Jharkhand Industrial Infrastructure Development Corporation Tender

Search from across the categories, cities, and authorities to find the latest Jharkhand tenders. Every Jharkhand tender is curated from credible sources of government websites (eProcurement Jharkhand portal) and newspapers, thus ensuring the credibility of the information presented to you. For more information on Jharkhand tender bidder registration, the login process and more read the FAQs section on this page.

Jharkhand Industrial Infrastructure Development Corporation - JIIDC Tender

Works
Civil And Construction
Water Storage And Supply
Eprocure
Opening Date27 Mar 2023
Closing Date3 Apr 2023
Tender Amount₹ 28,40,63,939 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Initial lift

227.5

-

-

... More
1st lift

125.62

-

-

... More
2nd lift

106.54

-

-

... More
3rd lift

89.04

-

-

... More
4th lift

73.1

-

-

... More
5th lift

58.74

-

-

... More
6th lift

45.94

-

-

... More
Earthwark in excavation of foundation trenches of toe wall spilllway ,head regulator intake well , outlet etc. as per designed section in ordinary or soft rock (where blasting is not needed ) (Vide classification of soil item-C) with disposal of soil (beyond 50M, from the edge of the trenches) with initial lead of 150 m. and lift of 1.5 m as per specification and direction of E/I . 7th lift

18.69

-

-

... More
Earthwark in excavation of foundation trenches of toe wall spilllway ,head regulator intake well , outlet etc. as per designed section in hard rock where blasting is needed and stacking properly in approved stack size in approved stack yard beyond 50m from the edge of the trenches in the country side) with initial lead of 150m. and initial lift of 1.5m. as per specification and direction of E/I (Excavated hard rock size should not be more than 150 lb.).

16.71

-

-

... More
Providing P.C.C M-15 with in nominal mix of (1:2:4) in foundation with approved quality of stone chips 20 mm to 6 mm size graded and clean coarse sand of F.M 2.5 to 3 ) including , screening ,shuttering ,mixing cement concrete in mixture and placing in position vibrating striking curing taxes and royality all complete as per building specification and direction of E/I.

4.82

-

-

... More
Providing and laying in situ cement concrete of trap / granite / quartzite / gneiss metal for RCC work in foundation like raft , grillage , strip foundation and footing of RCC columns and steel stanchions including normal dewatering , plywood from work bully / steel propups compaction , finishing and curing etc. complete . (By weigh batching and mix design for M-25 and M-30 only . Use of L& T , A.C.C. , Ambuja , Birla Gold , Manikgad Rajasree etc. cement is permitted .) (excluding M.S or Tor For RCC M-20

14.6

-

-

... More
Providing and casting in situ cement concrete of trap / granite / quartzite / gneiss metal of approved quality for RCC work as per detailed drawing and designs or as directed by Engineer - in- charge including normal dewatering centering plywood form work , bully/steeel prop-ups compaction finishing the formed surfaces with CM 1 : 3 of sufficint minimum thickness if special finish is to be provided and curing etc. complete . (By weigh batching and mix design for M-25 and M-30 only . Use of L& T , A.C.C. , Ambuja , Birla Gold , Manikgad Rajasree etc. cement is permitted .) (excluding M.S or tor reinforcement ) for RCC M-300 grade vertical walls

67.65

-

-

... More
Providing and casting in situ cement concrete of trap / granite / quartzite / gneiss metal of approved quality for RCC work as per detailed drawing and designs or as directed by Engineer - in- charge including normal dewatering centering plywood form work bully /steel prop-ups , compection finishing the formed surface with CM1:3 of sufficient minimum thickness if special finish is to be provided and curing etc. complete ((By weigh batching and mix design for M-25 and M-30 only . Use of L& T , A.C.C. , Ambuja , Birla Gold , Manikgad Rajasree etc. cement is permitted .) (excluding M.S or tor reinforcement ) for RCC M-250 grade Beam

2.73

-

-

... More
Providing and casting in situ cement concrete of trap / granite / quartzite / gneiss metal of approved quality for RCC work as per detailed drawing and designs or as directed by Engineer - in- charge including normal dewatering centering plywood form work , bully/steeel prop-ups compaction finishing the formed surfaces with CM 1 : 3 of sufficint minimum thickness if special finish is to be provided and curing etc. complete . (By weigh batching and mix design for M-25 and M-30 only . Use of L& T , A.C.C. , Ambuja , Birla Gold , Manikgad Rajasree etc. cement is permitted .) (excluding M.S or tor reinforcement ) for RCC M-20 grade. For roof slab

6.8

-

-

... More
Providing RCC M 250 with nominal mix in columns with approved quality of stone chips 20mm to 6mm size graded and clean coarse sand of FM, 2.5 to 3 including shuttering, mixing cement concrete in mixer and placing in position, vibration, striking, curing (but excluding the cost of reinforcement ) taxes and royalty all complete job as per specification and direction of E/I.

2.25

-

-

... More
Providing RCC M - 20 with nominal mix in beams of all types with approved quality of stone chips 20mm to 6mm size graded and clean coarse sand of FM, 2.5 to 3 including screening, shuttering, mixing cement concrete in mixer and placing in position, vibration, striking, curing (but excluding the cost of reinforcement ) taxes and royalty all complete job as per specification and direction of E/I.

5.15

-

-

... More
Providing RCC M - 20 with nominal mix in roof slab with approved ) of stone chips 20mm to 6 mm size graded and clean coarse sand of FM, 2.5 to 3 including screening, shuttering, mixing cement concrete in mixer and placing in position, vibrating, striking, curing (but excluding the cost of reinforcement) taxes and royalty all complete as per building specification and direction of E/I

3.3

-

-

... More
Providing 63 mm average thick RCC M- 25 with nominal mix of (1:1.5.3) in chhajja with approved quality of stone chips 20 mm to 6 mm size graded and clean coarse sand of FM 2.5 to 3 including , shaking drip coarse in concrete screening centering shuttering , mixing cement concrete in mixer and placing in position , vibrating , striking , 6 mm thick cement plaster (1:4) with sand of FM 1.5 curing (excluding the cost of reinforcement ) taxes and royalty all comlete as per building specification and direction of E/I

0.32

-

-

... More
Suttering and centring

6.14

-

-

... More
Providing TMT reinforcement (TOR steel) 8mm to 16 mm as per approved design drawing , removal o f rust cutting , bending, binding including supplying annealed wire placing MS rods in position all complete job as per specification and directionof E/I.

10.01

-

-

... More
Providing designation 75 A brick work in CM 1:6 in superstructure with approved quality of clean coarse sand of FM 2 to 2.5 including providing 10 mm thick mortar joints,cost of screening of materials, scaffolding, racking out joints to 15 mm depth curing, taxes and royalty all complete as per building specification and direction of E/I

12.64

-

-

... More
Supplying fitting and fixing full glazed steel Supplying fitting and fixing fully glazed steel door window or ventilators standard rolled Z and mullion section and sizes as per I.S.-1038 joints met and welded with 100 x 16 x 3 mm MS lugs fixed in cement concrete (1:2:4) blocks 15 x 10 x 10 cm size including cost of oxidized iron fitting with hinges, handle per steps, catch springs 3mmv thick plain glass panes with Aluminium beads and inner frame fixed with lugs of 20 mm long 6.3mm G.I. counter sunk machine screw and nuts and applying a coat of red lead paint, carriage to work site hoisting and placing in position in all storey and taxes all complete as per building specification and direction of E/I.

7.2

-

-

... More
Supplying fitting & fixing collapsible gate of approved size and make properly fabricated with vertical double channel 20x10x2mm, at 100mm centres and braced with MS flat diagonals 20x3mm with top and bottom rails of T irons 40x40x6mm with 38mm dia steel pulleys complete with bolts nuts locking arrangements, stoppers, handles, including applying a priming coat of red lead paint, carriage, hoisting and taxes all complete as per b u i l d i n g s p e c i f i c a t i o n & direction of E/I .

5.76

-

-

... More
Providing 12 mm thick cement plaster (1:6) for inside &cut safe surface of p/H with clean coarse sand of P M 15 including screening, curing with all leads and lifts of water scaffolding taxes and royalty all complete as per building specification and direction of E/I.

151.99

-

-

... More
Providing 6 mm thick cement plaster (1:4) in ceiling of P/H & jack well with clean coarse sand of FM 1.5 including screening, curing with all leads and lift of water , scaffolding taxes and royalty all complete as per building specification and direction of E/I

59.97

-

-

... More
Providing 12 mm thick water proof cement plaster (1:3) with clean coarse sand of FM 1.5 with 5 % cicoor or any other approved water proofing compound including screening curing with all leads and lifts of water scaffolding taxes and royalty all tex etc. complete job as per building specification and direction of E/I

315.99

-

-

... More
Providing two coat of snowcem of approved shade and make over a coat of cement of primer on new surface including preparing the plastered surface smooth with sand paper,scaffolding, curing and taxes all complete as per building specification and direction of E/I

315.06

-

-

... More
Providing two coat of painting with ready mixed paint of approved shade and make over steel surface thoroughly cost of scaffolding and taxes all complete as per building specification and direction of E/I

29.16

-

-

... More
Providing & fixing R.S joist ISMB 300 x 140 mm size fitting and fixing in possion including cutting to required in shape and size, its carrage applying a priner coat of red lead paint etc. all complete job and direction of E/I 2 x 5.6 = 11.20 @44.2 kg / m = 495.04kg 1st floor

0.5

-

-

... More
Providing an fixing G.I pipe railling having 1.0 m height consisting 50 x 50x 6 mm thick M.S angles as vertical at 1.5 m c/c and additional post at every corner with 3 rows of 25mm dia G.I pipe of medium class variety as horizontal and painting 3 coat of oil paint over one coat of anticorrsive paint of approved colour and shade including cost of all labour transporting bents to curved shape etc. complete

20.88

-

-

... More
Providing and fixing MS sluice gates in position as per dtailed drawing and specification including cost of all materials, labour, operating pedestal, connecting rod, painting with three coats of anti-corrosive paint, etc. complete as directed by Engineer-in-charge.

500

-

-

... More
CI / MS Rose piece

500

-

-

... More
Providing and Fixing in Position of 20 mm dia M.S. bar Step with proper anchorage, etc. and providing and applying 3coats of ant- corrosive paint , etc. complete as directed by Engineer in charge.

45

-

-

... More
Earthwark in back filling foundation trenches or back filling of masonary structures with suitable earth in layers not exceding 150 mm thick well watered rammed and fully compacted and finaly dressed with earth obtained from excavtion of foundation and kept at a lead of 30 m and initial lead of 1.5 m complete as per specification and direction of E/I .

153.42

-

-

... More
Carriage of material from divisional store are kiln side or quality side to work including  contractor profit loading ,unloading transportation are complete . Cement 10 KM lead

89.27

-

-

... More
Steel 10 KM lead

10.01

-

-

... More
Sand 36 KM lead

70.01

-

-

... More
Bricks 6 KM lead

8787.64

-

-

... More
Stone/Stone Chips 11 KM lead

117.26

-

-

... More
Gangway 120 M long and 3.0M wide Earthwork in excavation of foundation trenches of toe wall Spillway head regulator , outlet ,intake well etc. as per a designed section in all kinds of soil, including moorum soil, soil mixed with kankar, pebbles and boulders up to 300 mm size and disposal of the same (beyond 50 M away from the edge of the trenches) with in initial lead of 150 M all lifts of 1.5 M as per specification and direction of E/I. Initial lift

180

-

-

... More
Gangway 120 M long and 3.0M wide Earthwork in excavation of foundation trenches of toe wall Spillway head regulator , outlet ,intake well etc. as per a designed section in all kinds of soil, including moorum soil, soil mixed with kankar, pebbles and boulders up to 300 mm size and disposal of the same (beyond 50 M away from the edge of the trenches) with in initial lead of 150 M all lifts of 1.5 M as per specification and direction of E/I. 1st Lift

120

-

-

... More
Earthwark in excavation of foundation trenches of toe wall spilllway ,head regulator intake well , outlet etc. as per designed section in ordinary or soft rock (where blasting is not needed) (Vide clasification of soil item C) with disposal of soil (beyond 50 m from the edge of trenches) with intial lead of 150 m. and lift of 1.5 m as per specification and direction of E/I.

120

-

-

... More
E/W in excavation of foundation trenches of toe wall spilllway ,head regulator intake well , outlet etc. as per designed section in hard rock where blasting is needed and stacking properly in approved stack size in approved stack yard beyond 50m from the edge of the trenches in the country side) with initial lead of 150m. and initial lift of 1.5m. as per specification and direction of E/I (Excavated hard rock size should not be more than 150 lb.). . 5 x 2 x 1 x 5 = 50

120

-

-

... More
Providing P.C.C M-150 with nominal mix of (1:2:4) in foundation with approved quality of stone chips (20 mm to 6 mm size graded and clean coarse sand of 2.5 to 3 including screening shuttering mixing cement concrete in mixer and placing in position vibrating , striking curing taxes and royalty all complete job of as per building specification and direction of E/I.

18

-

-

... More
Providing and laying in situ cement concrete of trap / granite / quartzite / gneiss metal for RCC work in foundation like raft , grillage , strip foundation and footing of RCC columns and steel stanchions including normal dewatering , plywood from work bully / steel propups compaction , finishing and curing etc. complete . (By weigh batching and mix design for M-25 and M-30 only . Use of L& T , A.C.C. , Ambuja , Birla Gold , Manikgad Rajasree etc. cement is permitted .) (excluding M.S or Tor in RCC M-20

46.8

-

-

... More
Providing and casting in situ cement concrete of trap / granite / quartzite / gneiss metal of approved quality for RCC work as per detailed drawing and designs or as directed by Engineer in charge including normal dewatering ,centering plywood from work bully / steel prop-ups, compaction , finishing the formed surfaces with CM 1:3 of sufficient minimum thickness if special finish is to be provided and curing etc. complete. (By weigh batching and mix design for M-250 and M-300 only . use of L&T , A.C.C , Ambuja ,Birla Gold , Manikgad , Rajashree etc. cement is permitted ) (excluding M.S or Tor reinforcement )

12.65

-

-

... More
Providing and casting in situ cement concrete of trap / granite / quartzite / gneiss metal of approved quality for RCC work as per detailed drawing and designs or as directed by Engineer in charge including normal dewatering ,centering plywood from work bully / steel prop-ups, compaction , finishing the formed surfaces with CM 1:3 of sufficient minimum thickness if special finish is to be provided and curing etc. complete. (By weigh batching and mix design for M-250 and M-300 only . use of L&T , A.C.C , Ambuja ,Birla Gold , Manikgad , Rajashree etc. cement is permitted ) (excluding M.S or Tor reinforcement )

3.22

-

-

... More
Providing and casting in situ cement concrete of trap / granite / quartzite / gneiss metal of approved quality for RCC work as per detailed drawing and designs or as directed by Engineer - in- charge including normal dewatering centering plywood form work bully /steel prop-ups , compection finishing the formed surface with CM1:3 of sufficient minimum thickness if special finish is to be provided and curing etc. complete ((By weigh batching and mix design for M-25 and M-30 only . Use of L& T , A.C.C. , Ambuja , Birla Gold , Manikgad Rajasree etc. cement is permitted .) (excluding M.S or tor reinforcement ) for RCC M-25 grade Beam

103.39

-

-

... More
Providing RCC M-200 (1:1.5: 3) in roof slab with approved Quality of stone chips 20 mm to 6 mm size graded and and clean coarse sand of F.M 2.5 to 3.0 including screening ,shuttering mixing cement concrete ,in mixer and placing in position ,vibration , strinking curing (but excluding the cost of reinforcement taxes in roylaty all complete job as per building specification and direction E/I

54

-

-

... More
Providing M.S. reinforcement of 8mm, 10mm, 12mm & 16mm dia. bar (tor steel) as per approved design, drawing, re-moval of rust, cutting, bending, binding including supplying annealed wire, placing M.S. rods in position all complete as per Specification and direction of E/I.

21.6

-

-

... More
Providing 12 mm thick cement plaster (1:4) with approved quality of sand of requisite F.M.1.5 w a s h e d a n d screened including curi n g , scaffolding wherever required and its removal royalty and all taxes etc. complete job as per specification & direction Of E/I.

786.62

-

-

... More
Providing 6 mm. Thick cement plaster (1:4) in ceiling with clean coarse sand of F.M. 1.5 including screening, curing with all leads & lifts of water, scaffolding taxes & royalty all complete as per building specification & direction of E/I.

360

-

-

... More
Providing &Fixing G.I Pipe Railling having 1.0 m height consisting 50 x 50 x 6 mm thick M.S Angles as verticals at 1.5M c/c , and additional posts at every corner with 3 rows of 25 mm dia G.I. pipes of medium class variety as horizontal & painting 3 coats of oil paint over 1 coat of anticorrosive paint of approved colour & shade including cost of all labour, transporting bends to curved shape, etc. complete.

240

-

-

... More
Providing two coat of snowcem of approved shade and make over a coat of cement primer on new surface including preparing plastered surface the smooth with sand paper, scaffolding, curing and taxes all complete as per building specification and direction of E/I.

1050.62

-

-

... More
Carriage of materials from divisional store or kiln site or quarry site to work site including contract profit, loading, unloading, transportation, etc. all complete.

-

-

-

... More
Cement 10 KM lead

141.86

-

-

... More
Steel 10 KM lead

21.6

-

-

... More
Sand 36 KM lead

105.41

-

-

... More
Stone/Stone Chips 11 KM lead

186.84

-

-

... More
Mechanical & Electrical Work at Intake well

-

-

-

... More
Supply, installation, testing and commisssioning of vertical turbine pumpsets with allied equipment as under (Please refer to Section 5,Sl. 2.4 of SBD)

-

-

-

... More
Vertical Turbine Pump [make: Kirloskar/WPIL/ Mather & Platt/Jyoti] as per IS: 1710, SIC of VT pump set , having Bronze Impeller, Stainless steel shaft, MS column pipe, line shaft, etc. capable of discharging 67.29 LPS against the head of 43 m coupled with energy efficient TEFC squirrel cage induction motor (IE3) as per IS 12615, having 15% more BHP than pump, operated on 3 Phase, 415V, 50Hz & A.C. Supply having 4 pole & 1500 rpm [make: Kirloskar/ ABB/ Crompton Greaves/ Marathon] all complete along with all arrangements for required discharge & head, base plate & other accessories such as suitable coupling, spider bearing, foot value with strainer, sluice valve(PN-1.6), NR valve, reducer, pressure gauge, specials, PCC foundation, nut & bolts, piping works for suction & delivery pipe, fitting & fixing with common header, etc. all complete required for the job.(As per the Indian standard and Instruction of E/I.)

-

-

-

... More
Discharge- 67.29 LPS and Head- 43m (1W+1S)

2

-

-

... More
Supplying and erecting Fully Automatic Star Delta starter to operate squirrel cage induction motor working on 380- 440 Volt, 3 phase, 50 Hz with no volt coil, over load element, and ON - OFF push buttons, with necessary material and connected to supply, etc complete. Starter with original sheet steel encloser.

2

-

-

... More
Supply, installation, testing and commissioning of LT Power Distribution Panel for Raw Water to be installed at Intake Well Pump House:- Floor mounted cubical LT Panel board fabricated with MS sheet of suitable guage and size, dust and vermin proof and painted consisting of proper power distribution 4 pole 250A copper busbar, 1 no. incoming feeder of 250A MCCB & 3 nos. outgoing feeder of 160A MCCB for pump sets including spare feeder and 2 nos. 32A MCB & 2nos. 63A MCCB outgoing feeder for lighting and utility, selector switches, Volt-meters, Ampere-meters, indicator lamps etc. all complete with internal wiring, including all types of protection units/relays & meters (MFM) and capacitor banks of proper KVAR for Power Factor control, etc.all complete with internal wiring with control cables all complete as per site requirement and IS.

1

-

-

... More
Supplying and erecting 120 sqmm XLPE / PVC insulated, armoured cable 1100 V grade with ISI mark Three and half core, stranded aluminium conductor with 6 mm thick 25 mm width M.S. spacer with G.I. Earth wire 6 sq mm, complete erected on wall / on pole with 25 X 3 mm M.S. clamps or in provided trench in an approved manner from Transformer to LT panel.

100

-

-

... More
Supplying and erecting 35 sqmm XLPE / PVC insulated, Unarmoured cable 1100 V grade with ISI mark Three core, stranded Copper conductor erected on wall / on pole in provided trench in an approved manner from LT panel to Motor.

50

-

-

... More
Cost of earthing as per IS 3043 for each motors. With all equipment & materials required for earthing e.t.c all complete.

2

-

-

... More
Providing, erecting 75 KVA Servo Controlled Automatic Voltage stabiliser suitable for output voltage of 415 Volt +/-1%, 3 Ph, 50 Hz, with copper wound transformer (oil cooled). The stabilizer shall be incorporated with protections and indications like Over Voltage / Under Voltage, Single Phasing, Cut off contactor with electronic output sensing unit, including change over switch, Earthing, t-oil, etc. all complete.

1

-

-

... More
Cost of construction DP structure in PCC Pole for Transformer with different type of MS channels, M.S. angles, brackets, insulators, AB Switch, three set of horn gap fuse, DO fuse and lightening arrester, nut bolts, fabrication work required for the job, cost of earthing of transformer (Two nos., one no. for neutral and one for body) with all required material labours, cost of providing disc & pin insulator for HV and LV side of the transformer, testing of dielectric strength of transformer oil etc. for transmission of power. All complete job as per I.E. rules.

1

-

-

... More
Providing, erecting triple spur gear type 3 Tonne Chain Pulley Block with 6 m lift complete with load chain and hand chain suitable for above lift, tested to 50% over load as per IS 3832 carrying ISI mark with travelling trolley.

1

-

-

... More
Providing internal and external lighting by wiring and installing lumenaries with suitable Wattage of LED light fittings in pump house, gangway, etc. all complete for Raw Water Plant.

1

-

-

... More
Supplying, Installation and erecting of Lightening Arrester at pump house of approved make and Fire extinguisher & First aid box, etc. at Pump house.

1

-

-

... More
Raw Water Rising main.

-

-

-

... More
Doing Geotechnical survey, Collecting field data, designing, getting it approved by competent authorityand Laying of Raw & clear water Rising Main (Please refer to Section 5,Sl. 3.0 of SBD)

-

-

-

... More
Providing and Supplying ISI mark centrifugally cast (spun) ductile iron pressure pipe for water works with socket a n d s p i g o t e n d s confirming to IS8329/2000 in standard working lengths of 4.5,5.5&6.0M for clasification K7 & K9 suitable for push- on - joint (Rubber gasket D jointing) with cement mortar lining inside the pipes with outside zinc and bituminous coating including transportation, inspection charges taxes & duties contractor profit and over head charge etc. (including cost of 1 no. gaskate for each pipe.

-

-

-

... More
DI Pipe 300 mm dia Class K-9

2797

-

-

... More
Providing and supplying ISI standard D.I. specials & fitting with sealing rubber gasket of S.B.R. complete with cast iron follower gland and M.S. nut & bolts coated or otherwise protected from rusting and suitable for D.I. pipes including complete as per I.S. 9523 class K12 (Ex factory Rates) Incpection charges Transpotation.

5105.89

-

-

... More
Providing and Supplying ISI mark CI D/F reflux valves (non return valves) of following dia inspection charges unloding from railway wagon, loading into truck, transportation upto departmental stores/ site, unloding, stacking etc. complete. Reflux valves as per I.S. 5312 Part l (1984) Without bypass arangement PN-1.6 300 mm Dia

1

-

-

... More
Providing Double Flanged Sluice valve confirming for IS 2906/14846 including worn gear arrangements as per test pressure stainless steel spindle, caps including all transportation etc. complete . (without bypass Arrangement )

-

-

-

... More
Sluice valve PN 1.6 300 mm dia

4

-

-

... More
Scour valve

-

-

-

... More
PN 1.6 100 mm dia

8

-

-

... More
Providing and supplying air valves as per IS - 14845-2000 and M J P's Standard specifications of approved make and quality of following diameters including all taxes (central and local ) , railway friegth, insurance third party inspection charges loading unloading transportation up to departmental store/site etc.complete .

-

-

-

... More
Single Ball Flanged / screwed Type P.N 1.6 Dia- 50 mm

5

-

-

... More
Earth Work in excavation (As per I.S. 3114/1965) for laying of Different types and size of pipes so as to give one meter average cover over the socket of pipe with disposal of excavated earth within initial lead and lift as per specification and direction of Engineer in-charge (b) For classification of soil item -B

2537.44

-

-

... More
Earth work in excavation of foundation trenches as per design section in ordinary or soft rock (where blasting is not required and disposal of excavated materials so obtained (50 m away from the edge of the trenches ) with initial lead of 150 m and initial lift of 1.5 m as per specification amnd direction of E/I.

634.36

-

-

... More
Supplying labours, tools , tackles, lubricant etc for laying and jointing C.I.S/S Tyton pipes (class L A/DI) trenches supplying rubber gasket (Rubber gaskets confirming to I.S.S.-5382-1969) and making gasket joint s including providing night guard ,barrier and red light to safe guard against accident ,all complete ( Pipe to be supplied departmentally free of cost and laying of pipes is to be done as per (I.S.S.3114-1985) as per design, specification and direction of E./I. (without cost of rubber gasket)

-

-

-

... More
300 mm dia DI K-9

2797

-

-

... More
Lowering, laying and fixing in proper alignment and position all types of C.I. air valves as directed by Engineer –in–charge including cost of conveyance from store to site of work, cost of all material and giving satisfactory hydraulic testing etc. complete.(for all class of valves).

-

-

-

... More
50 mm dia

5

-

-

... More
Supplying Labour and tools for fixing C.I. sluice valve in trenches with a pair of C.I. Tail piece including making lead caulked joints and flanged joints as per I.S.S .specification , including supplying all jointing materials (Pig lead confirming to I.S.S. 782-1978, yarn confirming to I.S.S. 6587– 1972 and nuts and bolts confirming to I.S.S. 1364 – 1983) including drilling holes in flanges if required as per specification and direction of E/I. (Sluice valve and pieces to be supplied departmentally free of cost).

-

-

-

... More
Sluice valve PN 1.6 300 mm dia

4

-

-

... More
Scour valve PN 1.6 100 mm dia

8

-

-

... More
Earthwork in back filling the trenches after laying different types and sizes of pipes with earth removed during excavation within initial lead and lift as per specification and direction of Engineer-in - Charge (for classification of Soil item A & B)

2537.44

-

-

... More
Supplying Labour ,tools and tackles for testing of laid C.I / DI or U.P.V.C or H.D.P.E or A.C pressure pipe up to 60 meter head of water all complete as per specification andection of E/I (Water to be supplied free of cost

-

-

-

... More
300 mm Dia Pipe

2797

-

-

... More
Labour charge for one cutting of C.I/ D.I and specials including suppying supplying , necessary tools and plants ,chipping or filling the surface finish as per specification and direction of E/I

-

-

-

... More
300 mm Dia Pipe

8

-

-

... More
Construction of B.W. masonry valve chamber of size 1.50 x 1.20 x 1.80 mt. as per enclosed annexure

17

-

-

... More
Supply all materials & construction of Thrust Block where required

10

-

-

... More
Infilltration Gallery

-

-

-

... More
Earthwork in excavation of foundation trenches of toe wall Spillway head regulator , outlet ,intake well etc. as per a designed section in all kinds of soil, including moorum soil, soil mixed with kankar, pebbles and boulders up to 300 mm size and disposal of the same (beyond 50 M away from the edge of the trenches) with in initial lead of 150 M all lifts of 1.5 M as per specification and direction of E/I.

-

-

-

... More
Initial lift

1282.3

-

-

... More
1st lift

298.49

-

-

... More
2 nd lift

66.33

-

-

... More
For Header Pipe

-

-

-

... More
Initial lift

384.69

-

-

... More
1st lift

89.55

-

-

... More
2 nd lift

19.9

-

-

... More
Providing at site of works ISI standard welded D.I Double flanged pipe excluding GST Levied by GOI & GOM inall respect ,Railway Frieght … Complete as directed by EIC (for-2.75m bore pipe)

-

-

-

... More
For Header M.S. pipe 450mm dia. 8 mm thickness

30

-

-

... More
Design and Supply of V-wire screen laterals Suitable for infiltration Gallary as per site condition and detail provided. End Connection - Suitable Flange including taxes and transporation.

-

-

-

... More
250 mm dia

100

-

-

... More
Lowering laying and jointing MS/ slotted pipes of following diameters including all leads and lifts , cost of jointing material ,labour etc. complete as directed by Engineer- in -charge.

-

-

-

... More
Header pipe 450mm dia.

30

-

-

... More
Perforeted/slotted pipe 250mm dia.

100

-

-

... More
Providing ,lowering ,laying and placing in position ,shrouding material for porous pipe gallery / slotted pipe gallery /trench gallery with all leads and lifts involved including transportation of materials to site of works screening and washing of materials and placing in position with given section , etc. complete as directed by Engineer- in - charge.

-

-

-

... More
For 40 mm Pebbles

18.05

-

-

... More
12 mm to 20 mm Pebbles

30.61

-

-

... More
6 mm to 12 mm Pebbles

44.74

-

-

... More
D.I. fitting special leg 300 mm tee etc.

300

-

-

... More
Filling in foundation trenches and plinth in layers not exceeding 150 mm thick well watered , rammed ,fully compacted and fine dressed with earth obtained after cutting within a lead of 50 M and lift of 1.5 m all complete as per building specification and direction of E/I total earth work (made of measurement compacted volume ).

833.53

-

-

... More
Coffer Dam

-

-

-

... More
Providing, constructing coffer dam in river basin / dam storages as per type design including excavation, filling the middle portion with B.C. soil (in gunny bags if required). Providing impervious / semimpervious materials on both side of B.C. soil (in gunny bags if required) including ramming , compacting to satifaction of Engineer-in-charge, till the completion of work including dismantling coffer dam after completion of works and disposing off material as directed by the Engineer-in-charge.

-

-

-

... More
Intake

942.6

-

-

... More
Gangway

600

-

-

... More
Infilltration Gallery

750

-

-

... More
Dewatering the excavated trenches and pools of water in the building trinches/pipe line trenches , well works by using pumps and other devices including disposing off water to safc distence as directed by Engineer- in -charge (including cost of machinery , labour fuel, etc. complete

-

-

-

... More
Intake

3600

-

-

... More
Gangway

2400

-

-

... More
Infilltration Gallery

1800

-

-

... More
Operation & Maintenance for One years

1

-

-

... More
Electricity charges for 1 year

1

-

-

... More
As per SBD Section - 5 Clouse 9.10

1414740

-

-

... More
Construction of Raw Water Reservoir with pump house Designing (aestheticalyy) , and Constructing Rcc ground Service reservoirs / RCC sumps in M-300 mix of required capacity including excavation in all types of strata foundation concrete container walls, bottom slab top RCC roof slab / or dome, 20 mm thick cement plaster with water proofing compound in CM 1:3 proportion to inside face of the container including epoxy paint from inside including refilling and disposing of surplus stuff within lead of 50M, all labour and material charges for laying and jointing of pipe assembly for inlet, outlet, washout, overflow and bye pass arrangement consisting of C.I / MS D/F pipes, specials and valves of given diameter providing and fixing accessories such as MS ladder inside and outside, CI manhole frame and cover, water top slab, BB masonry chamber for all valves, ventilating shafts, including giving satisfactory hydraulic test and water tightness test as per IS code and providing three coat of cement paints to all expose surface of structure including roof structure etc., complete as per design data, criteria, obligatory requirements and detailed specifications. Anti-termite treatment shall be given for under ground portion of the structure The Design shall be in accordance with various relevant IS specfications (I.S 456/2000, I.S 875-1987,I.S.3370-1965 or revised) Only MS bars grade I confirming to IS 432 Part I or high yield strength deformed bars conforming to IS 1786 or IS 1139 shall be used, Grade II MS bars shall not be used Entire structure shall be in M-300 only The scope of pipe assembly work shall be upto 5 meters beyond outside face of the wall, cost of pipes valves and specials is not included in the rate but labour cost for laying and jointing is included

1

-

-

... More
The G.S.R / Sump above 15 lakh litres capacity shall be in two compartments The job included designing the structure for up lift pressure and dewatering required during entire execution and disposal of surplus excavated stuff within lead of 50 metres as directed by Engineer in charge. If up lift considered in design then these rates shall be increased by 7.5% G.S.R outlets shall be with bell mouth of approved pattern in bottom slab and cost of designing bell mouth is included in the rate Sump well includes cost opf suction pit required at bottom For pipe diameters upto 300 mm only CI pipes and CI specials shall be used. For pipe diameters above 300 mm M.S pipe and specials minimum 10mm thick shall be used with proper anti corrosive epoxy treatment from inside and outside Cost of pump house is not included inthese rates Above rates are applicable for Seismic Zones 2,3 and 4 75%part rate shall be payable for reinforced concrete and plastering items of all types of G.S.R sand sump still satisfactory hydraulic testing for water tightness is given ; and till that work shall be treated as incomplete 10% shall be added for sump if over head pump house is proposed Note: Conditions from S.No 1 to 11 shall form a part and parcel of tender and must be included in the draft tender papers for work of R.C.C G.S.R and sumps Cost of 15,00,000 litres capacity (1500 KL)

-

-

-

... More
Add for capacity above 1500 KL, 8550 KL (8550KL)

8550000

-

-

... More
10% shall be added over the cost of GSR for sump where over head pump house is proposed

0.1

-

-

... More
Add 15% LS of cost of pipe, Specials and valves required for inlet , outlet washout, over flow, bypass arrengment, Epoxy painting Etc

0.15

-

-

... More
Mechanical & Electrical Works at Raw water Storage Tank Centrifugal Monoblock Pump Set Providing, erecting and giving test of Centrifugal Monoblock Pump set confirming to IS 9079 operating at 2900 RPM with CI impeller, priming funnel, cock, suitable flanges at suction and delivery side. Pump shall have common shaft for pump and motor. Motor shall be suitable for working on 415 V +- 10%, 3 Ph, 50 Hz A.C. Supply motor shall be TEFC type. Pump set shall be suitable for working at various discharge and head requirements. Pump shall be erected on provided C.C foundation block with suitable foundation bolts grouted in CC foundation block. 20 HP

2

-

-

... More
Supplying and erecting, assembled Fully Automatic Star Delta Starter, in a provided cubical panel to operate squirrel cage induction motor working on 380-440 Volt, 3 Phase, 50 Hz with no volt coil, over load relay and ON-OFF push buttons, with necessary material and connected to supply, etc complete. 12.5 HP & Up to 20 HP

2

-

-

... More
Supplying Single Girder Electrically Operated Circular/ Rectangular opverhead Travelling Crane with 6 m lift complete with wire rope hoist, Class II duty, all three motions electrically operated by suitable rating motor IP 54, control panel and down pendant control block. 5 Tonne capacity above 6m to 8m span

1

-

-

... More
Supplying triple spur gear type chain pulley block suitable for capacity as below with 6 m lift complete with load chain and hand chain suitable for above lift, tested to 50% over load as per IS 3832 carrying ISI mark with travelling trolley etc 3 Tonne Capacity

1

-

-

... More
Providing, erecting and fixing square bar of EN 8 as rail for over head crane on provided track girder / continuous corbel beam including supporting plate and J bolts

5

-

-

... More
Supplying and erecting 200 kVAr, 440 V 3 phase, 50 Hz., thyrister switched micro APFC passive filter panel, consisting of suitable steps of APP type capacitor units with harmonic filter reactors, as per specification no CP-ED/APFC

2

-

-

... More
Providing, erecting and commissioning out door type copper wound transformer continuously rated for 3 Ph, 50 Hz, at full load and temp. rise not exceeding 45º C by thermometer in oil and 50ºC by the resistance in winding after continuous run at full load rating, the transformer should have oil immersed winding having vector group DY 11, HT side connected in Delta and LT side connected in Star with neutral brought out connected to provided separate earthing. The transformer shall have power terminal arrangement, bushings / cable end box on HT side and cable end box on LT side. 2 Nos. channels with stoppers shall be provided and fixed on the provided plinth for mounting the transformer. The transformer should have following standard fittings. Transformer shall be of latest manufacturing standards as per amended IS specifications and the Load & No Load losses shall be limited to the values given below or as per IS or Norms issued by MSEDC Ltd whichever are lower. Power Transformer 11000/433 volts With off load Tap Changer – 12.5% to +2.5% in steps of 2.5% . 630 KVA (No load loss 1000w and load loss 7000w)

1

-

-

... More
Supply, installation and commissioning of LT switch disconnect or Isolator (TPN) of suitable rated Switch Disconnector IS: 13703 and IS: 13947(Part-3) IEC : 60947-3 Door interlock & padlock facility with S.S. Enclosure

1

-

-

... More
Supplying XLPE / PVC insulated, armoured cable 1100 V grade with ISI mark Three and half core, stranded aluminium conductor with 6 mm thick 25 mm width M.S. spacer with G.I. Earth wire 6 sq mm, complete in an approved manner as per IS 7098 3.5 core 240sq mm

100

-

-

... More
Supplying HT Aluminium three core cable XLPE insulated ,insulation screened with extruded semi conducting compound in combination with copper tape (0.3 kA for 1 sec.) cores laid up inner sheath of PVC tape ,galvanised steel flat strip armoured,and overall PVC sheathed cable conforming to IS :7098 /II/85 with latest amendments 3 core 240sq mm

300

-

-

... More
Cost of cable jointing kit making indoor termination and outdoor termination with suitable joints along with cable trays where ever required etc. all complete

1

-

-

... More
Providing, erecting electric Valve actuators totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and hand wheel for emergency manual operation which will automatically dis-engage on restoration of power to motor and with 10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction motor working on 440 Volts +/- 10%, 3 phase, 50 Hz AC of intermittent duty rating S-2, insulation class "F" and temp rise restricted to class "B" with IP - 67 protection class suitable for DOL starting and with three thermostat and 30% over load margin. The torque rating of reduction gear box shall be atleast 1.5 times max. torque required for opening and closing of valve with integral starter for ON & OFF operation. Electric Valve Actuator for non rising spindle type sluice valve, PN 1 & PN 1.6 rating For Valve Size (300 mm dia)

2

-

-

... More
Electromagnetic Flow Meter Supply, installation, testing and commissioning of Electromagnetic Flow Meter etc.As per ISO 4064 for RAW/Pur water with accuracy +/-0.5% of measured vaue & protection as per given specifications for size 100 mm-1000 mm including sensor transmitter surge sreestor cable GI duct if suitable size foe 25 m built in GSm (with simcard and its charges valid for 36 months) including pipe cutting, levelling and installation of flow meter in the pipelines with necessary tools tackles cranes including 36 months gurantee etc complete as may be required at site & based on tech specs 300 mm dia

1

-

-

... More
Cost of drawing 11 KV HT overhead electric Line on Rail poles with suitable ( DOG ) ACSR Conductor from the nearest grid upto ESS for Raw Water and making DP including cost of PTs & CTs and cost of taking clectrical connection from JSEB

0.2

-

-

... More
Raw Water Rising Main of 300 mm Dia DI K-7 Pipe @ 150 m Providing & Supplying centrifugally ISI Mark Centrifugally cast (spun) ductile iron pipe of 100mm and above all diameter for water works with socket and spigot ends confirming to IS8329/2000 in standard working lengths of 4.5, 5.5 & 6 m suitable for classification K-7 suitable for push on joint (Rubber gasket D jointing) with cement mortar lining on inside surface and outside zinc and bituminous coating. Including all other taxes insurance carriage to work site with loading Unloading etc. Including inspection charges and all complete (Including carriage up to 260km). Class K-7 300mm

150

-

-

... More
Supplying labours, tools and tackles for testing of laid CI/UPVC/HDPE/ AC pressure pipes upto 60 m head of water all complete as per specification and direction of E/I 450mm

150

-

-

... More
Providing and supplying ISI standard D.I. specials & fitting with sealing rubber gasket of S.B.R. complete with cast iron follower gland and M.S. nut & bolts coated or otherwise protected from rusting and suitable for D.I. pipes including ED, CST all taxes e t c . complete as per I.S. 9523 (Including 10% C.P and 5% OHC) as per item-4 100 to 300mm dia.

452.4

-

-

... More
Providing Double Flanged Sluice valve confirming for IS 2906/14846 including worn gear arrangements as per test pressure stainless steel spindle caps including all taxes transportation etc.complete. With including 10% CP with E.D With byepass arrangement. Sluice valve PN 1.6 300mm

1

-

-

... More
Providing and supplying Kinetic Double Orifice type Air Valves confirming to IS 14845 as per MJP’s standard specifications combined with screw down isolating valve, small orifice elastic ball resting on a gun metal orifice nipple, large orifice vulcanite ball seating on moulded seat ring, inlet face and drilled, including insurance, third party inspection charges, loading, unloading, transportation upto departmental stores, excluding GST levied by GOI & GOM in all respect etc. complete Kinetic Air Valve Flanged P.N. 1.6 Type - PN -1.6 100 mm dia.

1

-

-

... More
Earth Work in excavation (As per I.S. 3114/1965) for laying of Different types and size of pipes so as to give one meter average cover over the socket of pipe with disposal of excavated earth within initial lead and lift as per specification and direction of Engineer in-charge (b) For classification of soil item -B

153.09

-

-

... More
Earthwork in excavation of foundation trenches as per designed section in ordinary or soft rock (vide classification of soil item C ) and disposel of excavated material so obtained (50 m awaty from the edge of the trenches ) with in initial lead of 150 m and initial lift of 1.5 M as per specification and direction of E/I.(in ordinary or soft rock where blasting is not required)

17.01

-

-

... More
Supplying labours, tools, tackles, lubricant etc. for laying and jointing C.I.S/S tyton pipes (class LA) /D.I. pipe in trenches supplying rubber gasket (Rubber gaskets confirming to I.S.S.- 5382- 1969) and making gasket joints including providing night guard,barrier and red light to safe guard against accident, all complete (Pipe to be suppllied departmenatlly free of cost and laying of pipes is to be done as per I.S.S.3114-1985) as per design, specification and direction of E/I. Class K-7 300mm

150

-

-

... More
Labour charge for one cutting of DI / CI pipes and specials including supplying, necessary tools and plants, chipping or refilling the surface finish as per specification and direction of E/I Class K-7 300mm

1

-

-

... More
Supplying labour & tools for fixing Kinectic double orific type Air valve in trenches as per specification and direction of E/I. ( Air valve to be supplied departmentally free of cost). 100 mm dia.

1

-

-

... More
Supplying Labour and tools for fixing cI sluice valve trenches with a pair of cI Tail pair including making) flanged joints as per I.S. specification, including flanged joints as per IS specification confirming to I.S.S. 782 – 1978 confirming to I.S.S. 6587 – 1972 and nuts and bolts confirming to I.S.S. 1364 – 1983). Including drilling holes in flanged if required as per specification and direction of E/I. (Sluice valve and pieces to be supplied departmentally free of cost). 300 mm dia

1

-

-

... More
Supplying tools and cutting road as well restoring the same as per specification and direction of E/I. (a) Pucca road (except black top only taken out materials to be used) For cutting road as per requirement. Approx 80% of Pucca Road

24

-

-

... More
Dismantling of Cement Concrete Pavement (Dismantling of cement concrete pavement by mechanical means using pneumatic tools, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 metres, stacking serviceable and unserviceable materials separately)

0.9

-

-

... More
Providing ,coarse clean sand in filling in foundation trenches/in plinth including ramming & watering in layers not exceeding 150 mm thick with all leads & lift, including cost of all materials ,labour ,royalty & taxes all complete as per b u i l d i n g s p e c i f i c a t i o n & direction of E/I.

2.25

-

-

... More
PCC 1:3:6 in Foundation (Plain cement concrete 1:3:6 nominal mix in foundation with crushed stone aggregate 40 mm nominal size mechanically mixed, placed in foundation and compacted by vibration including curing for 14 days.)

4.5

-

-

... More
Providing designation 75A one brick falt soling joint filled with local sand including cost of watering taxes royalty all complete as per building specification and direction of E/I.

30

-

-

... More
Providing, Fixing and supplying ISI mark CI D/F reflux valves (non-return valves) of following dia including all taxes (central and local), railway freight, inspection charges unloading from railway wagon, loading into truck, transportation upto departmental stores/ site, unloading, stacking etc. complete. Reflux valves as per I.S.5312 Part I(1984). 300mm (PN-1.6 with byepass arrangement.)

1

-

-

... More
Lowering, laying and jointing in position following C.I. D/F Reflux valves, Butterfly valves and Sluice valves including cost of all labour, jointing material, including nut bolts and giving satisfactory hydraulic testing, etc. complete. (Rate for all class of valves) 300mm dia

1

-

-

... More
Earthwork in back filling the trenches after laying different types and sizes of pipes with earth removed during excavation within initial lead and lift as per specification and direction of Engineer-in-Charge ( for classification of Soil item A & B )

136.08

-

-

... More
Valve Chamber with Precast RCC Covers Providing and constructing B.B. masonry valve chamber with 15 cm thick 1:3:6 proportion PCC bedding, excluding excavation, B.B. masonry in CM 1:5 proportion precast RCC frame and cover, etc. complete as directed by Engineer-in-charge. G. As above of 1.5 x 1.5 M internal size and depth upto 1.8 M with precast R.C.C slab cover.

1

-

-

... More
Carrage of Material Brick upto 8 km

150

-

-

... More
Sand upto 10 KM

2.97

-

-

... More
Stone Chips upto 10 KM

3.96

-

-

... More
Cement Upto 5 KM

1.41

-

-

... More
Cost of 4.8 MLD Water Treatment Plant Designing (aesthetically),providing constructing and commissioning conventional Water Treatment Plant consisting of all civil ,Mechanical and Electrical works including cost of providing and applying Epoxy paint to inside surface of water retaining structures in contact with chlorine and providing ant termite treatment to entire structure below ground level ,Mechanical and Electricals components of various sub works as given below ,including necessary hydraulic testing ,structural testing ,equipment testing and trial run for 3 months,etc. complete as directed by Engineer -in-charge.(Turn-Key Job). Aeration Foundation : Plan area not less than 0.625 square meter per MLD Ventury Flume : With necessary devices, consisting of simple mechanical indicator (Pedestal type guauge). Flash Mixer : Rapid mixer device, detention time 60seconds to give velocity gradient 300 to 400 sec-I vane mixer type confirming to IS 7090 of 1985 Flocculator : confirming to I.S. 7028 of 1974 (Type -C) with detention period of 30 minutes. Clarifier : Horizontal flow circul;ar tank , detention period 2.5 hours, overflow rate 30 cubic meter per square meter per day (to be specified), Weir loading not more than 300 cubic meter per meter per day, with mechanical sludge scraper confirming to I.S. 10313/1982 with necessary inlet outlet arrangement. Rapid Sand Filters and Filter House : Filter deisgned for filtration rate of 5000 lit/m2/hr at normal flow minimum 2 beds for plant upto 10 MLD , for larger plants as specified , filters to be located in filter house with roof slab, pipe gallery and platform minimum 5.5 meter in width. With constant rate filtration or declining rate filtration. a) Filter sand : Effective size 0.45 to 0.70mm , uniformity coefficient not more than 1.7, nor less than 1.3,m depth of water over sand 0.75m free board 50cm gravel 0.45m in depth sand and gravel confirming to I.S. 849 (I)-77 back wash by air wash . Standard appurtenances (to be specified).rate of flow controller, fitter gauge, sand expansion guage etc. b) Wash Water Tank : capacity to be spacified and suitable to supply water to wash specified number of filter beds at a time 12 minute at 600 lit/M2/min under a head of 12 m at under drain. c) Wash water Pumps : Capacity to fill water tank in one hour with 100% stand by d) Air Blowers : Capable of delivering 600 LMP per square meter of free air, of filter area at 0.4 kg/scuare cm at the underdrains (100% stand by) for period of 5 min. Chemical House in Two Storey's a) Ground floor to accommodate 7 days alum requirement and sundry storage (minimum 4 m height) b) First floor to accommodate alum and lime tanks chain pulley block etc. (minimum 5 m height) c) Solution Tanks : Minimum 3 tanks (One for preparation , Second for dosing and third as standby), each tank capable of giving 8 hours maximum dose without interruption , minimum free board 0.30 M trays for dissolving , level indica tor mechanical agitation devices, solution feed device (Constant head device strength of solution upto 10% only) confirming to I.S.9222 part-I/1979. Pure water Sump and Pump House a) Capacity of sump : One hour of deisgned flow. b) Pump House : Pump house of required size over the sump or by the side Store House : Suitable for alum storage of three months and 7 days temporary storage , 7 days TCL requirement in mansoon with 20% extra capacity for other sundry articles Vacuum feed type chlorinators : make to be approved by MJP a) confirming to I.S. 10533- A part - II 1983 b) Rate of withdrawal c) Chlorinator and equipment and container room : to conform to I.S. 10553 Part - I 1983 d) 100% standby shall be provided By pass arrangement - C.I or MS pipes i) By passing all units of TP ii) By passing flash mixer, clariflocculator. iii) By passing flash mixer, clariflocculator and filter Disposal of waste from WTP : Safe disposal arrangement to nearby nalla including cost of pipes. For WTP of capacity 30 mld and more additional arrangement for backwash water recycle shall be provided , including sump, pumping machinery, rising main etc. complete. Drainage arrangement : To decant all units of WTP with CI pipes upto boundary of each unit and further extension with RCC pipes to nearby nalia. Electrical Installation : Both internal and external including entire plant area.

4.8

-

-

... More
Mechanical & Electrical Works at WTP Supply, delivery at site with necessary packing, receiving, unloading, shifting, storing, installation, testing and commissioning of Horizontal Centrifugal Split Casting pumps with motor, CI casing and casing ring, SS 316 impeller, SS 410 Shaft and shaft sleeve, coupling guard, common base plate, foundation bolts etc. complete with all respect as per the specification. Discharge 20 to 30 LPS and head 20 to 30 M.

4

-

-

... More
Providing, installation, testing and commissioning of Centrifugal Monoblock pump set conforming to IS 9079 , 2 pole motor operating at syncronised speed of 3000 RPM with requisite MOC impeller, priming funnel, cock, suitable flanges at suction and delivery side. Pump shall have common shaft for pump and motor. Motor shall be suitable for working on 415 V ± 10%, 3 Ph, 50 Hz A.C. Supply. Motor shall be TEFC type and Pump set shall be suitable for working at various discharge and head requirements as per scope of work. Pump shall be erected on C.C. foundation / cross channels / RSJ frame block with suitable foundation bolts grouted in C.C. foundation block etc. complete in all respect as per specification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD. Centrifugal Monoblock Pump set (Single Stage) 2.2 KW (3.0 HP)

2

-

-

... More
5.5 KW (7.5 HP)

2

-

-

... More
Supplying and erecting, assembled Fully Automatic Star Delta Starter, in a provided cubical panel to operate squirrel cage induction motor working on 380-440 Volt, 3 Phase, 50 Hz with no volt coil, over load relay and ON-OFF push buttons, with necessary material and connected to supply, etc complete. 12.5 HP & Up to 20 HP

4

-

-

... More
Supplying and erecting assembled DOL starter in provided cubical panel, with ON-OFF push buttons, no volt coil, over load element and required power and control wiring complete. Upto 7.5 HP

4

-

-

... More
Manufacturing, providing and supplying spirally welded / ERW/ SAW / fabricated M. S. pipes (Commercial Quality) including procurements of plates, gas cutting to required size rolling, tack welding assembling in suitable lengths to form pipes, welding on automatic welding machine and forming ‘V’ edge on both ends of pipes including railway freight, insurance, unloading from railway wagon, loading into truck, transport to stores, unloading, stacking, excluding GST levied by GOI & GOM in all respect etc. complete as per IS - 3589 and IS-5504 as applicable as per specifications (No negative tolerance in thickness is permissible). 300 ID

100

-

-

... More
Special for Pipe Work

900

-

-

... More
Providing , Laying, Jointing Double Flanged Sluice valve confirming for IS 2906/14846 including worn gear arrangements as per test pressure stainless steel spindle caps including all taxes transportation etc.complete. (PN 1 with byepass) arrangement. 200mm

6

-

-

2

-

-

... More
Providing, Fixing and supplying ISI mark CI D/F reflux valves (non-return valves) of following dia including all taxes (central and local), railway freight, inspection charges unloading from railway wagon, loading into truck, transportation upto departmental stores/ site, unloading, stacking etc. complete. Reflux valves as per I.S.5312 Part I(1984). 200mm (PN-1 with byepass arrangement.)

6

-

-

... More
100mm (PN-1 with byepass arrangement.)

2

-

-

... More
Providing , erecting C.I. foot valve having single leather flap and gunmetal sealing. Valve shall be fixed on suction side of pump as per requirement including jointing material and hardware. Flanged type150mm

8

-

-

... More
Desidning,supplying,installing,commissioning & testing with complete priming arrangements for centrifugal pumps as applicable & as required shall be done with interface with PLC panels & further to SCADA system.

1

-

-

... More
Substation at WTP ( Transformer + Associated Structure ) Designing, Providing, Eracting, commissioning & testing of 150 KV out door type 11KV/.433 KV Transformer with associated Structure and DB complete

1

-

-

... More
11 KV Line upto WTP by Tapping the Feeder supplying to Head works Designing, providing, erecting, commissioning & testing of 11 KV Line upto WTP and Zone 2 Sump by tapping the 11 KV feeder coming from 33KV/11KV nearby substation and supplying to Head works JW . Complete.

5

-

-

... More
Panel Designing, Providing, Eracting, commissioning & testing of Electrical panel for Pumps and Other Electrical Equipment including the incoming 4 pole okt Breaker

2

-

-

... More
Supplying and erecting 200 kVAr, 440 V 3 phase, 50 Hz., thyrister switched micro APFC passive filter panel, consisting of suitable steps of APP type capacitor units with harmonic filter reactors, as per specification no CP-ED/APFC

2

-

-

... More
Providing earthing with copper earth plate size 30X30X0.315 cm complete with all materials testing & recording the result as per spesification no. EA-EP

8

-

-

... More
GI strip Supplying and erecting G.I. strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joint required. as per specification No (EA-EP).

1200

-

-

... More
Street light in WTP , Transformer and zone 2 sump area and other outside area Providing and erecting street light in the head work area complete with fitting and fixing

15

-

-

... More
Providing and erecting cable for street street and light in WTP area

1

-

-

... More
Lighting in WTP including Office Building and zone 2 sump area Providing , fixing and Testing of Internal Lighting in WTP Building complete with the detailed description

1

-

-

... More
Lighting in WTP Staff Quarters Providing , fixing and Testing of Internal Lighting in WTP Building complete with the detailed description

3

-

-

... More
Incoming Cable from Transformer to Elect Panel (WTP and zone 2 sump) Providing Fixing and Testing of 1.1 KV, 5x300 Sq MM 3 1/2 core Aluminium Conductor XLPE / PVC Armoured Cable

1

-

-

... More
Cabling and Other Electrical Work (WTP and zone 2 sump) Providing, Laying , Connecting, Testing of Cables in the WTP Area and Scada Room and Residential Area including Lighting

1

-

-

... More
Lifting Equipment Chain pulley block 3tonne

1

-

-

... More
Hand operated circular or rectangular Travelling Crane Supplying Single Girder Electrically Operated Circular/ Rectangular opverhead Travelling Crane with 6 m lift complete with wire rope hoist, Class II duty, all three motions electrically operated by suitable rating motor IP 54, control panel and down pendant control block. 5 Tonne capacity above 6m to 8m span

1

-

-

... More
Substation Fencing, Safety & Fire Fighting Equipment Emergency Lighting on Inverter Designing, providing, installing, commissioning of Inverter for Emergency Lighting in WTP (Office, Filter, Out side Emergency Lights, Other area )

4

-

-

... More
Structural steel for hoist arrangement & EOT Square Bar/ Rail

5

-

-

... More
Electromagnetic Flow Meter Supply, installation, testing and commissioning of Electromagnetic Flow Meter etc.As per ISO 4064 for RAW/Pur water with accuracy +/-0.5% of measured vaue & protection as per given specifications for size 100 mm-1000 mm including sensor transmitter surge sreestor cable GI duct if suitable size foe 25 m built in GSm (with simcard and its charges valid for 36 months) including pipe cutting, levelling and installation of flow meter in the pipelines with necessary tools tackles cranes including 36 months gurantee etc complete as may be required at site & based on tech specs EMF200 for DN 200 mm

3

-

-

... More
EMF100 for DN 100 mm

1

-

-

... More
Compound Wall With Gate for WTP & RWR 500 ( M) and Zone-1 & 2 E.S.R (240 M) E / W i n e x c a v a t i o n i n foundation trenches in ordinary soil (vide classification of soil i t e m - A ) & d i s p o s a l o f excavated earth obtained to a distance up to 50 M including all lift leveling ,ramming the foundation trenches removing root of trees, shurbs all complete as per approved design building specification and direction of E/I.

455.69

-

-

... More
PCC 1:3:6 in Foundation (Plain cement concrete 1:3:6 nominal mix in foundation with crushed stone aggregate 40 mm nominal size mechanically mixed, placed in foundation and compacted by vibration including curing for 14 days.)

34.08

-

-

... More
Furnishing and Placing Reinforced/Prestressed cement concrete in super-structure as per drawing and Technical Specification. RCC Grade M20, For solid slab super-structure.

70.1

-

-

... More
Furnishing and Placing Reinforced/Prestressed cement concrete in super-structure as per drawing and Technical Specification. RCC Grade M20, For solid slab super-structure.

65.16

-

-

... More
Furnishing and Placing Reinforced/Prestressed cement concrete in super-structure as per drawing and Technical Specification. RCC Grade M20, For solid slab super-structure.

49.39

-

-

... More
Providing designation 75 A brick work in C.M. (1:6)in f o u n d a t i o n & p l i n t h w i t h approved quality of clean coarse sand of F.M. 2 to 2.5 including providing 10 mm thick mortar joints ,cost of screening ,materials ,scaffolding ,raking out joints to 15 mm depth curing ,taxes & royalty all complete as per building specification & direction of E/I

312.23

-

-

... More
Providing 12 mm thick cement plaster (1:6) with approved quality of clean coarse sand of F.M. 1.5 including screening . Curing with all leads & lifts of water ,scaffolding ,taxes royalty all complete as per b u i l d i n g s p e c i f i c a t i o n & direction of E/I.

2606.4

-

-

... More
Supplying, fitting and placing HYSD bar reinforcement in super-structure complete as per drawing and technical specifications

14.5

-

-

... More
Providing all materials ,labors & d o i n g White washing three coat over new surface with approved quality of lime including cost of cleaning surface thoroughly and removing the scales of smoke & ash marks with jhama rubbing, scaffolding washing of floor sand taxes all complete as per building specification and direction of E/I.

2606.4

-

-

... More
Supplying Fitting and Fixing M.S. Grill gate made of 20*6 mm M.S. Flat fitted on 25mm *25 mm 6 mm M.S. angle frame as per approved design & drawing, properly fabricated with joints continuous fillet welded & finished smooth, providing necessary locking arrangements with Haskell including cost of fabrication & dummy duly fixed in C.C. 1:2:4) blocks of required size applying a red lead paints over steel works, taxes, carriage of grill to work site, as per the building specification & direction of E/I. ( w h e r e m a t e r i a l s is n o t supplied by the Dept.) Grill Gate @ 63 kg per Sqm

13.29

-

-

... More
Providing primer one coat of red lead paint of approved make over new steel surface including preparing the surface after cleaning, removing rust, dirt, scales, smokes and grease and cleaning the surface thoroughly including cost of scaffolding and taxes all complete as per building specification and direction of E/I.

13.29

-

-

... More
Providing 2(two) coats of Painting with ready mixed paints of approved shade & make over steel surface including cleaning the surface thoroughly, scaffolding & taxes all complete as per building specification & direction of E/I.

13.29

-

-

... More
Brick upto 20 KM (6.05X 500)

66.52

-

-

... More
Steel upto 10 km (0.48 )

6.64

-

-

... More
Sand upto 10 KM (25.94 X 0.012 + 6.05 X0.33 + 6.91 X0.44 )

110.41

-

-

... More
Chips upto 11 KM (6.91 X0.88 )

90.72

-

-

... More
Cement Upto 10 KM (6.91 X 0.313 + 6.05 X0.08 + 25.95 X0.012 )

13.96

-

-

... More
Staff Quarter at WTP E / W i n e x c a v a t i o n i n foundation trenches in ordinary soil (vide classification of soil i t e m - A ) & d i s p o s a l o f excavated earth obtained to a distance up to 50 M including all lift leveling ,ramming the foundation trenches removing root of trees, shurbs all complete as per approved design building specification and direction of E/I.

63.56

-

-

... More
Providing ,coarse clean sand in filling in foundation trenches/in plinth including ramming & watering in layers not exceeding 150 mm thick with all leads & lift, including cost of all materials ,labour ,royalty & taxes all complete as per b u i l d i n g s p e c i f i c a t i o n & direction of E/I.

4.63

-

-

... More
Supplying all materials, labours, tools & doing providing designation 75 A, one brick flat soiling (75 mm)in foundation trenches joints filled with local sand including cost of watering taxes royalty all complete. as per specification & direction of E/I

4.63

-

-

... More
PCC 1:3:6 in Foundation (Plain cement concrete 1:3:6 nominal mix in foundation with crushed stone aggregate 40 mm nominal size mechanically mixed, placed in foundation and compacted by vibration including curing for 14 days.)

9.27

-

-

... More
Providing designation 75 A brick work in C.M. (1:6)in f o u n d a t i o n & p l i n t h w i t h approved quality of clean coarse sand of F.M. 2 to 2.5 including providing 10 mm thick mortar joints ,cost of screening ,materials ,scaffolding ,raking out joints to 15 mm depth curing ,taxes & royalty all complete as per building specification & direction of E/I

40.09

-

-

... More
Providing 25 mm thick water proof cement plaster (1:6) with clean coarse sand of F.M 2.5 to 3 including screening, curing with all leads and lift of water, scaffolding taxes & royalty all complete as per building specification & direction of E/I.

28.73

-

-

... More
Providing designation 75 A brick work in C.M. (1:6) in superstructure with approved quality of clean coarse sand of F . M . 2 t o 2 . 5 i n c l u d i n g providing 10 mm thick mortar jo i n t s , c o s t o f s c r e e n i n g ,materials ,scaffolding ,raking out joints to 15 mm depth curing ,taxes & royalty all complete as per building specification & direction of E/I

52.85

-

-

... More
Lintel Beam Furnishing and Placing Reinforced/Prestressed cement concrete in super-structure as per drawing and Technical Specification. RCC Grade M20, For solid slab super-structure.

2.81

-

-

... More
Chajja Furnishing and Placing Reinforced/Prestressed cement concrete in super-structure as per drawing and Technical Specification. RCC Grade M20, For solid slab super-structure.

11.28

-

-

... More
Furnishing and Placing Reinforced/Prestressed cement concrete in super-structure as per drawing and Technical Specification. RCC Grade M20, For solid slab super-structure.

0.96

-

-

... More
Supplying fitting & fixing good quality ,well dressed & well seasoned sal wood work in choukhat in doors ,windows, , s k y l i g h t s , f a n l i g h t a n d celestial windows openings ,including wedge over clamps a l l c o m p l e t e i n c l u d i n g application of two coats of wood preservative of approved quality on the surface butting walls & lintels all complete as per building specification & direction of the E/I.

3

-

-

... More
Supplying fitting and fixing 250 X 20 X 6 mm L-type M.S . Clamp properly fish tailed .including making holes and setting the same in 375 X 125 X 75 mm cement concrete block (1:2:4) with cost of all labour and materials and taxes as per building specification and direction of E/I .

76

-

-

... More
Supplying all materials ,labors and fitting & fixing 38 mm (1.5) thick well seasoned Sal wood battened shutter ledged & braced in door and windows with oxidized iron fitting such as hinges, sliding door bolts, tower bolts, handles or rings, hooks and eyes ,cleats ,sand block as per schedule, taxes & royalty all complete as per b u i l d i n g s p e c i f i c a t i o n & d i r e c t i o n o f E n g i n e e r –in-Charge

23.7

-

-

... More
Supplying, fitting & fixing M.S. /Grill made of 20*6 mm M.S. Flat as per approved design & drawing properly fabricated with Joints continuous fillet welded and finished smooth ,carriage of grill to work site ,hoisting as per the building specification and direction of E/I.(where materials is not supplied by the Dept.) @40Kg/sqm (40x7.56m2)

283.2

-

-

... More
Providing 25 mm thick pre cast R.C.C. M-150 with nominal mix of (1:2.4) in jali with approved quality of stone chips of 6 mm nominal size and clean coarse sand of FM 2.5 to 3 with 1.6 mm thick M.S. wire as per approved design and drawing and placing the same in position true to plumb and level and properly grouted with cement mortar (1:3) including cost of curing, scaffolding and finishing all complete as per b u i l d i n g s p e c i f i c a t i o n a n d direction of E/I.

0.23

-

-

... More
Providing and fixing fan hook of 16 mm dia M.S. bar 1 meter long bent to required size and shape placed in position and fixing in R.C.C. slab/beam at the time of casting all complete as per building specification and direction of E/I.

2

-

-

... More
Supplying Fitting and Fixing M.S. Grill gate made of 20*6 mm M.S. Flat or16mm M.S. bar fitted on 25x25x6mm , M.S. angle frame 60x60x6mm including cost of fabrication , pro vinding necessary locking arrangment with haskal & dummy duly fixed in C.C. 1:2:4) blocks of required size applying a red lead paints over steel works, taxes, carriage of grill to work site, as per the building specification & direction of E/I. ( w h e r e steel is n o t supplied by the Dept.) Grill Gate @ 63 kg per Sqm (2 x1.05 x 1.95 x 63 = 257.985)

257.99

-

-

... More
Providing 6 mm thick cement plaster (1:4) in ceiling with approved quality of coarse sand of F.M. 1.5 including screening, curing with all leads & lifts of water ,scaffolding ,taxes & royalty all complete as per building specification & direction of E/I

68.34

-

-

... More
Providing 12 mm thick cement plaster (1:6) with approved quality of clean coarse sand of F.M. 1.5 including screening . Curing with all leads & lifts of water ,scaffolding ,taxes royalty all complete as per b u i l d i n g s p e c i f i c a t i o n & direction of E/I.

576.82

-

-

... More
Providing average 115 mm thick lime tracing (24 lime :36 shurkhi:100 brick khoa) well beaten and compacted including maintaining proper level & slope, making ghundi with finishing treatment, cost of carriage, curing ,royalty & taxes all complete as per building specification & direction of E/I.

60.33

-

-

... More
F i l l i n g i n foundation trenches & plinth in layers not exceeding 150 mm thick well watered ,rammed ,fully compacted & fine dressed with earth obtained from e x c a v a t i o n o f f o u n d a t i o n trenches within a lead of 50 m & lift of 1.5 m all complete as per building specification & direction of E/I.(Mode of measurement :- compacted volume)

82.98

-

-

... More
Providing average 150 mm thick dry rammed khoa bitten to 1 1 2 m m ( c o m p a c t e d w i t h water) made of well burnt or j h a m a b r i c k s i n c l ud i n g ramming p r o p e r l y t i l l compacted t h i c k n e s s i s achieved, curing & carriage of water with all leads making proper slope & blending the top with cement mortar (1:10) all complete as per building specification & direction of E/I.

82.98

-

-

... More
Providing 25 mm thick first class patent stone flooring (1:2:4) with stone chips in two layers , bottom layer 19 mm thick (1:2:4)with 12 mm to 6 mm size graded stone chips and top layer 6 mm thick (1:2) with 6 mm down stone chips in panels including cost of curing ,finishing the surface smooth by rubbing with carborandum stone taxes & royalty with all complete as per building specification & direction of E/I.

82.98

-

-

... More
Providing designation 75 A one brick on edge flooring in C.M. (1:4) inwith top surface flush pointing in cement mortar (1:4) with approved quality of sand including cost of curing taxes, royalty all complete as per building s pecification and direction of E/I .

82.98

-

-

... More
w h i t e washing three coat over new surface with approved quality of lime including the cost of cleaning s u r f a c e t h o r o u g h l y a n d removing the scales of smoke of mash marks with jhama rubbing ,scaffolding washing of floor sand taxes all complete as per b u i l d i n g s p e c i f i c a t i o n a n d direction of E/I. Less 50% of item 18(C)

283.77

-

-

... More
Providing all materials ,labors & d o i n g 2 ( t w o ) c o a t c o l o u r washing over a two coat of white wash over the new surface with approved quality of lime including the cost of cleaning s u r f a c e t h o r o u g h l y a n d removing the scales of smoke of mash marks with jhama rubbing ,scaffolding washing of floor sand taxes all complete as per b u i l d i n g s p e c i f i c a t i o n a n d direction of E/I. Quantity as per item no 18(B)

211.97

-

-

... More
Providing two coats of painting with ready mix paint synthetic enamel paint over a coat of primer of approved shad and make over new wooden s u r f a c e a f t e r c l e a n i n g , removing dirt scales, smokes, grease and sand papering including cost of scaffolding and taxes all complete as per b u i l d i n g s p e c i f i c a t i o n & direction of E/I. Quantity as per item no 13 x 2.25 i.e ( 29.205 x 2.25)

22.62

-

-

... More
Providing primer one coat of red lead paint of approved make over new steel surface including preparing the surface after cleaning, removing rust, dirt, scales, smokes and grease and cleaning the surface thoroughly including cost of scaffolding and taxes all complete as per building specification and direction of E/I. (As per item no 14+17) [2 x(7.56+ 4.10)]

18.72

-

-

... More
Providing 2(two) coats of Painting with ready mixed paints of approved shade & make over steel surface including cleaning the surface thoroughly, scaffolding & taxes all complete as per building specification & direction of E/I.

18.72

-

-

... More
Supplying, fitting and placing HYSD bar reinforcement in super-structure complete as per drawing and technical specifications

1.79

-

-

... More
Carrage of Material Brick upto 8 km

48.78

-

-

... More
Steel upto 5 km

1.79

-

-

... More
Sand upto 10 KM

107.14

-

-

... More
Stone Chips upto 10 KM

125.02

-

-

... More
Cement Upto 5 KM

59.37

-

-

... More
Earth Work in excavation (As per I.S. 3114/1965) for laying of Different types and size of pipes so as to give one meter average cover over the socket of pipe with disposal of excavated earth within initial lead and lift as per specification and direction of Engineer in-charge (b) For classification of soil item -B 10x.75x0.3

32.25

-

-

... More
Providing and supplying GI pipe (tata Mark) or Equivalent including all carrage , royality, CP & OHC 25mm dia

5

-

-

... More
20mm dia

20

-

-

... More
15mm dia

15

-

-

... More
Supplying and fixing of G.M. ferrule of approved make in existing C.I. main including drilling and taping C.I. main all complete as per specification and direction of Engineer-in-Charge. (i) 3 mm, 6 mm, 10 mm dia ferrule weight not less 425 gms.

2

-

-

... More
Providing and fixing Gun metal full way valve of approved quality, all complete, as per specification and direction of E/I. 25mm dia

2

-

-

... More
20 mm dia

1

-

-

... More
Supplying and fixing G.I. fittings of approved make all complete as per specification and direction of E/I. (1) Elbow 25mm dia

8

-

-

... More
20mm dia

3

-

-

... More
15mm dia

6

-

-

... More
(2) TEE 25mm dia

1

-

-

2

-

-

... More
(3) REDUCING SOCKET 25 mm dia

2

-

-

... More
REDUCING SOCKET

2

-

-

... More
(4) Nipple 25mm dia

2

-

-

... More
20mm dia

2

-

-

... More
15mm dia

4

-

-

... More
(4) Nipple

2

-

-

... More
(6) UNION SOCKET 25mm dia

2

-

-

... More
20mm dia

1

-

-

... More
15mm dia

2

-

-

... More
(5)PLUGS

1

-

-

... More
(6) UNION SOCKET

2

-

-

... More
(7) SOCKET 25mm dia

2

-

-

... More
20mm dia

3

-

-

... More
15mm dia

5

-

-

... More
(7) SOCKET

8

-

-

... More
Making long screw in G.I.pipe including supplying and fitting Jam nuts and extra socket etc. all complete as per specification and direction of E/I. 25mm dia

1

-

-

... More
20mm dia

1

-

-

... More
Laying of G.I. pipes of approved make in trenches with red lead and yarn with socket and screw joints and cutting pipes to sizes and threading ends where necessary etc. all complete as per specification and direction or Engineer-in-Charge.(Pipes to be supplied departmentally free of cost).25mm dia

100

-

-

... More
Supplying labour and tools for fixing G.I. pipes with Red lead and yarn of following nominal bore with screwed and socketted joints on wall, ceiling and floor including supplying and fitting of wall hooks or pipe clamps, wooden plugs, cutting pipes to size and threading ends if required etc. all complete as per specification and direction of Engineer-in-Charge. (Pipe with socket to be supplied departmentally free of cost). 15mm dia

15

-

-

... More
20mm dia

10

-

-

... More
25mm dia

5

-

-

... More
Providing and fixing 15mm dia male ended C.I.Body brass spindle valve and seat bib cock of approved quality (Wt. not less than 400gms.) with extra socket all complete as per specification and direction of E/I.

4

-

-

... More
Cutting chajja or cornice for laying G.I. pipe and restoring the same with R.C.C.(1:2:4) brick work in cement mortar (1:4) and cement plaster(1:4) as per specification and direction of Engineer-in-Charge.

2

-

-

... More
Making holes in walls for laying G.I. pipes and restoring the same after pipe laying as per specification and direction of E/I. 125mm thick wall

2

-

-

... More
250mm thick wall

2

-

-

... More
Polythene water storage tank of ISI mark (e.g. sintex / Sinter / Himgiri/Gangotri etc.) with cover and locking system Including carriage, CP, OHC & installation charge.

500

-

-

... More
E a r t h w o r k i n f i l l i n g i n foundation trenches & plinth in layers not exceeding 150 mm thick well watered ,rammed ,fully compacted & fine dressed with earth obtained after cutting within a lead of 50 m & lift of 1.5 m all complete as per building specification & direction of E/I.(Mode of measurement :- compacted volume)

2.25

-

-

... More
Making long screw in G.I.pipe including supplying and fitting Jam nuts and extra socket etc. all complete as per specification and direction of E/I. 25mm dia

1

-

-

... More
Laying of G.I. pipes of approved make in trenches with red lead and yarn with socket and screw joints and cutting pipes to sizes and threading ends where necessary etc. all complete as per specification and direction or Engineer-in-Charge.(Pipes to be supplied departmentally free of cost).25mm dia

100

-

-

... More
E a r t h w o r k i n f i l l i n g i n foundation trenches & plinth in layers not exceeding 150 mm thick well watered ,rammed ,fully compacted & fine dressed with earth obtained after cutting within a lead of 50 m & lift of 1.5 m all complete as per building specification & direction of E/I.(Mode of measurement :- compacted volume)

30

-

-

... More
Providing and supplying GI pipe (tata Mark) or Equivalent including all carrage , royality, CP & OHC 25mm dia

100

-

-

... More
E/W in excavation in foundation trenches in foundation trenches in ordinary soil (vide classification of soil item-B) & disposal of excavated earth obtained to a distance upto 50M including all lift leveling, rammimg the foundation trenches removing root of trees, shrubs all complete as per approved design.building specification and direction of E/I + Extra for earth work in hard soil as per approved design.building specification and direction of E/I

14.28

-

-

... More
Providing, coarse clean sand in filling in foundation trenches/ in plinth including ramming & watering in layers not exceeding 150mm thick with all leads, including cost of materials, labour, royalty & taxes all complete as per building specification & direction of E/I.

0.69

-

-

... More
Providing designation 75A one brick falt soling joint filled with local sand including cost of watering taxes royalty all complete as per building specification and direction of E/I.

0.93

-

-

... More
PCC 1:3:6 in Foundation (Plain cement concrete 1:3:6 nominal mix in foundation with crushed stone aggregate 40 mm nominal size mechanically mixed, placed in foundation and compacted by vibration including curing for 14 days.)

1.02

-

-

... More
Honey comb Brick work with 15% vertical gaps in rest part of wall-85%

1.05

-

-

... More
Furnishing and Placing Reinforced/Prestressed cement concrete in super-structure as per drawing and Technical Specification. RCC Grade M20, For solid slab super-structure.

3.32

-

-

... More
Supplying, fitting and placing HYSD bar reinforcement in super-structure complete as per drawing and technical specifications

0.26

-

-

... More
Providing 25 mm thick water proof cement plaster (1:6) with clean coarse sand of F.M 2.5 to 3 including screening, curing with all leads and lift of water, scaffolding taxes & royalty all complete as per building specification & direction of E/I.

16.58

-

-

... More
Providing 6 mm thick cement plaster (1:4) in ceiling with approved quality of coarse sand of F.M. 1.5 including screening, curing with all leads & lifts of water ,scaffolding ,taxes & royalty all complete as per building specification & direction of E/I

1.62

-

-

... More
Providing 1.5mm cement punning including curing, carriage of water with all leads and lifts as per building specification and direction of E/I.

21.44

-

-

... More
Providing 12 mm thick cement plaster (1:6) with approved quality of clean coarse sand of F.M. 1.5 including screening . Curing with all leads & lifts of water ,scaffolding ,taxes royalty all complete as per b u i l d i n g s p e c i f i c a t i o n & direction of E/I.

12.6

-

-

... More
Providing supplying & fixing of C.I. main holl cover size 500x450mm (wt not less than 25 kg) on septic tank etc. all complete as per direction of E/I.

2

-

-

... More
Providing brickbats of 90 mm to 45 mm size of approved quality in the gap between wall of the pit and earth including cost of materials, labours, taxes, royalty, carriage at site etc. all complete as per standard specifications and direction of the E/I.

6.73

-

-

... More
Supplying materials and labours for construction inspection chamber of designation class 75-B bricks size 750mm deep, 600 mm x 450 mm internal dimension having 250 mm wall thickness in cement mortar (1:6) including 12 mm cement plaster (1:4) with punning on side and cement plaster (1:6) with 600 mm x 475 mm G.I. cover with frame (weight not less than 36 kg.) along with earht work in excavation and 80 mm thick PCC-(1:3:6) in foundation and refilling all complete as per specification and direction of E/I.

5

-

-

... More
Carriage of materials Brick upto 8 km

4.35

-

-

... More
Steel upto 5 km

0.26

-

-

... More
Sand upto 10 KM

2.9

-

-

... More
Stone Chips upto 10 KM

3.81

-

-

... More
Cement Upto 5 KM

6.47

-

-

... More
Supplying, fitting and fixing vitreous white glazed earthen ware I.W.C. of parry Hindustan or any other I.S.S.approved make with 100mm H.C.I. ‘p’ trap 15 litres C.I. pull and let go flushing cistern of names or other I.S.S.equivalent make, complete with all fittings,C.I. or C. C.brackets 32mm alkathene/P.V.C. telescopic flush, pipe about 2 M long with one brass coupling and clamps G.I. chain and pull including supplying and fixing a pair of vitreous white glazed earthenware ware footrest to be fixed in floor 15mm C.I. body brass spindle stope cock of weight not less than 50grms, 15mm P.V.C. connection pipe 450 mm. long and the exposed pipe and cistern with two coats of approved paint over a coat of red oxide primer etc. all complete as per specification and direction of E/I. 580 mm long with 12.5 lit. low level PVC cistern

2

-

-

... More
Supplying fitting and fixing vitreous white glazed earthen ware wash hand basin of Perry of Hindustan or any other iSS apprived make supported on painted C.I. or RS Brackets 32mm C.I. brass waste 15mm dia.C.I. body brass spindle stop cock of approved quality of weight not less than 350grams, 32mm P.V.C. waste pipe 750mm long with brass coupling at one end and making plumber joints etc. all complete as per specification and direction of E/I.

2

-

-

... More
Supplying S.W.R.U.P.V.C. pipes of approved make 1) 110mm dia 3M double socket PVC/SWR Pipe - 4kg/ sqm (350)

2

-

-

... More
1219mm (4'-0) double socket PVC/SWR Pipe - 4kg/ sqm (359)

2

-

-

... More
609.6mm (2'-0) double socket PVC/SWR Pipe - 4kg/ sqm (365)

4

-

-

... More
2) 75mm dia 3M double socket PVC/SWR Pipe - 4kg/ sqm (348)

2

-

-

... More
1219mm (4'-0) double socket PVC/SWR Pipe - 4kg/ sqm (357)

2

-

-

... More
609.6mm (2'-0) double socket PVC/SWR Pipe - 4kg/ sqm (363)

4

-

-

... More
Supplying SWR P.V.C fitting and labour, tools and equipments for laying of all size SWR fitting and fixing in trenches/on wall etc. all complete as per direction of E/I. 110mm dia coupler (SI-427)

3

-

-

... More
Door tee (SI-406)

2

-

-

... More
Plain bend (SI-391)

2

-

-

... More
Door bend (SI-394)

2

-

-

... More
Door Y (SI-424)

2

-

-

... More
Pipe clip (SI-440)

4

-

-

... More
Vent cowl (SI-434)

2

-

-

... More
Rubber ring (SI-469)

32

-

-

... More
Door sOCKET (SI-472)

6

-

-

... More
75mm dia coupler SI-425

3

-

-

... More
Door tee (SI-404)

2

-

-

... More
Plain bend (SI-389)

2

-

-

... More
Door bend (SI-392)

2

-

-

... More
Door Y (SI-422)

2

-

-

... More
Pipe clip (SI-432)

2

-

-

... More
Rubber ring (SI-467)

30

-

-

... More
Round jali 75mm SI-455

2

-

-

... More
Nahani trap with jali 75mm SI-452

4

-

-

... More
110mm x 75mm dia P. trap (110X110mm) SI-442

2

-

-

... More
Reducer (110X75mm) SI-429

4

-

-

... More
1000 ML Solvent cement SI-483

2

-

-

... More
Wirirn g for light point /fan point/exhaust point/call bell point with 1.5 sq mm FR PVC insulated copper conducter single core cable in surface / recessesd PVC conduit with piano type switch, phenolic laminated sheet suitable size PVC /GI box etc. Group B

26

-

-

... More
Supplying and fixing suitable size GI/PVC box on surface or in recess with phenolic laminated sheet cover in front including providing and fixing 5 pin 5/6 amp socket outlet and 5/6 amps piano type swithch connection, painting etc. as required

6

-

-

... More
Supplying and fixing suitable size GI/PVC box on surface or in recess with phenolic laminated sheet cover in front including providing and fixing 6 pin 15/16 amp socket outlet and 15/16 amps piano type swithch connection, painting etc. as required

4

-

-

... More
Wiring for circuit/sub main wiring along with earth wire with the following size PVC insulated copper conducter single core cable in surface /recessed PVC conduit as required 2*2.5SQmm +1*2.5Sqmm earth wire

100

-

-

... More
Wiring for light power plug with 2*4 sqmm FR PVC insulated copper conducter single core cable in surface/recessed PVC conduit along with 1 no. 4 sqmm FR PVC insulated cover conducter single core cable for loop earthing as required

50

-

-

... More
S/F batten or angle holder complete including connection etc. as required

20

-

-

... More
Earthing with G.I. earth pipe 4.5 M long 40mm dia  including accessories and providing masonry enclosure with  cover  plate having locking arrangement and watering pipe etc with charcoal ,salt all complete as per electrical rule

2

-

-

... More
Supplying ,fitting and fixing 2 pin 5 amp ceiling rose on the existing junction box including connection as required

6

-

-

... More
JSEB charges with meter

2

-

-

... More
Supplying and fixing following way single pole neutral, sheet, MCB distribution board, 240 volts, on surface/recess, complete with tinned copper busbar, neutral busbar, earth bar, din bar, detachable gland plate, interconnections, phosphatized and powder painted including earthing et. as required(But without MCB/RCCB/Isolator) 6way single door

2

-

-

... More
Supplying and fixing 6 amps to 32 amps ratin, 240volts, B series miniature circuit breaker suitable for lighting and other loads of following poles in the existing MCB DB complete with connections testing and commissioning etc. as required.

6

-

-

... More
S/F SPN RCCB: Supplying and fixing following rating double pole, (Single Phase and neutral) 240 volts residual current circuit breaker (RCCB) having a sensitivity current upto 300 milliamperes in the existing MCB DB Complete with connection testing and commissioning etc. as required. 16/25 amps

2

-

-

... More
Clear Water Rising Main of 100mm, 200 mm dia DI K-7 for ESR I & II Providing & Supplying centrifugally ISI Mark Centrifugally cast (spun) ductile iron pipe of 100mm and above all diameter for water works with socket and spigot ends confirming to IS8329/2000 in standard working lengths of 4.5, 5.5 & 6 m suitable for classification K-7 suitable for push on joint (Rubber gasket D jointing) with cement mortar lining on inside surface and outside zinc and bituminous coating. Including all other taxes insurance carriage to work site with loading Unloading etc. (Note The rate of F.O.R at work site in jharkhand including Royality, inspection, C.P and other taxes. ) Class K-7 100mm

200

-

-

1574

-

-

... More
Supplying labours, tools and tackles for testing of laid CI/UPVC/HDPE/ AC pressure pipes upto 60 m head of water all complete as per specification and direction of E/I. 100mm

200

-

-

1574

-

-

... More
Providing and supplying ISI standard D.I. specials & fitting with sealing rubber gasket of S.B.R. complete with cast iron follower gland and M.S. nut & bolts coated or otherwise protected from rusting and suitable for D.I. pipes including ED, CST all taxes e t c . complete as per I.S. 9523 (Including 10% C.P and 5% OHC) as per item-4 100 to 150 mm dia.

100.27

-

-

... More
200 to 300mm dia.

1444

-

-

... More
Providing Double Flanged Sluice valve confirming for IS 2906/14846 including worn gear arrangements as per test pressure stainless steel spindle caps including all taxes transportation etc.complete. With including 10% CP with E.D Sluice valve PN 1.6 100mm (without Byepass arrangement)

1

-

-

2

-

-

... More
Providing and supplying Kinetic Double Orifice type Air Valves confirming to IS 14845 as per MJP’s standard specifications combined with screw down isolating valve, small orifice elastic ball resting on a gun metal orifice nipple, large orifice vulcanite ball seating on moulded seat ring, inlet face and drilled, including insurance, third party inspection charges, loading, unloading, transportation upto departmental stores, excluding GST levied by GOI & GOM in all respect etc. complete 80mm dia

2

-

-

... More
Earth Work in excavation (As per I.S. 3114/1965) for laying of Different types and size of pipes so as to give one meter average cover over the socket of pipe with disposal of excavated earth within initial lead and lift as per specification and direction of Engineer in-charge (b) For classification of soil item -B

1239.78

-

-

... More
Earthwork in excavation of foundation trenches as per designed section in ordinary or soft rock (vide classification of soil item C ) and disposel of excavated material so obtained (50 m awaty from the edge of the trenches ) with in initial lead of 150 m and initial lift of 1.5 M as per specification and direction of E/I.(in ordinary or soft rock where blasting is not required)

137.75

-

-

... More
Supplying labours, tools, tackles, lubricant etc. for laying and jointing C.I.S/S tyton pipes (class LA) /D.I. pipe in trenches supplying rubber gasket (Rubber gaskets confirming to I.S.S.- 5382- 1969) and making gasket joints including providing night guard,barrier and red light to safe guard against accident, all complete (Pipe to be suppllied departmenatlly free of cost and laying of pipes is to be done as per I.S.S.3114-1985) as per design, specification and direction of E/I. Class K-7 with Rubber ring 100mm

200

-

-

1574

-

-

... More
Labour charge for one cutting of DI / CI pipes and specials including supplying, necessary tools and plants, chipping or refilling the surface finish as per specification and direction of E/I Class K-7 100mm

5

-

-

32

-

-

... More
Supplying labours, tools and tackles for testing of laid C.I. or U.P.V.C. or H.D.P.E. or A.C. pressure pipe upto 60metre head of water all complete as per specification and direction of E/I. (Water to be supplied free of cost departmentally). Class K-7 100mm

200

-

-

1574

-

-

... More
Supplying tools and cutting road as well restoring the same as per specification and direction of E/I. (a) Pucca Road (Except black top only taken out material to be used) for cutting road as per requirement. Approx. 40% of Pucca Road. Total Length

283.84

-

-

... More
Dismantling of Cement Concrete Pavement (Dismantling of cement concrete pavement by mechanical means using pneumatic tools, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 metres, stacking serviceable and unserviceable materials separately) 40 % of total road cutting work

42.58

-

-

... More
Providing ,coarse clean sand in filling in foundation trenches/in plinth including ramming & watering in layers not exceeding 150 mm thick with all leads & lift, including cost of all materials ,labour ,royalty & taxes all complete as per b u i l d i n g s p e c i f i c a t i o n & direction of E/I. 40 % Pucca Road + 40 % of PCC restoration work

106.44

-

-

... More
Providing designation 75A one brick falt soling joint filled with local sand including cost of watering taxes royalty all complete as per building specification and direction of E/I. 40 % Pucca Road + 40 % of PCC restoration work

1419.2

-

-

... More
PCC 1:3:6 in Foundation (Plain cement concrete 1:3:6 nominal mix in foundation with crushed stone aggregate 40 mm nominal size mechanically mixed, placed in foundation and compacted by vibration including curing for 14 days.) 40 % Pucca Road + 40 % of PCC restoration work

212.88

-

-

... More
Supplying labour & tools for fixing Kinectic double orific type Air valve in trenches as per specification and direction of E/I. ( Air valve to be supplied departmentally free of cost). 100mm dia

2

-

-

... More
Supplying Labour and tools for fixing cI sluice valve trenches with a pair of cI Tail pair including making) flanged joints as per I.S. specification, including flanged joints as per IS specification confirming to I.S.S. 782 – 1978 confirming to I.S.S. 6587 – 1972 and nuts and bolts confirming to I.S.S. 1364 – 1983). Including drilling holes in flanged if required as per specification and direction of E/I. (Sluice valve and pieces to be supplied departmentally free of cost). 100mm

1

-

-

2

-

-

... More
Providing, Fixing and supplying ISI mark CI D/F reflux valves (non-return valves) of following dia including all taxes (central and local), railway freight, inspection charges unloading from railway wagon, loading into truck, transportation upto departmental stores/ site, unloading, stacking etc. complete. Reflux valves as per I.S.5312 Part I(1984). 200mm (PN-1.6 with byepass arrangement.)

2

-

-

... More
Lowering, laying and jointing in position following C.I. D/F Reflux valves, Butterfly valves and Sluice valves including cost of all labour, jointing material, including nut bolts and giving satisfactory hydraulic testing, etc. complete. (Rate for all class of valves) 200mm dia

2

-

-

... More
Earthwork in back filling the trenches after laying different types and sizes of pipes with earth removed during excavation within initial lead and lift as per specification and direction of Engineer-in-Charge ( for classification of Soil item A & B )

1323.04

-

-

... More
S u p p l y a l l m a t e r i a l s & construction of Thrust Block where required

1

-

-

... More
Construction of B.W. masonry valve chamber as per enclosed annexure (1.2m X.9m X1.5m )

2

-

-

... More
Carrage of Material Brick upto 8 km

1128

-

-

... More
Sand upto 10 KM

321.48

-

-

... More
Stone Chips upto 10 KM

304.56

-

-

... More
Cement Upto 5 KM

32.86

-

-

... More
5,00,000 Litre Capacity E.S.R. for Zone-1 (18.0 M Staging) Designing (aestheticalyy) , and Constructing Rcc elevated Service reservoirs of following capacity with RCC staging consisting of columns, internal and external bracings spaced vertically not more than 4.5 meters centre to centre of E.S.R having capacity above 500 m3 & not more than 6 m c/c of E.S.R having capacity 500 m3 including excavation in all types of strata, foundation concrete, cement plaster with water proofing compound to the inside face of the container including refilling disposing of the surplus stuff within a lead of 50 meters, all labour and material charges including lowering, laying, erecting hoisting and jointing of pipe assembly of inlet, outlet wash out over flow and bypass aeeangement as per approved design. providing and fixing acessories such as ms ladder ct manhole frame and cover, water level indicator. lightning conductor GI pipes railing around walk way and top floor slab, providing spiral stair case from ground level to roof level ,M.S Grill Gate of 2 Mtrs height with locking arrangement , of approved design, BB , masonary chambers for all valves , ventilating shaft , providing and applying there coats of cement paint to the structure including roof slab and epoxy paint to internal surface & anti -terminate treatment for underground parts of the structure and giving satisfactory water tightness test as per I.S code , Then Job to including painting the name of the Scheme and other details on the reservoir as per the direction of Engineer -in- charge including Landscaping, Gardening & Plantation etc. The Design of the structure be in accordance with relevant (I.S.3370-2009 or revised)

-

-

-

... More
The design shall satisfy the stipulation as per I S 1893 - 1984 and I.S. 13920/1993 for seismic force and I.S. - 11682/ 1985 for R.C.C. staging of overhead tanks. For design having more than 6 columns, providing of internal bracing is obligatory, External bracing is also obligatory. The entire structure shall be in M/250 mix only. However concrete in contact with water such as container, base slab, wall, roof slab & footing in water borne area shall be M-300. Plain round mild steel bars grade-I confirming to I.S., 432 Part-I or high yield strength deformed bars confirming to I.S. 1786 or I.S. 1139 shall be used, grade-II mild steel bars will not be allowed. Irrespective of the type of foundation proposed in the design, one set of bracing be provided at the ground level. These rates are include providing ,M.S ladder for E.S.R's upto 2 lakhs Litres Capacity and Providing spiral staircase for E.S.R. above 2 lakhs liters capacity. Staging shall be designed with stresses of M-200 for ESR. However all RCC construction should be done in M-250 extra Concrete in contact with water shall be designed & constructed in M=300 These rates are including the cost of uplift pressure if any and entire dewatering during execution. In case of water logging area where water is struck at shallow depth extra" provision of dewatering shall be made as per site condition. All condition given in the Member Secretary’s Circular No. MJP/TS - I / 350 / 1668 dt .

-

-

-

... More
2.08.97 and MJP/S-I/350/2127 dt. 13.7.99 shall be strictly followed and additional cost is any due to these conditions is included in ratio mentioned below. 75%part rate shall be payable for reinforced concrete and plastering items of containers of E.S.R. till satisfactory hydraulic testing for water tightness is given ; and till that work shall be treated as incomplete The rates indicated in the table are excluding the cost of pipes, specials and valves required for in l e t , o u t l e t washout overflow and by - pass arrangement . The scope of work , however includes cost of erecting , laying and jointing of pipes and valves including cost of jointing materials upto 5M beyond outer face of outermost column. For ESR upto 500 cum capacity C.I.D. double flanged pipes upto 300mm dia shall be provided and C.I. Specials shall be used . For ESR above 500 cum capacity C.I./M.S . pipes assembly with minimum 8 mm thickness upto 500mm dia and in min. 10mm above 500mm dia can be used with proper anti-corrosive epoxy treatment from inside and outside.

-

-

-

... More
Below mentioned rates are for foundation, with individuals footing with bearing capacity of 30 tonnes per square meter. For raft foundations , these rates shall be increased by 7.5% where safe bearing capacity (SBC) is 5M.T, per Sq.m and by 5% where SBC is more than 5MT/ Sqm. and upto 10 MT / Sq.m This percentage of 5% or 7.5% is applicable for estimation of amount of L.S. items ESR for Extra item due to change from individual footing foundation to raft actual increase in concrete and steel quantities be paid as per relevant DSR Item The rates shall be increase by 30% for bearing piles upto depth of 10m and for further increased in depth by 5M each it shall be increased by another 10% These rates are applicable where raft is not feasible for pile foundation sulphate resistant cement shall only be used . Single Pile for the column is not permitted Group of piles shall be designed with pile cap for each column of ESR. These rates are applicable for staging height of 12 M. These rates shall be increased or decreased for per metre variation in the staging height as below For 18m staging Height 12m to 16m = 4 x 2 = 8% 16m to 18m = 2 x 3 = 6% Total = 14% Conditions from Sr.No.1 to 10 shall form a part and parcel of the tender papers and must be included in the draft tender papers for works of R.C.C. E.S.R.

1

-

-

... More
.Conditions from Sr.No.11 to 16 are for estimation purpose only and shall not appear in the tender. The design of the structure be in accordance with relevant (I.S. 3370 - 2000 or revised) Cost of 5,00,000 litres capacity

-

-

-

... More
For 18m staging Height 12m to 16m = 4 x 2 = 8% 16m to 18m = 2 x 3 = 6% Total = 14%

0.14

-

-

... More
Mountain cutting Add 15% LS of cost of pipe, Specials and valves required for inlet , outlet washout, over flow, bypass arrengment, Epoxy painting Etc and including room Below ESR

0.15

-

-

... More
1,00,000 Litre Capacity RCC Sump for fire fighting storage tank Designing (aestheticalyy) , and Constructing Rcc ground Service reservoirs / RCC sumps in M-300 mix of required capacity including excavation in all types of strata foundation concrete container walls, bottom slab top RCC roof slab / or dome, 20 mm thick cement plaster with water proofing compound in CM 1:3 proportion to inside face of the container including epoxy paint from inside including refilling and disposing of surplus stuff within lead of 50M, all labour and material charges for laying and jointing of pipe assembly for inlet, outlet, washout, overflow and bye pass arrangement consisting of C.I / MS D/F pipes, specials and valves of given diameter providing and fixing accessories such as MS ladder inside and outside, CI manhole frame and cover, water top slab, BB masonry chamber for all valves, ventilating shafts, including giving satisfactory hydraulic test and water tightness test as per IS code and providing three coat of cement paints to all expose surface of structure including roof structure etc., complete as per design data, criteria, obligatory requirements and detailed specifications. Anti-termite treatment shall be given for under ground portion of the structure The Design shall be in accordance with various relevant IS specfications (I.S 456/2000, I.S 875-1987,I.S.3370-1965 or revised) Only MS bars grade I confirming to IS 432 Part I or high yield strength deformed bars conforming to IS 1786 or IS 1139 shall be used, Grade II MS bars shall not be used Entire structure shall be in M-300 only

-

-

-

... More
The scope of pipe assembly work shall be upto 5 meters beyond outside face of the wall, cost of pipes valves and specials is not included in the rate but labour cost for laying and jointing is included The G.S.R / Sump above 15 lakh litres capacity shall be in two compartments The job included designing the structure for up lift pressure and dewatering required during entire execution and disposal of surplus excavated stuff within lead of 50 metres as directed by Engineer in charge. If up lift considered in design then these rates shall be increased by 7.5% G.S.R outlets shall be with bell mouth of approved pattern in bottom slab and cost of designing bell mouth is included in the rate Sump well includes cost opf suction pit required at bottom For pipe diameters upto 300 mm only CI pipes and CI specials shall be used. For pipe diameters above 300 mm M.S pipe and specials minimum 10mm thick shall be used with proper anti corrosive epoxy treatment from inside and outside Cost of pump house is not included inthese rates Above rates are applicable for Seismic Zones 2,3 and 4 75%part rate shall be payable for reinforced concrete and plastering items of all types of G.S.R sand sump still satisfactory hydraulic testing for water tightness is given ; and till that work shall be treated as incomplete 10% shall be added for sump if over head pump house is proposed Note: Conditions from S.No 1 to 11 shall form a part and parcel of tender and must be included in the draft tender papers for work of R.C.C G.S.R and sumps

1

-

-

... More
Cost of 1,00,000 litres capacity (100 KL)

-

-

-

... More
Add 15% LS of cost of pipe, Specials and valves required for inlet , outlet washout, over flow, bypass arrengment, Epoxy painting Etc

0.15

-

-

... More
5,00,000 Litre Capacity E.S.R for Zone-2 (18.0 M Staging) Designing (aestheticalyy) , and Constructing Rcc elevated Service reservoirs of following capacity with RCC staging consisting of columns, internal and external bracings spaced vertically not more than 4.5 meters centre to centre of E.S.R having capacity above 500 m3 & not more than 6 m c/c of E.S.R having capacity 500 m3 including excavation in all types of strata, foundation concrete, cement plaster with water proofing compound to the inside face of the container including refilling disposing of the surplus stuff within a lead of 50 meters, all labour and material charges including lowering, laying, erecting hoisting and jointing of pipe assembly of inlet, outlet wash out over flow and bypass aeeangement as per approved design. providing and fixing acessories such as ms ladder ct manhole frame and cover, water level indicator. lightning conductor GI pipes railing around walk way and top floor slab, providing spiral stair case from ground level to roof level ,M.S Grill Gate of 2 Mtrs height with locking arrangement , of approved design, BB , masonary chambers for all valves , ventilating shaft , providing and applying there coats of cement paint to the structure including roof slab and epoxy paint to internal surface & anti -terminate treatment for underground parts of the structure and giving satisfactory water tightness test as per I.S code , Then Job to including painting the name of the Scheme and other details on the reservoir as per the direction of Engineer -in- charge . The Design of the structure be in accordance with relevant (I.S.3370-2009 or revised) The design shall satisfy the stipulation as per I S 1893 - 1984 and I.S. 13920/1993 for seismic force and I.S. - 11682/ 1985 for R.C.C. staging of overhead tanks.

-

-

-

... More
For design having more than 6 columns, providing of internal bracing is obligatory, External bracing is also obligatory. The entire structure shall be in M/250 mix only. However concrete in contact with water such as container, base slab, wall, roof slab & footing in water borne area shall be M-300. Plain round mild steel bars grade-I confirming to I.S., 432 Part-I or high yield strength deformed bars confirming to I.S. 1786 or I.S. 1139 shall be used, grade-II mild steel bars will not be allowed. Irrespective of the type of foundation proposed in the design, one set of bracing be provided at the ground level. These rates are include providing ,M.S ladder for E.S.R's upto 2 lakhs Litres Capacity and Providing spiral staircase for E.S.R. above 2 lakhs liters capacity. Staging shall be designed with stresses of M-200 for ESR. However all RCC construction should be done in M-250 extra Concrete in contact with water shall be designed & constructed in M=300 These rates are including the cost of uplift pressure if any and entire dewatering during execution. In case of water logging area where water is struck at shallow depth extra" provision of dewatering shall be made as per site condition. All condition given in the Member Secretary’s Circular No. MJP/TS - I / 350 / 1668 dt . 2.08.97 and MJP/S-I/350/2127 dt. 13.7.99 shall be strictly followed and additional cost is any due to these conditions is included in ratio mentioned below.

-

-

-

... More
75%part rate shall be payable for reinforced concrete and plastering items of containers of E.S.R. till satisfactory hydraulic testing for water tightness is given ; and till that work shall be treated as incomplete The rates indicated in the table are excluding the cost of pipes, specials and valves required for in l e t , o u t l e t washout overflow and by - pass arrangement . The scope of work , however includes cost of erecting , laying and jointing of pipes and valves including cost of jointing materials upto 5M beyond outer face of outermost column. For ESR upto 500 cum capacity C.I.D. double flanged pipes upto 300mm dia shall be provided and C.I. Specials shall be used . For ESR above 500 cum capacity C.I./M.S . pipes assembly with minimum 8 mm thickness upto 500mm dia and in min. 10mm above 500mm dia can be used with proper anti-corrosive epoxy treatment from inside and outside. Below mentioned rates are for foundation, with individuals footing with bearing capacity of 30 tonnes per square meter. For raft foundations , these rates shall be increased by 7.5% where safe bearing capacity (SBC) is 5M.T, per Sq.m and by 5% where SBC is more than 5MT/ Sqm. and upto 10 MT / Sq.m This percentage of 5% or 7.5% is applicable for estimation of amount of L.S. items ESR for Extra item due to change from individual footing foundation to raft actual increase in concrete and steel quantities be paid as per relevant DSR Item

-

-

-

... More
The rates shall be increase by 30% for bearing piles upto depth of 10m and for further increased in depth by 5M each it shall be increased by another 10% These rates are applicable where raft is not feasible for pile foundation sulphate resistant cement shall only be used . Single Pile for the column is not permitted Group of piles shall be designed with pile cap for each column of ESR. These rates are applicable for staging height of 12 M. These rates shall be increased or decreased for per metre variation in the staging height as below For 18m staging Height 12m to 16m = 4 x 2 = 8% 16m to 18m = 2 x 3 = 6% Total = 14% Conditions from Sr.No.1 to 10 shall form a part and parcel of the tender papers and must be included in the draft tender papers for works of R.C.C. E.S.R. Conditions from Sr.No.11 to 16 are for estimation purpose only and shall not appear in the tender. The design of the structure be in accordance with relevant (I.S. 3370 - 2000 or revised) OHT- 1 (staging ht. 18m) Cost of 5,00,000 litres capacity (500 KL)

1

-

-

... More
For 18m staging Height 12m to 16m = 4 x 2 = 8% 16m to 18m = 2 x 3 = 6% Total = 14%

0.14

-

-

... More
Add 15% LS of cost of pipe, Specials and valves required for inlet , outlet washout, over flow, bypass arrengment, Epoxy painting Etc and including room Below ESR

0.15

-

-

... More
1,25,000 Litre Capacity RCC Sump at Zone - 2 Designing (aestheticalyy) , and Constructing Rcc ground Service reservoirs / RCC sumps in M-300 mix of required capacity including excavation in all types of strata foundation concrete container walls, bottom slab top RCC roof slab / or dome, 20 mm thick cement plaster with water proofing compound in CM 1:3 proportion to inside face of the container including epoxy paint from inside including refilling and disposing of surplus stuff within lead of 50M, all labour and material charges for laying and jointing of pipe assembly for inlet, outlet, washout, overflow and bye pass arrangement consisting of C.I / MS D/F pipes, specials and valves of given diameter providing and fixing accessories such as MS ladder inside and outside, CI manhole frame and cover, water top slab, BB masonry chamber for all valves, ventilating shafts, including giving satisfactory hydraulic test and water tightness test as per IS code and providing three coat of cement paints to all expose surface of structure including roof structure etc., complete as per design data, criteria, obligatory requirements and detailed specifications. Anti-termite treatment shall be given for under ground portion of the structure The Design shall be in accordance with various relevant IS specfications (I.S 456/2000, I.S 875-1987,I.S.3370-1965 or revised) Only MS bars grade I confirming to IS 432 Part I or high yield strength deformed bars conforming to IS 1786 or IS 1139 shall be used, Grade II MS bars shall not be used Entire structure shall be in M-300 only The scope of pipe assembly work shall be upto 5 meters beyond outside face of the wall, cost of pipes valves and specials is not included in the rate but labour cost for laying and jointing is included

1

-

-

... More
The G.S.R / Sump above 15 lakh litres capacity shall be in two compartments The job included designing the structure for up lift pressure and dewatering required during entire execution and disposal of surplus excavated stuff within lead of 50 metres as directed by Engineer in charge. If up lift considered in design then these rates shall be increased by 7.5% G.S.R outlets shall be with bell mouth of approved pattern in bottom slab and cost of designing bell mouth is included in the rate Sump well includes cost opf suction pit required at bottom For pipe diameters upto 300 mm only CI pipes and CI specials shall be used. For pipe diameters above 300 mm M.S pipe and specials minimum 10mm thick shall be used with proper anti corrosive epoxy treatment from inside and outside Cost of pump house is not included inthese rates Above rates are applicable for Seismic Zones 2,3 and 4 75%part rate shall be payable for reinforced concrete and plastering items of all types of G.S.R sand sump still satisfactory hydraulic testing for water tightness is given ; and till that work shall be treated as incomplete 10% shall be added for sump if over head pump house is proposed Note: Conditions from S.No 1 to 11 shall form a part and parcel of tender and must be included in the draft tender papers for work of R.C.C G.S.R and sumps Cost of 1,00,000 litres capacity

-

-

-

... More
Add for capacity above 100 KL, 25 KL

1

-

-

... More
Note: 10% shall be added over the cost of GSR for sump where over head pump house is proposed

0.1

-

-

... More
Add 15% LS of cost of pipe, Specials and valves required for inlet , outlet washout, over flow, bypass arrengment, Epoxy painting Etc

0.15

-

-

... More
Distribution System and Appurtenant Works for 2-Zones Earth Work in excavation (As per I.S. 3114/1965) for laying of Different types and size of pipes so as to give one meter average cover over the socket of pipe with disposal of excavated earth within initial lead and lift as per specification and direction of Engineer in-charge (b) For classification of soil item -B Add Extra for 5% for Socket

1725.11

-

-

... More
Earthwork in excavation of foundation trenches as per designed section in ordinary or soft rock (vide classification of soil item C ) and disposel of excavated material so obtained (50 m awaty from the edge of the trenches ) with in initial lead of 150 m and initial lift of 1.5 M as per specification and direction of E/I.(in ordinary or soft rock where blasting is not required)

191.68

-

-

... More
Earthwork in back filling the trenches after laying different types and sizes of pipes with earth removed during excavation within initial lead and lift as per specification and direction of Engineer-in-Charge ( for classification of Soil item A & B )

1533.43

-

-

... More
Providing and supplying in standard lengths High Denaity Polyethylene Pipe (HDPE Pipe) confirming to IS 4984-4984/12786/13488 (Latest Revision with necessary jointing materials like mechanical connector ie thread/insert joint/ quick release coupler joint/compression fitting joint or flanged joints excluding coupler/specials and taxes (Note- The rates of F.O.R at worksite in jharkhand including royality ,inspection and C.P charges.) HDPE PE -100 PN 10 90mm

5727

-

-

61

-

-

... More
Providing and supplying ISI standard D.I. specials & fitting with sealing rubber gasket of S.B.R. complete with cast iron follower gland and M.S. nut & bolts coated or otherwise protected from rusting and suitable for D.I. pipes including ED, CST all taxes e t c . complete as per I.S. 9523 (Including 10% C.P and 5% OHC) as per item-4 100 to 300mm dia.

1487.67

-

-

... More
Supplying labours and tools for laying and jointing H.D.P.E pipes in trenches and making butt welded joint supplying heating mirror, jack etc and providing night guard barrier and red light to safe guard against accident all complete as per specification and direction of E/I (H.D.P.E pipes will be supplied departmentally free of cost) H.D.P.E pipes 90/80 mm dia

5727

-

-

... More
110/100 mm dia

61

-

-

... More
Supplying labours, tools and tackles for testing of laid C.I. or U.P.V.C. or H.D.P.E. or A.C. pressure pipe upto 60metre head of water all complete as per specification and direction of E/I. (Water to be supplied free of cost departmentally). H.D.P.E pipes 90/80 mm dia

5727

-

-

... More
110/100 mm dia

61

-

-

... More
Labour charges for one cutting of H.D.P.E/U.P.V.C/A.C pressure pipe including supplying, necessary tools and plants, chipping or filling the surface finish as per specification and direction of E/I H.D.P.E 80 mm outer dia

105

-

-

... More
100 mm outer dia

2

-

-

... More
Supplying tools and cutting road as well restoring the same as per specification and direction of E/I. (a) Pucca road (except black top only taken out materials to be used) For cutting road as per requirement. Approx 40% of Pucca Road

185.22

-

-

... More
Water bound macadam Road (taken out material will be used) for cutting road as per requirement and making good the same

138.91

-

-

... More
Dismantling of Cement Concrete Pavement (Dismantling of cement concrete pavement by mechanical means using pneumatic tools, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 metres, stacking serviceable and unserviceable materials separately)

20.84

-

-

... More
Providing ,coarse clean sand in filling in foundation trenches/in plinth including ramming & watering in layers not exceeding 150 mm thick with all leads & lift, including cost of all materials ,labour ,royalty & taxes all complete as per b u i l d i n g s p e c i f i c a t i o n & direction of E/I.

24.31

-

-

... More
PCC 1:3:6 in Foundation (Plain cement concrete 1:3:6 nominal mix in foundation with crushed stone aggregate 40 mm nominal size mechanically mixed, placed in foundation and compacted by vibration including curing for 14 days.)

48.62

-

-

... More
Providing designation 75A one brick falt soling joint filled with local sand including cost of watering taxes royalty all complete as per building specification and direction of E/I.

324.13

-

-

... More
Providing Double Flanged Sluice valve confirming for IS 2906/14846 including worn gear arrangements as per test pressure stainless steel spindle caps including all taxes transportation etc.complete. With including 10% CP with E.D With bypass arrangements PN-1 80mm

9

-

-

1

-

-

2

-

-

... More
Providing, installation, testing and commissioning of Bulk Flow Meter with removable mechanism class "B" confirming to ISO: 4064/1 including all materials (excluding CI/DI fittings) and making connection with existing pipeline required for Bulk Flow Meter including cutting the existing pipe line etc complete in all respect as per technical specification and as per direction of Engineer. 80mm dia

111

-

-

... More
Supplying Labour and tools for fixing cI sluice valve trenches with a pair of cI Tail pair including making) flanged joints as per I.S. specification, including flanged joints as per IS specification confirming to I.S.S. 782 – 1978 confirming to I.S.S. 6587 – 1972 and nuts and bolts confirming to I.S.S. 1364 – 1983). Including drilling holes in flanged if required as per specification and direction of E/I. (Sluice valve and pieces to be supplied departmentally free of cost). Sluice Valve 80mm

9

-

-

1

-

-

2

-

-

... More
Construction of B.W. masonry valve chamber as per enclosed annexure (1.2m X.9m X1.5m )

12

-

-

... More
Providing ,coarse clean sand in filling in foundation trenches/in plinth including ramming & watering in layers not exceeding 150 mm thick with all leads & lift, including cost of all materials ,labour ,royalty & taxes all complete as per b u i l d i n g s p e c i f i c a t i o n & direction of E/I.

477.51

-

-

... More
Supplying transporting, the S.P. fire hydrants including duck foot bend, S.V. and S.V. road box, painting the hydrant,fixing the saddle piece, supplying, and laying required length of C.I. pipeline and jointing the same spun yarn, molten lead including caulking, fixing the S.V. road box in one brick masonry chamber in 1:5 C.M. with 12 mm thick 1:3 cement plaster both inside and outside on 1:3:6: C.C.150 mm thick etc, complete specified and directed. [As per I.S.900/1965 Revised

4

-

-

... More
Carrage of Material Brick upto 8 km

1.62

-

-

... More
Sand upto 10 KM

1742.31

-

-

... More
Stone Chips upto 10 KM

1650.6

-

-

... More
Cement Upto 5 KM

178.11

-

-

... More
Water Connections with Meter (111) Earthwork in excavation (as per IS 3114/1965) for laying of different types and sizes of pipes so as to give one metre average cover over the socket of pipe with disposal of excavation earth within intial lead and lift as per specification and direction of E/I.(Soil B)

249.75

-

-

... More
Providing and fixing of GM ferrule of approved make in existing distribution line including drilling and taping distribution pipeline all complete as per specification and direction of E/I. 3mm, 6mm ,10mmdia ferrule

111

-

-

... More
Providing and Supplying Blue MDPE pipes conforming to ISO 4427:1996 manufactured from virgin resin PE 80 Food grade compounded Raw Material having Blue Colour only with quality assurance certificate from quality agencies like WRC / CIPET (India) / DVGM / KIWA / SPGN etc. for usage in Drinking Water system. The cost shall include testing of all materials, Inspection charges, transportation up to store, transit insurance, loading, as specified and directed, unloading, stacking excluding GST levied by GOI & GOM in all respect, etc. complete as specified and directed by E/I PN 16 (SDR 9) 20mm Dia

1110

-

-

... More
Providing and fixing Gun metal full way valve of approved quality, all complete, as per specification and direction of E/I. 20mm dia and weight not less than 400gms

111

-

-

... More
Providing & Supply of Compression fittings, PN16 rated in conformation to ISO:14236-2000 and shall be tested as per ISO:3459, ISO:3501 & ISO:3503, suitable for drinking water & approved by WRAS, UK/ KIWA etc, in food grade polypropylene and shall be inclusive of all cost such as testing, inspection charges, transportation up to store, transit insurance, loading, unloading, stacking excluding GST levied by GOI & GOM in all respect, etc. complete. Metal adapter 20x1/2"

111

-

-

... More
Female Adaptor 20x1/2"

111

-

-

... More
Elbow 90 Degree 20mm dia

222

-

-

... More
Coupling20x20 mm dia

222

-

-

... More
Supplying tools and cutting road as well restoring the same as per specification and direction of E/I. (b) Water bound macadum road (taken out materials will be used) For cutting road as per requirement

66.6

-

-

... More
Earth work in back filling the trenches after laying different types and size of pipes with earth removed during excavation within initial lead and lift as per specification and direction of Engineerin- Charge. (For classification for Soil item - A & B)

249.75

-

-

... More
Providing, installing and giving satisfactory field testing of Domestic water meter, horizontal inferential multijet type with magnetic drive and dry dial suitable for ambient 50º C Temperature duly sealed against tampering complete with couplings at both ends and conforming to class B as per IS 779/1994 (VI Revision) with ISI mark along with manufacturer's test certificate and guarantee certificate, including cost of all materials and labour. (15 mm Diameter GI Pipe)

111

-

-

... More
Water METER BOX- with Weather resistant PE/ GRP box, press fitted Lid fixing & built-in or external lock.

111

-

-

... More
Providing and Supply of Clamp saddle ( DI Strap Saddle ) for house Service connection from metal pipe distribution System. Mains shall be fastened strap type with treadead outlet for serive connection . Clamp saddle shall be elastomer coated ( Insulated) type for firm grip on pipe as well as protect the coating on pipe and to insulate the unidentical metals. The saddle shall be single strap type upto pipe size of NB 600 and service outlet 15mm, 20mm, & 25mm dia. Fasteners shall be threaded nut bolt washer type. The sealling between saddle and mains shall be obtained by using a profieled elastomer seal matching to the curvature of pipe. The seal shall be elastomer type, suitable for all potable water application. The material of constrution of body, straps, fastener etc. shall be of non-corrosive such as engineering plastic (PE/PP) or stainless steel or a combination of both (100NB x15mm,20mm,25mm)

111

-

-

... More
Road Crossing Manufacturing providing and supplying spirally welded / ERW / SAW / Fabricated M.S. Pipes (Commercial Quality) including procurement of plates. Gas cutting to required size rolling, tack welding, assembling in suitable lengths to form pipes, welding on automatic welding machine and forming 'v' edge on both ends of pipe including all taxes, railway freight, insurance, unloading from railway wagon, loading into truck transport to stores / site, unloading, stacking etc. complete as per IS - 3589 and IS - 5504 as applicable as per specifications (No negative tolerance in thickness is permissible). A) For 90 mm dia DI pipe - 323.9 mm dia 9.5 mm thick MS pipe for casing (13 Nos.)

168

-

-

... More
Pushing of M.S. pipe of following dia for road crossing and raiway crossing by push through method in all types of strata by using hydraulic jack and drilling machine of required diameter below 3.0 m depth including lowering, laying, jointing of M.S. casting pipe including cost of labour, fuel and material, required welding machinery, tripod, chain pulley block, crane, blower,etc., transportation and dewatering etc. complete as directed by Engineer in charge but excluding cost of M.S. pipe. a) 200 mm to 499 mm dia MS pipe

168

-

-

... More
Providing and applying primer first coat of intertol 49 W emaline 05/ 58 pipe coat or any other equivalent approved paint to the internal surface of pipeline at site, etc. complete. a) For 300 mm dia MS pipe - 168 m X 3.142 X 0.323 (two surface) First Coat

328.81

-

-

... More
Second Coat

328.21

-

-

... More
Operation & Maintenance Cost for 1 Year 1 Year Operation & Maintenance

1

-

-

... More
Earthwork in excavation in foundation trenches in ordinary soil ( vide classification of soil item A) and disposal of excavated earth as obtained to a distance upto 50M including all lifts, evelling , ramming the foundation trenches, removing roots of trees , surbs all complete as per approved design, building specification and direction of E/I.

4117.2

-

-

... More
Filling in foundation trenches and plinth in layers not exceeding 150 mm thick well watered, rammed fully compacted and fine dressed with earth obtained from excavation of foundation trenches within a lead of 50 m and lift of 1.5 m all complete as per building specification and direction of E/I

1499.6

-

-

... More
Disposal of surplus earth beyond 50m lead by mechanical means upto 1 Km. Item 3 - Item 2.

2614.6

-

-

... More
Providing coarse clean sand in filling in foundation trenches or in plinth including ramming and watering in layers not exceeding 150mm thick with all leads and lifts including cost of all materials, labour, royalty and taxes all complete as per building specification and direction of E/I.

137.5

-

-

... More
Providing designation 75B one brick flat soling joints filled with local sand including cost of watering taxes royalty all complete as per building specification and direction of E/I.

1374.5

-

-

... More
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size).

104

-

-

... More
Provided Reinforced cement concrete work in walls (any thickness), including attached palasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level upto floor five level, excluding cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sandzone-III) : 3 graded stone aggregate 20mm nominal size)

1086.4

-

-

... More
Provided Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15 degree landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral staircases above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sandzone-III) : 3 graded stone aggregate 20mm nominal size)

122.3

-

-

... More
Providing Tor steel reinforcement of 8mm - 12 mm dia rods as per approved design and drawing excluding carriage of M.S. Rods to work site, cutting, bending, and binding with annealed wire with cost of wire removal of rust, placing the rods in position all complete as per building specification and direction of E/I.

118.7

-

-

... More
Providng 12mm thick cement plaster (1:4) with clean coarse sand of F.M. 1.5 including screening, curing with all leads and lifts of water, scaffolding taxes and royalty all complete as per building specification and direction of E/I.

3447.9

-

-

... More
Providing 1.5mm. Cement punning including curing, carriage of water with all leads and lifts all complete as per building specification and direction of E/I.

184.4

-

-

... More
Providing and fixing in position pre-cast RCC manhole cover and frame of required shape and approved qrality . HD 20

-

-

-

... More
Circular shape 560mm internal dia.

16

-

-

... More
M.S. Ladder (1 No.)

5400

-

-

... More
Carriage

-

-

-

... More
Sand for filling

146

-

-

... More
Coarse Sand

480

-

-

... More
Stone chips

490

-

-

116

-

-

... More
Cement

84

-

-

... More
Bricks

46

-

-

... More
Cost of Electromachnical of 650 KLD (2 nos.) & 600 KLD (2 nos.)

2500

-

-

... More
Operation and Maintanance for One year

1

-

-

... More
Earthwork in excavation in foundation trenches in ordinary soil ( vide classification of soil item A) and disposal of excavated earth as obtained to a distance upto 50M including all lifts, evelling , ramming the foundation trenches, removing roots of trees , surbs all complete as per approved design, building specification and direction of E/I.

589

-

-

... More
Filling in foundation trenches and plinth in layers not exceeding 150 mm thick well watered, rammed fully compacted and fine dressed with earth obtained from excavation of foundation trenches within a lead of 50 m and lift of 1.5 m all complete as per building specification and direction of E/I

37.66

-

-

... More
Providing coarse clean sand in filling in foundation trenches or in plinth including ramming and watering in layers not exceeding 150mm thick with all leads and lifts including cost of all materials, labour, royalty and taxes all complete as per building specification and direction of E/I.

89.51

-

-

... More
Providing designation 75A brick work in C.M. (1:6) in foundation and plinth with approved quality of clean coarse sand of F.M. 2 to 2.5 including providing 10mm thick mortar joints, cost of screening materials, raking out joints to 15mm depth, curing taxes and royalty all complete as per building specification and direction of E/I.

30.25

-

-

... More
Providing designation 75A brick work in C.M.(1:4) in superstructure with approved quality of clean coarse sand of F.M. 2 to 2.5 including providing 10 mm thick mortar joints, cost of screening, materials, scaffolding, raking out joints to 15 m depth, curing taxes and royalty all complete as per building specification and direction of E/I.

43.09

-

-

... More
Providing designation 125 mm thick rainforced designation 75A brick work in 1:4 in super structure with approved quality of cvlean couse sand of FM 2 to 2.5 including the cost of screening carriage of materials scape holding ranking out joint 215 mm depth curring taxes and royalty but excluding the cost of rainforcement all complete as per building specification and direction of EI

95.98

-

-

... More
Providing P.C.C M-150 with nominal mix of (1:2:4) in foundation with approved quality of stone Chip 20 mm to 6mm size graded and clean coarse sand of FM 2.5 to 3 including screening shuttaring mixing cement concrete in mixing and placing in position vibrating striking curing taxes and royalty all complete as per building specification and direction of engineer in charge.

2.63

-

-

... More
Providing P.C.C M-100 with nominal mix of (1:3:6) in foundation with approved quality of stone metal grade-III (50mm to 25mm), size clean coarse sand of F.M 2.5 to 3 including screening, shuttering mixing cement concrete in mixer and placing in position vibrating, striking, curing, taxes and royalty all complete as per building specification and direction of E/I.

122

-

-

... More
Providing P.C.C. M-75 with normal mix of (1:4:8) in foundation with approved quality of stone metal grade - lll (50 mm to 25 mm size) & clean coarse sand of F.M 2.5 to 3 including screening, shuttering, mixing cement concrete in mixer and royalty all complete as per building specification and direction of Engineer in charge.

110.88

-

-

... More
Providing RCC M-200 with nominal mix of (1:1.5:3) in all type of lintel with approved quality of stone chips 20mm to 6mm size graded and clean coarse sand of F.M. 2.5 to 3 including screening, shuttering, mixing cement concrete in mixer and placing in position, vibrating, striking, curing (but excluding the cost of reniforcement, taxes and royalty all complete, as per building specification and direction of E/I.

0.67

-

-

... More
Providing P.C.C M-100 with nominal mix of (1:3:6) in foundation with approved quality of stone metal grade-III (50mm to 25mm), size clean coarse sand of F.M 2.5 to 3 including screening, shuttering mixing cement concrete in mixer & placing in position vibrating, striking, curing, taxes & royalty all complete as per building specification & direction of E/I.

13.43

-

-

... More
Providing 25mm thick damp proof course with cement concrete M-150 with nominal mix of (1:2:4) with approved quality of stone chips of 20mm to 6mm size graded and clean coarse sand of F.M. 2.5 to 3 including screening, shuttering, and mixing cement concrete in mixer with 5% cico or any other approved water proffing compound and placing in position, stricking, curing, taxes and royalty all complete, as per building specification and direction of E/I.

7.6

-

-

... More
Providing RCC M200 with -do- in plinth beam

59.95

-

-

... More
Providing RCC M-200 with nominal mix of (1:1.5:3) inlintal beam with approved quality of stone chips 20mm to 6mm size graded and clean coarse sand of F.M. 2.5 to 3 including screening, shuttering, mixing cement concrete in mixer and placing in position, vibrating, striking, curing (but excluding the cost of reniforcement, taxes and royalty all complete, as per building specification and direction of E/I.

0.57

-

-

... More
RCC M200 in sunshed (chajja)

3.87

-

-

... More
Providing R.C.C M-200 with nominal mix (1:1.5:3) in roof slab with approved quality of stone chips 20mm to 6mm size graded and clean coarse sand of F.M. 2.5 to 3 including screening, shuttering, mixing cement concrete in mixer and placing in position, vibrating, striking, curing (but excluding the cost of reniforcement, taxes and royalty all complete, as per building specification and direction of E/I.

41.83

-

-

... More
Providing R.C.C M-200 with nominal mix of (1:1.5:3) in columns with approved quality of stone chips 20mm to 6mm size graded and clean coarse sand of F.M. 2.5 to 3 including screeing, shuttering, mixing cement concrete in mixer and placing in position, vibrating, striking, curing (but excluding the cost of reinforcement, taxes and royalty all complete as per building specification and direction of E/I.

17.21

-

-

... More
Providing R.C.C M200 with nominal mix of (1:1.5:3) in all types of beam with approved quality of stone metal grade-III (20mm to 6mm), size clean coarse sand of F.M 2.5 to 3 including screening, shuttering mixing cement concrete in mixer & placing in position vibrating, striking, curing, taxes & royalty all complete as per building specification & direction of E/I.

133.66

-

-

... More
Providing 25 mm thick precast R.C.C M - 200 with nominal mix of (1:1.5:3) jali with approved quality of stone chips of 6mm nominal size and clean coarse sand of F.M 2.5 to 3 with 1.6mm thick M.S. wire as per approved design and drawing and placing the same in position true to plumb and level and properly grouted with cement mortar (1:3) including cost of curing, scaffolding and finishing, all complete, as per building specifications and direction of E/I.

2.1

-

-

... More
Providing RCC M-200 with nominal mix of (1:1.5:3) in all type of Chajja with approved quality of stone chips 20mm to 6mm size graded and clean coarse sand of F.M. 2.5 to 3 including screening, shuttering, mixing cement concrete in mixer and placing in position, vibrating, striking, curing (but excluding the cost of reniforcement, taxes and royalty all complete, as per building specification and direction of E/I.

4.05

-

-

... More
S/P/F good quality well dressed and well seasoned sal wood work in chaukhats in doors, windows opening…. Including wedge over all clamps complete including application of two coats of wood preservative of approved quality on the surface facing wall and lintal all complete as per building specification and direction of Engineer in Charge

0.3

-

-

... More
Supplying fitting and fixing oxidised iron fittings of approved quality and make to doors and windows all complete as per building specification and direction of EI 100 mm butt hinge

24

-

-

... More
Supplying fitting and fixing 35mm thick solid core type non-decorative single leaf flush shutters in doors and windows with black board core blended with high quality phenol formaldehyde synthetic resin both side commercial veneered of standard make with oxidised iron fittings hinges, tower bolts, handle, cleats and sand blocks and taxes all complete as per building specification and direction of E/I.

13.86

-

-

... More
Providing Tor steel reinforcement of 8mm - 12 mm dia rods as per approved design and drawing excluding carriage of M.S. Rods to work site, cutting, bending, and binding with annealed wire with cost of wire removal of rust, placing the rods in position all complete as per building specification and direction of E/I.

6.4

-

-

... More
Providing Tor steel reinforcement of 8 mm & above dia rods as per approved design and drawing excluding carriage of M.S. Rods to work site, cutting, bending, and binding with annealed wire with cost of wire removal of rust, placing the rods in position all complete as per building specification and direction of E/I.

13.32

-

-

... More
Providing and fixing fan hook of 16mm dia M.S. bar 1 metre long bent to required size and shape placed in position and fixed in R.C.C. slab/ beam at the time of casting all complete as per building specification and direction of E/I.

6

-

-

... More
Supplying fixing and fitting collapsible gate of approved size and make properly fabricated with vertical double channels 20x10x2 mm at 100 mm centres and braced with M.S. flat diagonals 20x3 mm , with bottom rails of T iron 40x40x6 mm with 38 mm dia steel pulley complete with bolts nuts locking arrangement stoppers handles including applying a priming coat of red lead paint car riage hoisting and taxex all complete as per building specification and direction E/I

5.67

-

-

... More
Supplying, fitting and fixing fully glaxed steel door, windows or ventilations of standard rolled 'T' and mullion steel sectioons and size as per IS- 1038 joints met and welded with 100x16x3mm M.S. lugs fixed in cement concrete (1:2:4) blocks 15x10x10cm, size including cost of oxidised iron fittings, with hinges, handle per steps, catch springs, 3mm thick palin glass panes with Aluminimum beads and inner frame fixed with lugs with 20mm long 6.3mm G.I. counter sunk machine screw and nuts and applying a coat of red lead paint carriage to work site hoisting and placing in position in all storys and taxes all complete as per building specification and direction of E/I.

14.89

-

-

... More
Labour for fabricating, erecting, hoisting and fixing in position structural steel work in R.S. joists, channels, angles, Tees, flats, plates, lattice members, built up compound sections in columns, girders, staircase, or trusses including cost of gusset plates, holding down bolts, anchor plates at all heights and depths, bolting, welding (machining wherever necessary) with applying a priming coat of red lead paint all complete as per building specification and direction of E/I.

15.5

-

-

... More
S/F/F MS grill gate with MS grill made of 20X6 MS flats or 16 mm square bars fitted on ---- do --- E/I

-

-

-

... More
Entry gate 4M wide and 1.5M height and wicket gate 1 M wide and 1.5 M height.

400

-

-

... More
Providing designation 75A one brick flat soiling joints filled with local sand including cost of watering taxes royalty all complete as per building specification and direction of Engineer

4.77

-

-

... More
Providing designation 75A one brick on edge soling E/I (qty between road flank & drain)

26.25

-

-

... More
Providing designation 75B one brick flat soiling joints filled with local sand including cost of watering taxes royalty all complete as per building specification and direction of Engineer.

833.12

-

-

... More
Providing 50 mm thick cement concrete flooring 1:2:4 with 20 mm to 6 mm graded stone chips and top layer 6 mm thick (1:3) with 6 mm down graded chips

455.14

-

-

... More
Extra for Providing and fixing 30x4mm glass strips in joints of flooring, complete job as per specifications and direction of E/I.

948

-

-

... More
Providing and laying hydraulically machiine pressed terrazo tilles 20mm thick of approved texture with down marble chips of approved shade, size and quality, laid on 19mm, thick bed of lime mortar (1:1:1) (lime: surkhi: sand) with neat cement slurry mixed with pigment to match the shade of tiles between joints, including rubbing and polishing to granolithic finish with approved quality of carborandum stone including cost of curing, roualty and taxes all complete as per building specification and direction of E/I.

48

-

-

... More
Providing and laying hydraulically machiine pressed terrazo tilles 20mm thick in skirting of approved texture with 4 mm down marble chips of approved shade, size and quality, over 12mm thick cement palster (1:3) base with neat cement slurry mixed with pigment to match the shade of tiles between joints, including rubbing and polishing to granolithic finish with approved quality of carborandum stone including cost of curing, roualty and taxes all complete as per building specification and direction of E/I. (c) any light colour with 100% white cement

5.4

-

-

... More
Providing and laying 25 mm thick kota stone slab flooring of approved size, texture and colour laid over 19mm thick base of lime mortar (1:1:1) (lime putty : surkhi : coarse sand) and jointed with gray cement slurry mixed with pigment to match the shade of slab including rubbing and polishing to granolithic finish with approved quality of carborundum stone including cost of curing, taxes and royalty all complete as per building specification and direction of E/I.

-

-

-

... More
In Lobby 600 mmX600mm

7.98

-

-

... More
Providing and laying 6mm precast white glazed tiles in walls over 12mm, cement mortar (1:3) and jointed with gray cement slurry, flush pointed with white cement including rubbing, polishing and cost of curing, taxed and royalty all complete as per building specification and direction of E/I.

39.45

-

-

... More
Providing and laying 25mm thick kotah stone in risers of steps, skirting and pillars of approves size, texture and colour laid over 12mm thick cement palster (1:3) base with neat cement slurry mixed with pigment to match the shade of tiles between joints, including rubbing and polishing to granolithic finish with approved quality of carborandum stone including cost of curing, roualty and taxes all complete as per building specification and direction of E/I.

2.25

-

-

... More
Providng 12mm thick cement plaster (1:3) with clean coarse sand of F.M. 1.5 including screening, curing with all leads and lifts of water, scaffolding taxes and royalty all complete as per building specification and direction of E/I.

130.21

-

-

... More
Providng 12mm thick cement plaster (1:4) with clean coarse sand of F.M. 1.5 including screening, curing with all leads and lifts of water, scaffolding taxes and royalty all complete as per building specification and direction of E/I.

105.76

-

-

... More
Providng 12mm thick cement plaster (1:6) with clean coarse sand of F.M. 1.5 including screening, curing with all leads and lifts of water, scaffolding taxes and royalty all complete as per building specification and direction of E/I.

334.43

-

-

... More
Providing 6mm thick cement plaster (1:4) in ceiling with celean coarse sand of F.M. 1.5 including screening, curing with all leads and lifts of water, scaffolding taxes and royalty all complete as per building specification and direction of E/I.

76.09

-

-

... More
providing 1.5 mm cement punning including curing , carriage of water with all leads and lifts as per building specification and direction

89.25

-

-

... More
Providing two coats of dry distemper of approved shade and make over a primer coat of washing over new surface including preparing the plastered surface by rubbing smooth with pumice stone or fine sand paper applying putty wherever required, scaffolding washing floors and taxes all complete as per building specification and direction of E/I.

232.47

-

-

... More
White washing three coats over new surface in ceiling.

76.09

-

-

... More
Providing two coat of snowcem of approved shade and make over a coat of cement of primer on new surface mcluding preparing the plastered surface smooth with sand paper, soaping, curing and taxes all complete as per building specification and direction of E/I.

205.66

-

-

... More
Providing french spirit polishing over new wooden surface to give desired texture and gloss with approved make and shade of ready mixed french polish including preparing the surface after cleaning, removing dirt scales, smokes, grease and sand papering, including cost of scaffolding and taxes all complete as per building specification and direction of E/I.

22.37

-

-

... More
Providing two coats of synthetic enamel paint of approved shade and make over steel surface including cleaning the surface thoroughly cost of scaffolding and taxes all complete as per building specification and direction of E/I.

-

-

-

... More
For Door & Window Frame

2942.94

-

-

... More
Labour for fitting and fixing GCI sheet roofing in proper slope including the cost of 'J' or 'L' hooks, limpet and bitumen washers, carriage of sheets to work site and taxes all complete.

649.44

-

-

... More
Supply of corrugated G.C.I. sheet 0.8 mm thick with zinc coating not less than 375 Gm/Sqm confirming to IS 227 (3 x 0 .885 M size of each sheet) cost with 10% CP+5% OHC

18.12

-

-

... More
Supply of following sizes structural steel: (add 10% CP+5% OHC)

-

-

-

... More
Angle iron of 50 x 50 x 6 (as per IS:226)

6.66

-

-

... More
ISMC channel size ISMC 100 (as per IS: 227)

0.66

-

-

... More
MS Plate 12 mm thick

4.71

-

-

... More
MS Sag Rod & Bolt 16mm dia HYSD bars confirming to IS: 1786

0.35

-

-

... More
Supplying, fitting and fixing vitreous white glazed earthen ware I.W.C of parry Hindustan or any other ISS approved make with 100mm H.C.I 'P' trap 15 litres C.I pull and let go flushing cistern of names or other I.S.S equivalent make, complete with all fittings, C.I. or CC brackets 32mm alkathene/PVC telesopic flush, pipe about 2M long with one brasscoupling and clamps G.I. chain and pull including supplying and fixing a pair of vitreous white glazed earthenware ware footrest to be fixed in floor 15mm C.I. body brass spindle stope cock of weight not less than 50gm, 15mm PVC connection pipe 450mm long and the exposed pipe and cistern with two coats of approved paint over a coat of red oxide primer etc. all complete as per specification and

-

-

-

... More
A- 510mm long with 12.5 ltr. Low level PVC cistem

5

-

-

... More
Supplying, fitting and fixing flat back or angular, lipped front vitreous white glazed earthen ware urinal of 'Hindustan "Parry" or any other approved ISS make with 5 liters capacity C.I automatic fulsiing cistern of reliance for any other ISS approved make with all fittings with CI or RS brackets, standare size GI flush pipe with fitting clamps, 15mm C.I. brass spindle stop cock of approved quality weight not less than 400gm, 15mm PVC / Alkthene pipe 450mm longwith brass coupling at both ends and doing plumber joints including painting of exposed part with two coats of approved paintover a priming coat of red oxide, cutting wall and floor, making good the same etc. all complete as per specification and direction of E/I.

-

-

-

... More
Flat back or standing corner (600mm x 350mm)

4

-

-

... More
Supplying, fitting and fixing vitreous white glazed earthen ware wah hand basin of parry or Hindustan or any other ISS approved make supported on painted C.I. or R.S. brackets 32mm C.I. brass waste, 15mm dia C.I. body brass spindle stop cock of approved quality of weight not less than 350 gm, 32mm PVC waste pipe 750mm long wtih brass coupling at one end and making plumber joints etc. all complete as per specification and as per direction of E/I.

3

-

-

... More
Providing and fixing 600 x 450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.

3

-

-

... More
Supplying tools and making connection of new G.I. distribution branch 15 mm to 50 mm dia with existing G.I. main by providing and fixing G.I. Tee including cutting of pipe at two places and threading their ends, providing long screw and one G.I. Nipple, all complete as per specification and direction of E/I.

-

-

-

... More
50mm dia.

2

-

-

... More
Providing and fixing brass/C.I. Stop cock of approved quality all complete as per specification and direction of E/I.

-

-

-

... More
15mm dia

4

-

-

... More
Providing and fixing male ended 15 mm dia brass bib cock of approved quality (Wt. not less than 350 gms.) with extra socket all complete as per specification and direction of E/I.

8

-

-

... More
Supplying materials and labours for construction inspection chamber of designation class 75 B bricks size 750 mm deep, 600 x 450 internal dimension having 250 mm wall thickness in cement mortar (1:6) including 12 mm cement plaster (1:4) with punning on inside and cement plaster (1:6) with 600 x 475 mm G.I. cover with frame (Weight not less than 36 kg.) along with earth work in excavation and 80 mm thick P.C.C (1:3:6) in foundation and refilling all complete.

8

-

-

... More
Excavation for roadwork in soli with hydraulic excavator of 0.9 cum bucket capacity including cutting and loading in tipper, trimming in bottom and slopes in accordence with requirement of lines and grades and cross section and transporting to the embankment location with all lifts grades and cross section, lift and lead up to 1000 m including royalty @ 24.00 per cum. cost of watering rolling and compection.

88.2

-

-

... More
Granular sub base with coarse graded material (400-2) (construction of granular sub base by providing coarse graded material, spreading in uniform layers with motor grader on prepared surface, mixing by mix in place method rotavator at OMC and compacting with the vibratory roller to achive the desired density, complete as per clause 401.

-

-

-

... More
For grading I material

50.4

-

-

... More
Wet Mix Macadam (Providing, laying,spreading and compacting graded stone aggregates to WMM specification including premixing the materials with water at OMC in mechanical mix plant carriage of mixed material by tipper to site , laying in uniform layers with paver in sub- base/basecourse on well prepared surface and compacting with vibratory roller to achieve desired density. with vibratory rollar

32.4

-

-

... More
Prime coat, providing and applying primer coat with bitumen emulsion on prepared surface granular base including cleaning of road surface and spraying primer coat at the rate of 0.6 kg/sqm using mechanical means.

216

-

-

... More
Open graded premix surfacing: Providing laying and rolling of open graded premixed surfacing of 20 mm thickness composed of 13.2 to 5.6 mm aggregates either using penetration grade bitumin or cut back or emulsion to required line, grade and level to serve as wearing course on apreviously prepared base including mixing in a suitable plant, laying and rolling with a smooth wheel roller 10 tonne capacity finished to required level and grades. Mechanical method using penetration grade Bitumin as HMP of appropriate capacity with less than 75 tonnes/Hrs

216

-

-

... More
Providing and applying tack coat with bituminus emulsion pressure distributer at the rate of 0.20 kg per sqm on the prepared bituminious granular surface cleaned with mechanical broom

216

-

-

... More
Seal coat (providing and laying seal coat sealing the voids in a bituminus surface laid to the levels grades and cross using Type A and Type B seal coats). Case II Type B (providing and laying of premix sand seal coat with HMP of appropria

216

-

-

... More
Construction of Embankment with material deposited from roadway cutting (construction of emabankment with approved material deposited at site graded and compacted to meet requirements of Table 300-2, rolling with smooth wheeled roller.

6.12

-

-

... More
Painting lines, dashes on roads in two coats on new work (painting lines, dashes arrow ete on roads in two coats on new work with ready mix road marking paint confirming to IS 164 bituminious surface including cleaning the surface of all dirt dust and other forigen matter demarcation at site and traffic control. Upto 10 cm in width.

14.4

-

-

... More
Providing and fixing of Retro reflectorised cautionary mandatory and informatory sign as per IRC:67 made of encapsulated leas type reflective sheeting vide vide clause 801.3, fixed over aluminium sheeting, 1.5 mm thick supported on a mild steel angle iron post 75mmX 75 mmX6 mm firmly fixed to the ground by means of properly designed foundation with M15 grade cement concrete 45 cm X45 cmX60 cm, 60 cm below ground level as per approved drawing.

-

-

-

... More
60 cm equileteral trangle

2

-

-

... More
60X45 cm rectangle

4

-

-

... More
Road marker/road stud with plastic body of RPM/ASA/HIPS as per clause 804.2.1 of MORTH fitted with lens reflectors installed in concrete or asphaltic surface by drilling hole 30 mm upto a depth of 60 mm and bedded in suitable bituminious grout or epoxy mortar , all as per ...confirming BS 873 part 4 1973 @ 6.00m c/c 2 rows.

24

-

-

... More
Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank

1500

-

-

... More
Providing and laying water proofing treatment on roofs of slabs by applying cement slurry mixed with water proofing cement compound consisting of applying: a) after surface preparation, first layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/sqm. b) laying second layer of Fibre glass cloth when the first layer is still green. Overlaps of joints of fibre cloth should not be less than 10 cm. c) third layer of 1.5 mm thickness consisting of slurry of cement @ 1.289 kg/sqm mixed with water proofing cement compound @ 0.670 kg/sqm and coarse sand @ 1.289 kg/sqm. This will be allowed to air cure for 4 hours followed by water curing for 48 hours. The entire treatment will be taken upto 30 cm on parapet wall and tucked into groove in parapet all around. d) fourth and final layer of brick tiling with cement mortar (which will be paid for separately. For the purpose of measurement the entire treated surface will be measured.

85.05

-

-

... More
Making plinth protection 50 mm thick of cement concrete 1:3:6 (1 cemnt: 3 coarse sand: 6 graded stone aggregate 20 mm nominal size) over 75 mm bed of dry brick ballast 40 mm nominal size well rammed and consolidated and grouted with fine sand including finishing the top smooth.

44.71

-

-

... More
Providing and fixing on wall face unplasticised - Rigid PVC rain water pipes conforming to IS : 13592 Type A. 110 mm dia

316.05

-

-

... More
Providing and fixing on wall face unplasticised - PVC moulded fittings / accessories for unplasticised - Rigid PVC rain water pipes conforming to IS : 13592 Type A. 110 mm shoe.

6

-

-

... More
Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter.

6

-

-

... More
Providing and fixing M.S holder-bat clamps of approved design to Sand Cast iron/cast iron (spun) pipe embedded in and including cement concrete blocks 10 x 10 x 10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone sggregate 20 mm nominal size) including cost of cutting holes and making good the walls etc.

-

-

-

... More
100 mm dia Pipe

6

-

-

... More
Providing and fixing G.I.pipes complete with G.I.fittings and clamps,including cutting and making good the walls etc. (Internal work): Concealed pipe including painting with anti corrosive bitumastic paint,cutting chases and making good the wall.

-

-

-

... More
15 mm dia nominal bore

15

-

-

... More
20 mm dia nominal bore

20

-

-

... More
Providing and fixing C.P. brass bib cock of approved quality conforming to IS : 8931.

-

-

-

... More
15 mm nominal bore

3

-

-

... More
Providing and fixing PTMT soap Dish Holder having length of 138 mm, breadth 102mm, height of 75mm with concealed fitting arrangements. Weighing not less than 106 gms.

6

-

-

... More
Providing and laying rectified Glazed Ceramic floor tiles 300 x 300 mm or more (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours White, lvory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand) including grouting the joints with white cement and matching pigment etc., complete.

9.59

-

-

... More
Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in- charge.“(Note :- Cement content considered in this item is @ 330 kg/cum.“Excess/ less cement used as per design mix is payable/recoverable separately). All works upto plinth level

123

-

-

... More
Providing M-35 grade concrete instead of M-25 grade BMC/ RMC. (Note : Cement content considered in M- 35 is @ 350 kg/ cum)

120

-

-

... More
Centering and shuttering including strutting, propping etc. and removal of form for all heights :

120

-

-

... More
Providing and fixing 15 cm wide 45 cm over all semicircular plain G.S sheet gutter with iron brackets 40 x 3 mm size, bolts, nuts and washers etc. including making necessary connections with rain water pipes complete. 0.8 mm thick with zinc coating not less than 275 gm/Sqm.

250

-

-

... More
Providing ridges or hips of width 60cm over all width plain G.S. sheet fixed with polymer coated J. or L hooks, bolts and nuts 8 mm dia. G.I. limpet and bitumen washers complete (0.80mm thick with zinc coating not less than 275gm/m2)

121

-

-

... More
Providing & fixing M.S holder-bat clamps of approved design to Sand Cast iron/cast iron (spun) pipe embedded in and including cement concrete blocks 10x10x10cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including cost of cutting holes and making good the wall etc.

-

-

-

... More
For 100 mm dia pipe

54

-

-

... More
Providing and fixing in position pre-cast RCC manhole cover and frame of required shape and approved qrality . HD 20

-

-

-

... More
Circular shape 560mm internal dia.

1

-

-

... More
Making soak pit 2.5 m diameter 3.00 m deep with 45X45 cm dry brick honey comb shaft with bricks and SW drain pipe 100 mm diameter, 1.8 m long complete as per standard design. With common burnt clay FPS (non moduler) brick of class

1

-

-

... More
Providing and Fixing soil ,waste and vent pipe: 75 mm dia sand cast iron socket & spigot pipe

1.8

-

-

... More
Wiring for light point/fan point/ exhaust fan point/ call bell point with 1.5 sq. mm FR PVC insulated copper conductor single core cable in surface / recessed PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq. mm FR PVC insulated copper conductor single core cable etc as required.

-

-

-

... More
Group A

12

-

-

... More
Group B

5

-

-

... More
Group C

1

-

-

... More
Wiring for light point with 1.5 Sq.mm FR PVC insulated copper conductor single core cable in surface/ recessed PVC conduit alongwith 2 No 2.5 sq. mm FR PVC insulated copper conductor single core cable for loop earthing as required.

18

-

-

... More
Wiring for light/ power plug with 4 X 4 sq. mm FR PVC insulated copper conductor single core cable in surface/ recessed PVC conduit alongwith 2 No 4 sq. mm FR PVC insulated copper conductor single core cable for loop

18

-

-

... More
Supplying and fixing of following sizes of PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm

150

-

-

... More
Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required. 75x75x50mm

2

-

-

... More
Supply and fixing following modular base & cover plate on existing modular metal boxes etc as required. 4/5 module

5

-

-

... More
Supply and fixing following modular switch and socket on the existing modular plate & switch box including connections but excluding modular plate etc as required

-

-

-

... More
3 pin 5/6 amp socket outlet

34

-

-

... More
Telephone socket outlet

2

-

-

... More
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection, painting etc as required

9

-

-

... More
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps modular switch, connection, painting etc as required

4

-

-

... More
Supply and fixing stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc as required

8

-

-

... More
Supply and fixing call bell/ buzzer suitable for D.C/ A.C single phase 230 volts complete as required.

1

-

-

... More
Supply and fixing 3 pin, 5 amp. Ceiling rose on the existing junction box/ wooden block including connection etc as required.

9

-

-

... More
Supply and fixing brass batten/ angle holder including including connection etc as required

9

-

-

... More
Installation, testing and comissioning of ceiling fan, ancluding wiring the down rods of standard length(upto 30 cm) with 1.5sq mm FR PVC insulated, copper conductor single core cable, including providing and fixing phenolic laminated sheet cover on fan box etc as required

12

-

-

... More
Installation , testing and commissioning of pre- wired, flourescent fitting/compact flourescent fitting of all types, comlete with all accessories and tube etc directly on ceiling/wall, including connection with 1.5 sq. mm FR PVC insulated, copper conductor, single core cable and earthing etc as required.

36

-

-

... More
Installation of exhaust fan upto 510 mm sweep in the existing opening including making the hole to suit the size of the above fan making good the damage connection testing commissioning etc as required.

3

-

-

... More
Extra for cutting and threading of G.I pipe heavy guage down rod for ceiling fan etc. as required.

10

-

-

... More
Distribution Boards

-

-

-

... More
Supply and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper busbar, neutral busbar, earth bar, din bar, detachable gland plate, interconnections, phosphatized and powder painted including earthing etc as required. 2 way single door

2

-

-

... More
Supply and fixing 6 amps to 32 amps rating 240 volts 'B' series miniature circuit breaker suitable for lighting and other loads of following poles in the exsisting MCB DB complete with connection testing and commisssioning etc. as required 6/32 amps, single pole B series

10

-

-

... More
Providing and fixing 4 mm dia copper wire on surface or in recess for loop earthing as required

75

-

-

... More
P & F double ball bearing capacitor start ceiling fan of approved make complete with regulator and other accessories as required. (for estimation purpose only)

-

-

-

... More
1200 mm sweep

4

-

-

... More
Cost of Carriage

-

-

-

... More
Sand for filling

122

-

-

... More
Coarse Sand

170

-

-

... More
Stone chips

300

-

-

40

-

-

... More
Cement

95

-

-

... More
Bricks

240

-

-

... More
Operation and Maintanance for One year

1

-

-

... More
Cost of Equipment for collection Transportion segregation and processing of solid waste

1

-

-

... More
Rain Water Harvesting 4 nos.

4

-

-

... More
GST18%

0.18

-

-

... More
Labour Cess@1%

0.01

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.