Power Development Department Tender
Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Power Development Department - PDD Tender
Electrical Goods and Equipments
Electrical and Electronics
Eprocure
Opening Date11 Aug 2023
Closing Date1 Sep 2023
Tender AmountRefer Documents
Costs
EMD
₹ 1,42,000Document Cost
₹ 2,000Tender Fee
Refer Documents
Summary
Survey, Supply, Transportation, Carriage, Erection, Testing And Commissioning For Creation Of 250 Kva, 100 Kva Sub Stations Alongwith Erection Of 11 Kv Line 9 Mtr. St Poles, 30mm Sq Acsr Weasel Conductor Lt Line 8 Mtr. St Pole Wss Pipple Under Jjm
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_PDD_226020_1Bid Award Id
ViewTender No
ED/Udh/60 of 2023-24 dt. 11-08-2023Tender Authority
Power Development Department ViewPurchaser Address
-Website
http://http://www.jkpdd.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
GI Channel X-arm including clamps and Angle for braces
700
-
-
30mm² ACSR conductor
13
-
-
PG clamps
50
-
-
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
234
-
-
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KV Positive and 80 KV Negative, creepage distance 320mm with fitting
51
-
-
Galvanized Nuts and Bolts
88
-
-
Danger Plates with Clamps
88
-
-
Anti climbing device with clamps
88
-
-
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
88
-
-
Painting of 9 mtr ST poles with two coat of Aluminium Paint.
88
-
-
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
44
-
-
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
23
-
-
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for creation of 250 KVA Sub stn. at WSS Pipple Stage Thilli.
-
-
-
11/0.433 KV, 3-phase distribution Transformer 250 KVA with Bimetallic Terminal Connectors Energy Level-2 Copper Wound, & with LV Cable box having detachable Aluminium Gland plate
1
-
-
Gapless surge Arestor, 9 kv, 10 KA , LA with polymer housing stn. Type
1
-
-
11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical
1
-
-
11 KV Horn gap fuse set 3 phase 200 A
1
-
-
300mm² 1.1 KV Grade, PVC insulated stranded conductor FRLS Type
44
-
-
9 mtr. Long ST poles (ST-410 SP33)
2
-
-
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KV Positive and 80 KV Negative, creepage distance 320mm with fitting
3
-
-
GI Channel /Angle/flat of sizes including clamps
300
-
-
Galvanized Nuts and Bolts.
15
-
-
Earthing of sub stn. Excavation of earth pit of dia 650mm & depth 3000mm installation of earthing pipe of 40mm Nominal bore & 4mm wall thickness & length 2.5 mtr. Long as per IS 1239. G.I Strip for neutral earthing of size 25mmx3mm for connection of transforemr body, GO Set & lightening arrestor as per IS 2629/85, GI Nuts & bolts refilled with earth enhancement materials and earth chamber with RCC Slab cover
3
-
-
11 KV Polymer composite pin insualtor, 12 KV, 5KN Lightening impulse 75 KV Positve and 80 KV Negative, creepage distance 320mm
3
-
-
LT distribution box for 250 KVA DTR with MCCB for incomer and SFU's for outgoing circuits
1
-
-
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
2
-
-
PG Clamps
6
-
-
Danger Plates with Clamps
1
-
-
GI Barbed wire for Anticlimbing
15
-
-
3-Phase 4 Wire Trivector Meter with CT PT Unit
1
-
-
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
1
-
-
Painting of ST poles 9 mtr. Long with 1 coat of Red oxide & 2 coat of Aluminum paint.
2
-
-
Survey, supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 3 Phase 4 Wire LT line on 8 mtr. ST poles at WSS Pipple (Stage-Thilli).
-
-
-
8 mtr. Long ST poles (ST-410 SP15)
17
-
-
GI M Clamps for shackle insulator
68
-
-
50mm² ACSR Rabbit Conductor
3.4
-
-
Shackle insulator
68
-
-
Galvanized Nuts and Bolts.
17
-
-
Danger Plates with Clamps
17
-
-
Anti climbing device with clamps
17
-
-
Earthing complete by GI Rod 20mm 2.5 mtr. Long through GI Strip
17
-
-
Painting of 8 mtr ST poles with two coat of Aluminium Paint
17
-
-
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
8.5
-
-
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
4
-
-
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 11 KV line on 9 mtr. ST poles, 30mm² ACSR Conductor at WSS Pipple Stage-Pipple
-
-
-
9 mtr. Long ST Pole (ST-410 SP-33)
14
-
-
GI V Cross -arm with top Bracket including clamps
200
-
-
GI Channel X-arm including clamps and Angle for braces
110
-
-
30mm² ACSR Weasel conductor
2
-
-
PG Clamps
7
-
-
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
36
-
-
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KV Positive and 80 KV Negative, creepage distance 320mm with fitting
9
-
-
Galvanized Nuts and Bolts
14
-
-
Danger Plates with Clamps
14
-
-
Anti climbing device with clamps
14
-
-
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
14
-
-
Painting of 9 mtr ST poles with two coat of Aluminium Paint.
14
-
-
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
7
-
-
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
3
-
-
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for creation of 100 KVA Sub stn. at WSS Pipple (Stage Pipple).
-
-
-
11/0.433 KV, 3-phase distribution Transformer 100 KVA with Bimetallic Terminal Connectors Energy Level-2 Aluminium Wound, & with LV Cable box having detachable Aluminium Gland plate
1
-
-
Gapless surge Arestor, 9 kv, 10 KA , LA with polymer housing stn. Type
1
-
-
11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical
1
-
-
11 KV Horn gap fuse set 3 phase 200 A
1
-
-
120mm² 1.1 KV Grade, PVC insulated stranded conductor FRLS Type
44
-
-
9 mtr. Long ST poles (ST-410 SP33)
2
-
-
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KV Positive and 80 KV Negative, creepage distance 320mm with fitting
3
-
-
GI Channel /Angle/flat of sizes including clamps
300
-
-
Galvanized Nuts and Bolts.
15
-
-
Earthing of sub stn. Excavation of earth pit of dia 650mm & depth 3000mm installation of earthing pipe of 40mm Nominal bore & 4mm wall thickness & length 2.5 mtr. Long as per IS 1239. G.I Strip for neutral earthing of size 25mmx3mm for connection of transforemr body, GO Set & lightening arrestor as per IS 2629/85, GI Nuts & bolts refilled with earth enhancement materials and earth chamber with RCC Slab cover
3
-
-
11 KV Polymer composite pin insualtor, 12 KV, 5KN Lightening impulse 75 KV Positve and 80 KV Negative, creepage distance 320mm
3
-
-
LT distribution box for 100 KVA DTR with MCCB for incomer and SFU's for outgoing circuits
1
-
-
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
2
-
-
PG Clamps
6
-
-
Danger Plates with Clamps
1
-
-
GI Barbed wire for Anticlimbing
15
-
-
3-Phase 4 Wire LT Prodigy Meter with Box.
1
-
-
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
1
-
-
Painting of ST poles 9 mtr. Long with 1 coat of Red oxide & 2 coat of Aluminum paint.
2
-
-
Survey, supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 3 Phase 4 Wire LT line on 8 mtr. ST poles at WSS Pipple (Stage-Pipple).
-
-
-
8 mtr. Long ST poles (ST-410 SP15)
4
-
-
GI M Clamps for shackle insulator
16
-
-
50mm² ACSR Rabbit Conductor
1
-
-
LT Shackle insulator
16
-
-
Galvanized Nuts and Bolts.
4
-
-
Danger Plates with Clamps
4
-
-
Anti climbing device with clamps
4
-
-
Earthing complete by GI Rod 20mm 2.5 mtr. Long through GI Strip
4
-
-
Painting of 8 mtr ST poles with two coat of Aluminium Paint
4
-
-
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
2
-
-
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
1
-
-