Power Development Department Tender

Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.

Power Development Department - PDD Tender

Eprocure
Opening Date17 Feb 2021
Closing Date27 Mar 2021
Tender AmountRefer Documents 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Supply & Fixing of M.S Iron Cross Arm (75*40*5mm).with one coat of red oxide and two coats of aluminium paint/ Support Angle frame & legs (50x50x6 mm) for Distribution feeder pillar, leg height 1 mt. with 0.3 mt in soil approx. ( Size of MS Iron as per the site requirement for Pole mounted/ Plinth Mounted Structure)

63

-

-

... More
Providing and fixing of Galvanized Nuts and Bolts of Sorts

6

-

-

... More
Providing and fixing of Galvanized Pole Collar /Clamps

8

-

-

... More
Supply,laying,Testing and Commissioning of 400 mm sq 1-core 1.1 KV grade , stranded Aluminium Conductor, XLPE insulated PVC Outer Sheathed, Unarmoured cable (Havells/Gloster/Polycab/Paramount/Grandlay)) as per IS-7098 amended up to date

160

-

-

... More
Providing and fixing of Pad Clamps of suitable size for 400 sq mm Cable

16

-

-

... More
Providing and fixing of 400 mm sq Aluminium Thimbles.

36

-

-

... More
Cement Grounting 1:2:4 of Standalone arrangement of LTDB

0.3

-

-

... More
For distribution Transformer of capacity (500/400 KVA DT; Two Circuits ) Supply,fixing,testing and commissioning of 400 Amp 3 Pole Thermal Magnetic MCCB's having adjustable thermal (0.8 In-1.0 In) . with fixed magnetic setting of 10*In, breaking capacity not less than 65kA (Ics=Icu=100%), with spreader links, phase barriers, & direct mounting rotary operating mechanism(ROM). The ROM shall be lockable in OFF position. The MCCB should be CE marked and shall conform to IEC:60947-2-2003 Standards. The MCCB shall have a maximum operational voltage(Ue) 690V, insulation voltage (Ui) 1000V, and impulse withstand voltage (Uimp) 8kV. MCCBs shall be actuated by a rotary-handle that clearly indicates the three distinctive positions: ON, OFF and TRIPPED, Total Opening Time 10msec, Mechanical Life 25000 operations & Electrical Life @415V AC 10000 operations. ABB/EATON/HAVELLS/L&T/SCHNEIDER/SEIMENS/LEGRAND

2

-

-

... More
Supply, Fixing , testing & Commissioning M S Enclosure (1440X1140X450) with Busbar (Aluminium) not less than 800 mm sq. for 2 No. 400A MCCBs, Cable Holding arrangement of suitable size for holding cable, with rubber glands The thickness of enclosure on load bearing side (Backside/Frontside) should not be less than 3 mm and not less than 2 mm for all other sides . Surface preparation by chemical pre-treatment using electrostatic powder painting process minimum coating thickness 80 microns. The Enclosure shall be dust, moisture & vermin proof for tropical use and shall provide a degree of protection not less than IP-55 in accordance with IS:2147 complete as per the drawings annexed. This includes earthing of the enclosure and earthing of neutral (earthing will be done using GI strip of size as per standard). The neutral shall be terminated through Neutral busbar of rated operational current (Ie) 1400 Amps having Impulse Withstand voltage (Uimp) of 3kV . (Makes: 1. Tricolite Energy Solutions. 2. Balaji Switchgears. 3. Metfab Products. 4. Milestones Switchgears. 5. M B Automation 6. ALBA Power or equivalent makes/designs)

1

-

-

... More
Providing and fixing of Bi-metalic Clamps suitabe for vertical entry of 300 sqmm cable and 400 kVA DT LT Bush rods.

4

-

-

... More
Supply & Fixing of M.S Iron Cross Arm (75*40*5mm).with one coat of red oxide and two coats of aluminium paint/ Support Angle frame & legs (50x50x6 mm) for Distribution feeder pillar, leg height 1 mt. with 0.3 mt in soil approx. ( Size of MS Iron as per the site requirement for Pole mounted/ Plinth Mounted Structure)

31.5

-

-

... More
Providing and fixing of Galvanized Nuts and Bolts of Sorts

3

-

-

... More
Providing and fixing of Galvanized Pole Collar /Clamps

4

-

-

... More
Supply,laying,Testing and Commissioning of 300 mm sq 1-core 1.1 KV grade , stranded Aluminium Conductor, XLPE insulated PVC Outer Sheathed, Unarmoured cable (Havells/Gloster/Polycab/Paramount/Grandlay) as per IS-7098 amended up to date

80

-

-

... More
Providing and fixing of Pad Clamps of suitable size for 300 sq mm Cable

8

-

-

... More
Providing and fixing of 300 mm sq Aluminium Thimbles.

18

-

-

... More
Cement Grounting 1:2:4 of Standalone arrangement of LTDB

0.15

-

-

... More
For distribution Transformer of capacity (250 KVA DT ) Supply,fixing,testing and commissioning of 400 Amp 3 Pole Thermal Magnetic MCCB's having adjustable thermal (0.8 In-1.0 In) . with fixed magnetic setting of 10*In, breaking capacity not less than 65kA (Ics=Icu=100%), with spreader links, phase barriers, & direct mounting rotary operating mechanism(ROM). The ROM shall be lockable in OFF position. The MCCB should be CE marked and shall conform to IEC:60947-2-2003 Standards. The MCCB shall have a maximum operational voltage(Ue) 690V, insulation voltage (Ui) 1000V, and impulse withstand voltage (Uimp) 8kV. MCCBs shall be actuated by a rotary-handle that clearly indicates the three distinctive positions: ON, OFF and TRIPPED, Total Opening Time 10msec, Mechanical Life 25000 operations & Electrical Life @415V AC 10000 operations. ABB/EATON/HAVELLS/L&T/SCHNEIDER/SEIMENS/LEGRAND

31

-

-

... More
Supply, Fixing , testing & Commissioning M S Enclosure (1190X710X355) with Busbar (Aluminium) not less than 500 mm sq. for Single 400A MCCBs, Cable Holding arrangement of suitable size for holding cable, with rubber glands. The thickness of enclosure on load bearing side (Backside/Frontside) should not be less than 3 mm and not less than 2 mm for all other sides . Surface preparation by chemical pre-treatment using electrostatic powder painting process minimum coating thickness 80 microns. The Enclosure shall be dust, moisture & vermin proof for tropical use and shall provide a degree of protection not less than IP-55 in accordance with IS:2147 complete as per the drawings annexed. This includes earthing of the enclosure and earthing of neutral (earthing will be done using GI strip of size as per standard). The neutral shall be terminated through Neutral busbar of rated operational current (Ie) 1400 Amps having Impulse Withstand voltage (Uimp) of 3kV. (Makes: 1. Tricolite Energy Solutions. 2. Balaji Switchgears. 3. Metfab Products. 4. Milestones Switchgears. 5. M B Automation 6. ALBA Power or equivalent makes/designs)

31

-

-

... More
Providing and fixing of Bi-metalic Clamps suitabe for vertical entry of 300 sqmm cable and 250 kVA DT LT Bush rods.

124

-

-

... More
Supply & Fixing of M.S Iron Cross Arm (75*40*5mm).with one coat of red oxide and two coats of aluminium paint/ Support Angle frame & legs (50x50x6 mm) for Distribution feeder pillar, leg height 1 mt. with 0.3 mt in soil approx. ( Size of MS Iron as per the site requirement for Pole mounted/ Plinth Mounted Structure)

976.5

-

-

... More
Providing and fixing of Galvanized Nuts and Bolts of Sorts

62

-

-

... More
Providing and fixing of Galvanized Pole Collar /Clamps

124

-

-

... More
Supply,laying,Testing and Commissioning of 300 mm sq 1-core 1.1 KV grade , stranded Aluminium Conductor, XLPE insulated PVC Outer Sheathed, Unarmoured cable (Havells/Gloster/Polycab/Paramount/Grandlay) as per IS-7098 amended up to date

1240

-

-

... More
Providing and fixing of Pad Clamps of suitable size for 300 sq mm Cable

124

-

-

... More
Providing and fixing of 300 mm sq Aluminium Thimbles.

279

-

-

... More
Cement Grounting 1:2:4 of Standalone arrangement of LTDB

4.65

-

-

... More
For distribution Transformer of capacity (100 KVA DT ) Supply,fixing,testing and commissioning of 160 Amp 3 Pole Thermal Magnetic MCCB's having adjustable thermal (0.8 In-1.0 In) . with fixed magnetic setting of 10*In, breaking capacity not less than 50kA (Ics=Icu=100%), with spreader links, phase barriers, & direct mounting rotary operating mechanism(ROM). The ROM shall be lockable in OFF position. The MCCB should be CE marked and shall conform to IEC:60947-2-2003 Standards. The MCCB shall have a maximum operational voltage(Ue) 690V, insulation voltage (Ui) 1000V, and impulse withstand voltage (Uimp) 8kV. MCCBs shall be actuated by a rotary-handle that clearly indicates the three distinctive positions: ON, OFF and TRIPPED, Total Opening Time 10msec, Mechanical Life 25000 operations & Electrical Life @415V AC 10000 operations. ABB/EATON/HAVELLS/L&T/SCHNEIDER/SEIMENS/LEGRAND

60

-

-

... More
Supply, Fixing , testing & Commissioning M S Enclosure (860X550X300) with Busbar (Aluminium) not less than 250 mm sq. for Single 160A MCCBs, Cable Holding arrangement of suitable size for holding cable, with rubber glands. The thickness of enclosure on load bearing side (Backside/Frontside) should not be less than 3 mm and not less than 2 mm for all other sides . Surface preparation by chemical pre-treatment using electrostatic powder painting process minimum coating thickness 80 microns. The Enclosure shall be dust, moisture & vermin proof for tropical use and shall provide a degree of protection not less than IP-55 in accordance with IS:2147 complete as per the drawings annexed. This includes earthing of the enclosure and earthing of neutral (earthing will be done using GI strip of size as per standard). The neutral shall be terminated through Neutral busbar of rated operational current (Ie) 1400 Amps having Impulse Withstand voltage (Uimp) of 3kV . (Makes: 1. Tricolite Energy Solutions. 2. Balaji Switchgears. 3. Metfab Products. 4. Milestones Switchgears. 5. M B Automation 6. ALBA Power or equivalent makes/designs)

60

-

-

... More
Providing and fixing of Bi-metalic Clamps for Transformer suitabe for vertical entry of 185 sqmm cable and 100 kVA DT LT Bush rods.

240

-

-

... More
Supply & Fixing of M.S Iron Cross Arm (75*40*5mm).with one coat of red oxide and two coats of aluminium paint/ Support Angle frame & legs (50x50x6 mm) for Distribution feeder pillar, leg height 1 mt. with 0.3 mt in soil approx. ( Size of MS Iron as per the site requirement for Pole mounted/ Plinth Mounted Structure)

1890

-

-

... More
Providing and fixing of Galvanized Nuts and Bolts of Sorts

120

-

-

... More
Providing and fixing of Galvanized Pole Collar /Clamps

240

-

-

... More
Supply,laying,Testing and Commissioning of 185 mm sq 1-core 1.1 KV grade , stranded Aluminium Conductor, XLPE insulated PVC Outer Sheathed, Unarmoured cable (Havells/Gloster/Polycab/Paramount/Grandlay) as per IS-7098 amended up to date

2400

-

-

... More
Providing and fixing of Pad Clamps of suitable size for 185 sq mm Cable

240

-

-

... More
Providing and fixing of 185 mm sq Aluminium Thimbles.

720

-

-

... More
Cement Grounting 1:2:4 of Standalone arrangement of LTDB

9

-

-

... More
For distribution Transformer of capacity (63 KVA DT ) Supply,fixing,testing and commissioning of 100 Amp 3 Pole Thermal Magnetic MCCB's having adjustable thermal (0.8 In-1.0 In) . with fixed magnetic setting of 10*In, breaking capacity not less than 36 kA (Ics=Icu=100%), with spreader links, phase barriers, & direct mounting rotary operating mechanism(ROM). The ROM shall be lockable in OFF position. The MCCB should be CE marked and shall conform to IEC:60947-2-2003 Standards. The MCCB shall have a maximum operational voltage(Ue) 690V, insulation voltage (Ui) 1000V, and impulse withstand voltage (Uimp) 8kV. MCCBs shall be actuated by a rotary-handle that clearly indicates the three distinctive positions: ON, OFF and TRIPPED, Total Opening Time 10msec, Mechanical Life 25000 operations & Electrical Life @415V AC 10000 operations. ABB/EATON/HAVELLS/L&T/SCHNEIDER/SEIMENS/LEGRAND

28

-

-

... More
Supply, Fixing , testing & Commissioning M S Enclosure (860X550X300) with Busbar (Aluminium) not less than 150 mm sq. for Single 100A MCCBs, Cable Holding arrangement of suitable size for holding cable, with rubber glands. The thickness of enclosure on load bearing side (Backside/Frontside) should not be less than 3 mm and not less than 2 mm for all other sides . Surface preparation by chemical pre-treatment using electrostatic powder painting process minimum coating thickness 80 microns. The Enclosure shall be dust, moisture & vermin proof for tropical use and shall provide a degree of protection not less than IP-55 in accordance with IS:2147 complete as per the drawings annexed. This includes earthing of the enclosure and earthing of neutral (earthing will be done using GI strip of size as per standard). The neutral shall be terminated through Neutral busbar of rated operational current (Ie) 1400 Amps having Impulse Withstand voltage (Uimp) of 3kV . (Makes: 1. Tricolite Energy Solutions. 2. Balaji Switchgears. 3. Metfab Products. 4. Milestones Switchgears. 5. M B Automation 6. ALBA Power or equivalent makes/designs)

28

-

-

... More
Providing and fixing of Bi-metalic Clamps for Transformer suitabe for vertical entry of 95 sqmm cable and 63 kVA DT LT Bush rods.

112

-

-

... More
Supply & Fixing of M.S Iron Cross Arm (75*40*5mm).with one coat of red oxide and two coats of aluminium paint/ Support Angle frame & legs (50x50x6 mm) for Distribution feeder pillar, leg height 1 mt. with 0.3 mt in soil approx. ( Size of MS Iron as per the site requirement for Pole mounted/ Plinth Mounted Structure)

882

-

-

... More
Providing and fixing of Galvanized Nuts and Bolts of Sorts

56

-

-

... More
Providing and fixing of Galvanized Pole Collar /Clamps

112

-

-

... More
Supply,laying,Testing and Commissioning of 95 mm sq 1-core 1.1 KV grade , stranded Aluminium Conductor, XLPE insulated PVC Outer Sheathed, Unarmoured cable (Havells/Gloster/Polycab/Paramount/Grandlay) as per IS-7098 amended up to date

1120

-

-

... More
Providing and fixing of 95 mm sq Aluminium Thimbles.

336

-

-

... More
Cement Grounting 1:2:4 of Standalone arrangement of LTDB

4.2

-

-

... More
For distribution Transformer of capacity (25 KVA /16 KVA DT ) Supply,fixing,testing and commissioning of 40 Amp 3 Pole Thermal Magnetic MCCB's having adjustable thermal (0.8 In-1.0 In) . with fixed magnetic setting of 10*In, breaking capacity not less than 36kA (Ics=Icu=100%), with spreader links, phase barriers, & direct mounting rotary operating mechanism(ROM). The ROM shall be lockable in OFF position. The MCCB should be CE marked and shall conform to IEC:60947-2-2003 Standards. The MCCB shall have a maximum operational voltage(Ue) 690V, insulation voltage (Ui) 1000V, and impulse withstand voltage (Uimp) 8kV. MCCBs shall be actuated by a rotary-handle that clearly indicates the three distinctive positions: ON, OFF and TRIPPED, Total Opening Time 10msec, Mechanical Life 25000 operations & Electrical Life @415V AC 10000 operations. ABB/EATON/HAVELLS/L&T/SCHNEIDER/SEIMENS/LEGRAND

12

-

-

... More
Supply, Fixing , testing & Commissioning M S Enclosure (860X550X300) with Busbar (Aluminium) not less than 75 mm sq. for Single 40A MCCBs, Cable Holding arrangement of suitable size for holding cable, with rubber glands. The thickness of enclosure on load bearing side (Backside/Frontside) should not be less than 3 mm and not less than 2 mm for all other sides . Surface preparation by chemical pre-treatment using electrostatic powder painting process minimum coating thickness 80 microns. The Enclosure shall be dust, moisture & vermin proof for tropical use and shall provide a degree of protection not less than IP-55 in accordance with IS:2147 complete as per the drawings annexed. This includes earthing of the enclosure and earthing of neutral (earthing will be done using GI strip of size as per standard). The neutral shall be terminated through Neutral busbar of rated operational current (Ie) 1400 Amps having Impulse Withstand voltage (Uimp) of 3kV. (Makes: 1. Tricolite Energy Solutions. 2. Balaji Switchgears. 3. Metfab Products. 4. Milestones Switchgears. 5. M B Automation 6. ALBA Power or equivalent makes/designs)

12

-

-

... More
Providing and fixing of Bi-metalic Clamps for Transformer suitabe for vertical entry of 35sqmm cable and 16kVA/25kVA DT LT Bush rods.

48

-

-

... More
Supply & Fixing of M.S Iron Cross Arm (75*40*5mm).with one coat of red oxide and two coats of aluminium paint/ Support Angle frame & legs (50x50x6 mm) for Distribution feeder pillar, leg height 1 mt. with 0.3 mt in soil approx. ( Size of MS Iron as per the site requirement for Pole mounted/ Plinth Mounted Structure)

378

-

-

... More
Providing and fixing of Galvanized Nuts and Bolts of Sorts

24

-

-

... More
Providing and fixing of Galvanized Pole Collar /Clamps

48

-

-

... More
Supply,laying,Testing and Commissioning of 35 mm sq 1-core 1.1 KV grade , stranded Aluminium Conductor, XLPE insulated PVC Outer Sheathed, Unarmoured cable (Havells/Gloster/Polycab/Paramount/Grandlay) as per IS-7098 amended up to date

480

-

-

... More
Providing and fixing of 35 mm sq Aluminium Thimbles.

144

-

-

... More
Cement Grounting 1:2:4 of Standalone arrangement of LTDB

1.8

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.