Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Power Development Department - PDD Tender
Eprocure
Opening Date22 Feb 2020
Closing Date16 Mar 2020
Tender Amount₹ 73,50,000
Costs
EMD
₹ 1,47,000Document Cost
₹ 2,000Tender Fee
Refer Documents
Summary
E-nit No. 21 Of 2019-20 Dated 22-2-2020
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2020_PDD_93427_1Bid Award Id
ViewTender No
e-NIT No. 21 of 2019-20 dated 22-02-2020Tender Authority
Power Development Department ViewPurchaser Address
-Website
http://http://www.jkpdd.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
36kV, 50c/s , 2500 Amp, 25kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with One Earthing
Blades
1
-
-
Single phase, 50 c/s 36KV Current Transformers (1200-600-300 /1-1-1 A or
as per site specifications) , 25KA for one second, rated dynamic current 25KA(peak), Class A insulation, Burden 20 VA
3
-
-
Single Phase 36KV 50 c/s, outdoor metal oxide gapless type, 120KV (rms) Surge Arrestor including Surge counters/monitors, insulating base all
associated accessories, auxiliaries.
3
-
-
33KV Control and Relay Panel for Line/Feeder completely wired including
Substation automation supporting IEDs/numerical relays
1
-
-
33KV Post Insulators Solid Core Type, Power Frequency Withstand Voltage
95KVP Dry lightning impulse withstand voltage ± 170 (KVP)
6
-
-
Galvanised Structures
13
-
-
Galvanised NUTS AND BOLTS
0.75
-
-
2 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control
cable complete
380
-
-
6 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control
cable complete
100
-
-
8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control
cable complete
350
-
-
12 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control
cable complete
1400
-
-
4 Core, 4 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, Un armoured stranded Aluminium conductor control
cable complete
450
-
-
Marshalling kiosk with Kiosk frames mild steel structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. Frames shall be enclosed in cold-rolled sheet steel of thickness not less than 1.6 mm. Doors and covers shall also be cold rolled sheet steel of thickness not less than 1.6 mm. complete structures shall be rigid, self- supporting, free from flows, twists and bends. Dust and vermin proof construction and shall be provided with a degree of protection of IP: 55, with Copper Bar earthing. Finishing paint on panels shall be of shade 692 (smoke grey) of IS: 5. The inside shall be properly stoved. The paint thickness shall be at least 50 microns.
1
-
-
500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN
0.5
-
-
Tension Fittings For Twin 500 mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum
Ultimate strength (Tensile strength) shall be 70 KN.
24
-
-
Suspension Fittings For Twin 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm.
6
-
-
Single Tension Fittings For Single 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm.Minimum Ultimate strength (Tensile strength) shall be 70 KN.
12
-
-
Single Suspension Fittings For Single 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm.
12
-
-
Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia.
Creepage total 430 mm and 260 mm protected.
130
-
-
Clamps of sorts and sizes
1
-
-
Earth wire
0.15
-
-
Casting of Gantry & Equipment foundations including all activities likereinforcement, concreting, excavation, back filling, shuttering, dewatering etc
-
-
-
Laying of 33KV Column foundations
4
-
-
Laying of 33KV Isolator foundations
4
-
-
Laying of 33KV CT foundations
3
-
-
Laying of 33KV LA foundations
3
-
-
Laying of 33KV VCB foundations
1
-
-
Laying of 33KV P.I foundations
6
-
-
Earth Mat (40mm dia steel bars) as per approved design, Galavanised Iron
(75mm x 12mm/ 50mm x 6 mm) risers for Equipment and Structural Earthing
175
-
-
CABLE TRAYS/CABLE RACKS/ACCESSORIES
-
-
-
Cable Trays of size 400mm x 3000mm made of M.S angles
40x40x6mm,40x6 Flat.
180
-
-
Cable Trays of size 300mm x 2500mm made of M.S angles
40x40x6mm,40x6 Flat.
90
-
-
Lugs, Ferrules, Welding Material, Cotton Waste etc (132KV,33KV side)
1
-
-
Cable Ducts With Covers
-
-
-
Main Duct of Size 900mm x 600mm with 6 mm M.S Chequered Trench Covers of size 500 x 1000 mm
6
-
-
Main Duct of Size 900mm x 600mm with concrete grade M15 of size 500 x
1000 mm
30
-
-
Sub Main Duct of Size 600mm x 450mm with concrete grade M15 of size
700x500 mm
30
-
-
Tee off Duct: 150mm sand filled HDPE pipes from Sub main to Equipments
in the outdoor area
20
-
-