Power Development Department Tender
Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Power Development Department - PDD Tender
Civil And Construction
Electrical and Electronics
Water Storage And Supply
Electrical Works
Eprocure
Opening Date24 Jan 2024
Closing Date15 Feb 2024
Tender Amount₹ 2,99,30,000
Costs
EMD
₹ 5,98,600Document Cost
₹ 4,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_PDD_243472_1Bid Award Id
ViewTender No
eNIT No 286/EDA of Electric Divn Anantnag KPDCLTender Authority
Power Development Department ViewPurchaser Address
-Website
http://http://www.jkpdd.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
4
-
-
11 kV Horn Gap Fuse Set 3 Phase 200A
4
-
-
300 mm²(3Ckt) Single Phase Cable, 1.1K V Grade, XLPE Insulated Stranded Conductor FRLS type
528
-
-
9 Mtr. Long Pole ( ST-410 SP33)
8
-
-
G.I Pipe of 150 mm dia 2 mtr long for Pole Butts (6")
8
-
-
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting
12
-
-
GI Channel/Angle/Flat of sizes including clamps for L.A Set/G.O Set/Horn Gap
600
-
-
Galvinized Nuts and Bolts.
88
-
-
Earthing of Substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
12
-
-
Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm
8
-
-
Transformer Pad/G.I Channel Bedding (300Kg)
1200
-
-
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
12
-
-
LT Distribution Box for 400 kVA DTR with 630 Amp MCCB 3P (36 KA) adjustable 1 No. for incomer & 200 Amp 3 P (16 KA) 4 No.s fixed for Outgoing Circuits as per drawings
4
-
-
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 )mm, nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
8
-
-
Wedge Connectors / PG Clamps
24
-
-
Danger Plates with Clamps
4
-
-
GI Barbed Wire for Anti Climbing
60
-
-
Cement bottoming 1:2:4 mix as per Standards 0.48cum /pole
16
-
-
Red Oxide(one coat) and Almunium paint(2 or more coats so as to obtain smooth finish)
8
-
-
Supply of Bamboo Ladders (16 ft long)
7
-
-
Sundry items like Aluminium lugs, Jumpers, binding Tape etc
4
-
-
Supply,installation,Testing,Commissioning,Carriage,Loading and unloading at site ( 02 No.250 KVA DT sub-Stations)
-
-
-
250 kVA,11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2,(Cu wound) , and with LV Cable Box having detachable Al. Gland plate with LV Bimetallic terminal connection suitable for vertical take off of cable..
2
-
-
11 kV Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
2
-
-
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
2
-
-
11 kV Horn Gap Fuse Set 3 Phase 200A
2
-
-
240mm² (2Ckt ) single core Cable,1.1kV Grade, XLPE Insulated Stranded Conductor FRLS type (44mtr for 1 Ckt)
176
-
-
9 Mtr. Long Pole,(ST-410 SP33)
4
-
-
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting
6
-
-
GI Channel/Angle/Flat of sizes including clamps
600
-
-
Galvinized Nuts and Bolts.
16
-
-
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
6
-
-
Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm
4
-
-
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
6
-
-
LT Distribution Box for 250 kVA DTR with 400 Amp MCCB 3P 36 kA for incomer & 200 Amp MCCB 3P 16 kA 1 No. and 160 Amp MCCB 3P 16 kA 2 No.s for Outgoing Circuits as per drawings
2
-
-
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6) mm, nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
4
-
-
Wedge Connectors / PG Clamps
12
-
-
Danger Plates with Clamps
2
-
-
GI Barbed Wire for Anti Climbing
30
-
-
Cement bottoming 1:2:4 mix as per Standards 0.48 cum/pole
4
-
-
Red Oxide(one coat) and Almunium paint(2 or more coats so as to obtain smooth finish)
4
-
-
Sundry items like Aluminium lugs, Jumpers, Binding Tape etc
2
-
-
Supply,installation,Testing,Commissioning,Carriage,Loading and unloading at site ( 01 No.25 KVA DT sub-Station)
-
-
-
25kVA,11/0.433kV 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate with LV Bimetallic terminal connection suitable for vertical take off of cable.
1
-
-
11 kV Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
1
-
-
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
1
-
-
11 kV Horn Gap Fuse Set 3 Phase 200A
1
-
-
35 mm² Single-Core Cable,1.1kV Grade XLPE Insulated Stranded Conductor FRLS type
44
-
-
9 Mtr. Long Pole( ST-410 SP33)
2
-
-
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
3
-
-
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
3
-
-
GI Channel/Angle/Flat of sizes including clamps
250
-
-
Galvinized Nuts and Bolts.
8
-
-
LT Distribution Box for 25 kVA DTR with 40 Amp MCCB 3P 16 kA for incomer & 25 Amp MCCB 3P 16 kA/10 kA 1 No each (=2No.) for Outgoing Circuits as per drawings
1
-
-
Cement bottoming 1:2:4 mix as per Standards 0.48cum /pole
2
-
-
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
3
-
-
Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm
2
-
-
3 Phase LT prodigy Meter
1
-
-
Red Oxide(one coat) and Almunium paint(2 or more coats so as to obtain smooth finish)
2
-
-
Danger Plates with Clamps
2
-
-
Supply,installation,Testing,Commissioning,Carriage,Loading and unloading at site ( 11KV Line (H-Frame/Single Circuit/Double Circuit ))
-
-
-
13 Mtr. Long Pole(ST-410 SP69)
3
-
-
9 Mtr. Long Pole( ST-410 SP33)
40
-
-
11 Mtr. Long Pole( ST-410 SP56)
140
-
-
GI V cross-arm with top Bracket including clamp
10665
-
-
100 mm² ACSR Conductor
15.5
-
-
50 mm² ACSR Conductor
15.5
-
-
PG Clamps for 100 mm² ACSR Conductor
80
-
-
PG Clamps for 50 mm² ACSR Conductor
80
-
-
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
1098
-
-
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting
132
-
-
Galvanized Nuts and Bolts
260
-
-
Danger Plates with Clamps
183
-
-
Anti-Climbing Device with Clamps
183
-
-
Earthing Complete by GI Pipe 40 mm 3mtr long through GI Strip 25x3 mm
183
-
-
Red Oxide(one coat) and Almunium paint(2 or more coats so as to obtain smooth finish)
183
-
-
Cement bottoming 1:2:4 mix as per Standards 0.7 cum / pole
3
-
-
Cement bottoming 1:2:4 mix as per Standards 0.66 cum / pole
140
-
-
Cement bottoming 1:2:4 mix as per Standards 0.48 cum /pole
40
-
-
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 )mm, nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
20
-
-
Guard netting (Appx 40m Span)
20
-
-
120 mm² AB (HT) Cable (3x120 + 1x95 insulated) mm² XLPE(11 kV, 3C + Earth)
1
-
-
Heat Shrinkable Outdoor Cable Termination Kit
20
-
-
Suspension/Tension Clamp with eye hook
20
-
-
Dismantling of the Existing structure
-
-
-
Dismantling by way of uprooting of Existing ST Poles(11/9/8 mtr) and stacking of the same in Divisional stores including transportation loading and unloading etc.
26
-
-
Dismantling by way of Cutting of Existing ST Poles(11/9/8 mtr) and stacking of the same in Divisional stores including transportation loading and unloading etc
20
-
-
Dismantling by way of Cutting of Existing wooden Poles and stacking of the same in Divisional stores including transportation loading and unloading
8
-
-
Rubble of PCC Pole to be dumped at the site as identified by the site engineer to the lead upto 200 mtrs
34
-
-
Dismantling of ACSR (50/30 sqmm) and stacking of the same in Divisional stores including transportation loading and unloading
9
-
-
Branch Cutting /Pruning of trees
3
-
-
Supply,installation,Testing,Commissioning,Carriage,Loading and unloading at site ( Street Lights)
-
-
-
9.0 mtr Long GI (65 micron DFT single dip) Octogonal poles uniformally tappered with thickness of 3mm with bottom/top Dia of 175 mm x 70mm & base plate of 275x275x16mm/pcd 250 mm provided with proper door opened gear box for connections on the bottom side with G.I. Foundation Bolts (J Type) M24x750 mm long (Set of 4 no.’s per pole)
55
-
-
Laying of RCC foundation for 9.0 mtr. Long Octagonal poles including proper curing. 0.6mX0.6mX1.2m (RCC with concrete ratio (1 : 1.5 : 3 ) with minimum 8 Nos. of 12 mm dia longitudinal MS reinforcement rods with rings of 8 mm dia not more than 200 mm C.C for fixing the pole).
55
-
-
Earthing of Octagonal Pole Complete by GI Pipe 40 mm or GI Rod 20mm 3 mtr long through GI Strip (25x3)mm
55
-
-
Pre fabricated galvanized double way top bracket (1500mm long with 48.3 OD GI Pipe) to be fitted on top of Octogonal pole for holding lighting
55
-
-
DK thermoplastic cable Junction/ Termination T boxes 8"x10"of class IP55/IP65 fitted with two 2-5 Amp MCB strip,4-way terminal block / connectors Incl. copper lugs, Clamps ,nut & bolts washers etc (Hansel or equivalent make) or poles with two way type bracket to be fitted properly inside the door opened gear box provided on the
bottom side of the pole.
55
-
-
120/190 Watt LED Luminaries of IP 67 protection
110
-
-
Surge Protector for the 120/190 watt LED type lighting fixture complete.
110
-
-
3X1.5 mm² PVC insulated multistrand flexible copper wire for service connections from connection plate to the LED luminary individual circuit including loop & earthings laid properly.
1100
-
-
HDPE pipe 50 mm O/D and inner Dia 38 mm including trench excavation in hard soil (0.3x0.45x1000m) for laying of 25/16 sq mm Almunium armored cable . The job further inludes refilling back the same and removal of surplus excavted material to an appropriate place.
2000
-
-
LT 25 mm² 4 core Aluminium XLPE Armoured cable to be carried through conduit/pipe U/G or A/G only in case of site constrains excluding cost of pipe & trench excavation. The cable shall include end termination lugs with its crimping /taping.
1500
-
-
LT 16 mm² 2 core Aluminium XLPE Armoured cable to be carried through conduit/pipe U/G or A/G only in case of site constrains excluding cost of pipe & trench excavation. The cable shall include end termination lugs with its crimping /taping.
1000
-
-
Outdoor type LT control panel size 900mmX900mmX450mm having input main control of 100Amp MCCB with TPN Bus Bar with 40 Amp TPN MCB 4Nos for outgoing circuits,including astronomical switching with contactor of required capacity. The panel should be fitted with a digital composite voltmeter/amper meter/indicator set with selecter switch and backup protection system, thimbling and the panel shall further be provided with proper openings on front side as well as on rear side including its locking arrangement and also with required glands and 4No. angle iron legs for grouting the panel on bed , the panel shall also be provided with powder coat/PU paint. The item includes its thimble as required at taping point for incomming , out going and internal panel wiring complete unit.
3
-
-
Dust/rain/snow-proof canopy type mini-outdoor LT feeder panel of size 450X300mm with front door opening duly powdered colour coated with inbuilt 2No TPN 16-32 Amp MCCB,TPN busbars of same capacity installed on cement concrete block with 4 angle iron legs grouted in the cement concrete of termination of main 25sqmm cable and outgoing 25/16 sqmm cable circuits.
3
-
-
Supply,installation,Testing,Commissioning,Carriage,Loading and unloading at site ( All in One Solar Street Lights)
-
-
-
6 Mtr long GI pole of (3 inch Dia) Standard Make
45
-
-
GI Bracket suitable for for fixing of solar street light including clamps nuts and Bolts
202.5
-
-
100W ALL-IN-ONE Solar Street Light integrated with PV Panel(Lumens=4000LM,Life span greater than 50000 hours, Solar panel Poly solar Cell,Battery LiFePO4 lithium battery,Battery rating Min 3-rainy days backup,Life span greater than 2000 charging cycles ,operation mode (Dawn to desk) with Motion sensor of PIR infrred having sensing distance of 12M with remote control and manual switch,working temprature -20 Deg C to + 60 Deg C,Water proof ,CRI greater than 85%
45
-
-
Earthing Complete by GI Rod 20mm 2.5 mtr long through GI Strip.
45
-
-
Cement bottoming 1:2:4 as per REC standars 0.2cum/pole
45
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements