirming to IS standard 13039 with necessary flanges, nuts and bolts etc., complete. 50 mm dia

5

-

-

... More
65 mm dia

10

-

-

... More
100 mm dia

1

-

-

... More
Supplying, installing, testing and commissioning of brass body nickel plated automatic air release valves with necessary GI Specials, thread, holdtight, brass spindle, NBR and elastomeric, stainless steel spring polypropylenic float at the top most points of water supply distribution ring main. 20 mm dia

7

-

-

... More
Supplying, installing, testing and commissioning of approved make Brass non - return valve PN 16 conforming to IS 778 with unions, & other accessories etc., complete. 65mm nominal bore

4

-

-

... More
Supplying, installing, testing and commissioning of bronze `Y' strainer CI body with MS flange of suitable length fabricated from 16 gauge brass sheet with 3mm slots with necessary nuts and bolts, neoprene rubber gaskets, flanges etc., complete. 65 mm dia

2

-

-

... More
100 mm dia

1

-

-

... More
Supplying and laying of P . C . C support blocks of 1 : 2 : 4 concrete mix of sizes as given below for pipe supports at terrace level to run the terrace water supply pipes with necessary shuttering, plastering, pipe fixing anchors etc., complete as per specifications. 250 mm x 250mm x 200 mm

60

-

-

... More
Supplying, installing, testing and commissioning of approved make Conductive type level sensor from UG sump / overhead water storage tanks with SS 316 probes MS 2-1/2" table E std flange and weather proof cast aluminium enclosure to sense three levels.

2

-

-

... More
Supplying, installing, testing and commissioning of approved make Conductive type level sensor from UG sump / overhead water storage tanks with SS 316 probes MS 2-1/2" table E std flange and weather proof cast aluminium enclosure to sense three levels. (For borewell pump)

1

-

-

... More
Supplying, installing, testing and commissioning of 4 core 1.5 sq mm copper armoured cable from UG sump / overhead water storage tanks sensors to level control instruments laid in a 32 mm dia PVC 6 Kg / sqcm pipes.

60

-

-

... More
Supply, fabrication, fixing, testing and commissioning of GI Class "C "puddle flanged pipes of required sizes for inlet, outlet, vent and overflow pipes for Over Head & UG Sump Tank. The puddle flanged pipes shall be threaded end upto 80 mm dia and flanged ends above 100 mm dia. All the puddle flanged pipes, plates and fittings shall be Hot dip galvanized after fabrication as per IS specifications. PVC RUNGS

105

-

-

... More
50mm Diamater

12

-

-

... More
65mm Diamater

5

-

-

... More
80mm Diamater

18

-

-

... More
100mm Diamater

24

-

-

... More
150mm Diamater

3

-

-

... More
Supplying, installing, testing and commissioning of CI frame and cover for following sizes to overhead water tank, UG Tank, complete with step irons as shown on the drawings etc., complete, accessories comprising of the following: Rectangular 1200 x900 mm CI man hole side opening frame & cover Composite water tank frame & cover 1200 x 900 UG SUMP PUMP ROOM -Medium duty

4

-

-

... More
Square 600 x600 mm CI man hole top openingframe& cover Composite water tank frame & cover 600 x 600 OVER HEAD HEAD -Medium duty

10

-

-

... More
Construction of valve chamber for water meter with 230 mm thick best quality Table moulded bricks in CM 1:4, laid over a bed of 150 mm thick PCC 1:4:8, walls plastered smooth, internal plastering 12mm thk in CM 1:3 and external plastering 12mm thick in CM 1:6 including finishing smooth inside surface of the chamber with cement rendering, curing etc., The quoted rate to include excavation in all types of soil, necessary wooden/steel form work, back filling of the chamber sides with the excavated soil, disposing of the surplus earth after back filling with initial lead of 30 metres or as directed, including lift, providing & filling of gravel below water meter. Providing and fixing of Precast RCC cover of DM precast/sobha concrete products /southern concrete industries SFRC manhole frame and cover, set in PCC 1:2:4 etc., complete as per specifications and drawings or as instructed from EIC. Size 600X600 & depth upto 900mm.

1

-

-

... More
Providing, fixing, testing and commissioning of water meter with direct reading dial in KL with all integral parts of gun metal or brass with necessary Ball valves, NRVs, Y - strainer, unions, threaded pieces, check nuts etc., (of approved makes - analog) & accessories complete as per detail drawing & specifications. 65 mm nominal dia. (Quote considering all necessary fittings.)

1

-

-

... More
Supplying, installing, testing and commissioning of MS (Hot dip galvanized) slotted angle iron brackets, hangers, supports with necessary drilling holes to suit the insertion of pipe clamps, debarring etc., as per detailed drawing for supporting soil, waste and rain water pipes and water supply pipes in shafts with suitable PVC coated 'U' clamps, bolts, anchor bolts, nuts and washers fixed on shaft walls/ outer walls etc., The quoted rate shall include with the cost of brackets galvanizing with zinc alloy of 0.08 mm thick conformed to IS 1239 etc., complete as directed by the employer. (for vertical pipes support)

200

-

-

... More
Supply, installation and testing of Medium quality ('B' Class) GI pipes as per IS : 1239 Part I & II with malleable 'New' brand specials such as tees, elbows, check nuts, unions, bushes, flanges, etc., including threading, cutting and fixing in/on walls, under ceiling, on terrace, etc., Holdtite or an equivalent jointing compound shall be used for jointing the pipes. The quoted rate shall include for making necessary chasing, making bores in foundation, walls, slabs, etc., and making good the chased surfaces and bores in cement mortar. The exposed pipes shall be given two coats of enamel paint over a coat of zinc chromate primer. 65mm dia (For municipal water supply)

45

-

-

... More
Supplying and painting for Buried pipes with two coats of anti - corrosive treatment of approved bituminous paint over which with 4 mm thick polymer corrosion resistant tape as per IS 10221 of Pypekote/ IWL or equivalent, & rate to include to provide an overlap of minimum 15mm.

90

-

-

... More
Supplying, installing, testing and commissioning of GI "C" class pipe 100 mm dia tanker inlet connection system near the raw water storage tank . This includes 100 dia stand post, non return valve, Butterfly Valve & instantaneous brass coupler, etc,.Complete.

1

-

-

... More
Supplying, fixing and testing of approved make inlet and outlet PVC float operated CI ball valve of approved brand of manufacture and fixed to the inlet pipe at underground sump. 65mm Diamater (For municipal water supply)

1

-

-

... More
INTERNAL & EXTERNAL SEWERAGE SYSTEM Supplying, installing, testing and commissioning of UPVC soil, waste (SWR) confirming to IS 13592 :1992, type B (6 Kg / Sqcm) with solvent joint inclusive of all necessary specials like bends, tees, offsets, door ends, junctions, cowls, clean outs, end caps etc., laid under floor/ under ceiling /fixed on walls and in pipe shafts etc., complete. The quoted rate should include necessary MS supports like hanger supports, GI 'U' clamps with bolts, nuts and GI washers, chasing the walls, making bore in walls, and making good the chased surfaces and bores, curing etc . Complete. Internal Toilet pipes with Solvent cement joint 75 mm dia

285

-

-

... More
110 mm dia

225

-

-

... More
Supplying, installing, testing and commissioning of PVC pressure pipes (6 Kg / Sqcm) confirming to IS 4985 selfit type for waste connection from wash basin to floor trap / floor drain, anti syphonage pipe with solvent cement joints, including necessary specials like bends, tees, offsets, door ends, junctions etc, laid in sunken slab etc., the work shall include wall chase and making good the same in cement mortar etc ., complete. The quoted rate should include necessary MS supports like hanger supports, GI 'U' clamps with bolts, nuts and GI washers, chasing the walls, making bore in walls, and making good the chased surfaces and bores, curing etc .,Complete. Internal Toilet pipes 40 mm dia

160

-

-

... More
50 mm dia

120

-

-

... More
Supplying, installing, testing and commissioning of UPVC soil, waste and vent pipes Type B (SWR-4 Kg / Sqcm) confirming to IS 13592 : 1992, with rubber ring joint inclusive of all necessary specials like bends, tees, offsets, door ends, junctions, cowls, clean outs, end caps etc., laid under floor/ under ceiling /fixed on walls, and in pipe shafts etc., complete . The quoted rate should include necessary, scaffolding, MS Brackets of suitable size, GI 'U' clamps with bolts, nuts and GI washers, chasing the walls, making bore in walls, and making good the chased surfaces and bores, curing etc. Complete. Vertical pipes in shaft 75 mm dia

60

-

-

... More
110 mm dia

40

-

-

... More
Supply, fixing and testing of PVC pipes class II (4 kg / cm2) confirming to IS 4985 selfit (Solvent) type for joint inclusive of all necessary specials like clean outs, end caps, bends, tees, offsets, door ends, junctions, cowls, etc., laid under floor/ under ceiling /fixed on walls, and in pipe shafts etc., complete . The quoted rate should include necessary, scaffolding, MS Brackets of suitable size, GI 'U' clamps with bolts, nuts and GI washers, chasing the walls, making bore in walls, and making good the chased surfaces and bores, curing etc,.Complete. (For Anti - syphonage Pipe) 63 mm dia

40

-

-

... More
Supplying, installing, testing and commissioning of Foamcore Selfit PVC pipes are SN 4 pipes confirming to IS 16098(Part 1), Selfit pipes inclusive of all necessary specials like bends, tees, shoe pipe supports and all other items as required to complete the installation. The pipes shall be buried in underground. The installation shall be as per the ramming,trimming & levelling of trech for laying the pipes in required level and providing thrust or anchor blocks (Size:300X300mm,450x450mm) as pipe supports etc., complete as per specifications. Buried pipes from IC to IC to MH 160 mm dia

100

-

-

... More
200 mm dia

10

-

-

... More
Supplying, fixing, jointing, testing and commissioning spun / centri CI pipe for waste pipes installation conforming to IS:3989 cut to required lengths including all necessary fittings and specials such as Bends, junctions, offsets, access pieces (plain or door) & vent cowl. Fixing at wall/ceiling level supported by galvanized steel clamps & hangers etc. Making proper connection with drip seal joint of required depth as per BIS / manufacturer. Cutting, chases / holes in floors / walls / slab, excavation, refilling watering, disposal of surplus earth, making connection to manholes, making the walls and floors good.laid under floor/ fixed on walls on G.I. brackets with 'U' clamps in pipe shafts etc., complete. - (for wet labs) a) 75mm dia

45

-

-

... More
b) 100mm dia

65

-

-

... More
Supplying, installing, testing and commissioning of C.I smart floor trap trap with extension pipe, with brass CP frame & cover (150 mm x 150 mm square / 125 mm round). Trap of 100 mm dia Inlet, 50mm dia Inlet and 75 mm dia outlet fixed on a bed of cement concrete etc., complete. (The frame and grating shall be approved by Architects) - Wet labs

6

-

-

... More
Supplying, installing, testing and commissioning of approved make 110 mm x 75 mm dia uPVC multi inlet floor trap of self cleansing design moulded or fabricated, fixed on a bed of cement, concrete, etc., complete

118

-

-

... More
Supplying, installing, testing and commissioning of approved make uPVC Pipes as per ASTM D 1785 Schedule 40 with sch 80 fittings pasted with solvent cement joints. The fittings and specials such as tees, elbows, couplers, bends, enlargers etc., with uPVC brass threaded combination / transition specials such as male adapters brass threaded female adapters, brass FPT Tee, elbows, bends etc., The specials & fittings for Sch 80 pipe such as couplers, elbows, tees, unions, hex adaptor, end plug & caps, pipe clip & bend 90 etc., where connection with metal is to be made including necessary drilling holes, chasing walls and making the same good in cement mortar 1 : 1 restore the same original condition neatly as directed by the Engineer in - charge . Including hanger supports, grip bolts & Clamps etc., 50mm Diamater for PRM from STP to collection sump for lab waste

65

-

-

... More
80mm Diamater for PRM from sewer sump to STP

15

-

-

... More
Construction of Inspection chamber with 230 mm thick best quality Table moulded bricks in CM 1 : 4 laid over a bed of 150 mm thick PCC 1 : 4 : 8, walls plastered smooth, internal plastering 12mm thk in CM 1 : 3 and external plastering 12 mm thick in CM 1 : 6 including finishing smooth inside surface of the chamber with cement rendering, curing etc., The quoted rate to include excavation in all types of soil, necessary wooden/steel form work, back filling of the chamber sides with the excavated soil, disposing of the surplus earth after back filling with initial lead of 30 metres or as directed, including, lift, benching and channelling shall be finished smooth, in PCC 1:2:4. Providing and fixing of Precast RCC cover of DM precast/sobha concrete products /southern concrete industries SFRC manhole frame and cover, set in PCC 1:2:4 with Thermo plastic moulded steps for chambers beyond 900 mm depth etc., complete as per specifications and drawings or as instructed from EIC . For following sizes: Inside size of 600 x 600 mm & depth not exceeding 900 mm

8

-

-

... More
Construction of Conical manhole with 230 mm thick best quality TM bricks in CM 1:4, 600 mm dia at top and 1200 mm dia at bottom clear . The bed concrete shall be minimum 150mm . The manhole shall be constructed over a bed of 150 mm thick PCC 1:4:8, walls plastered smooth, internal plastering 12mm thk in CM 1:3 and external plastering 12mm thick in CM 1:6 including finishing smooth inside surface of the chamber with cement rendering, water proofing compound as per manufacture's specification, including curing . The quoted rate to include excavation in all types of soil including soft and hard rock, necessary wooden/steel form work, back filling of the manhole sides with the excavated soil, disposing of the surplus earth after back filling with initial lead of 30 mts. . including lift, benching and channelling shall be finished smooth in PCC 1:2:4 including dewatering if required . Supply and fixing of heavy duty frame and cover, set in PCC 1:2:4 with Thermo plastic moulded steps fixed at regular intervals etc., complete all as specifications & drawing or as instructed from EIC . DM precast/sobha concrete products / SFRC manhole frame/ Southern concrete Industries/pvc steps - Above 1 . 20mt to 2 . 0 mts. depth .

1

-

-

... More
Supplying, installing, testing and commissioning of PVC gully trap of internal size 450 mm x 450 mm with rebated top square shape 250 mm x 250 mm x 100 mm dia outlet set in 75 mm thick PCC 1 : 4 : 8 bed, construction of 230 mm thick masonry chamber in CM 1 : 4, with internal plastering of 12mm thk in CM 1 : 3 and external plastering 12mm thick in CM 1 : 6, including finishing smooth inside surface of the chamber with cement rendering with necessary benching and channelling, supply and fixing of 450 mmx 450 mm.Size CI frame and cover (weight of frame and cover not less than 10 kgs.)/ FRP Cover set in PCC 1 : 2 : 4 as per the detailed drawing. The quoted rate shall also include necessary excavation, backfilling, ramming, disposing off surplus earth etc., complete as per specifications & drawing.

2

-

-

... More
Providing Core Cutting of required dia outlets using low vibration mechanical means . Cost to include identification of embedded reinforcement using profometer, the diameter core cut will be 12mm more than the outer diameter of the pipe. Bore packing will be done by waterproofing agency. RCC slabs (125 to 175 mm Thick) For 110 mm pipes

190

-

-

... More
Supply, fabrication, fixing, testing and commissioning of GI Class "C "puddle flanged pipes of required sizes for inlet, outlet, vent and overflow pipes for Over Head & UG Sump Tank. The puddle flanged pipes shall be threaded end upto 80 mm dia and flanged ends above 100 mm dia. All the puddle flanged pipes, plates and fittings shall be galvanized after fabrication as per IS specifications. Sewerage collection sump, STP & Back wash collection sump 50mm Diamater

3

-

-

... More
65mm Diamater

2

-

-

... More
80mm Diamater

3

-

-

... More
100mm Diamater

2

-

-

... More
Supplying, installing, testing and commissioning of CI frame and cover for following sizes to Sewer collection tank, complete with step irons as shown on the drawings etc., complete, accessories comprising of the following: Square 600 x600 mm CI man hole top opening frame & cover Composite water tank frame & cover 600 x 600mm -Medium duty

3

-

-

... More
Supplying, installing, testing and commissioning of approved make Conductive type level sensor for sewerage collection sump with SS 316 probes MS 2-1/2" table E std flange and weather proof cast aluminium enclosure to sense three levels.

3

-

-

... More
Supplying, installing, testing and commissioning of 4 core 1.5 sq mm copper armoured cable from UG sump / overhead water storage tanks sensors to level control instruments laid in a 32 mm dia PVC 6 Kg / sqcm pipes.

50

-

-

... More
RAIN WATER PIPES Supplying, installing, testing and commissioning of UPVC rain water down take pipes Type A (SWR) confirming to IS 13592 :1992, with solvent joint inclusive of all necessary specials like clean outs, bends, tees, offsets, door ends, junctions, cowls, etc., laid under floor/ under ceiling /fixed on walls, and in pipe shafts etc., complete. The quoted rate should include necessary, scaffolding, MS Brackets of suitable size, GI 'U' clamps with bolts, nuts and GI washers, chasing the walls, making bore in walls, and making good the chased surfaces and bores, curing etc,.Complete. a)75 mm dia

55

-

-

... More
b)110 mm dia

135

-

-

... More
c)160 mm dia

120

-

-

... More
Supplying, fixing, testing and commissioning of leaf trap with kurra made out of UPVC with flange and PVC grating for rainwater outlets on terrace including all necessary grouting with sealants to make it absolutely waterproof. (for balcony & terrace rain water) a) 75 mm dia

30

-

-

... More
b)110 mm dia

10

-

-

... More
Supplying, installing, testing and commissioning of approved make uPVC Pipes as per ASTM D 1785 Schedule 40 with sch 80 fittings pasted with solvent cement joints. The fittings and specials such as tees, elbows, couplers, bends, enlargers etc., with uPVC brass threaded combination / transition specials such as male adapters brass threaded female adapters, brass FPT Tee, elbows, bends etc., The specials & fittings for Sch 80 pipe such as couplers, elbows, tees, unions, hex adaptor, end plug & caps, pipe clip & bend 90 etc., where connection with metal is to be made including necessary drilling holes, chasing walls and making the same good in cement mortar 1 : 1 restore the same original condition neatly as directed by the Engineer in - charge . Including hanger supports, grip bolts & Clamps etc., 80mm Diamater for PRM from storm water sump to external drain

150

-

-

... More
Construction of storm water Recharge pit / 1.2m dia 3.0m depth with the clear dimensions as mentioned in the drawing, and filling the annular space with gravel,pebbles,sand to the entire depth with RCC top cover slab of 600 x 600 mm, RCC precast cover inlet and outlet including precast rings, pre cast slab at top able to lift during maintenace , provisions of drain connections all leads and lifts etc, 150mm dia PVC borewell casing(1.5m length), geo filter wrapping around borewell casing and 100mm dia MS discharge pipe 2.5m length etc complete.complete.

5

-

-

... More
Construction of Catch basin of size a per below with 230mm thick walls in well burnt table molded bricks in CM 1:6 over a bed of 150mm thick PCC 1:4:8 internal walls shall be plastered smooth in CM 1:3 and external walls plastered CM 1:3 with sponge finish. Fixing MS Fabricated Higed Grating with MS frame of 50x50x6mm.The top surfaceof the catch basin fixing precast RCC grating shall be flushed to the landscape level and making suitable outlet arrangement to lateral drain with necessary trimming of soil, back filling with the selected earth. with all leads and lifts etc., complete. Inside size of 600 x 600 mm

50

-

-

... More
Inside size of 900 x 900 mm

2

-

-

... More
Supply, installation, testing and commissioning of RCC NP2 Class hume pipes conforming to IS: 458, with collar joint in CM 1:3 packing the collar joints with hemp rope dipped in cement slurry, finishing the surface smooth with neat cement slurry, including, curing & laid to correct levels and required slope below ground in trenches up to required depth & backfilling with available good quality earth in layer not exceeding 20 cm in depth, watering, levelling consolidation etc., complete. 150 mm dia

445

-

-

... More
200 mm dia

320

-

-

... More
Providing and constructing of External box drain with perforated precast cover slabs and drain detail and length is as per layout and details enclosed. 450mm Wide drain

105

-

-

... More
Supplying and installing MS fabricated ramp drain grating at Entrance/ where ever indicated using 50mm nominal bore, MS pipes at 105mm C/C and 8mm thick MS flats welded together and placed on MS angles of size 65mm x 65mm x 6mm as enumerated in the drawings, the quoted rates shall include for painting two coats of enamel paint over a coat of primer etc., complete.

22

-

-

... More
Supply, fabrication, fixing, testing and commissioning of GI Class "C "puddle flanged pipes of required sizes for inlet, outlet, vent and overflow pipes for Over Head & UG Sump Tank. The puddle flanged pipes shall be threaded end upto 80 mm dia and flanged ends above 100 mm dia. All the puddle flanged pipes, plates and fittings shall be galvanized after fabrication as per IS specifications. Storm water collection sump PVC RUNGS

24

-

-

... More
50mm Diamater

2

-

-

... More
80mm Diamater

6

-

-

... More
100mm Diamater

2

-

-

... More
Supplying, installing, testing and commissioning of CI frame and cover for following sizes to Storm water colletion Tank, complete with step irons as shown on the drawings etc., complete, accessories comprising of the following: Square 600 x600 mm CI man hole top opening frame & cover Composite water tank frame & cover 600 x 600mm-Medium duty

4

-

-

... More
Providing, installing, testing and commissioning of approved make Conductive type level sensor for UG sump storage tank with SS 316 probes MS 2-1/2" table E std flange and weather proof cast aluminium enclosure to sense three levels. (For strom & rain sumps)

3

-

-

... More
Supplying, installing, testing and commissioning of 4 core 1.5 sq mm copper armoured cable from UG sump / overhead water storage tanks sensors to level control instruments laid in a 32 mm dia PVC 6 Kg / sqcm pipes.

200

-

-

... More
Supplying, fixing, testing and commissioning of Rainy filter for rainwater vertical pipes outlets at ground floor including all necessary grouting with sealants, etc,. Complete 110mm diameter

2

-

-

... More
160mm diameter

7

-

-

... More
PUMPS & ACCESSORIES Supply, installing, testing and commissioning of approved make centrifugal monobloc pumps inside the Pump room. The quoted rate shall include Automatic control panel with level switches, starters panel, dry run preventer, O/L relays, necessary wiring up to the pumps and control panel,all accessories like valves, non return valve, pipes etc the pumps shall run 415V 50Hz electric supply, complete. 1 no. working + 1 no. standby = 1 SET Duty : from Treated sump to Domestic OHT a) 1 Lps at 2 - 40 M head

1

-

-

... More
1 no. working + 1 no standby = 1 Set Duty : from STP to Flushing OHT a) 2 Lps at 35 M head

1

-

-

... More
1 no. working + 1 no standby = 1 Set Duty of each pump: for irrigation lift pump a) 6.0 Lps @ 35 M head

1

-

-

... More
1 no. working + 1 no standby = 1 Set Duty of each pump: for Lab waste disposal pump a) 1.0 Lps @ 25 M head

1

-

-

... More
Supply, Installing, testing and commissioning submersible lift pump with IP - 68 enclosure of adequate HP, capable of giving a required discharge at suitable head to work on 3 Ph 50 Hz, 400 / 440 V AC supply fitted on a common base frame accessories to lift the pump during maintenance , control panel with level switches with wiring from TPN switch to control panel and to the pump and the control panel comprising of O/L relays, single phase preventor, separate overload trip and relayset, ON/OFF/TRIP indicating lamps, start/stop push buttons with necessary unions, flanges, all accessories like valves, non return valve, pipes etc will be measured under relevant item. etc., complete. Duty : Dewatering sump to external drain (In WTP & STP) a) 1 Lps at 35 M head

3

-

-

... More
1 no. working + 1 no standby = 1 Set Supplying, installing, testing and commissioning of approved make Conductive type level sensor for back wash collection sump in WTP & STP with SS 316 probes MS 2-1/2" table E std flange and weather proof cast aluminium enclosure to sense three levels.

2

-

-

... More
Supplying, installing, testing and commissioning of 4 core 1.5 sq mm copper armoured cable from UG sump / overhead water storage tanks sensors to level control instruments laid in a 32 mm dia PVC 6 Kg / sqcm pipes.

50

-

-

... More
Supplying, Installing, testing and commissioning Storm water disposal submersible pump with IP - 68 enclosure of adequate HP, capable of giving a required discharge at suitable head to work on 3 Ph 50 Hz, 400 / 440 V with necessary unions, flanges, all accessories like valves, non return valve, pipes, control panel with level switches etc., complete. 2 Lps at 35 M head (storm water sump pump-1)

1

-

-

... More
1 no. working + 1 no standby = 1 Set 3 Lps at 35 M head (storm water sump pump-2)

1

-

-

... More
1 no. working + 1 no standby = 1 Set Supplying, fixing, testing and commissioning of Booster system with variable frequency drive. The system shall comprises of pump, precharged pressure tank, pressure switch etc., complete with electric motor at 1500 RPM 415V 3Ph 50 Hz required duty conditions mounted on common base plate and wiring from panel to the motor including air volume controls, all accessories like valves, non return valve, pipes etc., complete. Duty :for Domestic water a)5.0 Lps Cut in pressure : 2.0 Kg/cm2 and Cut out Pressure :2.5 Kg /cm2:(1 Working + 1 Standby)

1

-

-

... More
Duty :for Flushing water b] 6 Lps Cut in pressure : 2.0 Kg/cm2 and Cut out Pressure :2.5 Kg /cm2:(1 Working + 1 Standby)

1

-

-

... More
Supplying, Installing, testing and commissioning Waste & Sewerage water cutter disposal submersible pump with IP - 68 enclosure of adequate HP, capable of giving a required discharge at suitable head to work on 3 Ph 50 Hz, 400 / 440 V with necessary unions, flanges, all accessories like valves, non return valve, pipes etc., complete. Duty :for Lower ground floor toilets a) 2.0 Lps @ 35 M head

1

-

-

... More
EXCAVATION FOR ALL PIPING WORKS Excavation in All Types of Soil for trenches by mechanical means including manual excavation for levelling, dressing the edges, with all leads and lifts, dewatering of surface water/ removal of slurry generated while excavation and keeping the area free of water with necessary shoring, required for keeping earth in position etc, Rate to include for backfilling with available earth, disposing of the excess earth and spreading in layers to the required levels within the site wherever specified and carting away excess earth & disposing off the same to be transported outside the site premises & dumped at approved dump yards by local authorities/statutory bodies, so that Client should not receive complaint from any local bodies/ Govt . agencies/ public in general . The rate to include loading, transporting, unloading/ dumping including the cost of mechanical transport/ labour etc complete as directed by EIC . Note: a) Working space & provision of slopes if required for execution shall be measured & paid, but not exceeding width stipulated in IS 1200. For External Seweage, External water supply, External rain water pipes From 0.0M to 1.5M

500

-

-

... More
WATER TREATMENT PLANT Supplying, installing, testing and commissioning approved make of centrifugal Monoblock pumps for Raw water Filter feed water inside the Pump room . The quoted rate shall include Automatic control panel with level switches, starters, dry run, O/L relays, single phasing preventer necessary copper armoured Cables up to the pumps and control panel, Internal control /power wiring will done by FRLS wire, potential free spare contacts for ON/OFF/TRIP status indication and remote ON/OFF with selector switch for Building Automation System, Starter should be Type-2 coordination, enclosure should be IP-52,Colour Siemens grey of RAL 7032, pumps shall run 3PH 50Hz 400/440 V electric supply, Butterfly valve, NRV etc . , complete . 1 no . working + 1 no . standby = 1 SET . Refer the techicnal specification for cable size, earthing etc. Filter feed pump 2 lps at 35M head (1 Working + 1 Standby = 1 set)

1

-

-

... More
Supplying, Installing, testing and commissioning submersible lift pump with IP - 68 enclosure of adequate HP, capable of giving a required discharge at suitable head to work on 3 Ph 50 Hz, 400 / 440 V AC supply fitted on a common base frame accessories to lift the pump during maintenance , control panel with wiring from TPN switch to control panel and to the pump and the control panel comprising of O/L relays, single phase preventor, separate overload trip and relayset, ON/OFF/TRIP indicating lamps, start/stop push buttons with necessary unions, flanges, all accessories like valves, non return valve, pipes etc will be measured under relevant item. etc., complete. Duty : from rain water sump to WTP a) 5 Lps at 35 M head

1

-

-

... More
Supplying, Installing, testing and commissioning approved make Multigrade/Pressure sand filter with necessary accessories complete for auto back wash along with Multiport Valve, suitable supports for mounting pressure gauges, orifice plates. The filter shall be made of FRP with necessary protective coating. The cost of filter shall also include initial charge of underbed & multi-grade filter media to suit the requirement etc., complete as per the standards. (Raw water and rain water tanks) a) Max. working pressure = 3.5kg/Sqcm b) Max flow rate = 5Cum / hr at 8 hrs. cycle

2

-

-

... More
Supplying, installing, testing and commissioning approved make Activated carbon filter in MS vessel construction with internals, electrical control system complete with Frontal piping, valves, suitable supports for mounting, pressure gauge, orifice plate etc.., complete as per the detailed specification for the efficient working of system. The maximum working Pressure shall be 3.5 Kg/Sqcm. a) Max. working pressure = 3.5kg/Sqcm b) Max flow rate = 5Cum / hr at 8 hrs. cycle

2

-

-

... More
Supplying, installing, testing and commissioning approved make Electronic dosing system for dosing Chlorine into the treated water with pre-set dosage based on the quantity of water. The dosing system shall consist of Electronic dosing pump with positive displacement type with adjustable stroke length & frequency. The quoted rate shall also include HDPE chemical solution tank necessary electricals etc., complete to make the operation automatic. Duty = 6.0 lph

2

-

-

... More
Supplying, installing, testing and commissioning inter unit .SH 80 piping with necessary flanges, bolts, nuts, neoprene gaskets, welding wherever necessary, with necessary control valves, non return valves etc. and with one coat of primer and two coats of approved enamel paint with IS recommended colour etc., complete.

1

-

-

... More
Control panel with plant wiring. Cost to include the automation of auto pump swapping, auto on/off based on level controllers, continuity in operation .

1

-

-

... More
Supply and charging of first fill of all chemicals and lubricants to commission and operate the plant. Chemicals for First three months operation - NaOCl, NaCl & NaOH are considered.

1

-

-

... More
Operation & Maintenance with own staff and consumable for a period of one year. (24/7 365 days)

12

-

-

... More
STP WORKS (SBR)STP, Capacity 45KLD works Design, Engineering, and providing all equipment /machinery at site, installation and commissioning of equipments/ electrical/ piping exclusive of all types of taxes and duties as described in specification. Note: Coordination for getting approval from Pollution Control Board at initial & various other stages of works including preparation of report / drawings as per Pollution Control Board requirement arrangement of final treated raw sewage water testing (Required consumables for testing in the scope of vendor) PART- I-ELECTROMECHANICAL EQUIPMENTS BAR SCREEN Supplying, installing, testing and commissioning of bar screen consisting of one set shall be provided in front of the intake works, so as to exclude the large size particles with associated set of guide angles in MS flat of 10.0mm screen kept inclined at 45 degree to the horizontal at 40mm c/c with one no. hand rack in GI. Bar rack fabricated from SS-304 bars to cover the width of the screen chamber with a racking arm for manual operation. Size : 1000 x 600 mm

1

-

-

... More
RAW SEWAGE TRANSFER PUMP (from EQT to PreAeration tank) Supplying, installing, testing and commissioning consisting of 2 Nos. (submersible type) Raw Effluent transfer pump with cutter version to pump sewage from equalisation sump to SBR tank at uniform flow rate. Dry run protection Industrial type electronic liquid level controllers with stainless steel probes / sensors or float switch for automatic operation. Alarm indication with signal in the event of pump failure etc., Pumps Type : Vertical Non-clog fully floodable submersible pump suitable to handle raw sewage having minimum 50mm to 75mm solid handling capacity Material of Construction (M.O.C): Corrosion Resistant in general Motor : ABB/KSB/ Grundfos / Armstrong /Approved Equivalent Pump: KSB/ Grundfos / Armstrong /Approved Equivalent Duty: (1 working + 1 standby) = 1 Set Discharge : 8 m3/hr. Head : 15M Accessories : coupling nylon ropes for pump lifting etc,. Complete

1

-

-

... More
COARSE BUBBLE DIFFUSER Supplying, installing, testing and commissioning of Coarse bubble diffuser with 80mm dia × 800mm long of uPVC pipe grid with necessary orifices uPVC pipe of 6.0 kg/sq cm pressure rating with removable deflector to provide clog-free oxygen for Equalization Tank , Sludge Holding Tank, collection sump, clarified water tank and Treated Water Tank. Make : Scogen / SSI/ EDI / Proflex / Approved Equivalent

4

-

-

... More
FINE BUBBLE DIFFUSER Supplying, installing, testing and commissioning, consisting fine bubble diffusers along with membrane from EDI, USA, set of EPDM membranes, SS-304 clips PVC support pipe (10 Kg pressure rating), PVC fitting, nylon rope braided hose with all accessories to make it retrievable & to provide clog-free oxygen for Sequencing batch reactor (SBR) Tank. Make : Scogen / SSI/ EDI / Proflex / Approved Equivalent Fine pore Diffusers 90dia x 1000mm long with membrane

10

-

-

... More
AIR BLOWER Supplying, installing, testing and commissioning of Twin Lobe design type air blower complete with motors, pulleys, Rigid one piece CI casing and side plates, silencer, base plate, Anti-friction bearings,. Rotary oil sealing having horizontal configuration approved make Twin lobe roots type Air Blower of adequate capacity at 0.50 Kg/sq cm capacity of required head comprising of common base frame, suction filter, suction silencer, non return, V belt, safety valve, belt guard, drive and driven pulleys, pressure gauge, inter connection piping, discharge silencer, anti vibration pads including required motor. Air Blower for Equalization tank, Decant Tank, Sludge Holding tank and treated water tanks Duty: 105 m3 /hr @ 0.45m (1 no. working + 1 no. stand by = 1set) for Equalization tank, sludge holding tank. Make : Kay International / Everest / Approved Equivalent

1

-

-

... More
SLUDGE TRANSFER PUMPS Supplying, installing, testing and commissioning of 2 nos (1 working + 1 stand by = 1 set) sludge disposal pumps to pump the sludge from aeration tank to sludge holding tank. The pump shall be submersible / horizontal centrifugal non-clog pumps with vetted parts in CI construction. The pump shall be coupled to the adequate H.P electrical motor, mounted on a common base frame. The rate quoted shall be inclusive of 1 no pressure gauge 4" dial with valve tee and fittings. Pumps: Monoblock self priming sewage pump with mechanical seal Material of Construction (M.O.C): Corrosion Resistant in general Make: Johnson / Lubi / KSB/Approved Equivalent make Duty: 1 working + 1 standby = 1 Set Discharge ( each pump) : 4 M3/hr. Head : 10M

1

-

-

... More
FILTER FEED PUMPS Supplying, installing, testing and commissioning of filter feed pump consisting of Monobloc type filter feed pumps to feed semi tested water to secondary treatment process through the filters. The pump shall be coupled to the adequate HP, electrical motor, mounted on a common base frame, 1 no pressure gauge 4" dial with valve tee and fittings. a) Pumps: Monoblock self priming pump with mechanical seal Material of Construction (M.O.C): Corrosion Resistant in general Make: Johnson / Kirloskar/Lubi / KSB/ Approved Equivalent Duty: 1 working + 1 standby = 1 Set Discharge ( each pump) : 3 M3/hr. Head : 35 M (max)

1

-

-

... More
CHLORINE DOSING SYSTEM Supplying, installing, testing and commissioning of on line automatic electronic sodium hypo dosing unit (Chlorine Dosing) with automatically operated dosing pump etc,. The unit shall comprise of the following: One no. Single moulded HDPE cylindrical type chemical solution tank of 100 litres capacity having detachable lids with moulded inserts for mounting of pump and stirrer Complete set of pipes, valves and fittings, foot valve magnetic float switch to trip the dosing pump at low level of chemical in the tank. Capacity :0 - 6lph Make : Ion exchange / Edose / Approved Equivalent

1

-

-

... More
Pressure Sand Filters Supplying, installing, testing and commissioning of vertical down flow type Pressure Sand filters for filtration faceted with FRP as per the manufactures specification. The filter shall be suitable for 6 cum/hr flow rate and designed to operate for 16 hours and handle sewage water. complete with pedestal, access cover, PVC underbid, 65 mm dia frontal piping with butterfly valve, sampling arrangement, pressure gauge, first charge of filter media. etc The SPF shall be designed for a specific velocity of 24cum/hr/sq.m. area and 1600mm dia. The filtration unit shall comply with the following technical requirements: Flow rate - 18.0 cum/hr Back wash duration - once in 16 hours for 20 min. Multiport Valve - 1.5 inch Painting internal - Two coats of bituminous paint Painting external - One coat of redoxide primer and above that finish paint Filtering Media - Multi grade of sand / Pebbles Dia of filter unit - 800mm x 1050 HOS Dia of filter unit - 800mm x 1050 HOS

1

-

-

... More
ACTIVATED CARBON FILTER Providing, installing, testing and commissioning vertical down flow type activated carbon filter for filtration with FRP as per the manufactures specification and removal of colour in treated sewage water. The filter shall be suitable for 6.0 cum/hr flow rate and designed to operate for 16 hours. complete with pedestal, access cover, PVC underbed, 65 mm dia frontal piping with butterfly valve, sampling arrangement, pressure gauge, first charge of filter media. etc The ACF shall be designed for a specific velocity of 24cum/hr/sq.m. area and the approach dia shall not be less than 1600mm dia. The filtration unit shall comply with the following technical requirements: Flow rate - 18.0 cum/hr Back wash duration - once in 16 hours for 20 min. Multiport Valve - 1.5 inch Painting internal - Two coats of bituminous paint Painting external - One coat of redoxide primer and above that finish paint Filtering Media - Activated Carbon Dia of filter unit - 800mm x 1050 HOS

1

-

-

... More
SOFTNER (if required) Providing, installing, testing and commissioning vertical down flow type softner for filtration with FRP as per the manufactures specification and removal of colour in treated sewage water. The filter shall be suitable for 6.0 cum/hr flow rate and designed to operate for 16 hours. complete with pedestal, access cover, PVC underbed, 65 mm dia frontal piping with butterfly valve, sampling arrangement, pressure gauge, first charge of filter media. etc The ACF shall be designed for a specific velocity of 24cum/hr/sq.m. area and the approach dia shall not be less than 1600mm dia. The filtration unit shall comply with the following technical requirements: Flow rate - 18.0 cum/hr Back wash duration - once in 16 hours for 20 min. Multiport Valve - 1.5 inch Painting internal - Two coats of bituminous paint Painting external - One coat of redoxide primer and above that finish paint Filtering Media - Softner Dia of filter unit - 800mm x 1050 HOS

1

-

-

... More
DECANTER MECHANISM Supply, fixing testing of PLC based decant valve for suitable dia with auto electrical operated with isolation (butterfly valve) at suitable time as required opening & closing automatically cost including all pipes with necessary fittings, electrical connection wiring etc. Complete. Make : Siemens / Stork / Approved Equivalent

2

-

-

... More
PLANT PIPING Plant Piping with UPVC Sch-40 pipes with Sch-80 fittings, supports & painting and approved make valves, gauges, instrumentation etc., for all plumbing lines and MS B Class pipeline with fittings for Blower Air Lines

1

-

-

... More
FILTER PRESS Supplying, fixing and commissioning of automatic hydraulic closing mechanism filter press suitable for handling sludge, cast iron body grade FG 20, suitable no. of polypropylene plate of size 450 mm X 450 mm etc., complete. Make: Hydropress / Lenntech / Approved Equivalent

1

-

-

... More
SCREW PUMP Supplying, installing, testing and commissioning of screw pumps with cutter version to pump sewage from sludge holding tank to filter press at uniform flow rate. the pump shall be coupled to the adequate HP. Electrical motor, mounted on a common base frame. Type : Helical screw pumps Make : Hydro Prokav Pumps / rotomac/approved equivalent Duty : 3.0 M3 per Hr. at 60M head.

1

-

-

... More
SIGHT GLASS TUBE (LEVEL INDICATOR) Supply, installation, testing and fixing of Sight glass tube / level indicator outside the tank. Sight glass tube with graduated wooden scale to indicate the level of liquid inside the tank, for 2 number treated water tank. Quoted rate shall include 2nos GM ball valve of 25mm dia, Level indicator scale on 100mm wide x 20mm thick teak wood board, 25mm dia heavy guage polyethiline tube.

2

-

-

... More
PART- II-ELECTRIAL EQUIPMENTS STP PANEL Supply, installation, testing and commissioning of front operated, front access, totally enclosed, free standing, dust and vermin proof Panel (Indoor type) with IP 54 ingress protection, fabricated from 2 mm thick CRCA sheets, with hinged, gasketted and lockable doors including the cost of interconnections, copper crimping lugs, brass glands, bonding to earth and painting, suitable for use at 415 volts, 3 phase 4 wire 50 Hz system with 16 KA rupturing capacity at 415 volts complete. Electrical Motor Control Centre shall be suitable for all equipments connected to the STP with 3 Nos of spare feeders

1

-

-

... More
LV CABLE, CABLE END TERMINATIONS Supply, laying, end termination, testing and commissioning of following sizes of 1100V Steel/Aluminium and Wire/Strip armoured, enamoured, sheathed Aluminium / Copper conductor cables of approved make. End termination of cables using brass type cable glands single / double compression with aluminium / copper lugs Note : a) Hydraulic crimping tool shall be used for making the end terminations. b) Single compression glands - up to 150 sq.mm. c) Double compression glands for sizes 150 sq.mm shall be used. d) Cable identification shall be made vide details furnished in single line viz., AYFY for PVC insulated, steel strip armoured, aluminium conductor cable and with PVC outer sheath. PVC Insulated Armoured COPPER conductor cables 4C x 6 Sq.mm - YFY

200

-

-

... More
Cable End Termination

12

-

-

... More
4C x 4 Sq.mm - YFY

50

-

-

... More
Cable End Termination

4

-

-

... More
3C x 6 Sq.mm - YFY

200

-

-

... More
Cable End Termination

12

-

-

... More
3C x 4 Sq.mm - YFY

200

-

-

... More
Cable End Termination

12

-

-

... More
EARTH ELECTRODES, EARTH CONNECTIVITY CONDUCTORS Supply, laying, testing and commissioning of following sizes of GI/Cu earth continuity conductor (strips/ stranded wires) for interconnection between the equipments to main earth strip within the STP Room. Corrosion protection for buried, Joints, conductors with bituminous coating and covered with PVC tapes etc all in conformity with the specifications as required, approved and directed. 25 x 3 mm Hot dip galvanised GI strips

60

-

-

... More
2R x 4 Sq.mm MSCC

100

-

-

... More
2R x 2.5 Sq.mm MSCC

225

-

-

... More
Busbar of 1.0 Mtr length made out of 25x6 mm GI strip with drill holes of M8 at 25mm interval mounted on insulators.

1

-

-

... More
Ladder type cable tray Quoted rate for installation shall include necessary supports, anchor fasteners and fixing for supporting the cable tray. Supports shall be powder coated with required colour Size of Cable Tray :300 mm x 50 mm Supply

50

-

-

... More
Installation.

50

-

-

... More
Size of Cable Tray :150 mm x 50 mm Supply

100

-

-

... More
Installation.

100

-

-

... More
Size of Cable Tray :100 mm x 50 mm Supply

300

-

-

... More
Installation.

300

-

-

... More
ELECTORNIC DIGITAL WATER LEVEL INDICATOR Water level indicator Supply, Installation testing and commissioning of Water Level Indicator with 1" Display to indicate the level of water in tanks listed below The unit will be housed at a location as directed by the Engineer incharge STP Equalization Tank , Treated Water Tank Make : ABB/Seagulll / Vinayaka / Approved Equivalent

2

-

-

... More
Level Sensor Cabling Supply, and laying of 6 core 0.5 sqmm copper flexible cable from UG Sump / Over Head tanks sensors to the level indicators. The cables shall be laid inside a PVC Conduit pipe of adequate size. The rate shall include SS Probes laid inside the tanks Make : ABB/Sunrich / Approved Equivalent

1000

-

-

... More
Metal Enclosure for Water level indicator Supply, installation, testing and commissioning of Metal Enclosure for Housing the level indicators with viewing glass and labling the tank names. The enclosure shall be of adequate size of house 4indicators in one housing. Make : ABB/Seagull / Approved Equivalent

1

-

-

... More
OPERATION AND MAINTATENANCE Installation, Commissioning and operating the system for one month with own staff and consumables (total for 30 days operation from the date of start commissioning) all required chemical to be supplied by the Contractor.

1

-

-

... More
STATUTORY APPROVAL Commissioning and obtaining the statutory approvals from the concerned authority

1

-

-

... More
FIRE PUMP ROOM EQUIPMENT: Supply, installation, testing & commissioning of electrical motor driven end suction top discharge pump capable of delivering 1620 LPM (97.2 m³/hr) at head of 60m for hydrant & sprinkler system (motor shall be of approx 37KW) running at minimum of 2900 rpm complete having tail piece for proper connection to suction & delivery line & having a name plate indicating suction / delivery, head, discharge, stage, r.p.m & direction of rotation with gland packing, coupling, coupling guard (zero access type), anti-vibration mounting pad, base plate, foundation bolts to suit above mentioned duty points. Pump shall be capable of furnishing not less than 150 % of rated capacity at a head of not less than 65% rated head. Shut off head shall not exceed 120% of rated head. Pump shall be coupled to squirrel cage induction motor, TEFC type with efficiency 1(IE2), IP55 protection with suitable speed as per technical specification. Complete set shall be mounted on common base frame for operation of 415 volts +/- 10%, 3 phase, 50 Hz +/- 5% A.C supply & of suitable H.P minimum for the pump running at 2900 r.p.m keeping in view above operating characteristics. Common base plate shall be manufactured out of M.S channel with suitable coupling & coupling guard for direct coupling of pump motor. RCC foundation for pumps shall be provided by civil contractor (as recommended by manufacturer). However, dimensions & load data shall be furnished by fire contractor.

1

-

-

... More
Supply, installation, testing & commissioning of horizontal end suction top discharge diesel engine driven common stand-by pump suitable for automatic operation consisting of following: Pump shall be capable of delivering 1620 LPM (97.2 m³/hr) at head of 60m running at minimum of 1800 rpm complete having tail for proper connection for suction/delivery, head, discharge, stage, r.p.m & direction of rotation with gland packing, coupling, coupling guard (zero access type) for direct coupling of engine & pump, anti-vibration mounting pad, base plate, foundation bolts to suit above mentioned duty points. Pump shall be coupled to an radiator cooled diesel engine of suitable BHP & speed as per technical specification. Set shall be provided with safety control panel, 2 nos of batteries of 12V-2nos 180 AH lead acid battery with boost/trickle charger for starting the engine automatically complete as required with battery leads & stand, battery charger panel, residential silencer, double walled diesel tank with necessary structural supports of capacity adequate for 6 hours operation & fitted with level gauge, level switch, nozzles, stand, diesel piping, valves to & from engine, tank & exhaust silencer (exhaust pipe shall be payable separately). Complete set shall be mounted on common base frame manufactured out of M.S. channel. RCC foundation for pumps shall be provided by civil contractor (as recommended by manufacturer). However, dimensions & load data shall be furnished by fire contractor.

1

-

-

... More
Supply, installation, testing & commissioning of electric motor driven vertical inline "JOCKEY PUMP" capable to deliver 180LPM (10.8m³/hr) @60MWC with mechanical seal, coupling, coupling guard (zero access type), anti-vibration pad, foundation bolt to suit above mentioned duty point. Pump shall have CI GG20 construction & impellers, diffusers, shaft sleeve, seal bush & pump shaft shall be in SS 304 material. It shall be coupled to squirrel cage induction motor, TEFC type of Efficiency 1(IE2), IP55 of suitable HP & speed as per technical specification. Complete set shall be mounted on common base frame for operation of 415 volts +/- 10%, 3 phase, 50 HZ +/- 5% A.C supply. RCC foundation for the pump shall be provided by client (as recommended by the manufacturer). However, dimensions & load data shall be furnished by contractor.

1

-

-

... More
Control Panel for Fire pumps. Detail design, manufacturing, supply, installation, testing, commisioning of 3 Phase, 4 wire, 415 V, 50 Hz panels. Fabrication shall be made with cold rolled annealed sheet with nachine pressing, surface shall be rigorously treated for derusting in 7 tank process with powder coating. Panel shall be totally enclosed metal clad type with double gasketting with rubber / foam gasketting. It shall be off- white painted inside & shall be having control directory pasted on inside surface of panel door. Panel shall be suitable for mounting on existing trench & shall have cable entry provision from top & bottom with suitable alley as case may be. Panel shall be tested for same KA rating of relevant highest rating of breaker. All components shall be of approved make & shall have relevant IS/IEC approvals (Fabrication, drawing, list of components & panel detail shall be got approved before fabrication). Panel shall include base frame channel support. All complete as per relevant standard, technical specification, SLD, data sheets & direction of Engineer-in-charge.

1

-

-

... More
1100 V GRADE POWER / CONTROL CABLES Supply, installation, testing & commissioning of FRLS, PVC outer sheathed, steel armoured, aluminium/copper conductor, 1100V grade power cables as per IS 1554/7098 part-I with glands etc. Cables shall be laid in trays / trenches / on walls / floor etc. as required. End termination of cables shall be using single compression brass type cable glands & pin type tinned copper lugs. For cables that are laid outdoor, rate shall include earth excavation providing brick & sand protection, refilling & compacting the earth. Cables shall be measured on the basis of linear measurements from gland to gland. Rate shall excludes cable tray & hume pipes. 3.5C x 95 sq.mm XLPE Aluminium cable for main pumps (hydrant & sprinkler).

30

-

-

... More
End terminations

2

-

-

... More
3C x 16 Sqmm XLPE Aluminium cable for jockey pumps.

30

-

-

... More
End terminations

2

-

-

... More
12C x 2.5 Sqmm copper cable for diesel engine.

30

-

-

... More
End terminations

2

-

-

... More
2C x 1.5 Sqmm copper armoured for instrumentation

80

-

-

... More
End terminations

6

-

-

... More
CABLE TRAY Supply & installation of perforated G.I sheet cable tray with necessary angle iron suspension supports, anchor fasteners etc. complete. Maximum height of suspension shall not exceed 800mm & thickness of the tray shall be 2mm. Size of tray shall be suitable for laying above mentioned cables. 50x300x50mm

20

-

-

... More
40x150x40mm

50

-

-

... More
40x100x40mm

20

-

-

... More
Supply & installation of G.I Earthling strips of 50mm x 6mm thick, strip shall be run on floor/ceiling/walls from the equipment to nearest earth pit with necessary accessories as required. (Earth pit shall be executed by other agencies). 50mm x 6mm thick

30

-

-

... More
Extention/end connection to earth terminals at motors/panels using single core, multi strand PVC insulated, copper conductor cables in suitable size PVC conduits.

50

-

-

... More
End termnation using copper lugs

6

-

-

... More
Supply, installation, testing & commissioning of above ground M.S "C" class ERW pipes confirming to IS: 3589 with a minimum wall thickness of 6.35mm with specials such as tees, elbows, flanges. Quoted rate shall be inclusive of cutting, welding, fixing in / on walls, ceiling by using suitable supports & painting on exposed M.S pipes with one coat of etching primer with two coats of synthetic enamel paint of approved colour / shade no. 536 as per IS: 5. Pipe fittings shall be MS confirming to IS: 1239 part-II or malleable iron fittings confirming to IS: 1879, part I to X such as reducers, tees, elbows, RF type flanges etc. Quoted rate shall also include for chasing / chipping walls / slabs & making them good with filler material & finished in cement mortar in the opening for pipes passing through walls, RCC floors, masonry walls as instructed by site engineer. Refer technical specification for detailed description. 200mm nominal dia

12

-

-

... More
Supply, installation, testing & commissioning of above ground "Galvanized (G.I)" ERW pipes confirming to IS: 1239 part-1, heavy grade "C" class pipes for sizes upto 150NB. Rate shall include cost of one coat of etching primer & two coats of synthetic enamel paint. Pipe fittings shall be GI confirming to IS: 1239 Part-II or malleable iron fittings confirming to IS: 1879, part I to X such as reducers, tees, elbows, RF type flanges etc. Including cutting, welding (with aersol spray on the welding), fixing on walls, ceiling or floor by using supports above 80 dia shall be MS supports, 65 dia and below shall be threaded rod with hanger supports etc, (supports for pipes shall be paid separately). Quoted rate shall also include for chasing / chipping walls & making them good with filler material & finished in cement mortar in the opening for pipes passing. Refer technical specification for detailed desrcription. 150mm nominal dia

60

-

-

... More
100mm nominal dia

24

-

-

... More
80mm nominal dia

6

-

-

... More
65mm nominal dia

6

-

-

... More
50mm nominal dia

18

-

-

... More
25mm nominal dia

24

-

-

... More
15mm nominal dia

12

-

-

... More
Supply, installation, testing & commissioning of C.I swing check type non-return valves suitable for horizontal/vertical installation with pressure rating of PN-10 with required matching flanges, nuts, bolts & gaskets etc. complete as per technical specification. 100 mm nominal dia

2

-

-

... More
65 mm nominal dia

1

-

-

... More
Supply, installation, testing & commissioning of Cast Iron wafer type butterfly valve (std lever operated type upto 150 mm dia. & gear operated type for 200 mm & above). Valves shall be confirming to BS 5155/ IS 13095 with pressure class of PN-10 having nylon coated CI disc, nitrile rubber seat complete with matching flanges, gaskets, galvanised fasteners. Valves shall be fitted with lockable steel strapping (pad lock) arrangement. 150mm nominal dia

4

-

-

... More
100mm nominal dia

2

-

-

... More
65mm nominal dia

1

-

-

... More
Supply, installation, testing & commissioning of C.I flanged end "Y-strainer" with SS strainer element/mesh of pressure rating (PN-10) with matching flanges, bolts, nuts, washer, gaskets etc.. as per technical specification 200mm nominal dia

2

-

-

... More
Supply, installation, testing & commissioning of C.I Gate/Sluice valve as per IS:14846 with pressure rating of PN-10 for suction side of pumps. Valves shall be of non-rising spindle type with matching flanges, bolts, nuts, washers, gaskets etc. Valves shall be fitted with lockable steel strapping (pad lock) arrangement. 200mm nominal dia

4

-

-

... More
150mm nominal dia

4

-

-

... More
80mm nominal dia

1

-

-

... More
Supply, installation, testing & commissioning of forged brass screwed ends full bore ball valves of pressure rating PN-16 complete with fittings of screwed end type etc.. Complete as per technical specification. 15mm dia.

8

-

-

... More
25 mm dia

4

-

-

... More
50 mm dia

2

-

-

... More
Supply, installation, testing & commissioning of bellow type pressure switch suitable range (0-16 Kg/cm²) as per pumps discharge pressure. Quoted rate shall include necessary fittings like unions / collars / reducers, siphon etc as required.

4

-

-

... More
Supply, installation, testing & commissioning of glycerine filled die cast aluminium body & SS 316 bourden type pressure gauge of 150mm dial size & calibration 0-16 kg/cm² with accuracy of 1% of full scale with necessary fittings like unions / nipples / collars / reducers, siphon etc as required.

4

-

-

... More
Supply, installation, testing & commissioning of Electro-magnetic type flow meter on test line to measure 150% of main pump flow. Size of flow meter shall be 150mm dia based on the pump discharge capacity.

1

-

-

... More
Supply, installation, testing & commissioning of Exhaust pipes from diesel engine - M.S pipe confirming to IS: 1239 part-1, medium grade (class-B) including long radius elbows, flanges, metallic expansion bellow as required. Rate shall include civil works as instructed by site engineer, 2 coat of heat resistant paint, rust proof, bituminous paint of approved colors to full height in stages of following sizes including rain hood at the top of exhaust pipe. Fixing shall be done with proper GI clamps, expansion bolts, support angle of size 40 x 25 x 3mm also painted, fixed on the wall / inside duct etc. Rate shall also include insulation material as required for 150 NB pipe x 50 mm thick mineral wool insulation (density 140 kg/cum) with 24 SWG aluminium sheet.

30

-

-

... More
Supply, installation, testing & commissioning of stainless steel (SS 304) metallic expansion bellows (PN 10) with control unit & matching flanges, gaskets, galvanised fasteners etc as required. 150mm nominal dia

2

-

-

... More
80mm nominal dia

1

-

-

... More
100mm nominal dia

2

-

-

... More
65mm nominal dia

1

-

-

... More
Supply, installation, testing & commissioning of 6mm thick M.S air cushion vessel of 300 dia x 1000mm long etc. complete with 25mm dia gunmetal air release valve automatic action spring loaded at 7 Kg/sq. cm, safety valve, pressure gauge etc,. complete as per technical specification.

1

-

-

... More
Supply, installation, testing & commissioning of 300mm x 300mm x 10mm thick (SS) stainless steel fabricated vortex plate, suction lift type made with non corrosive material, conforming to BS 4504 with all accessories etc complete.

2

-

-

... More
HYDRANT SYSTEM: Supply, installation, testing & commissioning of above ground "galvanized (G.I)" ERW pipes confirming to IS: 1239 part-1, heavy grade "C" class pipes for sizes upto 150NB & MS pipes confirming to IS: 3589 Gr. Fe 330 with a minimum wall thickness of 6.35mm for sizes 200 NB & above. Rate shall include cost of one coat of etching primer & two coats of synthetic enamel paint. Pipe fittings shall be GI confirming to IS: 1239 Part-II or malleable iron fittings confirming to IS: 1879, part I to X such as reducers, tees, elbows, RF type flanges etc. Quoted rate shall include cutting, welding (with aersol spray on the welding), fixing on walls, ceiling or floor by using suitable supports. And pipe supports above 80 dia shall be MS supports, 65 dia and below shall be threaded rod with hanger supports etc, (supports for pipes shall be paid separately). Quoted rate shall also include for chasing / chipping walls / slabs & making them good with filler material & finished in cement mortar in the opening for pipes passing through walls, RCC floors, masonry walls as instructed by site engineer. 150mm nominal dia

100

-

-

... More
100mm nominal dia

250

-

-

... More
80mm nominal dia

30

-

-

... More
25mm nominal dia

40

-

-

... More
Supply, installation, testing & commissioning of under ground "galvanized (G.I)" ERW pipes confirming to IS: 1239 part-1, heavy grade "C" class pipes for sizes upto 150NB & MS pipes confirming to IS: 3589 Gr. Fe 330 with a minimum wall thickness of 6.35mm for sizes 200 NB & above. Pipe fittings shall be GI confirming to IS: 1239 Part-II or malleable iron fittings confirming to IS: 1879, part I to X such as reducers, tees, elbows, RF type flanges etc. Including cutting, welding (with aersol spray on the welding), fixing by using suitable supports such as channels/angles, threaded rod, U-clamps, hangers, anchor fasteners, bolt-nuts etc as per technical specification (supports for pipes shall be paid separately). Quoted rate shall also include for chasing / chipping walls / slabs & making them good with filler material & finished in cement mortar in the opening for pipes passing through masonry walls as instructed by site engineer. Note: Holiday test to be carried out for underground piping and quoted rate of pipe shall include same. 150mm nominal dia

290

-

-

... More
100mm nominal dia

20

-

-

... More
80mm nominal dia

30

-

-

... More
Supply, installation, testing & commissioning of anticorrosive material for buried pipes with coating of primer & wrapping with 4 mm thick polymer corrosion resistant tape as per IS:10221 with 15mm overlapp as per specifications etc.. complete.

200

-

-

... More
Supply, installation, testing & commissioning of Cast Iron wafer type butterfly valve (std lever operated type upto 150 mm dia. & gear operated type for 200 mm & above). Valves shall be confirming to BS 5155/ IS 13095 with pressure class of PN-10 having nylon coated CI disc, nitrile rubber seat complete with matching flanges, gaskets, galvanised fasteners. Valves shall be fitted with lockable steel strapping (pad lock) arrangement. 150mm nominal dia

5

-

-

... More
100mm nominal dia

10

-

-

... More
80mm nominal dia

4

-

-

... More
Supply, installation, testing & commissioning of C.I swing check type non-return valves suitable for horizontal/vertical installation with pressure rating of PN-10 with required matching flanges, nuts, bolts & gaskets etc. complete as per technical specification. 100mm nominal dia

1

-

-

... More
Supply, installation, testing & commissioning of C.I flanged end "Y-strainer" with SS strainer element/mesh of pressure rating (PN-10) with matching flanges, bolts, nuts, washer, gaskets etc.. as per technical specification. 100 mm nominal dia

1

-

-

... More
Supply, installation, testing & commissioning of landing hydrants comprising of following accessories. Single headed hydrant valve as per IS: 5290 Type-A, made of stainless steel (SS) with 63mm dia instantaneous out lets & 80mm dia flanged inlet, blank caps, chain & hand wheels etc complete.

16

-

-

... More
2nos of 15m long, 63mm dia RRL hose with stainless steel instantaneous couplings stored inside hose cabinet with bracket &required accessories.

16

-

-

... More
1 no. Stainless steel short branch pipe with nozzle.

16

-

-

... More
Fixed type hose reel drum with 19mm dia rubber braided hose of 40m. length with gate valve (upstream) & dual type discharge nozzle, complete.

16

-

-

... More
Fire duct Shutter fabricated out of MS sheet & frame of 16 SWG CRCA with 2 doors & 4 mm thick glazed glass with water proof beading. Door shall be of size 900mm x 1200/1500mm min. with suitable rubber beeding & locking arrangement. Quoted rate shall be includes all fasteners etc, and complete shutter shall be powder coated of approved colour both inside with white and red out side.

16

-

-

... More
Supply, installation, testing & commissioning of yard hydrants comprising of following accessories. Single headed hydrant valve as per IS 5290 Type-A, made of stainless steel (SS) with 63mm dia instantaneous out lets & 80mm dia flanged inlet, blank caps, chain & hand wheels etc complete.

4

-

-

... More
2 nos of 15m long, 63mm dia RRL hose with stainless steel instanteneous couplings stored inside hose cabinet.

4

-

-

... More
1 no. Stainless steel short branch pipe with nozzle.

4

-

-

... More
Supply, installation, testing & commissioning of weather proof outdoor lockable hose cabinet made of 16 SWG CRCA MS Sheet with 2 doors & 4 mm thick glazed glass with water proof rubber beading. It shall be painted in red out side & white inside with two coats of enamel paint over a coat of primer. "HOSE CABINET NO." shall be painted on the inner face of glass in 50 mm size block letter. Cost shall include rate of break glass box containing key of the cabinet. Cabinet size shall be of 750mm x 600mm x 250mm wall/column mounted type with necessary supports as required.

4

-

-

... More
Supply, installation, testing & commissioning of 4 way fire brigade inlet inlet connection with 63mm dia built-in gun metal non-return valves instantaneous coupling type arranged on 150mm dia. Pipe manifold & connected to wet riser main as well as to fire water tank. Quoted rate shall be included with C.I butterfly valve & MS cabinet of suitable size with mounting supports etc. complete.

1

-

-

... More
Supply, installation, testing & commissioning of 2 way fire brigade inlet inlet connection with 63mm dia built-in gun metal/SS non-return valves instantaneous coupling type arranged on 100 mm dia. Pipe connected to yard hydrant main & fire water tank.Quoted rate shall be included with C.I. butterfly valve, enclosure or boxing for FBI with mounting supports etc. complete

1

-

-

... More
Supply, installation, testing & commissioning of forged brass screwed ends full bore ball valves of pressure rating PN-16 complete with fittings of screwed end type etc. complete as per technical specification. 25mm dia.

3

-

-

... More
Supply, installation, testing & commissioning of single ball type forged brass air release valve (screwed ends) with unions, collars, nipple, siphon etc. complete. Pressure rating of air release valve shall be PN-16.

3

-

-

... More
Supply, installation of valve chamber for the underground isolation valves, with chamber size 1m x 1m x 1.5m. Quoted rate shall be for construction of valve chambers only.

5

-

-

... More
Excavation of trenches up to 1.5mts. in depth, for laying pipes up to 150 / 100 / 80mm dia. Including forming bottom surface to required level, backfilling the trenches with selected excavated earth around the pipe in layers of 150mm thick, watering, consolidating. Quoted price inclusive of disposing off / Carting away the surplus earth out side the site to a dump yard acceptable local bodies or as directed by the site engineer with a lead of 300mts. etc. complete. Excavation in all kinds of soil

160

-

-

... More
Supplying & installing of RCC hume pipes of 300mm dia & NP-2 class with collars for road / below floor crossing of fire water pipes. Rate shall include excavation, backfilling, PCC (1:4:8 100 mm thick) bed and ends shall be closed with Brick masonry work as directed by site engineer. 300mm dia.

80

-

-

... More
Supply & construction of PCC (1:2:4) pedastals/supports for under ground/above ground pipes. Quoted rate shall be inclusive of excavation (if required), chipping/chasing, shuttering, plastering etc. Complete

12

-

-

... More
Sealing of fire shafts at all floor levels by using M.S. angle (40 x40) Iron frame around the shaft M.S. chequered plate of 6mm thick on the plate for whole shaft area as per drawings and engineer - in - charge.

500

-

-

... More
Sealing of shaft openings with expanding firestop foam catridges (CP-636) for pipes, cables & conduits crossing in walls by using fire retardant sealant, with expansion upto 7 times, repenetrable to protect against fire, smoke & water complete with dispenser, mixer & cleaner.

12

-

-

... More
AUTOMATIC SPRINKLER SYSTEM: Supply, installation, testing & commissioning of above ground "galvanized (G.I)" ERW pipes confirming to IS: 1239 part-1, heavy grade "C" class pipes for sizes upto 150NB & M.S pipes confirming to IS: 3589 Gr. Fe-330 with a minimum wall thickness of 6.35mm for sizes 200NB & above. Rate shall include cost of one coat of etching primer & two coats of synthetic enamel paint (min total DFT 100 micron). Pipe fittings shall be forged threaded type for sizes up to 50 NB & butt welded fittings confirming to ASTM A234 Gr. WPB for sizes 65NB & above. Rate shall include cutting, welding (with aersol spray on the welding), fixing on walls, ceiling or floor by using suitable supports, as per technical specification (supports for pipes shall be paid separately). Quoted rate shall also include for chasing / chipping walls & making them good with filler material & finished in cement mortar in the opening for pipes passing through walls, floors, masonry walls as instructed by site engineer. 150mm nominal dia

50

-

-

... More
100mm nominal dia

520

-

-

... More
80mm nominal dia

390

-

-

... More
65mm nominal dia

335

-

-

... More
50mm nominal dia

465

-

-

... More
40mm nominal dia

390

-

-

... More
32mm nominal dia

220

-

-

... More
25mm nominal dia

2500

-

-

... More
Supply, installation, testing & commissioning of under ground "galvanized (G.I)" ERW pipes confirming to IS: 1239 part-1, heavy grade "C" class pipes for sizes upto 150NB & MS pipes confirming to IS: 3589 Gr. Fe-330 with a minimum wall thickness of 6.35mm for sizes 200 NB & above. Pipe fittings shall be GI confirming to IS: 1239 Part-II or malleable iron fittings confirming to IS: 1879, part I to X such as reducers, tees, elbows, RF type flanges etc. Including cutting, welding, fixing by using suitable supports such as channels/angles, threaded rod, U-clamps, hangers, anchor fasteners, bolt-nuts etc as per technical specification (supports for pipes shall be paid separately). Quoted rate shall also include for chasing / chipping walls / slabs & making them good with filler material & finished in cement mortar in the opening for pipes passing through masonry walls as instructed by site engineer. Note: Holiday test to be carried out for underground piping and quoted rate shall include the same. 100mm nominal dia

85

-

-

... More
Supply, installation, testing & commissioning of anticorrosive material for buried pipes with coating of primer & wrapping with 4 mm thick polymer corrosion resistant tape as per IS:10221 with 15mm overlapp as per specifications etc.. complete.

35

-

-

... More
Supply, installation, testing & commissioning of forged brass screwed ends full bore ball valves of pressure rating PN-16 complete with fittings of screwed end type etc.. Complete as per technical specification. 25mm dia

3

-

-

... More
Supply, installation testing & commissioning of Inspectors test & drain valve with sight glass assembly of 50mm dia. With suitable orifices & necessary fittings for fixing as per drawing & specifications. (Brass or Cast Iro 50mm dia

12

-

-

... More
Supply, installation, testing & commissioning of Cast Iron wafer type butterfly valve (std lever operated type upto 150 mm dia). Valves shall be confirming to BS 5155 / IS 13095 with pressure rating of PN-16 having nylon coated CI disc, nitrile rubber seat complete with matching flanges, gaskets & galvanised fasteners. Valves shall be fitted with lockable steel strapping (pad lock) arrangement. 100 mm nominal dia

3

-

-

... More
Supply, installation, testing & commissioning of Cast Iron wafer type butterfly valve (std lever operated type upto 150 mm dia. & gear operated type for 200 mm & above). Valves shall be confirming to BS 5155/ IS 13095 with pressure class of PN-16 having nylon coated CI disc, nitrile rubber seat complete with matching flanges, gaskets, galvanised fasteners. Valves shall be fitted with supervisory / tamper switch for monitoring. 100mm dia

12

-

-

... More
Supply, installation, testing & commissioning of Conventional std coverage std response quartzoid bulb type sprinkler with 15mm screwed end connection of 68 deg. C temperature rating, K-factor of 80 & orifice shall not be less than 6mm. Sprinklers shall be UL Listed & FM approved. Color / finish of the plate shall be as approved by client / architect. Pendent sprinkler

700

-

-

... More
Upright sprinkler

430

-

-

... More
Supply, installation, testing & commissioning of Conventional std coverage std response quartzoid bulb type sprinkler with 15mm screwed end connection of 79 deg. C temperature rating, K-factor of 80 & orifice shall not be less than 6mm. Color / finish of the plate shall be as approved by client / architect (for pantry). Pendent sprinkler

15

-

-

... More
Supply, installation, testing & commissioning of conventional std coverage Quick response quartzoid bulb type sprinkler with 15mm screwed end connection of 68°C temperature rating, K-80 sprinkler K-factor & orifice shall not be less than 6mm. Color/finish of plate shall be as approved by client. Pendent sprinkler

20

-

-

... More
Supply, installation, testing & commissioning of vane type flow switch on sprinkler distribution header on each floor & shall be connected to fire alarm panel through cable. Cable shall be measured separately. 100mm dia

12

-

-

... More
Supply, installation, testing & commissioning of carbon steel material rosette plates (recessed type in two piece for false ceiling areas) for sprinklers below false ceiling area & finish shall be powder coated as required complete as per technical specification. Color / finish of the plate shall be as approved by client / architect.

665

-

-

... More
Supply, installation, testing & commissioning of stainless steel braided flexible drop (hose) for droping sprinklers below false ceiling. Sprinkler drop shall be of 12 bar pressure rating along with 2 slip nuts, sprinkler reducer, light weight ceiling bracket component etc. as required complete as per technical specification. 1500mm length of flexible drop.

320

-

-

... More
Supply, installation, testing & commissioning of hydraulically operated Installation control valve with water motor gong bell & constant pressure trim consisting of pressure gauges, drain valves, ball valves, check valves etc. complete. Upstream valve shall be paid separately. 150mm dia

2

-

-

... More
Supply, installation, testing & commissioning of single ball type forged brass air release valve (screwed ends) with unions, collars, nipple, siphon etc. complete. Pressure rating of air release valve shall be PN-16. 25mm dia

3

-

-

... More
Supply, installation, testing & commissioning of glycerine filled die cast aluminium body & SS 316 bourden type pressure gauge of 150mm dial size & calibration 0-16 kg/cm² with accuracy of 1% of full scale with necessary fittings like unions / nipples / collars / reducers, siphon etc as required.

12

-

-

... More
Supply, installation, testing & commissioning of PVC insulated, PVC sheathed armored FRLS 2C x 1.5 sq.mm copper (fire retardant low smoke) cable as per IS: 1554 part-I. Cable shall be rated for a voltage rating of 650/1100 Volts & insulated with suitably compounded PVC. Cables shall be properly supported to ceiling through suitable clamps/saddles at an interval of 300mm. Cables shall be measured on the basis of linear measurements from gland to gland. Colour code FA cable shall be "RED".

450

-

-

... More
Supply, installation, testing of spinkler pipe supports (In deck slab area) Hexagonal nut, DIN 934, M10, galvanised

9500

-

-

... More
Hexagonal nut, DIN 934, M12, galvanised

85

-

-

... More
Threaded rod, M10, 2.000 mm, galvanised

840

-

-

... More
Threaded rod, M12, 2.000 mm, galvanised

5

-

-

... More
MPC-Rail nut M10, 33 x 23 x 6 mm for MPC-Support channels 38/24-40/120, galvanised

5500

-

-

... More
MPC-Rail nut M12, 33 x 23 x 6 mm for MPC-Support channels 38/24-40/120, galvanised

85

-

-

... More
Washer, 10,5 x 36 x 2 mm, galvanised

7850

-

-

... More
Washer, DIN 125, M10, galvanised

2200

-

-

... More
Washer, DIN 125, M12, galvanised

85

-

-

... More
MPC-Support channel 38/24, length: 2.000 mm, galvanised

370

-

-

... More
Swivel hanger, MSS SP-58 & SP-69 Type 10, M10, 1", galvanized

1300

-

-

... More
Swivel hanger, MSS SP-58 & SP-69 Type 10, M10, 1 1/2", galvanized

240

-

-

... More
Swivel hanger, MSS SP-58 & SP-69 Type 10, M10, 1 1/4", galvanized

220

-

-

... More
Swivel hanger, MSS SP-58 & SP-69 Type 10, M10, 2", galvanized

260

-

-

... More
Swivel hanger, MSS SP-58 & SP-69 Type 10, M10, 2 1/2", galvanized

300

-

-

... More
Swivel hanger, MSS SP-58 & SP-69 Type 10, M10, 3", galvanized

220

-

-

... More
Swivel hanger, MSS SP-58 & SP-69 Type 10, M10, 4", galvanized

260

-

-

... More
Swivel hanger, MSS SP-58 & SP-69 Type 10, M12, 6", galvanized

20

-

-

... More
Hexagonal nut, DIN 934, M12, galvanised

85

-

-

... More
MPC-Protection cap for MPC-Support channel profile 38/24 and 38/48

85

-

-

... More
Threaded rod, M12, 2.000 mm, galvanised

2

-

-

... More
MPC-Rail nut M12, 33 x 23 x 6 mm for MPC-Support channels 38/24-40/120, galvanised

85

-

-

... More
Washer, 12,5 x 36 x 2 mm, galvanised

85

-

-

... More
Steel anchor, M12 x 50 mm, galvanised

45

-

-

... More
STATO® Bracket, standard version, galvanised

5

-

-

... More
Through anchor, ST 10-20, galvanised

45

-

-

... More
MPC-Support channel 38/24, length: 2.000 mm, galvanised

3

-

-

... More
Washer, 10,5 x 30 x 3 mm, galvanised

85

-

-

... More
Single bossed clamp DÄMMGULAST® yellow, M10/M12, 2" (60-66 mm), galvanised

10

-

-

... More
Single bossed clamp DÄMMGULAST® yellow, M10/M12, 4" (112-118 mm), galvanised

1

-

-

... More
Single bossed clamp DÄMMGULAST® yellow, M10/M12, 6" (164-169 mm), galvanised

20

-

-

... More
BZ Heavy-duty anchor, M10. clamping range 10 mm or 30 mm, galvanised

45

-

-

... More
STATO® Clamp without lining (anchor point clamp), 6" (168.3 mm), galvanised

10

-

-

... More
Supply, installation, testing of spinkler pipe supports (In RCC with flat slab area) such as channels/angles, threaded rod, U-clamps, hangers, anchor fasteners, bolt-nuts etc as per technical specification. Quoted rate shall also include the same.

2500

-

-

... More
INTEGRATED ADDRESSABLE FIRE DETECTION & ALARM SYSTEM: Supply, installation, testing & commssioning of main fire alarm panel with fire fighter telephone (Digital voice command centre) & audio source unit(FACP). Panel shall have built-in battery with back up for 24 hours normal operation & 60 minutes alarm operation. Control panel, battery charger etc, shall be UL listed. Panel shall be of 07 loops capacity with provision of extension upto two additional loops. It shall include a full featured operator interface control & annunciation panel that shall include a backlit 640-character liquid crystal display, individual color coded system status LEDs & alphanumeric keypad for field programming & control of fire alarm system. Panel shall be capable of expansion via up to 10 SLC modules. Each module shall support a maximum of 250 addressable devices per loop with a combination of 125 detectors & 125 devices for a maximum system capacity of 2500 points. Panel shall be UL listed, FM approved & comply to UL 864, 9th edition requirement. Quoted rate shall include supply of necessary software & hardware for progamming panel with all necessary licence. Integration of FACP with BMS system shall be BACnet over IP or RS-485 Modbus protocol as suitable & rate quoted shall be inclusive of of necessary port/card required for integration. 07 Loops

1

-

-

... More
Supply, installation, testing & commssioning of Active repeater panel with 120/ 640 character LCD for monitoring fire alarm system @ museum floor reception desk. Panel shall be UL approved. Quoted rate shall include necessary battery for panel suitable for 24 hours of operation.

1

-

-

... More
Supply, installation, testing & commissioning of graphic software for programming (mapping) fire detection & alarm system through FACP or remote computers. Software shall be with facility like upload / down load of information's to FACP, graphics compatible to AutoCAD, detectors information with change in address / sensitivity etc as required. System shall meet the requirements as described vide technical specifications.

1

-

-

... More
Supply, installation, testing & commissioning of multisensor detector, programmable for timed automatic sensitivity selection with base & other accessories as mentioned vide technical specification. (true ceiling detectors)

360

-

-

... More
Supply, installation, testing & commissioning of multisensor detector, programmable for timed automatic sensitivity selection with base & other accessories as mentioned vide technical specification. (@false ceiling)

130

-

-

... More
Supply, installation, testing & commissioning of rate of rise heat detector, programmable for timed automatic sensitivity selection with detector base & other accessories as mentioned vide technical specification. (@false ceiling)

5

-

-

... More
Supply, installation, testing & commissioning of fault isolator module capable of monitoring shorted loop circuit & automatically restore communications when shorted conditions are corrected.

35

-

-

... More
Supply, installation, testing & commssioning of supervised monitor module monitoring potential-free, normally open dry contact input (providing DPDTcontact rated at 24v DC, 2A). Quoted rate shall be with the necessary back-box for mounting. (for flow switch, panic bar & tamper switch)

32

-

-

... More
Supply, installation, testing & commssioning of potential-free, SPDT contact based control module for notification activation. Quoted rate shall be with the necessary back-box for mounting. (for hooter/strobe)

20

-

-

... More
Supply, installation, testing & commssioning of potential-free, SPDT contact based control relay module to trigger 3rd party utilities like AHU shut-off, pressurization fan activation, lift grounding, electrical power supply shutdown, de-activation of access control doors, smoke extractor fans etc. Quoted rate shall be with the necessary back-box for mounting.

210

-

-

... More
Supply, installation, testing & commissioning of hooter cum flasher/strobe at 85 dBA @ 3m for Audible annunciation & 75cd flashing at 1Hz for visual indication. Hooter cum strobe shall be flush or surface mountable type with all accessories etc., complete as per technical specification.

20

-

-

... More
Supply, installation, testing & commissioning of addressable double action type manual pull station with all accessories etc., complete as per technical specification.

24

-

-

... More
Supply, installation, testing & commissioning of PVC insulated, PVC sheathed armored FRLS 2C x 1.5 sq.mm copper cable confirming to IS: 1554 part-I. Cable shall be rated for a voltage rating of 650/1100 Volts & insulated with suitably compounded PVC. Cables shall be properly supported to ceiling through suitable clamps/saddles at an interval of 300mm. Cables shall be measured on the basis of linear measurements from gland to gland. Colour code FA cable shall be "RED".

11000

-

-

... More
CABLE TRAY Supply & fixing of perforated G.I. sheet cable tray with neccessory angle iron suspension supports, anchor fasteners etc. complete. Maximum height of suspension shall not exceed 500 mm. Size of the tray is 50mm x 200mm x 50mm & 2mm thick.

350

-

-

... More
Supply, installation, testing & commissioning of MS junction box made of 16SWG CRCA sheet of suitable size to mount detector base evenly on it. It shall be duly painted with 2 coats of red oxide & 2 coats of enamel paint, each side cable knot of 19mm dia for cable termination.

500

-

-

... More
End termination of above cable to junction boxes using single compression brass type cable glands & pin type tinned copper lugs.

500

-

-

... More
Supply & fixing of fire command center (PC) with installation of graphic software & printer along with necessary softwares, intel core i7/i5 processer, 4 GB ram, windows 7 O.S, 500 GB hard disc, vide specification.

1

-

-

... More
Supply, installation, testing & commissioning of FRLS PVC Conduits of 2mm thick on ceiling / wall / floor etc. complete with accessories like, junction boxes, collars, bends etc 25 mm dia.

500

-

-

... More
Supply, installation, testing & commissioning of digital class-D audio amplifier designed for audio networks terminating at a DVC (digital voice command). Capacity & number of amplifiers shall be to cater 4 zones & number of speakers connected to each zone. Refer schematics for zone distribution. Each amplifier shall be housed inside rack along with necessary control wires, jacks etc complete as per technical specification. 75/100 watts

11

-

-

... More
Supply, installation, testing & commissioning of Rack assembly made of aluminium channels side & rear panels made of 16 SWG powder coated steel sheet front transparent persplex door bearing with rails & rollers, 2 fans at top for ventilation. Ventelted type side panels powder coated Suitable for mounting amplifiers, system controller & all accessories vide technical specification. Size of rack shall be 42U.

1

-

-

... More
Supply, installation, testing & commissioning of 2W ceiling recess / surface mounted speakers with optional 0.5-2W tapping with mounting clamp & supports complete in all respect as per technical specification & drawings.

395

-

-

... More
Supply, installation, testing & commissioning of 2W wall mounted speakers with optional 0.5-2W tapping with mounting clamp & supports complete in all respect as per technical specification & drawings.

6

-

-

... More
Supplying, installing, testing & commissioning of PVC insulated Armored FRLS 2C x 1.5 sq.mm copper cable with Accessories confirming to IS standards and specifications. The quoted rate shall includes closure of the opening for cables passing through fire compartment walls of RCC floors, masonry walls to provide up to 2 hours fire rating. Colour code for PA cable shall be "BLACK".

8000

-

-

... More
Supply, installation, testing & commissioning of BGM source FM tuner with necessary components like AC power cord, safety instructions, set of mounting brackets, remote control, 2-pair audio RCA cable (2.5m) & SD card including free music & instructions for use etc. vide technical specification.

1

-

-

... More
Supply & installation of MS back box of suitable size for 2W ceiling/surface mounted speakers with necessary glands, collars etc.. Complete for termination of cables into the speakers.

215

-

-

... More
TWO-WAY COMMUNICATION SYSTEM Supply, installation, testing & commissioning of 40 zone fire telephone control panel, networkable up to 8 panels, fully monitored, 24VDC powered that communicates with the field terminals like telephone jack, hands free speaker etc. complete with battery back up with all necessary accessories vide technical specification. Quoted rate shall include necessary supports, fittings to complete the installation & make system workable.

1

-

-

... More
Supply, installation, testing & commissioning of 6W wall mounted type handsfree speakers with talk back facility (Two way, Push to talk), in CRCA sheet fabricated housing, complete.

20

-

-

... More
Supply, installation, testing & commissioning of PVC insulated, PVC sheathed armoured FRLS 2C x 1.0 sq.mm copper cable as per IS: 1554 part-I. Cable shall be rated for a voltage rating of 650/1100 Volts & insulated with suitably compounded PVC. Cables shall be properly supported to ceiling through suitable clamps/saddles at an interval of 300mm. Cables shall be measured on the basis of linear measurements from gland to gland. Colour code PA cable shall be "GRAY/WHITE".

4500

-

-

... More
Supply, installation, testing & commissioning of FRLS PVC Conduits of 2mm thick on ceiling / wall / floor etc. complete with accessories like, junction boxes, collars, bends etc 25 mm dia.

550

-

-

... More
FIRE EXTINGUISHERS: Supply, installation, testing & commissioning of Portable Fire extinguishers of following type & capacity. ABC stored pressure type fire extinguisher of capacity 06 kgs bearing ISI mark for fighting ABC class of fire. Extinguisher shall be manufactured strictly as per IS: 15683. Quoted rate shall include necessary supports suitable for wall mounting with sutable hooks or floor mounted 3/4 leg MS stand (Area of usage: office areas)

60

-

-

... More
ABC stored pressure type fire extinguisher of capacity 02 kgs bearing ISI mark for fighting ABC class of fire. Extinguisher shall be manufactured strictly as per IS: 15683. Quoted rate shall include necessary supports suitable for wall mounting with sutable hooks or floor mounted 3/4 leg MS stand (Area of usage: Pantry & lift lobby)

10

-

-

... More
Carbon-di-oxide stored pressure type fire extinguisher of 4.5 Kgs capacity, CO2 gas filled in brand new seamless cylinder with powder coated finish, made out of Manganese steel, with wheel type valve, discharge Nozzle, bend & horn, wall mounting bracket /floor trolley mounting accessories with suitable signage's complete, confirming to IS: 15683. Quoted rate shall include necessary supports suitable for wall mounting with sutable hooks or floor mounted 3/4 leg MS stand (Area of usage: Electrical room & panel rooms).

15

-

-

... More
Mechanical Foam type fire extinguisher 9Lts capacity, with initial filling in brand new cylinder with powder coated finish, fitted with gun metal union, hose and ABS type branch pipe & wall mounting bracket/floor trolley mounting accessories with suitable signage's complete , confirming to IS: 15683. (Area of usage: Near the trasformer & diesel generator). Quoted rate shall include necessary supports suitable for wall mounting with sutable hooks or floor mounted 3/4 leg MS stand

4

-

-

... More
Modular counted type clean agent automatic fire extinguisher of capacity 15 kgs fitted with an automatic sprinkler valve & that shall be calibrated to discharge at an ambient temperature of 68°C. Extinguisher shall be manufactured strictly as per IS standards. Quoted rate shall include necessary supports suitable for ceiling mounting. (Area of usage: wet labs (chemical lab) & critical rooms such as UPS/battery room.)

35

-

-

... More
2nos of Fire buckets (filled with sand) round bottom type enamel painted, white inside & red out side, Letter "FIRE" in black out side & handle with mounting bracket.

10

-

-

... More
Fire bucket stand fabricated by MS angles to install 2 no's of buckets.

10

-

-

... More
SIGNAGES: Providing & installing in position the following type of sign boards made out of 3.0mm thick rigid PVC board with computer cut with texts written to recommended height in photolumiscent material complete vide technical specifications with mirror fasteners. Sizes & mounting height of the board shall be as per technical specification. Signage with printed "IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED OTHERWISE" of 1.5cm height letters in red with white back ground. Size of the board shall be 25cm x 30 cm & shall be fixed at height of 2 mts. from finished floor near Manual call points.

18

-

-

... More
Floor identification signage (ie, GROUND, 1st FLOOR etc..) at each stair enclosure on every floor, indicating floor number in words, lettering size shall be 7.5 cm with contrasting colour from back ground. Size shall be 15cm x 60cm.

18

-

-

... More
ALERT SECURITY AT SECURITY ROOM BY ACTUATING MANUAL CALL POINT LOCATED AT STRATEGIC LOCATIONS.

5

-

-

... More
ACTION BY SECURITY/RECEPTION UPON RECEIPT OF INFORMATION THROUGH FIRE ALARM OR FIRE DETECTORS OR BY USING PUBLIC ADDRESS SYSTEM.

5

-

-

... More
Fire extinguisher signage's.

89

-

-

... More
Manual call point (MCP) signage's.

20

-

-

... More
Fire hose reel drum signage's.

18

-

-

... More
Providing & installing in position the fire safety plan to a recommended scale & at suggested locations. Safety plan shall be with acrylic sheet & 6nos of SS studs for "A2" size.

45

-

-

... More
Photo luminescent type fire exit signage’s with image & supplementary text. (Size = 150mm x 400mm). Text on the signage's shall be double sided. Quoted rate shall include necessary chain hanger for hanging the signage's from false ceiling.

65

-

-

... More
Providing & installing in position the self contained (battery operated) signage's with necessary built-in battery (capacity of battery shall have a minimum back-up time of 90mins), mounting brackets, power supply cord etc complete vide technical specifications. (Size: 350 mm x 225 mm x 25mm)

30

-

-

... More
NOVEC GAS SUPPRESSION SYSTEM Supply, installation, testing & commissioning of NOVEC-1230 gas suppression system vide technical specification consisting of following units. (Shall be UL listed & FM approved 25 bar system). 80ltrs. Seamless Cylinder CCOE approved with valve, complete with a safety burst disc & safety cap.

1

-

-

... More
NOVEC - 1230 agent.

55

-

-

... More
Pr. Guage + Low Pr. Supervisory Switch

1

-

-

... More
Supply & installation of Cylinder bracket along with necessary supports for fixing.

1

-

-

... More
Supply, installation, testing & commissioning of Discharge nozzles of nickel plated brass material with holes drilled across 180° or 360°.

3

-

-

... More
Supply, installation, testing & commissioning of non-return valve of size 2".

1

-

-

... More
Supply, installation, testing & commissioning of discharge pressure switch with locking device suitable with operating pressure of 25 bar. Quoted rate shall include all necessary fittings.

1

-

-

... More
Supply, installation, testing & commissioning of M.S. Seamless pipes as per ASTM A 106 Gr. B. Sch. 40 with necessary manifold & fittings. 65mm dia.

12

-

-

... More
50mm dia.

18

-

-

... More
40mm dia.

10

-

-

... More
32mm dia.

12

-

-

... More
25mm dia.

10

-

-

... More
20mm dia.

12

-

-

... More
15mm dia.

6

-

-

... More
Supply, installation, testing & commissioning of Conventional 4-zone gas release panel with battery, vide technical specification.

1

-

-

... More
Supply, installation, testing & commissioning of conventional multicriteria detector (heat/smoke) with multiple sensitivity (adjustable at site) levels, programmable for timed automatic sensitivity selection with base, junction box & other accessories as required. Equipment shall meet requirements as described in technical specifications.

6

-

-

... More
Supply, installation, testing & commssioning of PVC insulated, PVC sheathed armoured FRLS 2C x 1.5 sq.mm copper FRLS cable.

150

-

-

... More
Supply, installation, testing & commissioning of control module shall be capable of providing DPDT contact rated at 24V DC, 2A.

1

-

-

... More
Supply, installation, testing & commissioning of monitor module shall be capable of providing DPDT contact rated at 24V DC, 2A.

1

-

-

... More
Supply, installation, testing & commissioning of manual abort switch with necessary interconnection with gas release manifold.

1

-

-

... More
Supply, installation, testing & commissioning of manual release switch with necessary interconnection with gas release manifold.

1

-

-

... More
Supply, installation, testing & commissioning of hooter cum flasher along with necessary interconnection with agent release panel.

1

-

-

... More
Supply & installation of caution labels & cylinder labels.

1

-

-

... More
Supply, installation, testing & commissioning of response indicators for all critical room detectors.

4

-

-

... More
Room integrity test for NOVEC gas suppression system. Quoted rate shall include supply of all necessary equipments required to carry out the test.

1

-

-

... More
Supply, installation, testing & commissioning of battery operated safety (Evacuation or alert) identification signage with battery back for 90mins. "DO NOT ENTER" identification signage

1

-

-

... More
"EVACUATE, GAS RELEASED" identification signage

1

-

-

... More
FIRE CURTAINS FOR OFFICE FLOOR COMPARTMENTATION: Supply, installation, testing & commissioning of "Fire Curtains" with galvanized MS head box, powder coated side guides along with adjustment channels & bottom bars with motors for power up operation with standard battery backup & operated system safe fixed into steel rollers with woven glass fiber fabric, reinforced with stainless steel wire having micronized aluminum polymer coating on each side of the fabric (silver/grey) with the necessary control panel & all installation assemblies & accessories required to complete the installation. Operation shall be suitable for dedicated 240 Volts UPS, 50 Hz AC supply. Complete system shall be tested in accordance with EN 1634-1 (for 120 minutes Integrity & tested at 1000°C) BS 476-22.8 and BS 7346-3. Quoted rate shall include necessary "Emergency Retract Switch" on both sides of the curtain along with necessary control panel housed within the provided false ceiling depth with suitable supports. Curtain shall reset automatically when fire alarm control panel is reset. Single Barrel fire curtain of size: 5000mm (W) x 3300mm (H)

4

-

-

... More
Double Barrel fire curtain of size: 6400mm (W) x 3300mm (H)

1

-

-

... More
Supply, installation, testing & commissioning of PVC insulated, PVC sheathed armored FRLS 2C x 1.5 sq.mm copper cable confirming to IS: 1554 part-I. Cable shall be rated for a voltage rating of 650/1100 Volts & insulated with suitably compounded PVC. Cables shall be properly supported to ceiling through suitable clamps/saddles at an interval of 300mm. Cables shall be measured on the basis of linear measurements from gland to gland. Colour code FA cable shall be "RED".

250

-

-

... More
Supply, installation, testing & commissioning of FRLS PVC Conduits of 2mm thick on ceiling / wall / floor etc. complete with accessories like, junction boxes, collars, bends etc. 20mm dia.

100

-

-

... More
Supply & installation of 3 pin power socket (suitable for 6/16A, 5 pin) for power supply to control panel.

5

-

-

... More
PANEL PROTECTION SYSTEM: Supply, installation, testing & commissioning of clean agent type local flooding direct low pressure Quick response system for main electrical panels. Extinguishing agent: 2kg clean agent NOVEC 1230 (UL/FM listed) with zero (ODP) ozone depletion potential. Container: Stored pressure type, deep drawn argon welded, M.S sheet metal thickness 1.5mm, 100% hydraulic pressure tested, confirm to EN/PED standard. Can shall be manufactured as per IS:15683 & complete test of body as per IS:15683, shall be demonstrated. Valve: Nickel plated brass, equipped with a pressure gauge to monitor system pressure, with ball valve interfacing the tubing & cylinder, with burst disc, working pressure 10-18 bar, leakage rate: 0.0001 mbar l/s.

3

-

-

... More
Supply, installation, testing & commissioning of Tube for automatic fire detection & supperession system made by special modified polyamaide (PA), colour red RAL300, inner diameter 4mm, outer diameter 6mm. Pressurised with dry nitrogen at 13.5/10.5 bar pressure UL approved.

90

-

-

... More
Supply, installation, testing & commissioning of "T" connection brass nickel plated for 4x6mm. Sensor tube, quick & easy disassembly using special tool, external diameter tube 6mm.

6

-

-

... More
Supply, installation, testing & commissioning of End of line plug for automatic fire suppression tube used for fitting at tube end to terminate the point. Fitting made by brass nickel plated material.

6

-

-

... More
Supply, installation, testing & commissioning of End of line adapter with pressure gauge for automatic fire suppression tube used for fitting at the end of tube for pressurizing & re pressurizing tube includes check valve, pressure gauge & fitting to connect to sensor tubing. Tube connection 6mm.

6

-

-

... More
Supply, installation, testing & commissioning of Pressure switch to monitor pressure drop in the tube, switch point 5bars

3

-

-

... More
Supply, installation, testing & commissioning of master control unit / control panel along with local hooter/sounder.

3

-

-

... More
HVAC WORKS CHILLER -AIR COOLED SCREW CHILLER SUITABLE FOR VARIABLE PRIMARY FLOW OPERATION The Chillers adopter box shall have extended bus bar for terminating 1R x 150 sqmm Aluminium Armoured XLPE cable with required support for mounting bus bar.The Panel also should have 250A MCCB for isolation purpose. The Adopter box shall have proper gland plate for cable entry. The adopter box shall suite as per Chiller control box requirement & shall be same IP rating as per Chiller. The cost shall be inclusive of necessary copper cables between a adopter box and chillers

2

-

-

... More
70 TR Actual capacity Water Cooled Chiller Package (Location: @ TERRACE )-(2W)

2

-

-

... More
Charges towards freight clearance, transportation, loading & un loading, rigging, lifting, shifting, positioning of chillers (installation), testing and commissioning and accessories on the designated location as indicated in the drawing.

2

-

-

... More
Coordination with HVAC low-side vendor for installation of chilled water and condenser water piping, electrical termination with the electrical vendor.

2

-

-

... More
CHILLER -AIR COOLED SCREW CHILLER SUITABLE FOR VARIABLE PRIMARY FLOW OPERATION The Chillers adopter box shall have extended bus bar for terminating 1R x 150 sqmm Aluminium Armoured XLPE cable with required support for mounting bus bar.The Panel also should have 630A MCCB for isolation purpose. The Adopter box shall have proper gland plate for cable entry. The adopter box shall suite as per Chiller control box requirement & shall be same IP rating as per Chiller. The cost shall be inclusive of necessary copper cables between a adopter box and chillers

2

-

-

... More
130 TR Actual capacity Water Cooled Chiller Package (Location: @ TERRACE )-(1W+1S)

2

-

-

... More
Charges towards freight clearance, transportation, loading & un loading, rigging, lifting, shifting, positioning of chillers (installation), testing and commissioning and accessories on the designated location as indicated in the drawing.

2

-

-

... More
Coordination with HVAC low-side vendor for installation of chilled water and condenser water piping, electrical termination with the electrical vendor.

2

-

-

... More
CHILLER PLANT MANAGER Chiller plant manger (CPM) with necessary hardware & Software for controlling, operating & monitoring 4 Nos. of Air Cooled Chillers, 5 Nos of ON/OFF control butterfly valves,5 nos of primary VARIABLE chilled water pump sets,. Chilled water supply and return temperature, flow, Chilled water leaving temperature reset. The quoted price should include the software / hardware for transfer of entire data points to the third party IBMS. Plant manager should be able to do sequencing, scheduling, load sharing between chillers etc.,

1

-

-

... More
2 core, 1 sqmm shielded armoured cable for control and communication cabling between plant manager to Chillers/ pump sets / panel / microprocessor/Chiller ON/OFF valve / temperature sensors (immersion & dry type) / flow meters to perform the function as per Plant Manager I/O Summary

500

-

-

... More
Electrical Power cable between the CPM and power socket with 3 Core, 2.5 sqmm, flexible copper cable.

50

-

-

... More
Supply, installation of ladder type cable trays with threaded rod supports, anchor fastners etc., inclusive of Supporting brackets/structures for cable trays,switch boards etc., fabricated out of MS angle,channel,plates and flats duly painted.(450mmx50mmx1.6mm thick )

150

-

-

... More
Ambient temperature and RH sensor

1

-

-

... More
Flow Switch

4

-

-

... More
Chiller inlet and oulet tempereture Sensor

8

-

-

... More
Extended Warranty for 4 years post DLP FOR CPM.

1

-

-

... More
VARIABLE FLOW PRIMARY CHILLED WATER PUMP IISC-VPP-01 TO VPP-03

3

-

-

... More
VARIABLE FLOW PRIMARY CHILLED WATER PUMP IISC-VPP-01 TO VPP-02

2

-

-

... More
VFD LOGICAL CONTROL PANEL (FOR PRIMARY VARIABLE PUMPS) Supply, installation, testing and commissioning of Microprocessor based pump logic control panel with 4 nos.VFD's suitable for indoor mounting and having the necessary power distribution arrangement for the individual VFD's. Single incomming power shall be provided. Necessary control wiring and power cabling as per site conditions shall be included Logic control VFD panel suitable for operating 5 Nos of PRIMARY pumps. 5 VFDs to be supplied along with the PLC

2

-

-

... More
Differential pressure sensor / Transmitter

10

-

-

... More
1R of 3 core 50 sqmm shielded armoured aluminium power cable between VFD PLC panel to individual PRIMARY pumps.

100

-

-

... More
2 core, 1.5 sqmm shielded armoured cable for control and communication cabling between DP sensor to panel.

100

-

-

... More
19mm dia PVC conduit for the above communication cable

100

-

-

... More
Pump Supplier shall provide necessary extended terminal box required for Aluminium / Copper motor cable termination.

5

-

-

... More
IDEC UNIT TWO STAGE EVAPORATIVE COOLING SYSTEM Two stage evaporative cooling system shall comprise of Indirect and Direct cooling heat exchangers. Indirect heat exchanger shall be of Engineered Polymer with thermally fused non woven media. Direct heat exchanger shall be made up of cellulose impregmented paper. Air velocity acoss heat exchangers shall be between 400-500 FPM. Plug fans to be supplied along with motor. The unit shall be provided with drive set & guard, vibration isolatator to fans and motor to avoid transmission of vibration Capacity - 11500 CFM @ 65mm TSP

2

-

-

... More
DOAS UNIT HORIZONTAL FLOOR MOUNTED AIR HANDLING UNITS FOR CHILLED WATER APPLICATION - TREATED FRESH AIR UNITS(DOAS) Double Skin Horizontal Air Handling Units complete with double skin (40±2 mm) insulated with CFC free polyurethane foam (PUF) panels of 40 Kg/cum density. The outer and inner panel thickness shall be 0.6 mm GI . Outer skin shall be preplastized G.I. sheet and internal skin shall be powder coated G.I. Sheet.,AHU frame works shall be of pre cast vertical and horizontal extruded aluminium profile with three way corner frame sections. Frame construction shall bear the load of structure and load of the frame structure shall be uniformly distributed along the entire housing of the AHU. Food grade self adhesive coated neoprene gasket to be provided between panels and structure of the AHU to ensure the entire housing is airtight. Plug fans to be supplied along with motor. The unit shall be provided with drive set & guard, vibration isolatator to fans and motor to avoid transmission of vibration, Chilled water fed cooling coils shall be of minimum 6 Row deep or as per computer coil selections which ever is greater. Face Velocity across the coils should not exceed 500 FPM. Chilled water cooling coils shall be constructed from premium quality seamless copper tubes and mechanically bonded to alumiunium fins. Chilled water cooling coils assembly shall be fitted on aluminium rails with nylon rollers for easy withdrawal from the AHU cabinet. Drain tray for chilled water cooling coils shall be made of single sheet of SS 304 grade stainless steel sheet and should have uniform slope from all sides leading to drain connection. Drain Pan shall be insulated with 19mm thick, 55kg/cum density closed cell elastomeric insulation. AHU inspection door shall be fitted to the frame with easy release half turn nylon handles and cam locks. Handles should have facility to operate from inside the AHU. 51.0TR - 13500 cfm-65mm. Wc. TSP - Treated Fresh Air

1

-

-

... More
45.0TR - 11500 cfm-65mm. Wc. TSP - Treated Fresh Air

1

-

-

... More
COOLING THERMOSTAT FOR DOAS Supply, installation, testing and commissioning of COOLING THERMOSTAT for various Air handling units as described in specifications. The thermostat shall be proportionatory type for modulating 2 way PIBC valve with digital temperature indicator. Item shall include supply & installation of necessary control wiring from thermostat & unit including termination with accessories.

2

-

-

... More
CEILING SUSPENDED UNITS CHILLED WATER TYPE DOUBLE SKIN CEILING SUSPENDED AC UNITS/CASETTE WITH ALL NECESSARY CONTROL & SAFETY ACCESSORIES Double skin type Ceiling suspended units complete with double skin (23±2 mm) insulated with CFC free polyurethane foam (PUF) panels of 40 Kg/cum density. Sandwitched between 0.6 mm thick G.I. Sheets.Outer skin shall be pre coated G.I. sheet and internal skin shall be plain G.I. Sheet., suitable for chilled water application. The unit shall be provided with backward curved aerofioil type blower, Motor, minimum 4 row cooling coil and drain pan with 16mm thick nitrile rubber insulation, inlet filter section with MERV-8 filters, drive set & guard, spring isolator to avoid transmission of vibration,etc. Chilled water fed cooling coils shall be of minimum 4 Row deep or as per computer coil selections which ever is greater. Face Velocity across the coils should not exceed 500 FPM. The unit shall be provided with belt driven backward curved fans, IE3 Motor, drive package, vibration isolating rubber bush to fans and motor to avoid transmission of vibration. All CSU motor pulleys shall be of adjustable type only. The Motor shall be of TEFC, IP-55 protected, IE-3, Class 'F' insulation, suitable for 3 phase, 415 volts, 50hz power supply as per tender drawing and specification. CSU-3.5TR - 1700cfm -30mm wc. Total Static Pressure-(Reception-LGF)

1

-

-

... More
CSU-2TR - 950cfm -30mm wc. Total Static Pressure-(Reception-GF)

1

-

-

... More
CSU-3.5TR - 1500cfm -30mm wc. Total Static Pressure-(Board room)

2

-

-

... More
CHILLED WATER TYPE CASSETTE UNITS Ceiling mounted 4way-Cassette type unit suitable for chilled water application. The Cassette unit shall have necessary filters, cooling coil, fan, fan motor, Condensate drain pump, decorative panels, port for connecting fresh air duct, cordless digital remote control unit etc., The unit scope of supply shall include Inlet & Outlet ball valve, 'Y'-Strainer, 2way Pressure-Independent Balancing cum Control valve with actuator, all necessary control wiring, power cabling of 2m length with plug-top, supports, isolators, insulation of valves etc., The cassette unit shall have its centre panel removable for accessing the valve package. The fan Motor shall be of 3speed, TEFC, IP-54 protection, suitable for 1phase, 230volts, 50hz power supply. as per tender drawing and specification. The cooling capacity mentioned shall be actual capacity to be delivered by the equipment at an indoor temperature of 24 deg C 1 TR - 400cfm - Cassette unit-(MR2,3,5,6,8,9,7,14,13)

10

-

-

... More
1.5 TR - 600cfm - Cassette unit-(MR17)

1

-

-

... More
2 TR - 800cfm - Cassette unit-(MR2)/SS

3

-

-

... More
Factory fabricated fire retardant flexible connection made of high quality self extinguishing, moisture resistant flexible fabric with matching angle flanges between AHU/CSU outlet flange and the supply air plenum with zipper for taking temperature readings.

14

-

-

... More
CRITICAL ROOM AIR CONDITIONING UNITS (CRAC) - Chilled Water Fed for UPS AND BATTERY ROOM (3F)-WORKING CRAC unit chilled water design temperature shall be as follows: Chilled water inlet shall be at 44⁰F Chilled water outlet shall be at 54⁰F Water flow shall be 2.4 usgpm/TR. Air on - 84.4 / 61.8 º F Air Off - 75.7 / 44.7º F Design SA Temp. - 56.0º F Room Temp. - 75.2 ±1.8 ºF False Floor Height - 600mm Motorized Dampers are to be installed at the return air side of the units. Necessary additional cabinet/plenum to be considered for housing the filters for access from the top. Without Heaters & Humidifiers :9 TR/ 5000 Cfm actual capacity from each unit at a external static of 15mm of wg. with Bottom Air Discharge Chilled water Precision Unit with all listed accessories as specified above.(Location: 3F-UPS/BATTER Room)

1

-

-

... More
CRITICAL ROOM AIR CONDITIONING UNITS (CRAC) - DX TYPE UPS AND BATTERY ROOM (3F)-WORKING Supply, Installation, testing and commissioning of High sensible load critical room air conditioning unit (CRAC) with single refrigerant ciruit. Each CRAC unit shall comprise direct expansion (DX) evaporator coils, inlet filter section with EU-4 filters, draw-through backward curved plug type fans made up of composite material, electronically commuted (EC) motors to deliver air quantity as specified. condensate drain pan,Refrigerant isolation valves, check valves & solenoid valves,Electronic Expansion valve,factory fitted liquid reciever,oil separator, HP/LP cutouts, microprocessor starter panel, necessary expansion kit for oil recovery and vibration isolating serrated rubber pads, hydrophilic coating shall be provided for both evaporator coil and condenser coil. (fixed) Scroll compressor suitable for R410A.Compressor Drive motor suitable for 415 +/- 15% V, 50 Hzs, 3P, TEFC squirrel cage induction motor. Microprocessor panel shall have digital display, programmable control & recording unit complete with intelligent 16 digit 2 line alpha numeric display, function keys, cursor keys, free programmable keys, inscription fields with integrated battery backup supply at 24 V AC 50 Hz. The unit shall be suitable for operation on 415 V 50 Hz AC supply. The Display panel shall display date, time, actual & set values, operating conditions, signal faults, collective faults limiting values. The unit shall be supplied with necessary inbuilt fan speed controller. Unit shall have fire alarm interlock arrangement. Design Parameters Room temperature : 75.2 ° F ± 1.8 ° F Entering Air temperture:85 / 62 ° F Air temperture leaving the evaporator coil: 75.8 / 44.8 ° F Evaporator coil ADP : 53.7 ° F Outdoor air condition for selection of condensing unit: 96.0 ° F ( 35.6 °C) Without Heaters & Humidifiers : Supply & Installation of 9 TR/ 5000 Cfm actual capacity from each unit at a external static of 15 mm of wg. with Floor Discharge type CRAC Unit with all listed accessories as specified under technical section. Motorized Dampers are to be installed at the return air side of the units. Filters shall be removable for maintenance without removing the dampers.(UPS ROOM-3F)

1

-

-

... More
LOW SIDE WORKS RELATED TO BOTH CHW AND DX CRAC Adequately sized control cabling & power cable of 3C x 2.5 Sqmm Cu power cabling as required between individual outdoor units and indoor units.

60

-

-

... More
Supply, Installation, termination and testing of power cabling between the isolator and units of size 4Cx16 Sqmm Cu armoured cable.

25

-

-

... More
Structural stand for positioning condenser units with necessary vibration isolating serrated rubber pads. Also the supplier to ensure that all support stands are of hot dipped galvanised frame with two 12.5 mm thick neoprene vibration isolators under the whole unit. Also rubber pads should be placed under the condenser units. The GI stand to be painted with two coats of primer and two coats of epoxy paint of Black Colour.

1

-

-

... More
Adjustable type hot-dip galvanized GI stand for indoor units made out of tubular section for rigidity. The height of the frame shall be 400mm and shall be adjustable for 60mm higher and lower. False floor depth is 450mm.

2

-

-

... More
Charges towards freight clearance, transportation, lifting, shifting and positioning of the above CRAC and accessories to respective floors and location (3rd Floor - UPS Room). The CRAC supplier is responsible for protection of units against weather and any other physical distrubance at site. The units with dents on the external panel, damages to the cooling coil or any other component will not be accepted at site. Testing & commissioning of the same with pressure testing. cost included for Initial Refrigerent gas and oil charge/top up for commissioning of the Dx PAC unit

2

-

-

... More
COPPER REFRIGERANT PIPING Hard drawn 16G copper refrigerant pipes with necessary fittings, extension kit and associated accessories. Copper pipes to be laid in a slotted cable tray with supports at regular intervals. Refrigerant pipes shall be clamped to the tray horizontal supports with necessary protection against mechnical friction with tray supports and shall be clamped firmly with heat resistant gromets. Copper refrigerant pipes laid above false ceiling space and inside the conditoined space till HVAC shaft / ambient to be insulated with 13 mm thick closed cell elastomeric tubular insulation material. The quoted rate per rmt of the refrigerant piping shall be for Hot gas + Liquid lines, inclusive of all the circuits between the IDU and ODU, inclusive of the supporting arrangements. 22.5 mm ( 7/8 ") dia hot gas pipe with 13 mm thick insulation

30

-

-

... More
22.5 mm dia(7/8") exposed hot gas pipe with only epoxy painting

30

-

-

... More
15.8 mm dia (5/8") liquid pipe with 13 mm thick insulation

30

-

-

... More
15.8 mm dia 5/8") exposed liquid pipe with only epoxy painting

30

-

-

... More
Extended service kit required for Oil return-if vertical height more than 30m

1

-

-

... More
Ladder type cable tray for laying of copper refirgerant pipes in false ceiling with supports at 1m interval. Heat resistant gromets to be used to hold the copper pipes. Metal to metal contact should be eliminated. Hot gas and Liquid line to be painted with two coats of epoxy paints. (Colour Code: Hot Gas Line: RED; Liquid Line: Orange.) 300mm (W) x 100mm (D) x 1.6mm (T)

10

-

-

... More
MOTORIZED ON / OFF DAMPER (Integral part of CRAC Supply) Supply & Installation of the motorized ON / OFF FLANGE TYPE damper with opposed blades, outer casing constructed of 1.6mm thick galvanized steel frame and the blade/Leaf with 1.6mm thick GSS and with matching flanges for duct connection. The Damper to be provided with high torque actuator, with auxiliary contacts to indicate the position and suitable for remote control operation & monitoring. The motorized damper shall be installed at the return air inlet of the floor Discharge CRAC unit and at the supply air side for Top Discharge CRAC unit. The actuator shall be interlocked with the respective CRAC unit so that the damper closes when the CRAC unit is switched OFF and opens when the unit is turned ON. The number of actuators per damper shall be selected based on the area and dimensions of the damper. For larger dampers, the number of actuator per damper can be selected 2 or more based on manufacturer selection to ensure smooth and reliable operation. The CRAC unit panel shall have necessary provision to provide the necessary power and control signal for the operation of the actuators. The panel shall also have arrangement to ensure that the fans are switched ON only after the damper is open. Motorized ON / OFF Damper of size suitable to fit the CRAC unit with Actuator and other details as mentioned above

2

-

-

... More
CONDENSATE DRAIN PUMP Supply & Installation of condensate drain pump kit with stand-by arrangement consisting of 2 pumps (1W+1S) with anti-siphoning device with float level switches and high level safety switch with a tank capacity of 4L suitable for pumping water for a vertical head of 6M with necessary piping and valve support arrangement. Water level sensor for automatic operation of the pump, power and control wiring, sequential control to ensure equal run hours of the pumps. Sequencing of the pumps and Alarm arrangement to generate signal incase of failure of pumps. An integral control panel shall also be provided with all the above integration arrangement with necessary electrical switchgears, contactors, overload relays, potential free contacts. Any other material required for effective functioning of the drain pump shall also be considered as part of this line item.

2

-

-

... More
PERFORATED FLOOR TILE WITH OPPOSED BLADE DAMPER (OBD) Rigid Perforated Floor Tile of 600mmx 600mm size with adjustable OBD for supply air in the cold aisle. Ther perforated floor tile shall be fabricated from mild steel, perforated top and a specially designed side channel section which houses a pre-punched 25 x 25 x 30 mm high mesh concealed within the side channel. The top and bottom are resistance welded at approximately 100 locations. The perforated floor tile shall be epoxy painted with 40 micron thicknesss and shall be designed to take a point load of 360kgs on a square indenter of 25 x 25 mm and a UDL of 1200 Kgs / sqm. The top finish of the perforated tile shall be fire retardant, floor grade antistatic perforated laminate (shade shall be the same as the adjascent raised floor panel). The edges of the laminate shall be protected with 5 mm PVC trim. The perforated floor tile shall meet the design criteria specificed for standard floor panels and shall have a uniform perforated pattern to ensure uniform air distribution. The perforated floor tile shall have a minimum of 50 % TO 60 % free area opening to achive the design air quanity. Pressure drop not to exceed 1.8 mmWG and average face velocity shall be 1.26 m/sec and air quantity range shall be 600 to 800 CFM.

15

-

-

... More
FLOOR AND SLAB INSULATION Supply and installation of floor thermal insulation shall be with closed cell nitrile rubber covered with Aluminium foil of density 40 to 60 kg/m³ including low VOC adhesive as per ASTM-D-1667, as per the thickness mentioned below. The insulation joints shall be sealed with 50mm wide moisture resistant self adhesive tape. (Areas : 3F UPS room) 25mm thick

100

-

-

... More
GRILLES - Al. The supply & installation of higher grade Aluminum Extruded powder coated grilles with blade deflection of 0 & 15 deg

10

-

-

... More
VARIABLE REFRIGERANT FLOW SYSTEM - ODU The system shall be suitable for variable refrigerant volume / flow air conditioner consisting of one outdoor unit and multiple indoor units. The outdoor units shall be of Inverter/digital scroll type capable of changing the rotating speed to follow variations in cooling load and shall be suitable for connecting multiple indoor units of different capacities & types as per the drawing and project requirements. The unit shall be with non-ozone depleting refrigerant R410A. The refrigerant piping length between farthest indoor units and outdoor unit shall be possible to extend up to 175m with maximum 50m level difference. Transportation, shifting, lifting, Installation,testing & commissioning of the below indoor units & Outdoor units with necessary mounting brackets & arrangements, pressure testing of the VRF system, vibration isolation pads, Refrigerant initail charge and after commissiong, electrical cable termination from breaker to ODU module etc., Testing and commissioning of VRF works shall be included All components shall be mounted on welded steel base frame, structural steel profiles/panels made out of galvanized sheet steel, protected with primary coat & finished with epoxy paint.Grouting shall be considered for the condenser units Note : All ODUs are located at TERRACE FLOOR For IDUs, refer drawings. 6HP- WORKING + STAND BY(Top discharge)-Right wing

2

-

-

... More
12HP- WORKING (Top discharge)-Right wing

1

-

-

... More
22 HP- STANDBY (Top discharge)-Right wing

1

-

-

... More
HI Wall type INDOOR UNITS - VRF type Hi Wall type Indoor unit suitable for VRF system. The unit shall have necessary filters, cooling coil, Electronic expansion valve, fan, fan motor, decorative panels, cordless digital remote control unit etc., as per specification. Note: The capacities prescribed below are nominal capacities and vendor shall refer the equipment schedule for actual cooling capacities and air flow requirements. 1 TR -350cfm-(IT ROOM) 1W+1S

16

-

-

... More
2 TR -650cfm-(BMS ROOM) 1W+1S

2

-

-

... More
CEILING MOUNTED DUCT TYPE - VRF type Ceiling mounted Duct type indoor unit shall be with necessary long life high quality filters, cooling coil, electronic expansion valve, fan, fan motor, cordless digital remote control unit etc., as per tender drawing and specification. Additional FRP drain tray shall be considered for this units. The units shall be suitable for input power supply of 1Phase, 230volts, 50hz. 4 TR /1200CFM-IT server/IT room (1W+1S)/Board room 1&2

4

-

-

... More
COPPER REFRIGERANT PIPING Hard drawn 18G copper refrigerant pipes with necessary fittings, extension kit and associated accessories. Refrigerant pipes shall be clamped to the tray horizontal supports with necessary protection against mechnical friction with tray supports and shall be clamped firmly with heat resistant gromets. Copper refrigerant pipes shall be insulated with 19 mm thick closed cell elastomeric tubular insulation material. tray quantities are considered separately The quoted rate inclusive of the supporting arrangements 28.6 mm dia

20

-

-

... More
22.2 mm dia

100

-

-

... More
19.1 mm dia

40

-

-

... More
15.9 mm dia

225

-

-

... More
12.7 mm dia

325

-

-

... More
9.5 mm dia

390

-

-

... More
6.4 mm dia

325

-

-

... More
Necessary Ref joints, valves as per the schematic drawing.

5

-

-

... More
Electrical Power cable between the indoor unit and power socket with 3 Core, 2.5 sqmm, flexible copper cable, with 1 no. plug top for each IDU.

500

-

-

... More
2 core, 1.5 sqmm shielded communication control cable between the indoor units and the outdoor units.

500

-

-

... More
Perforated cable tray with top cover for laying of copper refirgerant pipes in terrace with supports at 1m interval. Heat resistant gromets to be used to hold the copper pipes. Metal to metal contact should be eliminated. 300mm (W) x 100mm (D) x 1.6mm (T)

75

-

-

... More
150mm (W) x 100mm (D) x 1.6mm (T)

50

-

-

... More
100mm (W) x 100mm (D) x 1.6mm (T)

100

-

-

... More
CONDENSATE DRAIN PUMP Supply & Installation of condensate drain pump kit with anti-siphoning device with high level safety switch with appropriate tank capacity suitable for pumping water for a vertical head of 2M, minimum 10L/hr with necessary piping and valve support arrangement. This item shall be used for the removal of condensate water from the tray beneath the hi wall unit. Any other material required for effective functioning of the drain pump shall also be considered as part of this line item. Note : If the slope is not available as per site condition, then only this component shall be operated.

18

-

-

... More
INSULATED CONDENSATE DRAIN PIPE FOR ALL THE UNITS Supply,installation,testing and commissioning of rigid uPVC piping complete with fittings, supports as per specifications and duly insulated with 6 mm thick closed cell nitrile rubber. Density of uPVC pipe shall not be less than 10 kg / m3 50mm. Dia.

75

-

-

... More
40mm. Dia.

75

-

-

... More
25mm. Dia.

75

-

-

... More
VRF PLANT MANAGER A multifunctional compact centralized controller shall be provided with the system. It shall be provided with backup power supply. In case of total power failure it should have built in memory for recollect the latest settings. It shall be able to control up to 64 groups (128 indoor units) with the following functions a) Starting/stopping of Air-conditioners as a zone or group or individual unit. b) Temperature settling for each indoor unit or zone. c) Switching between temperature control modes, switching of fan speed and direction of airflow, enabling/disabling of individual remote controller operation. d) Monitoring of operation status such as operation mode & temperature setting of individual indoor units, maintenance information, trouble shooting information. e) Display of air conditioner operation history. f) Daily management automation through yearly schedule function with possibility of various schedules. g) It should able to communicate with BMS system with necessary hard ware & software of open protocol system ie., BACNet protocol. h) Auto sequencing of the circuits. If there is any breakdown of any circuit, the stand-by circuit shall operate immediately. The controller shall have wide screen user friendly display and can be wired by a non polar 2 wire transmission cable to a distance of 1 km. away from indoor unit. Controller shall have fire alarm interlock with all the indoor units, to switch "OFF" in the event of fire through potential free contacts and shall be capable of receiving signals from Fire safety system.

1

-

-

... More
Electrical Works for VRF System MCB/MPCBs for individual ODUs, power cables from feeders to ODUs to the individual ODUs(3m) and earthing for individual ODUS. Note: Power supply with isolater shall be provided at single point. Further distribution to respective ODUs with suitable size MCBs etc., shall be part of VRF system SITC. The enclosure for the MCB for individual ODU shall have IP65 enclosure, suitable for outdoor application.

4

-

-

... More
VARIABLE AIR VOLUME BOXES (VAV) - DAMPER ACTUATOR TYPE All VAV unit to be selected to perform for 120% to 20% of design capacity of air flow given below with provision for field setting adjustment as required. VAV shall be AHRI certified and shall meet the requirements of AHRI 880. VAV Unit shall be of the following sizes: Supply of the 450 cfm Capacity VAV (0-450)

64

-

-

... More
Supply of the 800 cfm Capacity VAV (450-800)

6

-

-

... More
Work station area thermostat - without set point adjuster and without display - Wall mounted

70

-

-

... More
All the communication & control cable between VAV system & Supervisory controller to be provided in 19mm PVC conduit. Supervisory controller required shall also be integral scope of VAV supply.

810

-

-

... More
All necessary Software & Hardware, Interface or integrator with open protocol like Native BACnet suitable for BMS connectivity for control & monitoring to be provided. Total no. of network controller shall be based on manufacturer requirement. 1 network controller shall be capable of intergrating minmum 30 VAV boxes.

1

-

-

... More
VENTILATION FANS FLOOR MOUNTED CABINET TYPE FRESH AIR UNITS Double Skin Horizontal floor mounted Air Handling Units complete with double skin (40±2 mm) insulated with CFC free polyurethane foam (PUF) panels of 40 Kg/cum density.Sandwitched between 0.6 mm thick G.I. Sheets. Outer skin shall be pre coated G.I. sheet and internal skin shall be plain G.I.with DIDW centrifugal fan with Backward curved aerofoil impeller, Motor, Pulleys, Belts & Belt guard, MERV-8 filters, drive sets, base frame, spring mounts, Limit switches, Marine lamp, Inspection door and all necessary accessories. The unit shall be suitable for outdoor application with necessary weather hood, canopy and supports with necessary MS channels & threaded rods. The Motor shall be of TEFC, IP-55 protection, Class 'F' insulation, motor shall be of IE-3 efficiency, suitable for 3phase, 415volts, 50hz power supply. Motor shall be suitable for Variable speed appllication (VFD). Unit height shall not exceed more than 1600mm height 12500cfm - 40mm wc. Total Static Pressure.(Location: Terrace) STP/pump room

1

-

-

... More
FLOOR MOUNTED CABINET TYPE EXHAUST UNITS Double Skin Horizontal floor mounted Air Handling Units complete with double skin (40±2 mm) insulated with CFC free polyurethane foam (PUF) panels of 40 Kg/cum density.Sandwitched between 0.6 mm thick G.I. Sheets. Outer skin shall be pre coated G.I. sheet and internal skin shall be plain G.I. Sheet with DIDW centrifugal fan with Backward curved aerofoil impeller, Motor, Pulleys, Belts & Belt guard, drive sets, base frame, spring mounts, Limit switches, Marine lamp, Inspection door and all necessary accessories. The unit shall be suitable for outdoor application with necessary weather hood, canopy and supports with necessary MS channels & threaded rods. The Motor shall be of TEFC, IP-55 protection, Class 'F' insulation, motor shall be of IE-3 efficiency, suitable for 3phase, 415volts, 50hz power supply. Unit height shall not exceed more than 1600mm height 4000cfm - 30mm wc. Total Static Pressure.(Location: Terrace) - Toilet

1

-

-

... More
4000cfm - 30mm wc. Total Static Pressure.(Location: Terrace) - Toilet

1

-

-

... More
11500cfm - 40mm wc. Total Static Pressure.(Location: Terrace) - STP

1

-

-

... More
3900 cfm- 40 mm wc.Total Static Pressure.(Location: Terrace) - pump room

1

-

-

... More
WALL MOUNTED PROPELLER TYPE FAN-EXHAUST AIR FAN The supply & installation of wall mountable propeller type inline fan with all accessories like fan, motor, mounting frame, duct sleeve, protection guarads,etc.,. The motor should be of IP21, class 'B' insulation suitable for operating at 3 phase, 230V, 50hz power supply. 100cfm - 15mm wc. Total Static Pressure for exhaust Air -storage

1

-

-

... More
RECTANGULAR INLINE FAN-EXHAUST AIR The supply & installation of Rectangular duct inline fan with all accessories like fan, motor, 20 micron wahsable filter with frame,flanges etc., The motor shall be with IP21 protection, class 'F' insulation. 2600cfm - 30mm wc. Total Static Pressure.(Location: Terrace) - pantry/ele room

1

-

-

... More
2300cfm - 30mm wc. Total Static Pressure (Location: Terrace) - ELE room

1

-

-

... More
900cfm - 30mm wc. Total Static Pressure for Utility area

1

-

-

... More
600cfm-15 mm wc. TSP - battery room

1

-

-

... More
CIRCULAR INLINE FAN-EXHAUST AIR The supply & installation of Circular inline fan with all accessories like fan, motor, flanges, 20 micron wahsable filter with framenon-canvass type fire retardant flexible connections, etc., The impeller shall be of forward type. The motor should be of IP21, class 'B' insulation suitable for operating at 1phase, 230V, 50hz power supply. 400cfm-15 mm wc. TSP - board 1& 2

1

-

-

... More
TUBE AXIAL FANS FOR CORRIDOR SMOKE EXTRACTION Axial fan shall comprise fan section with adjustable blade angles to deliver the design air quantity. The motor shall be suitable for outdoor ventilation application. The axial fan assembly shall be housed in a casing made of Mild Steel with enamel Painted, adjustable pitch die cast aluminium impeller (Hub and blades). The Motor shall be air over cooling type with IP-55 protection, Class 'H' insulation, IE-3 efficiency, suitable for 3phase, 415volts, 50hz power supply. Fan position shall be as per the tender drawings. The unit shall be suitable for indoor application with necessary supports with necessary MS channels & threaded rods. 8700cfm - 30mm wc. Total Static Pressure (Left wing) location:terrace

1

-

-

... More
5600cfm - 30mm wc. Total Static Pressure (right wing) location: terrace

1

-

-

... More
FUME HOOD EXHAUST -DRY SCRUBBER with SISW FAN Supply, Installation, Testing and Commissioning of Scrubber each comprising of extract air intake section, electrostatic precipitation technology, dry type air cleaner to remove oil, smoke and fumes from exhaust air, as per the Specifications. Electrostatic section shall be made of 16 gauge galvanised sheet, high bake epoxy powder coated, washable type aluminium mesh filters, stainless steel spiked ionizers to create high voltage DC field, aluminum collector plates which should be alternatively charged positive and negative with large collecting area with 14" deep cell, to work as magnet for charged smoke and oil particles. Average efficiency of 90-95% in single pass as per ASHRAE test method. Electrostatic Precipitator should be able to charge particles from 0.01 micron to 10 microns through solid state power supply. Collector cell should be of permanent type and incorporate slide out facility for easy removal for cleaning. Power supplies shall be 100% solid state UL Listed, Module of capacity above 3000 CFM shall be equipped with Pulse width modulating (PWM)The system should be fitted with interlock switch for safety . The system should allow connection to a fan section to achieve 500 FPM velocity across the air cleaner.Motor should be acoustically treated to reduce noise level. Horizontal floor mounted cabinet exhaust unit with SISW centrifugal fan with Backward type impeller, Motor, Pulleys, Belts & Belt guard, base frame, spring mounts, necessary flanges to connect the inlet & outlet duct, with suitable inspection door, casing drain etc., Motor shall be of TEFC, IP-55 protection, Class 'H' insulation, suitable for 3phase, 415volts, 50hz power supply. The motor and drive assembly shall be away from the stream of the air-flow. The entire equipment shall be suitable for outdoor installation. The equipment shall as per tender drawing and specification. 3150cfm - 125mm wc. Total Static Pressure - Fume hood (location:terrace)

1

-

-

... More
2650cfm - 125mm wc. Total Static Pressure - Fume hood (location: terrace)

1

-

-

... More
Supply, installation, testing, flushing, balancing and commissioning of entire condenser and chilled water piping network. Water Balancing shall be carried out 2 times and Flushing shall be carried out 3 times. CHILLED WATER PIPING WITH INSULATION MS 'C' Class pipes insulated with Closed cell elastomeric insulation of thickness as specified in the tender specification. The insulation shall be protected with treated woven glass cloth. Costing shall be including the entire piping Prokon protective coating that shall be used over the insulated surfaces for mechanical protection and UV protection. Piping supports to be provided as mentioned in the specification. The piping flange connection bolts, washers and nuts should be hot dipped galvanised.The pipes should be supported with MS Channels, angle frame with neoprene rubber / PUF saddles. Fitting accessories for installation of pressure gauges, thermometers, BMS sensors, drain ports to be provided by the HVAC lowside contractor. Flourscent Plastic Sticker/ paint shall be applied to indicate Water flow directions. Only End flanges to be used for capping of pipes. "Table E" of BS code for flange thickness to be adhered. 200mm dia

20

-

-

... More
150mm dia

400

-

-

... More
125mm dia

150

-

-

... More
100mm dia

340

-

-

... More
80mm dia

270

-

-

... More
65mm dia

230

-

-

... More
50mm dia

600

-

-

... More
40mm dia

620

-

-

... More
32mm dia

1180

-

-

... More
25mm dia

100

-

-

... More
BUTTERFLY VALVE WITH INSULATION The Butterfly valve shall be of Slim seal wafer type of PN 16 rating, companion flanges shall also be of PN16 rating. Butterfly valves installed for the chilled water pipelines shall be insulated with nitrile rubber insulation and the insulation thickness shall be similar to that of the pipe dimensions. (valve sizes above 200mm shall be wheel operated type instead of handles). All bolts, washers and nuts shall be hot dipped galvanized only. 125mm dia

20

-

-

... More
100mm dia

1

-

-

... More
80mm dia

24

-

-

... More
65mm dia

8

-

-

... More
50mm dia

8

-

-

... More
BALL VALVE WITHOUT STRAINER WITH INSULATION The ball valves with long stem, handles and threaded joints shall be of PN16 class and insulated with nitrile rubber. Draining of the pipes is considered under this line item. 40mm dia

22

-

-

... More
32mm dia

116

-

-

... More
25mm dia

24

-

-

... More
MOTORIZED VALVE (MODULATING Type) WITH INSULATION Globe valve type with heavy duty actuator suitable for 220V AC operation, step down transformer. The valve actuator shall be of electronic type to ensure that the valve modulates as per the load. The valve shall be insulated with nitrile rubber insulation of thickness similar to that of pipe sizes. 125mm dia

2

-

-

... More
MOTORIZED BUTTERFLY VALVE (ON- OFF Type) WITH INSULATION Wafer valve type with heavy duty actuator suitable for 220 V /24V AC operation, step down transformer. The valve actuator shall be of spring return type to ensure that the valve closes when the power supply is cut-off to the actuator. The actuator shall be electrically interlocked with the respective equipment such that the power is automatically supplied to the actuator when the equipment is switched ON and the power is cut-off when the equipment is switched OFF. The valve shall be insulated with nitrile rubber insulation of thickness similar to that of pipe sizes. 125mm. Dia

4

-

-

... More
PRESSURE INDEPENDENT TYPE DYNAMIC BALANCING CUM FLOW CONTROL VALVE. Valve selection to be submitted in the technical submittal for approval before procurement. Pressure Independent dynamic balancing cum equal percentage type modulating flow control valve fitted with high torque actuator with spring return to ensure the valve closes automatically in the event of power disconnect to actuator. Actuator enclosure shall be rated for IP 54 protection. Step down transformer if required shall be part of valve supply, matching flanges, hot dipped galvanized bolts and nuts. Valve body to be insulated with closed cell elastomeric insulation. Actuator should be provided with position feed back switch and also actuator should have BMS interfacing card and shall be suitable for accepting signals from temperature sensors supplied by BMS vendor. Actuator should also have facility to set the required flow rate as per site requirements through dip switch adjustments. Valve body to be rated for PN 16. The valve design flow rate should be factory calibrated with +/- 5% flow accuracy. Valve shall have necessary measuring ports, drain port, flanges etc., The balancing to be done through microprocessor based hand held terminal / POT and the same results shall be furnished in the water balancing report as part of commissioning report and handing over manual. 80 mm Dia

2

-

-

... More
40 mm. Dia

10

-

-

... More
32 mm Dia

54

-

-

... More
25mm. Dia

9

-

-

... More
The Y-strainer body construction shall be with Mild steel and strainer shall be of bronze with magnet and drain port. Note, the insulation quantity will be measured in running meters and the valve in numbers. 125mm dia

3

-

-

... More
100mm dia

1

-

-

... More
80mm dia

3

-

-

... More
50mm dia

1

-

-

... More
40 mm. Dia

11

-

-

... More
32 mm Dia

50

-

-

... More
25mm. Dia

8

-

-

... More
NON RETURN VALVE WITH INSULATION The Check valve shall be of Slim seal wafer type of Dual plate type with companion PN16 flanges & insulation.all bolts, nuts and washers shall be of Hot dipped galvanished. 125mm dia

6

-

-

... More
Automatic air vent to be provided at all high location of piping. The air vent to be provided with necessary ball valve.

40

-

-

... More
The Thermometer shall be of Dial type (100mm) Range 0⁰ to 50⁰C, with stainless steel body - IP 55 protection, with necessary theromowells.

30

-

-

... More
Thermowell

8

-

-

... More
TEST POINT Supply Installation testing and commissioning of test points for measuring chilled water pressure and temp. Test Point shall be of brass construction, 1/4" BSP with NEOPRENE sealing bushes and shall be provided with screwed cover.

160

-

-

... More
TEST POINT MEASURING INSTRUMENT supply & installation of dial type pressure & Temperature gauge with extended probe used for taking pressure & temperature measurements in liquid flow lines carring non-corrisive fluids using portable instruments made out of brass body & connection size of 1/4".

2

-

-

... More
PRESSURE GAUGE (GLYCERINE FILLED) The Pressure Gauge shall be of Bourdon tube Dial type (100mm) Range 0 to 10 kg/cm², with stainless steel body - IP55 protection with necessary pipe fitting and needle valve etc.,

40

-

-

... More
CONDENSATE DRAIN PIPE UIPVC 6kg/cm2 pipe with fitting, supports and with necessary fittings. 40mm. Dia.

50

-

-

... More
32mm. Dia.

25

-

-

... More
25mm. Dia.

25

-

-

... More
Drain valve 40 mm dia

144

-

-

... More
25 mm dia

50

-

-

... More
Flexible rubber couplings for Chiller and Condenser water piping connections with expansion stoppers with double folds, hot dipped galvanized bolts and nuts. The bellows should withstand pressure of 16kg/cm2. ( PN 16) at the Inlet & Outlet of Pumps & Chillers 125mm Dia.

10

-

-

... More
BTU meter shall include the following Heat Meter Integators & Flow meters. Heat Meter Integators: Shall include calibrated pair temperature sensor with the necessary accessories for installing the sensors.Shall have the features of Battery Backup up to 10 Years, Data logging for up to 15 years, 230V AC power supply provision, 8 Digit LCD display, Protection category of IP54, Modbus RTU. Flow meters: The flow meter shall include screwed / Flanged meters incorporate ultrosonic flow meters type that are mounted perpendicular to the flow. The meters shall use a magnetic transmission system between the impeller and the totalising 125mm. Dia

1

-

-

... More
150mm. Dia

1

-

-

... More
PRESSURE MAINTAINING STATION Pressurised closed expansion tank of M.S construction with interchangeable EPDM/BUTYL bladder working on nitrogen pressure with following accessories: Pressure gage, Safety valve, conforming as per specification and of below capacity unit shall be complete with adequately sized two stage high pressure pumps (1 working +1 standby) with control panel with soft starters, valves and other accessories as described in detailed specifications. The pumps shall be able to deliver at least 20 CMH flow at suitable pressure head. Unit shall include a vacuum degasser with pressure sensor and other accessories for the effective removal of air in the system. 200 Litres

2

-

-

... More
AIR SIDE WORKS G.S.S DUCTING as per SMACNA Standards. All ducting shall be of factory fabricated completely finished and transported to site in a boxed form (including the duct flange and the VAV transition pieces and Z pieces). GS sheet shall be Class VIII – with zinc coating of 120 gm / sqmt surface area. TDF type flanges with neoprene rubber gaskets of thickness to match the dimensions of the ducts shall be used for connecting two ducts. The cost of the duct shall include the wedge supports, angle flanges, anchor fastners, hot dipped galvanized bolts and nuts etc., The Duct to be manufactured and assembled as per SMACNA standard for Class-500pascals. Pressure testing of sheet metal ducts with necessary components like semi-rigid flexible ducts, fans and the measuring kit. Pressure testing shall be carried out for complete air distribution system excluding flexible ducts, diffuser box, diffusers and grilles. Pressure testing shall be carried out prior to thermal insulation and as per SMACNA standards and approval shall be obtained from PMC and consultants. Air Balancing of each individual supply air outlet to within +10% or -5% of the design air quantity and tabulating the same in a form of report and also the final air balancing figures to be indicated against each measured outlets in the as built drawings. Balancing also includes balancing of return air, supply air and outdoor fresh air quantity. Air flow hoods to be used for measuring the air flow across the square diffusers. 24G. Ducting

2470

-

-

... More
22G. Ducting

360

-

-

... More
20G. Ducting

100

-

-

... More
Elleptical ducts made of GSS, factory fabricated with single skin construction with necessary supporting brackets,wired aupport,wedge supports,threaded rods, anchor fasterners etc, Note : Insulation shall be provided from inside.Same is quntified under separete line item 24G. Ducting

330

-

-

... More
22G. Ducting

50

-

-

... More
Round ducts made of GSS, factory fabricated with single skin construction with necessary supporting brackets,threaded rods, anchor fasterners etc, Note : Insulation shall be provided from inside.Same is quntified under separete line item 200 mm Dia 24G. Ducting

50

-

-

... More
FIRE RATED GSS DUCTING - FOR SMOKE DUCTS WITH SPARY PAINT Fire rated ducting shall meet as per BS 476 Part 24 (1987) codes. A fire resistant/fire retardant coating of minimum thickness is sprayed over duct outer surface which sustain high temperature of the fire. The flame resistand and quality of coating of the duct shall be compitible maintain its stability and integrity for 2 hours as tested in a fire tested. All ducting shall be of factory fabricated finished and boxed duct only. 24G. Ducting

630

-

-

... More
22G. Ducting

190

-

-

... More
Note : Insulation shall be provided from inside.Same is quntified under separete line item 24G. Ducting

600

-

-

... More
22G. Ducting

200

-

-

... More
FRP duct to handle chemical fumes including strong acids. FRP duct shall be of low smoke & flame rating as per UL-181 & capable to handle low fire-gas toxicity. The duct shall be blend with interior corrossion barier with an exterior class-1 duct material.

50

-

-

... More
ACOUSTIC INSULATION OF DUCTS Class "1" type, Open cell elastomeric Acoustic insulation with density not less than 140 kg / m3. Insulation material to be fire retardant. Moisture resistant-joining tapes of 2 inches width with self adhesive to be supplied with the insulation material by the supplier. 15 mm thick

210

-

-

... More
THERMAL INSULATION Thermal insulation of the sheet metal duct with closed cell elastomeric insulation of Class 'O' material with density of 40 - 55 kg/cum as per the thickness mentioned below, with fire retardant adhesive and joints sealed with 3mm thick, 50mm wide nitrile rubber self adhesive tape. 9 mm thick

3770

-

-

... More
SINGLE SKIN PLENUM GSS 22G. single skin plenum with 50 mm thick rigid fiber glass board covered with 2 layers of RP tissue & finished with 26G GI perforated sheet.

25

-

-

... More
200 mm Dia.

120

-

-

... More
FLOW LIMITERS Circular volume flow limiters for the simple balancing of volume flow rates in air conditioning systems. Mechanical self-powered volume flow limiter without external power supply. Set the required volume flow rate using a scale.Casing and damper blade made of high-quality plastic, shall be of UL certified . Leaf spring shall be made of stainless steel. Polyurethane bellows Volume flow rate setting range 20 - 100% of the nominal volume flow rate. Volume flow rate accuracy approx. ± 10 % of the nominal volume flow rate Volume flow rate range 11 - 450 CFM 150 mm Dia.

12

-

-

... More
200 mm Dia.

2

-

-

... More
The round flexible duct inner core should be made of double lamination of Aluminum Foil, Polyester & Metalized polyester film permanently bonded to a coated spring steel wire helix. Fiberglass insulation shall be of 25mm thick with minimum density of 16 kg/m³. The outer insulation jacket vapor barrier shall be made of fiber glass reinforced metalized polyester film laminated with aluminum foil as per the technical specifications 200 mm Dia.

185

-

-

... More
The volume control damper shall be of low leakage type with the outer shell constructed of 16G thick galvanized steel frame and the blade/Leaf with 16G thick GSS. And with necessary flanges for connection etc., as per specification.

16

-

-

... More
The Back draft damper with the outer shell constructed of 16G thick galvanized steel frame and the blade/Leaf with 1mm thick aluminum. And with necessary flanges for connection and suitable for installing inside the duct and as per specifications.

2

-

-

... More
MOTORIZED VOLUME CONTROL OPPOSED BLADE DAMPER - STANDARD TYPE The supply & Installation of the volume control damper with the outer shell constructed of 16G thick galvanized steel frame and the blade/Leaf with 16G GSS. And with flanges for connection. The Damper to be provided with necessary high torque Actuator working on 24V AC/DC. and control panel with step down transformer, indicator, provision for remote control operation & monitoring etc. Refer tender drawings for more details. The number of Actuator per damper is based on the number of damper required for the project as per drawing. However if the damper size exceeds 1.5sqmt, the number of actuator per damper can be selected 2 or more based on manufacturer selection and requirement for the smooth operation.

5

-

-

... More
Necessary control contactors with power and control cabling shall be considered for interlocking motorized dampers with respective indoor units. Necessary Adapters / Contactors / control panels to be considered for interlocking of MVCD's of respective IDU's with MVCD's of VAV's. Motorized Volume Control Damper with Suitable Actuator and other details as mentioned above

20

-

-

... More
3 core, 1.5 sqmm shielded power and communication control cable between the panels and actuators.

550

-

-

... More
MOTORISED FIRE DAMPER WITH OPPOSED BLADE - Extended Sleeve type - 600 mm long The Fire damper as per UL 555S (SEALED & STAMPED), with outer shell of 16G galvanized steel frame and the blade/Leaf of 16G thick GSS. And with necessary flanges for connection as per specifications. The damper shall be of class 2 fire rating. With Spring return Actuator working on 220V AC and each fire damper should be supplied with necessary High torque Spring return type Actuator, Temperature sensor & control panel. The control panel shall be with step down transformer, indicator, auxiliary contacts, necessary power and control cabling, position feedback, relay provision for remote control operation etc, as per drawings & specifications. The control panel should be capable to operate the damper through BMS for remote control operation & monitoring.

8

-

-

... More
The number of Actuators per damper shall be selected based on the area and dimensions of the damper. For larger dampers, the number of actuator per damper can be selected 2 or more based on manufacturer selection to ensure smooth and reliable operation. Actuator set suitable for Fire damper of area upto 1 sqm, with other requirements as mentioned above.

16

-

-

... More
Control Panel compitable for output voltage of 230V for set of minimum of 7 fire dampers

2

-

-

... More
3 core, 1.5 sqmm shielded power and communication control cable between the panels and actuators.

450

-

-

... More
FIRE DAMPER WITH OPPOSED BLADE (Fusible Link type)- Extended Sleeve type - with 450 mm sleeve The Fire damper as per UL 555 (SEALED & STAMPED), outer shell constructed with 16G thick galvanized steel frame and the blade/Leaf with 16G thick GSS. And with necessary flanges for connection as per specifications and drawings. The damper shall be of class 2 fire rating.

6

-

-

... More
With Fusible Link & spring mechanism, the damper shall be held open by a replaceable fusible link rated at 74 deg C.

45

-

-

... More
STREAM SPLITTER DAMPER (Exposed Ducting) The stream splitter damper shall be constructed out of zinc coated steel with manual adjustment of blades to control air flow. Shall be used for the supply air grilles & registers as per the drawings & specifications.

2

-

-

... More
COLLAR DAMPER - OPPOSE BLADE TYPE The collar damper shall be constructed out of extruded aluminum alloy with multiple blade of oppose blade type. Shall be used for the supply air diffuser & grilles as per the drawings & specifications.

22

-

-

... More
GRILLES - Al. The supply & installation of higher grade Aluminum Extruded powder coated grilles with blade deflection of 0 & 15 deg

38

-

-

... More
CURVED GRILLES - Al. The supply & installation of higher grade Aluminum Extruded powder coated curved grilles.

2

-

-

... More
SPILL AIR PLENUM BOX. The supply & installation of FACTORY FABRICATED spill air boxes made out of 0.8mm thick GI sheet with necessary spigot connection for fixing flexible duct and suitable collar for connecting to various neck diffuser / slot diffuser. The box should be internally insulated with 10mm thick open cell nitrile rubber of class '1' material. The box size shall be as mentioned below.The cost shall be inclusive of necessary chain support Box size of 450x450x300 mm and equivalent required rectangular sizes. (For 375x375 neck size)

120

-

-

... More
Box size of 525x525x400 mm and equivalent required rectangular sizes. (For 450x450 neck size)

10

-

-

... More
Box size of 1100x250x400 mm and equivalent required rectangular sizes. (For 300X1200mm outer size)

10

-

-

... More
PLAQUE DIFFUSER - Al. SQUARE The diffuser shall be of removable core type and constructed with high grade aluminum extruded alloy and with powder coated finish (without collar damper). All diffusers shall have a continuous square neck of minimum 32mm height suitable for fixing spill air box 600X600 OUTER SIZE

140

-

-

... More
LOUVERS - Al. High grade aluminum extruded Louvers for Fresh air intake & Exhaust air exit at outer wall. The louver shall be of powder coated finish. The louver shall be with 45 deg deflection and shall prevent rain water entry through the louvers. High grade aluminum extruded Louvers for Fresh air intake with 20-micron washable filter suitable for external application. Louvers shall be powder coated finish.

10

-

-

... More
EXHAUST DISC VALVE - Al. Exhaust valves constructed from steel spinning with powder coated finish. The valve should provided high initial resistance with wide throttling capability to offset the high system resistances. And finished with powder coating. Neck size: 150mm dia.

120

-

-

... More
Wired supports for exposed hanging ducts from the existing structural truss work. (Only Supply air duct in seating area to be considered)

1000

-

-

... More
HVAC related all kind of civil works including grouting,pedastals, all leads & lifts, scaffolding, curing,chipping,filling, opening and closing of wall etc

1

-

-

... More
MS supporting works for laying piping, ducting, cable tray in terrace, Plant Room, shafts and wherever necessary

8000

-

-

... More
VARIABLE FREQUENCY DRIVE STARTER PANEL The Electrical starter panel shall comprise incoming MPCB, VFD, by-pass starters with all type-2 contactors, relays, single phase prevention, voltage imbalance protection, phase indicators with key switch, ON / OFF / TRIP indicators, Auto-OFF-Manual selector switch, Earth leakage relays. The panels shall be with necessary relays and potential free contacts required for complete control The starter panel shall have necessary potential free NO/NC contacts for integrating with the fire alarm panel. On receiving signal from the fire panel, the fan shall trip automatically. The Panel shall be of IP 54 protection for indoor application, with by pass starter arrangement. For up to 5.5 KW motor the starter / by-pass starter shall be of DOL type and for motors of 7.5 KW and above Star-Delta Starter shall be provided. The construction of the electrical panel casing shall be with 2mm thick GI sheet, powder coated with Siemens grey colour. The panel shall have access door, Gland plate, supporting frames for mounting etc.,panel shall be located inside kitchen and push button station at terrace The variable frequency drive (VFD) shall be supplied with IP 21 protection, digital display and with necessary active harmonic filter to prevent the injection of harmonics into the electrical system. The VFD shall be capable of regulating the speed of the fan from 120 % to 20% of rated fan speed at the specified rated flow & static. The VFD capacity shall be as per the actual motor selection of the fan. VFD shall have necessary in-built capacitors for power factor corrections to achieve 0.95 as power factor. 7.5 KW - FOR DOAS left/right wing

2

-

-

... More
5.5 KW - FOR FUME HOOD upper / lower wing

2

-

-

... More
STARTER PANEL - STAR DELTA Star delta starter panel with Outer panel, MPCB, contactors, Relays, phase indicators with key switch, ON, OFF push button switch, ON,OFF, TRIP indicators, Digital Ammeter & Voltmeter with selector switches, Auto-Off-Manual selector switch, etc., The Panel shall be with IP 54 protection. The construction of casing shall be with 1.6mm thick CRCA sheet steel powder coated with Siemens grey. And shall be provided with necessary door, Gland plate, supporting plate, etc., The Technical Specification of the starter panel with wiring diagram shall be provided for Consultant concurrence before procurement. Starter panel with A/M switch and potential free contacts for BMS control required. TPN MCB to be provided near the unit. Starter panel shall be compitable to integrate with the fire alarm panel such that the power is supplied automatically on receiving fire signal. Equipment schedule shall be refered for Panel ratings 15.5KW-FOR IDEC

2

-

-

... More
11 KW - FOR STP FRESH AIR FAN

1

-

-

... More
7.5 KW - FOR STP EXHAUST AIR FAN

1

-

-

... More
DOL starter panel with Outer panel, MPCB, contactors, Relays, phase indicators with key switch, ON, OFF push button switch, ON,OFF, TRIP indicators, Digital Ammeter & Voltmeter with selector switches, Auto-Off-Manual selector switch, etc., The Panel shall be with IP 54 protection. The construction of casing shall be with 1.6mm thick CRCA sheet steel powder coated with Siemens grey. And shall be provided with necessary door, Gland plate, supporting plate, etc., The Technical Specification of the starter panel with wiring diagram shall be provided for Consultant concurrence before procurement. Starter panel with A/M switch and potential free contacts for BMS control required. TPN MCB to be provided near the unit. Starter panel shall be compitable to integrate with the fire alarm panel such that the power is supplied automatically on receiving fire signal. 3.75 KW-toilet ex fans/pump exhaust fan

2

-

-

... More
2.2 KW- csu/pantry ele exhaust fans

3

-

-

... More
1.1 KW- csu

2

-

-

... More
0.75KW-fresh air fans

3

-

-

... More
0.55 KW- exhaust fans

2

-

-

... More
0.375 KW-ehaust fans

3

-

-

... More
0.22 KW- exhaust fans

1

-

-

... More
ELECTRICAL WORKS SITC of 4Cx25sqmm XLPE power cable(Cu) from Equiment to starter panel.cable rating shall be selected as per approved motor kw rating.Necessary earthing shall be provided-

100

-

-

... More
SITC of 4Cx16sqmm XLPE power cable(Cu) from Equiment to starter panel.cable rating shall be selected as per approved motor kw rating.Necessary earthing shall be provided

150

-

-

... More
SITC of 4Cx10 sqmm XLPE power cable(Cu) from Equiment to starter panel.cable rating shall be selected as per approved motor kw rating.Necessary earthing shall be provided

200

-

-

... More
SITC of 4Cx4 sqmm XLPE power cable(Cu) from Equiment to starter panel.cable rating shall be selected as per approved motor kw rating.Necessary earthing shall be provided

100

-

-

... More
SITC of 4Cx1.5sqmm power cable from toilet fan to push button staion.

20

-

-

... More
SITC of 2Cx2.5sqmm power cable from scrubber to starter panel.

40

-

-

... More
Radiant Ceiling baffles Supply, installation, testing & commissioning of baffle with powder coating finish, complete accessories like supports, piping connector etc. Having maximum and minimun output of 110 W/Sq.m-120 W/Sq.m Preferabaly more. Size of the baffles: Length: varies based on the zones Height of Baffles: 150 to 250 mm Baffle Chilled water operating temperature shall be 16/20 deg C (Chilled water inlet at 16 deg C to baffles and outlet at 20 deg C) Material of Baffles: Baffles : Aluminium pipes : Copper/PEX/PERT Header pipe: Copper/PEX/PERT Insulation : For copper pipe of 25mm ID thickness 13 mm./ For PEX/PERT pipe 19mm ID with thickness of 13mm. (Copper Pipe Size: 15 mm diameter and 0.7 mm thickness) embedded inside baffles/ aluminium tube of OD 12 mm

3450

-

-

... More
Supply and Installation of Copper Header pipe for Baffles 22.7 mm diameter and 0.9 mm thick. Cost shall be inclusive of dieletric union connection between MS pipe and copper pipe or MS pipe to Brass for PEX / PERT pipe connection.

1150

-

-

... More
Supply and Installation of Class 'O' Nitrile 13 mm Thickness.

1150

-

-

... More
Ceiling Frame Supply & Installation of G.I 'C ' type frames with supports (Nut, bolts, threaded rods Anchor fasteners & etc). for the radiant baffles.

7050

-

-

... More
MANUAL BALANCING VALVE WITH INSULATION Necessary manual balancing valve with fittings

160

-

-

... More
BUILDING AUTOMATION SYSTEM (BAS) BACNET IP BASED DDC CONTROLLERS Automation stations / DDC Controller with I/O module etc., The controllers shall be NativeBacNET IP based. The controller shall be with 32 bit microprocessor, working in standalone or networkable mode, with real time clock and historical database of min 3600 events & Peer to Peer Communication. The controller shall support minimum of 8 trend log objects, 10 program areas and 8 PID loop objects. The DDC's shall store programs and program parameters in non volatile memory. Number of controllers shall be as mentioned against each area of control. The indoor DDCs shall be with suitable IP 54 enclosure complete with all wiring and accessories. The outdoor DDC shall be with suitable IP 65 enclosure with canopy & floor mount arrangements complete with all wiring and accessories. [ Note: The selection of DDC controller shall be as per I/O schedule and the quantity of DDC controller shall be as mentioned below, no deviation shall be acceptable] LCES-IISC-DDC-01 (Outdoor Panel with IP65 enclosure)

1

-

-

... More
LCES-IISC-DDC-02 (Outdoor Panel with IP65 enclosure)

1

-

-

... More
LCES-IISC-DDC-03 (Outdoor Panel with IP65 enclosure)

1

-

-

... More
LCES-IISC-DDC-04

1

-

-

... More
LCES-IISC-DDC-05

1

-

-

... More
LCES-IISC-DDC-06

1

-

-

... More
LCES-IISC-DDC-07

1

-

-

... More
LCES-IISC-DDC-08

1

-

-

... More
LCES-IISC-DDC-09

1

-

-

... More
LCES-IISC-DDC-10

1

-

-

... More
INTEGRATION REQUIREMENT Integration of the below mentioned Equipments: Necessary data exchange hardware / software points units required to integrate the below third party systems and to convert to open protocol BACnet over I/P and the ACMV vendor to accommodate the software address required for integration. Refer I/O Summary for total quantities of each component listed below. Chiller Plant Manager

1

-

-

... More
VRF

1

-

-

... More
Variable Air Volume

1

-

-

... More
Variable Primary Pump Logic Controller

1

-

-

... More
Variable Frequency Drive

1

-

-

... More
PAC

1

-

-

... More
Diesel Generators

1

-

-

... More
UPS

1

-

-

... More
Energy Meters

1

-

-

... More
Fire alarm panel

1

-

-

... More
Solar PLC Soft Integration

1

-

-

... More
Water Meters

1

-

-

... More
BTU Meter

1

-

-

... More
FIELD DEVICES Differential pressure switch to monitor the Fan Run Status & Filter status.

20

-

-

... More
Duct static pressure sensor with necessary control cabling in 19mm PVC conduit to terminate to the respective VFD drive of the AHU's. ( Pressure Range -1 - 0 to 500 pa and Range 2 - 0 to 1000 pa.( Field adjustable) (Total control cabling quantity shall be approximately 75 rmt per sensor). The VFD shall able to operate based on 0 to 10V / 2 to 20mA signal from Differential pressure switch fixed on the Supply air duct

4

-

-

... More
Supply & installation of ceiling mounted Hydrogen (H) detectors/ Sensors for battery room. The sensor Shall exhibits a highly sensitive, selective, and rapid response to the presence of hydrogen in ambient air. It reliably measures H2 concentrations over a wide range of temperature and humidity variation and provides a repeatable response, even in the presence of other combustible gases. The sensor shall be capable of measuring minimum 0- 4 % H2 level in air (100% of the LFL). Sensor shall provide 4-20mA or 0-10VDC output

1

-

-

... More
Duct mount Temperature Sensors with all mounting accessories.

10

-

-

... More
Explosion proof Oil/Fuel level transmitter for measuring DG Tank Fuel Levels

3

-

-

... More
CABLES AND CONDUITS FRLS 2 C X 1.0 SQ. MM - unarmoured , multistrand, unscreened overall PVC cables [For digital command and status feedback]

6100

-

-

... More
FRLS 4 C X 1.0 SQ. MM - unarmoured , multistrand,unscreened overall PVC cables [For digital command and status feedback]

8400

-

-

... More
FRLS 2 C X 1.0 SQ. MM - unarmoured , multistrand, screened overall PVC cables

1000

-

-

... More
FRLS 2 C X 1.5 SQ. MM - unarmoured , multistrand,twisted,screened overall PVC cables for communication

15000

-

-

... More
FRLS 2 C X 1.5 SQ. MM - armoured , multistrand,twisted,screened overall PVC cables for communication

500

-

-

... More
FRLS 4 C X 1.0 SQ. MM - unarmoured , multistrand, screened overall PVC cables [For analogue control and feedback]

1000

-

-

... More
FRLS 4 C X 1.0 SQ. MM - armoured , multistrand, screened overall PVC cables [For analogue control and feedback]

500

-

-

... More
FRLS 6 C X 1.0 SQ. MM - unarmoured , multistrand, unscreened overall PVC cables [For analogue control and feedback]

3000

-

-

... More
Cat 6 unarmoured, bus cable for connecting Gateway, router and PC to the network

5000

-

-

... More
Optic Fibre Cable

2000

-

-

... More
25 mm dia PVC Conduit.

15000

-

-

... More
20 mm dia PVC Conduit.

20000

-

-

... More
CABLES TRAYS Supply, installation of perforated cable trays with threaded rod supports, anchor fastners etc., inclusive of Supporting brackets/structures for cable trays,switch boards etc., fabricated out of MS angle,channel,plates and flats duly painted and complete with necessary hardware. 300 mm wide

175

-

-

... More
200 mm wide

175

-

-

... More
150 mm wide

175

-

-

... More
PVC TRUNKING - FOR INTERIOR CONDUITS Supply and installation of PVC trunking with cover between BMS room false ceiling and BMS components. 175 mm wide

30

-

-

... More
300 mm wide

30

-

-

... More
SOFTWARE SYSTEM Enterprise Management Software (EMS) with standard modules like asset management system, user and locatiion module and Smart Facilty Managment and Mobile app users' as default. Following additonal modules shall also be considered as part of this line item. Refer System Global Architecture & Technical Specification for more details. Refer Tender specification for more details and compliance requriement C2O (Commissioning to Operate)

12

-

-

... More
Gateway server to be deployed On-Premises by BMS and CCTV vendor VM Qty:2 (BMS and CCTV) Setup: Active CPU Power (GHz): 4 vCPU Xeon @ 2.5GHz RAM Size (GB):16 Storage Size (GB):1 TP OS:Windows 2016 standard one Software: 1. .NET FW 4.5 or above 2. Powershell V4 or above Note: Static IP: BMS contractor to install the gatway server in the device subnet and assing the static ip address Static IP: CCTV contractor to install the gatway server in the CCTV camera subnet and assing the static ip address Minimum Bandwith 10Mbps

2

-

-

... More
Firewall to be selected and considered as part of the hardware part of the system.

1

-

-

... More
Cloud Management System (CMS) - Consider 3 months subscription ( 2months prior to commissioning and 1 months post commissioning) for 15000 points includes Web server, Redis Server, Database Server, Trend Server Refer Tender specification for software and server sizing

1

-

-

... More
LCD SCREEN MOUNTED ON COMMON FRAME Dimension Size: 42" Display Area: 1209.6 x 680.4 mm View Angle: 178° (H) / 178° (V) Backlight Source: LED Contrast Ratio: 3500:1 Physical resolution: 1920 x 1080 (Full HD) Display Colours: 16.7 M Bezel width: 3.5mm (U/L), 1.8 mm (R/B) MTBF: 50000 hrs Interface Signal Input: VGA,DVI,HDMI, CVBS Singal Output: CVBS Control Input: RS232 Control Output: RS 232 x 2 Working Conditions Power consumption: 200 Watts Power Supply: AC -1Ph, 50 Hz, 220 -240 V Operating Temperature: 0 to 50° C Operating Relative Humidity: 20 to 90% ( non-condensing) Note: Vendor shall take prior approval for monthly subscription in the case of post commissioning period gets extended.

4

-

-

... More
BMS Engineering commissioning & Documentation and graphic development Charges

1

-

-

... More
VERTICAL TRANSPORTATION Supply,Installation, testing & commissioning of following Elevators. The quoted rate shall be inclusive of 36 months guarantee period and free maintenance from the date of handing over. ELEVATOR TYPE A : 8 Passenger Fire Lift complete as per technical specifications in Annexure and details.

1

-

-

... More
ELEVATOR TYPE B : 15 Passenger Lift complete as per technical specifications in Annexure and details.

1

-

-

... More
ELEVATOR TYPE C: 15 Passenger Lift complete as per technical specifications in Annexure and details.

1

-

-

... More
ELEVATOR TYPE D : 1.5 Tonne Service Lift complete as per technical specifications in Annexure and details.

1

-

-

... More
Supply, Installation, testing & Commissioning of the following gases including piping from centralised gas bank within the building to respective end points at wet labs across the building. 4 Nos cylinders of each gas to be considered. i) UHP Nitrogen Gas ii) Oxygen Gas iii) Argon Gas iv) Carbon Dioxide Gas v) Hydrogen vi) Installation, testing & commissioning of compressed air including piping from centralised compressor room within the building to respective end points at wet labs.

1

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.