Bengaluru Metropolitan Transport Corporation Tender
Karnataka, also known as Karunadu, is a state in the southwestern region of India. Karnataka was formed originally as Mysore State on 1st November 1956 and currently is the biggest state in south India. Its capital and largest city is Bengaluru. It covers an area of 191,791 km2 (74,051 sq mi) and is the sixth largest state by area comprising 31 districts. Karnataka is also a state of multiple languages; Kannada being the official and most widely spoken language in Karnataka. Other languages spoken in the state include Tamil, Telugu, Malayalam, Kodava, Konkani and much more.Karnataka tenders are issued by the government of Karnataka, public & private sector organisations. The state government issues majority of the Karnataka tenders, which are for goods and services including construction, road and bridge construction, IT services, engineering services, medical services, educational services amongst many others. Bidassist is one of the largest eprocurement portals, which offers all government tenders from across the world in one place. Bidassist offers information on all Karnataka tenders and other state and authority tenders in no time. Bidassist is a platform where users can look for various Karnataka tenders as well as other tenders.
Bengaluru Metropolitan Transport Corporation - BMTC Tender
Electrical and Electronics
Electrical Works
Opening Date13 Nov 2024
Closing Date20 Nov 2024
Tender Amount₹ 21,18,421.17
Costs
EMD
₹ 50,000Document Cost
Refer DocumentsTender Fee
₹ 530
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
BMTC/2024-25/EL/WORK_INDENT109Bid Award Id
ViewTender No
BMTC/2024-25/EL/WORK_INDENT109Tender Authority
Bengaluru Metropolitan Transport Corporation ViewPurchaser Address
-Website
http://https://www.mybmtc.karnataka.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
Others - Tender Notification
BOQ Items
... More
code04 - Do- 4 mm2 2.3.4
1200
69
83160
... More
code05 - Supplying and fixing surface/flush mounting unbreakable PVC modular box suitable for mounting modular switch plates with due groove cutting in Brick/C.C wall, including necessary rawl plugs, Machine/NF screws etc., complete. 1-2 Way 3.3.1
2
113
226.6
... More
code06 - Do- 8 Way 3.3.5
10
240
2409
... More
code07 - Do- 10-12 Way 3.3.6
8
287
2296.8
... More
code08 - Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. 1 to 2 Module 3.5.1
2
150
301.4
... More
code09 - Do- 8 Module 3.5.5
10
312
3124
... More
code10 - Do- 10-12 Module 3.5.6
8
378
3027.2
... More
code11 - Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. 6A One Way Switch 3.6.1
50
112
5610
... More
code12 - Do- 6A Three Way socket 3.6.3
29
188
5454.9
... More
code13 - Supplying fully automatic star-delta starter unit push button type with suitable wires, 3 contactors, one adjustable thermal timer mounted on a common base plate held in steel enclosure for use on 400/440 V 3 phase and wired after fixing to the existing wooden board for motor. 5.2.1
2
8200
16401
... More
code14 - Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898. 6-32 A SP 5.18.1
60
456
27390
... More
code15 - Do- 6-32 A DP 5.18.4
30
812
24387
... More
code16 - Do- 6-32 A TPN 5.18.7
23
1888
43440.1
... More
code17 - Do- 50-63 A TPN 5.18.9
20
3396
67936
... More
code18 - Supplying and fixing Moulded Case Circuit Breaker (MCCB) over the existing wood/panel board using necessary screws, bolts, nuts, necessary phase separators, handle and wiring complete. Protection of Overload and Short circuitwith adjustable thermal magnetic release, Micro processor release shall have Earth Fault as per IS/IEC 60947-2 . (Icu=100% lcs). In 4P MCCB, all Poles should have protection for Short-Cicrcuit/Over Load. For Microprocessor MCCBS Facility for segregating Priority and Non-Priority loads must be available in the MCCB. MCCB shall be provided with double insulation (insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open). Multi-pole breakers shall be designed to break all the poles simultaneously and they shall have a single mechanism. THREE Pole 100 A 25 kA 5.15.1
4
6694
26778.4
... More
code19 - Do- 125 A 25 kA 5.15.2
1
9457
9457.8
... More
code20 - 200 A 25kA 5.15.4
2
15988
31977
... More
code21 - 500-630 A 50 kA 5.15.19
4
46088
184355.6
... More
code22 - Supplying and fixing regular MCB distribution boards on wall/ood board / flush mounting using required clamps, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase/3 phase/single door with powder coated painting Made out of 14 SWG MS enclosure. II - Double Door 8 Way SP & N 5.19.8
4
2039
8157.6
... More
code23 - Supplying and fixing regular MCB distribution boards on wall/ood board / flush mounting using required clamps, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase/3 phase/single door with powder coated painting Made out of 14 SWG MS enclosure. III - Double Door 4 Way TP & N 5.19.11
1
4441
4441.8
... More
code24 - Do- 8 Way TP & N 5.19.13
3
6700
20100.3
... More
code25 - Supplying of .....feet -PVC Batten with integrated LED tube W with high quality diffuser with Life of 25000 burning hours & 70% lumen maintenance with CRI Greater than 80. Power Input: 220-240Vat 50/60Hz & Power factor Greater than0.9 along with CE approved. 2 years Warranty against any manufacturing defect working under standard electrical condition. LED light fitting 1 x 4' - 20/22 W 11.3.2
10
759
7590
... More
code26 - Do- LED light fitting 1 x 4' - 36/40 W 11.3.3
100
1395
139590
... More
code27 - Fixing all types and all capacities of fluorescent /false ceiling / spot light / CFL / LED fittings indoor on the wall/ ceiling / rafters / girders using 23/0.0076" twin twisted PVC insulated wires, required Nos of round blocks and clamps. On wall/ ceiling / Rafter / Girders 13.7.1
100
134
13420
... More
code28 - Supply of LED Streetlight luminaire with pressure die cast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of anti glare clear diffuser with Injection moulded polycarbonate material, delivering superior light output Rated life Burning Hrs 50000 hr at Lumen Maintenance of 70%, maximum light intensity should be between 60 degrees to 70 degrees. CCT Greater than 5500K, IP66 optical and electrical compartment & impact resistance of complete luminaire Greater than IK08. Power Factor Greater than0.9 with mains, Surge Protection- Min 5KV along with Over voltage/ Overload, short circuit/ miss-wiring protection. Compatible for pole mounting with outer dia of 40mm to 50mm. Universal Voltage driver to operate wide voltage range from 100V to 270V 50/60Hz application. Compliance to IS 10322/IEC 60598, LM 79 & LM 80 Adherence with RoHS. UL approved MCPCB. Top access street light with single screw to ensure ease of maintenance at the sight site location with minimized minimal tools. LED Light fixture with ........W System Power consumption. LED EfficiencyGreater than1301m/w, nominal CRI Greater than75. Luminaire manufacturer should have in-house facility accredited by NABL/CPRI & any Government certified agency & Design & Development facility certified by ISO 9001:2008. Housing with supplier word mark /name shall be Engraved / Embossing on the die cast housing/ Body part. Warranty of 2 Years against any manufacturing defect working under conditions. LED Streetlight 90 W 11.8.4
10
9746
97460
... More
code29 - Supplying and Fixing of........mm dia class A GI pipe bracket upto 2 ms long bent at suitable angle and fixing to this bracket street light fitting of all capacities to GI or GI or rail or RCC pole / wall using suitable clamps, bolts, and nuts and wiring using suitable capacity wires. Using 32mm dia G.I.Pipe. 13.1.2
5
1149
5747.5
... More
code30 - Supply of LED floodlight luminaire with pressure die cast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of anti glare clear diffuser with Injection moulded polycarbonate/clear glass material, delivering superior light output Rated life Burning Hrs 50000 hr at Lumen Maintenance of 70%, CCT Greater than 5500K, IP 66 optical and electrical compartment & impact resistance of complete luminaire Greater than IK08. Power Factor Greater than0.9 with mains, Surge Protection- Min 5KV along with Over voltage/ Overload, short circuit/ miss-wiring protection. Compatible for pole mauling with outer dia of 40mm to 50mm. Universal Voltage driver to operate wide voltage range from 100 V to 270V 50/60Hz application. Compliance to IS 10322/ IEC 60598, LM 79 & LM 80 Adherence with RoHS. UL approved MCPCB. Top access street light with single screw to ensure ease of maintenance at the sight site location with minimized minimal tools. LED Light fixture with W System Power consumption. LED EfficiencyGreater than 1301m/w, nominal CRI Greater than75. Luminaire manufacturer should have in- house facility facility accredited by NABL / CPRI & any Government certified agency & Design & Development facility certified by ISO 9001:2008. Housing with supplier word mark / name shall be Engraved / Embossing on the die cast housing / Body part Warranty of 2 Years against any manufacturing defect working under standard electrical conditions as mentioned above should be given by LED manufacturer & Cree/Nichia/ Lumileds/Osram make LED Source. LED Floodlight 150W 11.9.4
6
13739
82434
... More
code31 - Fixing halogen/metal halide /SVL/IL/LED floodlight fitting over existing pole / wall ceiling including clamps, bolts, nuts and wiring using suitable capacity wires. 13.5
6
178
1069.2
... More
code32 - Supplying, fixing and wiring Electronic Trivector Meter (ETV) 5 to
20A single phase Class-1 Accuracy with Temper Proof Energy Meter. 5.30
4
1518
6072
... More
code33 - Supplying and fixing Electronic Trivector Meter (ETV) suitable for operation LT operation and -CT operated meter in polycarbonate body in class 0.5 accuracy as per IS 14697 and completely wired. 5.31
2
4829
9658
... More
code34 - Supplying of multi function digital meter with three line back light LCD type display for voltage, Current, frequency, Power, power factor, kVA, kWH, kVAR suitable for 3 phase, 4 wire LT network with IP 54 degree of protection and completely wired as required with communication Port and Class 0.5s accuracy 5.33
3
10246
30739.5
... More
code35 - Supplying, fixing and wiring 50/5 to 400/5A 5VA burden Current Transformer Class 0.5 accuracy with Tape Wound. 5.34
12
618
7418.4
... More
code36 - Supplying, fixing, wiring, earth electrode for grounding conduits, I.C. cutouts and other equipment's on the meter board using 40 mm dia 2.90 mm thick GI pipe 2.5m long buried in a pit . The pit should be filled with equal proportion of salt and charcoal 150 mm all-round the pipe to complete depth. The connection from the pipe to the conduit etc., is to be established through GI wire of size as per lSI specification 7.3.3. of IS 732 using 12 mm dia bolts, nuts, washers and check nuts etc., the pipe shall have 16 through holes of 12 mm dia. 12.56
8
3861
30888
... More
code37 - Supplying fixing and wiring earth electrode for grounding of lifts, transformers, DG sets etc. using 40 mm dia 2.9 mm thick 2.5m long GI pipe with GI funnel with mesh and suitable size reducer fixed on the top of the earth electrode.The funnel should be enclosed in a CC chamber of 400x400x400 mm with a cast iron cover. The earth electrode shall have staggered holes of 12 mm dia and the electrode should be covered 150 mm all- round with alternate layers of salt and charcoal from the bottom of the CC chamber. The connection from the electrode is to be established through GI strip using GI bolts and nuts. 12.57
6
4681
28089.6
... More
code38 - Supply and fixing GI/Copper strips for grounding connections, using necessary fixing materials as required. 25 x 6 mm GI strip 12.58.3
60
140
8448
... More
code39 - Do- 25 x 3 mm Copper strip 12.58.7
20
627
12540
... More
code40 - Do- 600 x 600 x 3 mm Copper plate
12.58.11
6
8163
48978.6
... More
code41 - 1.1 kV, XLPE or Heat resistant PVC insulated, PVC exutruted Inner Seath Armoured LTUG Cable as per IS-1554 (Part- 1) or IS-7098 Part-1, Armouring strip thickness and resistivity as per IS- 3975 16 Sqmm, 4 Core, (11 GI Strips - 4 x 0.8 mm) 32.05
0.3
156026
46807.86
... More
code42 - Do- 25 Sqmm, 3.5 Core, (12 GI Strips - 4 x 0.8 mm) 32.07
0.3
153503
46051.17
... More
code43 - Do- 50 Sqmm, 3.5 Core, (16 GI Strips - 4 x 0.8 mm) 32.11
0.4
196870
78748.12
... More
code44 - Laying LTUG cable of 2.5 to 25 Sqmm (Single/3.5/4 Core) 20.05
0.6
1305
783.42
... More
code45 - Laying LTUG cable of 35 to 95 Sqmm (3.5/4 Core) 20.06
0.4
2623
1049.4
... More
code46 - Heavy Duty Copper Terminal Long Barrel 25 Sqmm Copper Terminal, Apprx Wt: 11 Gm 59.01
40
29
1188
... More
code47 - Repairs and Reconditioning of 11KV class single coil/multi coil Conventional (Aluminium wound) and 3/4/5 Star Rated failed Distribution Transformers of various Capacities and Conversion of CSP to Conventional bolt & nut type on lumpsum percentage (%) basis (Material, Labour & Salvage) at Transformer repair center Note: 1.The rates are exclusive of Transformer Oil 2. The rates are for repair of 3 Coils 3. Released Oil has to be returned to the stored by concerned ESCOM officers 4. The released winding will be retained by the repair agency. (The salvage value is added in the rates)500 kVA, Aluminium Wdg, 3/4/5 Star
1
103266
103266.9
... More
code48 - Filtration of oil using filter set of the contractor to bring the insulation value to I.E. specification
300
7
2310
... More
code49 - EHV Grade unused uninhibited mineral insulating oil in new steel barrels of 210 litres capacity strictly confirming to IEC 60296 (latest version) (Greater than170kV class) 1.15
0.5
138578
69289
... More
code50 - Servicing of Air Circuit Breaker by isolating the breaker, cleaning of the ACB, cleaning of old grease, dust and oil content, cleaning of carbon from main contact terminal, cleaning of cluster contact studs, rail wheel and applying grease oil to rail. Cleaning the carbon on the Contact Mechanism and energizing including Microprocessor Logic testing including replacement of ELR, Moving contacts and relay as required., complete
8
24000
192000
... More
code51 - Supplyof Three Phase 50 Hz, 7.5 KW/10 HP Monoblock Openwell submersible pumpset made of cast iron body, stainless steel strainer with 50-75 mm discharge outlet including transport to the site in Bengaluru limits
1
45432
45432
... More
code52 - Erection charges of openwell pumpset. 13.3.19
1
2200
2200
... More
code53 - Transformer Servicing: Draining out the oil from Transformer, Removal of cable box, Removal of Terminal cables, Replacement of Bushing gasket, Oil seals (3 bushing side), Refitment of cables, stopping oil leakage, Refilling Oil to the transformer, Cleaning of all Terminal contacts, Removal of Carbon deposits, Tightening of Bolts and nuts, cleaning and Lubrication of Moving parts, rectification of contact Mechanisms and Tap positions and replacement of moving parts complete.,
1
21200
21200
... More
code54 - Servicing of 1100 KVA Diesel Generator including Draining out the lubricant, Removal of Terminal cables, Replacement of belts, gasket, Oil seals etc., filling of compatible lubricants, Refitment of cables, stopping oil leakage, Cleaning of all Terminal contacts, Removal of Carbon deposits, Tightening of Bolts and nuts, cleaning and Lubrication of Moving parts, rectification of contact Mechanisms and replacement of moving parts complete., with B-check of Diesel Generator sets.
1
195000
195000
Evaluation Notes How It Works ?