Himachal Pradesh Irrigation And Public Health Department Tender
Bidassist allows us to explore new opportunities across the whole world so as to support the growth of the business. It is designed in such a manner that if we need any kind of information about any government e-tender the Himachal Pradesh government has posted on its website, Bidassist provides the same in a very hassle-free manner. As BidAssist is designed as a very user-friendly website which helps us find the specific Himachal Pradesh etender we are looking for.
Himachal Pradesh Irrigation And Public Health Department - HPIPH Tender
Machinery and Tools
Eprocure
Opening Date6 Dec 2023
Closing Date14 Dec 2023
Tender Amount₹ 7,36,740
Costs
EMD
₹ 14,725Document Cost
₹ 250Tender Fee
Refer Documents
Summary
Remodeling Of Water Supply Scheme Kanger Khad In Tehsil Haroli Distt. Una (hp)
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_HPIPH_82360_1Bid Award Id
ViewTender No
No. JSV-1/TA/ E-tender/23- 17180-209 dt 06-12-2023Tender Authority
Himachal Pradesh Irrigation And Public Health Department ViewPurchaser Address
-Website
http://http://hpiph.org/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Providing , Fixing and welding of MS flanges conforming to table as specified below of BIS code 6392-1971( Latest with upto date ammendments) welding of M.S. flanges on ( Two layers on inner face and one layers on outer face of each flange) GMS pipes & bends on both ends ( The GMS pipe to be measured and paid for separately )The welding of flanges conforming to IS 816-1998 with electrodes as per IS 814-1997, prov.& fixed with nuts, bolts of required size conforming to IS 1364, provide & fixes 3 mm (Min.) thick compressed asbestos fibre / synthetic rubber gasket conforming relevant BIS Code IS 2712-1965 in trenches complete in all respect& i/c entire carriage of materials in all leads and lifts as per the directoon of the Eng. in-Charge
-
-
-
65 mm dia Table-5
6
-
-
65 mm dia Table-17
2
-
-
Providing circumferencial Butt welded joints by electrical arc welding to GMS pipe, welded in three layer number of weld runs so as to achieve the minimum effective throat thickness of weld conforming to IS: 816-1969 specifications, by using welding electrodes conforming to IS:814-1991, at site of work complete in all respects, including manual / mechanical handling of pipes in all leads and lifts to the entire satisfaction of Engineer-in-Charge.
-
-
-
GMS Pipe (H) 65 mm dia
152
-
-
Supply of submersible pumping set of KSB/ Calama / BS/ Worthigton / Sabar/ Seerex /Johnston / Amrut confirming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ; 5659-1978 with upto date amendments, suitable for raw / clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to submersible motor of same as that of offered submersible pump make confirming to BIS ; 9283-1979 with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed, lubricated bearing and provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum wear and tear. It should also be fitted with a device to make up expantion of water with heating of motor. The pumpset should include water level guard i/c cable, errection clamps, cable clips and depth gauge etc. and suitable for opertion on data given below:- (a) Pump :- Specifications i) Make ii) Model iii) No. of stages iv) Manfacuring' certificate o be attached performance i) Discharge ii) head Make ii) Model iii) efficiency of pump a) duty Head b) (+) 10% duty head c). (-) 15% Duty Head d) performance curve to be attached b). Motors:- Specificions Make ii) Model iii) BHP iv). speed v) Insulation
2
-
-
Discharge = (Q) 7.12 LPS
-
-
-
Total Head = ( H) 111.72 Mts.
-
-
-
a) SWL in Tubewell = 57.50 Mtr. bgl.
-
-
-
c) R.L. point of discharge =103.00 Mtr.
-
-
-
d) Seasonal fluctuation + draught condition + bowl assembly. = 9.00 Mtrs.
-
-
-
e) Drawdown in Tubewell =31.40 Mtrs.
-
-
-
f) R.L of lowest point of pumpset installation = 2.10mtrs.
-
-
-
g) Static column lift = 97.90 Mtrs.
-
-
-
Rising main.
-
-
-
Length 30 Mtrs.
-
-
-
Dia meter. 80 mm
-
-
-
Class GMS Pipe (MG)
-
-
-
Column Pipe.
-
-
-
Length 107.90 Mtr.
-
-
-
Dia 80 mm
-
-
-
Class GMS. (M)
-
-
-
Pumping hours = 8.00 Hours
-
-
-
Altitude of installations above M.S.L. 350 Mtr.
-
-
-
Characteristic of water.
-
-
-
a) Temperature 20 Deg Cel.
-
-
-
b) Turbidity ________JTU.
-
-
-
c) Allkanity. ___________mg/ l Ca Co3
-
-
-
d) Size of solids ____________mm
-
-
-
e) others
-
-
-
Depth of T/well = 140.00Mtr.
-
-
-
Dia of T/ well assembly 300mm & 200 mm
-
-
-
Length of assembly pipe. 124.00 meter .
-
-
-
Dia of housing pipe 300 mm
-
-
-
Length of housing pipe. meter
-
-
-
OPERATING CONDITIONS.
-
-
-
Type of Current :- A.C.Three Phase.
-
-
-
Frequency:- 50 Cycles /Sec.
-
-
-
Rated Voltage 415 +/- 15 % Volts.
-
-
-
System of earthing:- Double Loop earthing as per BIS 3843-1987 Latest.
-
-
-
Speed of Revolution ____________ RPM 2900
-
-
-
MOTOR.
-
-
-
Ref. to BIS code BIS 9283-1979 with upto date amendments.
-
-
-
Type of enclosure of motor: As per BIS ; 4691-1985 ( latest )
-
-
-
Mechanical out put in H.P.
-
-
-
Class of insulation : Class B
-
-
-
The motor should be able to withstand initial current of 2.50 times the rated current for two minutes without suffering damages of permanent deformations.
-
-
-
PUMP
-
-
-
Ref. to BIS code ; BIS ; 5659-1978 with upto date amendments.
-
-
-
Driver Type: Electric driven.
-
-
-
Operating Range: -15 % to+10 % of Total head at duty point.
-
-
-
Delivery size of Pump : ________( To be quoted by tenderer.)
-
-
-
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947- P I & II with upto date amendments. i) Make : ii) Type : iii) Capacity : 63 amp.
1
-
-
Providing MS Sheet steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections. Panel/ Switch Board i) Drawing. ii) Layout Plan
1
-
-
MCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments. i) Make : ii) Type : iii) Range 63 amp. iv) Capacity
1
-
-
ELCB of recommended make L&T /Havells as per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault. ELCB i) Make : ii) Type : iii) Range 63 Amp. iv) Capacity
1
-
-
The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage, reverse phasing, overloading and phase voltage difference as per IS; 3842 ( Latest Edition )i) Make : ii) Type : iii) Range 0-500.
1
-
-
A.C. supply, voltmeter of recommended make Havells/A.E./ L&T of suitable range with selector switches as per IS ;1248-1983 with latest amendments. Voltmeter i) Make : ii) Type : iii) Range 0-500.
1
-
-
AC supply ammeter of Havells/ A.E / L&T make of suitable range with selector switches and CIS operated as per IS :1248 ( P-I&II ) -1983 with upto date amendments. Ammeter i) Make : ii) Type : iii) Capacity 60 Amp.
1
-
-
Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS ; 8084-1976 and IS : 11353-1985 read with BIS ; 5578 -1985 with upto date amendments including. 3 phase indicators i) Make : ii) Type : iii) Rating
1
-
-
Three phase indicator lamps complete with toggle switches for individual motors as per IS 3452 (P- I&II ) with upto date amendments. 3 Phase indicators
1
-
-
Capacitor of BHEL / L&T make as per IS ; 2834-1968 with upto date amendments, to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter/ IEC make) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments .Rate of capacitor will be approved by HPSEB. i) Make : ii) Type : iii) Range. 5 KVAR
1
-
-
Providing suitable starter of L&T/ Havell's /BHEL make as per IS :13947-II with upto date 'amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic 'type overload release and dashpot, time lag, under voltage release, with or without 'initial oil filling as the case may be with Air Break. Type Star Delta with single phase preventor as per IS ;1248 ( P-V ) 1983 with up to date amendments. Single Phase Preventor i) Make : ii) Type : iii) Range.
1
-
-
Providing and fixing double flanged Cast iron Sluice valve of Leader / Kirloskar /Kartar/LP/RG Brand make for the delivery line of pump and capable of withstanding the normal seat pressure and as per IS :- 780-1992 with latest ammendments i) Make : ii) Type : iii) Make :- Cast Iron Class PN-1.00 for Column Pipe 805 mm dia
1
-
-
Providing and fixing double flanged swing type cast Iron Reflux valve of Leader/ Kirloskar/Kartar / LP/RG Brand make having Bye pass arrangement on the delivery line of the Pump and capable of 'withstanding normal Seat Pressure as per IS:15312 Part-1 with latest ammendments i) Make : ii) Material : Cast Iron iii) Class PN-1.0 For for R/main 80 mm dia.
1
-
-
Providing and fixing pressure gauge of Prega / Precision make complete with all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendements. i) Make :
1
-
-
Supply of PVC jointless, flat water proof cable with copper conductor as per BIS 694-1998 latest with upto date ammendments of Havells/ Finolex make suitable for the pumpsets offered from MCB to motor including all other electrical equipments / accessories such as thimble, flexible pipe, solder, nuts and bolts, cable glands, clips etc, laid in pipes or trenches under floor. The type, size and make shall be subject to approval of HPSEB authorities. i) Make : Finolex/ Havells ii) Size 3x 6.00 mm2 iii). type- IV capacity V Core-3
86
-
-
Lowering of GMS Column pipefor assembly 125 mm dia including MS flanges' of Table 17 as per IS : 6392-1971 with upto date amendments, rubber/asbestos gasket of min. 3mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 . The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated under item No. 5.03 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction of Rising main . The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2Nos.) at the top of T/well assembly, and as per the direction of Engineer - in - Charge. (The pipe shall be supplied by the Department free of cost from Divisional Store Malahat. Column Pipe 125 mm dia GMS pipe
43
-
-
Installation of all items appearing as above as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
1
-
-
Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 (P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay /Finolex/ Havells make including all other accessories such as thimble, flexible pipes, solder nuts and bolts, cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A) Supply Side From meter of HPSEB to Bus Bar and Switch) i) Size 10.00 mm2 ii) Make Finolex/Havells. iii) Type iv) Capacity v) Core 3.
1
-
-
Providing and fixing double loop earthing with G.I. plate 600 mmx600mmx6.3 mm thick electrode complete with material such as thimble, nuts and bolts, charcoal, salt, common as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) 25x3 mm upto 20 HP
1
-
-
Centrifugal Pumping Machinery alongwith allied accessories
-
-
-
Providing horizontal spindle, horizontal / radial split casing /end suction ( back pull out arrangement ) Single /double /multi stage centrifugal Pumps combination of pumps in series/parallel of recommended makes such as Mather and plant/ Kirlosker / BE/Jyoti/LUBI/Grand Fos/ Hindustan as per BIS IS 1520-1980 with upto date amendments read with IS: 9137-1978 or latest edition suitable for lifting water for under mentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron / cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring / Squirrel cage screen protected drip proof induction motor / motors of standard make such as Crompton / NGEF / GEC / Seimens /Jyoti/ Kirloskar BHEL / ABB suitable for operation on 415 (+/-15%) volts. 50 Cycles /Sec. 3 phase AC electric supply of 2900 RPM.The power of electric motor/ motors should be at least +10% in excess of the maximum power required by the pump / pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor / motors as per IS 325 IS -1978 with upto date amendments read with IS 900 -1972. It should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements. (a) Pump :- Specifications i) Make ii) Model iii) No. of stages iv) Manfacuring' certificate o be attached performance i) Discharge ii) Total head iii) BHPl iv) efficiency of pump v) performance curve to be attached b).Motors:- Specificions Make ii) Model iii) Raing iv). speed v) Coupling of Base plate
2
-
-
Discharge (Q) = 2.26 LPS.
-
-
-
Total Head (H) = 61.58 Mtrs.
-
-
-
a)LWL In Sump well = 100.00 mtr
-
-
-
b)R.L. of shaft = 100.00 Mtrs.
-
-
-
c)R.L. of discharge Pt. = 141.70 Mtrs.
-
-
-
d)Suction lift. +ve mtrs.
-
-
-
e)Discharge Head = 0.00 Mtrs.
-
-
-
f) Static Head = 41.70 Mtrs.
-
-
-
Rising main.
-
-
-
Length = 960 Mtrs.
-
-
-
Diameter = 65 mm. dia
-
-
-
Class GMS Tube(M)
-
-
-
Pumping hours. = 8 Hours.
-
-
-
Altitude of installations above M.S.L =425 mtrs.
-
-
-
Characteristic of Water
-
-
-
a)Temperature 20 Deg.Col.
-
-
-
b)Turbidity ________ JTU
-
-
-
c)Alloanity _________ mg/1 ca Co3
-
-
-
d)Size of solids __________ mm
-
-
-
e) Others.
-
-
-
Providing ICTP Main Switch with HRC fuses of L&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947-P I & II with upto date amendments.i) Make : ii) Type : iii) Capacity : 32 amp.
1
-
-
Providing MS Sheet, steel fabricated floor mounted closed (Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm duly painted with steel sheet of 16 Gauge comprising and capable of mounting the following acccessories with all internal connections.
1
-
-
i) MCB of L&T / Havells make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per IS: 2516--1985 with upto date amendments . i) Make : ii) Type : iii) Capacity : 32 Amp.
1
-
-
ii)ELCB of recommended make L&T / Havells make as per IS: 2516-1985 with upto date ammendments, and of suitable range which should have control box, operating handle and trip / reset bush button on / off of indicators, reindicating off spring condition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal release with metallic tape CTS. It should also be fitted with earth fault for tripping of breaker on occurence of Earth fault. i) Make : ii) Type : iii) up to 32 Amp
1
-
-
iv )The voltage monitor Relay three Phase with all protection and usual indicator and electric siren against single phasing, low vaoltage, high voltage reverse phasing, overloading and phase voltage difference as per IS 3842 ( Latest Edition). i) Make : ii) Type : iii) Range:0-500
1
-
-
100 mm diameter circular, A.C. supply, voltmeter of recommended make Havells / AE / L&T of suitable range with selector switches as per IS: 4064-1978 with latest up to ammendments.i) Make : ii) Type : iii) Range: 0-500
1
-
-
Power factor meter of standard make as per relevent IS code with upto date ammendments.i) Make : ii) Type : iii) Range: 0-500
1
-
-
Frequency meter of standard make as per relevent IS code with upto date ammendments..i) Make : ii) Type : iii) Range: 0-500
1
-
-
Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three line phases and suitable for induced current one copper bar of half the rating of full length for neutral phase as per IS : 8084-1976 and IS: 11353-1985 read with BIS : 5578- 1985 with upto date ammendments including.i) Make : ii) Type : iii) Rating 32 Amp.
1
-
-
Three phase indicator lamps complete with toggle switches for individual motors as per IS: 3452 (P-I&II) with upto date ammendments. i) Make : ii) Type : iii) Capacity
1
-
-
100 mm diameter AC supply Ammeter of Havells / AE/ L&T make of suitable range with selector switches and CIS operated as per IS: 1248 (P-I&II)-1983 with upto date ammendments.i) Make : ii) Type : iii) Capacity : 60 Amp.
1
-
-
Capacitor of BHEL / L&T make as per IS : 2834-1986 with upto date ammendments, to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevant ISI code (of Seimens / Clocter / IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064-1978 with upto date ammendments, Rating of capacitor will be approved by HPSEB. i) Make : ii) Type : iii) Range 4 KVR
1
-
-
Providing suitable Starter of L&T / Havell's / BHEL make as per IS : 13947-II with upto date 'amendments for Squirrel cage / Slipring motor mounted on panel board with magnetic type over load release and dashpot, time lag under voltage release, with or without 'initial oil filling as the case may be with single Phase preventor as per IS ;1248 ( P-V ) 1983 with up to date amendments. i) Type ii) Make
1
-
-
Providing and fixing of double flanged foot valve with with stainer of as per IS 188- 1999 with update ammendments of Kirloskar/Leader / Kartar/LP/RG Brand make for suction pipe of 65 mm dia.
1
-
-
Providing and fixing of double flanged Cast iron swing type reflux valve of kirloskar/Leader / Kartar/LP/RG Brand make IS 5312 Part 1 of 65 mm dia for rising main rising Main and capable with standing the normal Seat Pressure as per IS 5312-1992 part-1 class PN 1.00 upto date ammendments i)Make ii)Class PN 1.00 iii)Seat pressure(MPa) iv)Material Cast iron
1
-
-
Providing and fixing of double flanged Cast iron swing type reflux valve of kirloskar/Leader / Kartar/LP/RG Brand make IS 5312 Part 1 of 65 mm dia for rising main rising Main and capable with standing the normal Seat Pressure as per IS 5312-1992 part-1 class PN 1.00 upto date ammendments i)Make ii)Class PN 1.00 iii)Seat pressure(MPa) iv)Material Cast iron
1
-
-
Providing and fixing of double flanged Cast iron swing type reflux valve of kirloskar/Leader / Kartar/LP/RG Brand make IS 5312 Part 1 of 65 mm dia Delivery pipe and capable with standing the normal Seat Pressure as per IS 5312-1992 part-1 class PN 1.00 upto date ammendments i)Make ii)Class PN 1.00 iii)Seat pressure(MPa) iv)Material Cast iron
1
-
-
Providing circular dial pressure gauge of Precision / Fiebig make complete with all accessories such as stop cock, Copper tubing etc. as per IS: 3624-1987 with upto date ammendments. i) Make : Range.
1
-
-
Installation of all above items appearing above as per the systematic drawing attached with the documents or as per the direction of Engineer-in-Charge. .`
1
-
-
Fixing double flanged GMS piping work ( Layout to be approved by Engineer-in-Charge). for suction suitable to pumps offered and as per the rising main respectively complete with all specials such as bends, Tees, Reducers / Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing including rubber / asbestos gasket of 3 mm thickness as per IS : 2712-1979 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.50 times total head stipulated under item No.26.01.( GMS PIpe shall be issued by the department free of cost from Divisional store Malahat . The size of various components to be as under:-
-
-
-
Suction Pipe 65 mm dia. (M)
10
-
-
Delivery Pipe 50 mm dia. (M)
10
-
-
and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of 65 mm dia to be joined.
-
-
-
Providing and laying copper PVC Insulated 3 core armoured power cable (One cable carrying all the three phases) of suitable size and capacity to Motors and all other elelctrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Seimen / Gloster / IEC / ICC / EICO / National / Grandlay / finolex / Havell make ' including all other accessories such as thimble, flelxible pipes, solder, nuts & bolts, cable glands etc. laid in pipes or trenches under floor. Armoured Power Cable (A) Motor side (From Switch to Starter & Starter to motor) i) Size 2.5 mm2 ii) Make iii) Type - Armounred power cable iv) Capacity v) Core 3 (B) Supply Side (From meter of HPSEB to Bus Bar & Switch) i) Size 2.50 mm2 ii) Make iii)Type - Armounred power cable iv) Capacity v) Core 3
1
-
-
Providing and fixing double loop earthing with G.I. plate 600 mmx600mmx6.3 mm thick electrode complete with material such as thimble, nuts and bolts, charcoal, salt, common as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) Copper wire 8 SWG upto 20 HP
1
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements