Power Development Department Tender
Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Power Development Department - PDD Tender
Eprocure
Opening Date15 Jun 2021
Closing Date24 Jun 2021
Tender AmountRefer Documents
Costs
EMD
₹ 74,000Document Cost
₹ 1,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2021_PDD_127299_1Bid Award Id
ViewTender No
E- NIT NO 33 OF 2021-22Tender Authority
Power Development Department ViewPurchaser Address
-Website
http://http://www.jkpdd.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Providing, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site, Laying, stringing and binding of conductor including joints with PG clamps of required size
50 mm2 ACSR ( Rabbit)
10.5
-
-
Providing, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site, Laying, stringing and binding of conductor including joints with PG clamps of required size 30 mm2 ACSR ( Weasel)
1.5
-
-
Supplying and erection of GI Channel 100x50x6mm cross-arm (75 x 40x6mm) with Braces of (50X50X6mm) with GI Angle Pole Top Bracket (50x50x6 mm) including back clamps of 50X8 mm for fixing Cross arm and pole top bracket without making holes in the ST pole as per REC standard for single pole structure.
2913.5
-
-
Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site 11 KV Polymeric Composit pin with insulator insulator 12 KV, 5 KN,Light Impulse 75 KVPositive and 80 KV Negative ,Creepage distance 320 mm
355
-
-
Supply and laying of Cement bottoming 1:2:4 mix as per REC standards 0.45 cum/pole, muffing 20 cm above ground level ,including plaster and curing of concrete in size of 600x600x1700mm for 8 mtrs Long ST Poles (410, SP-15) (the leftover pit after concreting to be filled with soil and boulders)
20
-
-
Supply and laying of Cement bottoming 1:2:4 mix as per REC standards 0.50 cum/pole, muffing 20 cm above ground level ,including plaster and curing of concrete in size of 600x600x1700mm for 13/11/9 mtrs Long ST Poles (410, SP-33/56) (the leftover pit after concreting to be filled with soil and boulders)
86
-
-
Supplying and fixing of 11 kV Disc Insulators (polymer) Complete with fittings (45KN) depending upon conductor size.
36
-
-
Supplying and fixing of pole Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip(25x3) to each HT pole including supply and welding of GI channel 70x40x150 on pole for earth connection
106
-
-
Supplying and fixing of . sub station earthing by way of Excavation of Earthing Pit of Dia 650mm Dept 3000mm and instllation of GI Pipe 40 mm or GI Rod 20mm, 2.5 mtr long as per IS 1239 through GI Strip of 50X6 mm 1 no for neutral earthing and 25X3 mm 2 nos (for 2 transformer body earth, two no. pole earth, 1 no. LA Earth and 1 no. GO handle earth). Note: For LA Earth 1 pipe shall be kept separate as per IS Standard 2629/85 GI Nuts & Bolts refilling with Earth enhancement materials and earthe Chamber made of Brick Massionary with RCC Slab COver (Distribution Sub Station)
9
-
-
Supplying and erection of Danger Plates with clamps with writing in English and Regional Language
86
-
-
Supply and fixing of anti-climbing GI Barbed wire binding with Clamps at a distance of 30 to 40 cm at a height of 3.5 to 4 m from ground level. At-least 2 kgs GI barbed wire(12 SWG) is to be used per pole for the purpose.
86
-
-
Supplying and fixing of Galvanized Nuts and Bolts of sizes.
106
-
-
Supply and fixing of Parallel Grove (PG) clamps, binding wire etc
7
-
-
Supply and painting of each Pole 1 coat red oxide paint and 2 coats of aluminium paint (@ 1 ltr/pole red oxide paint and 1 ltr/pole aluminium paint)
106
-
-
Providing, fixing and Commissioning of LT Shackle insulators as per REC standard
230
-
-
Supply and fixing of Muky Clamps fibricated out of 50x8 mm flat iron of appropiate size and specification for holding LT Shackle insulators.
345
-
-
Supply and fixing of TPN MCCBs 63 Amp and suitable MCCBs for outgoing circuits with terminal extensions.
1
-
-
Supply and installation of Guy Insulators (polymer) Complete with fitting(5 KN)
6
-
-
Supply and installation of Gapless Surge Arrestor,9 kV,10 kA, LA with (polymer) housing, Station Type
3
-
-
Supply and installation of 11 kV, G.O AB Switch , 3-phase, 200A
3
-
-
Supply and installation of 11 kV Horn, Gap Fuse 3-phase 100A
3
-
-
Supply and fixing of Un Armoured Single Core XPLE, FRLS Cable (240mm2 Havells/Polycab/Gloster or equivalent make.
105
-
-
Supply and Fixing of Wedge Connectors/PG Clamps
36
-
-
Dismanteling and carriage of of 9 M ST Poles from site to Store
50
-
-
Dismanteling and carriage of of 8 M ST Poles from site to Store
12
-
-
Dismanteling and carriage of of PCC Poles from site to Store
14
-
-
Dismanteling and carriage of of old conductor 0.5/0.3 from site to Store
7
-
-
Dismanteling and carriage of Channel Iron 100x50x6mm 9ft, 75x40x6mm 9/6 ft, 50x50x6mm 5 ft long from site to Store
96
-
-
Dismanteling and carriage of 11KV Disc Sets from site to Store
17
-
-
Dismanteling and carriage of 11KV Pin Insulators from site to Store
144
-
-
Dismanteling and carriage of 11KV GO Sets from site to Store
3
-
-
Dismanteling and carriage of 11KV DO Sets from site to Store
3
-
-
Dismanteling and carriage of Sub Station frame including Poles from site to Store
3
-
-
Dismanteling and carriage of 25mm Sq 3-core Cable
1.2
-
-
Providing of Stencil and spray painting (black in Colour) on each pole at an height of 4.5 feet above ground levelwith following specification :- 1. The dimension of the stencil should be not less than 21"x 9" per Pole . 2. The following details are to be recorded on each pole with the spray paint. a. Name of the work b. Year c. Name of The contractor d. SR of the Pole. The said stencil should be approved by EDV Ganderbal.
106
-
-
Pre and post Geo tagged photographic Evidence consisting of 5x7 inch Photographs in coffee table book and autocad single line diagram
1
-
-