Public Health Engineering Department Tender
Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Public Health Engineering Department - PHED Tender
Machinery and Tools
Eprocure
Opening Date16 Nov 2024
Closing Date22 Nov 2024
Tender Amount₹ 24,17,248
Costs
EMD
₹ 48,345Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_PHE_264858_1Tender No
JSD/PHE/MDSA/ e-NIT No. 25Tender Authority
Public Health Engineering Department ViewPurchaser Address
-Website
http://jktenders.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Earth work in excavation by manual means in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed:
i. All kinds of soil (80%) 01 mtr from cutting edge.
20
479
9580
ii. Ordinary Rock (20%) 01 mtr from cutting edge.
5
924
4624
Filling available excavated earth in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by reaming and watering, lead upto 50 m and lift upto 1.5m.
22
198
4371.4
Providing and laying of stone soling including manual compaction.
6
740
4440
Centering and shuttering including strutting, propping etc. and removal of form work for Foundation, footings, bases for columns.
23
286
6578
Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering, all work upto plinth level with 1: 2 : 4 mix (1 cement , 2 coarse sand , 4 graded stone aggregate 20 mm nominal size).
22
6591
145007.5
Providing and laying in position 12 mm thick cement plaster of mix. 1 : 4 mix (1 cement , 4 fine sand).
18
283
5108.4
Fabrication, providing and fitting of washout Tee with each arm one feet long shall be fabricated out of 80 mm dia C-Class Pipe with M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) fastened with weld joints on three ends. The size of the Tee is given Below:
Size : DN 80 MM Class: C (Heavy)
1
4050
4050
Supply, Installation, Testing and Commissioning of Ductile Iron double flanged, non-rising spindle Resilient seated gate/ sluice valves (PN16) in accordance with IS 14846 for regulating the water supply outside the pumping units. The body and bonnet of the valve shall be of ductile iron, wedge with fully vulcanized EPDM rubber (Approved for drinking water) and NBR seal. The Gate/Sluice valve shall be compatible for buried applications and shall be safe to install in both horizontal and vertical positions. It shall have electrostatic epoxy coating (approved for drinking water) both inside and outside of the valve. The valve shall be supplied along with hand wheel.
Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work.
The job includes providing and fitting of 02 Nos. M.S flanges perfectly adaptable to the inbuilt flanges of the valve which shall be fitted with rising main of the pumping unit at appropriate spots as per site requirement. The job includes the cost on account of P/F of nuts, bolts and gasket required for the job. The Test Certificates of Sluice/Gate Valves mentioning the Material of Construction as above duly stamped by OEM shall be provided at the time of supply of material.
Size: DN 80 mm Rating: PN 1.6/16
2
15497
30994
Supply, Installation, Testing and Commissioning of Ductile Iron double flanged, Slanted seat swing check valve (NRV) (PN16) as per IS 5312. The body shall be of ductile cast iron with fully encapsulated vulcanized EPDM rubber (Approved for drinking water). The valve shall be compatible for buried applications and shall be safe to install in both horizontal and vertical positions.
It shall have electrostatic epoxy coating (approved for drinking water) both inside and outside of the valve.
Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work.
The job includes providing and fitting of 02 Nos. M.S flanges perfectly adaptable to the inbuilt flanges of the valve which shall be fitted with Rising main of the pumping unit at appropriate spots as per site requirement. The job includes the cost on account of P/F of nuts, bolts and gasket required for the job. The Test Certificates of Check Valves (NRVs) mentioning the Material of Construction as above duly stamped by OEM shall be provided at the time of supply of material
Size: DN 80 mm Rating: PN 1.6/16
2
17489
34978
Fabrication, Providing and fitting of 90-120 degree bend/elbow to be fabricated out of Class B GI pipe, 1 m length and flanged on both ends a to make it leak proof. The flanges shall be M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) and welded on both sides. The job includes nuts, bolts, gaskets etc as per site requirement.
Size : DN 80 mm Class :- B
3
2797
8391
Fabrication, providing and fitting of split type MS clamps 10 mm thick, 2 ft long and 3 inch wide for lowering and holding of pumping unit fitted. The job includes the cost of required size of nuts and bolts.
Size : DN 80 mm
2
1801
3602
Fabrication of MS Gantry mechanism by way of providing Structural steel in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer and two coats of enamel paint of approved shade complete in all aspects. The detailed drawing Shall be provided by the site incharge at the time of execution of work.
600
111
66600
Providing, installation and testing of manual type triple spur gear chain pulley block along with monorail geared travelling trolley having following features
Gears:- The hoist shall have precision machine case Hardened alloy steel gear mounted on bearings and housed in a dust proof gear box. The lubrication of gears should be of high viscosity and temperature for longer life of gears.
Load Chain:- The load chain be made of high tensile alloy steel having wear resistance and greatest mobility. The chain should be accurately collaborated, tested and have adequate in built factor of safety for safer operation.
Load chain wheel:- the load chain well should be double ball bearing supported and Specially designed, perfectly machined wheel providing correct grip of load chain to makes the hoist most safe and reliable against any failure. The main specifications of C.P Block are given below : Make = Reputed make Capacity = 2 ton (P)
No. Of load chain falls = 2 or above
Min. Height of lift = 6 M
Test certificate of Manufacturer to be appended.
1
44473
44473
Supply, Installation, Testing and Commissioning of outdoor type Electric Sub Station as per the technical specifications given here under -
Specifications conforming to IS: 1180 (Part 1) 2014 with latest amendments.
Type: HT/LT Transformer (Energy Level-2 with biometallic terminal conductors)
Capacity:- 25 KVA
Type of cooling: ONAN.
Operating conditions:
Input = 11000 volts
Output = 433 volts AC supply in 3- phase.
Terminals:
Input = 3 No. HT Brass bush rods with insulators, washer, nuts etc.
Output = 4 No. LT Brass bush rods switch insulators, washers, nuts etc.
Core: The core shall be of high permeability to reduce core losses and the strips shall be of suitable size and gauge. Transformer Coils: Suitable number of HT and LT coils in each leg of the core. The transformer coils shall be fabricated out of superior quality aluminum wire/strips, properly wound. The HT transformer is completely filled with suitable grade transformer oil up to required level. The job includes carriage, and all leads and lifts involved.
The HT transformer shall be of reputed make from an ISO certified company as per relevant standards and a test certificate shall be provided before installation. The transformer shall also be provided with breather fill with silica jel crystals, conservator with oil level indicator, explosion vent and adequate radiator fins/ Tubes. The impedance of transformer shall be as per IS: 1180 (Part 1) 2014 with latest amendments. NOTE: The scope of the work shall include obtaining of necessary inspection/clearance certificate from the concerned department for all the required equipment. The testing and commissioning shall be completed only after obtaining above certificate.
1
74442
74442
Providing and fitting G.I Channel /Angle/ Flat of sizes including clamps, v-cross and f-top
650
123
79950
Supply, Installation, Testing and commissioning of Polymeric Gang operated Air break switch, outdoor type, triple pole, suitable for vertical installation, single break provided with locking arrangement at both ON and OFF position consisting of HT pole double insulator, copper or copper alloy high pressure heavy contact assembly, rod with bearings, operating handle and 32mm dia. GI pipe conforming to IS 1818 1961, 06 No. of insulators, rated voltage 11KV 200A complete as per IS specs.
2
11730
23460
Supply, Installation, Testing and commissioning of 11KV polymer fuses Set Horn Gap 3-phase 200 A suitable for vertical installation.
1
4983
4983
Supply, Installation, Testing and commissioning of Gapless Surge arrestor station class, 10KA, 9KV, LA With polymer housing, Station Type.
1
7754
7754
Supply and fitting of 11 KV polymeric composite pin insulator 12 KV, 5KN, Lighting impulse 75KV Positive, and 80 KV Negative, creepage distance 320 mm.
50
347
17350
Supply and fitting of 11 KV polymeric composite disc insulator 12 KV, min. falling load 45KN, Lighting impulse 75KV Positive, and 80 KV Negative, creepage distance 320 mm.
6
347
2082
Supply, installation, erection, Testing and Commissioning of 9 mtrs long H.T Steel Tubular pole of specifications ST- 410 (SP-33). The job further includes drilling of holes for installation of various accessories, wherever required the job further includes G.I wire earthing of pole as per REC standard. The Test Certificates from the original equipment manufacturer is to be provided at the time of supply of material.
22
20686
455092
P/F of Galvanized nuts bolts of various sizes as per site requirement.
60
142
8520
P/F Danger Plate with clamps on every HT pole.
22
153
3366
Providing and fixing G.I Barbed wire for anti-climbing/ anti-climbing devices. The barbed wire shall be tightly close wrapped around the pole.
22
136
2992
Supply, Installation, Testing and Commissioning of Galvanized stay set with 50 X 8 mm Stay Clamp, Guy insulator (2 No.), Anchor plate (200X200X6mm), nuts and bolts, 2 No.- turn buckle, 1.8 m long, 16 mm diameter solid G.I stay rod & 7/3.15 mm dia. G.I stranded wire complete.
6
4922
29532
Painting of poles with Red oxide.
22
306
6732
Painting of poles with Aluminum paint.
22
510
11220
Providing and fitting of ACSR as per IS 398 (part-2) 1996 for 35 sq.mm ACSR (Galvanized steel reinforced) for fitment of various accessories.
2100
36
75600
Supply, Installation, Testing and Commissioning of 35 sq mm XLPE HT cable (ABC type) of 11 KV Grade with following specifications size cross sectional area in square mm) = 3x35
phases Red, Yellow, Blue The Test Certificate of Cables duly stamped by manufacturer shall be provided at the time of supply of material.
30
818
24540
Providing and fitting of suspension/tension clamp with eye hook.
4
457
1828
Supply, Installation, Testing and Commissioning 11 KV cable termination kit for connecting 35 Sq mm ABC cable (ABC type) with the existing HT line near tapping point and HT transformer. The Test Certificates from the original equipment manufacturer is to be provided at the time of supply of material.
4
8994
35976
Providing and fitting of LT Distribution box for H.T transformer with 100 amp-4 pole, 50 KA MCCB For incomer and 80 amp SFU for outgoing circuits. The Capacity of H.T transformer is 25 KVA. All the items shall be housed in MS Box 14 swg Gauge with outdoor type mounted on substation.
1
28118
28118
P/I/T/C of LT 3 phase, 4 wire, Prodigy meter of capacity suitable for 100 KVA Substation, 415 V, 50 Hz preferably of Secure/L&T make with all accessories & fittings, cabling required as pe site requirement. the Prodigy meter shall be housed in MS water proof/dust proof enclosure with lock mounted on HT frame.
NOTE:- The job includes complete charging of subsation which includes getting clearnace from PDD and sealing of meter etc. The Test Certificates from the original equipment manufacturer is to be provided at the time of supply of material.
1
28000
28000
Fabrication, Providing and fitting of MUG 20 Modular motor control panel of appropriate size fabricated out of 14 SWG sheet having required openings/vents and protection Class : IP-55 & fitted with accessories as under:
a) Bus bar Chamber:
The bus bar chamber shall be fitted at the top of the panel horizontally throughout the length. There shall be 3 Nos. of phase bus bar and 1 No neutral bus bar and 1 No earthing bus bar. The bus bars shall be air insulated and made-up of high conductivity COPPER with current density of suitable rating for 100 Ampere. All panel compartments shall be provided with suitable cable alley and vertical bus bar alley. Suitable segregation shall be provided in between bus bar chamber and adjoining compartments. The bus bar shall be PVC sleeved with color strips of red, yellow, blue and black and the same be arranged in accordance with IS-375 specs. Electrical clearances shall be maintained between phases, neutral and body as per standards.
b) Main Circuit Breaker (Incomer D-Sine MCCB):
Qty. = 02 No.
No. of poles = 4 Pole
Current Rating : DZ1 160N, 108-160A, 50 KA
Rated operational voltage = 415 V + 15 % Rated frequency = 50+/-3%Hz Ambient temperature = 40C˚
Ultimate S.C Breaking Cap at (415V AC, 50 Hz) = 50KA = Thermal-Magnetic Overload protection = 0.8 – 1×ln adjustable Short-circuit protection = 6-10×ln adjustable.
c) Change over Switch:
Current Rating = 100A
Qty. = 01 No.
Type = Front operated, on load, 4 pole, 400 +15%V, 50 + 3%Hz.
d) Motor Back-up Protection MCCB:
Qnty = 2 No.
No. of poles = 3P
Current Rating = DN100D, 80-100A, 36KA Voltage = 415 V +15 % Rated frequency = 50 + 3% Hz
Ambient temperature = 40C˚
Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 36KA e. Submersible starters = Fully automatic star delta Capacity = 20HP MUG 20
Power Specs = 3 Ф, 415 + 15% V, 50 + 3 % Hz.
Relay range = 13-21A Coil Voltage = 380 v
Protection = single phasing, phase
Reversal, phase unbalance (55 ± 5 V), Fabrication,
Rated insulation voltage = 690V
Terminal capacity = 120 Sq. mm with lug or above Conformity to standard = IS/IES 60947-4-1
Qty. = 2 No’s
f) Auxiliary MCCB for Heating/Lighting: Circuit Breaker = MCCB (Outgoing)
Qty. = 1 No.
Current Rating = 63A at 415 V + -15 % Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 25KA
g) Motor Protection Relay:
Digital Motor Protection Relay MM10 of L&T with LCD Display for 3-phase supply with following protections suitable for the Modular Control Panel:-
Protections = Thermal Overload with pre-alarm, Short Circuit, Phase Loss, Unbalance, Phase reversal, Under Current, over current, Prolong starting, Locked Rotor, Under voltage, over voltage & Earth fault. Qty= 02 No.
h. M-power module for mobile starter for submersible motor 1P/3P 3 wire IVRS Languages – English, Hindi,
Suitable Region- North India Qty = 02 No.
i) Minelac for Over load and Under Voltage Qty= 02 No.
The panel shall be provided with phase indicator lamps (03 No.) and digital ammeter of range 0-60 A (02 No.), digital voltmeter of range 0-500 V (02 nos), and digital frequency meter (01 No). The enclosure of the panel shall be of excellent fit and finish, corrosion resistant and powder coated gliding hinges for smooth and noiseless movement of windows and advanced locking arrangements. The pannel shall be mounted on MS baseframe fabricated out of angle iron of sutable size to withstand the deadload of pannel which is included in the scope of work. MUG 20 details:-
i) Bus bar size (10 mtrx .02 mtrx 0.003 mtr) = 8960 kg/m3 = 5.38 kgs =100A ii) D-sine MCCB 4 pole (100-160A, 50KA)=02 No. iii) Change over switch Front Operated onload 100A = 01 No.
iv) D sine MCCB 3 pole (DN0 100D, 80-100, 36KA) =02 No.
v) MUG x2 (MUG 20, 13-21Amp relay) =02 No.
vi) Auxiliary MCCB 63Amp, 25 KA = 01 No. vii) MM 10 of L&T (Motor Protection) Motor Protection = 02 No. viii) Module for mobile starter =02 No.
ix) Digital Meters ,(Digital Ammeter & Digital voltmeter 02 nos each) and Digital Freq Meter 01 No.
x) Indicators LS = 03 No.
xi) Over load and Under Voltage Minlec = 02 No.
1
188581
188581
Supply, Installation, Testing and Commissioning of 25 KVA voltage stabilizer as per specifications below: Type of voltage controller: Manually operated copper wound, 3-phase, AC power supply multi step.
Type of Regulator : Double plate type with electrolytic copper contacts.
Input voltage :175-400 volts.(3 phase)
Output voltage : 415 ± 10% volts.
Frequency : 50 ±3 C/S.
Windings : Electrolytic grade copper of adequate section, vacuum impregnated and Oven-dried.
Insulation : Fiber glass insulations to tested parameters.
Cooling : Naturally, Oil cooled (ONAN)
Temp. Rise (Max) : 30°C above ambient
Mounting : On Uni-directional wheels.
Correction rate : 30 volts per step
Wave form distortion : virtually nil
Duty cycle : 100% continuous.
Enclosure : MS sheet enclosure in pressed CGR Sheet powder coated with radiators.
Core laminates : High grade, low eddy loss, grain oriented silicon steel laminations.
Load : Three phase induction motor load.
Load Amperes (continuous)
Overload in 24-hours operation: 10% above continuous Ampere rating.
The voltage stabilizer shall have T-oil level indicator gauge preferably glass type tube or otherwise visible to naked eye. The top of the container to have a display panel for housing 02 numbers Digital voltmeters (0-500V) along with 4-way selector switch and set of neon indicators for incoming and outgoing phases (06 No’s).
Insulating media (T. Oil) of 11 KVA grade to be provided and filled up to top level, with dielectric strength of 5 KV at 4m air gap. The T-Oil of specific grade should be provided in separate barrels and filled at site up to top level.
The voltage Stabilizer shall be accepted with manufacturers dully stamped test certificate and shall have name plate with specifications.
2
58040
116080
Providing and fitting of 3.5 core, XLPE, 1.1KV and 11KV grade 35 sqmm armored Aluminium cable conforming to IS : 7098 (part -1) 1988 With latest amendments as service from the HT transformer to control panel. The job includes providing and fitting of suitable rating Aluminium thimbles duly crimped and taped at conductor ends by hydraulic crimping tool. The job also includes laying of wire in air, ground or over the wall with proper supports as per the directions of site engineer.
The Test Certificate of Cables duly stamped by manufacturer shall be provided at the time of supply of material.
i) 35 sqmm, 3.5 core, LT cable
60
380
22800
Providing and fitting of 3-Core flat submersible copper cable conforming to IS: 694 (Part 1st) – 1964 & IS: 694 (Part 2nd) - 1964 for Submersible Pumping Unit and other electrical Equipment. The cable connections terminal shall be fitted with copper thimbles of required size. The main specification of the cable is given below:
Size :- 16 sqmm
The Test Certificate of Cables duly stamped by manufacturer shall be provided at the time of supply of material.
200
711
142200
Providing and fitting of 25 mm square single core copper cable for interconnecting various electrical gadets as per IS 694: 2010 along with thimbling as per requirement. The cables shall be laid in PVC conduits over the walls/ceilings ground with proper supports. The Test Certificate of Cables duly stamped by manufacturer shall be provided at the time of supply of material.
50
394
19700
Supply, Installation, Testing and Commissioning of earthing station for electric substation, LT panel and stabilizer comprising of company fabricated GI earthing electrode as per IS: 3043. The job includes Auguring of bore of required dia/depth for installation of electrode along with backfill compound mixed with soil and all other items required thereof for achieving the best result. The job includes connecting of electric gadgets through GI strip (25x3mm) as per relevant standards.
Safe earthing electrode size : 80 mm dia,
Length : 2000 mm
Back fill compound : 30 kg
6
10462
62772
Supply, installation of 6 kg Co2 type fire extinguisher manufactured as per IS:15683 OF 2006 with IS mark and comply with DGMS(Approval). The Co2 extinguisher should be suitable for class B & C fire and also for fire involving electrical equipments. the cylinder used for fire extinguisher shall be approved by protroleum and explosive safety organization (PESO) as per gas cylinder rules 2004 and as per IS: 7285 of 2004. The body should be made of seamless steel (manganese) confirming to IS:7285 with IS mark and should be provided with squeeze grip nozzle and should be filled with Co2 confirming to IS : 15222 of 2002 with certificate. The extinguisher shall be provided with manufactures test certificate and hydraulic test certificate by BIS from PESO.
2
6447
12894
Illumination of Premises:
Providing and erection of 9 Mtr long Hot Dip Galvanized octagonal pole (single Section) with bottom 150mm, top 75mm wide, thickness 3mm with 70 Microns Zinc coating having inside arrangement for providing of power connection along with following items.
1) 3 Way Terminal Connector 20 Amp.
2) 3 No MCB 8 Amp.
The job includes fabrication, providing and fitting of three arm GI structures at the top having 120˚ angle between arms and each arm having 15˚ inclination with respect to horizontal plane. Each arm should be of 2’ length and size and shape appropriate as per requirement of the luminary.
The job also includes providing and fitting of required length of flexible multi strand 2 mm copper wire from each terminal connector to each holding arm.
The pole is mounted on 1:2:4 Cement concreting of size not less than 2’x2’x6” (cost of concreting not included in the job) using 04 No anchor bolts of required size not less than 7” in length. The complete job includes earthing in GI Electrode as per relevant IS Code.
2
22226
44452
Providing, installation, testing and commissioning of area lighting 120 Watt LED (Street Light Type) on top of octagonal pole.
Having following specs:
Input: 90-240 V 50 Hz
Power Factor: 0.9
Colour Temperature: 4K - 6.5K
Beam Angle: 120˚ - 170˚
Lumens: 12000
Operating Temperature: -20˚C to 60˚C
The LED is pressure die cast aluminum housing with power coated finish and having Ingress Protection up to IP-68.
The LED is properly fitted on the arm of the pole and connected to the copper wire as provided in the high mast pole.
Suggested Make: Philips/Havells/Syska
6
9486
56916
Providing Laying and connection of 2Cx10 mm² XLPE Aluminum Armored Cable from the connector of high mast pole to the stabilizer. The job includes underground laying or overhanging along with thimbling as per requirement and directions of the site in-charge. The cables shall be laid in flexible PVC conduits over the walls/ceilings ground with proper supports.
60
162
9720
Supply, Installation, Testing and Commissioning of Junction Box with DP 32 A MCB to serve as Main switch for LED Lighting. The job includes making of connection to the circuit.
1
2227
2227
Supply, Installation, Testing And Commissioning of 2KVA fully automatic voltage stabilizer with input voltage 70-240 V and output 220 V. The stabilizer shall be installed and connected to the electric circuit as per location provided by site in charge. The job includes wall mounting of voltage stablizer over the wall using proper brackets etc.
1
8154
8154
Supply, installation, Testing & commissioning of 1000VA Full Sine wave power inverter (Make: Microtek/Luminous) including Providing / Installation of 12V, 180AH Tubular inverter Battery with trolley and cover. (Make: Amaron /Exide) with 2-core 6mm2 Cu wiring as per site requirement along with other accessories like SS-Combine (02 No’s), 3-pin plugs etc of reputed make for proper fitment and installation of the item. The job further including providing and fitting of 08 No. of lighting points including wires, conduits, switches, bulbs etc.
1
34053
34053
Providing, laying & fixing with adhesive/bonding material of insulation rubber mats on the floor of the pump house, covering area around electro-mechanical machinery for safeguarding the life & limb of the workmen due to possible leakage of current & short circuit. The floor surface shall be made good & shall be free from dust, grease, foreign material & moisture free. The mats shall be as per IS 15652:2006 & shall have the following specifications: -
Composition: Rubber (synthetic mats for electrical purpose)
Thickness: - 2.5mm, Size: - 1M wide.
The rubber mats shall be accepted with manufacturers test certificate.
10
1205
12050
TOOL KIT For Maintenance: -
The Tool Kit for maintenance shall comprise of the following and all the items as mentioned below shall be of Taparia make:
Providing of tool kit consists of following items i. Double ended Spanner (Chrome plated) of size in mm
6/7,8/9,10/11,12/13,14/15,16/17,18/19,20/22,21/23,24/26,25/28, 24/27, 30/32 make – Taparia each – 02 No. ii. double ended Ring spanners chrome plated of size in mm 6/7,8/9,10/11,12/13,14/15,16/17,18/19,20/22,21/23,24/26,25/28, 24/27, 30/32 make – Taparia each – 02 No. iii. Allen key set black finish of size in mm 1.5, 2, 2.5, 3, 4,5,6,8,10 make – Taparia each – 2 No.
iv. Combination Pliers insulated with thick C.A sleeve ; size in mm 165, 210, 255 make – taparia each – 02 No.
v. Long nose plier insulated with thick C.A sleeve ; size in mm 165, 205 make – taparia each – 02 No.
vi. Side cutting plier insulated with thick C.A sleeve ; size in mm 165, 205 make – taparia each – 02 No.
vii. Insulated screw Drivers ( make – Taparia)
Blade length in mm Blade dia. in mm Tip dimensions in mm Quantity 50 3 1.6 x 0.4 02
75 3 1.6 x0.4 02
100 3 3 x 0.4 02
125 3.5 3.5 x 0.5 02
150 3.5 3.5 x 0.5 02
200 4 4 x 0.6 02
300 5 5 x 0.8 02
viii. Hammer with handle, weight – 110 mg , 340 gm , 600 gm –each – 01 No. Make Taparia. ix. Heavy duty pipe Wrench length in mm - 200, 300, 600 each – 01 No. Make Taparia.
x. Digital multimeter – 01 No.(Fluke/Meco/scemens/Mastech)
xi. Earthing Resistance Tester - 01 No.
xii. Digital Clamp tester capable to measure up to 400A - 01 No.
xiii. Hack saw frame with hack saw blade – 01 No.
xiv. S-16 MXL, S- 16 H X L Socket Set (19 sockets + 6 Accessories) – 01 No. make Taparia
xv. Digital Altimeter - 01 No.
1
28840
28840
Fabrication of 6’ x 6’ angle iron bed by way of providing and fitting of Structural steel in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete welded.
95
105
9975
Providing and fitting of 19 mm thick multilayered ply sheet of size 6 x 3 feet, 2 Nos. including cutting, fixing all complete including painting of the play sheet by one coat of primer and two coats of enamel paint.
36
154
5544
a) Providing of good quality bedding for night stay/Shift consisting of: -
i) Mattress with warm cover size 6'x3' (6Kg)- 02 No’s
ii) Quilt with warm cover size 5'x8' (6Kg)- 02 No’s
iii) Pillows with covers - 02 No’s
iv) Single bed warm blankets with one sided Fur- 02 No’s
The filling material for mattress, quilt and pillow shall be of good quality cotton
b) The job also includes providing of pressure cooker 5ltr 02 No’s, Steel patila( utensil) 5ltrs 02 No’s, cooking heater 01 No., room heater 01 No., steel buckets 10 litre capacity 01 No., Plastic bucket 10 litre capacity with Mug 02 No’s each, steel glasses 06 No’s, steel Plates with large spoons and bowls 03 No’s each, Cup and Saucer set (01 No. Set) and, 5kg Gas cylinder with burner/ stove. All the utensils shall be of Prestige, Pigeon, Wonder chef, United, Futura make.
The job also includes providing of thermo-cool 15’x12’ along with excel matting of 15’x12’ size. The job also includes providing of unbreakable Plastic Chair table set consisting of chairs 04 No’s, extra heavy Table 01 No. of Samruddhi/ Neel kamal/Supreme /Anmol Make. The job also includes providing of good quality safety Door locks (03 No’s) of Godrej, Link locks, Thapar make.
1
39619
39619
Providing of solar/electrical lantern chargeable on both solar & electrical 220v supply. The solar lantern is to be provided with solar panel also along with allied wires.
1
1911
1911
Providing of bamboo ladders 18 feet long along with 15 feet long Link rods and HT Glove pair (01 No each) of reputed make with test certificate.
1
7350
7350
Providing of 2 KW heat convector for operators for winter season.
2
1205
2410
Providing of 12 V, capacity 200 AH battery charger of reputed make for operators for winter.
1
3500
3500
Providing and fitting of electric ceiling fan 1200mm copper wound of standard make with wiring, dimmer etc, all complete job.
2
1900
3800
Providing and fitting of 01 No. angle iron/sheet metal board duly painted showing various specifications of the mechanical and electrical equipments installed at site. Size: 4’×6’ out MS ANGLE OF 40 X 40 X 5 of 36 rft and MS sheet of 1 mm thick total weight of 50.16 kgs. The details shall include details of various electro-mechanical equipments installed in the WSS along with name of department etc.
24
250
6000
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements