Public Health Engineering Department Tender
Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Public Health Engineering Department - PHED Tender
Machinery and Tools
Eprocure
Opening Date6 Jul 2024
Closing Date12 Jul 2024
Tender Amount₹ 43,11,011
Costs
EMD
₹ 86,220Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_PHE_252280_5Bid Award Id
ViewTender No
JSD/PHE/MDSA/ e-NIT No. 09Tender Authority
Public Health Engineering Department ViewPurchaser Address
-Website
http://jktenders.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Earth work in excavation by mechanical means (Hydraulic Excavator) in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed: All kinds of soil- 1m from cutting edge.
The job includes earth work of HT Poles, Gantry etc
216
55479
256.85
... More
Filling available excavated earth in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by reaming and watering, lead upto 50 m and lift upto 1.5m.
195
38746
198.7
... More
Providing and laying of stone soling including manual compaction.
8
5920
740
... More
Centering and shuttering including strutting, propping etc. and removal of form work for Foundation, footings, bases for columns.
30
8590
286.35
... More
Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering, all work upto plinth level with 1: 2 : 4 mix (1 cement , 2 coarse sand , 4 graded stone aggregate 20 mm nominal size)
The job includes CC for DG Set Shed, HT Poles, Gantry etc.
16
105460
6591.25
... More
Fabrication, providing and fitting of washout Tee. The Tee shall be fabricated out of G.I C-class pipe with M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) fastened with weld joints on three ends. The size of the Tee is given Below:
ND= 65 MM Class: C (Heavy)
1
4050
4050
... More
Supply, Installation, Testing And Commissioning of Ductile Iron double flanged, non-rising spindle Resilient seated gate/ sluice valves (PN16) in accordance with BS 5163 part 1 and part 2 / EN 1074 Part 1 & 2/ IS 14846 for regulating the water supply outside the pumping units. The body and bonnet of the valve shall be of ductile iron, wedge with fully vulcanized EPDM rubber (Approved for drinking water) and NBR seal. The Gate/Sluice valve shall be compatible for buried applications and shall be safe to install in both horizontal and vertical positions. It shall have electrostatic epoxy coating (approved for drinking water) both inside and outside of the valve. The valve shall be supplied along with hand wheel.
Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work.
The job includes providing and fitting of 02 nos. M.S flanges perfectly adaptable to the inbuilt flanges of the valve which shall be fitted with rising main of the pumping unit at appropriate spots as per site requirement. The job includes the cost on account of P/F of nuts, bolts and gasket required for the job. Material of Construction
• Body: Ductile iron EN-GJS-400-15 / GJS-500-7 (GGG-40/GGG-50)
• Bonnet: Ductile iron EN-GJS-400-15/ GJS-500-7 GGG-40/GGG-50)
• Bonnet bolts: Stainless steel A2 (DIN EN ISO 3506)
• Stem Nut : Brass
• Check valve disk: Ductile iron EN-GJS-400-15/ GJS-500-7 (GGG-40/GGG-50)encapsulated with EPDM vulcanize
Suggested Make: AVK/ VAG/ Sigma Flow/ Talis
The Test Certificates of Sluice/Gate Valves mentioning the Material of Construction as above duly stamped by OEM shall be provided at the time of supply of material.
Size: DN 65 mm Rating: PN 16
3
39990
13330
... More
Supply, Installation, Testing And Commissioning of Ductile Iron double flanged, Slanted seat swing check valve (NRV) (PN16) as per EN 1074- Part -3 / BS 5153/IS 5312. The body shall be of ductile cast iron with fully encapsulated vulcanized EPDM rubber (Approved for drinking water). The valve shall be compatible for buried applications and shall be safe to install in both horizontal and vertical positions.
It shall have electrostatic epoxy coating (approved for drinking water) both inside and outside of the valve.
Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work.
The job includes providing and fitting of 02 Nos. M.S flanges perfectly adaptable to the inbuilt flanges of the valve which shall be fitted with Rising main of the pumping unit at appropriate spots as per site requirement. The job includes the cost on account of P/F of nuts, bolts and gasket required for the job. Material of Construction
• Body: Ductile iron EN-GJS-400-15 / (GGG-40) • Bonnet: Ductile iron EN-GJS-400-15/ GGG-40)
• Bonnet bolts: Stainless steel A2 (DIN EN ISO 3506) • Stem Nut : Brass
• Check valve disk: Ductile iron EN-GJS-400-15/ (GGG-40) encapsulated with EPDM vulcanized
Suggested Make: AVK/ VAG/ Sigma Flow/ Talis
The Test Certificates of Check Valves (NRVs) mentioning the Material of Construction as above duly stamped by OEM shall be provided at the time of supply of material
Size: DN 65 mm Rating: PN 16
3
45459
15153
... More
Providing, fitting, testing and commissioning of ARV (Air Release valve) (PN16) as per EN 1074 Part 4/IS 14845 to be fitted to G.I rising Main. The ARV Shall have the following specifications: -
i. Valve type - single chamber, single orifice.
ii. End connection - flanged ends to IS 1538 iii. Test pressure - body / seat 2.5 x PN
iv. Sealing ring - EPDM
v. Construction -ductile iron with stainless steel floats
vi. Coating - epoxy with corrosion resistance vii. Working temperature (-450c to 550c)
Besides the above works, The job also cost on account of P/F R.I gasket, nuts and bolts required for installation of ARV and arrangement of gas cutter/ welding set at site. Material of Construction
• Body: Ductile iron EN-GJS-400-15 (GGG-40)
• Bonnet: Ductile iron EN-GJS-400-15 (GGG-40)
• Inner parts: Stainless steel 1.4541
• Float: Stainless steel A4 (exception: DN 50 - PN 10/16 synthetic, from PN 25 of A4)
• Sealing: EPDM
• Bonnet bolts: Stainless steel A4 (DIN EN ISO 3506)
Suggested Make: AVK/ VAG/ Sigma Flow/ Talis
The Test Certificates of Air Release Valves mentioning the Material of Construction as above duly stamped by OEM shall be provided at the time of supply of material.
Size : DN 50 Rating: PN16
3
58182
19394
... More
Fabrication, Providing and fitting of 90-120 degree bend/elbow to be fabricated out of Class C GI pipe, 1 m length and flanged on both ends a to make it leak proof. The flanges shall be M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) and welded on both sides. The job includes nuts, bolts, gaskets etc as per site requirement.
Size : DN 65 Class :- C (Heavy)
16
35776
2236
... More
Fabrication, providing and fitting of split type MS clamps10 mm thick, 2 ft long and 3 inch wide for lowering and holding of pumping unit fitted. The job includes the cost of required size of nuts and bolts.
Size : DN 65
2
2998
1499
... More
Providing, Fabrication and fitting of Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. The Structural steel is to be utilized for Fabrication of DG set Shed, Gantry, Platform and any other support required as per site requirement. The Steel may include ISMB, ISMC, ISA (Angle Iron), Chequered plate etc as per the site requirement. The drawings and Dimensions will be provided by Site In Charge at the time of execution of job.
1250
138750
111
... More
Providing and fitting of M.S 4 inch hinges -6 no and M.S handle heavy -4 No., Anchor bolts with nuts (M16) of 0.3 m long = 04 No.
Metallic strip (350mm×50mm×3mm) = 02 No.
1
2500
2500
... More
Supply, Installation, Testing And Commissioning of manual type triple spur gear chain pulley block along with monorail geared travelling trolley having following features
Gears: - The hoist shall have precision machine case Hardened alloy steel gear mounted on bearings and housed in a dust proof gear box. The lubrication of gears should be of high viscosity and temperature for longer life of gears. Load Chain: - The load chain be made of high tensile alloy steel having wear resistance and greatest mobility. The chain should be accurately collaborated, tested and have adequate in built factor of safety for safer operation.
Load chain wheel: - The load chain well should be double ball bearing supported and Specially designed, perfectly machined wheel providing correct grip of load chain to makes the hoist most safe and reliable against any failure. The main specifications of C.P Block are given below : Capacity = 2 ton No. Of load chain falls = 2 or above
Min. Height of lift = 6 M
Suggested Make: Indeff/ Pull Lift
Testing/Inspection Certificates are mandatory and are to be produced at the time of supply of material
1
44473
44473
... More
Supply, Installation, Testing And Commissioning of outdoor type Electric Sub Station as per the technical specifications given here under -
Specifications conforming to IS: 1180 (Part 1) 2014 with latest amendments.
Type: HT/LT Transformer (Level-2)
Capacity:- 63 KVA
Type of cooling: ONAN.
Operating conditions:
Input =11000 volts
Output = 433 volts AC supply in 3- phase.
Terminals:
Input=3 No. HT Brass bush rods with insulators, washer, nuts etc.
Output=4 No. LT Brass bush rods switch insulators, washers, nuts etc.
Core: The core shall be of high permeability to reduce core losses and the strips shall be of suitable size and gauge. Transformer Coils: Suitable number of HT and LT coils in each leg of the core. The transformer coils shall be fabricated out of superior quality aluminum wire/strips, properly wound. The HT transformer is completely filled with suitable grade transformer oil up to required level. The job includes carriage, and all leads and lifts involved.
The HT transformer shall be of reputed make from an ISO certified company as per relevant standards and a test certificate shall be provided before installation. The transformer shall also be provided with breather fill with silica jel crystals, conservator with oil level indicator, explosion vent and adequate radiator fins/ Tubes. The impedance of transformer shall be as per IS: 1180 (Part 1) 2014 with latest amendments. Suggested Make: Servokon/ AE/ Electricfield/ALBA
NOTE: The scope of the work shall include obtaining of necessary inspection/clearance certificate from the concerned department for all the required equipment.
1
171963
171963
... More
Providing and fitting G.I Channel /Angle/ Flat of sizes including clamps. The job includes fitting of Channels on two poles for the installation of insulators and safety devices, GO Set, Lighting Arrestor etc. It also includes the channels for fitting of LT Meter and LT Distribution Box. The job includes P/F of GI channels at Tapping point for installation of GO Link Set, Pin Insulators Etc as per site requirement
Size of Channel= ISMC 75X40MM & ISMC 100x40mm
450
55350
123
... More
Supply, Installation, Testing and commissioning of 02 No. Polymeric Gang operated Air break switch, outdoor type, triple pole, suitable for vertical installation, single break provided with locking arrangement at both ON and OFF position consisting of HT pole double insulator, copper or copper alloy high pressure heavy contact assembly, rod with bearings, operating handle and 32mm dia. GI pipe conforming to IS 1818 1961, 06 No. of insulators, rated voltage 11KV 200A complete as per IS specs. The 11 KV AB switches shall conform to IS: 9920 (Part-I to IV).
01 No. GO Set is to be fitted at tapping point and 01 No at HT Transformer (Substation).
2
23460
11730
... More
Supply, Installation, Testing and commissioning of 11KV polymer fuses Set Horn Gap 3-phase 200 A suitable for vertical installation.
1
4983
4983
... More
Supply, Installation, Testing and commissioning of Gapless Surge arrestor station class, 10KA, 9KV, LA With polymer housing, Station Type.
1
7754
7754
... More
Supply and fitting of 11 KV polymeric composite pin insulator 12 KV, 5KN, Lighting impulse 75KV Positive, and 80 KV Negative, creepage distance 320 mm.
78
27066
347
... More
Supply, installation, erection, Testing And Commissioning of 9 mtrs long H.T Steel Tubular pole of specifications ST- 410 (SP-33). The job further includes drilling of holes for installation of various accessories .wherever required the job further includes G.I wire earthing of pole as per REC standard. The tubular steel poles shall conform to the latest edition of Indian Standard specification IS: 2713 (Part – I, III): 1980 The materials used in construction of tubular steel poles shall be of the tested quality of steels of minimum tensile strength 540 MPa. The Poles shall be fitted with base plate as per above standard. The poles shall be applied with Red Oxide Primer and two coats of anti-corrosive Red paint at bottom up to the length of 4M and two coats of paint of silver shade for the rest.
26
537836
20686
... More
P/F of Galvanized nuts bolts of various sizes as per site requirement.
65
9230
142
... More
P/F Danger Plate with clamps on every HT pole.
26
3978
153
... More
Providing and fixing G.I Barbed wire for anti-climbing/ anti-climbing devices. The barbed wire shall be tightly close wrapped around the pole for 10-12 turns, commencing at 2.50m above the datum line.
60
8160
136
... More
Providing and Fitting of PG Clamps.
20
8420
421
... More
Supply, Installation, Testing And Commissioning of Galvanized stay set with 50 X 8 mm Stay Clamp, Guy insulator (2 No.), Anchor plate (200X200X6mm), nuts and bolts, 2 No.- turn buckle, 1.8 m long, 16 mm diameter solid G.I stay rod & 7/3.15 mm dia. G.I stranded wire complete.
10
49220
4922
... More
Providing and fitting of ACSR as per IS 398 (part-2) 1996 for 0.50 sq.mm ACSR (Galvanized steel reinforced) for fitment of various accessories.
2350
131600
56
... More
Supply, Installation, Testing And Commissioning of 35 sq mm XLPE HT cable (ABC type) of 11 KV Grade with following specifications size cross sectional area in square mm )= 3x35+1x70 sq mm
phases Red, Yellow, Blue
The Cable should conform to IS: 8130-1984, IS: 398 (Part-IV)-1994, IS: 7098 (Part-II) - 2011 & IS: 5831-1984 with up to date amendments, if any.
The Test Certificate of Cables duly stamped by manufacturer shall be provided at the time of supply of material.
60
49080
818
... More
Supply, Installation, Testing And Commissioning 11 KV cable termination kit for connecting 35 Sq mm ABC cable (ABC type) with the existing HT line near tapping point and HT transformer.
4
35976
8994
... More
Providing and fitting of Anchoring clamps comprising clamp body, plastic wedge, steel bill bracket, straps and buckles or nuts and bolts required for holding of 3 – Core, 35 Sq. mm H.T AB Cable.
8
3656
457
... More
Providing and fitting of LT Distribution box for H.T transformer with 200 amp MCCB For incomer and 100 amp SFU for outgoing circuits. The LT distribution Box is to be fitted on GI Channels.
Capacity of transformer: 63 KVA
1
28118
28118
... More
Supply, Installation, Testing And Commissioning of PRODIGY LT Meter of following specification complete with all fixtures required for fitment at site Type: 3 Phase, 4 wire Measurements offered: KWh, KVARh, KVAh, KVA
Voltage : 3x240V (415v), 50HZ
Ib : 40A Imax: 200A Battery: Lithium
The Prodigy Meter must be fitted inside the Box, that is to be fitted on GI Channels near LT Distribution Box. Both the enclosures must be symmetrical Suggested Make: Secure/ L&T
Sealing /Inspection report of Prodigy meter from JKPDCL (Concerned) is to be submitted by the firm at the time of charging of SUBSTATION.
1
28000
28000
... More
Supply, Installation, Testing and Commissioning of (MUG-30) Modular motor control panel of appropriate size fabricated out of 14 SWG sheet having required openings/vents and protection Class: IP-55 & fitted with accessories as under:
a) Bus bar Chamber:
The bus bar chamber shall be fitted at the top of the panel horizontally throughout the length. There shall be 3 Nos. of phase bus bar and 1 No neutral bus bar and 1 No earthing bus bar. The bus bars shall be air insulated and made-up of high conductivity COPPER with current density of suitable rating for 100 Ampere. All panel compartments shall be provided with suitable cable alley and vertical bus bar alley. Suitable segregation shall be provided in between bus bar chamber and adjoining compartments. The bus bar shall be PVC sleeved with color strips of red, yellow, blue and black and the same be arranged in accordance with IS-375 specs. Electrical clearances shall be maintained between phases, neutral and body as per standards.
b) Main Circuit Breaker (Incomer MCCB):
Qty. = 02
No. of poles = 4 Pole
Current Rating = 160-200A (DN2-250N)
Rated operational voltage = 415 V ± 10 %
Rated frequency = 50 ± 3%Hz
Ambient temperature = -70C to 40 0C
Type of release = Thermal-Magnetic
Overload protection = 0.8 – 1×ln adjustable
Short-circuit protection = 6-10×ln adjustable.
Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 50kA
c) Change over Switch:
Qty. = 01 No.
Rating = 100A
Type = Front operated, on load, 4 pole, 415 +10 %V, 50 + 3%Hz.
d) Motor Back-up Protection MCCB:
Qnty = 2 No
No. of poles = 3P
Current Rating = 100 -125A
Rated operational voltage = 415 V ± 10 %
Rated frequency = 50 ± 3% Hz
Ambient temperature = -70C to 40 0C
Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 36kA
e. Submersible starters:-= Fully automatic star delta starters.(M-30)
Power Specs = 3 Ф, 415 ± 10 % V, 50 ± 3 % Hz.
Relay range = 30-50 A
Coil Voltage = 380 v Protection = single phasing , phase Reversal, phase unbalance (55 ± 5 V) ,
Conformity to standard = IS/IES 60947-4-1 Qty. = 2 No’s
f) Auxiliary MCCB for Heating/Lighting:
Circuit Breaker = MCCB (Outgoing)
Qty. = 1 No.
No. of poles = 4P
Current Rating = 63A
Rated operational voltage = 415 V ± 10 %
Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 36kA
g) Motor Protection Relay:MM10/Siemens
Digital Motor Protection Relay with LCD Display for 3-phase supply with following protections suitable for the Modular Control Panel:-
Protections = Thermal Overload with pre-alarm, Short Circuit, Phase Loss, Unbalance, Phase reversal, Under Current, Prolong starting, Locked Rotor & Earth fault. And over current Qty. = 02 No’s (01 No. for each starter)
h) M-power module for mobile starter for submersible motor 1P/3P 3 wire( for both starters) Quantity – 02 no. IVRS Languages – English , Hindi, Suitable Region- North India
i) Over Voltage and Under Voltage Protection relay (02No.) to be fitted separately for both starters The panel shall be provided with phase indicators (03 N0) and digital ammeter of range 0-60 A, digital voltmeter of range 0-500 V, and digital frequency meter (01 No each). The enclosure of the panel shall be of excellent fit and finish, corrosion resistant and powder coated gliding hinges for smooth and noiseless movement of windows and advanced locking arrangements. Suggested Make of accessories: L&T/Havells/Siemens/ Scheneider
1
234576
234576
... More
Supply, Installation, Testing And Commissioning of 50 KVA voltage stabilizer as per specifications below: Type of voltage controller: Manually operated copper wound, 3-phase, AC power supply multi step.
Type of Regulator : Double plate type with electrolytic copper contacts.
Input voltage :180-400 volts.(3 phase)
Output voltage : 415 ± 10% volts.
Frequency : 50 ±3 C/S.
Windings : Electrolytic grade copper of adequate section, vacuum impregnated and Oven-dried.
Insulation : Fiber glass insulations to tested parameters.
Cooling : Naturally, Oil cooled (ONAN)
Temp. Rise (Max) : 30°C above ambient
Mounting : On Uni-directional wheels.
Correction rate : 40 volts per step
Wave form distortion : virtually nil
Duty cycle : 100% continuous.
Enclosure : MS sheet enclosure in pressed CGR Sheet powder coated with radiators.
Core laminates : High grade, low eddy loss, grain oriented silicon steel laminations.
Load : Three phase induction motor load.
Load Amperes (continuous)
Overload in 24-hours operation: 10% above continuous Ampere rating.
The voltage stabilizer shall have T-oil level indicator gauge preferably glass type tube or otherwise visible to naked eye. The top of the container to have a display panel for housing 02 numbers Digital voltmeters (0-500V) along with 4-way selector switch and set of neon indicators for incoming and outgoing phases (06 No’s).
Insulating media (T. Oil) of 11 KVA grade to be provided and filled up to top level, with dielectric strength of 5 KV at 4m air gap. The T-Oil of specific grade should be provided in separate barrels and filled at site up to top level.
Suggested Make: Servokon/ AE/ Electricfield
The voltage Stabilizer shall be accepted with manufacturers dully stamped test certificate and shall have name plate with specifications.
2
214802
107401
... More
Supply, Installation, Testing And Commissioning of 3.5-Core, 2 core XLPE, 1.1KV and 11KV grade Armored Aluminum Cable of various sizes conforming to IS: 7098 part 1st as service line from the HT transformer to control panel including necessary thimbling, crimping, taping etc. Suggested Make: L&T/ Polycab /Havells
The Test Certificate of Cables duly stamped by manufacturer shall be provided at the time of supply of material.
i) 70 sqmm, 3.5 core, LT cable
115
76820
668
... More
ii) 10 sqmm, 2 core, LT cable
130
21060
162
... More
Providing and fitting of 3-Core flat submersible copper cable conforming to IS: 694 (Part 1st) – 1964 & IS: 694 (Part 2nd) - 1964 for Submersible Pumping Unit and other electrical Equipment. The cable connections terminal shall be fitted with copper thimbles of required size. The main specification of the cable is given below:
Size :- 16 sqmm
170
120870
711
... More
Supply, Installation, Testing And Commissioning of L.T, 50 sqmm 1 core, capable to work up to 1.1 KV, XLPE insulated, galvanized steel strip armored copper cable conforming to IS : 7098 (part -1) 1988 With latest amendments to be utilized for interconnection of various electrical gadgets. The job includes providing and fitting of suitable rating copper thimbles duly crimped and taped at conductor ends by hydraulic crimping tool. The job includes laying of cable in cable tray Size :- 50 sqmm Suggested Make: L&T/ Polycab /Havells
The Test Certificate of Cables duly stamped by manufacturer shall be provided at the time of supply of material.
95
74100
780
... More
Supply, Installation, Testing And Commissioning perforated cable trays including horizontal and vertical bends, tees, cross members and other accessories as required and duly bolted to walls of building with Geyser bolts including Nuts and Washers etc.
Size= 150x50x1.6mm
30
27000
900
... More
Supply, Installation, Testing And Commissioning of earthing station for electric substation, LT panel and stabilizer comprising of company fabricated GI earthing electrode as per IS: 3043. The job includes Auguring of bore of required dia/depth for installation of electrode along with backfill compound mixed with soil and all other items required thereof for achieving the best result. The job includes connecting of electric gadgets through GI strip (25x3mm) as per relevant standards.
Safe earthing electrode size : 80 mm dia,
Length : 2000 mm
Back fill compound : 30 kg
6
62772
10462
... More
Supply, Installation, Testing And Commissioning of 6 kg Co2 type fire extinguisher manufactured as per IS: 15683 of 2006 with IS mark and comply with DGMS (Approval). The Co2 extinguisher should be suitable for class B & C fire and also for fire involving electrical equipment. The cylinder used for fire extinguisher shall be approved by petroleum and explosive safety organization (PESO) as per gas cylinder rules 2004 and as per IS: 7285 of 2004. The body should be made of seamless steel (manganese) confirming to IS: 7285 with IS mark and should be provided with squeeze grip nozzle and should be filled with co2 confirming to IS: 15222 of 2002 with certificate. The extinguisher shall be provided with manufactures test certificate and hydraulic test certificate by BIS from PESO.
2
12894
6447
... More
Illumination of Premises:
Providing and erection of 9 Mtr long Hot Dip Galvanized octagonal pole (single Section) with bottom 150mm, top 75mm wide, thickness 3mm with 70 Microns Zinc coating having inside arrangement for providing of power connection along with following items.
1) 3 Way Terminal Connector 20 Amp.
2) 3 No MCB 8 Amp.
The job includes fabrication, providing and fitting of three arm GI structures at the top having 120˚ angle between arms and each arm having 15˚ inclination with respect to horizontal plane. Each arm should be of 2’ length and size and shape appropriate as per requirement of the luminary.
The job also includes providing and fitting of required length of flexible multi strand 2 mm copper wire from each terminal connector to each holding arm.
The pole is mounted on 1:2:4 Cement concreting of size not less than 2’x2’x6” (cost of concreting not included in the job) using 04 No anchor bolts of required size not less than 7” in length. The complete job includes earthing in GI Electrode as per relevant IS Code.
2
44452
22226
... More
Providing, installation, testing and commissioning of area lighting 120 Watt LED (Street Light Type) on top of octagonal pole.
Having following specs:
Input: 90-240 V 50 Hz
Power Factor: 0.9
Colour Temperature: 4K - 6.5K
Beam Angle: 120˚ - 170˚
Lumens: 12000
Operating Temperature: -20˚C to 60˚C
The LED is pressure die cast aluminum housing with power coated finish and having Ingress Protection up to IP-68.
The LED is properly fitted on the arm of the pole and connected to the copper wire as provided in the high mast pole.
Suggested Make: Philips/Havells/Syska
6
56916
9486
... More
Supply, Installation, Testing And Commissioning of Junction Box with DP 32 A MCB to serve as Main switch for LED Lighting. The job includes connecting the junction box to the main power supply from panel.
2
4454
2227
... More
Supply, Installation, Testing And Commissioning of 2KVA fully automatic voltage stabilizer with input voltage 70-240 V and output 220 V. The stabilizer shall be installed and connected to the electric circuit as per location provided by site in charge. The voltage stabilizer is to be connected to the heating and lighting circuit of the scheme including the street lights.
1
8154
8154
... More
Supply, installation, Testing & commissioning of 1050VA Full Sine wave power inverter including Providing / Installation of 12V, 180AH Tubular inverter Battery with trolley and cover. with 2-core 4 mm2 Cu ( 25 m) wiring as per site requirement along with other accessories like SS-Combine (02 No’s), 3-pin plugs etc of reputed make for proper fitment and installation of the item.
1
34053
34053
... More
Providing, laying & fixing with adhesive/bonding material of insulation rubber mats on the floor of the pump house, covering area around electro-mechanical machinery for safeguarding the life & limb of the workmen due to possible leakage of current & short circuit. The floor surface shall be made good & shall be free from dust, grease, foreign material & moisture free. The mats shall be as per IS 15652:2006 & shall have the following specifications: -
Composition: Rubber (synthetic mats for electrical purpose)
Thickness: - 2.5mm Size: - 1M wide.
The rubber mats shall be accepted with manufacturers test certificate.
10
12050
1205
... More
TOOL KIT For Maintenance: -
The Tool Kit for maintenance shall comprise of the following and all the items as mentioned below shall be of :
Providing of tool kit consists of following items ( Taparia /Bosch)
i. Double ended Spanner (Chrome plated) 02 sets complete
ii. Double ended Ring spanners chrome plated 02 sets complete
iii. Allen key set black finish 02 sets complete
iv. Combination Pliers insulated with thick C.A sleeve; size in mm 165, 210, 255 each – 02 No.
v. Long nose pliers insulated with thick C.A sleeve; size in mm 165, 205 each – 02 No.
vi. Side cutting pliers insulated with thick C.A sleeve; size in mm 165, 205 make – 02 No.
vii. Insulated screw Drivers ( Taparia /Bosch) Blade length Blade dia. Tip dimensions Quantity 50 3 1.6 x 0.4 02
75 3 1.6 x0.4 02
100 3 3 x 0.4 02
125 3.5 3.5 x 0.5 02
150 3.5 3.5 x 0.5 02
200 4 4 x 0.6 02
300 5 5 x 0.8 02
viii. Hammer with handle weight – 110 mg, 340 gm , 600 gm –each – 1No. . ix. Heavy duty pipe Wrench length in mm - 200, 300, 600 each – 01 No. RIGID/IRWIN/Maxpower
x. Electric Multi-meter =1No Make: Fluke /Klein
xi. Digital Clamp tester capable to measure up to 400A - 1 No. Make: Fluke /Klein xii. Hack saw frame with hack saw blade – 01 no.
xiii. S-16 MXL, S- 16 H X L Socket Set (19 sockets + 6 Accessories) – 01 No. Make: Taparia /Bosch
Tool kit Make: Taparia /Bosch
The tool kit is to be provided in tool box of Make: Taparia /Gear Wrench/ Stanley.
1
28840
28840
... More
Providing of good quality bedding for night stay/Shift consisting of: - i) Mattress with warm cover size 6'x3' (6Kg)- 02 No’s.
ii) Quilt with warm cover size 5'x8' (6Kg)- 02 No’s. iii) Pillows with covers - 02 No’s.
iv) Single bed warm blankets with one sided Fur- 02 No’s The filling material for mattress, quilt and pillow shall be of good quality cotton b) The job also includes providing of pressure cooker 5ltr 02 No’s, Steel patella(utensil) 5ltrs 02 No’s, cooking heater 01 No., room heater 01 No., steel buckets 10 litre capacity 01 No., Plastic bucket 10 litre capacity with Mug 02 No’s each, steel glasses 06 No’s, steel Plates with large spoons and bowls 03 No’s each, Cup and Saucer set (01 No. Set) and, 5kg Gas cylinder with burner/ stove. The job also includes providing of thermo-cool 15’x12’ along with excel matting of 15’x12’ size. The job also includes providing of unbreakable Plastic Chair table set consisting of chairs 04 No’s, extra heavy Table 01 No. The job also includes providing of good quality safety Door locks (03 No’s) of Godrej, Link locks.
1
39619
39619
... More
Fabrication of 7’ (L) x 6’(B) x 1.5' (H) angle iron bed for operators with back-height of 2 feet by way of providing and fitting of Structural steel in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete welded.
114
11628
102
... More
Providing and fitting of 19 mm thick multilayered ply sheet of size 6 x 3 feet , 3 No’s including cutting , fixing all complete including painting of the play sheet by one coat of primer and two coats of enamel paint.
54
8316
154
... More
Providing of 1kw heat convector for operators for winter season
1
1205
1205
... More
Providing and fitting of 01 no. LED (Scroll type) sign board fabricated out of stainless steel and metal showing the names of water supply scheme and the Department. Size: 6’×1’6” = 9 sft
9
35982
3998
... More
Providing of CP 12 5WP solar/electrical lantern chargeable on both solar & electrical 220v supply. The solar lantern is to be provided with solar plate (provided in box with lantern)
1
1911
1911
... More
Providing of bamboo Ladder,18 ft long along with 15 ft long link rods and HT Gloves pair (01 No. Each)
1
7350
7350
... More
Providing of Industrial Rubber 11 KV Electrical Hand Shock Proof Safety Gloves for handling electrical equipments/connections.
3
2250
750
... More
Providing and fitting of 02 No. angle iron/sheet metal board duly painted showing various specifications of the mechanical and electrical equipment installed at site (01 No.) and The name of water supply Scheme (01 No.) of appropriate sizes. The details, drawings and specifications will be provided by Site Incharge.
35
8750
250
... More
Supply, Installation, Testing And Commissioning of L.T, 1 core , capable to work up to 1.1 KV , XLPE insulated , galvanized steel strip armored copper cable conforming to IS : 7098(part -1) 1988 With latest amendments to be fitted from D.G Set to Modular control panel . The job includes providing and fitting of suitable rating copper thimbles duly crimped and taped at conductor ends by hydraulic crimping tool. The job includes earth work in excavation wherever required for laying of cable underground.
Size:- 50 sqmm
Suggested Make: L&T/ Polycab /Havells
100
78000
780
... More
Supply, Installation, Testing And Commissioning of OFF-Load (Side operated) Changeover Switch in Separate SS Enclosure as below Capacity:- 250Amp, 415V, 50hz
Type: OFF Load
Voltage : 415V
No of Poles: 4
Operation: Side Operated
Standard Conformity: IS / IEC: 60947 - 1&3
Suggested Make: L&T/Havells/Siemens/ Scheneider
1
23000
23000
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements