Public Works Department Tender
Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Public Works Department - PWD Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date12 Nov 2024
Closing Date18 Nov 2024
Tender Amount₹ 3,87,000
Costs
EMD
₹ 7,740Document Cost
₹ 200Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_PWDJK_264294_1Bid Award Id
ViewTender No
MHDS/TS /2024-25/117/e-tendering, Dated 12 -11-2024Tender Authority
Public Works Department ViewPurchaser Address
-Website
http://http://jkpwdrb.nic.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Providing and fixing glazing in aluminum door, window, ventilator shutters and partitions etc. to the chamber aluminium framework with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer in-charge. (Cost of aluminum snap beading shall be paid in basic item.) With float glass panes of 5.0 mm thickness (weight not less than 12.50 kg / sqm)
15
-
-
Providing and laying of 25 mm dia PVC conduit alongwith all bends and other 2 fixtures
100
-
-
Providing and fitting of 100 mm Deep Junction for lighting
12
-
-
Providing and fixing of Lighting points inclusive of copper wire 1 sqmm,ON/OFF switch 5Amp along with require capacity of MCB to be fitted distribution box, all electric fittings, protective devices and accessories, 12Watt LED light of reputed make
12
-
-
Providing and fixing of three pin socket inclusive of copper wire 1 sqmm, ON/OFF sitch 5Amp all electric fittings, protective devices and accessories, of reputed make
4
-
-
Providing and fixing of Heating points inclusive of copper wire 2.5 sqmm, ON/OFF switch 16 Amp along with require capacity of MCB to be fitted in distribution box, all electric fittings, protective devices and accessories.
3
-
-
Providing and fixing of 100W High mast flood lights for plant room illumination, shall inclusive of copper wire 1.5 sqmm /OFF 16A Single pole MCCB switch along with enclosures
12
-
-
Providing and fixing of metallic distribution box (8-way) along with the cost of 32A capacity DP and other necessary fittings as shall be required at the site
1
-
-
Electrification of HWG control panel to main panel by way of connecting A wire alongwith replacement of faulty 4 pole 63A MCCB (2 Nos) in main control panel, Providing & fixing of DOL starter having following specifications: Phase 3-phase, Thermal Over Load Protector: Yes, Power Supply 20-32 A Power Rating: 14.9 KW, Motor Power 20 hp in place of damaged starter. The job further includes electrification of burner panel to HWG panel alongwith replacement of faulty contactors and overload relays with
current rating 9-13A (2 Nos.)
1
-
-
Opening of Thermax Make AMW06 Hot Water Generator. Dismounting of the burner gun assembly, removing the front plate coil from it by employing chain pulley block. The job involves thoroughly removing soot and carbon deposits from shell and coil by using wire brush, scrapers and blower etc. The inside of the coil shall be cleaned by circulating through it a solution of de-scaling compound, sulphamic acid powder of Thermax Make (approx . 25 Kg) and water continuously for 24 hr with the help of pump while maintaining a PH of 1-2. The solution is to be circulated from tank/barrel/trays. All consumable items viz. Brushes, detergent, diesel/kerosene oil, dhoti cloth etc. required shall be provided by the executing agency. The HWG shall then be reassembled, tested and commissioned after overhauling. The job includes replacement of all seals, gaskets, asbestos rope, asbestos felt, asbestos sheet, defective nuts, bolts etc. as required .The tools and tackles required for the job and any other consumables shall be provided by the contractor.
1
-
-
Replacement of Refractory of Thermax Make AMW06 Hot water Generator. The job includes complete removal of old/damaged refractory and thorough cleaning of refractory surfaces/bases. Angle Iron hooks/holdfasts shall be firmly welded to the refractory base wherever necessary and collar of the top plate shall be repaired if required. Refractory shall be laid in "fire Crete Super' brand castible cement.
-
-
-
Front Plate Refractory
1
-
-
Back plate refractory
1
-
-
Servicing of 15 HP circulation water pump/s by way of removing/dismantling of the pump assembly followed by checking of impeller, diffuser rings, bushes bearing, and mechanical water seal for complete water leakage seal. All faulty components viz. impeller, diffuser rings, bushes bearing, and mechanical water seal should be replaced by the firm. The pump/s should be reassembled and sealed back with packings for mounting into the central heating circuitry followed by testing and commissioning
1
-
-
Servicing of 5 HP feed water pump/s by way of removing/dismantling of the pump assembly followed by checking of impeller, diffuser rings, bushes bearing, and mechanical water seal for complete water leakage seal. All faulty components viz. impeller, diffuser rings, bushes bearing, and mechanical water seal should be replaced by the firm. faulty components should be replaced by the firm. The pump/s should be reassembled and sealed back with packings for mounting into the central heating circuitry followed by testing and
commissioning.
1
-
-
Replacement of damaged inlet/oulet EDPM fuel pipe hoses PN 16 rated in all four HWGs (03 hoses in each) of the hot water system including dismantling of the damaged inlet/outlet pipe connections of the radiators and then providing/fitting of new 304 Grade Stainless Steel cladded EDPM pipe with washer and nuts other necessary fittings including Ball valves, elbows, Tees, Unions, Adapters, etc. to make the fuel lines leak proof and fully functional. The job also includes testing of the system for its satisfactory
performance.
4
-
-
Supply, installation, testing and commissioning of:
-
-
-
M S Piping:
-
-
-
P/F of new supply and return header for 06 Lac Lcal/hr HWG from and to main supply and return header with overhead laying with MS Structural steel hangers and MS ISMC supports where ever required with Mild Steel class ‘C’ ERW pipes of following diameters with fittings like tees, elbows, bends, junctions, unions, flanges etc. clamps structural supports, wooden pedestals as per site requirements including application of anticorrosive paint of approved shade over a coat of steel primer/ red oxide.
-
-
-
80mm
20
-
-
P/F of new flue gas header for 06 Lac Lcal/hr HWG to main erected flue gas chimney with angular laying with MS Structural steel hangers and MS ISMC supports where ever required through punctured brill wall with Mild Steel class ‘C’ ERW pipes of following diameters with fittings like tees, elbows, bends, junctions, unions, flanges etc. clamps structural supports, wooden pedestals as per site requirements including application of anticorrosive paint of approved shade over a coat of steel primer/ red oxide.The job further includes sealing of punctured wall with concrete and brick mortor.
-
-
-
200mm
8
-
-
P/F of new fuel header for 06 Lac Lcal/hr HWG from main fuel line with angular laying with MS Structural steel hangers and supports where ever required with Mild Steel class ‘C’ ERW pipes of following diameters with fittings like tees, elbows, bends, junctions, unions, flanges etc. clamps structural supports, wooden pedestals as per site requirements including application of anticorrosive paint of approved shade over a coat of steel primer/
red oxide.
-
-
-
25mm
15
-
-
Insulation for Indoor: Discard and replacement
-
-
-
Elastomeric nitrile foam.
-
-
-
80mm
20
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements