Bidassist allows us to explore new opportunities across the whole world so as to support the growth of the business. It is designed in such a manner that if we need any kind of information about any government e-tender the Himachal Pradesh government has posted on its website, Bidassist provides the same in a very hassle-free manner. As BidAssist is designed as a very user-friendly website which helps us find the specific Himachal Pradesh etender we are looking for.
Himachal Pradesh Irrigation And Public Health Department - HPIPH Tender
Civil And Construction
Water Storage And Supply
Eprocure
Opening Date3 Feb 2025
Closing Date13 Feb 2025
Tender Amount₹ 7,69,586
Costs
EMD
₹ 15,392Document Cost
₹ 500Tender Fee
Refer Documents
Summary
Remodeling Of Old Tube Well In Indora Constituency In Tehsil Indora Tw Dah Kathgarh Tw Lodhwan 1
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2025_HPIPH_99253_1Tender No
EE-JSV-IND-8100-50 dated 03-01-2025Tender Authority
Himachal Pradesh Irrigation And Public Health Department ViewPurchaser Address
-Website
http://http://hpiph.org/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
... More
No. of pump required 1.00 No. working at a time
-
-
-
... More
Location of the site of installation of machinery. The site is located at a distance of 27 KM from Pathankot (chakki) Railway station by road & 0.100 KM on head load (for the installation of both machineries.
-
-
-
... More
The Altitude of installation. The altitude of place is 465.00 mtrs above MSL
-
-
-
... More
Type of current. AC Three phase supply with
-
-
-
... More
Rate Voltage 415+ 10%
-
-
-
... More
Type of water and its source Clear water (Tube well)
-
-
-
... More
Charactristics of water. -
-
-
-
... More
a)Ambient Temperature dig.c 20 dig. C
-
-
-
... More
b)Turbidity NTU 113 NTU
-
-
-
... More
c)Hardness260Mg/Ltrs(as CaCO3) 540 Mg/ltr
-
-
-
... More
d) PH 6.5 to 8.5
-
-
-
... More
e) TDS 540PPM
-
-
-
... More
f)Other -
-
-
-
... More
Depth of T/ Well 140.00 mtrs
-
-
-
... More
LWL in T/Well 55.00 mtrs.
-
-
-
... More
Center line level of Pump 55.00 mtrs
-
-
-
... More
Discharge level of highest point 133.00 mtrs
-
-
-
... More
Static head in Mrs 78.00 mtrs.
-
-
-
... More
Length of R/Main 356 mtrs.
-
-
-
... More
Dia of Rising main 150 MM dia MSERW pipe 4.80mm thickness
-
-
-
... More
No of working hours per day 20 Hours
-
-
-
... More
Limit of pump operation. (-) 15 % (+) 10% of total head
-
-
-
... More
R.P.M. of pumping set. 2900 RPM
-
-
-
... More
Test run. 8 Hours continueously for 7 days
-
-
-
... More
Supply , Installation, Testing and Commissioning of Fully Automatic LT Panel for Submersible pump made out of 16 Gauge sheet powder coated dust and veremin proof wall mounted and front opering door type switch board with copper insulated wiring suitable to operate 1 No. pump of rating 30 HP automatically through Variable Frequency Drive Starter. Starter should be capable to handle all the faults like short circuit, over current, under current, over voltage, under voltage, dry pump protection. It should get on and off command automatically from PLC and HMI. Monitoring and controlling of Pump running and tripping status should be monitored and controlled remotely through IOT enabled device. Access should be given to 3 users. Reputed make.
1
-
-
... More
Energy saving Variable frequency drive starter of 30 HP Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to control the frequecy of pumps through out the operation and also should be capable to maintain the power factor of the system within acceptable limits. It should be able to withstand ambient temperature 50 Degree celcius without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make:- L&T/Conserve/Schmeder/Aarmation1 No. 3 (ii) Main incomer MCCB of suitable capacity of L&T/ Schmeder/ABB/Siemens make on the coming feeder for pumping set confirming to BIS-2516-1985 ( Latest edition) 1 No. 3(iii) LED Three phase inicating lamps complete with logged switches for individual motore confirming to BIS 3452 ( Part I &II) latest with upto date amendments ( 1 No. ) 3(iv) LED On/Off Lincommer MCCB with proper short circuit capability for both the starters make L&T / Schinieder/ ABB ( 1 No. ) 3(v) On / Off & Trip indicator and push button, control and power wiring Power capacitor ,Cooling fan 230 VAC Control terminal , Buss Bar i.e. Bolt , insulator etc ( 1 No. ) 3( v) Selector switch for Auto and Manual Oparation 1 No. 3 (vi) Input Choke of required HP for Energy saving variable frequencty Starter which shoud be installed at the input of Energy saving variable frenqencty starter, so that there whould be proper protection in case of any voltage surge and distortons 2 No. 3 (vii) Control Transformer Make Surge supressor device with isolating MCCB to circunate the power surges due to lightening and system surges 1 No. 3 (viii) Power and Control Wiring and Busbar 1 No. 3(ix) Installation, commissioning and Software Development 1 NO. 3 (x) Surge supressor debvice with Isolating MCCB toeleminate the power surge due to lightening and system surges 1 o. 3 (xi) Power quality monitoring & controlling relay with Control Contactor to safeguard Electronic and Electric elements 1 No. 3 (xii) Independent Cont4rol Panel with stiwth Fuse Unit and Fuses fo Suitable Amperage to eliminate the Kit Kat fuses of HPSEB Make Aarmaton/Siemens/ Schnieder/ L&T 1 No.Automation System for Unmannede Oparatins with SCADA features, PLC, HMI and Level Sensor :- (i) PLC (Programmable logic controller) with appropriate digital and analog and inpute and output to give automatic command to Star Deltar Starer Panel energy saving Variable Freqency Starter Panel Make Aarmation Electric Bechoff Automation/ Rockwell Automatin 1 No. (ii) Electronicrelay card & channel 1 No. (iii) SMPS 4.5 amps to energise PLC system 1 No. (iv) HIMI (Human Machine Interface) 7" display for Monotring and Controllling of Submersibnle pumps Make : Aarmation Electric/ Bechoff Automation / Roackwell 1 No. (v) Conrol MCB for Automation System 1 No. (vi) Level Sensor to indicate the water level of tank remotely 1 No. (vii) Shielded Data Cable for Communation of Level Snsor with PLC 1 No. (viii) Supply of Mobile App (Android IOS) with User ID and Password to monitor and control the pumping oparation from Mobile for 3 users Make Aarmation Electric/ Bechoff Automation Rock well Automation (ix) Could Gate way for Data Clouding to Server 1 No. (x) SCADA soft ware to be installed in Laptop/PC on remotely monitor and control the operation of pumps and also to anysis the pump start and stop history logging fuilt starter, fault history, Power quality Parameters like PE Current Voltage KWH THD etc Make Aarmation electric/ Rockwell Automation Rockwell 1 No. (xi) Cloud space for data storae at cloud/ server 1 No. (xii) Inatallation Commissioning and Software Development.
1
-
-
... More
Supply of Kirloskar/ Kilburn/Leader make Cast iron class PN 1.60 double flanged swing check type reflux valve having bypass arrangement equal to dia of Risng main i.e. 150mm shall be suitable for withstanding nominal seat pressure of 16.32 Kg/Cm2 as per BIS 5312-1984 Part-II.
1
-
-
... More
Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/Finolex/ Grandlay/ Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment /accessories such as thimbles ,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
-
-
-
... More
On supply side of 3½ core coper cable 10 mm^2 ( From HPSEB Meter to Switch & Starter).
12
-
-
... More
On motor side 3 core flat joint less copper cable of size 6 mm^2 ( From Switch & Starter to Motor) pump installed in the bore.
115
-
-
... More
Supply of standarad make 100 mm dia circular/square dial pressure gauge of suitable range Fiebeg/Bourden/ Precision make with all accessories such as stop cock,copper tubing etc. conforming to BIS 3624-1987 latest with up to date ammendments.
1
-
-
... More
Laying, Jointing and Testing of G.I. pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set . The pipe shall conform to relevant BIS codes & capable of with standing the feild test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. The pipe material shall conform to relevant BIS Code and capable of with standing FTP equal to 1.5 times the operating pressure the complete arrangement shall compromise of
-
-
-
... More
Delivery Pipe …...mm dia ( size to be specified by the tenderer)
45
-
-
... More
P/L double loop earthing with copper plate 600x600x3mm thick electrode complete with material such charcoal, common salt, GI pipes, thimbles, nuts & bolts, digging of pits, GI wiring & 25x5mm copper strips of required capacity conforming to BIS 3043-1987 latest with upto date ammendments for above motor & other electrical equipment.
1
-
-
... More
Errection of all equipments including cost of tees, bends tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
1
-
-
... More
Rising main Excavation in foundation treanches(Pipe & Pits) up to all depths in all classification of earth work such as pick work,jumper work,saturated soil including bailing or pumping out water,blasting soft /hard rock where blasting is prohibited in all lifts including trimming & dressing of sides leveling of beds to correct grade i/c shoring/strutting planking,timbering & dewatering wherever required stacking the usable & unusable material/soil separately & after laying,jointing & testing of pipes,returning the useable soil in trenches in 15cm layers including consolidating of such deposited layer by raming & watering & then disposing of all surplus excavated soil/unusable material as directed with in all leads & lifts including restoration of unmetalled surface to its original condition & including cost of diversion for traffic,night signals,fixing caution boards,crossing over trenches for access to houses,fencing etc.completein all respects with in all leads & lifts as per directions of Engineer-in-Charge.
216.27
-
-
... More
Laying, jointing & testing in trenches to be levelled to grade, BIS marked GI flanged pipes confirming to BIS:1239 (latest with upto date ammendments) of following mm dia (Medium class) duly flanged every 5th pipe. With intermediate butt welded joints including the cost of bends/short pieces made from parent tubes of diferent degrees cutting welding and jointing with flanges conforming to tables as specified below of BIS: 6392 (latest with upto date ammendments) of following Diameter (medium Class) with 80% circumference butt welder joint and 20% intermediate flange joint welded at both ends as per BIS:816 (latest with upto date ammendments) with electrodes confirming to BIS 814 (latest with upto date ammendments) & provided with nuts and bolts BIS: 1369 (latest with upto date ammendments) of required sizes 4 mm thick champion make compressed asbestos fiber gasket or synthetic rubber gasket confirming to BIS:2712 (latest with upto date ammendments) & approved specifications as per site conditions including flushing, cleaning & hydraulic testing complete to the best satisfaction of Engineer-in-charge.The Cost of Earth work in trenches and the cost of providing flanges i/c nuts & bolts & gasket will be measured and paid for seperately.
-
-
-
... More
150 mm Dia ( Medium Class) 4.80mm thick
356
-
-
... More
Providing , welding and fixing of M.S. flanges conforming to following tables as per IS 6392-1971 (Latest with up to date amendments) with plain end MSERW pipe /GI pipe by two layers on outer faces and one layers on inner face to make the joint leak proof (The cost of providing and laying of MSERW /GI pipes and butt welded joint to be measured and paid for separately). The welding of flanges should conform to IS: 816-1969 with electrodes as per IS: 814-1991 and required number of nuts and bolts conforming to IS 1364 including cost of gasket sheet nuts & bolts. The thickness of gasket sheet not less then 3.00mm conforming to IS 2712-1998. The work shall be done to the entire satisfaction of Engineer in Charge with in all leads and lifts.
-
-
-
... More
150mm dia (MS flange) table-5
12
-
-
... More
Test run. 8 Hours continueously for 7 days
-
-
-
Evaluation Notes How It Works ?