If you want to inquire about any e-tender the Haryana government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Haryana tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Haryana etender you're looking for. Read further to learn how to search and bid for etender Haryana.
Costs
EMD
₹ 8,360Document Cost
₹ 500Tender Fee
₹ 1,180
Summary
Construction Of Hospital Kitchen In Pt. B.d. Sharma, Uhs, Rohtak (providing Fire Alarm System Only)
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_HRY_408122_1Bid Award Id
ViewTender No
20240C90C2D6 07E8 42EB 8629 AE81BD915C6E667BARTender Authority
Public Works Department ViewPurchaser Address
-Website
http://https://haryanapwd.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
Supply and Erection of Fire Extinguishers complete in all respect. Make:- Safex / Minimax / Cease Fire
ABC 6KG Cap ISI Mark 15683
4
-
-
Supply, installation, testing and commissioning of minimum 500 Mtr. Range Siren provided at the roof of the building with separate power supply, relay etc. with all accessories required to complete the job in all respect up to the entire satisfaction of engineer in charge. Make: - National / Kheraj
1
-
-
Supply, Installation, Testing and Commissioning of Micro Processor Based 2 Wire Fault Tolerant, Networkable Type Fire Alarm / Detection Control Panel (having no. of loops to suit minimum 20% extra over the nos. of fire detectors). The panel shall be able to give location of all fire / fault conditions of addressable units via the address codes. Further, the panel must have access levels and Panel should be able to automatically switch ON/OFF respective control module when ever any alarm is triggered. The panel shall have rectifier, loop cards, minimum 160 characters LCD unit/ min. 5.7`TFT to indicate Fire / Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects. The Panel Shall be sheet Steel power coated, sealed to IP30. The Panel shall have 20 Zones with individual LED Indicators, expandable to 40 LED Indicators. The Panel shall have Serial Ports. Panel Power supply should be 24V-150W.The panel shall have a built in power supply, battery charger capable of running for a minimum 24 hours operation complete as required . RH 5% - 95% non-condensing and conforming to BS5839 standards and Duly Approved by EN 54/UL/VDS as per specifications complete in all respect up to the entire satisfaction of Engineer-in – charge of work. Make: - Honeywell Morley / Siemens Cerberus / Bosch FPA / GST
1
-
-
Supply, Installation, Testing and Commissioning of Intelligent Analog Addressable Type Smoke Detector that combine Photoelectric and fixed temp thermal with dual LED, hard addressable having rotary decade address switches, with mounting base complete as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the Job in all respect up to the entire satisfaction of the Engineer in charge of the work.
Make: - Honeywell Morley / Siemens Cerberus / Bosch FPA / GST
20
-
-
Supply, Installation, Testing and Commissioning of Addressable Heat Detector with fixed and rate of raise feature including mounting base with LED etc complete as required. Each detector should have 2 as per NFPA 72 style 7 wiring requirement (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005. Detector should monitor electromagnetic interference and report to the panel current and average values, EMC safety for detector shall be 50 V/m. shall be EN54/VDS/U: certification. (Detectors without inbuilt isolators may be considered with an additional isolator module per detector. Make: - Honeywell Morley / Siemens Cerberus / Bosch FPA / GST
16
-
-
Supply, Installation, Testing and Commissioning of Intelligent Analog Addressable Type Manual Call Point having Surface or flush mounting option fully compliant to EN 54 having Rotary Decade switches for addressing with back box for mounting as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect. Make: - Honeywell Morley / Siemens Cerberus / Bosch FPA / GST
4
-
-
Supply, Installation, Testing and Commissioning of Addressable Loop Powered sounder with strobe / flasher complete with mounting base as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect Make: - Honeywell Morley / Siemens Cerberus / Bosch FPA / GST
2
-
-
Supply, Installation, Testing and Commissioning of Addressable Control Relay Module with flexible network structures with a maximum switching current of 1A @ 30V DC and Operating Temp: -20 ºC to plus 60 ºC and Operating voltage 15 to 30 Vdc. RH (=95%. Shall be EN54/UL/VDS Certification Make: - Honeywell Morley / Siemens Cerberus / Bosch FPA / GST
1
-
-
Supply, Installation, Testing and Commissioning of Addressable Monitor Module for monitoring of a line with EOL resistor/ Potential free contact/voltage monitoring shall be EN54/UL/VDS approved. (In case of 2 monitoring features in one module (points) each point shall be consider separately for payment).
Make: - Honeywell Morley / Siemens Cerberus / Bosch FPA / GST
1
-
-
Supply, Installation, Testing and Commissioning of Addressable Type Fault Isolator for isolating shorted, de-linked and loose circuits between two successive fault isolators with automatic resetting arrangement to be interconnecting to loop cable complete as required conforming to BS5839 standards and duly approved by EN54/UL/VDS/BSA with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer in charge of the work.
Make: - Honeywell Morley / Siemens Cerberus / Bosch FPA / GST
1
-
-
Supply, Installation, Testing and Commissioning of Glow Type EXIT Sign Board Photo luminescent of size 300 mm x 250 mm x 1.5 mm rigid sheet signage containing Zink Sulphate as bare chemical class – 1 material PSPA fixed on 3 mm acrylic sheet on both side showing marking (running man, Arrow and Exit) and hanged with the ceiling with chain and fastener including cost of labour and material required to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work.
Make: - Glolite / Pearl/ Omex
4
-
-
Supply and Erection of PVC FRLS unsheathed Copper Conductor Cable Two Core 1100 volts grade in pipe of suitable size excluding cost and erection of pipe. Make Polycab / Havells / Finolex 2 core PVC unsheathed Copper Size 1.5 Sqmm
780
-
-