Himachal Pradesh Irrigation And Public Health Department Tender
Bidassist allows us to explore new opportunities across the whole world so as to support the growth of the business. It is designed in such a manner that if we need any kind of information about any government e-tender the Himachal Pradesh government has posted on its website, Bidassist provides the same in a very hassle-free manner. As BidAssist is designed as a very user-friendly website which helps us find the specific Himachal Pradesh etender we are looking for.
Himachal Pradesh Irrigation And Public Health Department - HPIPH Tender
Machinery and Tools
Eprocure
Opening Date20 Jul 2024
Closing Date30 Jul 2024
Tender Amount₹ 21,00,000
Costs
EMD
₹ 39,000Document Cost
₹ 400Tender Fee
Refer Documents
Summary
Remodeling Improvement Of Lwss Matyara In Gp Narola Tehsil Baldwara Distt Mandi Hp Under Jal Jeevan Mission
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_HPIPH_90781_1Tender No
2618-60 dt. 20.07.2024Tender Authority
Himachal Pradesh Irrigation And Public Health Department ViewPurchaser Address
-Website
http://http://hpiph.org/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Providing M.S. sheet, steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm, duly painted, with steel sheet of 16 gauge comprising, capable of mounting the following accessories with all internal connections.(1.00 No.)
-
-
-
... More
M.C.B. 63 Amp. Havell/MDS/Standard/Jyoti or JSV approved make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516 (Part - II) 1985 with up to date amendments.(1.00 No.)
-
-
-
... More
E.L.C.B. 63 Amp. of Havell/MDS/INDETEC or JSV Approved Make make as per IS: 2516 (Part - II) 1985 with upto date amendment which should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape etc. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.(1.00 No.)
-
-
-
... More
The voltage monitor relay of L&T/AE make three phase with all protection and usual indicator and electric siren against single phasing low voltage, high voltage, reverse phasing, over loading and phase voltage difference as per IS: 1248 (Part - II ) 1983 (Latest edition).(1.00 No.)
-
-
-
... More
100mm square type A.C. supply voltmeter of AE/L&T Rishab make of suitable range (0-500 Volt) with selector switches as per IS: 4064 (Part - II ) -1978 with up to date amendments.(1.00 No.)
-
-
-
... More
Power factor meter of AE/L&T Rishab make as per IS: 1248 (Part - V ) 1983 (Latest edition) with up to date amendments of suitable rating.(1.00 No.)
-
-
-
... More
Frequency meter of AE/ L&T Rishab make as per IS: 1248 (Part - IV ) 1983 ( Latest edition) with up to date amendments of suitable rating.(1.00 No.)
-
-
-
... More
Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11354-1985 read with IS 5578-1985 with up to date amendments.(1.00 Set.)
-
-
-
... More
ICTP switches with HRC fuses 60 Amp of L&T/ Standard/Havells make and of suitable capacity as per IS: 4064 (Part - II) -1978 with up to date amendments.(2.00 Nos.)
-
-
-
... More
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 ( P-I & II) with up to date amendments.(1.00 Set.)
-
-
-
... More
100mm Square type AC supply Ammeter 60 Amp. of AE /L&T Rishab make of suitable range (0-200) with selector switches and CTS operated as per IS:1248 (P-II) 1983 with up to date amendments.(2.00 Nos.)
-
-
-
... More
Supply & errection of floor/wall mounted power factor shunt capacitor of L&T make as per IS:2834 -1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of 5 KVAr rating according to HP offered including cables as per relevant ISI code (of L&T/Finolex make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064 (Part - II) 1978 with upto date amendments. (2.00 Nos.)
-
-
-
... More
Providing suitable Star Delta starter of M.E.I / Kilburn make as per IS:8544 (Part - II ) -1987 with up to date amendments for Squirrel Cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments.(2.00 Nos.)
-
-
-
... More
Providing Hour run meter of recommended make as per IS: 722 (Latest edition) .(2.00 Nos.)
-
-
-
... More
Providing double flanged Cast iron sluice valve of Leader/Kirloskar make or JSV approved make of 50 mm dia for the suction pipe and capable of withstanding the normal seat pressure as per IS: 14846-2000 with up to date amendments. (Class PN-1.6)(2.00 Nos.)
-
-
-
... More
Providing double flanged Cast steel sluice valve of Leader/Kirloskar make or JSV approved make and size of 40 mm dia. and capable of with standing nominal seat pressure of 52 kg/cm2 as per BS : 1414 / API - 600 (Class ASA-300) .(2.00 Nos.)
-
-
-
... More
Providing double flanged Cast steel reflux valve of Leader/Kirloskar make or JSV approved make and size of 40 mm dia. and capable of with standing nominal seat pressure of 52 kg/cm2 as per: BS : 1868 / API - 600 (Class ASA-300) (2.00 Nos.) .
-
-
-
... More
Providing double flanged Cast steel 50 mm non return valve of Leader/ Kirloskar make or JSV approved make having bye pass arrangement for rising main and capable of with standing normal seat pressure of 52 kg/cm2 as per BS : 1868 / API - 600 (Class ASA-300) . . (1.00 No.)
-
-
-
... More
Providing 50 mm dia. circular dial pressure gauge of Fiebig/bourden make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0 - 75 Kg/cm2.(2.00 Nos.)
-
-
-
... More
Providing 50 mm dia. vacume dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0 - 760 mercury.(2.00 Nos.)
-
-
-
... More
Installation of all the items appearing at Serial No. 3 to 10 complete in all respect as per direction of Engg-in-Charge.(1.00 Job.)
-
-
-
... More
Providing and fixing double flanged piping work layout to be approved by the Engineer-in-Charge for suction and delivery pipes suitable to pump(s) offered and common header as per the rising main respectively complete with all specials such as bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS: 1364-1983. The pipes shall be as per relevant IS Code and to withstand 1.5 times total head stipulated under item No. 2. (1.00 Job.)
-
-
-
... More
The size of the various components to be as under:-
-
-
-
... More
(i) Suction pipe 50 mm dia Min. length = 10 mtr.
-
-
-
... More
(ii) Delivery pipe 40 mm dia -do- = 6 mtr.
-
-
-
... More
(iii) Common Header 50 mm dia -do- = 6 mtr.
-
-
-
... More
and will extend up to 5 meters from the outer wall of the pump house in the direction to be jointed.
-
-
-
... More
Providing and laying copper PVC insulated armoured power cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of L&T/Finolex make including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor.
-
-
-
... More
(i) Motor side: 4 mm2 Min length = 20 mtrs.(20.00 per Rmt.)
-
-
-
... More
(ii) Supply side: 6 mm2 Min. length = 10 mtrs.(10.00 per Rmt.)
-
-
-
... More
Providing and fixing double loop earthing and Cu plate 600 mm x 600mm x 3mm thick electrode complete with material such as thimbles, nuts and bolts, charcoal and common salt, 20 mm x 3 mm G.I. strips & G.I. wire of 4 SWG as per IS: 3043 -1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect. (1.00 Job.)
-
-
-
... More
Centrifugal Pump (LWSS Kashmaila Ropdi):- Supply & errection of horizontal spindle horizontal split casing/end suctions (back pull out arrangement) Single/double/multistage centrifugal pumps or combination of pumps in series/parellel of Mather & Platt/KSB/ Kirloskar or JSV approved make conforming to BIS 1520-1980 pump (Latest with up to to date amendments), read with BIS: 9137-1978 (latest edition) suitable for lifting clear water of under mentioned characteristics with bronze/Suitable alloy, priming funnels, casing ring and shaft motor of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel plate (base plate from the principal manufacturer of pumping set) to coupling 3 phase squirrel cage electric induction motor of standard make such as Kirloskar/ NGEF/Cromption or JSV approved make conforming to IS 12615-2018 and should be energy efficient minimum IE2 compliant and totally enclosed fan cooled (TEFC) type ( latest with upto date ammendments) it should include the cost of bearings, nuts & bolts, painting etc. and shall be suitable for operation on the data given below: 2 Sets of 15 HP
30
-
-
... More
"SITE CONDITIONS:- Total Head 242.43 mtrs
Discharge required 2.60 LPS each set.
No. of Pump required. 2.00 No. set (1 Nos. act as Standbye)
Length of R/main 2120 mtrs.
Dia of R/main 40 mm dia Location of the site of installation of machinery-The site is located near village Ropdi Nallah & head load from nearest road head (for the installation of both machinery). Head Load (for the installation of both machinery).
The Altitude of :- The Altitude of place is 1145 mtrs above MSL
Type of Current:- AC three phase supply with
Rated Voltage:- 415 +/- 10% Type of water :- Clear water
Charactristics of water :- a) Ambient Temperature
b) Turbidity NTU 50.00 NTU
c) Hardness 260 Mg/Ltrs --
d) PH Value 7.5 --
e)Total Solid Mg/Lts)PH Value --
No of working hours. 8 Hours.
Limit of Pump (-) 15% (+) 10% R.P.M. of Pumping RPM(or to be specified by the tenderer)
Test run 8 Hours continueously for 7 days."
-
-
-
... More
Providing ICTP Main Switch 63 Amp with HRC fuses / Side handled operated Change over switch of L&T/Crompton/Standard/Havells or JSV approved make suitable capacity Operational rating as per IS: 4064 (Part - II) 1978 with up to date amendments immediately after the power meter of HPSEB. (1.00 No.)
-
-
-
... More
Providing M.S. sheet, steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm, duly painted, with steel sheet of 16 gauge comprising, capable of mounting the following accessories with all internal connections.(1.00 No.)
-
-
-
... More
M.C.B. 63 Amp. Havell/MDS/Standard/Jyoti or JSV approved make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516 (Part - II) 1985 with up to date amendments.(1.00 No.)
-
-
-
... More
E.L.C.B. 63 Amp. of Havell/MDS/INDETEC or JSV Approved Make make as per IS: 2516 (Part - II) 1985 with upto date amendment which should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape etc. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.(1.00 No.)
-
-
-
... More
The voltage monitor relay of L&T/AE make three phase with all protection and usual indicator and electric siren against single phasing low voltage, high voltage, reverse phasing, over loading and phase voltage difference as per IS: 1248 (Part - II ) 1983 (Latest edition).(1.00 No.)
-
-
-
... More
100mm square type A.C. supply voltmeter of AE/L&T Rishab make of suitable range (0-500 Volt) with selector switches as per IS: 4064 (Part - II ) -1978 with up to date amendments.(1.00 No.)
-
-
-
... More
Power factor meter of AE/L&T Rishab make as per IS: 1248 (Part - V ) 1983 (Latest edition) with up to date amendments of suitable rating.(1.00 No.)
-
-
-
... More
Frequency meter of AE/ L&T Rishab make as per IS: 1248 (Part - IV ) 1983 ( Latest edition) with up to date amendments of suitable rating.(1.00 No.)
-
-
-
... More
Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11354-1985 read with IS 5578-1985 with up to date amendments.(1.00 Set.)
-
-
-
... More
ICTP switches with HRC fuses 60 Amp of L&T/ Standard/Havells make and of suitable capacity as per IS: 4064 (Part - II) -1978 with up to date amendments.(2.00 Nos.)
-
-
-
... More
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 ( P-I & II) with up to date amendments.(1.00 Set.)
-
-
-
... More
100mm Square type AC supply Ammeter 60 Amp. of AE /L&T Rishab make of suitable range (0-200) with selector switches and CTS operated as per IS:1248 (P-II) 1983 with up to date amendments.(2.00 Nos.)
-
-
-
... More
Supply & errection of floor/wall mounted power factor shunt capacitor of L&T make as per IS:2834 -1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of 4 KVAr rating according to HP offered including cables as per relevant ISI code (of L&T/Finolex make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064 (Part - II) 1978 with upto date amendments. (2.00 Nos.)
-
-
-
... More
Providing suitable Star Delta starter of M.E.I / Kilburn make as per IS:8544 (Part - II ) -1987 with up to date amendments for Squirrel Cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments.(2.00 Nos.)
-
-
-
... More
Providing Hour run meter of recommended make as per IS: 722 (Latest edition) .(2.00 Nos.)
-
-
-
... More
Providing double flanged Cast iron sluice valve of Leader/Kirloskar make or JSV approved make of 40 mm dia for the suction pipe and capable of withstanding the normal seat pressure as per IS: 14846-2000 with up to date amendments. (Class PN-1.6)(2.00 Nos.)
-
-
-
... More
Providing double flanged Cast steel sluice valve of Leader/Kirloskar make or JSV approved make and size of 32 mm dia. and capable of with standing nominal seat pressure of 52 kg/cm2 as per BS : 1414 / API - 600 (Class ASA-300) (2.00 Nos.) .
-
-
-
... More
Providing double flanged Cast steel reflux valve of Leader/Kirloskar make or JSV approved make and size of 32 mm dia. and capable of with standing nominal seat pressure of 52 kg/cm2 as per: BS : 1868 / API - 600 (Class ASA-300) (2.00 Nos.) .
-
-
-
... More
Providing double flanged Cast steel 40 mm non return valve of Leader/ Kirloskar make or JSV approved make having bye pass arrangement for rising main and capable of with standing normal seat pressure of 52 kg/cm2 as per BS : 1868 / API - 600 (Class ASA-300) (1.00 No.) . .
-
-
-
... More
Providing 40 mm dia. circular dial pressure gauge of Fiebig/bourden make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0 - 75 Kg/cm2.(2.00 Nos.)
-
-
-
... More
Providing 40 mm dia. vacume dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0 - 760 mercury.(2.00 Nos.)
-
-
-
... More
Installation of all the items appearing at Serial No.17 to 24 complete in all respect as per direction of Engg-inCharge.(1.00 Job.)
-
-
-
... More
Providing and fixing double flanged piping work layout to be approved by the Engineer-in-Charge for suction and delivery pipes suitable to pump(s) offered and common header as per the rising main respectively complete with all specials such as bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS: 1364-1983. The pipes shall be as per relevant IS Code and to withstand 1.5 times total head stipulated under item No.16.(1.00 Job.)
-
-
-
... More
The size of the various components to be as under:-
-
-
-
... More
(i) Suction pipe 40 mm dia Min. length = 10 mtr.
-
-
-
... More
(ii) Delivery pipe 32 mm dia -do- = 6 mtr.
-
-
-
... More
(iii) Common Header 40 mm dia -do- = 6 mtr.
-
-
-
... More
and will extend up to 5 meters from the outer wall of the pump house in the direction to be jointed.
-
-
-
... More
Providing and laying copper PVC insulated armoured power cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of L&T/Finolex make including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor.
-
-
-
... More
(i) Motor side: 2.5 mm2 Min length = 20 mtrs.(20.00 mtrs)
-
-
-
... More
(ii) Supply side: 4mm2 Min. length = 10 mtrs.(10.00 mtrs)
-
-
-
... More
Providing and fixing double loop earthing and Cu plate 600 mm x 600mm x 3mm thick electrode complete with material such as thimbles, nuts and bolts, charcoal and common salt, 20 mm x 3 mm G.I. strips & G.I. wire of 8 SWG as per IS: 3043 -1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect.(1.00 Job)
-
-
-
... More
Centrifugal Pump (LWSS Ghori Matoli Phase-I):- Supply & errection of horizontal spindle horizontal split casing/end suctions (back pull out arrangement) Single/double/multistage centrifugal pumps or combination of pumps in series/parellel of Mather & Platt/KSB/ Kirloskar or JSV approved make conforming to BIS 1520-1980 pump (Latest with up to to date amendments), read with BIS: 9137-1978 (latest edition) suitable for lifting clear water of under mentioned characteristics with bronze/Suitable alloy, priming funnels, casing ring and shaft motor of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel plate (base plate from the principal manufacturer of pumping set) to coupling 3 phase squirrel cage electric induction motor of standard make such as Kirloskar/ NGEF/Cromption or JSV approved make conforming to IS 12615-2018 and should be energy efficient minimum IE2 compliant and totally enclosed fan cooled (TEFC) type ( latest with upto date ammendments) it should include the cost of bearings, nuts & bolts, painting etc. and shall be suitable for operation on the data given below: 2 Sets of 25 HP .
50
-
-
... More
SITE CONDITIONS:- Total Head 142.56 mtrs
Discharge required 4.94 LPS each set.
No. of Pump required. 2.00 No. set (1 Nos. act as Standbye)
Length of R/main 1518 mtrs.
Dia of R/main 80 mm dia Location of the site of installation of machinery-The site is located near village Matoli & 500 mtr head load from nearest road head (for the installation of both machinery). Head Load (for the installation of both machinery).
The Altitude of :- The Altitude of place is 856 mtrs above MSL
Type of Current:- AC three phase supply with
Rated Voltage:- 415 +/- 10% Type of water :- Clear water
Charactristics of water :- a) Ambient Temperature
b) Turbidity NTU 50.00 NTU
c) Hardness 260 Mg/Ltrs --
d) PH Value 7.5 --
e)Total Solid Mg/Lts)PH Value --
No of working hours. 8 Hours.
Limit of Pump (-) 15% (+) 10% R.P.M. of Pumping RPM(or to be specified by the tenderer)
Test run 8 Hours continueously for 7 days.
-
-
-
... More
Providing ICTP Main Switch 63 Amp with HRC fuses / Side handled operated Change over switch of L&T/Crompton/Standard/Havells or JSV approved make suitable capacity Operational rating as per IS: 4064 (Part - II) 1978 with up to date amendments immediately after the power meter of HPSEB. (1.00 No)
-
-
-
... More
Providing M.S. sheet, steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm, duly painted, with steel sheet of 16 gauge comprising, capable of mounting the following accessories with all internal connections.(1.00 No)
-
-
-
... More
M.C.B. 63 Amp. Havell/MDS/Standard/Jyoti or JSV approved make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516 (Part - II) 1985 with up to date amendments.(1.00 No)
-
-
-
... More
E.L.C.B. 63 Amp. of Havell/MDS/INDETEC or JSV Approved Make make as per IS: 2516 (Part - II) 1985 with upto date amendment which should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape etc. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.(1.00 No)
-
-
-
... More
The voltage monitor relay of L&T/AE make three phase with all protection and usual indicator and electric siren against single phasing low voltage, high voltage, reverse phasing, over loading and phase voltage difference as per IS: 1248 (Part - II ) 1983 (Latest edition).(1.00 No)
-
-
-
... More
100mm square type A.C. supply voltmeter of AE/L&T Rishab make of suitable range (0-500 Volt) with selector switches as per IS: 4064 (Part - II ) -1978 with up to date amendments.(1.00 No)
-
-
-
... More
Power factor meter of AE/L&T Rishab make as per IS: 1248 (Part - V ) 1983 (Latest edition) with up to date amendments of suitable rating.(1.00 No)
-
-
-
... More
Frequency meter of AE/ L&T Rishab make as per IS: 1248 (Part - IV ) 1983 ( Latest edition) with up to date amendments of suitable rating.(1.00 No)
-
-
-
... More
Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11354-1985 read with IS 5578-1985 with up to date amendments.(1.00 Set)
-
-
-
... More
ICTP switches with HRC fuses 60 Amp of L&T/ Standard/Havells make and of suitable capacity as per IS: 4064 (Part - II) -1978 with up to date amendments.(2.00 Nos)
-
-
-
... More
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 ( P-I & II) with up to date amendments.(1.00 Set)
-
-
-
... More
100mm Square type AC supply Ammeter 60 Amp. of AE /L&T Rishab make of suitable range (0-200) with selector switches and CTS operated as per IS:1248 (P-II) 1983 with up to date amendments.(2.00 Nos)
-
-
-
... More
Supply & errection of floor/wall mounted power factor shunt capacitor of L&T make as per IS:2834 -1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of 6 KVAr rating according to HP offered including cables as per relevant ISI code (of L&T/Finolex make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064 (Part - II) 1978 with upto date amendments. (2.00 Nos)
-
-
-
... More
Providing suitable Star Delta starter of M.E.I / Kilburn make as per IS:8544 (Part - II ) -1987 with up to date amendments for Squirrel Cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. (2.00 Nos)
-
-
-
... More
Providing Hour run meter of recommended make as per IS: 722 (Latest edition) .(2.00 Nos)
-
-
-
... More
Providing double flanged Cast iron sluice valve of Leader/Kirloskar make or JSV approved make of 65 mm dia for the suction pipe and capable of withstanding the normal seat pressure as per IS: 14846-2000 with up to date amendments. (Class PN-1.6)(2.00 Nos)
-
-
-
... More
Providing double flanged Cast steel sluice valve of Leader/Kirloskar make or JSV approved make and size of 50 mm dia. and capable of with standing nominal seat pressure of 52 kg/cm2 as per BS : 1414 / API - 600 (Class ASA-300) .(2.00 Nos)
-
-
-
... More
Providing double flanged Cast steel reflux valve of Leader/Kirloskar make or JSV approved make and size of 50 mm dia. and capable of with standing nominal seat pressure of 52 kg/cm2 as per: BS : 1868 / API - 600 (Class ASA-300) . (2.00 Nos)
-
-
-
... More
Providing double flanged Cast steel 65 mm non return valve of Leader/ Kirloskar make or JSV approved make having bye pass arrangement for rising main and capable of with standing normal seat pressure of 52 kg/cm2 as per BS : 1868 / API - 600 (Class ASA-300) . . (1.00 No)
-
-
-
... More
Providing 65 mm dia. circular dial pressure gauge of Fiebig/bourden make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0 - 75 Kg/cm2.(2.00 Nos)
-
-
-
... More
Providing 65 mm dia. vacume dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0 - 760 mercury.(2.00 Nos)
-
-
-
... More
Installation of all the items appearing at Serial No. 31 to 38 complete in all respect as per direction of Engg-inCharge.(1.00 Job)
-
-
-
... More
Providing and fixing double flanged piping work layout to be approved by the Engineer-in-Charge for suction and delivery pipes suitable to pump(s) offered and common header as per the rising main respectively complete with all specials such as bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS: 1364-1983. The pipes shall be as per relevant IS Code and to withstand 1.5 times total head stipulated under item No.30.(1.00 Job)
-
-
-
... More
The size of the various components to be as under:-
-
-
-
... More
(i) Suction pipe 65 mm dia Min. length = 10 mtr.
-
-
-
... More
(ii) Delivery pipe 50 mm dia -do- = 6 mtr.
-
-
-
... More
(iii) Common Header 65 mm dia -do- = 6 mtr.
-
-
-
... More
and will extend up to 5 meters from the outer wall of the pump house in the direction to be jointed.
-
-
-
... More
Providing and laying copper PVC insulated armoured power cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of L&T/Finolex make including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor.
-
-
-
... More
(i) Motor side: 4 mm2 Min length = 20 mtrs. (20.00 per Rmt)
-
-
-
... More
(ii) Supply side: 10 mm2 Min. length = 10 mtrs.(10.00 per Rmt.).
-
-
-
... More
Providing and fixing double loop earthing and Cu plate 600 mm x 600mm x 3mm thick electrode complete with material such as thimbles, nuts and bolts, charcoal and common salt, 20 mm x 3 mm G.I. strips & G.I. wire of 4 SWG as per IS: 3043 -1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect.(1.00 Job)
-
-
-
... More
Centrifugal Pump (LWSS Ghori Matoli Phase-II):- Supply & errection of horizontal spindle horizontal split casing/end suctions (back pull out arrangement) Single/double/multistage centrifugal pumps or combination of pumps in series/parellel of Mather & Platt/KSB/ Kirloskar or JSV approved make conforming to BIS 1520-1980 pump (Latest with up to to date amendments), read with BIS: 9137-1978 (latest edition) suitable for lifting clear water of under mentioned characteristics with bronze/Suitable alloy, priming funnels, casing ring and shaft motor of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel plate (base plate from the principal manufacturer of pumping set) to coupling 3 phase squirrel cage electric induction motor of standard make such as Kirloskar/ NGEF/Cromption or JSV approved make conforming to IS 12615-2018 and should be energy efficient minimum IE2 compliant and totally enclosed fan cooled (TEFC) type ( latest with upto date ammendments) it should include the cost of bearings, nuts & bolts, painting etc. and shall be suitable for operation on the data given below: 2 Sets of 10 HP.
20
-
-
... More
SITE CONDITIONS:- Total Head 89.13 mtrs
Discharge required 3.00 LPS each set.
No. of Pump required. 2.00 No. set (1 Nos. act as Standbye)
Length of R/main 1045 mtrs.
Dia of R/main 65 mm dia Location of the site of installation of machinery-The site is located near village Ghori & 400 mtr head load from nearest road head (for the installation of both machinery). Head Load (for the installation of both machinery).
The Altitude of :- The Altitude of place is 860 mtrs above MSL
Type of Current:- AC three phase supply with
Rated Voltage:- 415 +/- 10% Type of water :- Clear water
Charactristics of water :- a) Ambient Temperature
b) Turbidity NTU 50.00 NTU
c) Hardness 260 Mg/Ltrs --
d) PH Value 7.5 --
e)Total Solid Mg/Lts)PH Value --
No of working hours. 8 Hours.
Limit of Pump (-) 15% (+) 10% R.P.M. of Pumping RPM(or to be specified by the tenderer)
Test run 8 Hours continueously for 7 days.
-
-
-
... More
Providing ICTP Main Switch 32 Amp with HRC fuses / Side handled operated Change over switch of L&T/Crompton/Standard/Havells or JSV approved make suitable capacity Operational rating as per IS: 4064 (Part - II) 1978 with up to date amendments immediately after the power meter of HPSEB. (1.00 No)
-
-
-
... More
Providing M.S. sheet, steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm, duly painted, with steel sheet of 16 gauge comprising, capable of mounting the following accessories with all internal connections.(1.00 No)
-
-
-
... More
M.C.B. 32 Amp. Havell/MDS/Standard/Jyoti or JSV approved make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516 (Part - II) 1985 with up to date amendments.(1.00 No)
-
-
-
... More
E.L.C.B. 32 Amp. of Havell/MDS/INDETEC or JSV Approved Make make as per IS: 2516 (Part - II) 1985 with upto date amendment which should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape etc. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.(1.00 No)
-
-
-
... More
The voltage monitor relay of L&T/AE make three phase with all protection and usual indicator and electric siren against single phasing low voltage, high voltage, reverse phasing, over loading and phase voltage difference as per IS: 1248 (Part - II ) 1983 (Latest edition).(1.00 No)
-
-
-
... More
100mm square type A.C. supply voltmeter . of AE/L&T Rishab make of suitable range (0-500 Volt) with selector switches as per IS: 4064 (Part - II ) -1978 with up to date amendments.(1.00 No)
-
-
-
... More
Power factor meter of AE/L&T Rishab make as per IS: 1248 (Part - V ) 1983 (Latest edition) with up to date amendments of suitable rating.(1.00 No)
-
-
-
... More
Frequency meter of AE/ L&T Rishab make as per IS: 1248 (Part - IV ) 1983 ( Latest edition) with up to date amendments of suitable rating.(1.00 No)
-
-
-
... More
Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11354-1985 read with IS 5578-1985 with up to date amendments.(1.00 Set)
-
-
-
... More
ICTP switches with HRC fuses 30 Amp of L&T/ Standard/Havells make and of suitable capacity as per IS: 4064 (Part - II) -1978 with up to date amendments.(2.00 Nos)
-
-
-
... More
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 ( P-I & II) with up to date amendments.(1.00 Set)
-
-
-
... More
100mm Square type AC supply Ammeter 30 Amp. of AE /L&T Rishab make of suitable range (0-200) with selector switches and CTS operated as per IS:1248 (P-II) 1983 with up to date amendments.(2.00 Nos)
-
-
-
... More
Supply & errection of floor/wall mounted power factor shunt capacitor of L&T make as per IS:2834 -1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of 3 KVAr rating according to HP offered including cables as per relevant ISI code (of L&T/Finolex make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064 (Part - II) 1978 with upto date amendments. .(2.00 Nos)
-
-
-
... More
Providing suitable Star Delta starter of M.E.I / Kilburn make as per IS:8544 (Part - II ) -1987 with up to date amendments for Squirrel Cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments..(2.00 Nos)
-
-
-
... More
Providing Hour run meter of recommended make as per IS: 722 (Latest edition) .(2.00 Nos)
-
-
-
... More
Providing double flanged Cast iron sluice valve of Leader/Kirloskar make or JSV approved make of 50 mm dia for the suction pipe and capable of withstanding the normal seat pressure as per IS: 14846-2000 with up to date amendments. (Class PN-1.6).(2.00 Nos)
-
-
-
... More
Providing double flanged Cast steel sluice valve of Leader/Kirloskar make or JSV approved make and size of 40 mm dia. and capable of with standing nominal seat pressure of 52 kg/cm2 as per BS : 1414 / API - 600 (Class ASA-150) .(2.00 Nos) .
-
-
-
... More
Providing double flanged Cast steel reflux valve of Leader/Kirloskar make or JSV approved make and size of 40 mm dia. and capable of with standing nominal seat pressure of 52 kg/cm2 as per: BS : 1868 / API - 600 (Class ASA-150) .(2.00 Nos) .
-
-
-
... More
Providing double flanged Cast steel 50 mm non return valve of Leader/ Kirloskar make or JSV approved make having bye pass arrangement for rising main and capable of with standing normal seat pressure of 52 kg/cm2 as per BS : 1868 / API - 600 (Class ASA-150) .(1.00 No) . .
-
-
-
... More
Providing 50 mm dia. circular dial pressure gauge of Fiebig/bourden make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0 - 75 Kg/cm2..(2.00 Nos)
-
-
-
... More
Providing 50 mm dia. vacume dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0 - 760 mercury..(2.00 Nos)
-
-
-
... More
Installation of all the items appearing at Serial No. 45 to 52 complete in all respect as per direction of Engg-inCharge..(1.00 Job)
-
-
-
... More
Providing and fixing double flanged piping work layout to be approved by the Engineer-in-Charge for suction and delivery pipes suitable to pump(s) offered and common header as per the rising main respectively complete with all specials such as bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thickness as per IS 2712-1979 and required number of nuts and volts as per IS: 1364-1983. The pipes shall be as per relevant IS Code and to withstand 1.5 times total head stipulated under item No. 44 (1.00 Job)
-
-
-
... More
The size of the various components to be as under:-
-
-
-
... More
(i) Suction pipe 50 mm dia Min. length = 10 mtr.
-
-
-
... More
(ii) Delivery pipe 40 mm dia -do- = 6 mtr.
-
-
-
... More
(iii) Common Header 50 mm dia -do- = 6 mtr.
-
-
-
... More
and will extend up to 5 meters from the outer wall of the pump house in the direction to be jointed.
-
-
-
... More
Providing and laying copper PVC insulated armoured power cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of L&T/Finolex make including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor.
-
-
-
... More
(i) Motor side: 2.50 mm2 Min length = 15 mtrs.(20.00 per Rmt.)
-
-
-
... More
(ii) Supply side: 4 mm2 Min. length = 10 mtrs.(10.00 per Rmt.)
-
-
-
... More
Providing and fixing double loop earthing and Cu plate 600 mm x 600mm x 3mm thick electrode complete with material such as thimbles, nuts and bolts, charcoal and common salt, 25 mm x 3 mm G.I. strips & G.I. wire of 8 SWG as per IS: 3043 -1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect.(1.00 Job)
-
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements