Public Health Engineering Department Tender
Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Public Health Engineering Department - PHED Tender
Machinery and Tools
Eprocure
Opening Date18 Nov 2023
Closing Date28 Mar 2024
Tender Amount₹ 49,45,732
Costs
EMD
₹ 98,915Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_PHE_237346_12Tender No
JSD/PHE/MDSA/ e-NIT No. 33Tender Authority
Public Health Engineering Department ViewPurchaser Address
-Website
http://jktenders.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Earth work in excavation by mechanical means (Hydraulic Excavator) in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed: All kinds of soil- 1m from cutting edge.
The job includes earth work of HT Poles, Gantry etc
200
51370
256.85
... More
Filling available excavated earth in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by reaming and watering, lead upto 50 m and lift upto 1.5m.
160
34944
218.4
... More
Providing and laying of stone soling including manual compaction.
3
2220
740
... More
Centering and shuttering including strutting, propping etc. and removal of form work for Foundation, footings, bases for columns.
18
5154
286.35
... More
Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering, all work upto plinth level with 1: 2 : 4 mix (1 cement , 2 coarse sand , 4 graded stone aggregate 20 mm nominal size)
The job includes CC for DG Set Shed, HT Poles, Gantry etc.
8.96
59057
6591.25
... More
Fabrication, providing and fitting of washout Tee. The Tee shall be fabricated out of G.I C-class pipe with M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) fastened with weld joints on three ends. The size of the Tee is given Below:
Size : DN 80 MM Class: C (Heavy)
3
13731
4577
... More
Supply, Installation, Testing And Commissioning of Ductile Iron double flanged, non-rising spindle Resilient seated gate/ sluice valves (PN16) in accordance with BS 5163 part 1 and part 2 / EN 1074 Part 1 & 2/ IS 14846 for regulating the water supply outside the pumping units. The body and bonnet of the valve shall be of ductile iron, wedge with fully vulcanized EPDM rubber (Approved for drinking water) and NBR seal. The Gate/Sluice valve shall be compatible for buried applications and shall be safe to install in both horizontal and vertical positions. It shall have electrostatic epoxy coating (approved for drinking water) both inside and outside of the valve. The valve shall be supplied along with hand wheel.
Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work.
The job includes providing and fitting of 02 nos. M.S flanges perfectly adaptable to the inbuilt flanges of the valve which shall be fitted with rising main of the pumping unit at appropriate spots as per site requirement. The job includes the cost on account of P/F of nuts, bolts and gasket required for the job. Material of Construction
• Body: Ductile iron EN-GJS-400-15 / GJS-500-7 (GGG-40/GGG-50)
• Bonnet: Ductile iron EN-GJS-400-15/ GJS-500-7 GGG-40/GGG-50)
• Bonnet bolts: Stainless steel A2 (DIN EN ISO 3506)
• Stem Nut : Brass
• Check valve disk: Ductile iron EN-GJS-400-15/ GJS-500-7 (GGG-40/GGG-50)encapsulated with EPDM vulcanize
Suggested Make: AVK/ VAG/ Sigma Flow/ Talis
The Test Certificates of Sluice/Gate Valves mentioning the Material of Construction as above duly stamped by OEM shall be provided at the time of supply of material.
Size: DN 80 mm Rating: PN 16
3
46491
15497
... More
Supply, Installation, Testing And Commissioning of Ductile Iron double flanged, Slanted seat swing check valve (NRV) (PN16) as per EN 1074- Part -3 / BS 5153/IS 5312. The body shall be of ductile cast iron with fully encapsulated vulcanized EPDM rubber (Approved for drinking water). The valve shall be compatible for buried applications and shall be safe to install in both horizontal and vertical positions.
It shall have electrostatic epoxy coating (approved for drinking water) both inside and outside of the valve.
Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work.
The job includes providing and fitting of 02 Nos. M.S flanges perfectly adaptable to the inbuilt flanges of the valve which shall be fitted with Rising main of the pumping unit at appropriate spots as per site requirement. The job includes the cost on account of P/F of nuts, bolts and gasket required for the job. Material of Construction
• Body: Ductile iron EN-GJS-400-15 / (GGG-40) • Bonnet: Ductile iron EN-GJS-400-15/ GGG-40)
• Bonnet bolts: Stainless steel A2 (DIN EN ISO 3506) • Stem Nut : Brass
• Check valve disk: Ductile iron EN-GJS-400-15/ (GGG-40) encapsulated with EPDM vulcanized
Suggested Make: AVK/ VAG/ Sigma Flow/ Talis
The Test Certificates of Check Valves (NRVs) mentioning the Material of Construction as above duly stamped by OEM shall be provided at the time of supply of material
Size: DN 80 mm Rating: PN 16
5
87445
17489
... More
Providing, fitting, testing and commissioning of ARV (Air Release valve) (PN16) as per EN 1074 Part 4/IS 14845 to be fitted to G.I rising Main. The ARV Shall have the following specifications: -
i. Valve type - single chamber, single orifice.
ii. End connection - flanged ends to IS 1538 iii. Test pressure - body / seat 2.5 x PN
iv. Sealing ring - EPDM
v. Construction -ductile iron with stainless steel floats
vi. Coating - epoxy with corrosion resistance vii. Working temperature (-450c to 550c)
Besides the above works, The job also cost on account of P/F R.I gasket, nuts and bolts required for installation of ARV and arrangement of gas cutter/ welding set at site. Material of Construction
• Body: Ductile iron EN-GJS-400-15 (GGG-40)
• Bonnet: Ductile iron EN-GJS-400-15 (GGG-40)
• Inner parts: Stainless steel 1.4541
• Float: Stainless steel A4 (exception: DN 50 - PN 10/16 synthetic, from PN 25 of A4)
• Sealing: EPDM
• Bonnet bolts: Stainless steel A4 (DIN EN ISO 3506)
Suggested Make: AVK/ VAG/ Sigma Flow/ Talis
The Test Certificates of Air Release Valves mentioning the Material of Construction as above duly stamped by OEM shall be provided at the time of supply of material.
Size : DN 50 Rating: PN16
2
38788
19394
... More
Fabrication, Providing and fitting of 90-120 degree bend/elbow to be fabricated out of Class C GI pipe, 1 m length and flanged on both ends a to make it leak proof. The flanges shall be M.S Flanges conforming to BIS 6392/1997 Table 28 (Rating PN25) and welded on both sides. The job includes nuts, bolts, gaskets etc as per site requirement.
Size : DN 80 Class :- C (Heavy)
10
27970
2797
... More
Fabrication, providing and fitting of split type MS clamps10 mm thick, 2 ft long and 3 inch wide for lowering and holding of pumping unit fitted. The job includes the cost of required size of nuts and bolts.
Size : DN 65
2
2998
1499
... More
Fabrication of gravel Hooper for proper feeding of gravels to the bore well and platform to bear the load of pumping unit, column pipes etc by way of providing and fitting of Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. The job involves following steel details:
Size:- Top= 3 x 3 feet
Bottom = 2x2 feet
Height = 3 Feet
Thickness of Sheet= 6mm
In stringers, treads, landings etc of stair cases including use of chequered plate wherever required, all complete.
226
27300
120.8
... More
Providing and fitting of M.S 4 inch hinges 4 no and M.S handle heavy -2 no., Anchor bolts with nuts (M16) of 0.3 m long = 04 No. MS Channel 75x40 (600mm long)= 02 No.
1
2500
2500
... More
Providing, Fabrication and fitting of Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. The Structural steel is to be utilized for Fabrication of DG set Shed, Gantry, Platform and any other support required as per site requirement. The Steel may include ISMB, ISMC, ISA (Angle Iron), Chequered plate etc as per the site requirement. The drawings and Dimensions will be provided by Site In Charge at the time of execution of job.
1550
172050
111
... More
Supply, Installation and testing of motorized chain hoist with hook suspension along travelling trolley of proper specifications having following features The chain hoist shall also have the following characteristics:- Motor: The basic drive of the hoist be provided with 3 phase squired cage totally enclosed induction motor having a high starting torque with class “F” insulation. The make of the motor be NGEF / SEIMNS / GEC/ Crompton and conform to IS : 325 (RPM-1500) Brake: The hoist shall have instant action, Fail to safe electromagnetic disc brake mounted on the end of the motor to ensure minimum safety and reliability when the load is held in its position as soon as the supply to the motor is switched off internally or accidentally. The adjustment & maintenance of break shall be quick and simple.
Gears: The hoist shall have precision cut super and helical gears made of alloy steel mounted on bearings and housed in a dust proof gear box. The lubrication of gears be of high viscosity and temperature for longer life of gears.
Load Chain: The load chain be made of high tensile alloy steel having wear resistance and greatest mobility. The chain should be accurately collaborated, tested and have adequate in built factor of safety for safer operation.
Load chain wheel: Specially designed, perfectly machined wheel providing correct grip of load chain made of malleable cast iron makes the hoist most safe and reliable against any failure.
Lifting Hook: The lifting hook shall be forged with provision for free swiveling. Limit Switch: The limit switch shall have snap action, shunt type prevent over hoisting or over lowering to ensure maximum safety of operation.
Control: The unit shall be controlled by heavy duty air break direction reversing type bidders and electrically inter – locked for safety. Contactors relay, fuses, low voltage transformer be fitted for control voltage and are to be housed in fabricated / pressed sheet steel box dust proof.
Push button pendent: The contactors shall be operated by a pendent push button station suspended from hoist by a rope / dog chain to prevent any damage to the pendent cable and for easy operation.
Test: The hoist supplied is to be tested at 25% overload and the test certificate of the same be provided at the time of installation. The complete unit as specified above is required to be fitted / tested at site. Besides the above works the job Includes Providing and fitting 3-Core 6 sq. mm ,50 m submersible cable for providing power supply to motor of chain Hoist including P/F protection device of suitable capacity. The main specifications of the chain Hoist are given below:
Capacity = 3 ton Hoisting speed = 2.4 M/Min
Hoist motor H.P = as per requirement No. Of chain falls = 4
Min. Height of lift = 6 M Suggested Make: Indeff/ Pull Lift
1
161700
161700
... More
Supply, Installation, Testing And Commissioning of outdoor type Electric Sub Station as per the technical specifications given here under -
Specifications conforming to IS: 1180 (Part 1) 2014 with latest amendments.
Type: HT/LT Transformer (Level-2)
Capacity:- 100 KVA
Type of cooling: ONAN.
Operating conditions:
Input =11000 volts
Output = 433 volts AC supply in 3- phase.
Terminals:
Input=3 No. HT Brass bush rods with insulators, washer, nuts etc.
Output=4 No. LT Brass bush rods switch insulators, washers, nuts etc.
Core: The core shall be of high permeability to reduce core losses and the strips shall be of suitable size and gauge. Transformer Coils: Suitable number of HT and LT coils in each leg of the core. The transformer coils shall be fabricated out of superior quality aluminum wire/strips, properly wound. The HT transformer is completely filled with suitable grade transformer oil up to required level. The job includes carriage, and all leads and lifts involved.
The HT transformer shall be of reputed make from an ISO certified company as per relevant standards and a test certificate shall be provided before installation. The transformer shall also be provided with breather fill with silica jel crystals, conservator with oil level indicator, explosion vent and adequate radiator fins/ Tubes. The impedance of transformer shall be as per IS: 1180 (Part 1) 2014 with latest amendments. Suggested Make: Servokon/ AE/ Electricfield/ALBA
NOTE: The scope of the work shall include obtaining of necessary inspection/clearance certificate from the concerned department for all the required equipment.
1
209945
209945
... More
Providing and fitting G.I Channel /Angle/ Flat of sizes including clamps. The job includes fitting of Channels on two poles for the installation of insulators and safety devices, GO Set, Lighting Arrestor etc. It also includes the channels for fitting of LT Meter and LT Distribution Box. The job includes P/F of GI channels at Tapping point for installation of GO Link Set, Pin Insulators Etc as per site requirement
Size of Channel= ISMC 75X40MM & ISMC 100x40mm
500
61500
123
... More
Supply, Installation, Testing and commissioning of 02 No. Polymeric Gang operated Air break switch, outdoor type, triple pole, suitable for vertical installation, single break provided with locking arrangement at both ON and OFF position consisting of HT pole double insulator, copper or copper alloy high pressure heavy contact assembly, rod with bearings, operating handle and 32mm dia. GI pipe conforming to IS 1818 1961, 06 No. of insulators, rated voltage 11KV 200A complete as per IS specs. The 11 KV AB switches shall conform to IS: 9920 (Part-I to IV).
01 No. GO Set is to be fitted at tapping point and 01 No at HT Transformer (Substation).
Testing/Inspection Certificate as per IS 9921 Part IV is mandatory and is to be produced at the time of supply of material.
2
23460
11730
... More
Supply, Installation, Testing and commissioning of 11KV polymer fuses Set Horn Gap 3-phase 200 A suitable for vertical installation.
1
4983
4983
... More
Supply, Installation, Testing and commissioning of Gapless Surge arrestor station class, 10KA, 9KV, LA With polymer housing, Station Type.
1
7754
7754
... More
Supply and fitting of 11 KV polymeric composite pin insulator 12 KV, 5KN, Lighting impulse 75KV Positive, and 80 KV Negative, creepage distance 320 mm.
42
14364
342
... More
Supply, installation, erection, Testing And Commissioning of 9 mtrs long H.T Steel Tubular pole of specifications ST- 410 (SP-33). The job further includes drilling of holes for installation of various accessories, wherever required the job further includes G.I wire earthing of pole as per REC standard. The tubular steel poles shall conform to the latest edition of Indian Standard specification IS: 2713 (Part – I, III): 1980 The materials used in construction of tubular steel poles shall be of the tested quality of steels of minimum tensile strength 540 MPa. The Poles shall be fitted with base plate as per above standard. strength 540 MPa. The Poles shall be fitted with base plate as per above standard. The poles shall be applied with Red Oxide Primer and two coats of anti-corrosive Red paint at bottom up to the length of 4M and two coats of paint of silver shade for the rest.
14
289604
20686
... More
P/F of Galvanized nuts bolts of various sizes as per site requirement.
32
4544
142
... More
P/F Danger Plate with clamps on every HT pole.
12
1836
153
... More
Providing and fixing G.I Barbed wire for anti-climbing/ anti-climbing devices. The barbed wire shall be tightly close wrapped around the pole for 10-12 turns, commencing at 2.50m above the datum line.
32
4352
136
... More
Providing and Fitting of PG Clamps.
4
1684
421
... More
Supply, Installation, Testing And Commissioning of Galvanized stay set with 50 X 8 mm Stay Clamp, Guy insulator (2 No.), Anchor plate (200X200X6mm), nuts and bolts, 2 No.- turn buckle, 1.8 m long, 16 mm diameter solid G.I stay rod & 7/3.15 mm dia. G.I stranded wire complete.
4
19688
4922
... More
Providing and fitting of ACSR as per IS 398 (part-2) 1996 for 50 sq.mm ACSR (Galvanized steel reinforced) for fitment of various accessories.
900
50400
56
... More
Supply, Installation, Testing And Commissioning of 35 sq mm XLPE HT cable (ABC type) of 11 KV Grade with following specifications size cross sectional area in square mm) = 3x35+1x70 sq mm
phases Red, Yellow , Blue The Cable should conform to IS: 8130-1984, IS: 398(Part-IV)-1994, IS: 7098(Part-II)-2011 & IS: 5831-1984 with up to date amendments, if any.
The Test Certificate of Cables duly stamped by manufacturer shall be provided at the time of supply of material.
50
40900
818
... More
Supply, Installation, Testing And Commissioning 11 KV cable termination kit for connecting 35 Sq mm ABC cable (ABC type) with the existing HT line near tapping point and HT transformer.
4
35976
8994
... More
Providing and fitting of Anchoring clamps comprising clamp body, plastic wedge, steel bill bracket, straps and buckles or nuts and bolts required for holding of 3 – Core, 50 Sq. mm H.T AB Cable.
2
914
457
... More
Providing and fitting of LT Distribution box for H.T transformer with 200 amp MCCB For incomer and 100 amp SFU for outgoing circuits. The LT distribution Box is to be fitted on GI Channels.
Capacity of transformer: 100 KVA
1
39422
39422
... More
Supply, Installation, Testing And Commissioning of PRODIGY LT Meter of following specification complete with all fixtures required for fitment at site Type: 3 Phase, 4 wire Measurements offered: KWh, KVARh, KVAh, KVA
Voltage : 3x240V (415v), 50HZ
Ib : 40A Imax: 200A Battery: Lithium
The Prodigy Meter must be fitted inside the Box, that is to be fitted on GI Channels near LT Distribution Box. Both the enclosures must be symmetrical Suggested Make: Secure/ L&T
Sealing /Inspection report of Prodigy meter from JKPDCL (Concerned) is to be submitted by the firm at the time of charging of SUBSTATION.
1
28000
28000
... More
Supply, Installation, Testing And Commissioning of Modular motor control panel (MUG-40) of appropriate size fabricated out of 14 SWG sheet having required openings/vents and protection Class : IP-55 & fitted with accessories as under:
a) Bus bar Chamber:
The bus bar chamber shall be fitted at the top of the panel horizontally throughout the length. There shall be 3 Nos. of phase bus bar and 1 No neutral bus bar and 1 No earthing bus bar. The bus bars shall be air insulated and made-up of high conductivity COPPER with current density of suitable rating for 200 Ampere. All panel compartments shall be provided with suitable cable alley and vertical bus bar alley. Suitable segregation shall be provided in between bus bar chamber and adjoining compartments. The bus bar shall be PVC sleeved with color strips of red, yellow, blue and black and the same be arranged in accordance with IS-375 specs. Electrical clearances shall be maintained between phases, neutral and body as per standards.
b) Main Circuit Breaker (Incomer MCCB):
Qty. = 02
No. of poles = 4 Pole
Current Rating = 200A Rated operational voltage = 415 V ± 10 %
Rated frequency = 50 ± 3%Hz
Ambient temperature = -70C to 40 0C
Type of release = Thermal-Magnetic
Overload protection = 0.8 – 1×ln adjustable
Short-circuit protection = 6-10×ln adjustable.
Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 50kA
c) Change over Switch:
Qty. = 01 No.
Rating = 200A
Type = Front operated, on load, 4 pole, 415 +10 %V, 50 + 3%Hz.
d) Motor Back-up Protection MCCB:
Qnty = 2 No
No. of poles = 3P
Current Rating = 160A
Rated operational voltage = 415 V ± 10 %
Rated frequency = 50 ± 3% Hz
Ambient temperature = -70C to 40 0C
Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 50kA
e. Submersible starters:-= Fully automatic star delta starters.
Power Specs = 3 Ф, 415 ± 10 % V, 50 ± 3 % Hz.
Relay range = 36-60 A
Coil Voltage = 380 v Protection = single phasing , phase Reversal, phase unbalance (55 ± 5 V) ,
Conformity to standard = IS/IES 60947-4-1 Qty. = 2 No’s
f) Auxiliary MCCB for Heating/Lighting:
Circuit Breaker = MCCB (Outgoing)
Qty. = 1 No.
No. of poles = 4P
Current Rating = 63A
Rated operational voltage = 415 V ± 10 %
Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 36kA
g) Motor Protection Relay:MM10/Siemens
Digital Motor Protection Relay with LCD Display for 3-phase supply with following protections suitable for the Modular Control Panel:-
Protections = Thermal Overload with pre-alarm, Short Circuit, Phase Loss, Unbalance, Phase reversal, Under Current, Prolong starting, Locked Rotor & Earth fault. And over current Qty. = 02 No’s (01 No. for each starter)
h) M-power module for mobile starter for submersible motor 1P/3P 3 wire Quantity – 02 no. IVRS Languages – English , Hindi, Suitable Region- North India
i) Over Voltage and Under Voltage Protection relay (02No.) to be fitted separately for both starters The panel shall be provided with phase indicators (03 N0) and digital ammeter of range 0-60 A, digital voltmeter of range 0-500 V, and digital frequency meter (01 No each). The enclosure of the panel shall be of excellent fit and finish, corrosion resistant and powder coated gliding hinges for smooth and noiseless movement of windows and advanced locking arrangements. Suggested Make of accessories: L&T/Havells/Siemens/ Scheneider
1
272539
272539
... More
Supply, Installation, Testing And Commissioning of 75 KVA voltage stabilizer as per specifications below: Type of voltage controller: Manually operated copper wound, 3-phase, AC power supply multi step.
Type of Regulator : Double plate type with electrolytic copper contacts.
Input voltage :180-400 volts.(3 phase)
Output voltage : 415 ± 10% volts.
Frequency : 50 ±3 C/S.
Windings : Electrolytic grade copper of adequate section, vacuum impregnated and Oven-dried.
Insulation : Fiber glass insulations to tested parameters.
Cooling : Naturally, Oil cooled (ONAN)
Temp. Rise (Max) : 30°C above ambient
Mounting : On Uni-directional wheels.
Correction rate : 40 volts per step
Wave form distortion : virtually nil
Duty cycle : 100% continuous.
Enclosure : MS sheet enclosure in pressed CGR Sheet powder coated with radiators.
Core laminates : High grade, low eddy loss, grain oriented silicon steel laminations.
Load : Three phase induction motor load.
Load Amperes (continuous)
Overload in 24-hours operation: 10% above continuous Ampere rating.
The voltage stabilizer shall have T-oil level indicator gauge preferably glass type tube or otherwise visible to naked eye. The top of the container to have a display panel for housing 02 numbers Digital voltmeters (0-500V) along with 4-way selector switch and set of neon indicators for incoming and outgoing phases (06 No’s).
Insulating media (T. Oil) of 11 KVA grade to be provided and filled up to top level, with dielectric strength of 5 KV at 4m air gap. The T-Oil of specific grade should be provided in separate barrels and filled at site up to top level.
Suggested Make: Servokon/ AE/ Electricfield
The voltage Stabilizer shall be accepted with manufacturers dully stamped test certificate and shall have name plate with specifications.
2
327442
163721
... More
Supply, Installation, Testing And Commissioning of 3.5-Core, 2 core XLPE, 1.1KV and 11KV grade Armored Aluminum Cable of various sizes conforming to IS: 7098 part 1st as service line from the HT transformer to control panel including necessary thimbling, crimping, taping etc. Suggested Make: L&T/ Polycab /Havells
The Test Certificate of Cables duly stamped by manufacturer shall be provided at the time of supply of material.
i) 70 sqmm, 3.5 core, LT cable
60
40080
668
... More
ii) 10 sqmm, 2 core, LT cable
150
24300
162
... More
Providing and fitting of 3-Core flat submersible copper cable conforming to IS: 694 (Part 1st) – 1964 & IS: 694 (Part 2nd) - 1964 for Submersible Pumping Unit and other electrical Equipment. The cable connections terminal shall be fitted with copper thimbles of required size. The main specification of the cable is given below:
Size :- 16 sqmm
120
85320
711
... More
Supply, Installation, Testing And Commissioning of L.T, 50 sqmm 1 core, capable to work up to 1.1 KV, XLPE insulated, galvanized steel strip armored copper cable conforming to IS : 7098 (part -1) 1988 With latest amendments to be utilized for interconnection of various electrical gadgets. The job includes providing and fitting of suitable rating copper thimbles duly crimped and taped at conductor ends by hydraulic crimping tool. The job includes laying of cable in cable tray Size :- 50 sqmm Suggested Make: L&T/ Polycab /Havells
The Test Certificate of Cables duly stamped by manufacturer shall be provided at the time of supply of material.
90
70200
780
... More
Supply, Installation, Testing And Commissioning perforated cable trays including horizontal and vertical bends, tees, cross members and other accessories as required and duly bolted to walls of building with Geyser bolts including Nuts and Washers etc.
Size= 150x50x1.6mm
25
22500
900
... More
Supply, Installation, Testing And Commissioning of earthing station for electric substation, LT panel and stabilizer comprising of company fabricated GI earthing electrode as per IS: 3043. The job includes Auguring of bore of required dia/depth for installation of electrode along with backfill compound mixed with soil and all other items required thereof for achieving the best result. The job includes connecting of electric gadgets through GI strip (25x3mm) as per relevant standards.
Safe earthing electrode size : 80 mm dia,
Length : 2000 mm
Back fill compound : 30 kg
6
62772
10462
... More
Illumination of Premises:
Providing and erection of 9 Mtr long Hot Dip Galvanized octagonal pole (single Section) with bottom 150mm, top 75mm wide, thickness 3mm with 70 Microns Zinc coating having inside arrangement for providing of power connection along with following items.
1) 3 Way Terminal Connector 20 Amp.
2) 3 No MCB 8 Amp.
The job includes fabrication, providing and fitting of three arm GI structures at the top having 120˚ angle between arms and each arm having 15˚ inclination with respect to horizontal plane. Each arm should be of 2’ length and size and shape appropriate as per requirement of the luminary.
The job also includes providing and fitting of required length of flexible multi strand 2 mm copper wire from each terminal connector to each holding arm.
The pole is mounted on 1:2:4 Cement concreting of size not less than 2’x2’x6” (cost of concreting not included in the job) using 04 No anchor bolts of required size not less than 7” in length. The complete job includes earthing in GI Electrode as per relevant IS Code.
1
22226
22226
... More
Providing, installation, testing and commissioning of area lighting 120 Watt LED (Street Light Type) on top of octagonal pole.
Having following specs:
Input: 90-240 V 50 Hz
Power Factor: 0.9
Colour Temperature: 4K - 6.5K
Beam Angle: 120˚ - 170˚
Lumens: 12000
Operating Temperature: -20˚C to 60˚C
The LED is pressure die cast aluminum housing with power coated finish and having Ingress Protection up to IP-68.
The LED is properly fitted on the arm of the pole and connected to the copper wire as provided in the high mast pole.
Suggested Make: Philips/Havells/Syska
3
28458
9486
... More
Supply, Installation, Testing And Commissioning of Junction Box with DP 32 A MCB to serve as Main switch for LED Lighting. The job includes connecting the junction box to the main power supply from panel.
2
4454
2227
... More
Supply, Installation, Testing And Commissioning of 2KVA fully automatic voltage stabilizer with input voltage 70-240 V and output 220 V. The stabilizer shall be installed and connected to the electric circuit as per location provided by site in charge. The voltage stabilizer is to be connected to the heating and lighting circuit of the scheme including the street lights.
1
8154
8154
... More
Supply, installation, Testing & commissioning of 1050VA Full Sine wave power inverter including Providing / Installation of 12V, 180AH Tubular inverter Battery with trolley and cover. with 2-core 4 mm2 Cu ( 25 m) wiring as per site requirement along with other accessories like SS-Combine (02 No’s), 3-pin plugs etc of reputed make for proper fitment and installation of the item.
1
34053
34053
... More
Providing, laying & fixing with adhesive/bonding material of insulation rubber mats on the floor of the pump house, covering area around electro-mechanical machinery for safeguarding the life & limb of the workmen due to possible leakage of current & short circuit. The floor surface shall be made good & shall be free from dust, grease, foreign material & moisture free. The mats shall be as per IS 15652:2006 & shall have the following specifications: -
Composition: Rubber (synthetic mats for electrical purpose)
Thickness: - 2.5mm Size: - 1M wide.
The rubber mats shall be accepted with manufacturers test certificate.
10
12050
1205
... More
TOOL KIT For Maintenance: -
The Tool Kit for maintenance shall comprise of the following and all the items as mentioned below shall be of :
Providing of tool kit consists of following items ( Taparia /Bosch)
i. Double ended Spanner (Chrome plated) 02 sets complete
ii. Double ended Ring spanners chrome plated 02 sets complete
iii. Allen key set black finish 02 sets complete
iv. Combination Pliers insulated with thick C.A sleeve; size in mm 165, 210, 255 each – 02 No.
v. Long nose pliers insulated with thick C.A sleeve; size in mm 165, 205 each – 02 No.
vi. Side cutting pliers insulated with thick C.A sleeve; size in mm 165, 205 make – 02 No.
vii. Insulated screw Drivers ( Taparia /Bosch) Blade length Blade dia. Tip dimensions Quantity 50 3 1.6 x 0.4 02
75 3 1.6 x0.4 02
100 3 3 x 0.4 02
125 3.5 3.5 x 0.5 02
150 3.5 3.5 x 0.5 02
200 4 4 x 0.6 02
300 5 5 x 0.8 02
viii. Hammer with handle weight – 110 mg, 340 gm , 600 gm –each – 1No. . ix. Heavy duty pipe Wrench length in mm - 200, 300, 600 each – 01 No. RIGID/IRWIN/Maxpower
x. Electric Multi-meter =1No Make: Fluke /Klein
xi. Digital Clamp tester capable to measure up to 400A - 1 No. Make: Fluke /Klein xii. Hack saw frame with hack saw blade – 01 no.
xiii. S-16 MXL, S- 16 H X L Socket Set (19 sockets + 6 Accessories) – 01 No. Make: Taparia /Bosch
Tool kit Make: Taparia /Bosch
The tool kit is to be provided in tool box of Make: Taparia /Gear Wrench/ Stanley.
1
28840
28840
... More
Providing of good quality bedding for night stay/Shift consisting of: - i) Mattress with warm cover size 6'x3' (6Kg)- 02 No’s.
ii) Quilt with warm cover size 5'x8' (6Kg)- 02 No’s. iii) Pillows with covers - 02 No’s.
iv) Single bed warm blankets with one sided Fur- 02 No’s The filling material for mattress, quilt and pillow shall be of good quality cotton b) The job also includes providing of pressure cooker 5ltr 02 No’s, Steel patella(utensil) 5ltrs 02 No’s, cooking heater 01 No., room heater 01 No., steel buckets 10 litre capacity 01 No., Plastic bucket 10 litre capacity with Mug 02 No’s each, steel glasses 06 No’s, steel Plates with large spoons and bowls 03 No’s each, Cup and Saucer set (01 No. Set) and, 5kg Gas cylinder with burner/ stove. The job also includes providing of thermo-cool 15’x12’ along with excel matting of 15’x12’ size. The job also includes providing of unbreakable Plastic Chair table set consisting of chairs 04 No’s, extra heavy Table 01 No. The job also includes providing of good quality safety Door locks (03 No’s) of Godrej, Link locks.
1
39619
39619
... More
Fabrication of 7’ (L) x 6’(B) x 1.5' (H) angle iron bed for operators with back-height of 2 feet by way of providing and fitting of Structural steel in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete welded
114
11628
102
... More
Providing and fitting of 19 mm thick multilayered ply sheet of size 6 x 3 feet, 3 No’s including cutting, fixing all complete including painting of the play sheet by one coat of primer and two coats of enamel paint.
54
8316
154
... More
Providing of CP 12 5WP solar/electrical lantern chargeable on both solar & electrical 220v supply. The solar lantern is to be provided with solar plate (provided in box with lantern)
1
1911
1911
... More
Providing of 6.0 meter (20.0 ft) Foldable, portable & compact aluminum Telescopic Ladder, EN131 Certified., built from rust-proof, high-grade aluminum alloy and precise engineered HDPE components to ensure maximum corrosion resistance. It should be designed for use in all climatic and weather conditions and to enhance safety, and a strong grip even on wet surfaces. Ladder should be easy to extend and retract with storage straps, convenient to use, store and carry around. The length of step should be 40-50cm Approximately with distance of 40-50cm between steps.
1
19500
19500
... More
Providing of Industrial Rubber 11 KV Electrical Hand Shock Proof Safety Gloves for handling electrical equipments/connections.
3
2250
750
... More
Providing and fitting of 02 No. angle iron/sheet metal board duly painted showing various specifications of the mechanical and electrical equipment installed at site (01No.) and The name of water supply Scheme (01No.) of appropriate sizes. The details, drawings and specifications will be provided by Site Incharge.
45
11250
250
... More
Supply, Installation, Testing And Commissioning of OFF-Load (Side operated) Changeover Switch in Separate SS Enclosure as below Capacity:- 250Amp, 415V, 50hz
Type: OFF Load
Voltage : 415V
No of Poles: 4
Operation: Side Operated
Standard Conformity: IS / IEC: 60947 - 1&3
Suggested Make: L&T/Havells/Siemens/ Scheneider
2
46000
23000
... More
Electrification of Pump House by way of P/F of 1.5 mm sq. multi strand PVC wire for lighting points (08Nos.) and 2.5 sq.mm for heating points (04Nos.) to be laid in PVC Conduit Pipes in slab and brick walls of Pump House /as per site requirement. Lighting points should be run on Inverter also. Providing and fitting of Modular type board comprising of 6A Switch =08 No’s, 5-Pin 6A socket =04 No’s, Indicator= 02 No’s , Fan dimmer = 01No, 3-Pin 16A Switch Socket Combine =04No’s, 12 watt Slim Round Conceal Ceiling type = 08 No’s, Ceiling Fan=01 No , Main Switch board with input and output arrangement etc.
Suggested Make: L&T/Havells/Siemens/ Scheneider/GM/Anchor
1
30000
30000
... More
Providing, installation, testing and commissioning of ‘Silent type” WATER COOLED Diesel Generator set of 62.5 KVA Rating and 3 Phase. The DG Set shall be able to operate at (1800 meters ASL) efficiently without causing any malfunctioning. The DG Set shall comprise of Diesel Engine and Alternator coupled together with heavy duty flexible coupling and mounted on M. S. Base Frame along with all standard accessories, Control Panel, Battery, M. S. Canopy, duly painted and conforming to noise reduction norms as per environmental protection rules 1986 as laid down by Ministry of Environmental (Protection) and Forest, read with GSR-371(E) Dated:17-05-2002 at S. No. 95 for emissions limits and GSR-371(E) Dated:17-05-2002 at S. No. 94 (Paragraph 1 and 3) for noise limits for the DG Set and as per the latest amendments if any. The engine shall conform to IS: 10000/BS: 649/BS: 5514 amended up to date. The DG Set should be rated for continuous duty with overload provision of 10% for the period not exceeding one hour in twelve hours.
Suggested Make: Eicher/ Stamford/KOEL i-Green
A) ALTERNATOR:- Suggested Make: CG/ Stamford/KOEL i-Green
The alternator shall be self-excited, self-regulated for 62.5 KVA rating and shall be brushless, continuous duty. The alternator shall be screen protected drip proof enclosure, and horizontal foot mounted in double bearing construction. The alternator shall conform to IS-4722 / IEC-34/BS2613
a) Rated Output : 62.5 KVA (At 1800mtrs ASL)
b) Rated Speed : 1500 RPM
c) Efficiency at full load 0.8 P.f. = Not less than 86.00% or as per relevant IS code.
d) total distortion factor = less than 3%
e) Voltage : 415 V at 50 Hz
f) Class of Insulation : H
g) Enclosure: IP 23.
h) Governor = Electronic
Standards:
The alternators shall be in accordance with the following standards as are applicable a. IS-4722/IS-2613:1970. The performance of rotating electrical machines.
b. IS-4889/BS 269 rules for method of declaring of efficiency of electrical machines.
B). DIESEL ENGINE (Prime Mover)
Suggested Make: CG/ Stamford/KOEL i-Green/Eicher
The Prime Mover shall be diesel driven to develop requisite BHP as per ISO-8528-part- I at 1500 RPM for the alternator rated as above with ambient temperature ranging from -10C to +45C with 70% humidity.
a) Speed :1500 RPM
c) Cooling System : Water cooled
d) Method of Start: Electric Start with a Key.
e) Rated BHP : Suitable for 62.5.00 KVA rating output at 1800mtrs ASL as per ISO-8528-part- I
The engine shall be fitted with following accessories:-
1) Fuel Tank:
The capacity of the fuel tank shall be so as to last for 12 hours of continuous running on full load. The fuel tank shall be mounted on an angle iron frame of suitable height and fabricated out of M.S. Sheet of 4 mm Thickness duly painted and fitted with connections for inlet, outlet and return and also to be provided with air vent, drain with valve, level indicator and fuel pipes complete in all respects.
2) Battery:
Battery suitable for above capacity DG set. 3) Starting System
Providing and Fitting of Terminals, Leads, C/W Charging Dynamo and fitted with 12 Volt Starting System. The system shall be able of starting of DG set with 20-30 Sec even in winter conditions with ambient temp down to -50C
4) Engine Instrument Panel:
The Engine Instrument Panel shall be fitted with starting switch with keys, Lube Oil Gauge, Temperature & Pressure Gauge, Speedometer, Kilowatt Hour Meter etc and all other accessories as required.
5) Safety Control:
The D. G. Set shall be provided & fitted with all the safety controls i.e. for Low lube oil Pressure indication switch, High water temperature indication, RPM indication, water temperature indication, battery charging indication etc.
C. Standard Control Panel:
The Control Panel shall be fabricated out of steel sheet 1.5 mm thick duly pre-treated and aesthetically finished. It shall be totally enclosed, dust, vermin proof with IP-53 degree of protection as per IS 2147-62. The panel shall consist of following instruments:
a) 0 – 600 V, AC Voltmeter of class 1.5 accuracy with phase selector switch
b) A.C. Ammeter of Class 1.5 accuracy.
c) HRC Fuses of required rating.
d) One No MCCB of required rating.
e) Frequency Meter.
f) Power factor meter.
g) Pilot Lamps
h) Energy Metre
i) Push Button Switch for ON-OFF operation.
All the above components shall be properly mounted duly wired and shall be of reputed make.
D) Canopy:
The Canopy of the D. G. Set shall be fabricated out of M. S. Sheet of required gauge so as to withstand the snow load etc, duly painted. The Canopy shall be as per the Norms of the as laid down in the environmental protection rules 1986 of Ministry of Environmental (Protection) and Forest, read with GSR-371(E) Dated:17-05-2002 at S.No 95 for emissions limits and GSR-371(E) Dated:17-05-2002 at S.No 94 (Paragraph 1 and 3) for noise limits for the DG Set and as per the latest amendments if any.
The following jobs are also included in the scope of work:
The job includes providing of 50 ltrs of HSD for initial testing of DG set at site.
1
715670
715670
... More
Supply, Installation, Testing And Commissioning of L.T, 1 core , capable to work up to 1.1 KV , XLPE insulated , galvanized steel strip armored copper cable conforming to IS : 7098(part -1) 1988 With latest amendments to be fitted from D.G Set to Modular control panel . The job includes providing and fitting of suitable rating copper thimbles duly crimped and taped at conductor ends by hydraulic crimping tool. The job includes earth work in excavation wherever required for laying of cable underground.
Size:- 50 sqmm
Suggested Make: L&T/ Polycab /Havells
90
70200
780
... More
Providing, Installation, Testing & Commissioning of complete switchgear unit for protection of D.G Set consisting of 200A MCCB 3- pole , 415 V, 50 KV breaking capacity housed properly in cubical enclosure made up of M.S SWG – 16 sheet steel (outdoor type) duly powder painted with anti-corrosive paint comprising of three compartments for incoming / outgoing circuits and MCCB. The panel should have adequate double locking Arrangement with Cu-. Bus Bar 12x40 mm with Bakelite insulation and LT Arrangement selector switches, phase indicators. The equipment should be installed at appropriate height in a stand consisting of 50 x 50 x 6 mm angle grouted in ground with appropriate cement bottoming as per the IS standard.
Suggested Make: L&T/Havells/Siemens/ Scheneider
1
39422
39422
... More
Colour Coated ROOFING
Providing fitting and Installation of HI RIB Colour Coated sheet roofing including upto any pitch in horizontal vertical/curved surface fixed with polymer coated J or L hooks, bolts and nuts 8mm diameter with bitumen and limpet washers. The Roofing sheets shall be manufactured from zinc/ aluminum alloy coated high tensile steel.
Thickness of Sheet 0.50 mm (+ 0.05 %) total coated thickness with zinc coating 120 grams per sqm
Material Steel / Stainless Steel/Pre Coated GI Profile Sheets
Colour Blue/green/red/as desired by site incharge
Surface Treatment Colour Coated
Usage/Application Roofing/Walls
Manufacturing Technique Cold Rolled
68.5
58396
852.5
... More
Providing fitting and Installation of ridges or hips of 60 cm wide overall in HI RIB Colour Coated sheets fixed with polymer coated J. or L. hooks, bolts and nuts 8 mm dia G.I. limpet and bitumen washers complete. Thickness= 0.50mm
Width = 60 cm
Length= 14 feet
4.25
2936
690.85
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements