Public Health Engineering Department Tender
Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Public Health Engineering Department - PHED Tender
Machinery and Tools
Eprocure
Opening Date31 Jan 2024
Closing Date16 Feb 2024
Tender Amount₹ 69,99,977
Costs
EMD
₹ 1,40,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_PHE_243985_2Bid Award Id
ViewTender No
JSD/PHE/MDSA/ e-NIT No. 47Tender Authority
Public Health Engineering Department ViewPurchaser Address
-Website
http://jktenders.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Providing/supplying and fitting of G.I flanged Rising Main at site. The Pipe shall be hot dip Galvanized, class C confirming to IS 1239. The job includes providing and fitting of M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16). The flanges shall be double welded both from inside and outside of the pipe using standard electrode of reputed make.
Flanges (as per IS 6392/1997 Table:17)
Thickness shall conform to IS 6392 Part 1st Table-17. The flange welding shall be carried out in double layers using reputed make electrodes to form strong welding joint.
Welding Electrode
DC Arc Welding using welding electrode having diameter not less than 4mm. Nuts and Bolts
Nuts and Bolts (conforming to IS:1363 Part 1st) Rubber Insertion Gaskets
Rubber Insertion Gaskets (conforming to IS: 638/79) to be used between flanged joints. The main technical specifications of the pipe are given here under:
Size : DN 100 Class : C (Heavy)
1450
3174050
2189
Providing and fitting of 300 mm in length GI Reducer bend flanged on both sides, the thickness of flange shall conform to IS 6392 Part 1st Table-17 (PN 16) to be fitted with the column pipe/delivery manifold of submersible pumping unit to join rising main and column pipe/delivery manifold. The flange welding shall be carried out in double layers using reputed make electrodes to form strong welding joint. The size of the reducer bend is given below :
Size : DN 100 mm Class : C
4
24000
6000
Fabrication, Providing and fitting of Y- junction having 1m length (Approx.) of each arm to be fabricated out of hot dip galvanized G.I, C-Class pipe. The job also includes providing and welding of M.S flanges to the ends of each arm. The Thickness of flange shall conform to IS 6392 Part 1st Table-17. The flange welding shall be carried out in double layers using reputed make electrodes to form strong welding joint by dint of DC arc welding. The job further includes Providing and Fitting of nuts and bolts (conforming to IS:1363 Part 1st) and Rubber Insertion Gaskets (conforming to IS: 638/79) to be used between flanged joints. The size of the Y- junction is given below :
Size : 100 mm Class : C
3
29211
9737
Providing and fitting of Ductile Iron double flanged, non-rising spindle soft seated glandless gate/ sluice valves as per IS14846 for regulating the water supply outside the pumping units.
The body and bonnet of the valve shall be of ductile iron, wedge with fully vulcanized EPDM rubber(Approved for drinking water) and NBR seal. The Gate/Sluice valve shall be compatible for buried applications and shall be safe to install in both horizontal and vertical positions
It shall have electrostatic epoxy coating(approved for drinking water) both inside and outside of the valve. The valve shall be supplied along with hand wheel.
Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work.
The job includes providing and fitting of 02 nos. M.S flanges (Table flanges) perfectly adaptable to the inbuilt flanges of the valve which shall be fitted with rising main of the pumping unit at appropriate spots as per site requirement. The job includes the cost on account of P/F of nuts, bolts and gasket required for the job.
Size : DN 100 mm Rating : PN 1.6
9
171846
19094
Providing and fitting of Ductile Iron double flanged, Slanted seat swing check valve (NRV) as per IS 5312. The body shall be of ductile cast iron,wedge with fully encapsulated vulcanized EPDM rubber(Approved for drinking water). The valve shall be compatible for buried applications and shall be safe to install in both horizontal and vertical positions.
It shall have electrostatic epoxy coating (approved for drinking water) both inside and outside of the valve.
Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work.
The job includes providing and fitting of 02 nos. M.S flanges (Table flanges) perfectly adaptable to the inbuilt flanges of the valve which shall be fitted with Rising main of the pumping unit at appropriate spots as per site requirement. The job includes the cost on account of P/F of nuts, bolts and gasket required for the job. Size : DN 100 mm Rating : PN: 1.6/16
8
164648
20581
Providing, fitting, testing and commissioning of ARV (Air Release valve) as per IS 14845 to be fitted to G.I rising Main. The ARV Shall have the following specifications: -
i. Valve type - single chamber, single/double orifice.
ii. End connection - flanged ends to IS 1538 iii. Working temperature - 45oc to -150 c iv. Test pressure - body / seat 2.5 x PN
v. Sealing ring - EPDM
vi. Construction -ductile iron with stainless steel floats
vii. Coating - epoxy with corrosion resistance Besides the above works, The job also cost on account of P/F R.I gasket, GI Pipe, nuts and bolts required for installation of ARV and arrangement of gas cutter/ welding set at site.
Size: 50 mm
2
38788
19394
Structural steel work in build up welded sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a primed coat of approved steel primer all complete.
1600
177600
111
Providing, installation and testing of manual type triple spur gear chain pulley block along with monorail geared travelling trolley having following features
Gears: The hoist shall have precision machine case Hardened alloy steel gear mounted on bearings and housed in a dust proof gear box. The lubrication of gears should be of high viscosity and temperature for longer life of gears.
Load Chain:- The load chain be made of high tensile alloy steel having wear resistance and greatest mobility. The chain should be accurately collaborated, tested and have adequate in built factor of safety for safer operation.
Load chain wheel:- the load chain well should be double ball bearing supported and Specially designed, perfectly machined wheel providing correct grip of load chain to makes the hoist most safe and reliable against any failure.
Make = Reputed make
No. Of load chain falls = 2 or above
Min. Height of lift = 6 M Capacity = 2 Ton
2
88946
44473
Earth work in excavation by manual means in trenches for foundation , drains ,pipes , cables (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and reaming of bottom lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth lead upto 1m from cutting edge in all kinds of soil.
112.6
52601
467.15
Filling available excavated earth in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth , consolidating each deposited layer by reaming and watering , lead upto 50 m and lift upto 1.5 m.
101.34
22149
218.57
Supply , installation , commissioning and creation of pole mounted, outdoor type Electric Sub Station as per the technical specifications given here under -
Specifications conforming to IS: 1180 (Part 1) 2014 with latest amendments.
Type: HT/LT Transformer
Type of cooling: ONAN.
Operating conditions:
Input = 6.6 KV
Output = 433 volts AC supply in 3- phase, 50 Hz
Terminals:
Input=3 No. HT bush rods with insulators, washer, nuts etc.
Output=4 No. LT bush rods switch insulators, washers, nuts etc.
Core: The core shall be of high permeability to reduce core losses and the strips shall be of suitable size and gauge. Transformer Coils: Suitable number of HT and LT coils in each leg of the core. The transformer coils shall be fabricated out of superior quality aluminum wire/strips, properly wound. The HT transformer is completely filled with suitable grade transformer oil up to required level. The job includes carriage, and all leads and lifts involved.
The HT transformer shall be of reputed make from an ISO certified company as per relevant standards and a test certificate shall be provided before installation. The transformer shall also be provided with breather fill with silica gel crystals, conservator with oil level indicator, explosion vet and adequate radiator fins/ Tubes. The impedance of transformer shall be as per IS: 1180 (Part 1) 2014 with latest amendments. NOTE: The scope of the work shall include obtaining of necessary inspection/clearance certificate from the concerned department for all the required equipment. The testing and commissioning shall be completed only after obtaining above certificate.
Rating : 200 KVA
1
382996
382996
Providing and laying in position cement concrete of 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 20 mm nominal size) excluding the cost of centering and shuttering - including cost and carriage of all materials involved upto site of work complete.
5
26908
5381.6
Providing and fitting of Prodigy LT meter of following specification complete with all fixtures required for fitment at site for above mentioned scheme
Type: E3L 100, 3-phase, 4-wire.
Measurements offered: KWh, KVARh, KVAh, KVA.
Voltage: 2240 V(415 V) 50 Hz, Ib: 40 A, Imax: 200 A, Battery: Lithium
1
25000
25000
Providing and fitting G.I Channel /Angle/ Flat of sizes including clamps
300
36900
123
Supply, Installation, Testing and commissioning of Polymeric Gang operated Air break switch, outdoor type, triple pole, suitable for vertical installation, single break provided with locking arrangement at both ON and OFF position consisting of HT post double insulator, copper or copper alloy high pressure heavy contact assembly, rod with bearings , operating handle and 2 length of 32mm dia. GI pipe conforming to IS 1818 1961, 06 No. of insulators, rated voltage 11KV 200A complete as per IS specs.
2
23460
11730
Supply, Installation, Testing and commissioning of 11KV polymer fuses Set Horn Gap 3-phase 200 A suitable for vertical installation .
1
4983
4983
Supply, Installation, Testing and commissioning of Gapless Surge arrestor station class, 10KA, 9KV, LA With polymer housing , Station Type .
1
7754
7754
Supply and fitting of 11 KV polymeric composite pin insulator 12 KV, 5KN, Lighting impulse 75KV Positive, and 80 KV Negative , creepage distance 320 mm
8
2776
347
P/F of Galvanized nuts, bolts of various sizes as per site requirement.
35
4970
142
Providing and fixing G.I Barbed wire for anti climbing
70
9520
136
Providing and fitting of Galvanized stay set with 50 X 8 mm Stay Clamp , Guy insulator (2no.), Anchor plate (200X200X6mm) , nuts and bolts , 2 N0- turn buckle , 1.8 m long , 16 mm diameter solid G.I stay rod & 7/3.15 mm dia. G.I stranded wire complete.
2
9844
4922
Painting of poles Red oxide
16
4896
306
Painting of poles Aluminum paint
16
8160
510
Providing and fitting of ACSR as per IS 398 (part-2) 1996 for 50 sq.mm ACSR (Galvanised steel reinforced) for fitment of various accessories
45
2520
56
Fabrication, Providing and fitting of Modular motor control panel (MUG-30, 30 HP) of appropriate size fabricated out of 14 SWG sheet having required openings/vents and protection Class : IP-55 & fitted with accessories as under:
a) Bus bar Chamber:
The bus bar chamber shall be fitted at the top of the panel horizontally throughout the length. There shall be 3 Nos. of phase bus bar and 1 No neutral bus bar and 1 No earthing bus bar. The bus bars shall be air insulated and made-up of high conductivity COPPER with current density of suitable rating for 100 Ampere. All panel compartments shall be provided with suitable cable alley and vertical bus bar alley. Suitable segregation shall be provided in between bus bar chamber and adjoining compartments. The bus bar shall be PVC sleeved with color strips of red, yellow, blue and black and the same be arranged in accordance with IS-375 specs. Electrical clearances shall be maintained between phases, neutral and body as per standards.
b) Main Circuit Breaker (Incomer MCCB):
Qty. = 01 No
No. of poles = 4 Pole
Current Rating = 160-200 A
Rated operational voltage = 415 V + 15 %
Rated frequency = 50+/-3%Hz
Ambient temperature = 40C˚
Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 50 KA
Type of release = Thermal-Magnetic
Overload protection = 0.8 – 1×ln adjustable
Short-circuit protection = 6-10×ln adjustable.
c) Change over Switch:
Qty. = 01 No.
Rating = 100 A
Type = Front operated, on load, 4 pole, 400 +15%V, 50 + 3%Hz.
d) Motor Back-up Protection MCCB:
Qnty = 2 No
No. of poles = 3P
Current Rating = 100-125 A
Rated operational voltage = 415 V +15 %
Rated frequency = 50 + 3% Hz
Ambient temperature = 40C˚
Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 36 KA
e) Submersible starters = Fully automatic star delta/DOL starters.
Capacity = 30 HP
Power Specs = 3 Ф, 415 + 15% V, 50 + 3 % Hz.
Relay range = 30-50 A
Coil Voltage = 380 v Protection = single phasing , phase Reversal, phase unbalance (55 ± 5 V) ,
Rated insulation voltage = 690V Terminal capacity = 120 Sq. mm with lug Or above
Conformity to standard = IS/IES 60947-4-1 Qty. = 2 No’s
f) Auxiliary MCCB for Heating/Lighting:
Circuit Breaker = MCCB (Outgoing)
Qty. = 1 No.
No. of poles = 4P
Current Rating = 63 A
Rated operational voltage = 415 V + 15 %
Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = As per requirement g) Motor Protection Relay:
Digital Motor Protection Relay with LCD Display for 3-phase supply with following protections suitable for the Modular Control Panel:-
Protections = Thermal Overload with pre-alarm, Short Circuit, Phase Loss, Unbalance, Phase reversal, Under Current, over current, Prolong starting, Locked Rotor, Under voltage, over voltage & Earth fault.
h) M-power module for mobile starter for submersible motor 1P/3P 3 wire IVRS Languages – English , Hindi, Suitable Region- North India
The panel shall be provided with phase indicators (03 N0) and digital ammeter of range 0-60 A, digital voltmeter of range 0-500 V, and digital frequency meter (01 No for each starter). The enclosure of the panel shall be of excellent fit and finish, corrosion resistant and powder coated gliding hinges for smooth and noiseless movement of windows and advanced locking arrangements.
1
234576
234576
Fabrication, Providing and fitting of Modular motor control panel (MUG-40, 40 HP) of appropriate size fabricated out of 14 SWG sheet having required openings/vents and protection Class : IP-55 & fitted with accessories as under:
a) Bus bar Chamber:
The bus bar chamber shall be fitted at the top of the panel horizontally throughout the length. There shall be 3 Nos. of phase bus bar and 1 No neutral bus bar and 1 No earthing bus bar. The bus bars shall be air insulated and made-up of high conductivity COPPER with current density of suitable rating for 200 Ampere. All panel compartments shall be provided with suitable cable alley and vertical bus bar alley. Suitable segregation shall be provided in between bus bar chamber and adjoining compartments. The bus bar shall be PVC sleeved with color strips of red, yellow, blue and black and the same be arranged in accordance with IS-375 specs. Electrical clearances shall be maintained between phases, neutral and body as per standards.
b) Main Circuit Breaker (Incomer MCCB):
Qty. = 01 No.
No. of poles = 4 Pole
Current Rating = 160-200 A
Rated operational voltage = 415 V + 15 %
Rated frequency = 50+/-3%Hz
Ambient temperature = 40C˚
Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 50 KA
Type of release = Thermal-Magnetic
Overload protection = 0.8 – 1×ln adjustable
Short-circuit protection = 6-10×ln adjustable.
c) Change over Switch:
Qty. = 01 No.
Rating = 200 A
Type = Front operated, on load, 4 pole, 400 +15%V, 50 + 3%Hz.
d) Motor Back-up Protection MCCB:
Qnty = 2 No
No. of poles = 3P
Current Rating = 84-125 A
Rated operational voltage = 415 V +15 %
Rated frequency = 50 + 3% Hz
Ambient temperature = 40C˚
Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 36 KA
e) Submersible starters = Fully automatic star delta/DOL starters.
Capacity = 40 HP
Power Specs = 3 Ф, 415 + 15% V, 50 + 3 % Hz.
Relay range = 36-60 A
Coil Voltage = 380 v Protection = single phasing , phase Reversal, phase unbalance (55 ± 5 V) ,
Rated insulation voltage = 690V Terminal capacity = 120 Sq. mm with lug Or above
Conformity to standard = IS/IES 60947-4-1 Qty. = 2 No’s
f) Auxiliary MCCB for Heating/Lighting:
Circuit Breaker = MCCB (Outgoing)
Qty. = 1 No.
No. of poles = 4P
Current Rating = 63 A
Rated operational voltage = 415 V + 15 %
Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = As per requirement g) Motor Protection Relay:
Digital Motor Protection Relay with LCD Display for 3-phase supply with following protections suitable for the Modular Control Panel:-
Protections = Thermal Overload with pre-alarm, Short Circuit, Phase Loss, Unbalance, Phase reversal, Under Current, over current, Prolong starting, Locked Rotor, Under voltage, over voltage & Earth fault.
h) M-power module for mobile starter for submersible motor 1P/3P 3 wire IVRS Languages – English , Hindi, Suitable Region- North India
The panel shall be provided with phase indicators (03 N0) and digital ammeter of range 0-60 A, digital voltmeter of range 0-500 V, and digital frequency meter (01 No for each starter). The enclosure of the panel shall be of excellent fit and finish, corrosion resistant and powder coated gliding hinges for smooth and noiseless movement of windows and advanced locking arrangements.
1
272539
272539
Fabrication, Providing and fitting of Modular motor control panel (MUG-7.5, &.5 HP) of appropriate size fabricated out of 14 SWG sheet having required openings/vents and protection Class : IP-55 & fitted with accessories as under:
a) Bus bar Chamber:
The bus bar chamber shall be fitted at the top of the panel horizontally throughout the length. There shall be 3 Nos. of phase bus bar and 1 No neutral bus bar and 1 No earthing bus bar. The bus bars shall be air insulated and made-up of high conductivity COPPER with current density of suitable rating for 100 Ampere. All panel compartments shall be provided with suitable cable alley and vertical bus bar alley. Suitable segregation shall be provided in between bus bar chamber and adjoining compartments. The bus bar shall be PVC sleeved with color strips of red, yellow, blue and black and the same be arranged in accordance with IS-375 specs. Electrical clearances shall be maintained between phases, neutral and body as per standards.
b) Main Circuit Breaker (Incomer MCCB):
Qty. = 01 No.
No. of poles = 4 Pole
Current Rating = 100-125 A
Rated operational voltage = 415 V + 15 %
Rated frequency = 50+/-3%Hz
Ambient temperature = 40C˚
Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 36 KA
Type of release = Thermal-Magnetic
Overload protection = 0.8 – 1×ln adjustable
Short-circuit protection = 6-10×ln adjustable.
c) Change over Switch:
Qty. = 01 No.
Rating = 100 A
Type = Front operated, on load, 4 pole, 400 +15%V, 50 + 3%Hz.
d) Motor Back-up Protection MCCB:
Qnty = 2 No
No. of poles = 3P
Current Rating = 80-100 A
Rated operational voltage = 415 V +15 %
Rated frequency = 50 + 3% Hz
Ambient temperature = 40C˚
Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 36 KA
e) Submersible starters = Fully automatic star delta/DOL starters.
Capacity = 7.5 HP
Power Specs = 3 Ф, 415 + 15% V, 50 + 3 % Hz.
Relay range = 9-14 A
Coil Voltage = 380 v Protection = single phasing , phase Reversal, phase unbalance (55 ± 5 V) ,
Rated insulation voltage = 690V Terminal capacity = 120 Sq. mm with lug Or above
Conformity to standard = IS/IES 60947-4-1 Qty. = 2 No’s
f) Auxiliary MCCB for Heating/Lighting:
Circuit Breaker = MCCB (Outgoing)
Qty. = 1 No.
No. of poles = 4P
Current Rating = 63 A
Rated operational voltage = 415 V + 15 %
Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = As per requirement g) Motor Protection Relay:
Digital Motor Protection Relay with LCD Display for 3-phase supply with following protections suitable for the Modular Control Panel:-
Protections = Thermal Overload with pre-alarm, Short Circuit, Phase Loss, Unbalance, Phase reversal, Under Current, over current, Prolong starting, Locked Rotor, Under voltage, over voltage & Earth fault.
h) M-power module for mobile starter for submersible motor 1P/3P 3 wire IVRS Languages – English , Hindi, Suitable Region- North India
The panel shall be provided with phase indicators (03 N0) and digital ammeter of range 0-60 A, digital voltmeter of range 0-500 V, and digital frequency meter (01 No for each starter). The enclosure of the panel shall be of excellent fit and finish, corrosion resistant and powder coated gliding hinges for smooth and noiseless movement of windows and advanced locking arrangements.
1
156601
156601
Providing, fitting, testing and commissioning of 50 KVA voltage stabilizer as per specifications below: Type of voltage controller: Manually operated copper wound, 3-phase, AC power supply multi step.
Type of Regulator : Double plate type with electrolytic copper contacts.
Input voltage : 250-400 volts.(3 phase)
Output voltage : 400 ±10% volts.
Frequency : 50 ±3 C/S.
Windings : Electrolytic grade copper of adequate section, vacuum impregnated and Oven-dried.
Insulation : Fiber glass insulations to tested parameters.
Cooling : Naturally, Oil cooled
Temp. Rise (Max) : 30°C above ambient
Mounting : On Uni-directional wheels.
Correction rate : 30 volts per step
Wave form distortion : virtually nil
Duty cycle : 100% continuous.
Enclosure : MS sheet enclosure in pressed CGR Sheet powder coated with radiators.
Core laminates : High grade, low eddy loss, grain oriented silicon steel laminations.
Load : Three phase induction motor load.
Load Amperes (continuous)
Overload in 24-hours operation: 10% above continuous Ampere rating.
The voltage stabilizer shall have T-oil level indicator gauge preferably glass type tube or otherwise visible to naked eye. The top of the container to have a display panel for housing 02 numbers Digital voltmeters (0-500V) along with 4-way selector switch and set of neon indicators for incoming and outgoing phases (06 No’s).
Insulating media (T. Oil) of 11 KVA grade to be provided and filled up to top level, with dielectric strength of 5 KV at 4m air gap. The T-Oil of specific grade should be provided in separate barrels and filled at site up to top level.
The voltage Stabilizer shall be accepted with manufacturers dully stamped test certificate and shall have name plate with specifications.
3
322203
107401
Providing and fitting of 3-Core flat submersible copper cable conforming to IS: 694 (Part 1st) – 1964 & IS: 694 (Part 2nd) - 1964 for Submersible Pumping Unit and other electrical Equipments . The cable connections terminal shall be fitted with copper thimbles of required size.
16 sqmm
180
127980
711
Providing and Fitting of 3 /3.5/2-Core, XLPE Armoured Aluminium Cable conforming to IS: 7089 part 1st as service line from the HT transformer to control panel including necessary thimbling, crimping, taping etc.
NOTE:- The cable terminal ends for connection to switchgear at various requisite points shall be Al. Thimbles of dowel’s make and of appropriate size and connected by hydraulic crimp tool only.
50 sqmm, 3.5 core
180
89460
497
10 sqmm, 2 core
90
14580
162
Providing and Fitting of three/single-Core, copper pvc insulated Cable, XLPE armoured conforming to IS: 7089 part 1st for internal connections, crimping, taping etc.
NOTE:- The cable terminal ends for connection to switchgear at various requisite points shall be Al. Thimbles and of appropriate size and connected by hydraulic crimp tool only.
Single core PVC insulated 16 sqmm
90
22320
248
P/I of earthing station for substation, LT panel, DG set and stabilizer comprising of company fabricated earthing electrode as per IS: 3043. The job includes Auguring of bore of required dia/depth for installation of electrode along with backfill compound mixed with soil and all other items required thereof for achieving the best result. The job includes connecting of electric gadgets through GI strip as per relevant standards.
Safe earthing electrode size : 80 mm dia , Length : 2000 mm
Back fill compound : 30 kg
7
73234
10462
Supply, installation of 6 kg CO2 type fire extinguisher manufactured as per IS: 15683 of 2006 with IS mark and comply with DGMS (Approval). The co2 extinguisher should be suitable for class B & C fire and also for fire involving electrical equipment. The cylinder used for fire extinguisher shall be approved by petroleum and explosive safety organization (PESO) as per gas cylinder rules 2004 and as per IS: 7285 of 2004. The body should be made of seamless steel (manganese) confirming to IS: 7285 with IS mark and should be provided with squeeze grip nozzle and should be filled with co2 confirming to IS: 15222 of 2002 with certificate. The extinguisher shall be provided with manufactures test certificate and hydraulic test certificate by BIS from PESO.
4
25788
6447
Illumination of Premises:
Providing and erection of 9 Mtr long Hot Dip Galvanized octagonal pole (single Section) with bottom 150mm, top 75mm wide, thickness 3mm with 70 Microns Zinc coating having inside arrangement for providing of power connection along with following items.
1) 3 Way Terminal Connector 20 Amp.
2) 3 No MCB 8 Amp. The job includes fabrication, providing and fitting of three arm GI structure at the top having 120˚ angle between arms and each arm having 15˚ inclination with respect to horizontal plane. Each arm should be of 2’ length and size and shape appropriate as per requirement of the luminary.
The job also includes providing and fitting of required length of flexible multi strand 2 mm copper wire from each terminal connector to each holding arm.
The pole is mounted on 1:2:4 Cement concreting of size not less than 2’x2’x6” (cost of concreting not included in the job) using 04 No anchor bolts of required size not less than 7” in length. The complete job includes earthing in GI Electrode as per relevant IS Code.
3
66678
22226
Providing, installation, testing and commissioning of area lighting 120 Watt LED (Street Light Type) on top of octagonal pole.
Having following specs:
Input: 90-240 V 50 Hz
Power Factor: 0.9
Colour Temperature: 4K - 6.5K
Beam Angle: 120˚ - 170˚
Lumens: 12000
Operating Temperature: -20˚C to 60˚C
The LED is pressure die cast aluminum housing with power coated finish and having Ingress Protection up to IP-68.
The LED is properly fitted on the arm of the pole and connected to the copper wire as provided in the high mast pole
9
85374
9486
Providing, Installation and testing of 2KVA fully automatic voltage stabilizer with input voltage 70-240 V and output 220 V. The stabilizer shall be installed and connected to the electric circuit as per location provided by site incharge.
2
16308
8154
Providing and installation of Junction Box with DP 32 A MCB to serve as Main switch for LED Lighting. The job includes making of electric connection to the circuit.
2
4454
2227
Supply, installation, Testing & commissioning of 1000VA Full Sine wave power inverter including Providing / Installation of 12V, 180AH Tubular inverter Battery with trolley and cover with 2-core 6mm2 Cu wiring as per site requirement along with other accessories like SS-Combine (02 No’s), 3-pin plugs etc of reputed make for proper fitment and installation of the item.
2
68106
34053
Providing, laying & fixing with adhesive/bonding material of insulation rubber mats on the floor of the pump house, covering area around electro-mechanical machinery for safeguarding the life & limb of the workmen due to possible leakage of current & short circuit. The floor surface shall be made good & shall be free from dust, grease, foreign material & moisture free. The mats shall be as per IS 15652:2006 & shall have the following specifications: -
Composition: Rubber (synthetic mats for electrical purpose)
Thickness: - 2.5mm Size: - 1M wide.
The rubber mats shall be accepted with manufacturers test certificate.
10
12050
1205
TOOL KIT For Maintenance: -
The Tool Kit for maintenance shall comprise of the following and all the items as mentioned below shall be of Providing of tool kit consists of following items i. Double ended Spanner (Chrome plated) 02 sets complete
ii. Double ended Ring spanners chrome plated 02 sets complete
iii. Allen key set black finish 02 sets complete
iv. Combination Pliers insulated with thick C.A sleeve; size in mm 165, 210, 255 each – 02 No.
v. Long nose plier insulated with thick C.A sleeve; size in mm 165, 205 each – 02 No.
vi. Side cutting plier insulated with thick C.A sleeve; size in mm 165, 205 make – 02 No.
vii. Insulated screw Drivers Blade length in mm Blade dia. in mm Tip dimensions in mm Quantity 50 3 1.6 x 0.4 02
75 3 1.6 x0.4 02
100 3 3 x 0.4 02
125 3.5 3.5 x 0.5 02
150 3.5 3.5 x 0.5 02
200 4 4 x 0.6 02
300 5 5 x 0.8 02
viii. Hammer with handle weight – 110 mg, 340 gm , 600 gm –each – 1No. . ix. Heavy duty pipe Wrench length in mm - 200, 300, 600 each – 01 No.
x. Electric Multimeter=1No
xi. Digital multimeter – 1No.
xii. Digital Clamp tester capable to measure up to 400A - 1 No.
xiii. Hack saw frame with hack saw blade – 01 no.
xiv. S-16 MXL, S- 16 H X L Socket Set (19 sockets + 6 Accessories) – 01 No.
2
57680
28840
a) Providing of good quality bedding for night stay/Shift consisting of: -
i) Mattress with warm cover size 6'x3' (6Kg)- 02 No’s
ii) Quilt with warm cover size 5'x8' (6Kg)- 02 No’s
iii) Pillows with covers - 02 No’s
iv) Single bed warm blankets with one sided Fur- 02 No’s
The filling material for mattress, quilt and pillow shall be of good quality cotton
b) The job also includes providing of pressure cooker 5ltr 02 No’s, Steel patella (utensil) 5ltrs 02 No’s, cooking heater 01 No., room heater 01 No., steel buckets 10 litre capacity 01 No., Plastic bucket 10 litre capacity with Mug 02 No’s each, steel glasses 06 No’s, steel Plates with large spoons and bowls 03 No’s each, Cup and Saucer set (01 No. Set) and, 5kg Gas cylinder with burner/ stove. The job also includes providing of thermo-cool 15’x12’ along with excel matting of 15’x12’ size. The job also includes providing of unbreakable Plastic Chair table set consisting of chairs 04 No’s, extra heavy Table 01 No. The job also includes providing of good quality safety Door locks (03 No’s) of Godrej, Link locks,
1
39619
39619
Providing of solar/ electrical lantern chargeable on both solar & electrical 220v supply.
2
3822
1911
Providing of bamboo ladders 18 feet long along with 15 feet long Link rods and HT Glove pair (01 No each)
1
7350
7350
Providing of 1 KW heat convector for operators for winter season.
2
2410
1205
Providing and fitting of 01 No. LED (scroll type) sign board fabricated out of stainless steel and metal showing the names of water supply scheme and the Department. Size: 6’×1’6”
9
35982
3998
Providing and fitting of 01 No. angle iron/sheet metal board duly painted showing various specifications of the mechanical and electrical equipments installed at site. Size: 4’×6’ out MS ANGLE OF 40X 40X 5mm and MS sheet of 1 mm thick
24
6000
250