The AAI has issued a formal invitation for competitive bids for the Airports Authority Of India project, for Replacement Of Existing 02 Nos Of 200 Tr Chillers At Srinagar Airport in Budgam, Jammu & Kashmir, with an estimated contract value of Rs. 4,59,50,770. The bid opening date for this tender is 14-04-2025 and the last date for bid submission is 19-05-2025. Interested bidders for Airports Authority Of India tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.
Airports Authority Of India - AAI Tender
Opening Date14 Apr 2025
Closing DateCancelled
Tender Amount₹ 4,59,50,770
AI Insights
Technical
Technical
Financial
Additional Eligibility
Class Of Bidder
... View More
The class eligibility requirement to bid or participate in this tender is not explicitly mentioned, however, it is stated that the tenderer must be a registered contractor of appropriate class.
Technical Capacity
... View More
The required prior work experience for the bidder includes:
i) Three separate works each costing not less than Rs. 18380308/- (Excl GST)
OR
ii) Two separate works each costing not less than Rs. 22975385/- (Excl GST)
OR
iii) One work costing not less than Rs. 36760616/- (Excl GST) The bidder should have satisfactorily completed or substantially completed specified works of a similar nature. Substantial completion is based on 80% (eighty percent) of the awarded cost or more value-wise works completed under the contract. Additionally, the bidder should have achieved a minimum annual value of General E&M Works, with a minimum value of Rs. 1378.52 Lakhs (excluding GST), out of which a minimum of Rs. 689.26 Lakhs (excluding GST) should be from HVAC works. The experience criteria and current costing level should be arrived at by enhancing the actual value of work at a simple rate of 7% per annum, calculated from the date of completion to the date of bid opening. No specific percentage of similar works completed is mentioned, except for substantial completion which is 80%. The bidder needs to provide details of the completed works, including the name of the work, work order/agreement number and date, contract cost, stipulated date of completion, actual date of completion, and actual completion cost.
Costs
EMD
₹ 13,78,523Document Cost
₹ 1,180Tender Fee
Refer Documents
Summary
Replacement Of Existing 02 Nos Of 200 Tr Chillers At Srinagar Airport
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2025_AAI_232773_1Tender No
AAI/SNR/ENGG-E/STC-CHILLERTender Authority
Airports Authority Of India ViewPurchaser Address
-Website
http://https://www.aai.aero/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
EARTHING (SUB-STATION EQUIPMENTS & DG SET)
-
-
-
... More
Earthing with copper earth plate 600mm x 600mm x 3.0mm thick including accessories and providing masonary enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal and salt complete as required.
5
-
-
... More
above 185 sq.mm. and upto 400 sq.mm.
50
-
-
... More
Supply, Installation, Testing and Commissioning of cubicle LT panel as per IEC 61439-1 & 2, IP42, suitable for 415V+/-10%, 3 Phase, 4 wire 50 Hz AC supply system, tested for 12kV impulse withstand voltage,form 4b construction, fabricated in compartmentalized modular design from CRCA sheet steel of 2 mm thick for frame work and covers, , plates i/c cleaning & finishing complete with 8 tank process for powder coating in approved shade, having TPN Aluminium alloy bus bars for high conductivity, SMC bus bar supports,with short circuit withstand capacity of 50 KA for 1 sec ,internal arc type tested as per IEC 61641 50kA for 0.3sec at HBB,VBB & Cable Chamber,bottom base channel of MS section not less than 100mm x 50mm x 3mm thick, fabrication shall be done in transportable section s, entire panel shall have a common earth bar sized for prospective earth fault , solid / flexible connections from main bus bar to switchgears and from switchgear output to cable termination in cable alley with required size of AL conductors / bus bars and control wiring with 2.5 sqmm PVC insulated copper conductor cable (FRLS), cable alleys, cable gland plates , i/c providing following switchgears / accessories as per specifications.
Panel shall be completed in all respect and must follow tech specs .
1
-
-
... More
Supply, Installation, Testing and Commissioning of cubicle LT panel as per IEC 61439-1 & 2, IP42, suitable for 415V+/-10%, 3 Phase, 4 wire 50 Hz AC supply system, tested for 12kV impulse withstand voltage,form 4b construction, fabricated in compartmentalized modular design from CRCA sheet steel of 2 mm thick for frame work and covers, , plates i/c cleaning & finishing complete with 8 tank process for powder coating in approved shade, having TPN Aluminium alloy bus bars for high conductivity, SMC bus bar supports,with short circuit withstand capacity of 50 KA for 1 sec ,internal arc type tested as per IEC 61641 50kA for 0.3sec at HBB,VBB & Cable Chamber,bottom base channel of MS section not less than 100mm x 50mm x 3mm thick, fabrication shall be done in transportable section s, entire panel shall have a common earth bar sized for prospective earth fault , solid / flexible connections from main bus bar to switchgears and from switchgear output to cable termination in cable alley with required size of AL conductors / bus bars and control wiring with 2.5 sqmm PVC insulated copper conductor cable (FRLS), cable alleys, cable gland plates , i/c providing following switchgears / accessories as per specifications.
Panel shall be completed in all respect and must follow tech specs .
1
-
-
... More
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm
MS flat clamp)
50
-
-
... More
Above 185 sq. mm and upto 400 sq. mm
50
-
-
... More
Supply and installing following size of galvanised iron perforated type cable trays including with perforation not more than 17.5%, in convenient sections horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling with GI suspenders etc as required.
-
-
-
... More
Dismantling of existing 200 TR screw type chiller units, foundation and associated accessories, including shifting the same from the HVAC plant location to dismantle items store located not more than 200 metres away.
2
-
-
... More
Above 185 sq. mm and upto 400 sq. mm
50
-
-
... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
-
-
-
... More
Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 kV grade of the following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required.
-
-
-
... More
3.5 core, 240 Sq.mm.
100
-
-
... More
Upto 35 sq. mm
50
-
-
... More
Upto 35 sq. mm
50
-
-
... More
3.5 core, 25 Sq.mm.
150
-
-
... More
Chiller Plant Panel
-
-
-
... More
Providing & fixing of 50mm x 5mm copper strip on surface or recess for earth connection as required.
100
-
-
... More
Supply and installing following size of galvanised iron Lader type cable trays with radil bends supports, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling with GI suspenders etc as required.
-
-
-
... More
Supply , installation , testing and commesioning of reversible air cooled screw heat pump package of 1160 kW heating/ 328 TR cooling actual capacity with twin-screw type with two rotors/ Mono Screw Rotor compressor & Star-delta starter, comprising of screw compressors with direct drive motor (speed not exceeding 3000 RPM, multi-compressor with Shell & Tube Type Evaporator duly insulated, and full refrigerant charge. Air cooled condenser having copper tube with mechanically bonded aluminum fins, fan motor with housing, inter-connecting copper piping all mounted on MS frame with vibration isolator mounting below compressors. The microprocessor based control pannel completely factory wired comprising of all necessary operative and safety controls and sensors with LCD display panel. TPN weather proof isolator switch for in coming power cable. The motor shall be suitable for 415 ± 10% volts, 3 phase , 50 Hz AC power supply. The package Heat Pump shall be BMS compatible including necessary interface card suitable for transferring data to BMS. Heat Pump shall be provided with mechanical couplings for water connections, and complete as per detailed technical Tender specifications.
2
-
-
... More
Supply and Laying of GI Pipe for running GI/Copper strip for earth connection as required and as per specifications. 80 mm inner dia
100
-
-
... More
Supplying and fixing of Shock treatment chart both in Regional, Hindi & English.and framed with 5mm thick glass as required.
2
-
-
... More
1000 mm width x 60mm depth x 2 mm thickness.
50
-
-
... More
above 185 sq.mm. and upto 400 sq.mm.
50
-
-
... More
Providing Single Line Diagram on 5mm thick Aluminium sheet in A1 Size duly laminated.
1
-
-
... More
Providing & fixing of 50mm x 5mm GI strip on surface or recess for earth connection as required.
100
-
-
... More
Up to 35 sq.mm
100
-
-
... More
above 185 sq.mm. and upto 400 sq.mm.
50
-
-
... More
3.5 core, 240 Sq.mm.
4
-
-
... More
SAFETY EQUIPMENTS
-
-
-
... More
Laying and fixing of one number PVC insulated and PVC sheathed/XLPE Power cable of 1.1kV grade of following sizes on existing cable tray etc. as required.
-
-
-
... More
Supply of First aid box containing material as prescribed by St. John Ambulance brigade OR Indian Red Cross complete as required.
2
-
-
... More
3.5 core, 400 Sq.mm.
200
-
-
... More
Laying of one number additional PVC insulated and PVC sheathed/ XLPE power cable of 1.1 kV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushionning, protective covering and refilling the trench etc as required.
-
-
-
... More
BOILER PLANT PANEL
-
-
-
... More
Up to 35 sq.mm
50
-
-
... More
Providing Single Line Diagram on 5mm thick Aluminium sheet in A0 Size duly laminated.
1
-
-
... More
3.5 core, 35 Sq.mm.
150
-
-
... More
Up to 35 sq.mm
50
-
-
... More
Supply, installing, testing & commissioning of Centrifugal Horizontal, End-Suction, Top Discharge Chilled Water Pumps with VFD, complete with CI body, bronze / gun metal / CF8 impeller with stainless steel shaft, bronze or gun metal shaft sleeve, mechanical shaft seals and flexible coupled with electric motor for re-circulation of water for the central air conditioning system. The pump shall be flexible coupled protected by OSHA compliant coupling guard. All pumps shall be aligned properly as required. The pump motor shall be TEFC squirrel cage induction motor having efficiency class IE3 (as per IS 12615) with class 'F' insulation, 1500 RPM synchronous speed, operating on 415 V +/- 10%, 3 phase, 50 Hz AC supply. The motor shall be non- overloading type. Pumps shall be with performance characteristics as given below. The pump and motor shall be mounted on a common base plate. The complete pump set alongwith base plate, coupling and coupling guard shall be factory assembled and tested. Pump set shall be complete with thermal insulation same as chilled water pipes, cladding, rubber flexible connections (PN-16) at suction and discharge, necessary anti vibration pads, MS base plate, coupling guard, and all other accessories complete as required. (two working + one standby)
1
-
-
... More
Earthing with GI earth plate 600mm x 600mm x 6.0mm thick including accessories and providing masonary enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal and salt complete as required.
5
-
-
... More
3.5 core, 400 Sq.mm.
16
-
-
... More
600 mm width x 60mm depth x 2 mm thickness.
50
-
-
... More
Laying and fixing of one number PVC insulated and PVC sheathed/XLPE powercable of 1.1 kV grade of following size on wall surface as required.
-
-
-
... More
3.5 core, 25 Sq.mm.
8
-
-
... More
Supply of following size of 1.1kv grade multicore aluminium conductor XLPE insulated and PVC sheathed armoured cable as per IS: 7098:1988 (Part - I) with upto date amendments.
-
-
-
... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonary open duct as required.
-
-
-
... More
Supplying and making end termination with double compression brass gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
-
-
-