Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Power Development Department - PDD Tender
Civil And Construction
Civil Works Others
Electrical and Electronics
Electrical Works
Eprocure
Opening Date19 Nov 2022
Closing Date17 Dec 2022
Tender Amount₹ 41,00,000
Costs
EMD
₹ 82,000Document Cost
₹ 1,000Tender Fee
Refer Documents
Summary
Survey, Design, Supply, Transportation, Carriage, Erection, Testing And Commissioning Of 25kva New Sub Stations Along With 11kv Ht Line And Lt Line At Sarbag Pyt. Hassote A, Morha Sarma Dandakote And Morha Dhangli Pyt Banna B In Electric Sub Division
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2022_PDD_196604_1Bid Award Id
ViewTender No
e NIT 29 of 2022-23 dated 18.11.2022Tender Authority
Power Development Department ViewPurchaser Address
-Website
http://http://www.jkpdd.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
GI Channel X-arm including clamps and braces
438
-
-
11kV GO AB Swich set 3-Phase, 3-Pole, 200 Amp
3
-
-
ACSR Weasel Conductor
8.42
-
-
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
156
-
-
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
33
-
-
Galvinized Nuts and Bolts
52
-
-
Danger Plates with Clamps
52
-
-
Anti-Climbing Device with Clamps
52
-
-
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25x3)mm.
52
-
-
Aluminium Paint (Asian/Nerolac or reputed make)
52
-
-
Cement bottoming 1:2:4 mix as per REC standards 0.5cum /pole
52
-
-
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete.
13
-
-
Creation of 25KVA Distribution substation as per scope of work mentioned in SBD wherein 25KVA distribution Transformers are available in stores (Reasi town) of Electric Division JPDCL Reasi
-
-
-
Loading, transportation, carriage, erection, testing and commissioning of 11/0.433KV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) and with LV cable box having detachable Aluminium Gland plate (from stores in reasi town to site of work)
3
-
-
Loading, transportation, carriage, erection, testing and commissioning of 9 mtr long Pole ST-410, SP33 (from stores in reasi town to site of work)
6
-
-
Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type
3
-
-
11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type
3
-
-
11kV Horn Gap Fuse set 3-phase, 200 Amp
3
-
-
95sqmm cable 1.1KV grade, PVC insulated stranded conductor FRLS type
132
-
-
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
9
-
-
GI Channel/Angle/Flat of different sizes including clamps
750
-
-
Galvanised Nuts & Bolts
24
-
-
Earthing of s/stn - Excavation of earthing pit of dia 650mm & depth 3000mm, installation ofEarthing pipe of 40mm nominal bore & 4mm wall thickness & length 2.5 mtr long as per IS 1239. GI strip for neutral earthing of size 25mm x 3mm for connection of transformer body, GO set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover
9
-
-
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
6
-
-
Danger Plates with clamps
3
-
-
G.I Barbed Wire for anti climbing
45
-
-
Bus bar insulator
24
-
-
Aluminium strip 50x10 mm
9
-
-
Cement bottoming 1:2:4 mix as per REC standards 0.5cum/Pole
6
-
-
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
9
-
-
Aluminium (Asian/Nerolac or reputed make) Paint
6
-
-
Aluminium Thymbals 95sqmm
36
-
-
Laying of LT Line as per scope of work mentioned in SBD wherein 8 mtr long Pole ST-410, SP15 poles are available in stores (Reasi town) of Electric Division JPDCL Reasi
-
-
-
Loading, transportation, carriage, erection, testing and commissioning of 8 mtr long Pole ST-410, SP15 (from stores in reasi town to site of work)
131
-
-
GI M Clamp for shackle Insulator
262
-
-
ACSR weasel Conductor
17.82
-
-
Shackle insulator
262
-
-
Galvanised Nuts & Bolts
131
-
-
Danger Plates with clamps
131
-
-
Earthing Complete by GI Pipe 40mm or GI Rod 20 mm 2.5 Meter long through GI Strip(25x3)mm
131
-
-
Aluminium Paint (Asian/Nerolac or reputed make)
131
-
-
Anti-Climbing Device with Clamps
131
-
-
Cement Bottoming 1:2:4 mix as per REC Standards 0.45CUM/Pole
131
-
-
Galvanised Stay setwith 50x8mm stay clamp, Guy Insulator (2 Nos), Anchor Plate (200x200x6mm) nuts and Bolts, 2Nos Turn Buckles, 1.8 long, 16mm diameter solid GS Stay rod & 7/3.15mm dia GI Standard wire complete
23
-
-