Public Works Department Tender
... More
Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Public Works Department - PWD Tender
Electrical and Electronics
Eprocure
Opening Date19 Oct 2024
Closing Date7 Nov 2024
Tender Amount₹ 30,00,000
Costs
EMD
₹ 1,100Document Cost
₹ 1,100Tender Fee
Refer Documents
Summary
Electrification Of College Building Gdc Ganderbal
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_PWDJK_261184_4Bid Award Id
ViewTender No
NIT NO.58/2024/25 dt/19/10/2024Tender Authority
Public Works Department ViewPurchaser Address
-Website
http://jktenders.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Wiring for 6Amp Plug (Computer) with (P+N+E) 3 x 2.5 sq.mm FRLS PVC Insulated Multi strand Copper Conductor single core cable in surface/Recessed Conduit (Havells/Polycab /Anchor/LS Make),including cost of Conduits other accessories like bends etc complete to be laid in wall and finishing the surface to its original shape by cement mortar plastering/Wall Putty/Paint etc with 02 No. of 6 Amp Modular Switch, 02 No.of Modular 6 Amp.of 5-PIN Socket,Modular Plate,Cover, Modular blanking plate where required and suitable GI box etc ISO/IEC Certified Havells/Legrand/ Panasonic/Anchor Rooma Plus/Schneider Make & shall be approved before execution of work.
109
1450
158050
... More
Wiring for Sub main Wiring along with earth Wire with the following Sizes of FRLS PVC insulated copper conductor, single core Cable in surface/Recessed medium class PVC conduit (Havells/Polycab/Anchor/LS Make) & shall be approved before execution of work.
-
-
-
... More
2x10 sq.mm+ 1x10 sq.mm (P+N+E) for Power point Sub main in One run from Main Panel to Distribution Boards.
400
475
190000
... More
2x6 sq.mm+ 1x6 sq.mm (P+N+E) for Lighting/ Sub main in One run from Main Panel to Distribution Boards.
300
439
131700
... More
2x4 sq.mm+ 1x4 sq.mm (P+N+E) for Inverter Sub main in One run from Main Panel to Distribution Boards.
250
334
83500
... More
2x2.5 sq.mm+ 1x2.5 sq.mm (P+N+E) for Inverter Circuit in One run from switch boards to Distribution Boards.
700
275
192500
... More
Supply/Fixing/Testing and Commissioning of 6Amp to 32Amp Rating SP,240v,*C* Curve 10K, Miniature Circuit Breaker suitable for inductive load of following poles in existing MCB . DB Complete with connections.(L&T/Siemens/Legrand/ABB /Schneider Make)
215
256
55040
... More
Supply and Fixing of single pole blanking plates on existing MCB boxes, excluding cost of Boxes.
20
24
480
... More
Supply/Fixing/Testing and Commissioning of following rating, Double pole, (P+N) 240 V, C* Curve 10K,Miniature Circuit Breaker (MCB) in the existing MCB DB complete with connections. (L&T/Siemens /Legrand/ABB/Schneider Make)
-
-
-
... More
32Amp.
16
700
11200
... More
40Amp.
12
1250
15000
... More
63Amp.
12
1850
22200
... More
Supplying and Fixing of MCB 16-Way horizontal typed , sheet steel, Double Door Distribution Board, SPN 240V V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc, as required. (L&T/Siemens/Legrand/ ABB /Schneider Make).The Job includes the cost of wall cutting and reshaping in original for fitting of DB.
12
2400
28800
... More
Supplying and Fixing of MCB 8-Way (4+24) horizontal typed , sheet steel, Double Door Distribution Board, TPN 240V/415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc, as required. (L&T/Siemens/Legrand/ ABB /Schneider Make) The Job includes the cost of wall cutting and reshaping in original for fitting of DB.
12
5000
60000
... More
ENVIRONMENTALLY SAFE MAINTENANCE FREE COPPER ROD EARTHING SYSTEM
Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance Value.Supply,Installation and Testing of 75 mm copper Pipe Filled with Crystalline conductive Mixture with Eco friendly GEM Backfill Compound 2No. Bags also having Earth pit chamber (300mm x 300mm) with man- hole cover for the above. Including cost of 20mm Wide copper strip as required in one run fitted with of brass nut bolt & spring washer from EARTHING ROD up to MAIN Control PANEL through suitable DWC High Density Poly ethylene Pipe having Corrugation complete job.
1
10500
10500
... More
Supply/Installation/Testing and Commissioning of 18W + LED Surface Mounted Panel light luminary fitting round shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium Heat Sink and P.F.0.95 ,THD10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV.Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/government of India authorised lab.The job includes AMC (reckoned from date of successful commissioning) of lighting fixtures for a period of Two years,which includes replacement of fixtures of Philips/Havell's/Wipro/Jaguar/Bajaj Make.
400
1550
620000
... More
Providing & Fixing of IK08 IP-66 protected high power LED 50 Watt flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each. Integrated potted driver as a unique BIS R number having efficiency more than 85% and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy =125 Im/wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @=300 V AC and Auto resetting Safety .Power Factor 0.95 , THD(I) 10% , driver current =750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector, Surge Protection Min =4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI70 and CCT 5700K 355K. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR:-High Power LED Flood Light Minimum lumen output 6200 Im of Havells/Crompton/Philips Make as approved and to be installed on outside block including S/F of suitable size of Gyser bolt.The job further includes replacement warranty of fixture (if damaged/burnt out what so ever reason) for a period of two years reckoned from date of successful commissioning /handing over of site to intending department.
8
3500
28000
... More
Supply/Installation/Testing and Commissioning of 225-250mm Shutter Typed,320 Cu.m/Hr.AC 220-240 Volts, 50 Hz Exhaust fan made out of ABS Plastic Material with inbuilt thermo cut-off Protection and Noise Level not exceeding 37dB of Following Sizes including connection etc USHA/Polycab/LUKER USA Make.(Minimum 3-Star)
20
1800
36000
... More
Supply/Installation/Testing and Commissioning of ABC type Fire Extinguisher 4.Kg. Capacity ISI Mark(IS:15683) and dully certified.
8
4500
36000
... More
Supply/Installation/Testing and Commissioning of CO2 Type Fire Extinguisher 4.5 Kg. Capacity ISI Mark(IS:15683)suitable for 'B' and 'C' class fires - inflammable liquids, gaseous fires like L.P.G,acetylene and electrical fires.
1
6500
6500
... More
Supply/Laying of 25/32/38mm Dia PVC Conduit of Anchor/Ravinder/Polypack/Finolex Make with other accessories like bends,etc complete to be laid in wall for downs and finishing the surface to its original shape by cement mortar plastering/Wall Putty/Paint etc.
3600
80
288000
... More
Supply and Fixing of GI fan hook to fiited on slab with D-fastners complete job
30
150
4500
... More
Supply/Installation/Testing and Commissioning of AC/DC Bells of standard make with its batteries
2
165
330
... More
Supply and Fixing of Modular 32Amp industrial Socket outlet having fitted with 32 Amps DP MCB and Top with Modular Plate,Cover in front & suitable GI box etcfor AC Points
6
1400
8400
... More
Providing and fixing of bakelite hylam sheets of required size including cutting, filing with S/F screws etc.
1000
2
2000
... More
Supply/Installation/Testing and Commissioning of 1200 mm sweep, ceiling fan with 03 No. blades, 30 cm long down rod, 02 No. canopies, shackle kit, Power Factor not less than 0.9, Service Value including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase Supply, etc. complete as required. USHA/Havells/Polycab/LUKER USA Make.(Minium 3-Star)
50
2200
110000
... More
Repairing of existing Control panel with Upgradation.fabrication,internal wiring,distribution and Separation of circuits on bus bars of existing panel from CPRI Approved (IS/IEC:61439) including Supply/Fixing of following adjustable type controlling /Protection switch gear devices:
(1) Normal Incoming
Volt meter =1 no, Ammeter = 1 no , CT coils for Ammeter 300 /5A = 1 set ,phase indicators =1set
,Selector Switch = 1 No. Generator Incomer
100 Amp Four Pole Change over switch of Havels / Siemens/ ABB /Schinder /L&T make = 1 No.
Outgoing .
(1) 125 Amps DP MCCB (10 KA) of Legrand / Siemens/ ABB /Schinder /L&T make = 13 No for normal Heating /AC Sub main.
(2) 40 Amps Double Pole MCB (10 KA) of Legrand / Siemens/ ABB /Schinder /L&T make = 13 No for Sub main lighting/invertor.The job includes cost of uninstallation/dismantling of existing damaged items and installation of existing Servo Stabilizer/other items.
1
52000
52000
... More
Supply/Installation/Testing and Commissioning of 3-Phase, Four Pole 200 Amp,415V Ac,50Hz offload Manual Changeover Switch side handle in enclosure Havells/L &T/ABB Make including S/F/Crimping of Suitable Size of thimbles for connections as per site requirement for bypassing Existing AVR. as approved.
1
18000
18000
... More
Providing and Laying of shock proof rubber mats of 2mx1mx12mm thick in size of Standard Make.
1
800
800
... More
Dismantling of existing wires in scraps,switches,sockets,fixtures etc for 3 Floor,Including Re-Installation of functional existing ceiling fans and handing over the same to conerned authorities.
3
10000
30000
Evaluation Notes How It Works ?
Potential Partner