Power Development Department Tender
Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Power Development Department - PDD Tender
Civil And Construction
Water Storage And Supply
Eprocure
Opening Date1 Nov 2023
Closing Date22 Nov 2023
Tender Amount₹ 41,25,000
Costs
EMD
₹ 82,500Document Cost
₹ 1,000Tender Fee
Refer Documents
Summary
Survey, Design, Supply, Transportation, Carriage, Erection, Testing And Commissioning For Creation Of 250kva Sub Stations Along With Erection Of 11kv Ht Line For Each Stage 0 And Stage 1st At Wss Aghar Ballian In Sub Division Reasi Under Deposit
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_PDD_235550_1Bid Award Id
ViewTender No
e NIT 43 of 23-24 dated 29.10.2023Tender Authority
Power Development Department ViewPurchaser Address
-Website
http://http://www.jkpdd.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
GI Channel X-arm including clamps and braces
30
-
-
11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type
1
-
-
ACSR Weasel Conductor
0.5
-
-
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
6
-
-
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
6
-
-
Galvinized Nuts and Bolts
4
-
-
Danger Plates with Clamps
4
-
-
Anti-Climbing Device with Clamps
4
-
-
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25x3)mm (for 4 No ST Poles and 1 No GO Set)
5
-
-
Aluminium Paint of reputed make
4
-
-
Cement bottoming 1:2:4 mix as per REC standards 0.5cum /pole
4
-
-
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
4
-
-
Laying of 11KV Line for Stage Ist (Supply, Transportation, Carriage, Installation,Testing and Commissioning - complete job)
-
-
-
ST Pole 9 mtr ST 410 SP33
22
-
-
GI V cross-arm with top Bracket including clamp
320
-
-
GI Channel/Angle Iron including clamps and braces
150
-
-
120mm² AB (HT) Cable (3x120 +1x95 mm²) XLPE (11KV, 3C+ Earth)
0.4
-
-
Heat Shrinkable Outdoor cable termination Kit
4
-
-
Suspension/Tension Clamp with eye hook
15
-
-
Mid Span Straight Through Jointing Kit for 11KV ABC
3
-
-
11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type
1
-
-
ACSR Weasel Conductor
2.2
-
-
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
27
-
-
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
18
-
-
Galvinized Nuts and Bolts
22
-
-
Danger Plates with Clamps
22
-
-
Anti-Climbing Device with Clamps
22
-
-
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25x3)mm. (for 22 No ST Poles and 1 No GO Switch)
23
-
-
Aluminium Paint of reputed make
22
-
-
Cement bottoming 1:2:4 mix as per REC standards 0.5cum /pole
22
-
-
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
8
-
-
Supply, Fabrication,Erection, Testing and commissioning of 250KVA Distribution substation (each for Stage 0 & Stage 1st)
-
-
-
11/0.433KV, 3-phase 250 KVA, 50 Hz Copper wound Distribution Transformer with Bimetallic Terminal Connectors of latest Energy Efficiency Level-2 (New), IS 1180 Part-I: 2014 as per latest uptodate amendment with externally fitted MCCB with cable box and 4x4 Mtrs. suitable cable of ratings.
2
-
-
9 mtr long Pole ST-410, SP33
4
-
-
Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type
2
-
-
11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type
2
-
-
11kV Horn Gap Fuse set 3-phase, 200 Amp
2
-
-
185sqmm cable 1.1kv grade, PVC insulated stranded conductor FRLS type
88
-
-
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
6
-
-
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
6
-
-
GI Channel/Angle/Flat of different sizes including clamps
600
-
-
Galvanised Nuts & Bolts
16
-
-
Earthing of substation - Excavation of earthing pit of dia 650mm & depth 3000mm, installation of Earthing pipe of 40mm nominal bore & 4mm wall thickness & length 2.5 mtr long as per IS 1239. GI strip for neutral earthing of size 25mm x 3mm for connection of transformer body, GO set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover
6
-
-
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
4
-
-
LT distribution box for 250KVA DTR with MCCB for incomer & SFU's for outgoing circuits
2
-
-
Wedge connectors/PG Clamps
12
-
-
Danger Plates with clamps
2
-
-
G.I Barbed Wire for anti climbing
30
-
-
11KV HT Metering CT/PT operated as per detailed scope mentioned in SBD at page no: 9
2
-
-
Cement bottoming 1:2:4 mix as per REC standards 0.5cum/Pole
4
-
-
Painting of Poles Aluminium Paint of reputed make
4
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements