Military Engineer Services Tender
... More
The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Cwe/kas-81/2026-27 Repair/ Maintenace Of Ht Electric Installations, Transformers, Vcbs And Other Connected Items At Dagshai Under Ge Kasauli in Solan, Himachal Pradesh, with an estimated contract value of Rs. 30,00,000. The bid opening date for this tender is 04-11-2026 and the last date for bid submission is 02-12-2026. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.
Military Engineer Services - MES Tender - HP Tender
Opening Date4 Nov 2026
Closing Date2 Dec 2026
Tender Amount₹ 30,00,000
Costs
EMD
₹ 60,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Cwe/kas-81/2026-27 Repair/ Maintenace Of Ht Electric Installations, Transformers, Vcbs And Other Connected Items At Dagshai Under Ge Kasauli
Contact
Tender Id
2026_MES_797227_1Tender No
CWE/KAS-81/2026-27Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
S&F cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and one primer coat of red oxide zinc chromate as under coat and one finishing coat of aluminium paint complete all as specified and directed by Engineer-in-charge.
3
53
-
... More
Taking down of insulators of any type and any size from its own position from existing pole structures, over head line complete all as specified and directed by Engineer-in-charge.
30
10
-
... More
S&F disc type insulator, porcelain, vitreous, 145 mm high and 255 mm dia, ball and socket type, white, brown or green, double disc with tension clamp for conductor for working pressure, voltage 11000 Volts grade, fixed on existing pole complete all as specified and directed by Engineer-in-charge.
12
11
-
... More
S&F pin type insulator, porcelain, vitreous, brown, including one galvanised mild steel spindle, two galvanised iron washer and one galvanised iron nut, 150 mm dia and 150 mm height for 11000 volts grade fixed on existing pole complete all as specified and directed by Engineer-in-charge.
12
53
-
... More
S&F loop type insulator, porcelain, vitreous, brown or green of size 90 mm x 140 mm and clearence hole 25.5 mm, fixed complete on existing pole complete all as specified and directed by Engineer-in-charge.
6
-
-
... More
Dismantling and taking down of stay assembly complete, (demolition of concrete etc., and excavation shall be measured separately) complete all as specified and as directed by Engineer-in-Charge.
4
1
-
... More
M&L for mild steel galvanised stay assembly set complete comprising of 14 mm dia, 400 mm long stay bow, 2150 mm long stay rod 20mm dia, 300mm x 300mm x 6mm stay plate, thimble, complete all as shown in electrical plate No.1 of MES Schedule part-I 2009 complete all as specified and as directed by Engineer-in-Charge. Note:- PCC, earth work and insulators etc., shall be measured and paid separately.
4
100
-
... More
S&F of anti-climbing device, spikes type fabricated out of M.S bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole suitable for PCC/ Steel poles including two coats of synthetic enamel paint over a coat of red oxide primer including taking down old anti-climbing device complete all as specified and as directed by Engineer-in-charge.
1
53
-
... More
Demolition of plain Cement concrete of any description and in any position not otherwise specifically provided for complete all as specified and as directed by Engineer-in-Charge.
1.75
10
-
... More
M&L for Plain cement concrete 1:4:8, type D-2 (using 40 mm graded stone aggregate) as in foundations, filling and mass concrete complete all as specified and as directed by Engineer-in-Charge.
0.5
11
-
... More
M&L for Plain cement concrete 1:3:6, type C-2 (using 40 mm graded stone aggregate) as in foundations, filling and mass concrete, complete all as specified and as directed by Engineer-in-Charge.
0.75
1
-
... More
M&L for cement concrete 1:2:4 Type B-1 (using 20 mm graded stone aggregate) as in copings, kneelers, apex stones, bed plates, kerbs and the like including weathering, slightly rounded or chamfered angles and throating with & incuding necessary use and waste of form work for fair faces of concrete, complete all as specified and as directed by Engineer-in-Charge.
0.5
-
-
... More
Supplying & fixing HDPE double walled corrugated (DWC) duct pipe of 110 mm outer dia conforming to IS-14930 (Part-II) of approved colour with fittings for cable protection complete all as specified and as directed by Engineer-in-Charge.
180
100
-
... More
Taking out carefully old/ unserviceable HT/LT UG cable of any type/ size from trenches/ pole/ duct after disconnecting from Pole/ busbar including taking out all bricks/ HDPE pipe/ GI pipe used for cable protection and removing from site complete all as specified and as directed by Engineer-in-charge.
700
53
-
... More
Supply, laying & testing of XLPE insulated, 11000 Volts grade 'Heavy duty' PVC sheathed armoured cable HT, XLPE insulated aluminium conductor multi stranded served with inner sheating of PVC tape armored with galvanised steel wire or tape and overall PVC sheathed of size 95 Sqmm nominal cross sectional area 3 core with suitable glands and lugs as per site requirement confirming to IS specifications, complete all as specified and as directed by Engineer-in-charge.
300
10
-
... More
Material and labour for 11KV Aerial Bunched (AB Cable) PVC, XLPE insulate and multistranded of aluminium conductor material with 4 core (i.e. 95 Sqmm, 3 core + 70 Sqmm, 1 core) including all the accessories such as hanging 'J' clamp, end extension/ support clamp etc, complete all as specified and as directed by Engineer-in-charge.
400
11
-
... More
M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm including taking down unserviceable one complete all as specified and as directed by Engineer-in-charge.
6
1
-
... More
M&L for cable jointing kit for 11 KV (Earthed) grade cable for indoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm including taking down unserviceable one complete all as specified and as directed by Engineer-in-charge.
6
100
-
... More
M&L for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm including dismantling / taking down unserviceable one complete all as specified and as directed by Engineer-in-charge.
4
53
-
... More
M&L for Air break switch, gang operated, triple pole, mechanically operated mounted on HT insulators (12 insulators pin type) and MS galvanised steel frame with operating mechanism operated from ground level with fixed contacts of phosphorous bronze and moving contacts of copper including operating rod for current rating upto 200 Amps, 11000 volts complete with locking arrangement, including 3 Nos drop out explusion type of fuses with fuse barrels of required capacity to suit load at site, also including provision of two coats of aluminium paint over a coat of red oxide primer on MS work complete all as specified and as directed by Engineer-in-charge.
2
1
-
... More
M&L for lightning arrestor, gapless metal oxide type, distribution class, system voltage-11KV, min rating-10 KV, discharge cap-65 kA, Line discharge class-1 complete with bracket and connection inclusive all necessary fixing arrengements all as specified and directed by Engineer-in-Charge.
2
-
-
... More
M&L for expulsion type drop out fuse, single pole, 11000 Volts, 25 Amps complete with insulator 150mm dia and 150 mm height including taking down old unserviceable one complete all as specified and directed by Engineer-in-Charge.
10
100
-
... More
Supply only chain link fencing of any type and size of dia not exceeding 4.00 mm galvanized steel wire, size of mesh as approved by GE including line wires, complete all as specified and as directed by Engineer-in-charge.
150
-
-
... More
Fixing only chain link fencing including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc. including provision of binding wire complete all as specified and as directed by Engineer-in-charge.
60
100
-
... More
M&L for stone aggregate of nominal size 40 mm graded, for laying under outdoor switch yard 2 pole/ 4 pole structure boundary complete all as specified and as directed by Engineer-in-charge.
3
53
-
... More
S&F galvanised, 2 strands, steel barbed wire 2.24 mm dia barbed with 2 mm dia barbs at 75 mm spacings and straining and fixing to any type of standard rails straining bolts, including, securing or tying at crossings with and provision of galvanised mild steel wire, staples or steel pins, etc. including taking down old barbed of any and dia complete all as specified and directed by Engineer-in-Charge.
35
10
-
... More
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth and getting out in hard/ dense soil for stay assembly/ laying of pipe line/ laying of cable/ erection of poles etc complete all as specified and as directed by Engineer-in-charge.
20
1
-
... More
All as per serial item No. 30.00 here-in-before but depth exceeding 1.5 metre but not exceeding 3.0 metre depth complete all as specified.
2
11
-
... More
Returning, filling in including spreading, levelling, watering and well ramming excavated soil in layers not exceeding 25 cm thick, filling back in trenches after cables have been laid and tested, complete all as specified and as directed by Engineer-in-Charge.
19
-
-
... More
Removing of surplus soil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above starting point complete all as specified and as directed by Engineer-in-Charge.
3
100
-
... More
M&L for cutting the existing bituminous road/ cement concrete surface 150 mm thick to the required width and depth for laying of cable protection pipe complete all as specified and as directed by Engineer-in-charge. Note: PCC for filling in road cutting shall be measured and paid separately under relevant item of this schedule.
1
53
-
... More
Taking down of old steel poles/ struts any size and taken as credit complete all as specified and as directed by Engineer-in-charge.
6
100
-
... More
Supply, erecting and fixing in true vertical position, steel tubular swaged pole (410 SP–55), 11 metre long, complete with cast iron base plate, pole cap/ finial taper plug, bolts, nuts and washers, welded reduced section and longitudinal welded throughout entire length of pole with and including two coats of black bituminous paint externally upto planting depth and remaining exterior portion of pole finished with one coat of red oxide primer and two coats of synthetic enamel paint including writing pole No. complete all as specified and directed by Engineer-in-Charge.
Note :- Earth work and foundation of PCC shall be measured and paid separately in relevant items of schedule.
6
53
-
... More
M&L for painting of HT steel tubular pole including cross arm/ bracing/ clamps complete with one coat of aluminum paint including cross arm, bracings, supports, nuts, bolts and including making alternative black and white strips on pole with synthetic enamel paint (each strip 30 cm height) up to 1.5 metre height from top of PCC foundation block and writing pole Nos and including applying one coat of cement base paint on exposed surface of PCC coping and foundation block complete all as specified and as directed.
50
10
-
... More
M&L in repair earth continuity conductor or main earthing lead of 32 x 6 mm galvanized iron strip, buried in ground or fixed to wall complete all as specified and as directed by Engineer-in-Charge.
50
1
-
... More
M&L for Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT pole etc, 25 x 20cm size complete all as specified and as directed by Engineer-in-charge.
30
11
-
... More
Supply and install synthetic rubber insulated mats, 2.5 mm thick for voltage upto 11KV for electrical purpose as per IS-15652-2006, suitable for electrical shock & safety of sizes 2 metre x 1 metre and taking out of old mat complete all as specified and as directed by Engineer-in-Charge.
5
-
-
... More
M&L for filtration/ dehydration of transformer oil of transformer voltage grade 11/ 0.433 KV, indoor/ outdoor type, pole/ plinth mounted installed at various electric Sub-station/ water supply installation achieves to di-electric strength min 50 kV at 4mm gap complete all as specified and as directed by Engineer-in-Charge.
Note :- (a) Filtration/ de-hydration of transformer oil shall be carried out at the location where transformer is installed and necessary filter/ dehydration plant having pressure gauge, hour meter, temperature gauge to be brought at site by the contractor including electric supply arrangement to run the de-hydration equipment and rate deemed to be included in the quoted rate.
1100
100
-
... More
M&L for topping up/ replacement of transformer oil with new transformer oil suitable for working voltage 11000 volts grade including necessary dehydration to achieve dielectric strength min 50 kV at 4mm gap complete all as specified and directed. Note :- transformer oil to be brought in company sealed ISI marked container with test certificate.
400
53
-
... More
Opening of top cover in situ or at workshop for transformer capacity from 100 KVA to 315 KVA, 11/0.433 kV grade by unscrewing all nuts, bolts & washers, draining out transformer oil upto required level and keeping in clean container and keepting transformer ready for replacement of spare parts and refixing complete with new cork sheet gasket, existing/ new nuts, bolts & washers for transformer indoor/ outdoor type, refilling of oil complete all as specified and as directed by Engineer-in-Charge. Note:- Spare parts as required shall be measured and paid sperately here-in-after.
2
100
-
... More
Taking out manually defective transformer of capacity from 100 KVA to 315 KVA from its own position upto road not exceeding 1 km and transportation of transformer by vehicle to workshop not exceeding 50 km back and forth and reinstallation on its original position after repair or shifting of transformer from present location to original location complete all as specified and as directed by Engineer-in-Charge. Note:- Rate deemed to be included for necessary disconnection and refixing the HT/ LT cables/ ACSR and earthing connection after re-installation of transformer.
2
53
-
... More
Lifting up carefully transformer core of capacity upto 315 KVA, 11/0.415 KV, after dismantling carefully terminal connections from core to HT/ LT bushings, tap changer assembly, drain out all oil and keeping in clean container, dismantling all HT & LT coils from core for rewinding, and re-assembling complete with HT/LT coils to core, required necessary numax paper insulation, insulating press board, pre-compressed board size of 6mm/ 3mm/ 1.5mm/ 1mm, varnishing, heating to achieve insulation level not less than 1000 megaohms at both HT & LT side, core at transformer chamber, tap changer assembly, terminal connection, top cover with new cork sheet gasket, required existing/new nuts, bolts & washers, filling transformer oil, testing after repair complete all as specified and directed. Note :- Opening of top cover, re-winding of HT/ LT coils, transformer oil, nuts, bolts & washers, HT/ LT bushings, required new are measured separately under appropriate items of schedule.
2
10
-
... More
M&L for cleaning, scraping out old rubbed paint/ rust from transformer of capacity 100 KVA to 850 KVA outdoor/ Indoor type and painting the transformer with one coat of spray painting with synthetic enamelled gray paint (first grade) by spray painting machine on transformer & Marking SM Nos on surface of transformers complete all as specified and as directed by Engineer-in-charge.
7
1
-
... More
S&F in replacement of old silica gel grains in the breather assembly of transformer complete all as specified and as directed by Engineer-in-Charge.
5
11
-
... More
S&F breather assembly made with polycarbonate base and clear acrylic glass of size min 50mm dia, min 120 mm long, suitable for transformer of various cap complete all as specified and as directed by Engineer-in-Charge.
4
-
-
... More
S&F transformer temperature gauge, dial type, having temp range 0 to 120 degree celsius complete all as specified and as directed by Engineer-in-Charge.
4
100
-
... More
S&F transformer porcelain bushing, outdoor/ indoor type as per existing in situ/ workshop, suitable for 11 kV grade complete with brass stud, rubber bush, washers, nuts, check-nuts and cork sheet gasket for the rating of 100 KVA to 850 KVA, 11/0.433 kV transformer complete all as specified and as directed by Engineer-in-Charge.
6
53
-
... More
M&L for replacement of transformer LT porcelain bushing indoor/ outdoor type as per existing in situ/ wksp suitable for 1100 volts grade complete with rubber bush, washers, nuts, check-nuts and cork sheet gasket for the rating of 63-100 KVA, 11/0.433 kV transformer complete all as specified and directed.
6
100
-
... More
All as per serial item No. 51.00 here-in-before but for transformers of capacity 100 to 200 KVA.
6
53
-
... More
All as per serial item No. 51.00 here-in-before but for transformers of capacity 200 to 250 KVA.
6
10
-
... More
All as per serial item No. 51.00 here-in-before but for transformers of capacity 300 to 850 KVA.
6
1
-
... More
M&L for replacement of brass stud suitable for transformers of capacity 63-100 KVA, LT, 1100 volts grade with cork & rubber washer, double Brass nuts & brass washer at both end of stud complete all as specified and as directed by Engineer-in-Charge.
6
11
-
... More
All as per serial item No. 55.00 here-in-before but for transformers of capacity 100 to 200 KVA.
6
-
-
... More
All as per serial item No. 55.00 here-in-before but for transformers of capacity 200 to 250 KVA.
6
100
-
... More
All as per serial item No. 55.00 here-in-before but for transformers of capacity 300 to 850 KVA.
6
53
-
... More
M&l for Rewinding of HT coils for transformers of capacity 160-315 KVA, 11000 volts grade with new DPC/ super enamelled copper wire having Class-F insulation as per existing size and turns complete all as specified and as directed by Engineer-in-Charge.
(Machine Nos : 143/3166/TR-11, 143/3167/TR-11)
170
100
-
... More
M&l for Rewinding of LT coils for transformers of capacity 160-315 KVA, 1100 volts grade with new DPC/ super enamelled copper wire having Class-F insulation as per existing size and turns complete all as specified and as directed by Engineer-in-Charge.
(Machine Nos : 143/3166/TR-11, 143/3167/TR-11)
130
53
-
... More
M&L for periodical servicing & calibration of HT 11 KV VCB indoor/ outdoor type panel by drawing out VCB panel having 400/ 630/ 800 Amps, removing all dust from VCB, VCB panel including busbar chamber using hot air blower, cleaning of all male/ female bushings, busbars, contact points, terminals using spirit, tightening of all contact terminals, greasing of contact point of CT/PT, metering equipments, busbars, greasing of male/ female contact points, checking of functional/ physical serviceability of CT/PT, ampmeter, voltmeter, selector switches, protection relays, tripping relays, closing coils, spring charging motors, LED indicators, MCBs, connectors, fuse bases with HRC fuses, breaker operating mechanism including identification of defective spare parts and reassemble of VCB panel complete all as specified and as directed by Engineer-in-Charge.
3
10
-
... More
Note :- (i) Result sheet to be prepared and submitted to the Deptt for record purpose i.e calibration of all metering devices, tripping system etc.,
(ii) defective/ unserviceable items found during the servicing of VCB the same will be measured and paid in relevant items of schedule.
-
-
-
... More
M&L for setting of 3 phase over current + earth fault relays by secondary injection of current with suitable equipment for over current & earth fault with high set and low set including necessary checking of trip circuit, relay circuit, closing circuit, alarm circuit, DC supply circuit, AC supply circuit and repair of same as required for 11 kV VCB after disconection of incoming and out going HT XLPE cable connection and reconnection of cable ends at existing terminals after completion of relay setting complete all as specified and as directed.
2
1
-
... More
S&F in replacement of LED indicator lamp (Neon type) for HT Panels complete with lamp Red/ Yellow/ green/ amber as per site requirement complete all as specified and as directed.
6
11
-
... More
S&F in replacement of LED indicator lamp (Neon type) for panel indicator complete with lamp blue/ white as per site requirement complete all as specified and as directed.
6
-
-
... More
S&F in replacement of spring charging motor as per existing, AC 230 volts as per existing complete all as specified and as directed by Engineer-in-Charge.
1
100
-
... More
S&F in replacement of battery of capacity 12 Volt, 80 Ah maintenance free battery along with battery charger similar to existing sample complete all as specified and as directed by Engineer-in-Charge.
2
53
-
... More
S&F in replacement of selector switch for Ampere meter complete all as specified and as directed by Engineer-in-Charge.
3
53
-
... More
S&F in replacement of selector switch for Volt meter complete all as specified and as directed by Engineer-in-Charge.
3
10
-
... More
S&F in replacement of 3 phase digital type Volt Meter, 0- 12 KV, class 0.5 of size 96mm x 96 mm to match the ratio of existing CT's complete all as specified and as directed by Engineer-in-Charge.
2
1
-
... More
S&F in replacement of 3 phase digital type Amp Meter, 0- 120 Amp, class 0.5 of size 96mm x 96 mm to match the ratio of existing CT's complete all as specified and as directed by Engineer-in-Charge.
2
11
-
... More
S&F in replacement vaccum interputer suitable for 11 KV VCB as per existing complete all as specified and as directed by Engineer-in-Charge.
1
-
-
... More
S&F in replacement of VCB trolley mechanism for auto tripping and ON/OFF mechanism as per existing sample complete all as specified and as directed by Engineer-in-Charge.
1
100
-
... More
M&L for Cradles, hexagonal/ rectangular, fabricated with galvanised steel wire 3.15 or 4 mm dia for underneath overhead lines fixed with poles incl all necessary accessories at various locations i.e., road crossings/ open ground etc., complete all as specified and as directed by Engineer-in-Charge.
0.5
53
-
... More
S&F Fluorescent retro-reflective tape of width not less than 50 mm, high grade quality of yellow/ Red colour fixed on pole including cleaning and removing of paint from existing pole surface complete all as specified and as directed by Engineer-in-Charge.
20
100
-
... More
S&F in replacement of non-drawout microprocessor-based (numerical), non-directional numerical overcurrent and earth fault protection relay complete with 3 Overcurrent (OC) elements, 1 Earth Fault (EF) element, and an Instantaneous (INST) high-set protection module including panel modification/ cutting if required, testing, integration, and commissioning, complete all as specified and directed by the Engineer-in-Charge. Note :- Relays shall be made available to suit as per existing type / Make for 11 KV VCB's / Control Panel.
1
53
-
... More
Deployment of manpower/ tools etc for Re-stretching / refixing the existing LT/HT OH Lines of existing ACSR conductor of any type and size including disconnecting binding wire on insulator, rebinding properly with 2 mm dia aluminium binding wire to avoid tension/ fitting bending of poles, complete all as specified and directed by Engineer-in-Charge.
10
10
-
... More
Deployment of manpower/ tools etc for Re-stretching / refixing the existing GI earth wire 4 mm dia on HT poles & including binding with 1.63 mm dia GI binding wire properly to avoid tension of poles, complete all as specified and directed by Engineer-in-Charge.
5
1
-
... More
M&L for trimming off branches of trees touching HT electric over head line by climbing up tree or using ladder at a height not less than 9.5 metre from ground level and making clear about 3 metres each side along the overhead line and removal of rubbish from site where directed not exceeding 50 metre complete all as specified and as directed by Engineer-in-Charge.
20
11
-
... More
M&L for mild steel screws, bolts (machine made) with hexagonal head at one end and screwed the other with washer and one hexagonal nut not exceeding 5 cm long and 5 to 10 mm dia of neck and taking down old one complete all as specified and as directed by Engineer-in-charge.
4
-
-
... More
M&L for cleaning of 2 pole/ 4 pole structure/ switch yard and cutting of grass/ bushes/ tree branches and throw out the debris from existing location and deposting where directed and carrying out the proper layout of incoming/ outgoing cables complete all as specified and directed by Engineer-in-Charge.
6
100
-
... More
S&F earth continuity conductor or main earthing lead of 32 x 6 mm copper strip, buried in ground or fixed to wall complete all as specified and as directed by Engineer-in-Charge.
15
53
-
... More
Disconnecting and taking out worn-out HT jumpers of any size/length from overhead lines or substations, including removing old binding wire/connectors from AB switches or DO fuse units, and replacing them with new ACSR Weasel conductor jumpers enclosed in colour-coded (R/Y/B) PVC sleeves including providing new bimetallic/substation connectors, aluminium binding wire, high-conductivity anti-corrosive contact jelly, safety earthing, and working at any height or structure type, complete all as specified and directed by the Engineer-in-Charge.
6
100
-
... More
M&L for earthing with galvanised steel earth electrode plate of size 600 mm x 600 mm x 6mm thick, buried directly in ground (earth pit not less than 2.25 metre deep below normal ground level) with top edge of the plate not less than 1.50 metre below normal ground level, connected to galvanised iron earth strip 32 x 6 mm upto test point with suitable GI nuts/ bolts and brazed properly up to main board including earth pit in cement concrete 1:2:4 type B-1 (using 20 mm graded stone aggregates), precast RCC cover in 1:2:4 reinforced with expanded metal, with suitable handle, excavation and earth work in any type of soil and including medium grade GI watering pipe 20mm bore with funnel wire mesh and light grade GI light grade strip protection pipe 40mm bore up to main board complete as shown in electrical plate No. 3 of MES schedule Part-I 2009, connected to earthing testing point and testing on completion including taking out existing unserviceable earthing complete all as specified and as directed.
2
53
-
... More
All as per serial item No. 83.00 here-in-before but using copper plate 600 mm x 600 mm x 3.15 mm and using 20 x 3 mm copper strip as earthing lead.
2
10
-
... More
M&L for earthing with galvanised steel earth electrode plate of size 600 mm x 600 mm x 6mm thick, buried directly in ground (earth pit not less than 2.25 metre deep below normal ground level) with top edge of the plate not less than 1.50 metre below normal ground level, connected to galvanised iron earth wire 4 mm dia (8 SWG) upto test point with suitable GI nuts/ bolts and brazed properly up to main board including earth pit in cement concrete 1:2:4 type B-1 (using 20 mm graded stone aggregates), precast RCC cover in 1:2:4 reinforced with expanded metal, with suitable handle, excavation and earth work in any type of soil and including medium grade GI watering pipe 20mm bore with funnel wire mesh and light grade GI light grade strip protection pipe 15 mm bore up to main board complete as shown in electrical plate No. 3 of MES schedule Part-I 2009, connected to earthing testing point and testing on completion including taking out existing unserviceable earthing complete all as specified and as directed.
2
1
-
... More
Note for 83.00 to 85.00:- 1. The units rate includes the cost of excavation & earth work in any type of soil, charcoal & salt in alternate layers, 20mm GI pipe (medium grade) for watering GI protection pipe (light grade) funnel wire mesh PCC chamber in PCC 1:3:6 type C-1 cast iron frame and 40mm thick RCC cover for pit etc & no extra payment will be made.
2. Rate quoted against items shall be inclusive of earthing lead and protection pipe upto 7.50 metre length.
-
-
-
... More
M&L for providing cable route markers, made up of Cast Iron, round shaped disc of 150 mm dia, 3 mm thick, embossed with marking 'HT CABLE', mounted on angle iron (25 x 3) mm of min 1 feet above ground level casted in PCC 1:2:4 block of size 150 x 150 x 200 mm complete and erected in ground parallel to the cable route complete all as specified and as directed by Engineer-in-Charge.
20
11
-
... More
Supply and Testing of HT busbar control panel board 11000 volt AC 3 Phase for outdoor installation Kisok type with sloping canopy fabricated out of steel sections ie CRCA sheet 3.15 mm thick, angle/channel and flat iron sections of suitable size with opening on front door in two halves fitted with handle and bold for pad lock. The panel door shutters fixed with stainless steel hinges, heavy duty and with door stoppers. The dooor opening not be less than 150 degree. The construction of panel board shall be, vermin proof IP 54 standard with phosphatised powder coating pating externally and internally to protect against corrosion. The panel shall be mounted on suitable size of PCC platform 1:2:4 and channel section having round clerance 60 cms from grounting bolts complete incl incoporated with busbar chammber with electrolytic grade aluminum strip with heat shrinkable sleeves with colour code supported on epoxy resin based insulators 3 strip of suitable length for current rating 150 amp complete all as specified and directed.
4
-
-
... More
Supply, installation, testing and commissioning of 11KV 630A switch disconnector outdoor panel for protection of various transformers . The switch shall use low pressure SF6 gas for current interruption and shall require no maintenance. Leakage rate shall not be over 0.1% per year, for life span of at least 30 years.It shall have three positions (closed, open and earthed). The switching device shall be suitable for three-phase systems operating at 12 kV and 50/60 Hz. The rated voltage shall be at least 12 kV. The short-time withstand current shall be 25 kA - 1 s / 12 kV. LBS Make dvepl/ lk /milestone.LBS panel should be provided with fuse trip assembly and HRC fuses of appropriate rating for protection of transformers. The operating mechanism should have following functions. a. Switch function:- Independent-operation closing by lever. Operating energy is provided by a compressed spring which, when released, causes the contacts to close. independent-operation opening by push-button (O) or trip units.b Earthing-switch function: Independent-operation closing and opening by lever. Operating energy is provided by a compressed spring which, when released, causes the contacts to open or close. c. Opening releases- shunt trip "Switch: The switch shall use low pressure SF6 gas for current interruption and shall require no maintenance. The switch enclosure shall be mounted horizontally within the cubicle and the position of the main and earthing contacts shall be clearly visible from the front of the cubicle. The position indicator shall be placed directly on the contact-operating shaft. The switch enclosures shall be made of cast epoxy resin. The mechanical endurance of the switch operating mechanisms shall ensure at least1000 operations class M1. LBS Panel: Medium voltage switchgear shall comply with the latest issues of the IEC recommendations: IEC 62271-200. Switchgear shall be Free standing, Floor mounted, metal enclosed suitable for Outdoor use. The frame of individual vertical panels shall be minimum 2 mm CRCA. Degree of protection shall not be less than IP55. All hardware shall be corrosion resistant. Busbar shall be high conductivity aluminum supported on insulators made of non-hygroscopic, non-inflammable material. Panel shall be provided with earth busbar of copper of suitable size rated for short time rating of switch board and Provision for receiving incoming or outgoing power cable through rear bottom entry. All metal surface shall be thoroughly cleaned, processed under 7 tank treatment. Make of Panel Lk/dvepl/Milestone.Panel shall be powder coated with final colour shade RAL 7032.
1
100
-
... More
Earthing of the Power Circuit: Cable earthing shall be carried out by an earthing switch with a short-circuit making capacity, in accordance with IEC 62271-102 recommendations. It shall be possible to operate the earthing switch when the switch or disconnector is open. Mechanical interlocking systems (rotating switch with 3 positions )shall be provided to prevent incorrect operations such as the closing of the earthing switch with the switch or disconnector in closed position.
-
-
-
... More
Control Wiring: The wiring shall be carried out using multi-strand copper conductor super flexible PVC insulated wires of 650/1100V Grade for AC Power. Control terminals shall be screw type for auxiliary wiring Minimum 10% spare terminals shall be provided for control circuit. Tests: Routine tests shall be carried out as per relevant standards at manufactures works.
-
-
-