Power Development Department Tender
Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Power Development Department - PDD Tender
Civil And Construction
Civil Works Others
Electrical and Electronics
Electrical Works
Eprocure
Opening Date7 Jan 2023
Closing Date27 Jan 2023
Tender Amount₹ 21,97,000
Costs
EMD
₹ 43,940Document Cost
₹ 1,000Tender Fee
Refer Documents
Summary
Survey, Design, Supply, Transportation, Carriage, Erection, Testing And Commissioning Of 25kva New Sub Station Along With 11kv Ht Line And Lt Line At Minukala Ward No.6 Upper Tuli-b In Electric Sub Division Dharmari On Turnkey Basis In District Reasi
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_PDD_201824_1Bid Award Id
ViewTender No
e-NIT No 37 of 2022-23 DT 05.01.2023Tender Authority
Power Development Department ViewPurchaser Address
-Website
http://http://www.jkpdd.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
... More
GI Channel X-arm including clamps and braces
126
-
-
... More
11kV GO AB Swich set 3-Phase, 3-Pole, 200 Amp
1
-
-
... More
ACSR Weasel Conductor
2.5
-
-
... More
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
45
-
-
... More
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
18
-
-
... More
Galvinized Nuts and Bolts
15
-
-
... More
Danger Plates with Clamps
15
-
-
... More
Anti-Climbing Device with Clamps
15
-
-
... More
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25x3)mm.
15
-
-
... More
Aluminium Paint (Asian/Nerolac or reputed make)
15
-
-
... More
Cement bottoming 1:2:4 mix as per REC standards 0.5cum /pole
15
-
-
... More
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete.
4
-
-
... More
Creation of 25KVA Distribution substation as per scope of work mentioned in SBD
-
-
-
... More
11/0.433KV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors fully Efficient Energy Level-2 (i.e actual Efficient energy level 3 redesignated as Efficient Energy Level 2 as per amendment no.4 of relevant IS ) , (Aluminium wound) and with LV cable box having detachable Aluminium Gland plate
1
-
-
... More
9 mtr long Pole ST-410, SP33
2
-
-
... More
Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type
1
-
-
... More
11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type
1
-
-
... More
11kV Horn Gap Fuse set 3-phase, 200 Amp
1
-
-
... More
95sqmm Single Core PVC Cable, 1.1KV Grade FRLS Type
44
-
-
... More
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
3
-
-
... More
GI Channel/Angle/Flat of different sizes including clamps
250
-
-
... More
Galvanised Nuts & Bolts
8
-
-
... More
Earthing of s/stn - Excavation of earthing pit of dia 650mm & depth 3000mm, installation ofEarthing pipe of 40mm nominal bore & 4mm wall thickness & length 2.5 mtr long as per IS 1239. GI strip for neutral earthing of size 25mm x 3mm for connection of transformer body, GO set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover
3
-
-
... More
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
2
-
-
... More
Danger Plates with clamps
1
-
-
... More
G.I Barbed Wire for anti climbing
15
-
-
... More
Bus bar insulator
8
-
-
... More
Aluminium strip 50x10 mm
2
-
-
... More
Cement bottoming 1:2:4 mix as per REC standards 0.5cum/Pole
2
-
-
... More
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
3
-
-
... More
Aluminium (Asian/Nerolac or reputed make) Paint
2
-
-
... More
Aluminium thymbals 95sqmm
12
-
-
... More
Laying of LT Line as per scope of work mentioned in SBD
-
-
-
... More
Loading, transportation, carriage, erection, testing and commissioning of 8 mtr long Pole ST-410, SP15 (from site stores to site of work) (15 Nos poles are available at site stores, Upper Tulli B)
15
-
-
... More
8 mtr long Pole ST-410, SP15
32
-
-
... More
GI M Clamp for shackle Insulator
94
-
-
... More
ACSR weasel Conductor
6.5
-
-
... More
16 KN Polymer Shackle Insulators
94
-
-
... More
Galvanised Nuts & Bolts
47
-
-
... More
Danger Plates with clamps
47
-
-
... More
Earthing Complete by GI Pipe 40mm or GI Rod 20 mm 2.5 Meter long through GI Strip(25x3)mm
47
-
-
... More
Aluminium Paint (Asian/Nerolac or reputed make)
47
-
-
... More
Anti-Climbing Device with Clamps
47
-
-
... More
Cement Bottoming 1:2:4 mix as per REC Standards 0.45CUM/Pole
47
-
-
... More
Galvanised Stay setwith 50x8mm stay clamp, Guy Insulator (2 Nos), Anchor Plate (200x200x6mm) nuts and Bolts, 2Nos Turn Buckles, 1.8 long, 16mm diameter solid GS Stay rod & 7/3.15mm dia GI Standard wire complete
10
-
-
Evaluation Notes How It Works ?