Bidassist allows us to explore new opportunities across the whole world so as to support the growth of the business. It is designed in such a manner that if we need any kind of information about any government e-tender the Himachal Pradesh government has posted on its website, Bidassist provides the same in a very hassle-free manner. As BidAssist is designed as a very user-friendly website which helps us find the specific Himachal Pradesh etender we are looking for.
Jal Shakti Department - HPIPH Tender
Civil And Construction
Eprocure
Opening Date15 Jan 2024
Closing Date22 Jan 2024
Tender Amount₹ 7,54,95,427
Costs
EMD
₹ 7,87,454Document Cost
₹ 2,500Tender Fee
Refer Documents
Summary
Construction Of Lwss Amb Town In Tehsil Amb , Distt. Una (hp)
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_HPIPH_84034_1Bid Award Id
ViewTender No
EE-JSV-DIvision-Amb- Amrut02-8094-8194Tender Authority
Jal Shakti Department ViewPurchaser Address
-Website
http://hptenders.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Main Reservoir - Designing, Constructing, Testing & Commissioning (to be approved by the competent authority) RCC OHSR as per capacity given below at various stages/sites including excavation in foundation in all kinds of soil. including PCC (1:3:6) in foundation and M:30 design mix in bottom slab/raft ,walls and beams. And RCC (1:1.5:3) in roof slab/dome with provision of inspection path around the dome with all alied Civil Works such as c/o chamber for valves, refilling and disposing of surplus excavated earth with in all leads and lifts. The job also includes providing lowering, laying, erecting, hoisting and jointing of pipe assembly for inlet, outlet, overflow and scour pipe with bye pass arrangement consisting of GI / MS pipes special and valves of required classes and dia and all other accessories required such as MS ladders inside and outside, CI cowl type ventilator, M.S manhole covers with frames of heavy duty with proper locking arrangement, water level indicator. The tanks shall be hydraulically tested for water tightness, All works shall be conforming to relevant IS code. The cost of valves, be included in the rates of tanks .complete in all respects to the entire satisfaction of the Engineer-in-charge .The contractor shall provide 6 sets of approved drawing and design to the department including cost of site development required as per site conditions. (Refer to Data sheet No.2 A BCDE )
-
-
-
i) C/O RCC OHSR Tank of 2,70,000 Ltr. Capacity with 25 Mtr Staging Height at Amb Town
270000
-
-
ii) C/O RCC OHSR Tank of 70,000 Ltr. Capacity with 20 Mtr Staging Height at Node No B
70000
-
-
iii) C/O RCC OHSR Tank of 2,25,000 Ltr. Capacity with 20 Mtr Staging Height at Node No. D
225000
-
-
iv) C/O RCC OHSR Tank of 1,60,000 Ltr. Capacity with 20 Mtr Staging Height at Node No. C
160000
-
-
v) C/O RCC OHSR Tank of 1,15,000 Ltr. Capacity with 20 Mtr Staging Height at Node No. E
115000
-
-
Sector Reserviors:- Designing, Constructing, Testing & Commissioning (to be approved by the competent authority) RCC Circular under ground/partial under ground storage reservoirs as per capacity given below at various stages/sites including excavation in foundation in all kinds of soil. including PCC (1:3:6) in foundation and M:30 design mix in bottom slab/raft ,walls and beams. And RCC (1:1.5:3) in roof slab/dome with provision of inspection path around the dome with all alied Civil Works such as c/o chamber for valves, refilling and disposing of surplus excavated earth with in all leads and lifts. The job also includes providing lowering, laying, erecting, hoisting and jointing of pipe assembly for inlet, outlet, overflow and scour pipe with bye pass arrangement consisting of GI / MS pipes special and valves of required classes and dia and all other accessories required such as MS ladders inside and outside, CI cowl type ventilator, M.S manhole covers with frames of heavy duty with proper locking arrangement, water level indicator. The tanks shall be hydraulically tested for water tightness, All works shall be conforming to relevant IS code. The cost of valves,shall be included in the rates of tanks .complete in all respects to the entire satisfaction of the Engineer-in-charge .The contractor shall provide 6 sets of approved drawing and design to the department including cost of site development required as per site conditions. (Refer to Data sheet No.3 )
-
-
-
i) C/O RCC Collection Tank of 1,30,000 Ltr. Capacity at Node No.-1
130000
-
-
ii) C/O RCC Collection Tank of 1,60,000 Ltr. Capacity at Node No.-2
160000
-
-
iii) C/O RCC Collection Tank of 2,60,000 Ltr. Capacity at Node No.-3
260000
-
-
iv) C/O RCC UG SR Tank of 6,05,000 Ltr. Capacity at Node No.- A
605000
-
-
v) C/O RCC UG SR Tank of 2,35,000 Ltr. Capacity at Node No.- B
235000
-
-
EXCAVATION FOR :- Rising main , grvity main and distribution system
-
-
-
Excavation in foundation, trenches (for pipes & pits) upto all depths in all classification of earth work such as pick work, jumper work, saturated soil including bailing and pumping out water, blasting soft/ hard rock or chieselling soft/hard rock where blasting is prohibited in all lifts including trimming and dressing of sides, leveling of beds to correct grade i/c shoring /strutting , planking, timbering & dewatering wherever required, stacking the useable & unuseable material /soil separately & after laying jointing & testing of pipes, returning the useable soil in trenches in 15 cm layers including consolidating of such deposoited layer by ramming & watering & then disposing of all surplus excavated soil /unusable material as directed with in all leads & lifts Excluding restoration metalled surfaces to its original condition( Will be paid Separately) & including cost of diversion for traffic, night signals, fixing caution boards, crossing over trenches for access to houses, fencing etc. complete in all respects with in all leads & lifts as per directions of Engineer-in-charge. (Refer to Data sheet No. 6 )
13469.84
-
-
Laying, jointing and testing in trenches flanged GMS pipes (Medium grade) confirming to ISI specification : 1239--2004 including commissioning and cost of all fittings in respect of following diameters in Rising Main and Gravity main (Eath work in trenches to be measured and paid for separately) including entire carriage of material in all leads and lifts as per the directoon of the Engineer-in-charge.125 mm dia ( Medium Grade for Rising Main, Gravity main,distribution and fire brigade system Amb Twon)
-
-
-
i) 150 mm dia (MC)
4650
-
-
ii) 125 mm dia (MC)
12349
-
-
iii) 80 mm dia (MC)
1570
-
-
iv) 65 mm dia (MC)
884
-
-
Providing, laying, jointing and testing in trenches of Galvanized GMSERW zinc coated flanged pipes iof grade L-210 & L-290 excluding cost of flanged bends of all degrees conforming to IS/ISO 3183-2007 Grade A as per dimensions weight and test pressure mentioned below in a random length of 4m - 6m, The M.S. flanges are to be provided 1% of total joints as per table below conforming to IS: 6392-1971 (Latest upto date amendments) and welding of flanges with pipes as per IS: 816-1965 with a electrode as per IS: 814-1967 including required Nos. and size of M.S. Nuts and bolts as per IS: 1369-1967 and compressed asbestos fiber jointing gaskets sheet not less than 3 mm thick sas per IS: 2712-1965 & 99% butt welded joints by considering minimum three layers. The welding of flanges to be done on both faces in two layers on outer face + one layer on inner face to make the joints leak proof and to the entire satisfaction of the Engineer-in-charge. The laying of pipes should be conformed to IS: 5822-1994 (Earth work in trenches, MS flanges and butt welded joint to be measured and paid for seprately) . The pipe shall have zinc coating as per IS:4736 in factory latest with upto date ammendements. 200 mm dia 4.80 mm thick . (Refer to Data sheet No.5 )
-
-
-
i)2nd Stage: Rising main Stage Node-2 to 3 - 200 mm dia ,4.80 mm thick, L-210 (A) GMSERW pipe IS Code 3183 L 210 ( Flange table 5 )
2120
-
-
ii)Rising Main for Main 3rd Stage Node 3 to A- 200 mm dia ,4.80 mm thick, L-210 A GMSERW pipe IS Code 3183 L 210 ( Flange table 28 & 17 )
4500
-
-
Providing, Fixing & welding of M.S. flanges conforming to table as specified below of BIS- 6392-1971( Latest with upto date ammendments ) welding of M.S flanges on (Two layer on inner face and one layer on outer face of each flange) GMS pipe and bends on both ends ( The GMS pipe to be measured & paid for separately ) The welding of flanges confirming to IS 816-1998 with electrodes as per IS 814-1997. Prov. & fixed with nuts, bolts of required size confirming to IS 1364, providing and fixing 3 mm (minimum) thick compressed asbestos fibre / synthetic rubber gasket conforming relevant BIS code IS 2712-1965 ( The earth work in trenches to be measured and paid for seperately) all respect and including all kinds of leads and lifts and entire satisfaction of the Engineer-in-Charge.
-
-
-
i) 125 mm dia Table - 5
5
-
-
ii) 200 mm dia Table - 5
4
-
-
iii) 200 mm dia Table - 28
2
-
-
iv) 200 mm diaTable - 17
6
-
-
Providing Circumfrential butt welding joints to GMSERW/G.I pipe following dia with three layers on each end of welding using 3 mm and 4 mm dia electrodes after levelling the pipe ends according to relevent ISI specification and entire satisfaction of the Engineer-in-Charge i/c all leads and lifts. 200 mm dia.
-
-
-
200 mm dia GMSERW pipe Grade L-210 A
1092
-
-
150 mm dia GMS Pipe (MC)
775
-
-
125 mm dia GMS (MC)
2054
-
-
80 mm dia GMS (MC)
262
-
-
65 mm dia GMS (MC)
148
-
-
Submersible Pumping Machinery
-
-
-
Supply of 3 star arated Submersible pumping set of KSB/Calama/ /Johnson /Crompton/BS/Sabar/Oswal/Kirloskar make,confirming to latest relevents BIS.code -8034:1976. The pump should be fitted with Bronze impeller of suitable alloys suitable for handling clear water having greased packed bearings and shaft with wound stator on motor side and with soft protection sleeve on pump side ensuring better life for shaft coupled to submersible squirrel cage eletric induction motor of 3 star rating ( water proof type) of required HP and 2900/1450 RPM of reputed make conforming to BIS : 9283-1979 with upto date ammendements. totally dust and water proof for submersible ,duty isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed lubricated bearings and provided with stainless steel thrust bearing plate to with stand non vertical loads with minimum wear and tear. The poweer bearings and provided with stainless steel thrust bearing plate to with stand non vertical loads with minimum wear and tear .The power of electric motors should be atleast (+) 10% in excess of the maximum power required the pump/pumps in the operation range of (+) 10% and (-) 15% of the duty point head. It should also be fitted with a device to take up expansion of water with the heating of the motor. The pump set should be include water lavel gaurds,errection clamps,cable clips and depth gauge,sluice valve,NRV,common header and actuated valv etc. included. (Refer to Data sheet No. )
-
-
-
i) Booster stage 1st :- 30 HP Heavy duty VFD panel of Dantos / ABB/Siemens with Electronic Programmable Byepass System for the percolation well Suitable for Seamless intergration to the Advance cloud One VFd Panel for One pump for each Percolation Well 1 main +1Standby configuration.
-
-
-
ii)Booster stage 2 nd :-50 HP Heavy Duty VfD panel of Dantos/ ABB/ siemens with Electronic Programmable Byepass System for the Percolation well Suitable for seamless intergration to the advance cloud One VFD Panel for One Pump for each Percolation well 1 Main +1 Standby configuration
-
-
-
iii)Fully wired Automation panel consisting of smart Controller and Monitor all precess of the pump house, program the requried interlock suitable for seamless intergation to the Advance Cloud (2+2) ( for booster1st & 2nd)
-
-
-
iv) Non contact, high frequancy , high accuracy leval RADAR for parculation well .
-
-
-
v) Fully program linux based on line router for cloud connectivity data transfer bia MQTT/JSON protocol.
-
-
-
a) Booster 1st 13.46 LPS with head of 76.76 mtr-30 HP (2 No. set i/e 1 working 1 standby) T/well -1( 2X30 )
60
-
-
b) Booster 2nd 26.34 LPS with head of 76.17 mtr- 50 HP (2 No. set i/e 1 working 1 standby) T/well - 2 ( 2X50 )
100
-
-
PUMPING MACHINERY CENTRIFUGAL:- Supply , installation , testing and commissioning of energy efficient horizontal spindle ,horizontal / radial split casing / end ' suction ( back pull out arrangement).Single / double/ multi stage centrfugal pump suitqable for operation, in parallel of recommended make such as of Mather and Platt / KSB /kirloskar/ Beaconweir / confirming to BIS IS 1520-1980 with upto date ammendments, read with IS: 9137-1978 or latest edition suitable for lifting clear water for under mentioned characteristic with Bronze/Bronze with 2.5% nicked impellers, priming funnels of dia 405 mm casing ringing and shaft sleeves of Bronze/ steel,shaft of SS-410/IAS 1431 chrome plated with cast iron casing or as per manufacturer specification relevent to the technical parameter of NIT coupled directly through a flexible coupling on a common MS base plate squirrel cage induction motor TEFC type energy efficientminimum IE 2 compliance confirming to IS-12615-2018 with upto date ammendments of standard make such as kirloskar /BHEL /Crompton /NGEFF/ GEC/ Siemens/Jyoti/ABB/Marathon and suitable for operation on LT,50 cycles/second 3 Face AC elictric supply. The pump set should include water level guards, errection clamps ,cable,depth gauge,double loop earting ,NRV,common header Sluice valve and actuated valves of approved class including errection charges etc.The power eletric motor/Motors should be atleast (+ )10% in excess of the meximum power required by the pump /Pumps in the operation range of (+)10% and (- ) 15% of the duty point head .Thestarting current of the motor shall be limted to not more then 4.5 to 5 time of full load current including . (Daat sheet No )
-
-
-
i) Main stage 1st (Ward No.-8 & 9 :- 30 HP Heavy duty VFD panel of Dantos / ABB/Siemens with Electronic Programmable Byepass System for the lift scheme. Suitable for Seamless intergration to the Advance cloud 1 running and 1 standby configuration .
-
-
-
ii) Main stage 2nd :- 15 HP Heavy duty VFD panel of Dantos / ABB/Siemens with Electronic Programmable Byepass System for the lift scheme. Suitable for Seamless intergration to the Advance cloud 1 running and 1 standby configuration .
-
-
-
iii) Main stage 3rd :- 120 HP Heavy duty VFD panel of Dantos / ABB/Siemens with Electronic Programmable Byepass System for the lift scheme. Suitable for Seamless intergration to the Advance cloud 1 running and 1 standby configuration .
-
-
-
iv) Fully wired automation panel consisting of smart controler to control and monitior all process of the pump house, program the required interlocks, fully programmable SCADA system with local data logging,cloud connectivity,MQTT protocol, customised reprting and emailing package.Centralised SCADA should have in built IOT MQTT protocol with unlimted tags and all open protocol for field communication.The SCADA shall be communicating to remote devices and stations bia advance cloud system. The SCADA system should be capable of storing the historical data in a standard RDBMS and should be providing rear time data analytics,historical reports and trends, alarms as per the requirement of Engineering-in-charge of Jal Shakti department(3+3) 9for main stage 1st,2nd and 3rd)
-
-
-
v) Non contact, high frequancy , high accuracy leval RADAR for clear water tank
-
-
-
vi) Industrial grade PC with UPS for the installation of the SCADA, core i5 processor,16 GB RAM ,MS windows 10 pro, MS office,MS SQL data base ,lan & wifi interface, 3 years support.
-
-
-
vii) Industrial grade monitor suitable for interface with the PC. Sixe 32 in, fully edge to edge.
-
-
-
viii) Laser jet printer a4 size for taking the prints of the reports. HP/Samsung.
-
-
-
ix) Fully programmable, linux based online router for cloud connectivity. Data transfor bia MQTT/GSON protocol.
-
-
-
a ) Main Stage -1st (Ward No. 8 & 9) -:- 13.46 LPS with Head of 84.51 m - 2ZX30 HP (2Nos. Set.including 1 No Working & 1 Nos Stand By )
60
-
-
b)Main Stage 2nd - 26.34 LPS with Head of 22.07 m - 2X15 HP (2Nos. Set.including 1 No Working & 1 Nos Stand By )T
30
-
-
c)Main Stage 3rd - 26.34 LPS with Head of 168.10 m - 2X120 HP (2Nos. Set.including 1 No Working & 1 Nos Stand By )
240
-
-
Providing and fixing C.I Sluice valve double flang as per ISI : 14846-2000 with hand wheel of the following dia Complete in all respect within all leads and lifts.
-
-
-
i) 125 mm Dia.
1
-
-
Providing converision of wards for 24X7 water supply system on mode. (Refer to Data sheet No. 7 )
-
-
-
Providing fixing of enabied MULTITET/ Tarbine WOLUMANN type mechanical flow bulk meter specification of reputed make confirming to ISO 9001 certification with removale mechinism, having dry dial, megnetcally coupled, hermetically sealed totaled Class B as per ISO 4064( International Standareds) Meters must be pre-cquipped for AMR ( Automated Meter packing) capable of resisting pressure up to PN 16, PVC/Cast Iron strainer, fittings, cuttings,threading, plumbing and electrical accessories engineering with all leads and lifts as per direction of Engineer in-Charge.
-
-
-
i) 80 mm dia
3
-
-
ii) 100 mm dia
1
-
-
iii) 125 mm dia
3
-
-
iv) 200 mm dia
2
-
-
METAL BOX :- Providing fixing of MS Metal Sheet minimum 1.0 mm thick metallic Box size ( 30X30X30cm) bottom less with MS ANGLE ( 25X 25 X5 mm) less of 150 mm height properly anchored/grouted in ground with CC 1:2:4 ( Cement Concrte) as per specifications with LOCKING arrangments duly redoxide and paint on all side inside outside to house Bulk Flow meter with all leads and lifts as per direction of Engineer in-Charge.
9
-
-
Providing fixing of IOT enabled WOLTMANN type mechanical ISOLATION VALVE specification of reputed make conforming to ISO 9001 certification with removalbe mechanism, having dry dial, megnetcally coupled, hermetically sealed totaled Class B as per ISO 4064( International Standareds) Meters must be pre-cquipped for AMR ( Automated Meter packing) capable of resisting pressure up to PN 16, PVC/Cast Iron strainer, fittings, cuttings,threading, plumbing and electrical accessories engineering with all leads and lifts as per direction of Engineer in-Charge.
-
-
-
i) 80 mm dia
1
-
-
ii) 100 mm dia
3
-
-
iii) 125 mm dia
2
-
-
iv) 200 mm dia
2
-
-
Communication Devices:-
-
-
-
LORA UNIT: Providing fixing RTU ( Remote Terminal Unit) operated with 5 V Lilon battery for secured transfer of DATA from sensor/ Flowmeter with networking cellular LORA/ Ei-fi ethernet RF range-400 m-1000 m ( for LORA based RTU) Secured transmission of telemetry via MQTT/AMQP,/TTPS using TLS/DTLS/AES standreds including memory card for storing DATA for a minimum of 30 days in case of power failures/loss of connectivity complete in all respect with certification with all leads and lifts as per direction of Engineer-In-Charge.
9
-
-
LORA GATEWAY UNIT WITH NANO SIM :- Providing fixing DATA coommunication GATEWAY device with solar powered supply shell be measured and paid seperatly) for DATA acquisition from RTU and Communication through secured transmission iclemetry with standards protocol using LORA Wi-Fi /NBV Wi-Fi cellular GPRS ethent for connecting to Cload never for at lease 2 months DATA back up as per detailed specifications with all leads and lifts as per direction of Engineer-In-Charge.
9
-
-
Stop overflow less SR level based pump automation
9
-
-
Consumer Flow meter providing fixing enabied MULTITET/ Tarbine WOLUMANN type mechanical bulk flow meter specification of reputed make confirming to ISO 9001 certification with removale mechinism, having dry dial, megnetcally coupled, hermetically sealed totaled Class B as per ISO 4064( International Standareds) Meters must be pre-cquipped for AMR ( Automated Meter packing) capable of resisting pressure up to PN 16, PVC/Cast Iron strainer, fittings, cuttings,threading, plumbing and electrical accessories engineering with all leads and lifts as per direction of Engineer in-Charge.
-
-
-
i) 15 mm dia
2066
-
-
Pressure Sensor :- Providing fixing Pressure Sensor enable to transmit pressure having pressure range ( 0.1 to 60 bars) having minimium IP-67 protection from moist and harsh envinment capable of transmitting analog digital output 4-20 m A to Rs 485 Modbus RTU ( Remote Terminal Unit) operating temperature range of ( 40 C to 125 C ) with complete accessories in all respect calibration certificate with all leads and lifts as per direction of Engineer in-Charge.
9
-
-
TV DISPLAY UNIT in GP :- Providig fixing LED TV DISPLAY UNIT minimum 43" cm screen of reputed make/ BRAND ( SAMSUNG,LG,SONI,PANNSONIC) approved from Himachal Pradesh State electronic corporation ( DISPLAY RESOLUTION) 1920X1080 full HD brightness : 32" 240 cd/m2, responce time 12 ms or less connectivity, 12XHDMI in, USB 2.0 X Components, IXR 145,IX RS 232 built in wi-Fi, Screen mirroring audio output RMS :10 Watt X 2 or Better Warranty 3 Years mounted to the wall with fixing stands complete set with all accessories wiring cables, electrical fittings networking cable Inking with networking devices with all leads and lifts as per direction of Engineer in-Charge.
1
-
-
SOLAR PANEL with Lead Acid Battery :- Providing fixing Reputred make and MNER approved Solar Panel power Supply system to pressure sensor/Communication GATEWAYdecice with 12 V-10 Watt SOLAR PANEL, with 7.5 Ah ACID Battery properly mounted onGI pipe not less then 40 mm dia (Light Class) minimum 2.0 m Height. The battery shall be properly fixed and encaged in a metal Box duly painted on all side ( inside,outside) having locking arrangments complete in all respect wiring to the nearest scnsor/communication GATEWAY device with all leads and lifts as per direction of Engineer in-Charge.
9
-
-
SIGNAL IMPROVING DEVICE
1
-
-
Wiring for light/Fan point/Exhaust fan point/call bell point with 1.5 Sq.mm PVC insulated copper conductor cable in surface/recessed PVC conduct at required including carriage of all material within all leads and lifts.Group "C"
30
-
-
Wiring for light/power plug with 2 x 4 Sq.mm PVC insulated copper conductor or single core cable in surface/recessed steel conduit alongwith 1 No. 2.24 mm dia bare copper wire for loop earthing as required including carriage of materials within all leads and lifts.
160
-
-
Wiring for circuit wiring with 2 x 2.5 Sq.mm PVC insulated copper conductor single core cable in surface/recessed steel conduit as required including carriage of material within all leads and lifts.
120
-
-
Wiring for sub-main wiring with the following size of copper conductor single core cable in surface/recessed steel conduit as required including carriage of materials upto all leads and lifts.
-
-
-
i) 2x6 Sq.mm
12
-
-
Supplying and fixing metal box of 180 x 100 x 60mm deep (Nominal size) on surface/recess with suitable size phonolic leminated sheet cover fixing 3 pim 15/16 amps socket tumber/piano type switch connections painting etc. including carriage of materials within all leads and lifts.
6
-
-
Supplying and fixing backellite batten/angle holder including connection as required.
10
-
-
Providing, installing, testing and commissioning of ceiling fan and regulator including wiring the rod of standard length (upto 30cm) with 1.5 Sqmm PVC insulated copper conductor single core cabe etc. as required sweep type. Cat. A
8
-
-
Providing, installation, testing and commissioning of prewired flourscent tube fitting complete with ballast, starter and capactors but excluding flourscent tube rod, suitable to operate on 230 volts single phase A.C.supply directly on surface with copper wiring as required including carriage of materials within all leads and lifts tube fixture 1 x 36 watt Box type Category "A".
10
-
-
Supplying and fixing 40Amps to 63 Amps rating 240 Volts "L" series miniature circuit breaker of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required including carriage of material within all leads and lifts. Category- A, 63 Amps.
4
-
-
Supplying and fixing of following way single pole and neutral sheet steel MCB distribution board 240 volts on surface/recessed completed with tinned, copper busher neutral link, earth bar, detachable gland plate inter -connections, including painting, earthing etc. as required Bus bar 8 way.
4
-
-
Supplying and fixing 5 Amps to 32 Amps rating 240 volts, G series miniature circuit breaker of following poles in the existing MCB, DB complete with connections testing and commissioning etc. as required . Category "A", single pole.
12
-
-
Earthing with G.I. pipe earth, pipe 4.5 mtrs length, 40mm dia including accessories and providing masonry enclousres with cover plate having locking arrangement and watering pipe etc.( but without charcal coke and salt) complete as required including carriage of materials within all leads and lifts.
2
-
-
Extra using salt and charcoal for pipe earth electrode as required, including carriage of materials within all leads and lifts.
2
-
-
Supplying and laying 6 Sqmm G.I.wire at 0.50 mtr below ground level for conductor earth electrode, including soldering etc. as required including carriage of materials within all leads and lifts.
40
-
-
Providing, fixing & testing Street Light Fixture with CFL of 36 watt, copper ballast, G.I. Pipe bracket, complete in all respects.
10
-
-
Providing and fixing of fire hydrants Kartar make 63 mm double headed fire hydrants landing valve as per IS:5290, Type 'B' ISI with ABS Blank up and chain complete in all respect with in all leads and lifts as per the direction of the Engineer-in-Charge.(Refer to Data sheet No. 8 )
8
-
-