Himachal Pradesh Irrigation And Public Health Department Tender
Bidassist allows us to explore new opportunities across the whole world so as to support the growth of the business. It is designed in such a manner that if we need any kind of information about any government e-tender the Himachal Pradesh government has posted on its website, Bidassist provides the same in a very hassle-free manner. As BidAssist is designed as a very user-friendly website which helps us find the specific Himachal Pradesh etender we are looking for.
Himachal Pradesh Irrigation And Public Health Department - HPIPH Tender
Civil And Construction
Water Storage And Supply
Eprocure
Opening Date11 Dec 2024
Closing Soon20 Dec 2024
Tender Amount₹ 67,77,304
Costs
EMD
₹ 1,00,273Document Cost
₹ 800Tender Fee
Refer Documents
Summary
Lis To Bami Nallah In Gp Hurla, Naresh And Diyar Tehsil Bhunter.h.p
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_HPIPH_96466_1Tender No
LIS Bami Nallah NIT No-11082-11181 dt 11/12/2024Tender Authority
Himachal Pradesh Irrigation And Public Health Department ViewPurchaser Address
-Website
http://http://hpiph.org/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Foundations, footings, bases of columns and the like and mass concrete complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
37.86
-
-
... More
Stone/Boulder filling behind the R/Wall ,also under floor etc.in all leads & lifts complete in all respect & with entire satisfaction of Engineer-in-Charge
13.13
-
-
... More
Providing and laying cement concrete 1:4:8 ( 1cement: 4 Sand : 8 graded stone aggregate, 40mm nominal size) and curing complete excluding cost of centring and shuttering in foundation and plinth complete in all respects with in all leads and lifts as per direction of Engineer in charge.
16.24
-
-
... More
White Glazed tiles 6 mm thick in ,skirting,riser or steps & dedo on 12 mm thick cement plaster in 1:3 (1 cement:3 Sand)& Joined with white cement slurry complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
98.77
-
-
... More
15 mm thick cement plaster in single coat on fair side of RCC/BRICK/Stone masonary for interior plastering 1:6 (1 cement:6 sand) complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
332.58
-
-
... More
Distempering two coats with oil bond distemper of approved brand and manufacture and of required shade complete in all respect as per direction of Engineer -in - Charge
429.39
-
-
... More
Providing and fixing panelled glazed or panelled and glazed shutters for doors, windows and clerestory windows, including ISI marked M.S. Pressed butt hinges bright finished or required size with necessary screws,excluding panelling which will be pad for separately ,all complete as per direction of Engineer-in-Charge.
13.67
-
-
... More
Painting two coats (excluding priming coat) over new wood and wood based surfaces,with ready mixed paint to give an even shade including cleaningthe surface of dirt ,dust and other foreign matters sand papering and stopping with readymade paint other than white complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
75.95
-
-
... More
Structural steel work in single section ,fixed with or with out connecting plate ,including cutting hoisting,fixing in position & applying priming coat of approved steel primer all complete as specified & directed by the Engineer-in -Charge.
709.76
-
-
... More
Hydraulic Excavator 0.9 cum bucket capacity @ 60 cum per hour complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
5
-
-
... More
Providing tor steel reinforcement for reinforced cement concrete work including bending binding and placing in position complete including the cost of binding wire complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
702
-
-
... More
Electrical work
-
-
-
... More
Wiring for light point / fan point / exhaust fan / call bell pointwith 1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit and earthing the light point with 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable as required. Group-A
7
-
-
... More
Wiring for Circuit/sub-main with following size PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed PVC conduit along with 1 No. HRFRLS/PVC insulated single core copper conductor cable of same size for earthing as required.
-
-
-
... More
2x1.5 sqmm.
80
-
-
... More
2x2.50 sqmm.
70
-
-
... More
Supplying and fixing following rating Piano-type switch /socket on the existing switch box / cover including connections etc. as required with complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
-
-
-
... More
5 pin 5/ 6 Amps socket outlet, porcelain base/ piano type.
6
-
-
... More
S.P. 5/ 6 Amps one way switch, piano type.
6
-
-
... More
6 pin 15/ 16 Amps socket outlet, porcelain base/ piano type.
6
-
-
... More
S.P. 15/ 16 Amps one way switch,Porcelain base/ piano type.
6
-
-
... More
Supplying & fixing wooden box of following sizes (nominal size) on surface or in recess suitable for fixing phenolic laminated sheet cover in front including painting etc. as required with complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
-
-
-
... More
MODULE OF 200 mm x 150 mm size
2
-
-
... More
MODULE OF 125 mm x 125 mm size
3
-
-
... More
Supplying and fixing ceilling rose on existing junction including connection complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
5
-
-
... More
Supplying and fixing brass batten/angle holder including connection complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
4
-
-
... More
Supplying and fixing 6 AMPs to 32 Ampare rating 240 volts, L series miniature circuit breaker of following poles in the exixting MCBDB complete with connection,testing and commissioning etc. as required Cat-A(Single pole)
6
-
-
... More
Supplying and fixing following way single pole and neutral ,sheet MCB distribution board 240 volts,surface/recess,complete with tinned copper busbar ,netural link earthbar ,dibnbar, detachable gland plates ,inter connection i/c painting earthing etc. as required busbar 12 way as required with complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
1
-
-
... More
Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required with complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
-
-
-
... More
63 Amps. Cat-A.
1
-
-
... More
Supplying and fixing of following size of PVC casing and capping on surface as required:-
-
-
-
... More
25mmx15mm
20
-
-
... More
Supplying and fixing of casing Pin packet complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
3
-
-
... More
Supplying and fixing of casing of PVC Gitti packet complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
3
-
-
... More
Supplying and fixing of Syska make LED tube fixture 20 watt complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
4
-
-
... More
Installation of Pumping Machinery
-
-
-
... More
Raw water stage: Installation ,Varnishing & Testing of motor and pumps suitable raw water submersible pumpset type KSB make KRTK150-315/126 with 12.5 KW motor capable of handling 6000 PPM turbidity of KSB/all approved make conforming to latest BIS code. The pump shall be fitted with single vane impeller of suitable alloy for handling raw water as per IS 5669-1970 having oil/grease packed bearings and stainless steel shaft, wound stator on motor side with shaft protection sleeves on pump side ensuring better life for shaft . The impeller of pump shall be directly mounted on extended submersible sq cage motor shaft conf to BIS 9238-1979 with up to date amendments of 1450(N) RPM, totally dust and weather proof with detach able pump casing for easy inspection with double mechanical seal, grease/ oil lubricated bearings and provided with stainless steel thrust bearing plate to withstand vertical loads with minimum wear and tear,It should be fitted with device to take up expanion of water on heating of motor & suitable for operation on 415 +/- 10% volts 3 Phase 50 C/S AC supply. The power of motor should be at least 10% in excess of maximum power required by the pump in complete operating range with mounting stand/ duck foot bend, steel guide wire with mounting hook, lowering chain and standard accessories as supplied by the manufacturers complete, suitable for fulfilling the following requirements:-
Total Dynamic head: 10.89 mtrs. with suction head up to 5 mtrs.
Total Discharge: 97.30LPS (48.65LPS for each pump)
Dia of rising main: 350mm Length of rising main: 60 mtrs.
Altitude above MSL: 950Mtr Pumping hours: 20 LWL in the well/source:-1046.50 mtrs.
Pumpshaft level:- 1048 mtrs.
Level at discharge point:- 1056.50 mtrs.
Suction lift:- (-)1.50 mtrs.
Discharge Head:- 8.50 mtrs.
Static head: 8.50 mtrs.
Temrature: 20°centigrade
2
-
-
... More
Providing and installation of control panel as per KSB specifications and having protection of motor on occurance of faults (triping on occurance of fault(s) i.e. Moisture, high motor temperature, dry running, reverse rotation, single phasing, voltage imbalance, overload and short circuit) and indiation thereof by glowing fault lamp, for motors above 30KW another protection of Mechanical seal failure shall also be provided in addition to above protections, fitted with required accessories as per manufacturer standard practice.
2
-
-
... More
fixing of Double flanged Mechneil/Leader/Pelican/Bhel/Gled/Kirloskar/Kartar make Cast iron sluice valve in delivery side confirming to class IS:780 PN 1.0, one size higher than delivery outlet size of pump
2
-
-
... More
fixing of Double flanged Mechneil/Leader/Pelican/Bhel/Gled/Kirloskar/Kartar make Cast iron swing check type reflux valve in delivery side confirming to class IS:5312 PN 1.0, one size higher than delivery outlet size of pump
2
-
-
... More
Providing and laying PVC insulated armoured copper conductor cable Siemens/Gloster/IEC/ICC/EICO/National/Grandly make of suitable size and suitable for motor offered under item no.8 complete with flexible pipe and couplers from HPSEB meter to panel, switch, starter complete job. The type and size shall be subject to approval of Electrical authorities and in case of its non acceptance the same shall be replaced free of cost by the tenderer supply side as required
1
-
-
... More
fixing Double flanged Mechneil/Leader/Pelican/Bhel/Gled/Kirloskar/Kartar make Cast iron swing check type reflux valve in delivery side confirming to class IS:5312 PN 1.0, equal to dia of rising main i.e. 350mm dia
1
-
-
... More
Providing and laying PVC insulated round copper conducter cable of suitable size suitable for motor offered under item no. 8 complete having suitable cores to fulfill requirement of star delta starter and protection /controls from panel to motor 10 mtrs. cable per set shall be supplied free of cost ( cost inclusive in cost of pump set) additional lehgth shall be measured to and paid seperately. cost to be quoted for additional length over and above free cable of 10 mtr/pumpset
20
-
-
... More
Providing and fixing 100mm dial pressure guage of Fiebig/Bourden make having range 0-7Kg/cm² with copper tubing, stop cock and allied accessories as per IS:3624-1987 latest with upto date amendments
2
-
-
... More
Providing and fixing MS/MSERW pipe of suitable size as detailed here under for delivery and common header complete in all respects with all specials like bends, tees, reducers, increasers, companion flanges including rubber/asbestos gaskets of minimum 3mm thickness as per IS 1364-1983. The pipes shall be as per relevant IS code, the flanges shall be compatible with pumps, valvs etc. and sutable for withstanding 1.5 times the working pressure likely to be induced as stipulated against item no. 8 above. Delivery side: pipe of one step higher than delivery of pump (3x10 Rmtr.) Common header 350mm dia (5 rmtr.)
1
-
-
... More
Providing and fixing of L&T/Havells make shunt capacitor of suitable rating confirming to IS:2834-1986 latest with upto date amendments to raise power factor at site from 0.85 to 0.95, complete with required cable for direct connection to control panel and fittings.
2
-
-
... More
Providing and fixing of cable for water level guard, supporting clamps, cable clips of required size.
1
-
-
... More
1st Stage:- Installation ,Varnishing & Testing of motor and pumps horizontal spindle, horizontal radial split casing multistage centrifugal pump of Kirloskar make Model RKBF 100/23E8 Stages Pump or combination of pump in seris/parallel of recommended pumps such as per BIS 1520-1980 with upto date amendments, read with IS 9137-1978 or latest edition suitable for lifting water for under mentioned characteristics with bronze impellers/priming funnels, casing ring and shaft sleeves of bronze,shaft of steel grade 4508 FN8 with cast iron casing coupled directly through a flexible coupling and common MS/Cast steel base plateform ( base plate to be from the manufactturer of pumping unit only) to slip ring/squirrel cage screen protented drip proof induction motor of 250KW /335 HP Kirloskar make suitable for operation on 400(+/-) 10% volts, 50cycles/second, 3 phase AC electric supply. The power of electric motor/motors should be designed +10% in excess of the maximum power required by the pump/pumps inthe operation rangeof (+) 10% and (-) 15% of duty point head. The motor/motors a per IS 325-1978 with uo to date amendments read with IS 900-1972. It should include cost of bearing nuts, bolts and painting etc. and should meet the following requirement:
Discharge: 32.43 LPS for each pump Total Dynamic head: 464.52 mtrs.
a) LWL in sump well: 1054.50 mtrs.
b) Shaft level: 1053.00 mtrs.
c) Level at discharge point: 1507.00 mtrs.
d) Suction lift : -ve 1.50 mtrs.
e) Discharge head: 454 mtrs.
f) Static head: 454 mtrs.
Rising main: a) Length 1840 mtrs 350mm dia
Pumping hours: 20
Altitude of installation above MSL: 1000.00 mtrs.
Characteristics of water: Raw water with turbidity up to 3000 PPM Temprature : 20 degree centigrade. (Note:- All three pumps sets will run parallel to lift total discharge of 97.30LPS)
3
-
-
... More
Providing ICTP main switch with HRC fuses of Kilburn/ L&T/Siemens/Standard/ Havells make and having capacity 30% extra of the operational rating as per IS: 4064-1978 with up to date amendments, immediately after the power meter of the HPSEBL.
3
-
-
... More
"Providing MS sheet 16G steel fabricated floor mounted closed(almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm duly painted with steel sheet of 16 gauge comprising and capable of mounting the following accessories within all internal connections. All the accessories should be suitable for the proposed pumping machinery at item No.19 above and to the entire satisfaction of HPSEB authorities. The same shall have to be replaced with out extra cost if recommended by HPSEB authorities
"
3
-
-
... More
"a) OCB/MCCB of MEI/Havels/ standard make and of suitable capacity for offered motor on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage released as per relevent IS code with upto date ammendments
"
3
-
-
... More
"j) Digital 100mm dia circular dial A.C.supply flush ammeter of AE/IMP/Havells make of suitable range with selector switches and CTS operated as per IS:L1248(P-II) .183 with upto date ammendments
"
3
-
-
... More
"k) Capacitor of Crompton/L&T/NGEP/Mechneil/ BHEL/GEC make as per 15:2834:1986 with upto date ammendments, to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rting according to H.P.offered including cables as per relevant ISI code (of siemens/clocter.IEC make )from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per Is:4064:1978 with upto date ammendments
"
3
-
-
... More
"l) Providing suitable oil immersed starter delta/direct on line/auto transformer/. starter rotor starter of MEI/.Kilburn/Jyoti /L&T/Siemens make as per IS:8544:1979 with upto date ammendments for squirrel cage/slip ring motor mounted on panel board with magnetic type over-load release and dashpot, time lag, under voltage release with or without initial oil filling as the case may be with single phae preventor as per IS:1248( P-V) 1983 with upto date ammendments
"
3
-
-
... More
"m) Providng Digital hour run meter of recommended make and suitable capacity as per IS:722(latest edition.) complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
"
3
-
-
... More
"n) Providing antivibration pads under the pumps and motors of suitablesize for the above pumping machinery as per IS:6337:1971.complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
"
3
-
-
... More
"b) Earth leakage circuit breaker of recommended make (Kilburn/L&T/MEI/GEC) as per IS:2516:1977 with upto date ammendments of suitable range which should have control box, operation, handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the ciruit breaking for cover current protection. The circuit should be equipped with magnet thermal release with metallic tap etc, it should also be fitted with earth fault for tripping of breaker on occurnce of earth fault on off breaker load side end. complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
"
3
-
-
... More
"c) The voltage monitor relay of AE/MEI/L&T/Havells make three phase with all protection and usual indicator and electric siren against single phasing,low voltage,high voltage, reverse phasing, over loading and phase voltage difference as per IS:3482 (latest edition) complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
"
3
-
-
... More
"d) Digital 100 mm diameter circular dial A.C.supply voltmeter of recommended make AE/IMP/Havells of suitable range with selector switches as per IS:4064:1978 with upto date ammendments complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
"
1
-
-
... More
"e) Digital Power factor meter of standard make AE/L&T/IMP/Havells as per relevant IS code with upto dateammendments complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
"
1
-
-
... More
"f) Digital Frequencey meter of standard makeAE/L&T/IMP/Havells as per relvant IS code with uptodate ammendments complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
"
1
-
-
... More
"g) Bus bar chamber having three copper bars of suitable rating for full length equal to the width of the board for three live phases and suitable for inducted current, one copper bar of half the rating of full length for neutral phase as per IS 8084-1976 and IS:11353-1985 read with BIS 5578-1985 with upto date ammendments complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
3
-
-
... More
"h) ICTP switches with HRC fuses unit of Kilbur/L&T/siemens/stands/Havells make and of suitable capacity as per IS:4064:1978 with upto date ammendments complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
"
3
-
-
... More
"i) Three phase indicator lamps complete with toggle switches for individual motors as per IS:3452:(P-I & II) with upto date ammendments
"
3
-
-
... More
Fixing of double flanged CI sluice valve PN1 of Leader/BHEL/Kirlosker/GLEd/Kilburn Fourses / Kartar make and equal to dia of suction pipe and capable of withstanding the normal seat pressure as per IS:780:1984 with upto date ammendments complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
"
3
-
-
... More
Fixing of double flanged cast steel sluice valves ASA-300 of leader/BHEL Kirlosker/Kilburn GLED/fourses make for one step higher then delivery line of pump and capable of withstanding the normal seat pressure and as per BIS standard with upto date ammdnements complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
"
3
-
-
... More
Fixing of double flanged swing type cast steel valves class ASA-300 of Leader/BHEL/KILROSKER/Kartar/KILBURN/GLED/FOURSES make having bye pass arrangements of one step higher then delivery line of pump and capable of withstanding normal seat pressure as perBIS standards with upto date ammendments.complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
"
3
-
-
... More
Fixing of double flanged cast steel reflux valves class ASA-300 of Leader/BHEL/KILROSKER/Kartar/KILBURN/GLED/FOURSES make and of 350mm dia having bye pass arrangements for rising main and capable of withstanding normal seat pressure as per BIS standards with upto date ammendments complete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
"
1
-
-
... More
"Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date ammendmentscomplete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
3
-
-
... More
"Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per IS:2373:1981 with upto date ammendmentscomplete in all respect as per the direction and to the entire satisfaction of the Engineer-in-charge in all leads and lifts.
1
-
-
... More
"Installation / fixxing of all the items apparing at serial No.12 to 19 as per the systematic drawing "
1
-
-
... More
"Providing and fixing double flanged MS/GI piping work (Layout to be approved by the Engineer in charge) for suction and delivery pipes suitable to pump(s) offered and common header as per the R/Main respectively complete with all specials such as bends, tees, reducers. Increasers with companions flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thickness as per IS:2712:1979 and required number of nuts and bolts as per Is:1364:1983, The Pipes fittings and joints shall be as per relevant IS code & to withstand 1.5 times total head stipulated under item No.19. The size of the various components to be as under:
"
-
-
-
... More
"Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5M/second in the suction pipe
"
10
-
-
... More
"Delivery pipe: One dia higher then the delivery of the pump offered and suitable to keep the velocity of flow from 1.5 to 2M/second in the delivery pipe
"
10
-
-
... More
"Common header :One dia higher then delivery of pump x350 mm dia and will extend upto 5 meters from the outer wall of the pump house in the direction to be jointed
"
5
-
-
... More
"Providing and laying copper PVC insulated arsoured power cable (One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest ith upto date ammendments of siemens/GLOSTER /IEC/ICC/EICO/NATIONAL/GRANDLAY make including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor
"
-
-
-
... More
(a) Motor side (From switch to starter and starter to motor)
10
-
-
... More
(b) Supply side (From Meter of HPSEB to bus bar and switch)
10
-
-
... More
"Providing and fixing double loop earth with copper plate 600mmx600x3mm thick electrode complete with material such thimbles nuts and charcoal and common salt, 25mmx5mm copper strips as per IS:3043:1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
"
1
-
-
... More
Providing laying jointing and testing at site suitable size copper PVC insulated armoured power three and half core cable conforming to BIS 1554 (Part.I) 1988 or latest upto date ammendments or siemens/Gloster/ ICC/ EICO/National/IEC make from meter of HPSEB to circuit breaker and from circuit breaker to bus bar switch and starter (one cable carrying all three phases) including all other electrical equipment/accessories, such as thimbles, flexible pipe, solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor. The type, size and make will be subject to approval of HPSEB authorities. In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost i/c cost of carriage of material in all leads and lifts and as directed by the Engineer-in-charge. Suitable XLPE Unarmoured cable fromTransformer to Panel board / Motor )
30
-
-
... More
2nd stage:- Installation ,Varnishing & Testing of motor and pumps horizontal spindle, horizontal radial split casing/end suction (back out arrangment) multistage centrifugal pump or Kirloskar make Model RKBF 65/19LM 11 stages Pump set as per BIS 1520-1980 with upto date amendments, read with IS 9137-1978 or latest edition suitable for lifting water for under mentioned characteristics with bronze impellers/priming funnels, casing ring and shaft sleeves of bronze,shaft of steel grade 4508 FN8 with cast iron casing coupled directly through a flexible coupling and common MS/Cast steel base plateform ( base plate to be from the manufacturer of pumping unit only) to slip ring/squirrel cage screen protected drip proof induction motors of 180 KW /241 HP Kirloskar suitable for operation on 400(+/-) 10% volts, 50cycles/second, 3 phase AC electric supply. The power of electric motor/motors should be designed +10% in excess of the maximum power required by the pump/pumps inthe operation rangeof (+) 10% and (-) 15% of duty point head. The motor.motors a per IS 325-1978 with uo to date amendments read with IS 900-1972. It should include cost of bearing nuts, bolts and painting etc. and should meet the following requirement:
Discharge (Q): 26.04 LPS for each pump Total Dynamic head: 437.66 mtrs.
a) LWL in sump well: 1505.50 mtrs.
b) Shaft level: 1507.00 mtrs.
c) Level at discharge point: 1937 mtrs.
d) Suction lift : +ve 1.5 mtrs.
e) Discharge head: 430 mtrs.
f) Static head: 430 mtrs.
Rising main: a) Length 831 mtrs 350mm dia
Pumping hours: 20
Altitude of installation above MSL: 1300.00 mtrs.
Characteristics of water: Raw water with turbidity up to 3000 PPM Temprature : 20 degree centigrade. (Note:- All three pumps sets will run parallel to lift total discharge of 78.11LPS)
3
-
-
... More
Providing ICTP main switch with HRC fuses of Kilburn/ L&T/Siemens/Standard/ Havells make and having capacity 30% extra of the operational rating as per IS: 4064-1978 with up to date amendments, immediately after the power meter of the HPSEBL.
3
-
-
... More
"Providing MS sheet 16G steel fabricated floor mounted closed(almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm duly painted with steel sheet of 16 gauge comprising and capable of mounting the following accessories within all internal connections. All the accessories should be suitable for the proposed pumping machinery at item No.32 above and to the entire satisfaction of HPSEB authorities. The same shall have to be replaced with out extra cost if recommended by HPSEB authorities
"
3
-
-
... More
"a) OCB/MCCB of MEI/Havels/ standard make and of suitable capacity for offered motor on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage released as per relevent IS code with upto date ammendments
"
3
-
-
... More
"j) Digital 100mm dia circular dial A.C.supply flush ammeter of AE/IMP/Havells make of suitable range with selector switches and CTS operated as per IS:L1248(P-II) .183 with upto date ammendments
"
3
-
-
... More
"k) Capacitor of Crompton/L&T/NGEP/Mechneil/ BHEL/GEC make as per 15:2834:1986 with upto date ammendments, to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rting according to H.P.offered including cables as per relevant ISI code (of siemens/clocter.IEC make )from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per Is:4064:1978 with upto date ammendments
"
3
-
-
... More
"l) Providing suitable oil immersed starter delta/direct on line/auto transformer/. starter rotor starter of MEI/.Kilburn/Jyoti /L&T/Siemens make as per IS:8544:1979 with upto date ammendments for squirrel cage/slip ring motor mounted on panel board with magnetic type over-load release and dashpot, time lag, under voltage release with or without initial oil filling as the case may be with single phae preventor as per IS:1248( P-V) 1983 with upto date ammendments
"
3
-
-
... More
"m) Providng Digital hour run meter of recommended make and suitable capacity as per IS:722(latest edition.)
"
3
-
-
... More
"n) Providing antivibration pads under the pumps and motors of suitablesize for the above pumping machinery as per IS:6337:1971.
"
3
-
-
... More
"b) Earth leakage circuit breaker of recommended make (Kilburn/L&T/MEI/GEC) as per IS:2516:1977 with upto date ammendments of suitable range which should have control box, operation, handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the ciruit breaking for cover current protection. The circuit should be equipped with magnet thermal release with metallic tap etc, it should also be fitted with earth fault for tripping of breaker on occurnce of earth fault on off breaker load side end.
"
3
-
-
... More
"c) The voltage monitor relay of AE/MEI/L&T/Havells make three phase with all protection and usual indicator and electric siren against single phasing,low voltage,high voltage, reverse phasing, over loading and phase voltage difference as per IS:3482 (latest edition)
"
3
-
-
... More
"d) Digital 100 mm diameter circular dial A.C.supply voltmeter of recommended make AE/IMP/Havells of suitable range with selector switches as per IS:4064:1978 with upto date ammendments
"
1
-
-
... More
"e) Digital Power factor meter of standard make AE/L&T/IMP/Havells as per relevant IS code with upto dateammendments
"
1
-
-
... More
"f) Digital Frequencey meter of standard makeAE/L&T/IMP/Havells as per relvant IS code with uptodate ammendments
"
1
-
-
... More
"g) Bus bar chamber having three copper bars of suitable rating for full length equal to the width of the board for three live phases and suitable for inducted current, one copper bar of half the rating of full length for neutral phase as per IS 8084-1976 and IS:11353-1985 read with BIS 5578-1985 with upto date ammendments
"
3
-
-
... More
"h) ICTP switches with HRC fuses unit of Kilbur/L&T/siemens/stands/Havells make and of suitable capacity as per IS:4064:1978 with upto date ammendments
"
3
-
-
... More
"i) Three phase indicator lamps complete with toggle switches for individual motors as per IS:3452:(P-I & II) with upto date ammendments
"
3
-
-
... More
Fixing of double flanged CI sluice valve PN1 of Leader/BHEL/Kirlosker/GLEd/Kilburn Fourses / Kartar make and equal to dia of suction pipe and capable of withstanding the normal seat pressure as per IS:780:1984 with upto date ammendments
"
3
-
-
... More
Fixing of double flanged cast steel sluice valves ASA-300 of leader/BHEL Kirlosker/Kilburn GLED/fourses make for one step higher then delivery line of pump and capable of withstanding the normal seat pressure and as per BIS standard with upto date ammdnements
"
3
-
-
... More
Fixing of double flanged swing type cast steel valves class ASA-300 of Leader/BHEL/KILROSKER/Kartar/KILBURN/GLED/FOURSES make having bye pass arrangements of one step higher then delivery line of pump and capable of withstanding normal seat pressure as perBIS standards with upto date ammendments.
"
3
-
-
... More
Fixing of double flanged cast steel reflux valves class ASA-300 of Leader/BHEL/KILROSKER/Kartar/KILBURN/GLED/FOURSES make and of 350mm dia having bye pass arrangements for rising main and capable of withstanding normal seat pressure as per BIS standards with upto date ammendments.
"
1
-
-
... More
"Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date ammendments.
"
3
-
-
... More
"Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per Is:2373:1981 with upto date ammendments
"
1
-
-
... More
"Installation / fixing of all the items appearing at serial No. 25 to 32 as per the systematic drawing "
1
-
-
... More
"Providing and fixing double flanged MS/GI piping work (Layout to be approved by the Engineer in charge) for suction and delivery pipes suitable to pump(s) offered and common header as per the R/Main respectively complete with all specials such as bends, tees, reducers. Increasers with companions flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thickness as per IS:2712:1979 and required number of nuts and bolts as per IS:1364:1983, The Pipes fittings and joints shall be as per relevant IS code & to withstand 1.5 times total head stipulated under item No.32. The size of the various components to be as under:
"
-
-
-
... More
"Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5M/second in the suction pipe
"
10
-
-
... More
"Delivery pipe: One dia higher then the delivery of the pump offered and suitable to keep the velocity of flow from 1.5 to 2M/second in the delivery pipe
"
10
-
-
... More
"Common header :One dia higher then delivery of pump x350 mm dia and will extend upto 5 meters from the outer wall of the pump house in the direction to be jointed
"
5
-
-
... More
"Providing and laying copper PVC insulated arsoured power cable (One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest ith upto date ammendments of siemens/GLOSTER /IEC/ICC/EICO/NATIONAL/GRANDLAY make including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor
"
-
-
-
... More
(a) Motor side (From switch to starter and starter to motor)
10
-
-
... More
(b) Supply side (From Meter of HPSEB to bus bar and switch)
10
-
-
... More
Providing laying jointing and testing at site suitable size copper PVC insulated armoured power three and half core cable conforming to BIS 1554 (Part.I) 1988 or latest upto date ammendments or siemens/Gloster/ ICC/ EICO/National/IEC make from meter of HPSEB to circuit breaker and from circuit breaker to bus bar switch and starter (one cable carrying all three phases) including all other electrical equipment/accessories, such as thimbles, flexible pipe, solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor. The type, size and make will be subject to approval of HPSEB authorities. In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost i/c cost of carriage of material in all leads and lifts and as directed by the Engineer-in-charge. Suitable XLPE Unarmoured cable fromTransformer to Panel board / Motor )
30
-
-
... More
"Providing and fixing double loop earth with copper plate 600mmx600x3mm thick electrode complete with material such thimbles nuts and charcoal and common salt, 25mmx5mm copper strips as per IS:3043:1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
"
1
-
-
... More
3rd stage:- Installation ,Varnishing & Testing of motor and pumps horizontal spindle, horizontal radial split casing/end suction (back out arrangment) multistage centrifugal pump or combination of pump in seris/parallel of recommended pumps make model Kirloskar Make RKBF65/9E 9 stages Pump set as per BIS 1520-1980 with upto date amendments, read with IS 9137-1978 or latest edition suitable for lifting water for under mentioned characteristics with bronze impellers/priming funnels, casing ring and shaft sleeves of bronze,shaft of steel grade 4508 FN8 with cast iron casing coupled directly through a flexible coupling and common MS/Cast steel base plateform ( base plate to be from the manufactturer of pumping unit only) to slip ring/squirrel cage screen protected drip proof induction motor of 110 KW /148 HP Kirloskar Make suitable for operation on 400(+/-) 10% volts, 50cycles/second, 3 phase AC electric supply. The power of electric motor/motors should be designed +10% in excess of the maximum power required by the pump/pumps inthe operation rangeof (+) 10% and (-) 15% of duty point head. The motor.motors a per IS 325-1978 with uo to date amendments read with IS 900-1972. It should include cost of bearing nuts, bolts and painting etc. and should meet the following requirement:
45.01 Discharge (Q): 16.37 LPS for each pump 45.02 Total Dynamic head: 412.11 mtrs.
45.03 a) LWL in sump well: 1935.50 mtrs.
45.04 b) Shaft level: 1937.00 mtrs.
45.05 c) Level at discharge point: 2340.79 mtrs.
45.06 d) Suction lift : +ve 1.5 mtrs.
45.07 e) Discharge head: 403.79 mtrs.
45.08 f) Static head: 403.79 mtrs.
45.09 Rising main: a) Length 1178 mtrs 300mm dia
45.10 Pumping hours: 20
45.11 Altitude of installation above MSL: 1800.00 mtrs.
45.12 Characteristics of water: Raw water with turbidity up to 3000 PPM 45.13 Temprature : 20 degree centigrade. (Note:- All three pumps will run parallel to lift total discharge of 49.12LPS)
3
-
-
... More
Providing ICTP main switch with HRC fuses of Kilburn/ L&T/Siemens/Standard/ Havells make and having capacity 30% extra of the operational rating as per IS: 4064-1978 with up to date amendments, immediately after the power meter of the HPSEBL.
3
-
-
... More
"Providing MS sheet 16G steel fabricated floor mounted closed(almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm duly painted with steel sheet of 16 gauge comprising and capable of mounting the following accessories within all internal connections. All the accessories should be suitable for the proposed pumping machinery at item No.45 above and to the entire satisfaction of HPSEB authorities. The same shall have to be replaced with out extra cost if recommended by HPSEB authorities
"
3
-
-
... More
"a) OCB/MCCB of MEI/Havels/ standard make and of suitable capacity for offered motor on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage released as per relevent IS code with upto date ammendments
"
3
-
-
... More
"j) Digital 100mm dia circular dial A.C.supply flush ammeter of AE/IMP/Havells make of suitable range with selector switches and CTS operated as per IS:L1248(P-II) .183 with upto date ammendments
"
3
-
-
... More
"k) Capacitor of Crompton/L&T/NGEP/Mechneil/ BHEL/GEC make as per 15:2834:1986 with upto date ammendments, to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rting according to H.P.offered including cables as per relevant ISI code (of siemens/clocter.IEC make )from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per Is:4064:1978 with upto date ammendments
"
3
-
-
... More
"l) Providing suitable oil immersed starter delta/direct on line/auto transformer/. starter rotor starter of MEI/.Kilburn/Jyoti /L&T/Siemens make as per IS:8544:1979 with upto date ammendments for squirrel cage/slip ring motor mounted on panel board with magnetic type over-load release and dashpot, time lag, under voltage release with or without initial oil filling as the case may be with single phae preventor as per IS:1248( P-V) 1983 with upto date ammendments
"
3
-
-
... More
"m) Providng Digital hour run meter of recommended make and suitable capacity as per IS:722(latest edition.)
"
3
-
-
... More
"n) Providing antivibration pads under the pumps and motors of suitablesize for the above pumping machinery as per IS:6337-1971.
"
3
-
-
... More
"b) Earth leakage circuit breaker of recommended make (Kilburn/L&T/MEI/GEC) as per IS:2516:1977 with upto date ammendments of suitable range which should have control box, operation, handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the ciruit breaking for cover current protection. The circuit should be equipped with magnet thermal release with metallic tap etc, it should also be fitted with earth fault for tripping of breaker on occurnce of earth fault on off breaker load side end.
"
3
-
-
... More
"c) The voltage monitor relay of AE/MEI/L&T/Havells make three phase with all protection and usual indicator and electric siren against single phasing,low voltage,high voltage, reverse phasing, over loading and phase voltage difference as per IS:3482 (latest edition)
"
3
-
-
... More
"d) Digital 100 mm diameter circular dial A.C.supply voltmeter of recommended make AE/IMP/Havells of suitable range with selector switches as per IS:4064:1978 with upto date ammendments
"
1
-
-
... More
"e) Digital Power factor meter of standard make AE/L&T/IMP/Havells as per relevant IS code with upto dateammendments
"
1
-
-
... More
"f) Digital Frequencey meter of standard makeAE/L&T/IMP/Havells as per relvant IS code with uptodate ammendments
"
1
-
-
... More
"g) Bus bar chamber having three copper bars of suitable rating for full length equal to the width of the board for three live phases and suitable for inducted current, one copper bar of half the rating of full length for neutral phase as per IS 8084-1976 and IS:11353-1985 read with BIS 5578-1985 with upto date ammendments
"
3
-
-
... More
"h) ICTP switches with HRC fuses unit of Kilbur/L&T/siemens/stands/Havells make and of suitable capacity as per IS:4064:1978 with upto date ammendments
"
3
-
-
... More
"i) Three phase indicator lamps complete with toggle switches for individual motors as per IS:3452:(P-I & II) with upto date ammendments
"
3
-
-
... More
Fixing of double flanged CI sluice valve PN1 of Leader/BHEL/Kirlosker/GLEd/Kilburn Fourses / Kartar make and equal to dia of suction pipe and capable of withstanding the normal seat pressure as per IS:780:1984 with upto date ammendments
"
3
-
-
... More
Fixing of double flanged cast steel sluice valves ASA-300 of leader/BHEL Kirlosker/Kilburn GLED/fourses make for one step higher then delivery line of pump and capable of withstanding the normal seat pressure and as per BIS standard with upto date ammdnements
"
3
-
-
... More
Fixing of double flanged swing type cast steel valves class ASA-300 of Leader/BHEL/KILROSKER/Kartar/KILBURN/GLED/FOURSES make having bye pass arrangements of one step higher then delivery line of pump and capable of withstanding normal seat pressure as perBIS standards with upto date ammendments.
"
3
-
-
... More
Fixing of double flanged cast steel reflux valves class ASA-300 of Leader/BHEL/KILROSKER/Kartar/KILBURN/GLED/FOURSES make and of 300mm dia having bye pass arrangements for rising main and capable of withstanding normal seat pressure as per BIS standards with upto date ammendments.
"
1
-
-
... More
"Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date ammendments.
"
3
-
-
... More
"Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per IS:2373:1981 with upto date ammendments
"
1
-
-
... More
"Installation/ fixing of all the items appearing at serial No. 38 to 45 as per the systematic drawing "
1
-
-
... More
"Providing and fixing double flanged MS/GI piping work (Layout to be approved by the Engineer in charge) for suction and delivery pipes suitable to pump(s) offered and common header as per the R/Main respectively complete with all specials such as bends, tees, reducers. Increasers with companions flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thickness as per IS:2712-1979 and required number of nuts and bolts as per Is:1364-1983, The Pipes fittings and joints shall be as per relevant IS code & to withstand 1.5 times total head stipulated under item No.45. The size of the various components to be as under:
"
-
-
-
... More
"Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5M/second in the suction pipe
"
10
-
-
... More
"Delivery pipe: One dia higher then the delivery of the pump offered and suitable to keep the velocity of flow from 1.5 to 2M/second in the delivery pipe
"
10
-
-
... More
"Common header :One dia higher then delivery of pump x300 mm dia and will extend upto 5 meters from the outer wall of the pump house in the direction to be jointed
"
5
-
-
... More
"Providing and laying copper PVC insulated arsoured power cable (One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest ith upto date ammendments of siemens/GLOSTER /IEC/ICC/EICO/NATIONAL/GRANDLAY make including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor
"
-
-
-
... More
(a) Motor side (From switch to starter and starter to motor)
10
-
-
... More
(b) Supply side (From Meter of HPSEB to bus bar and switch)
10
-
-
... More
Providing laying jointing and testing at site suitable size copper PVC insulated armoured power three and half core cable conforming to BIS 1554 (Part.I) 1988 or latest upto date ammendments or siemens/Gloster/ ICC/ EICO/National/IEC make from meter of HPSEB to circuit breaker and from circuit breaker to bus bar switch and starter (one cable carrying all three phases) including all other electrical equipment/accessories, such as thimbles, flexible pipe, solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor. The type, size and make will be subject to approval of HPSEB authorities. In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost i/c cost of carriage of material in all leads and lifts and as directed by the Engineer-in-charge. Suitable XLPE Unarmoured cable fromTransformer to Panel board / Motor )
30
-
-
... More
"Providing and fixing double loop earth with copper plate 600mmx600x3mm thick electrode complete with material such thimbles nuts and charcoal and common salt, 25mmx5mm copper strips as per IS:3043:1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
"
1
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%