Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Public Health Engineering Department - PHED Tender
Machinery and Tools
Eprocure
Opening Date19 Jan 2024
Closing Date30 Jan 2024
Tender Amount₹ 32,79,179
Costs
EMD
₹ 65,584Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_PHE_243240_10Bid Award Id
ViewTender No
JSD/PHE/MDSA/ e-NIT No. 46Tender Authority
Public Health Engineering Department ViewPurchaser Address
-Website
http://jktenders.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Earth work in excavation by manual means in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed:
i. All kinds of soil (80%) 01 mtr from cutting edge.
30
14370
479
ii. Ordinary Rock (20%) 01 mtr from cutting edge.
30
27744
924.8
Filling available excavated earth in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by reaming and watering, lead upto 50 m and lift upto 1.5m.
54
11793
218.4
Providing and laying of stone soling including manual compaction.
6
4440
740
Centering and shuttering including strutting, propping etc. and removal of form work for Foundation, footings, bases for columns.
25
7150
286
Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering, all work upto plinth level with 1: 2 : 4 mix (1 cement , 2 coarse sand , 4 graded stone aggregate 20 mm nominal size).
25
164781
6591.25
Fabrication, providing and fitting of washout Tee, with each arm one feet long shall be fabricated out of 80 mm dia. G.I C-class pipe with 16mm thick flanges fastened with weld joints on three ends. The size of the Tee is given Below:
Size : DN 80 MM Class: C (Heavy)
1
4577
4577
Providing and fitting of PN 1.6/16 Ductile Iron double flanged, non-rising spindle soft seated glandless gate/ sluice valves as per IS14846 for regulating the water supply outside the pumping units.
The body and bonnent of the valve shall be of ductile iron, wedge with fully vulcanized EPDM rubber (Approved for drinking water) and NBR seal. The Gate/Sluice valve shall be compatible for buried applications and shall be safe to install in both horizontal and vertical positions
It shall have electrostatic epoxy coating(approved for drinking water) both inside and outside of the valve. The valve shall be supplied along with hand wheel.
Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work.
The job includes providing and fitting of 02 Nos. M.S flanges perfectly adaptable to the inbuilt flanges of the valve which shall be fitted with rising main of the pumping unit at appropriate spots as per site requirement. The job includes the cost on account of P/F of nuts, bolts and gasket required for the job. The Test Certificates of Sluice/Gate Valves mentioning the Material of Construction as above duly stamped by OEM shall be provided at the time of supply of material.
Size: DN 80 mm Rating: PN 1.6/16
3
46491
15497
Providing and fitting of DN 80 mm PN 1.6/16 Ductile Iron double flanged, Slanted seat swing check valve (NRV) as per IS 5312. The body shall be of ductile cast iron with fully encapsulated vulcanized EPDM rubber (Approved for drinking water). The valve shall be compatible for buried applications and shall be safe to install in both horizontal and vertical positions.
It shall have electrostatic epoxy coating (approved for drinking water) both inside and outside of the valve.
Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work.
The job includes providing and fitting of 02 nos. M.S flanges perfectly adaptable to the inbuilt flanges of the valve which shall be fitted with Rising main of the pumping unit at appropriate spots as per site requirement. The job includes the cost on account of P/F of nuts, bolts and gasket required for the job. The Test Certificates of Check Valves (NRVs) mentioning the Material of Construction as above duly stamped by OEM shall be provided at the time of supply of material.
Size: DN 80 mm Rating: PN 1.6/16
2
34978
17489
Fabrication, Providing and fitting of 90-120 degree bend/elbow to be fabricated out of Class B GI pipe, 1 m length and flanged on both ends a to make it leak proof. The flanges shall be M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) and welded on both sides. The job includes nuts, bolts, gaskets etc as per site requirement.
Size : DN 80 mm
6
16782
2797
Fabrication, providing and fitting of split type MS clamps 10 mm thick, 2 ft long and 3 inch wide for lowering and holding of pumping unit fitted. The job includes the cost of required size of nuts and bolts.
Size : DN 80 mm
2
3602
1801
Fabrication of MS Gantry mechanism by way of providing Structural steel in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer and two coats of enamel paint of approved shade complete in all aspects. The detailed drawing shall be provided by the site incharge at the time of execution of work.
800
88800
111
Providing, installation and testing of manual type triple spur gear chain pulley block along with monorail geared travelling trolley having following features
Gears:- The hoist shall have precision machine case Hardened alloy steel gear mounted on bearings and housed in a dust proof gear box. The lubrication of gears should be of high viscosity and temperature for longer life of gears.
Load Chain:- The load chain be made of high tensile alloy steel having wear resistance and greatest mobility. The chain should be accurately collaborated, tested and have adequate in built factor of safety for safer operation.
Load chain wheel:- the load chain well should be double ball bearing supported and Specially designed, perfectly machined wheel providing correct grip of load chain to makes the hoist most safe and reliable against any failure. The main specifications of C.P Block are given below : Make = Reputed make Capacity = 2 ton (P)
No. Of load chain falls = 2 or above
Min. Height of lift = 6 M
Test certificate of Manufacturer to be appended.
1
44473
44473
Supply, Installation, Testing and Commissioning of outdoor type 63 KVA Electric Sub Station as per the technical specifications given here under -
Specifications conforming to IS: 1180 (Part 1) 2014 with latest amendments.
Type: HT/LT Transformer (Energy Level-2 with biometallic terminal conductors)
Type of cooling: ONAN.
Operating conditions:
Input =11000 volts
Output = 433 volts AC supply in 3- phase.
Terminals:
Input=3 No. HT Brass bush rods with insulators, washer, nuts etc.
Output=4 No. LT Brass bush rods switch insulators, washers, nuts etc.
Core: The core shall be of high permeability to reduce core losses and the strips shall be of suitable size and gauge. Transformer Coils: Suitable number of HT and LT coils in each leg of the core. The transformer coils shall be fabricated out of superior quality aluminum wire/strips, properly wound. The HT transformer is completely filled with suitable grade transformer oil up to required level. The job includes carriage, and all leads and lifts involved.
The HT transformer shall be of reputed make from an ISO certified company as per relevant standards and a test certificate shall be provided before installation. The transformer shall also be provided with breather fill with silica jel crystals, conservator with oil level indicator, explosion vent and adequate radiator fins/ Tubes. The impedance of transformer shall be as per IS: 1180 (Part 1) 2014 with latest amendments. NOTE: The scope of the work shall include obtaining of necessary inspection/clearance certificate from the concerned department for all the required equipment. The testing and commissioning shall be completed only after obtaining above certificate. Testing certificates from the original equipment manufacturer is to be submitted at the time of supply of material.
1
171963
171963
Providing and fitting G.I Channel /Angle/ Flat of sizes including clamps, v-cross and f-top
400
49200
123
Supply, Installation, Testing and commissioning of Polymeric Gang operated Air break switch, outdoor type, triple pole, suitable for vertical installation, single break provided with locking arrangement at both ON and OFF position consisting of HT post double insulator, copper or copper alloy high pressure heavy contact assembly, rod with bearings , operating handle and 2 length of 32mm dia. GI pipe conforming to IS 1818 1961, 06 No. of insulators, rated voltage 11KV 200A complete as per IS specs.
2
23460
11730
Supply, Installation, Testing and commissioning of 11KV polymer fuses Set Horn Gap 3-phase 200 A suitable for vertical installation.
1
4983
4983
Supply, Installation, Testing and commissioning of Gapless Surge arrestor station class, 10KA, 9KV, LA With polymer housing, Station Type.
1
7754
7754
Supply and fitting of 11 KV polymeric composite pin insulator 12 KV, 5KN, Lighting impulse 75KV Positive, and 80 KV Negative, creepage distance 320 mm.
18
6246
347
Supply and fitting of 11 KV polymeric composite disc insulator 12 KV, min. falling load 45KN, Lighting impulse 75KV Positive, and 80 KV Negative, creepage distance 320 mm.
6
2082
347
Supply, installation, erection, testing and commissioning of 9 mtrs long H.T Steel Tubular pole of specifications ST- 410 (SP-33). The job further includes drilling of holes for installation of various accessories, wherever required the job further includes G.I wire earthing of pole as per REC standard.
8
165488
20686
P/F of Galvanized nuts bolts of various sizes as per site requirement.
35
4970
142
P/F Danger Plate with clamps on every HT pole.
8
1224
153
Providing and fixing G.I Barbed wire for anti-climbing/ anti-climbing devices. The barbed wire shall be tightly close wrapped around the pole.
16
2176
136
Supply, Installation, Testing And Commissioning of Galvanized stay set with 50 X 8 mm Stay Clamp, Guy insulator (2 No.), Anchor plate (200X200X6mm), nuts and bolts, 2 No.- turn buckle, 1.8 m long, 16 mm diameter solid G.I stay rod & 7/3.15 mm dia. G.I stranded wire complete.
4
19688
4922
Painting of poles with Red oxide.
8
2448
306
Painting of poles with Aluminum paint.
8
4080
510
Providing and fitting of ACSR as per IS 398 (part-2) 1996 for 50 sq.mm ACSR (Galvanized steel reinforced) for fitment of various accessories.
30
1680
56
Supply, Installation, Testing And Commissioning of 35 sq mm XLPE HT cable (ABC type) of 11 KV Grade with following specifications Size (cross sectional area in square mm) = 3x35
Phases: Red, Yellow, Blue The Test Certificate from the original manufacturer is to be submitted at the time of supply of material.
200
163600
818
Providing and fitting of suspension/tension clamps with eye hook.
10
4570
457
Supply, Installation, Testing And Commissioning 11 KV cable termination kit for connecting 35 Sq mm ABC cable (ABC type) with the existing HT line near tapping point and HT transformer.
4
35976
8994
Providing and fitting of LT Distribution box for H.T transformer with 200 amp MCCB For incomer and 100 amp SFU for outgoing circuits. The LT distribution Box is to be fitted on GI Channels.
Capacity of transformer: 63 KVA
1
28118
28118
P/I/T/C of LT 3 phase, 4 wire, Prodigy meter of capacity suitable for 100 KVA Substation, 415 V, 50 Hz preferably of Secure make with all accessories & fittings, cabling required as pe site requirement. The prodigy meter shall be housed in MS water proof/dust proof enlosure with lock mounted on HT frame. NOTE:- The job includes complete charging of subsation which includes getting clearnace from PDD and sealing of meter etc.
1
28000
28000
Fabrication, Providing and fitting of MUG 20 Modular motor control panel of appropriate size fabricated out of 14 SWG sheet having required openings/vents and protection Class : IP-55 & fitted with accessories as under:
a) Bus bar Chamber:
The bus bar chamber shall be fitted at the top of the panel horizontally throughout the length. There shall be 3 Nos. of phase bus bar and 1 No neutral bus bar and 1 No earthing bus bar. The bus bars shall be air insulated and made-up of high conductivity COPPER with current density of suitable rating for 100 Ampere. All panel compartments shall be provided with suitable cable alley and vertical bus bar alley. Suitable segregation shall be provided in between bus bar chamber and adjoining compartments. The bus bar shall be PVC sleeved with color strips of red, yellow, blue and black and the same be arranged in accordance with IS-375 specs. Electrical clearances shall be maintained between phases, neutral and body as per standards.
b) Main Circuit Breaker (Incomer D-Sine MCCB):
Qty. = 02 No.
No. of poles = 4 Pole
Current Rating : (DZ1 160N, 108-160 A, 50KA)
Rated operational voltage = 415 V + 15 % Rated frequency = 50+/-3%Hz Ambient temperature = 40C˚
Ultimate S.C Breaking Cap at (415V AC, 50 Hz) = 50KA Thermal-Magnetic Overload protection = 0.8 – 1×ln adjustable Short-circuit protection = 6-10×ln adjustable.
c) Change over Switch:
Current Rating = 100A
Qty. = 01 No.
Type = Front operated, on load, 4 pole, 400 +15%V, 50 + 3%Hz.
d) Motor Back-up Protection MCCB:
Qnty = 2 No No. of poles = 3P
Current Rating = DN0 100D, 80-100A, 36KA Voltage = 415 V +15 % Rated frequency = 50 + 3% Hz
Ambient temperature = 40C˚
Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 36KA e. Submersible starters: Fully automatic star delta
Capacity = 20 HP MUG-20
Power Specs = 3 Ф, 415 + 15% V, 50 + 3 % Hz.
Relay range = 20-32A Coil Voltage = 380 v
Protection = single phasing, phase
Reversal, phase unbalance (55 ± 5 V), Fabrication,
Rated insulation voltage = 690V
Terminal capacity = 120 Sq. mm with lug or above Conformity to standard = IS/IES 60947-4-1
Qty. = 2 No’s
f) Auxiliary MCCB for Heating/Lighting: Circuit Breaker = MCCB (Outgoing)
Qty. = 1 No.
Current Rating = 63A at 415 V + -15 % Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 25KA
g) Motor Protection Relay:
Digital Motor Protection Relay MM10 of L&T with LCD Display for 3-phase supply with following protections suitable for the Modular Control Panel:-
Protections = Thermal Overload with pre-alarm, Short Circuit, Phase Loss, Unbalance, Phase reversal, Under Current, over current, Prolong starting, Locked Rotor, Under voltage, over voltage & Earth fault. Qty= 02 No.
h. M-power module for mobile starter for submersible motor 1P/3P 3 wire IVRS Languages – English, Hindi,
Suitable Region- North India Qty = 02 No.
i) Minelac for Over load and Under Voltage Qty= 02 No.
The panel shall be provided with phase indicator lamps (03 No.) and digital ammeter of range 0-60 A (02 No.), digital voltmeter of range 0-500 V (02 Nos.), and digital frequency meter (01 No). The enclosure of the panel shall be of excellent fit and finish, corrosion resistant and powder coated gliding hinges for smooth and noiseless movement of windows and advanced locking arrangements. The pannel shall be mounted on MS baseframe fabricated out of angle iron of sutable size to withstand the deadload of pannel which is included in the scope of work. MUG 20 Modular Panel details/description item wise
i) Bus bar size (10 mtrx .02 mtrx 0.003 mtr=8960 kg/m3 =5.38 kgs = 100A ii) D-sine MCCB 4 pole (100, 50KA) = 02 No. iii) Change over switch Front Operated onload 100A = 01 No.
iv) D sine MCCB 3 pole (80-100 36KA) = 02 No.
v) MUG x 2 (MUG-20, 20-32 Amp relay) = 02 No.
vi) Auxiliary MCCB 63 Amp, 25 KA =1 No. vii) MM 10 of L&T (Motor Protection) Motor Protection =02 No. viii) Module for mobile starter =02 No.
ix) Meters ,(Ammeter & voltmeter 02 Nos. each) and Freq Meter 01 No.
x) Indicators LS = 03 No.
xi) Over load and Under Voltage Minlec = 02 No.
1
188581
188581
Supply, Installation, Testing and Commissioning of 30 KVA voltage stabilizer as per specifications below: Type of voltage controller: Manually operated copper wound, 3-phase, AC power supply multi step.
Type of Regulator : Double plate type with electrolytic copper contacts.
Input voltage :180-400 volts.(3 phase)
Output voltage : 415 ± 10% volts.
Frequency : 50 ±3 C/S.
Windings : Electrolytic grade copper of adequate section, vacuum impregnated and Oven-dried.
Insulation : Fiber glass insulations to tested parameters.
Cooling : Naturally, Oil cooled (ONAN)
Temp. Rise (Max) : 30°C above ambient
Mounting : On Uni-directional wheels.
Correction rate : 30 volts per step
Wave form distortion : virtually nil
Duty cycle : 100% continuous.
Enclosure : MS sheet enclosure in pressed CGR Sheet powder coated with radiators.
Core laminates : High grade, low eddy loss, grain oriented silicon steel laminations.
Load : Three phase induction motor load.
Load Amperes (continuous)
Overload in 24-hours operation: 10% above continuous Ampere rating.
The voltage stabilizer shall have T-oil level indicator gauge preferably glass type tube or otherwise visible to naked eye. The top of the container to have a display panel for housing 02 numbers Digital voltmeters (0-500V) along with 4-way selector switch and set of neon indicators for incoming and outgoing phases (06 No’s).
Insulating media (T. Oil) of 11 KVA grade to be provided and filled up to top level, with dielectric strength of 5 KV at 4m air gap. The T-Oil of specific grade should be provided in separate barrels and filled at site up to top level.
The voltage Stabilizer shall be accepted with manufacturers dully stamped test certificate and shall have name plate with specifications.
2
136216
68108
Providing and fitting of 35 sqmm 3.5 core, capable to work up to 1.1 KV, XLPE insulated, galvanized steel strip armored Aluminium cable conforming to IS : 7098 (part -1) 1988 With latest amendments, as service line from HT Transformer to control panel. The job includes providing and fitting of suitable rating Aluminium thimbles duly crimped and taped at conductor ends by hydraulic crimping tool. The cable shall be laid in air, ground/burried or over the wall with proper supports as per the directions of site engineer.
The Test Certificate of Cables duly stamped by manufacturer shall be provided at the time of supply of material.
i) 35 sqmm, 3.5 core, LT cable
120
45600
380
Providing and fitting of 3-Core flat submersible copper cable conforming to IS: 694 (Part 1st) – 1964 & IS: 694 (Part 2nd) - 1964 for Submersible Pumping Unit and other electrical Equipment. The cable connections terminal shall be fitted with copper thimbles of required size. Size :- 16 sqmm
270
191970
711
Providing and fitting of 25 mm square single core copper cable for interconnecting various electrical gadets as per IS 694: 2010 along with thimbling as per requirement. The cables shall be laid in PVC conduits over the walls/ceiling ground with proper supports.
180
70920
394
Supply, Installation, Testing and Commissioning of earthing station for electric substation, LT panel and stabilizer comprising of company fabricated GI earthing electrode as per IS: 3043. The job includes Auguring of bore of required dia/depth for installation of electrode along with backfill compound mixed with soil and all other items required thereof for achieving the best result. The job includes connecting of electric gadgets through GI strip (25x3mm) as per relevant standards.
Safe earthing electrode size : 80 mm dia,
Length : 2000 mm
Back fill compound : 30 kg
6
62772
10462
Supply, installation of 6 kg Co2 type fire extinguisher manufactured as per IS:15683 OF 2006 with IS mark and comply with DGMS(Approval). The Co2 extinguisher should be suitable for class B & C fire and also for fire involving electrical equipments. the cylinder used for fire extinguisher shall be approved by protroleum and explosive safety organization (PESO) as per gas cylinder rules 2004 and as per IS: 7285 of 2004. The body should be made of seamless steel (manganese) confirming to IS:7285 with IS mark and should be provided with squeeze grip nozzle and should be filled with Co2 confirming to IS : 15222 of 2002 with certificate. The extinguisher shall be provided with manufactures test certificate and hydraulic test certificate by BIS from PESO.
2
12894
6447
Illumination of Premises:
Providing and erection of 9 Mtr long Hot Dip Galvanized octagonal pole (single Section) with bottom 150mm, top 75mm wide, thickness 3mm with 70 Microns Zinc coating having inside arrangement for providing of power connection along with following items.
1) 3 Way Terminal Connector 20 Amp.
2) 3 No MCB 8 Amp.
The job includes fabrication, providing and fitting of three arm GI structures at the top having 120˚ angle between arms and each arm having 15˚ inclination with respect to horizontal plane. Each arm should be of 2’ length and size and shape appropriate as per requirement of the luminary.
The job also includes providing and fitting of required length of flexible multi strand 2 mm copper wire from each terminal connector to each holding arm.
The pole is mounted on 1:2:4 Cement concreting of size not less than 2’x2’x6” (cost of concreting not included in the job) using 04 No anchor bolts of required size not less than 7” in length. The complete job includes earthing in GI Electrode as per relevant IS Code.
1
22226
22226
Providing, installation, testing and commissioning of area lighting 120 Watt LED (Street Light Type) on top of octagonal pole.
Having following specs:
Input: 90-240 V 50 Hz
Power Factor: 0.9
Colour Temperature: 4K - 6.5K
Beam Angle: 120˚ - 170˚
Lumens: 12000
Operating Temperature: -20˚C to 60˚C
The LED is pressure die cast aluminum housing with power coated finish and having Ingress Protection up to IP-68.
The LED is properly fitted on the arm of the pole and connected to the copper wire as provided in the high mast pole.
Suggested Make: Philips/Havells/Syska
3
28458
9486
Providing Laying and connection of 2Cx10 mm² XLPE Aluminum Armored Cable from the connector of high mast pole to the stabilizer. The job includes underground laying or overhanging along with thimbling as per requirement and directions of the site in-charge. The cables shall be laid in PVC conduits over the walls/ceiling ground with proper supports.
70
11340
162
Supply, Installation, Testing and Commissioning of Junction Box with DP 32 A MCB to serve as Main switch for LED Lighting. The job includes connecting the junction box to the main power supply from panel.
1
2227
2227
Supply, Installation, Testing And Commissioning of 2KVA fully automatic voltage stabilizer with input voltage 70-240 V and output 220 V. The stabilizer shall be installed and connected to the electric circuit as per location provided by site in charge. The voltage stabilizer is to be connected to the heating and lighting circuit of the scheme including the street lights.
1
8154
8154
Supply, installation, Testing & commissioning of 1000VA Full Sine wave power inverter including Providing / Installation of 12V, 180AH Tubular inverter Battery with trolley and cover, with 2-core 6mm2 Cu wiring as per site requirement along with other accessories like SS-Combine (02 No’s), 3-pin plugs etc of reputed make for proper fitment and installation of the item.
1
34053
34053
Providing, laying & fixing with adhesive/bonding material of insulation rubber mats on the floor of the pump house, covering area around electro-mechanical machinery for safeguarding the life & limb of the workmen due to possible leakage of current & short circuit. The floor surface shall be made good & shall be free from dust, grease, foreign material & moisture free. The mats shall be as per IS 15652:2006 & shall have the following specifications: -
Composition: Rubber (synthetic mats for electrical purpose)
Thickness: - 2.5mm Size: - 1M wide.
The rubber mats shall be accepted with manufacturers test certificate.
10
12050
1205
TOOL KIT For Maintenance: -
The Tool Kit for maintenance shall comprise of the following and all the items as mentioned below shall be of :
Providing of tool kit consists of following items i. Double ended Spanner (Chrome plated) of size in mm
6/7,8/9,10/11,12/13,14/15,16/17,18/19,20/22,21/23,24/26,25/28, 24/27, 30/32, each – 02 No. ii. double ended Ring spanners chrome plated of size in mm 6/7,8/9,10/11,12/13,14/15,16/17,18/19,20/22,21/23,24/26,25/28, 24/27, 30/32, each – 02 No. iii. Allen key set black finish of size in mm 1.5, 2, 2.5, 3, 4,5,6,8,10 make – Taparia each – 2 NO.
iv. Combination Pliers insulated with thick C.A sleeve; size in mm 165, 210, 255 each – 02 No.
v. Long nose pliers insulated with thick C.A sleeve; size in mm 165, 205 each – 02 No.
vi. Side cutting pliers insulated with thick C.A sleeve; size in mm 165, 205 – 02 No.
vii. Insulated screw Drivers Blade length Blade dia. Tip dimensions Quantity 50 3 1.6 x 0.4 02
75 3 1.6 x0.4 02
100 3 3 x 0.4 02
125 3.5 3.5 x 0.5 02
150 3.5 3.5 x 0.5 02
200 4 4 x 0.6 02
300 5 5 x 0.8 02
viii. Hammer with handle weight – 110 mg, 340 gm , 600 gm –each – 1No. . ix. Heavy duty pipe Wrench length in mm - 200, 300, 600 each – 01 No. x. Digital Multi-meter =1 No.
xi. Digital Clamp tester capable to measure up to 400A - 1 No. xii. Hack saw frame with hack saw blade – 01 No.
xiii. S-16 MXL, S- 16 H X L Socket Set (19 sockets + 6 Accessories) – 01 No.
xiv. Earthing resistance tester - 01 No.
1
28840
28840
Fabrication of 6’ x 6’ angle iron bed by way of providing and fitting of Structural steel in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete welded.
94.75
9664
102
Providing and fitting of 19 mm thick multilayered ply sheet of size 6 x 3 feet, 2 Nos. including cutting, fixing all complete including painting of the play sheet by one coat of primer and two coats of enamel paint.
36
5544
154
a) Providing of good quality bedding for night stay/Shift consisting of: -
i) Mattress with warm cover size 6'x3' (6Kg)- 02 No’s
ii) Quilt with warm cover size 5'x8' (6Kg)- 02 No’s
iii) Pillows with covers - 02 No’s
iv) Single bed warm blankets with one sided Fur- 02 No’s
The filling material for mattress, quilt and pillow shall be of good quality cotton
b) The job also includes providing of pressure cooker 5ltr 02 No’s, Steel patila( utensil) 5ltrs 02 No’s, cooking heater 01 No., room heater 01 No., steel buckets 10 litre capacity 01 No., Plastic bucket 10 litre capacity with Mug 02 No’s each, steel glasses 06 No’s, steel Plates with large spoons and bowls 03 No’s each, Cup and Saucer set (01 No. Set) and, 5kg Gas cylinder with burner/ stove. All the utensils shall be of Prestige, Pigeon, Wonder chef, United, Futura make.
The job also includes providing of thermo-cool 15’x12’ along with excel matting of 15’x12’ size. The job also includes providing of unbreakable Plastic Chair table set consisting of chairs 04 No’s, extra heavy Table 01 No. of Samruddhi/ Neel kamal/Supreme /Anmol Make. The job also includes providing of good quality safety Door locks (03 No’s) of Godrej, Link locks, Thapar make.
1
39619
39619
Providing of solar/electrical lantern chargeable on both solar & electrical 220v supply. The solar lantern is to be provided with solar plate along with allied wires.
1
1911
1911
Providing of bamboo ladders 18 feet long along with 15 feet long Link rods and HT Glove pair (01 No each).
1
7350
7350
Providing of 1 KW heat convector for operators for winter season.
1
1205
1205
Providing & fitting of electric ceiling/wall fan of reputed make.
1
1900
1900
Providing and fitting of 01 No. angle iron/sheet metal board duly painted showing various specifications of the mechanical and electrical equipments installed at site. Size: 4’×6’ out MS ANGLE OF 40 X 40 X 5 of 36 rft and MS sheet of 1 mm thick total weight of 50.16 kgs. The details shall include details of various electro mechanical equipments installed in the said water supply lift scheme along with name of department etc.
24
6000
250
Providing, installation, Testing & commissioning of 415 ±10%V (output), 3 phase 25 KVA air cooled/fluid cooled Diesel Generator set as per IS 8528 (2018) and ISO 3046 (2002) for engine and IEC/IS 60034-1 for alternator suitably assembled and fitted in a pollution free acoustic enclosure / canopy of required size as per Ministry of Environment protection rule 1986 read with latest amendments. The DG Set is required to be fitted and tested on load at site. The DG Set shall have following specifications:
The DG Set shall be able to operate at 1600 mtrs ASL (at actual site conditions) efficiently without causing any malfunctioning. The DG Set shall comprise of Diesel Engine and Alternator coupled together with heavy duty flexible coupling and mounted on M. S. Base Frame along with all standard accessories, Control Panel, Battery, M. S. Canopy, duly painted and conforming to noise reduction norms as per environmental protection rules 1986 as laid down by Ministry of Environmental (Protection) and Forest, read with GSR-371(E) Dated: 17-05-2002 at S. No 95 for emissions limits and GSR-371(E) Dated: 17-05-2002 at S. No 94 (Paragraph 1 and 3) for noise limits for the DG Set and as per the latest amendments if any.
Besides the above works the D.G set shall be provided with 12 V, 150 AH Lead acid battery of reputed make fitted inside the D.G set Canopy along with necessary accessories like fuel tank (inbuilt) etc and battery charger of required capacity.
DG Set should be rated for continuous duty with overload provision of 10% for the period not exceeding one hour in twelve hours.
A) ALTERNATOR :- The alternator shall be self-excited, self-regulated for 25 KVA rating and shall be brushless, continuous duty. The alternator shall be screen protected drip proof enclosure, and horizontal foot mounted in double bearing construction. a) Rated Output: 25 KVA
b) Rated Speed: 1500 RPM c) Efficiency at full load 0.8 P.f. = Not less than 86.00% or as per relevant IS code. d) Total distortion factor = less than 3% e) Voltage: 415 V at 50 Hz f) Class of Insulation: H g) Enclosure: IP 23. h) Governor = Electronic
B). DIESEL ENGINE (Prime Mover) The Prime Mover shall be diesel driven to develop requisite BHP as per ISO-8528-part- I at 1500 RPM for the alternator rated as above with ambient temperature ranging from - 10C to +45C with 70% humidity. a) Speed: 1500 RPM b) Cooling System: Air cooled/fluid cooled
c) Method of Start: Electric Start with a Key. d) Rated BHP: Suitable for 25 KVA output at NTP as per ISO-8528-part- I The engine shall be fitted with following accessories:- 1) Fuel Tank: The capacity of the fuel tank shall be so as to last for 12 hours of continuous running on full load. The fuel tank shall be mounted on an angle iron frame of suitable height and fabricated out of M.S. Sheet of 4 mm Thickness duly painted and fitted with connections for inlet, outlet and return and also to be provided with air vent, drain with valve, level indicator and fuel pipes complete in all respects. 2) Battery: Battery suitable for above capacity DG set.3) Starting System: Providing and Fitting of Terminals, Leads, C/W Charging Dynamo and fitted with 12 Volt Starting System. The system shall be able of starting of DG set with 20-30 Sec even in winter conditions with ambient temp down to -50C. 4) Engine Instrument Panel: The Engine Instrument Panel shall be fitted with starting switch with keys, Lube Oil Gauge, Temperature & Pressure Gauge, Speedometer, Kilowatt Hour Meter etc and all other accessories as required. 5) Safety Control: The D. G. Set shall be provided & fitted with all the safety controls i.e. for Low lube oil Pressure indication switch, High water temperature indication, RPM indication, water temperature indication, battery charging indication etc. C) Standard Control Panel: -
The control panel shall be fabricated out of suitable sheet steel duly pretreated and aesthically finished. The control panel shall be totally enclosed, dust and vermin proof, floor/ wall mounted type. The control panel shall consist of following instruments:
i). A C Voltmeters of class1.5 accuracy and 0-600 V with 4 position Selector switch.
ii). A C Ammeter of class 1.5 accuracy and of suitable range
iii). HRC Fuses of suitable rating.
iv). One MCB of suitable rating for D G Sets.
v). Frequency meter vi). Power Factor meter digital type above 15 KVA.
vii). Push buttons switch for ON and OFF operation.
viii). Pilot lamps.
ix). Battery charger/ inverter with voltage regulator, Voltmeter and Ammeter for charging the battery from Mains. This will be in addition to battery charging alternator fitted on the engine.
x). Energy meter (class-2) of suitable rating confronting to relevant IS for DG Sets above 15 KVA rating.
xi). Instrument and control fuses.
All the components in the control panel shall be properly mounted, duly wired and labelled. Suitable terminals shall be provided for incoming and outgoing connections. The instruments / components shall be of reputed make. Item No II, v, vi, and x can be alternately supplied in one combined digital meter.
Canopy The Canopy of the D. G. Set shall be fabricated out of M. S. Sheet of required gauge so as to withstand the snow load etc, duly painted. The Canopy shall be as per the Norms of the as laid down in the environmental protection rules 1986 of Ministry of Environmental (Protection) and Forest, read with GSR-371(E) Dated:17-05-2002 at S. No 95 for emissions limits and GSR-371(E) Dated: 17-05-2002 at S. No 94 (Paragraph 1 and 3) for noise limits for the DG Set and as per the latest amendments if any.
The job also includes the cost on account of HSD and skilled operator required for operation of D.G set for a period of 10 hours continuously during its testing and commissioning of D.G set at site. Maunfacturers test certificates for Engine, Alternator, DG SET to be provided at the time of supply.
1
617206
617206
Providing and fitting of 25 sqmm 3.5 core, capable to work up to 1.1 KV, XLPE insulated, galvanized steel strip armored Aluminium cable conforming to IS : 7098(part -1) 1988 With latest amendments to be fitted from D.G Set to Modular control panel. The job includes providing and fitting of suitable rating Aluminium thimbles duly crimped and taped at conductor ends by hydraulic crimping tool. The job includes earth work in excavation wherever required for laying of cable underground and proper clamping wherever required to be routed over the walls ceiling etc. The Test Certificate of Cables duly stamped by manufacturer shall be provided at the time of supply of material.
i) 25 sqmm, 3.5 core, LT cable
50
17300
346
Providing, Installation, Testing & Commissioning of complete switchgear unit for protection of D.G Set consisting of 200A MCCB 3- pole, 415 V, 50 KV breaking capacity housed properly in cubical enclosure made up of M.S SWG – 16 sheet steel (outdoor type) duly powder painted with anti-corrosive paint comprising of three compartments for incoming / outgoing circuits and MCCB. The panel should have adequate double locking Arrangement with Cu-. Bus Bar 12x40 mm with Bakelite insulation and LT Arrangement selector switches, phase indicators. The equipment should be installed at appropriate height in a stand consisting of 50 x 50 x 6 mm angle grouted in ground with appropriate cement bottoming as per the IS standard.
1
39422
39422
Fabrication of CGI Shed for DG Set by way of Structural steel work in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of steel primer and two coats of approved paint all complete welded.
800
88800
111
Providing corrugated G. S. sheet roofing including vertical/curved surface fixed with polymer coated J or L hooks, bolts and nuts 8mm diameter with bitumen and G.I limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of approved paint on overlapping of sheets complete (upto any pitch in horizontal/vertical or curved surface) excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. 0.50 mm thick with zinc coating not less than 350 gram/m2
30
25575
852.5
Providing and fitting of welded MS wire mesh (0.50 sq inch and 1.40 mm wire dia for Bird screening to the CGI Shed.The job includes painting of the structure in two coats of red oxide and two coats of enamel paint.
450
16650
37
Evaluation Notes How It Works ?