Public Works Department Tender
If you want to inquire about any e-tender the Haryana government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Haryana tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Haryana etender you're looking for. Read further to learn how to search and bid for etender Haryana.
Costs
EMD
₹ 6,37,100Document Cost
₹ 15,000Tender Fee
₹ 1,180
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_HRY_383670_1Bid Award Id
ViewTender No
20243A449F1A B713 4612 BAC2 CA81D78E8C14663BARTender Authority
Public Works Department ViewPurchaser Address
-Website
http://https://haryanapwd.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
[24.1.12]EARTHING AND LIGHTENING ARRESTOR 12. Supplying and laying 6 S.W.G G.I. wire at 0.50 m below ground level from earth electrode including thimbles, soldering etc. as required.
100
-
-
[24.1.4]EARTHING AND LIGHTENING ARRESTOR 4. Earthing with tinned copper earth plate 600mmx600mmx3mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) etc. complete as required.
2
-
-
[24.1.5]EARTHING AND LIGHTENING ARRESTOR 5. Extra for charcoal or coke and salt for G.I. plate or copper plate earth electrode.
2
-
-
[24.1.9]EARTHING AND LIGHTENING ARRESTOR 9. Providing and fixing 25 mm x5 mm copper strip in 40 mm dia G.I. pipe from earth electrode as required.
75
-
-
[24.4.7.2]STREET LIGHT 7.2. Supplying and embedding following dia G.I. pipe (medium class) in pole collar/ foundation (during casting) for cable entry including bending the pipe to the required shape complete as required. 40 mm dia
50
-
-
[25.1.1]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 1. 300mm dia.
60
-
-
[25.1.10]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 10. 40mm dia.
100
-
-
[25.1.2]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 2. 250 mm dia
150
-
-
[25.1.3]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 3. 200mm dia.
150
-
-
[25.1.4]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 4. 150mm dia.
72
-
-
[25.1.5]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 5. 125mm dia.
72
-
-
[25.1.6]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 6. 100mm dia.
36
-
-
[25.1.7]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 7. 80mm dia.
36
-
-
[25.1.8]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 8. 65mm dia.
124
-
-
[25.1.9]Supplying, fixing, testing and commissioning of condenser water pipes / non insulated chilled water pipes of following sizes of MS C class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. 9. 50mm dia.
66
-
-
[25.3.10]Supplying, fixing, testing and commissioning of Butterfly valves PN 16 rated without insulation for water circulation as per specifications. 10. 40mm dia.
8
-
-
[25.3.3]Supplying, fixing, testing and commissioning of Butterfly valves PN 16 rated without insulation for water circulation as per specifications. 3. 200mm dia.
8
-
-
[25.3.4]Supplying, fixing, testing and commissioning of Butterfly valves PN 16 rated without insulation for water circulation as per specifications. 4. 150mm dia.
16
-
-
[25.3.5]Supplying, fixing, testing and commissioning of Butterfly valves PN 16 rated without insulation for water circulation as per specifications. 5. 125mm dia.
2
-
-
[25.3.6]Supplying, fixing, testing and commissioning of Butterfly valves PN 16 rated without insulation for water circulation as per specifications. 6. 100mm dia.
1
-
-
[25.3.8]Supplying, fixing, testing and commissioning of Butterfly valves PN 16 rated without insulation for water circulation as per specifications. 8. 65mm dia.
8
-
-
[25.3.9]Supplying, fixing, testing and commissioning of Butterfly valves PN 16 rated without insulation for water circulation as per specifications. 9. 50 mm dia.
16
-
-
[25.4.1]Supplying, fixing, testing and commissioning o NON - RETURN VALVE with dual plate of C I body SS plates vulcanized NBR seal flanged end and PN 16 pressure rating as specified. 1. 200mm dia.
2
-
-
[25.4.2]Supplying, fixing, testing and commissioning o NON - RETURN VALVE with dual plate of C I body SS plates vulcanized NBR seal flanged end and PN 16 pressure rating as specified. 2. 150mm dia.
2
-
-
[25.5.1]Supplying, fixing, testing and commissioning o BALANCING VALVE flanged end and PN 16 pressure rating as specified. 1. 200mm dia.
2
-
-
[25.5.2]Supplying, fixing, testing and commissioning o BALANCING VALVE flanged end and PN 16 pressure rating as specified. 2. 150mm dia.
2
-
-
[25.5.4]Supplying, fixing, testing and commissioning o BALANCING VALVE flanged end and PN 16 pressure rating as specified. 4. 100mm dia.
1
-
-
[25.5.6]Supplying, fixing, testing and commissioning o BALANCING VALVE flanged end and PN 16 pressure rating as specified. 6. 65mm dia.
4
-
-
[25.5.7]Supplying, fixing, testing and commissioning o BALANCING VALVE flanged end and PN 16 pressure rating as specified. 7. 50mm dia.
7
-
-
[25.5.8]Supplying, fixing, testing and commissioning o BALANCING VALVE flanged end and PN 16 pressure rating as specified. 8. 40mm dia.
4
-
-
[25.6.1]Supplying, fixing, testing and commissioning o STRAINER flanged end and PN 16 pressure rating as specified. 1. 200mm dia.
2
-
-
[25.6.2]Supplying, fixing, testing and commissioning o STRAINER flanged end and PN 16 pressure rating as specified. 2. 150mm dia.
2
-
-
[25.6.3]Supplying, fixing, testing and commissioning o STRAINER flanged end and PN 16 pressure rating as specified. 3. 125mm dia.
1
-
-
[25.6.6]Supplying, fixing, testing and commissioning o STRAINER flanged end and PN 16 pressure rating as specified. 6. 65mm dia.
4
-
-
[25.6.7]Supplying, fixing, testing and commissioning o STRAINER flanged end and PN 16 pressure rating as specified. 7. 50mm dia.
7
-
-
[25.6.8]Supplying, fixing, testing and commissioning o STRAINER flanged end and PN 16 pressure rating as specified. 8. 40mm dia.
3
-
-
[25.7.1]Supply, installation, and commissioning of factory/site fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. 1. Thickness 0.63 mm sheet
1000
-
-
[25.7.2]Supply, installation, and commissioning of factory/site fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. 2. Thickness 0.80 mm sheet
500
-
-
[25.7.3]Supply, installation, and commissioning of factory/site fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. 3. Thickness 1.00 mm sheet
1
-
-
Supply and Erection of 4 Sq. mm 4 Core Cable Armoured under ground cable ,loose in existing pipe or trenches, complete with necessary connections including all required material to complete the job in all respect up to the entire satisfaction of the Engineer in charge of the work. Make: Havells/Polycab/RR.
60
-
-
Supply and Erection of 10 Sq. mm 4 Core Cable Armoured under ground cable ,loose in existing pipe or trenches, complete with necessary connections including all required material to complete the job in all respect up to the entire satisfaction of the Engineer in charge of the work. Make:- Polycab/ RR/Havells.
150
-
-
Supply and Erection of 240 Sq. mm 3.5 Core Cable Armoured under ground cable ,loose in existing pipe or trenches, complete with necessary connections including all required material to complete the job in all respect up to the entire satisfaction of the Engineer in charge of the work. Make: Polycab/RR/Havells.
50
-
-
Supply and Erection of PVC insulated aluminium armoured cable 25 Sqmm x 3.5 Core 1100 Volts grade to complete the job in all respect up to the entire satisfaction of Engineer in Charge of work. Make - Havell`s / R.R. Kabel / Polycab
55
-
-
Supply, installation, testing and commissioning of Capacity 1600 CFM (4TR) factory fabricated Fan Coil units complete with valve package and cordless remote of capacity as below :-
2
-
-
Providing and fixing in position industrial type SS pressure gauges having dial size 100 mm complete with SS syphon and cock. Make :- Fiebig / H Guru
4
-
-
Providing and fixing in position the automatic purging valves 25 mm dia Make : Rapid Cool / Anergy
5
-
-
Supply , installation , testing and commissioning of Axial Flow Fan - 5900 CFM SP 25 mmwg, with suitable motor and drive assembly, with all accessories and fire rated flexible connections, mounting frame hangers etc. Motor shall be suitable for 415 V plus /- 10%, 3 phase, 4 wire, 50 plus /- 3% Hzs, electric supply Make : Air Flow/ Humidin / Greenheck
4
-
-
Supplying and fixing of powder coated extruded aluminium Supply Air Grills / diffusers with aluminium volume control dampers as per specifications. Make : Swirl Air/ Systemair/Carryair
50
-
-
Supplying and fixing of powder coated extruded aluminium return Air Grills / diffusers without volume control dampers as per specifications. Make : Swirl Air/ Systemair/Carryair
50
-
-
Supplying, Fixing, testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. Make : Swirl Air/ Systemair/Carryair
16
-
-
Actuators Motor for Fire Dampers Make : Belimo/ Siemens/ Falcon
16
-
-
Supplying and fixing of Fresh air intake louvers with bird screen and dampers (Aluminium extruded only). Make : Swirl Air/ Systemaire/Carryair
8
-
-
Supplying and fixing of duct insulation with insulation `O` class anti microbiol density 32 Kg/m³. Applied by Adhesive, conforming to standard specification. 9 mm thick closed cell Nitrile rubber (indoor application).Make : Armacell/K-Flex/Arma Flex
1
-
-
Supplying and fixing of duct insulation with insulation `O` class anti microbiol density 32 Kg/m³. Applied by Adhesive, conforming to standard specification.13 mm thick closed cell Nitrile rubber (indoor application).Make : Armacell/K-Flex/Arma Flex
1500
-
-
Acousting Insulation of Duct from inside with covered 10 mm open cell insulation/board
50
-
-
Sub Panel :- P2 for AHUs Wall mounted sub panel boards for AHUs with starter inter connections, Current operated single phase preventors A/M switch etc as per specifications and drawings as required.1 No incoming 100 Amps 4 pole TP plus NL MCB 1 No star delta starter for motor 3 Nos indication lights 2 Nos Push Buttons complete in all respect upto entire satisfaction of Engineer in Charge of work.
16
-
-
Earth Station as per ISI Specification.
1
-
-
Miscellaneous civil work
1
-
-
SITC of 32 mm dia (with inlet filters) Ball Valves complete in all respect upto entire satisfaction of engineer in charge of work.
20
-
-
SITC of 25 mm dia (De-scaling valves) Ball Valves complete in all respect upto entire satisfaction of engineer in charge of work.
50
-
-
Supply and Erection of 6 Sq. mm 4 Core Cable Armoured under ground cable ,loose in existing pipe or trenches, complete with necessary connections including all required material to complete the job in all respect up to the entire satisfaction of the Engineer in charge of the work. Make Havells/Polycab/RR.
90
-
-
Supply, installation, testing and commissioning of factory fabricated Fan Coil units complete with valve package and cordless remote of capacity Capacity 600 CFM (1.5TR) complete in all respect upto entire satisfaction of Engineer in charge of work. Make : Zeco / Edgetech / Citizen
4
-
-
Supply, installation, testing and commissioning of factory fabricated Fan Coil units complete with valve package and cordless remote of capacity 800 CFM (2TR) complete in all respect upto entire satisfaction of Engineer in charge of work. Make : Zeco / Edgetech / Citizen
7
-
-
Supply, installation, testing and commissioning of factory fabricated Fan Coil units complete with valve package and cordless remote of Capacity 500 CFM (1.25TR) complete in all respect upto entire satisfaction of Engineer in charge of work. Make : Zeco / Edgetech / Citizen
1
-
-
Supply, installation, testing and commissioning of factory fabricated Fan Coil units complete with valve package and cordless remote of Capacity 400 CFM (1TR) Complete in all respect upto entire satisfaction of Engineer in charge of work. Make : Zeco / Edgetech / Citizen
3
-
-
Supply, installation, testing and commissioning of factory fabricated Fan Coil units complete with valve package and cordless remote of Capacity 1200 CFM (3TR) Complete in all respect upto entire satisfaction of Engineer in charge of work. Make : Zeco / Edgetech / Citizen
7
-
-
Supply, installation, testing and commissioning of factory fabricated Fan Coil units complete with valve package and cordless remote of Capacity 1000 CFM (2.5TR) Complete in all respect upto entire satisfaction of Engineer in charge of work. Make : Zeco / Edgetech / Citizen
17
-
-
Providing and fixing in position the following DIA 32 MM, MS `C` class pipes, cut to required length and installed with welded joints, providing and fixing all necessary fittings such as bends, elbows, tees, reducers, flanges, sockets etc.
100
-
-
Providing and fixing in position the following MS `C` class pipes, DIA 25 MM cut to required length and installed with welded joints, providing and fixing all necessary fittings such as bends, elbows, tees, reducers, flanges, sockets
150
-
-
Providing and fixing in position dial type mercury-in-glass filled industrial thermometers/ digital, complete in all respect upto entire satisfaction of Engineer in charge of work: Make :- Fiebig / H Guru
32
-
-
Pressurized Expansion Tank cap 500 ltrs insulated with 50mm thick EPS (Expanded Polystyrene) slab covered with Vapour Barrier, Chicken Wire Mesh and Finished with Sand Cement Plaster with overflow valve, float valve as specified by Engineer-in-charge. Make :- Sintex / Ploycon / ANERGY.
1
-
-
CHILLED WATER PIPE INSULATION: Providing and fixing in position the following DIA 200 MM Chilled water piping insulation including Valves and fittings with 50/25 mm thick EPS / NITRIL Pipe Section (TF Quality) covered with 2 layers of sand cement plaster each layer of 8 mm for exposed piping or 26 SWG Aluminium cladding over piping for indoor installation complete in all respect upto entire satisfaction of Engineer in Charge of work.
112
-
-
CHILLED WATER PIPE INSULATION: Providing and fixing in position the following DIA 150 MM Chilled water piping insulation including Valves and fittings with 50/25 mm thick EPS / NITRIL Pipe Section (TF Quality) covered with 2 layers of sand cement plaster each layer of 8 mm for exposed piping or 26 SWG Aluminium cladding over piping for indoor installation complete in all respect upto entire satisfaction of Engineer in Charge of work.
36
-
-
CHILLED WATER PIPE INSULATION: Providing and fixing in position the following DIA 125 MM Chilled water piping insulation including Valves and fittings with 50/25 mm thick EPS / NITRIL Pipe Section (TF Quality) covered with 2 layers of sand cement plaster each layer of 8 mm for exposed piping or 26 SWG Aluminium cladding over piping for indoor installation complete in all respect upto entire satisfaction of Engineer in Charge of work.
36
-
-
CHILLED WATER PIPE INSULATION: Providing and fixing in position the following DIA 100 MM Chilled water piping insulation including Valves and fittings with 50/25 mm thick EPS / NITRIL Pipe Section (TF Quality) covered with 2 layers of sand cement plaster each layer of 8 mm for exposed piping or 26 SWG Aluminium cladding over piping for indoor installation complete in all respect upto entire satisfaction of Engineer in Charge of work.
36
-
-
CHILLED WATER PIPE INSULATION: Providing and fixing in position the following DIA 80 MM Chilled water piping insulation including Valves and fittings with 50/25 mm thick EPS / NITRIL Pipe Section (TF Quality) covered with 2 layers of sand cement plaster each layer of 8 mm for exposed piping or 26 SWG Aluminium cladding over piping for indoor installation complete in all respect upto entire satisfaction of Engineer in Charge of work.
36
-
-
CHILLED WATER PIPE INSULATION: Providing and fixing in position the following DIA 65 MM Chilled water piping insulation including Valves and fittings with 50/25 mm thick EPS / NITRIL Pipe Section (TF Quality) covered with 2 layers of sand cement plaster each layer of 8 mm for exposed piping or 26 SWG Aluminium cladding over piping for indoor installation complete in all respect upto entire satisfaction of Engineer in Charge of work.
124
-
-
CHILLED WATER PIPE INSULATION: Providing and fixing in position the following DIA 50 MM Chilled water piping insulation including Valves and fittings with 50/25 mm thick EPS / NITRIL Pipe Section (TF Quality) covered with 2 layers of sand cement plaster each layer of 8 mm for exposed piping or 26 SWG Aluminium cladding over piping for indoor installation complete in all respect upto entire satisfaction of Engineer in Charge of work.
66
-
-
CHILLED WATER PIPE INSULATION: Providing and fixing in position the following DIA 40 MM Chilled water piping insulation including Valves and fittings with 50/25 mm thick EPS / NITRIL Pipe Section (TF Quality) covered with 2 layers of sand cement plaster each layer of 8 mm for exposed piping or 26 SWG Aluminium cladding over piping for indoor installation complete in all respect upto entire satisfaction of Engineer in Charge of work.
100
-
-
CHILLED WATER PIPE INSULATION: Providing and fixing in position the following DIA 32 MM Chilled water piping insulation including Valves and fittings with 50/25 mm thick EPS / NITRIL Pipe Section (TF Quality) covered with 2 layers of sand cement plaster each layer of 8 mm for exposed piping or 26 SWG Aluminium cladding over piping for indoor installation complete in all respect upto entire satisfaction of Engineer in Charge of work.
100
-
-
CHILLED WATER PIPE INSULATION: Providing and fixing in position the following DIA 25 MM Chilled water piping insulation including Valves and fittings with 50/25 mm thick EPS / NITRIL Pipe Section (TF Quality) covered with 2 layers of sand cement plaster each layer of 8 mm for exposed piping or 26 SWG Aluminium cladding over piping for indoor installation complete in all respect upto entire satisfaction of Engineer in Charge of work.
150
-
-
SITC of Weather proof isolator for cooling tower: Outdoor weather proof switch box of continuous welded construction, fabricated out of 2 mm thick GI sheet complete with water tight gasket with front openable and lockable door including earthing, painting glands, danger boards etc. Suitable for mounting on MS angle frame consisting of revelant specification and drawings, 63 Amps TP plus NL isolators for cooling tower near cooling tower complete in all respect upto entire satisfaction of Engineer in Charge of work.
2
-
-
Supply and Erection of 16 Sqmm 4 Core Cable Armoured under ground cable ,loose in existing pipe or trenches, complete with necessary connections including all required material to complete the job in all respect up to the entire satisfaction of the Engineer in charge of the work. Make Havells/Polycab/RR.
75
-
-
Supply and Erection of 3 Core 1.5 Sqmm Control Cable shielded and analyed copper for inter locking, complete with necessary connections including all required material to complete the job in all respect up to the entire satisfaction of the Engineer in charge of the work. Make Havells/Polycab/RR. .
100
-
-
Supply and Erection of 4 Core 2.5 Sqmm Control Cable shielded and analyed copper for inter locking, complete with necessary connections including all required material to complete the job in all respect up to the entire satisfaction of the Engineer in charge of the work. Make Havells/Polycab/RR. .
200
-
-
Providing and fixing in 32mm dia position the following balancing valves (PN-16) complete in all respect upto entire satisfaction of Engineer in Charge of work.
3
-
-
Providing and fixing in 25mm dia position the following balancing valves (PN-16) complete in all respect upto entire satisfaction of Engineer in Charge of work. .
39
-
-
Supply, installation, testing and commissioning of Cap 3000 CFM, Static pressure 80 mm of WC, Cooling Coil : Deep 6 Row, Filteration 10 Micron outgoing factory fabricated Double Skin Chilled Water Air- handling unit horizontal type fabricated out of extruded aluminium section consisting with 0.63 mm pre-plasticized/pre-coated Galvanized steel sheet outside and 0.63 mm plain Aluminium sheet inside . with blower, blower section and Blower shall be DIDW forward / Backward Curved blade from and blower motor TEFC type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, Multi Row deep cooling coil made of Aluminium finned Copper tube with coil section, pre - filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90% , stainless steel drain pan made out of 18 G sheet duly insulated complete with motor and belt drive package etc. The AHU panels shall be insulated with 48±2 mm thick and 38 Kg/m³ density PU foam. The motor and blower assembly shall be mounted on Aluminium extruded section. The complete AHU shall conform to standard specification and with 3 way modulating valve, thermostat/sensor etc. complete in all respect: Make : Zeco / Edgetech / Citizen.
2
-
-
Supply, installation, testing and commissioning of Cap 3500 CFM, Static pressure 80 mm of WC, Cooling Coil : Deep 6 Row, Filteration 10 Micron outgoing factory fabricated Double Skin Chilled Water Air- handling unit horizontal type fabricated out of extruded aluminium section consisting with 0.63 mm pre-plasticized/pre-coated Galvanized steel sheet outside and 0.63 mm plain Aluminium sheet inside . with blower, blower section and Blower shall be DIDW forward / Backward Curved blade from and blower motor TEFC type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, Multi Row deep cooling coil made of Aluminium finned Copper tube with coil section, pre - filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90% , stainless steel drain pan made out of 18 G sheet duly insulated complete with motor and belt drive package etc. The AHU panels shall be insulated with 48±2 mm thick and 38 Kg/m³ density PU foam. The motor and blower assembly shall be mounted on Aluminium extruded section. The complete AHU shall conform to standard specification and with 3 way modulating valve, thermostat/sensor etc. complete in all respect: Make : Zeco / Edgetech / Citizen.
3
-
-
Supply, installation, testing and commissioning of Cap 5000 CFM, Static pressure 80 mm of WC, Cooling Coil : Deep 6 Row, Filteration 10 Micron outgoing factory fabricated Double Skin Chilled Water Air- handling unit horizontal type fabricated out of extruded aluminium section consisting with 0.63 mm pre-plasticized/pre-coated Galvanized steel sheet outside and 0.63 mm plain Aluminium sheet inside . with blower, blower section and Blower shall be DIDW forward / Backward Curved blade from and blower motor TEFC type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, Multi Row deep cooling coil made of Aluminium finned Copper tube with coil section, pre - filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90% , stainless steel drain pan made out of 18 G sheet duly insulated complete with motor and belt drive package etc. The AHU panels shall be insulated with 48±2 mm thick and 38 Kg/m³ density PU foam. The motor and blower assembly shall be mounted on Aluminium extruded section. The complete AHU shall conform to standard specification and with 3 way modulating valve, thermostat/sensor etc. complete in all respect: Make : Zeco / Edgetech / Citizen.
2
-
-
Supply, installation, testing and commissioning of Cap 6000 CFM, Static pressure 80 mm of WC, Cooling Coil : Deep 6 Row, Filteration 10 Micron outgoing factory fabricated Double Skin Chilled Water Air- handling unit horizontal type fabricated out of extruded aluminium section consisting with 0.63 mm pre-plasticized/pre-coated Galvanized steel sheet outside and 0.63 mm plain Aluminium sheet inside . with blower, blower section and Blower shall be DIDW forward / Backward Curved blade from and blower motor TEFC type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, Multi Row deep cooling coil made of Aluminium finned Copper tube with coil section, pre - filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90% , stainless steel drain pan made out of 18 G sheet duly insulated complete with motor and belt drive package etc. The AHU panels shall be insulated with 48±2 mm thick and 38 Kg/m³ density PU foam. The motor and blower assembly shall be mounted on Aluminium extruded section. The complete AHU shall conform to standard specification and with 3 way modulating valve, thermostat/sensor etc. complete in all respect: Make : Zeco / Edgetech / Citizen.
4
-
-
Supply, installation, testing and commissioning of Cap 8000 CFM, Static pressure 80 mm of WC, Cooling Coil : Deep 6 Row, Filteration 10 Micron outgoing factory fabricated Double Skin Chilled Water Air- handling unit horizontal type fabricated out of extruded aluminium section consisting with 0.63 mm pre-plasticized/pre-coated Galvanized steel sheet outside and 0.63 mm plain Aluminium sheet inside . with blower, blower section and Blower shall be DIDW forward / Backward Curved blade from and blower motor TEFC type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, Multi Row deep cooling coil made of Aluminium finned Copper tube with coil section, pre - filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90% , stainless steel drain pan made out of 18 G sheet duly insulated complete with motor and belt drive package etc. The AHU panels shall be insulated with 48±2 mm thick and 38 Kg/m³ density PU foam. The motor and blower assembly shall be mounted on Aluminium extruded section. The complete AHU shall conform to standard specification and with 3 way modulating valve, thermostat/sensor etc. complete in all respect: Make : Zeco / Edgetech / Citizen.
1
-
-
Supply, installation, testing and commissioning of Cap 10000 CFM, Static pressure 80 mm of WC, Cooling Coil : Deep 6 Row, Filteration 10 Micron outgoing factory fabricated Double Skin Chilled Water Air- handling unit horizontal type fabricated out of extruded aluminium section consisting with 0.63 mm pre-plasticized/pre-coated Galvanized steel sheet outside and 0.63 mm plain Aluminium sheet inside . with blower, blower section and Blower shall be DIDW forward / Backward Curved blade from and blower motor TEFC type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, Multi Row deep cooling coil made of Aluminium finned Copper tube with coil section, pre - filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90% , stainless steel drain pan made out of 18 G sheet duly insulated complete with motor and belt drive package etc. The AHU panels shall be insulated with 48±2 mm thick and 38 Kg/m³ density PU foam. The motor and blower assembly shall be mounted on Aluminium extruded section. The complete AHU shall conform to standard specification and with 3 way modulating valve, thermostat/sensor etc. complete in all respect: Make : Zeco / Edgetech / Citizen.
2
-
-
Supply, installation, testing and commissioning of Cap 12000 CFM, Static pressure 80 mm of WC, Cooling Coil : Deep 6 Row, Filteration 10 Micron outgoing factory fabricated Double Skin Chilled Water Air- handling unit horizontal type fabricated out of extruded aluminium section consisting with 0.63 mm pre-plasticized/pre-coated Galvanized steel sheet outside and 0.63 mm plain Aluminium sheet inside . with blower, blower section and Blower shall be DIDW forward / Backward Curved blade from and blower motor TEFC type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, Multi Row deep cooling coil made of Aluminium finned Copper tube with coil section, pre - filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90% , stainless steel drain pan made out of 18 G sheet duly insulated complete with motor and belt drive package etc. The AHU panels shall be insulated with 48±2 mm thick and 38 Kg/m³ density PU foam. The motor and blower assembly shall be mounted on Aluminium extruded section. The complete AHU shall conform to standard specification and with 3 way modulating valve, thermostat/sensor etc. complete in all respect: Make : Zeco / Edgetech / Citizen.
1
-
-
Supply, installation, testing and commissioning of Cap 13000 CFM, Static pressure 80 mm of WC, Cooling Coil : Deep 6 Row, Filteration 10 Micron outgoing factory fabricated Double Skin Chilled Water Air- handling unit horizontal type fabricated out of extruded aluminium section consisting with 0.63 mm pre-plasticized/pre-coated Galvanized steel sheet outside and 0.63 mm plain Aluminium sheet inside . with blower, blower section and Blower shall be DIDW forward / Backward Curved blade from and blower motor TEFC type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, Multi Row deep cooling coil made of Aluminium finned Copper tube with coil section, pre - filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90% , stainless steel drain pan made out of 18 G sheet duly insulated complete with motor and belt drive package etc. The AHU panels shall be insulated with 48±2 mm thick and 38 Kg/m³ density PU foam. The motor and blower assembly shall be mounted on Aluminium extruded section. The complete AHU shall conform to standard specification and with 3 way modulating valve, thermostat/sensor etc. complete in all respect: Make : Zeco / Edgetech / Citizen.
1
-
-
Supply, installation, testing and commissioning of End Suction Back pull out, flexible coupling with coupling guard centrifugal type Condenser Water pumping set with BZ/CF-8 ASTM #A351 Impeller , Casing/Volute - Cast Iron ASTM #159, Shaft – SS 416 complete with IE3 motor, base frame. Pumps efficiency should be more then 80%. The pump motor shall be suitable for 4 pole, 415 Volts ± 10%, 50 cycles, 3 phase power supply. Apart from this Pumps should be mandatory along with wireless optimyze monitoring device mounted over Pump set which is suitable to measure changes on vibration in three axis and temperature in pumps set. operating parameters: Pumping set with bronze impeller (1 Working plus 1 std by) , Cap 800 USGPM , HEAD 32 meter, complete in all respect upto entire satisfaction of Engineer in charge of work. Make :- Xylem/Grundfoss/Armstrong/CRI/Kirloskar/Lubi
2
-
-
Supply, installation, testing and commissioning of End Suction Back pull out, flexible coupling with coupling guard centrifugal type Chilled Water pumping set with BZ/CF-8 ASTM #A351 Impeller , Casing/Volute - Cast Iron ASTM #159, Shaft – SS 416 complete with IE3 motor, base frame. Pumps efficiency should be more then 80%. The pump motor shall be suitable for 4 pole, 415 Volts ± 10%, 50 cycles, 3 phase power supply. Apart from this Pumps should be mandatory along with wireless optimyze monitoring device mounted over Pump set which is suitable to measure changes on vibration in three axis and temperature in pumps set. operating parameters: Pumping set with bronze impeller (1 Working plus 1 std by), Cap 500 USGPM, HEAD 28 meter, complete in all respect upto entire satisfaction of Engineer in Charge of work: Make :- Xylem/Grundfoss/Armstrong/CRI/Kirloskar/Lubi.
2
-
-
Supply, installation, testing and commissioning of induced draft cooling towers of cap 300 TR. Each tower shall be complete with distribution system, fillings, louvers, Hot dipped galvanized ladder, axial flow fan and motor. Motor (IP:55) shall be suitable for 415 ± 10% volts, 50 cycles, 3 phase power supply. The Cooling Tower shall be complete in all respect capacity of each Cooling tower shall be as follows: (1 Working and 1 standby), Capacity: To Cool 800 USGPM of water at Cooling Tower In/Out 36.4/32,2 DegC, complete in all respect upto entire satisfaction of engineer in charge of work: Make :- Advance / Delta / Mihir/Bell.
2
-
-
SITC of main panel boards made of 1.6/2.0 mm thick steel sheet duly powder coated complete with voltmeter, ammeter, indicating lights, selector switch, incoming/ outgoing isolators, current operated single phase preventor, CTS contactors, A/M Switch for remote controls operation complete as per specifications and drawings and as required.`Main A.C. Panel-P1, Incomer: 1 No. 620 Amps ACB 4 Pole incoming (MDO) 65 KA, 1 No. 1000 Amps aluminium conductor bus bar duly sleeved, 1 No. electronic energy meter with CTs, 1 No. Ammeter with ASS and CTs., 1 No. voltmeter with VSS., 3 Nos. phase indicating lamps, Outgoing: 2 No. 400-500 Amps TP plus NL MCCB MDO 50 KA outgoing for 350 TR chillers, 1 Nos. 630A ACB TP plus NL MDO 50 KA outgoing for 300 KW Hot water generator, 2 Nos. 63-100 Amps 25 KA MCCB TP plus NL outgoing for condenser water pumps with 15HP motor (Chiller Condenser Water Pump), 2 No. 63 Amps MCCB 25 KA outgoing for Cooling Tower with 7.5kw x 2 nos motor, 2 Nos. 63-100 Amps TP MCCB 25 KA outgoing for chilled water pumps with 15 HP motor, 1 Nos. 100 Amps MCCB TP plus NL outgoing for spare, 2 Nos. automatic type star delta starter for water pumps (15HP), 2 No. Automatic Type DOL Starter for Cooling Tower (7.5 HPx 2Nos ), 2 No. Automatic Type Star Delta Starter for Condenser Water Pump (15HP), All starters shall have following accessories :1 No. overload relay, 1 No. Ammeter with ASS and CTs., `1 No. single phase preventer, 2 Nos. ON/OFF indicating lights, 2 Nos. ON/OFF push buttons, Powder Coated Enclosure made out of TATA/SAIL/ESSAAR make CRCA sheet having 2 mm for load bearing surfaces and 1.6 mm for non load bearing surfaces ,duly processed powder coated having Siemens grey colour, Hardware (PVC Channels/MCB Channels/FibreGlass/Gaskits/ Sleeves/nuts/Bolts/washers/cooling fans/etc),Complete Wiring inclusive of thimbles,etc, Note:ACB incomer to be 4 pole with O/L,EF,SC, in the main panel with display (V/A), ACB makes Schnieder model MVS /LandT make ACB U-Power /Siemens, MCCB Make LandT / Schnieder (CVS) / Siemens, MCCB upto 100 Amps to be 25 KA with ICU=ICS=100%, MCCB above 100 Amps to be 35/36 KA with ICU=ICS=100% , Contactors make LandT (MNX)/Siemens (3TS) /Schnieder (TVS/TeSys), SPP make Minilec/LandT/Procom complete in all respect upto entire satisfaction of Engineer in charge of wokr. Make, Meters Schnieder/LandT/HPL/Procom/ Nippen/ Elmeasure, Selector switches LandT/HPL/Eaton/Kaycee, Make :- Varindavan / SPC / Tricolite/Dhillon Fabrication.
1
-
-
SITC of 7.5 TR 25mm PIBCV/High-Rangeability Control Valves/Delta-T Valves - for AHU Control valves for FCU/CSU/AHU of sizes upto 32mm dia shall be 2way high rangeability/PIBCV type of Brass construction of PN25 rating with screwed connections. The valve shall be rotary/ball type with rangeability of more than 300, Control valves for air handling units of sizes above 32 mm dia shall be 2way high rangeability/PIBCV type of Cast Iron construction of PN16 rating with flanged connections. The valve shall have linear stroke of minimum 15mm and rangeability of more than 300, The actuator shall be electronic motorised modulating type operating on 24VAC and 0-10Vdc or 4-20 mA control signal. The actuator shall have provision for 0-10Vdc position feedback signal and manual operation. It shall be possible to operate the valve manually and the actuator shall switch back to auto mode when power supply is restored. The valve actuator housing shall have IP54 protection, The actuator should be suitable for a valve close-up pressure of 1.5 times the pump head or a minimum of 4 bars, Flow Rate/size, complete in all respect upto entire satisfaction of Engineer in Charge of work: Make - ANERGY/Belimo/Siemens.
2
-
-
SITC of 8.75 TR, 25mm PIBCV/High-Rangeability Control Valves/Delta-T Valves - for AHU Control valves for FCU/CSU/AHU of sizes upto 32mm dia shall be 2way high rangeability/PIBCV type of Brass construction of PN25 rating with screwed connections. The valve shall be rotary/ball type with rangeability of more than 300, Control valves for air handling units of sizes above 32 mm dia shall be 2way high rangeability/PIBCV type of Cast Iron construction of PN16 rating with flanged connections. The valve shall have linear stroke of minimum 15mm and rangeability of more than 300, The actuator shall be electronic motorised modulating type operating on 24VAC and 0-10Vdc or 4-20 mA control signal. The actuator shall have provision for 0-10Vdc position feedback signal and manual operation. It shall be possible to operate the valve manually and the actuator shall switch back to auto mode when power supply is restored. The valve actuator housing shall have IP54 protection, The actuator should be suitable for a valve close-up pressure of 1.5 times the pump head or a minimum of 4 bars, Flow Rate/size, complete in all respect upto entire satisfaction of Engineer in Charge of work: Make - ANERGY/Belimo/Siemens.
3
-
-
SITC of 12.5 TR, 40mm PIBCV/High-Rangeability Control Valves/Delta-T Valves - for AHU Control valves for FCU/CSU/AHU of sizes upto 32mm dia shall be 2way high rangeability/PIBCV type of Brass construction of PN25 rating with screwed connections. The valve shall be rotary/ball type with rangeability of more than 300, Control valves for air handling units of sizes above 32 mm dia shall be 2way high rangeability/PIBCV type of Cast Iron construction of PN16 rating with flanged connections. The valve shall have linear stroke of minimum 15mm and rangeability of more than 300, The actuator shall be electronic motorised modulating type operating on 24VAC and 0-10Vdc or 4-20 mA control signal. The actuator shall have provision for 0-10Vdc position feedback signal and manual operation. It shall be possible to operate the valve manually and the actuator shall switch back to auto mode when power supply is restored. The valve actuator housing shall have IP54 protection, The actuator should be suitable for a valve close-up pressure of 1.5 times the pump head or a minimum of 4 bars, Flow Rate/size, complete in all respect upto entire satisfaction of Engineer in Charge of work: Make - ANERGY/Belimo/Siemens.
2
-
-
SITC of 15TR, 40mm PIBCV/High-Rangeability Control Valves/Delta-T Valves - for AHU Control valves for FCU/CSU/AHU of sizes upto 32mm dia shall be 2way high rangeability/PIBCV type of Brass construction of PN25 rating with screwed connections. The valve shall be rotary/ball type with rangeability of more than 300, Control valves for air handling units of sizes above 32 mm dia shall be 2way high rangeability/PIBCV type of Cast Iron construction of PN16 rating with flanged connections. The valve shall have linear stroke of minimum 15mm and rangeability of more than 300, The actuator shall be electronic motorised modulating type operating on 24VAC and 0-10Vdc or 4-20 mA control signal. The actuator shall have provision for 0-10Vdc position feedback signal and manual operation. It shall be possible to operate the valve manually and the actuator shall switch back to auto mode when power supply is restored. The valve actuator housing shall have IP54 protection, The actuator should be suitable for a valve close-up pressure of 1.5 times the pump head or a minimum of 4 bars, Flow Rate/size, complete in all respect upto entire satisfaction of Engineer in Charge of work: Make - ANERGY/Belimo/Siemens.
4
-
-
SITC of 20TR, 50mm PIBCV/High-Rangeability Control Valves/Delta-T Valves - for AHU Control valves for FCU/CSU/AHU of sizes upto 32mm dia shall be 2way high rangeability/PIBCV type of Brass construction of PN25 rating with screwed connections. The valve shall be rotary/ball type with rangeability of more than 300, Control valves for air handling units of sizes above 32 mm dia shall be 2way high rangeability/PIBCV type of Cast Iron construction of PN16 rating with flanged connections. The valve shall have linear stroke of minimum 15mm and rangeability of more than 300, The actuator shall be electronic motorised modulating type operating on 24VAC and 0-10Vdc or 4-20 mA control signal. The actuator shall have provision for 0-10Vdc position feedback signal and manual operation. It shall be possible to operate the valve manually and the actuator shall switch back to auto mode when power supply is restored. The valve actuator housing shall have IP54 protection, The actuator should be suitable for a valve close-up pressure of 1.5 times the pump head or a minimum of 4 bars, Flow Rate/size, complete in all respect upto entire satisfaction of Engineer in Charge of work: Make - ANERGY/Belimo/Siemens.
1
-
-
SITC of 25TR, 65mm PIBCV/High-Rangeability Control Valves/Delta-T Valves - for AHU Control valves for FCU/CSU/AHU of sizes upto 32mm dia shall be 2way high rangeability/PIBCV type of Brass construction of PN25 rating with screwed connections. The valve shall be rotary/ball type with rangeability of more than 300, Control valves for air handling units of sizes above 32 mm dia shall be 2way high rangeability/PIBCV type of Cast Iron construction of PN16 rating with flanged connections. The valve shall have linear stroke of minimum 15mm and rangeability of more than 300, The actuator shall be electronic motorised modulating type operating on 24VAC and 0-10Vdc or 4-20 mA control signal. The actuator shall have provision for 0-10Vdc position feedback signal and manual operation. It shall be possible to operate the valve manually and the actuator shall switch back to auto mode when power supply is restored. The valve actuator housing shall have IP54 protection, The actuator should be suitable for a valve close-up pressure of 1.5 times the pump head or a minimum of 4 bars, Flow Rate/size, complete in all respect upto entire satisfaction of Engineer in Charge of work: Make - ANERGY/Belimo/Siemens.
2
-
-
SITC of 30TR, 65mm PIBCV/High-Rangeability Control Valves/Delta-T Valves - for AHU Control valves for FCU/CSU/AHU of sizes upto 32mm dia shall be 2way high rangeability/PIBCV type of Brass construction of PN25 rating with screwed connections. The valve shall be rotary/ball type with rangeability of more than 300, Control valves for air handling units of sizes above 32 mm dia shall be 2way high rangeability/PIBCV type of Cast Iron construction of PN16 rating with flanged connections. The valve shall have linear stroke of minimum 15mm and rangeability of more than 300, The actuator shall be electronic motorised modulating type operating on 24VAC and 0-10Vdc or 4-20 mA control signal. The actuator shall have provision for 0-10Vdc position feedback signal and manual operation. It shall be possible to operate the valve manually and the actuator shall switch back to auto mode when power supply is restored. The valve actuator housing shall have IP54 protection, The actuator should be suitable for a valve close-up pressure of 1.5 times the pump head or a minimum of 4 bars, Flow Rate/size, complete in all respect upto entire satisfaction of Engineer in Charge of work: Make - ANERGY/Belimo/Siemens.
2
-
-
SITC of Temperature Controller The temperature controller shall be electronic microprocessor based with display working on 24 VAC with 0-10Vdc output. It shall be capable of accepting inputs from 3 temperature sensors. One temperature sensor for space temperature measurement and the other two temperature sensors for coil inlet and outlet water temperature measurements. The controller shall be capable of comparing the signals and selecting the lower output to prevent excessive water flow through coil complete in all respect upto entire satisfaction of Engineer in Charge of work: Make - ANERGY/Belimo/Siemens
16
-
-
Supply, installation, testing and commissioning of 4TR 2-way valve for FCU 2-way motorized valve of ``Polymer composite body`` with on/off actuator of PN-25 rating.
2
-
-
Supply, installation, testing and commissioning of 1.5TR 2-way valve for FCU 2-way motorized valve of ``Polymer composite body`` with on/off actuator of PN-25 rating.
4
-
-
Supply, installation, testing and commissioning of 2TR 2-way valve for FCU 2-way motorized valve of ``Polymer composite body`` with on/off actuator of PN-25 rating complete in all respect upto entire satisfaction of Engineer in charge of work.
7
-
-
Supply, installation, testing and commissioning of 1.25 TR 2-way valve for FCU 2-way motorized valve of ``Polymer composite body`` with on/off actuator of PN-25 rating complete in all respect upto entire satisfaction of Engineer in charge of work.
1
-
-
Supply, installation, testing and commissioning of 1TR 2-way valve for FCU 2-way motorized valve of ``Polymer composite body`` with on/off actuator of PN-25 rating complete in all respect upto entire satisfaction of Engineer in charge of work.
3
-
-
Supply, installation, testing and commissioning of 3TR 2-way valve for FCU 2-way motorized valve of ``Polymer composite body`` with on/off actuator of PN-25 rating. complete in all respect upto entire satisfaction of Engineer in charge of work.
7
-
-
Supply, installation, testing and commissioning of 2.5TR 2-way valve for FCU 2-way motorized valve of ``Polymer composite body`` with on/off actuator of PN-25 rating. complete in all respect upto entire satisfaction of Engineer in charge of work.
17
-
-
SITC of Electronic Temperature Controller for FCU`s The thermostat for fan coil unit shall be electronic type with integrated minimum 3inch LCD Display, ON/OFF, 3 FAN SPEED and HEAT/FAN/COOL switches. The thermostat shall operate on 230 V mains voltage and shall be suitable for operating 2 position motorized 3/2 way mixing/diverting valve . The thermostat shall have a precalibrated NTC thermistor and shall be suitable for operation in the range of 15 -35 C with a switching differential of 1 C. All thermostat shall be fitted on standard mounting plate as recommended by the manufacturer. Complete in all respect upto entire satisfaction of Engineer in Charge of work: (Make - ANERGY/ Belimo/Siemens).
41
-
-
Supply, installation, testing and commissioning Closed Expansion Tank 500 Liter, PN 10 (Make - ANERGY/ITT/Spirotech) The closed expansion tank will be of M.S. construction with interchangeable Synthetic rubber membrane. The expansion tank shall be complete with safety relief valve and pressure gauge. The tank will be of pressure rating to suit the system pressure and will be sized to adequately compensate for water expansion due to operating temperature variations. For chilled water application, it will be insulated with 50 mm thick insulation to the specifications and cladded with 26G-aluminum cladding complete in all respect upto entire satisfaction of engineer in charge.
1
-
-
SITC of Pressurisation unit Head 25 meter, Flow 2CMH (Make - ANERGY/ITT/Spirotech) shall be with 2 nos. (1 working plus 1 stand by) horizontal/vertical multi-stage pumps of suitable rating and capacity, as indicated hereunder, factory mounted on a steel frame along with interconnected piping, valves, strainer, pressure gauge, pressure transmitter, flow meter to measure the make-up water quantity, control panel with duty cycling and dry-run protection, electrical relays/contactors and interconnecting wiring:The unit shall be capable of Pressurising the system to the required pressure with suction from a break-tank located at least 1m above pump level complete in all respect upto entire satisfaction of Engineer in Charge of work.
1
-
-
Supply, installation, testing and commissioning of Microbubble Air/Dirt Separator a combined Air and Dirt Separator of M.S construction as per specifications on the return water line located at the pump suction or a suitable location as suggested. The separator should be complete with high capacity air vent, service valve, butterfly valve, water inlet, flanges, drain valve etc. 250mm.. (Make - ANERGY/ITT/Spirotech)
1
-
-
Supply, installation, testing and commissioning Hot Water Generator arranged in steps of capacity 250 KW (1Working plus 0 Std By) complete in all respect upto entire satisfaction of Engineer in Charge of work. Make :- Rapid Cool / KEPL/Emrald.
1
-
-
Supply, installation, testing and commissioning of water cooled Screw type chilling unit of nominal capacity 215 TR /200 TR actual capacity with company fitted VFD at the parameters indicated below complete with Semi-hermetic / hermetic Helical Rotary twin Screw compressor with Single / twin compressor, TERC motor, factory insulated cooler, water cooled condenser, vibration isolators, integral refrigerant piping and wiring, flow switches at chiller and condenser outlets, first charge of refrigerant and lubricant, microprocessor based control panel, accessories as required. Motor shall be suitable for 415 ± 10% V, 50Hz, 3ph AC supply as per specifications (1 nos Working plus 1 Std by) including factory witness testing AHRI Certified, Cooler, Chilled water in : 54 DegF, Chilled water out : 44 DegF , Chilled water flow rate: 500 USGPM, Fouling Factor :- 0.0005 FPS, Pressure drop across chiller shall not exceed 14 Feet H2O, Condenser, Condenser water in :- 90 DegF, Condenser water out : 97.5 Deg F, Condenser water flow rate: 800 USGPM, Fouling Factor :- 0.001 FPS, Pressure drop across condenser shall not exceed 18 Feet H2O, COP at AHRI Conditions shall be 5.90 minimum, IKW/TR at designed conditions should be less than 0.67 IKW/TR @ 100% Load, Minimum IPLV : 0.35, Minimum NPLV :0.37, Make :- Voltas /Blue Star/ Carrier/ Climaveneta/ Daikin/ Dunhambush/Trane / Mitsubishi, complete in all respect upto entire satisfaction of Engineer in Charge of work
2
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements