Military Engineer Services Tender

... More
The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Ca No Ce Chz Chm T 18 2026 27 Provn Of Klp Accommodation For Ad Regt Self Propelled Including Affiliated Wksp Ph I Of Two Phase At Chandimandir in Panchkula, Haryana, with an estimated contract value of Rs. 27,11,00,000. The bid opening date for this tender is 25-09-2026 and the last date for bid submission is 28-11-2026. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.

Military Engineer Services - MES Tender - Haryana Tender

Opening Date25 Sep 2026
Closing Date28 Nov 2026
Tender Amount₹ 27,11,00,000 
Notes
Download

Costs

Description

Ca No Ce Chz Chm T 18 2026 27 Provn Of Klp Accommodation For Ad Regt Self Propelled Including Affiliated Wksp Ph I Of Two Phase At Chandimandir

Contact

Unlock the Tender details

GEM & Bid Advisory Services

Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

Unlock the Tender details
... More
Total amount of Sch 'A' Sec-IV (INTERNAL WATER SUPPLY WORKS) Lump sum price worked out by the contractor for " INTERNAL WATER SUPPLY WORKS" as listed in schedule 'A' Part-IV

1

1169800

-

... More
Total amount of Sch 'A' Sec-V (INTERNAL ELECTRIFICATION WORKS) Lump sum price worked out by the contractor for "INTERNAL ELECTRIFICATION WORKS" as listed in schedule 'A' Part-V

1

1264113

-

... More
Total amount of Sch 'A' Sec-VI (HOT WATER WORKS) Lump sum price worked out by the contractor for "HOT WATER WORKS" as listed in schedule 'A' Part-VI

1

24004

-

... More
Total amount of Sch 'A' Sec-VII (ROAD, PATH, CULVERTS AND HARD STANDING WORKS ) Lump sum price worked out by the contractor for "ROAD, PATH, CULVERTS AND HARD STANDING WORKS " as listed in schedule 'A' Part-VII

1

2204898

-

... More
Total amount of Sch 'A' Sec-VIII (EXTERNAL WATER SUPPLY WORKS) Lump sum price worked out by the contractor for "EXTERNAL WATER SUPPLY WORKS " as listed in schedule 'A' Part-IX

1

482019

-

... More
Total amount of Sch 'A' Sec-IX (EXTERNAL ELECTRIC SUPPLY WORKS ) Lump sum price worked out by the contractor for " EXTERNAL ELECTRIC SUPPLY WORKS " as listed in schedule 'A' Part-IX

1

508182

-

... More
Total amount of Sch 'A' Sec-X (SEWAGE DISPOSAL WORKS ) Lump sum price worked out by the contractor for "SEWAGE DISPOSAL WORKS " as listed in schedule 'A' Part-X

1

744915

-

... More
Total amount of Sch 'A' Sec-XI (AREA DRAINAGE WORKS ) Lump sum price worked out by the contractor for "AREA DRAINAGE WORKS " as listed in schedule 'A' Part-XI

1

1924993

-

... More
Total amount of Sch 'A' Sec-XII (CHAIN LINK FENCING WITH BARBED WIRE WORKS ) Lump sum price worked out by the contractor for "CHAIN LINK FENCING WITH BARBED WIRE WORKS " as listed in schedule 'A' Part-XII

1

118729

-

... More
Total amount of Sch 'A' Sec-XIII (ARBORICULTURE WORKS ) Lump sum price worked out by the contractor for "ARBORICULTURE WORKS " as listed in schedule 'A' Part-XIII

1

342961

-

... More
Schedule 'A'Section-XIV (Misc Items of Works) Note : This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col. 5 siginifies this fact only.

-

-

-

... More
ARBORICULTURE WORKS Supply and fixing 50 mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS-14930 Part-II with anti rodent and non flame propogating properties of approved colour with fittings for cable protection complete all as specified and as directed by Engineer-in-Charge.

270

-

-

... More
Supply installation, testing and commissioning factory made feeder pillar made out of 3.15mm thick incorporated with 3 phase 4 wire system aluminium busbar 50 amp, insulator with two nos of incoming 32 amp SPN, 220 volt fixed on angle iron frame grouted in the PCC 1:2:4 upto 30 cm duly painted with powder coated paint and angle iron frame with two coat of synthetic enamel paint over a coat of red oxide primer paint complete all as specified and directed. Note : Drawing for LT panel shall be approved by GE before placement of order. (For Arboriculture Lighting.)

1

-

-

... More
Supply and fixing of bollard light upto 24 watt capacity complete all as specified and directed.

4

-

-

... More
SUMMER APPLIANCES Supply, installation and testing of refrigerator of Capacity 165 Litres, Single Door, electric driven, single phase, 230 Volts, BEE 5 star rated having features such as smart inverter compressor with minimum 10 years of warranty, inbuilt stablizer, frost free etc. working on R-134 or superior environment friendly refrigerant gas equipped with accessories such as ice tray, egg tray, interior lamp, toughened glass partition (shelves) complete all as specified and as directed by Engineer-in-Charge.

275

-

-

... More
Supply and fixing Voltage stabilizer automatic operation, single phase naturally air cooled indoor type & designed with copper winding of suitable gauge for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of (+-) 25% and capacity 5 KVA.

279

-

-

... More
Supply, installation, testing and commissioning of water cooler of capacity 80 Litres and with minimum cooling capacity of 40 Litres per Hour(LPH) BEE 5 Star rated, having anti corrosive stainless steel body and tank, electric driven, single phase, 230 Volts complete with all connected fittings as per manufacturer's recommendations complete all as specified and as directed by Engineer-in-Charge.

6

-

-

... More
Supply, installation, testing and commissioning of Deep freezer with glass door opening, double door of capacity 100 Litres, BEE 5 star rated, Electric driven, single phase, 230 Volts with required fittings and fixtures for preserving all types of food in hygine condition, relaiable and robust design, special brakets, rugged and heavy duty shelves, 4 heavy duty caster wheels at the bottom of the freezer for easy movability, low emissivity glass for better visibility and insulation, UV grade plastic for long lasting appearence, anti corrosive, pre-coated body, aluminium inner lining with high density PUF insulation for better holding time, door lock feature for restricted accessibility, compressor having minimum 5 years of warranty complete all as specified and as directed by Engineer-in-Charge.

4

-

-

... More
Supply, installation, testing and commissioning of air cooled air conditioner with split type indoor and outdoor unit, of cooling capacity of 4500 K cal per hrs (2 Ton), electric driven, 230 Volts, single phase, 50Hz supply, all weather cold type, BEE 5 star rated, working on R-134 or superior environment friendly refrigerant gas including copper tubing and Electrical connection between indoor and outdoor unit located upto a maximum 10 meter distance complete including condensate water drainage pipe of maximum 3 meter long complete all as specified and as directed by Engineer-in-Charge.

26

-

-

... More
Supply, installation, testing and commissioning of air cooled air conditioner with split type indoor and outdoor unit, of cooling capacity of 4500 K cal per hrs (1.5 Ton), electric driven, 230 Volts, single phase, 50Hz supply, all weather type cold type, BEE 5 star rated, working on R-134 or superior environment friendly refrigerant gas including copper tubing and Electrical connection between indoor and outdoor unit located upto a maximum 10 meter distance complete including condensate water drainage pipe of maximum 3 meter long complete all as specified and as directed by Engineer-in-Charge.

2

-

-

... More
HOT WATER WORKS Supply, installation, testing and commissioning of solar water heater with heat exchanger type, conforming to IS 12933 & 13129 for cold region, 500 litre/ day capacity with electric heating backup of 2 KW and rotational moulded polyethylene water storage tank (cylindrical vertical tank with close top) of 500 Ltr capacity, tripple layer, as make up water tank. hoisted and fixed in position on suitable steel staging as directed by GE. complete all as specified and directed. Notes: (i) The system shall be tested on completion to ensure that 500 litres of water at 60 Degree centigrade is available in hot water tank on normal day in cold season. (ii) All other pipe/civil work, electrical work, providing electric connection with wire, MCB, conduit etc as per manufacturer's instruction all as required shall deemed to be included in unit rate quoted). (iii) Normal water pipes and accessories for normal water over head tank to inlet of plate collector shall be measured and paid for separtely.

12

-

-

... More
Supply, installation, testing and commissioning of solar water heater with heat exchanger type, conforming to IS 12933 & 13129 for cold region, 500 litre/ day capacity with electric heating backup of 2 KW and rotational moulded polyethylene water storage tank (cylindrical vertical tank with close top) of 200 Ltr capacity, tripple layer, as make up water tank. hoisted and fixed in position on suitable steel staging as directed by GE. complete all as specified and directed. Notes: (i) The system shall be tested on completion to ensure that 200 litres of water at 60 Degree centigrade is available in hot water tank on normal day in cold season. (ii) All other pipe/civil work, electrical work, providing electric connection with wire, MCB, conduit etc as per manufacturer's instruction all as required shall deemed to be included in unit rate quoted). (iii) Normal water pipes and accessories for normal water over head tank to inlet of plate collector shall be measured and paid for separtely.

4

-

-

... More
Supply and laying of Hot water pipe duly insulated with19 mm nitrile insulation and 26 gauge aluminium cladding suitable for 20 mm bore pipe medium grade laid in trenches/wall/floor and joined including necessary fittings such as bends, elbow, tees sockets etc including necessary saddles and clamps complete all as specified and directed

860

-

-

... More
Supply and laying of Hot water pipe duly insulated with19 mm nitrile insulation and 26 gauge aluminium cladding suitable for 25 mm bore pipe medium grade laid in trenches/wall/floor and joined including necessary fittings such as bends, elbow, tees sockets etc including necessary saddles and clamps complete all as specified and directed

973

-

-

... More
Supply and fix electric water heater (Geyser) storage type,steel body with copper inner tank and heating elements upto 2 kw electric,capacity 25 liters, BEE 5 star rated complete with all accessories such as safety valve,thermostat, NRV, connection piece and hot and cold connection fittings complete all as specified and as directed. Note - Water supply pipe line upto inlet of Geyser shall be part of internal water supply schedule. Note:- (i) Water supply pipe line upto inlet of Geyser shall be part of internal water supply schedule. (ii) Water supply pipe line from outlet of Geyser shall be part of internal water supply schedule.

4

-

-

... More
ROAD, PATH, CULVERTS AND HARDSTANDING WORKS Providing, Laying, compaction of granular sub-base of 150 mm thick compacted thickness by providing close graded material conforming to specifications i.e Grading II, conforming to Clause 401 of MORT&H Specifications for Road and Bridge Works (Fifth Revision), mixing in a mechanical mix plant at OMC, carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller of capacity 8 to 12 tonne to achieve compaction density of atleast 98% of maximum dry density and consolidating to required gradient and camber, complete all as specified and directed.

295

-

-

... More
Providing, Laying, compaction of Wet Mix Macadam conforming to Clause 406 of MORT&H Specifications for Road and Bridge Works (Fifth Revision) , 250 mm thick (compacted thickness,125 mm thick in two separate layers) with mechanically crushed graded stone aggregates and granular material (size range 53 mm to 0.075 mm ), grading of aggregates as per Table 400-13 of MORT&H Specifications for Road and Bridge Works (Fifth Revision) ,including premixing the material with water at OMC in for all leads & lifts, laying in uniform layers with mechanical paverfinisher in sub- base / base course on well prepared surface and compacting with vibratory roller of 8 to 12 tonne capacity to achieve the desired density , required gradient and camber etc., complete all as specified and directed. NOTES: 1. The WMM shall be laid in two layers i.e each layer of 125 mm thick (compacted thickness). 2. For payment purpose,both layers shall be considered as one unit.

485

-

-

... More
Preparation of un-surfaced Wet Mix macadam (WMM) surfaces by brushing with wire brushes for re-moving caked mud ,dust, loose material, foreign material etc., sweeping with power brooms and finally fanning the cleaned surface with air compressors to remove all loose dirt etc. and applying evenly a priming coat on un-surfaced wet mix macadam surfaces conforming to Clause 502 of MORT&H Specifications for Road and Bridge Works (Fifth Revision), with cationic bituminous emulsion SS1 grade,confirming to IS 8887(latest edition) @ 7.5 kg per 10 sq metres using primer distributor which shall be self-propelled or towed bitumen pressure sprayer complete all as specified and directed.

194

-

-

... More
Providing, laying & compaction of Bituminous Macadam (BM) 50 mm Compacted thickness conforming to Clause 504 of MORT&H Specifications for Road and Bridge Works (Fifth Revision), using mechanically crushed stone aggregates and granual material etc. of grading II as per Table 500-7 of MORT&H Specifications for Road and Bridge Works (Fifth Revision), premixed with bituminous binder, Bitumen grade VG-30 @ 3.50% (percentage by weight of total mix) prepared in Batch Type Hot Mix Plant of 100-120 TPH capacity transported to site by tippers, laid over a previously prepared surface with paver finisher equiped with electronic sensor to the required grade, level and alignment and rolling with smooth wheeled, vibratory and tandem rollers as per specifications to achieve the desired compaction and density complete all as specified and directed by Engineer-in-Charge. Notes : (i) The contractor shall quote the rate against Item considering 3.5% VG-30 bitumen content. Job mix formula as per MoRT&H specifications for road and bridge work (Fifth Revision) for bituminous concrete shall be got designed from NIT/ CTL/ Govt Engg College and shall be got approved from GE in writing well before commencement of work without any financial effect to the department. Also the bitumen content shall not be less 3.4% by weight of total mix as per clause 504.2.4 of MoRT&H specifications (Fifth Revision). (ii) If qty of binder contents is less than the qty as specified in respective items of BOQ, it shall be adjusted at supply only rates of paving bitumen @ Rs 45.00 Per Kg and if qty of binder contents is more than the qty as specified in respective items of BOQ no adjustment shall be made.

97

-

-

... More
Preparation of surfaces and applying evenly a Tack coat conforming to Clause 503 of MORT&H Specifications for Road and Bridge Works (Fifth Revision), with cationic bituminous emulsion RS1 grade,confirming to IS 8887(latest edition) @ 2.5 kg per 10 sq metres using using primer distributor which shall be self-propelled or towed bitumen pressure sprayer complete all as specified and directed.

194

-

-

... More
Providing and laying 30 mm thick (consolidated thickness) Bituminous premix asphaltic dense concrete conforming to Clause 507 of MoRTH Specification for Road and Bridge Works (Fifth Revision) premixed with bituminous binder using Bitumen grade VG-30@ 5.50 % by weight of total mix , laid /rolled and compacted to required gradient and camber level and alignment and rolling with smooth wheeled , vibratory and tandom rollers as per specifications to achieve the desired density complete all as specified.

194

-

-

... More
M & L Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5 mm), including making drainage opening wherever required complete all as specified and as directed.

770

-

-

... More
EXTERNAL WATER SUPPLY WORKS M& L for DI/GI pipe fittings for spigot and socketed/ flanged joint suitable upto 150/100 mm bore such as bends(any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc),Tee pieces single branch. Y junction, double branch, cross (all sockets and spigot ) collars, caps and plugs,tail pieces with one end flange(integrally cast) and one end socket, complete suitable for any size of pipe and push on flexible rubber tyton joints/ flange joints complete all as specified and directed

200

-

-

... More
Supply & Fix Centrifugally cast (spun) ductile iron pressure pipes with socket& spigot ends having ISI stamping marking with IS 8329/2000 classification K7, In standard length of 5.5 - 6 mtr suitable for and including push on tyton joint and gasket with cement mortar lining inside the pipes of 150 mm bore, cost of rubber joint shall be included in the overall cost quoted for jointing of pipe complete all as specified and directed.

940

-

-

... More
Supply & Fix Centrifugally cast (spun) ductile iron pressure pipes with socket& spigot ends having ISI stamping marking with IS 8329/2000 classification K7, In standard length of 5.5 - 6 mtr suitable for and including push on tyton joint and gasket with cement mortar lining inside the pipes of 100 mm bore, cost of rubber joint shall be included in the overall cost quoted for jointing of pipe complete all as specified and directed. NOTE:- For Sr No- 2 & 3 (I) Ductile iron fittings will be measured and paid separately. (II) Make of fittings same as that of pipe or as recommended by original pipe manufacturers.

290

-

-

... More
Supply & Fix Cast iron air release valves with two air outlets, 50 mm dia bore and fixing up in cast iron water supply mains of 150mm dia pipe complete all as specified and directed.

1

-

-

... More
Sluice valve of 150 mm dia bore, cast iron body, having brass spindle with iron wheel at top, class PN 1.6, with flanged ends, drilled suitably, complete with joints and including necessary joints by means of bolts, nuts washers and rubber gaskets, conformig to IS - 14846 complete all as specified and as directed.

2

-

-

... More
Sluice valve of 100 mm dia bore, cast iron body, having brass spindle with iron wheel at top, class PN 1.6, with flanged ends, drilled suitably, complete with joints and including necessary joints by means of bolts, nuts washers and rubber gaskets, conformig to IS - 14846 complete all as specified and as directed.

1

-

-

... More
Sluice valve of 80 mm dia bore, cast iron body, having brass spindle with iron wheel at top, class PN 1.6, with flanged ends, drilled suitably, complete with joints and including necessary joints by means of bolts, nuts washers and rubber gaskets, conformig to IS - 14846 complete all as specified and as directed.

3

-

-

... More
M&L for cutting existing hard standing/ road upto 45 cm depth for laying pipelines and making good the disturbed surface by providing M15 concrete after laying pipe lines and returning filling of soil complete all as specified and as directed.

2800

-

-

... More
Material & Labour for cutting of existing hard standing/road up to 45 cm depth for laying of pipe lines and making good the disturbed surfaces by providing PCC 1:2:4 type B-1 (using 20mm graded aggregate) after laying of pipes lines and returning filling of soil, complete all as specified and directed.

3

-

-

... More
Boring of hole under roads, hard stranding, pavements by trenchless technology using ultra sounding technique and necessary machine including 150 mm dia HDPE Pipe suitable for 0.4 Mpa pressure complete all as specified and directed.

30

-

-

... More
Construction of valve pit of size 1.2m x 1.2m x 1.0 m with concrete block construction with wall thickness not less than 200 mm including all necessary excavation and earth work in hard dense soil returning filling in disposal of surplus soil to a distance not exceeding 50 metre and depositing where as directe including PCC in foundation (1:3:6) type C2 using 40mm graded stone aggregate 150 mm thick, PCC in coping on top 1:2:4, type B1 using 20 mm graded stone aggregate 50 mm thick including rendering 15 mm thick on exposed surface and two coat of white wash on exposed surface on external wall above ground level and angle iron frame 50x50x6 mm MS sheet cover 3.15 mm thick with hinges, handle and locking arrangement. Painting all MS work with two coat of red oxide primer and painting all the MS surface embeded in PC with two coat of black bitumen paint, complete all as specified and directed.

5

-

-

... More
Construction of valve pit of size 0.9m x 0.9m x 0.9m with concrete block construction with wall thickness not less than 200 mm including all necessary excavation and earth work in hard dense soil returning filling in disposal of surplus soil to a distance not exceeding 50 metres and depositing where as directed. PCC in foundation (1:3:6) type C2 using 40mm graded stone aggregate 150 mm thick, PCC in coping on top 1:2:4, type 81 using20 mm graded stone aggregate50 mm thick including rendering 15 mm thick on exposed surface and two coat of white wash on exposed surface on external wall above ground level and angle iron frame 50x50x6 mm MS sheet cover 3.15 mm thick with hinges, handle and locking arrangement. Painting all MS work with two coat of red oxide primer and painting all the MS surface embeded in PC with two coat of black bitumen paint all as specified and directed.

2

-

-

... More
EXTERNAL ELECTRIC WORKS MS Box of size 300x200x150mm, made out of 1.6mm thick MS Sheet, with insulated aluminium bus bar 02 Nos two phase 240 Volts of rating 200 amps mounted on insulators, fixed with pole for street light with MCB SP B series 6 Amp, 240 Volts, 10 KA mounted on Din rail, thimbles Complete all as specified and directed by engr-in-charge.

12

-

-

... More
Supply and fixing of GI steel tubing light grade 40 MM dia bent to shape of offset angle upto 45 degree bracket mounting clamp , bolts and nuts for fixing of security light fitting Complete all as specified and directed by engr-in-charge.

12

-

-

... More
Supply and fixing of 1.5 Sqmm 2 core copper conductor overall pvc sheathed for submain wiring including PVC Conduit 20 mm dia medium grade along with fixing clamp etc complete all as specified and directed.

150

-

-

... More
Supply installation, testing and commissioning factory made ,outdoor type, floor mounted, main LT panel board, cubical type totally enclosed outer edge made out of 3.15 mm thick CRCA sheet and inner compartments of 2 mm thick sheet metel enclosed with angle iron frame of MS angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50HZ system , with hinged pannel door (covers) on two sides with handle, bottom cable gland with plate and locking arrangement consisting of sufficient nos of circuit cable entry holes at bottom only with suitable PVC/rubber/wooden brushes to prevant ingress of water/vermin etc,inside the enclouser,required nos of holes to be fixed with chromium plate brass cable glands for cable entry and exit complete with neccesary internal wiring with stranded copper conductor FRLSH wire of adequate size,duly powder coated internally and externally of approved colour with pcc foundation (1:2:4) and fixed with legs below ground 30 cm and above ground 60 cm with aluminium busbar 3000 amp ( 01 set comprising 4 nos strip) for 3 phase and neutral mounted on epoxy insulator,CTs, Ammeter, votmeter,indicator lamp including following accesories. MAIN LT PANEL INCOMING:- (i) ACB 415 Volts, 2000 amp, rating 4 pole 50 KA rupturing capacity, microprocessor release , manual draw out type including with overload, short circuit and earth fault protection-01 No. OUTGOING:- (i)MCCB 500 Amps, 4 pole, 36 KA ,Thermal adustable and fixed magnetic type= 1 No (To LT Panel-I Adm Bldg) (ii)MCCB 500 Amps, 4 pole, 36 KA ,Thermal adustable and fixed magnetic type= 1 No (To LT Panel-II SM Barrack) (iii)MCCB 250 Amps, 4 pole, 36 KA ,Thermal adustable and fixed magnetic type= 1 No (To LT Panel-III SM Barrack Air Cooling) (iv)MCCB 350 Amps, 4 pole, 36 KA ,Thermal adustable and fixed magnetic type= 1 No (To LT Panel-IV Cook house&Dining) (v)MCCB 200 Amps, 4 pole, 36 KA ,Thermal adustable and fixed magnetic type= 1 No (To Fire Panel in Pump room) All MCCB should be Microprocessor based. Note:- Drawing for LT Panel shall be approved by GE before placement of order by contactor.

1

-

-

... More
Supply installation, testing and commissioning factory made ,outdoor type, floor mounted, main LT panel board, cubical type totally enclosed outer edge made out of 3.15 mm thick CRCA sheet and inner compartments of 2 mm thick sheet metel enclosed with angle iron frame of MS angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50HZ system , with hinged pannel door (covers) on two sides with handle, bottom cable gland with plate and locking arrangement consisting of sufficient nos of circuit cable entry holes at bottom only with suitable PVC/rubber/wooden brushes to prevant ingress of water/vermin etc,inside the enclouser,required nos of holes to be fixed with chromium plate brass cable glands for cable entry and exit complete with neccesary internal wiring with stranded copper conductor FRLSH wire of adequate size,duly powder coated internally and externally of approved colour with pcc foundation (1:2:4) and fixed with legs below ground 30 cm and above ground 60 cm with aluminium busbar 750 amp ( 01 set comprising 4 nos strip) for 3 phase and neutral mounted on epoxy insulator,CTs, Ammeter, votmeter,indicator lamp including following accesories. LT PANEL-I Incomming (i) MCCB 500 Amps, 36 KA, 4 pole ,Thermal adustable and fixed magnetic type =1 No. Outgoing (i)MCCB 350 Amps, 36 KA, 4 pole ,Thermal adustable and fixed magnetic type = 1 Nos - For Adm Bldg Load (ii)MCCB 80 Amps, 25 KA, 4 pole ,Thermal adustable and fixed magnetic type = 1 Nos- For Air Cooling Load (iii)MCB 20 A DP - 2 Nos - For Car Parking & Security Light Note- All MCCB should be microprocessor Based (Location- Adm Bldg) Note:- Drawing for LT Panel shall be approved by GE before placement of order by contactor.

1

-

-

... More
Supply installation, testing and commissioning factory made ,outdoor type, floor mounted, main LT panel board, cubical type totally enclosed outer edge made out of 3.15 mm thick CRCA sheet and inner compartments of 2 mm thick sheet metel enclosed with angle iron frame of MS angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50HZ system , with hinged pannel door (covers) on two sides with handle, bottom cable gland with plate and locking arrangement consisting of sufficient nos of circuit cable entry holes at bottom only with suitable PVC/rubber/wooden brushes to prevant ingress of water/vermin etc,inside the enclouser,required nos of holes to be fixed with chromium plate brass cable glands for cable entry and exit complete with neccesary internal wiring with stranded copper conductor FRLSH wire of adequate size,duly powder coated internally and externally of approved colour with pcc foundation (1:2:4) and fixed with legs below ground 30 cm and above ground 60 cm with aluminium busbar 1500 amp ( 01 set comprising 4 nos strip) for 3 phase and neutral mounted on epoxy insulator,CTs, Ammeter, votmeter,indicator lamp including following accesories. LT PANEL-II Incomming (i)MCCB 500 Amps, 36 KA, 4 pole ,Thermal adustable and fixed magnetic type =1 No. Outgoing (i)MCCB 100 Amps, 25 KA, 4 pole ,Thermal adustable and fixed magnetic type = 4 Nos (For SM Barracks- 4 Nos) (ii)MCB DP 40 Amps = 1 No (For Security Light) Note- All MCCB should be microprocessor Based. (Location- SM Living Barracks) Note:- Drawing for LT Panel shall be approved by GE before placement of order by contactor.

1

-

-

... More
Supply installation, testing and commissioning factory made ,outdoor type, floor mounted, main LT panel board, cubical type totally enclosed outer edge made out of 3.15 mm thick CRCA sheet and inner compartments of 2 mm thick sheet metel enclosed with angle iron frame of MS angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50HZ system , with hinged pannel door (covers) on two sides with handle, bottom cable gland with plate and locking arrangement consisting of sufficient nos of circuit cable entry holes at bottom only with suitable PVC/rubber/wooden brushes to prevant ingress of water/vermin etc,inside the enclouser,required nos of holes to be fixed with chromium plate brass cable glands for cable entry and exit complete with neccesary internal wiring with stranded copper conductor FRLSH wire of adequate size,duly powder coated internally and externally of approved colour with pcc foundation (1:2:4) and fixed with legs below ground 30 cm and above ground 60 cm with aluminium busbar 375 amp ( 01 set comprising 4 nos strip) for 3 phase and neutral mounted on epoxy insulator,CTs, Ammeter, votmeter,indicator lamp including following accesories. LT PANEL-III Incomming (i)MCCB 250 Amps, 36 KA, 4 pole ,Thermal adustable and fixed magnetic type =1 No. Outgoing (i)MCCB 80 Amps, 25 KA, 4 pole ,Thermal adustable and fixed magnetic type = 4 Nos (For Air Washer-4 Nos) Note- All MCCB should be microprocessor Based. Location- SM Living(Air Cooling System) Note:- Drawing for LT Panel shall be approved by GE before placement of order by contactor.

1

-

-

... More
Supply installiation, testing and commissioning factory made ,outdoor type, floor mounted, main LT panel board, cubical type totally enclosed outer edge made out of 3.15 mm thick CRCA sheet and inner compartments of 2 mm thick sheet metel enclosed with angle iron frame of MS angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50HZ system , with hinged pannel door (covers) on two sides with handle, bottom cable gland with plate and locking arrangement consisting of sufficient nos of circuit cable entry holes at bottom only with suitable PVC/rubber/wooden brushes to prevant ingress of water/vermin etc,inside the enclouser,required nos of holes to be fixed with chromium plate brass cable glands for cable entry and exit complete with neccesary internal wiring with stranded copper conductor FRLSH wire of adequate size,duly powder coated internally and externally of approved colour with pcc foundation (1:2:4) and fixed with legs below ground 30 cm and above ground 60 cm with aluminium busbar 525 amp ( 01 set comprising 4 nos strip) for 3 phase and neutral mounted on epoxy insulator,CTs, Ammeter, votmeter,indicator lamp including following accesories. LT PANEL-IV Incomming (i) MCCB 350 Amps, 36 KA, 4 pole ,Thermal adustable and fixed magnetic type =1 No. Outgoing (i) MCCB 80 Amps, 25 KA, 4 pole ,Thermal adustable and fixed magnetic type = 4 Nos( For Cook House & Dining- 4 Nos) Note- All MCCB should be microprocessor Based. Location-SM Living(4X Cook House&Dining Hall) Note:- 1. Drawing for LT Panel shall be approved by GE before placement of order by contactor.

1

-

-

... More
Supply, install, testing and commissioning 11 KV HT 3 phase 50 Hz totally metal clad horizontally isolated and horizontally draw out type , 630 amps ,having repturing capacity 350 MVA, 18.4 KA for 1 sec outdoor floor mounted type Vacuum circuit breaker for incomer come outgoing conforming to IS : 13943 of latest version comprising of following specification( Near 4 pole structure ): (a) 630 Amps continuous rated electrolytic copper bus bar droppers and bus bar should be insulated with full system voltage sleeves of ruputed (b) Truck/ trolly mounted vacuum circuit breaker should have three nos resin encapsulated vacuum bottles of the same manufacturer as of circuit breaker . (c) Motorized spring charging mechanism with integral spring charging handle or can be supplied loop for manual spring charge . (d) Cast resin copper wound current transformer shall be conforming to IS : 2705 of lastest version of rating 11 KV , 800/ 5A , No of core 2 , core I for metering and core II for protection 1 : 1.0 10 VA core 2 , 5 P 10 , 15 VA . (e) Cast resin copper wound potential transformer conforming to IS ; 3156 of latest version of rating 3 phase 11 KV/√3/110V/ √ 3 , 100 VA , CI 1.0 CI 3P and HT fuse at the primary end and four pole MCB at the secondary end of the PT (f)Accessories like local/remote switch , breaker control switch (T-N-C) , space heater with thermostat , DC 7 AC control circuit through MCB indicating lamps for RYB , spring charge , DC supply healthy breaker ON/OFF breaker in service/Test (g)Digital ammeter , digital voltmeter , digital energy meter and anti pumping relay (h)Master trip relay -01 no Aux relay VAA33-02 Nos

1

-

-

... More
(j)Multi function meter with suitable communication to central Software data control, converter having facility of real time data monitoring, historical trend and Web Dashboard. (k)Comprehensive numerical protection relay open type can be either MOD BUS IEC , 870-103 or with IEC 61850 compatible for normal distribution O/C , E/F , U/V , O/V protection having following additional facilities : (i )Trip circuit supervision (ii)Disturbance recorder (iii)Event log with date and time (iv)Measurment and control feature (l) Panel shall also have additional facility like as under : - (i) Intemittant rated closing and tripping coil (ii)Fully tested for internal arc ( 18.4 KA for 1 sec ) as per latest IEC 62271-200 at CPRI / Accredit Lab . (iii)Vacuum bottle shall be epoxy encapsulated . (iv)Racking in/out manual closing/tripping of CB with compartment door closed .

-

-

-

... More
(m)Breaker shall be provided with following contacts . (i)Auxillary switch with 6 NO+NC mounted on the draw out portion of the switch gear . (ii)Position switches with 3 NO+1 NC contacts for each position in SERVICE and TEST . (iii)Position switches with 3 NO+1 NC contacts for each position in SERVICE and TEST . (iv)Mechanical operator counter (n)Panel height should not be exceed 2300 mm . (o)Electrically and mechanically interlocking between two Nos incomer (p)Breaker , panel , relay , Voltmeter and ammeter shall be of same manufacturer. (q)Type test report shall be submitted alongwith drawing submission . Note- (I) Drawing for VCB shall be approved by GE before placement of order by contactor. (II) Pre dispatch Inspection of VCB shall be carried out by the rep of AO within over all cost quoted. (III) Pre commissioning test shall be carried out by SEI or rep of AO. (IV) CT ratio to be provided shall be approved by GE before placement of order by contactor. (V)Foundation for the equipment shall be made as per the OEM direction .The cost of the same is deemed to be included in the overall quotted cost by the bidder.

-

-

-

... More
Supply installing, commissioning and testing of transformer, step down, Copper wounded, Outdoor type complete with standard fittings HT 11 KV/433 volts (at no load) 3 phase 4 wire, 50 Hz, capacity 1000 KVA or next higher capacity, core type double copper wound, oil immersed naturally cooled, Oil naturally Air natural (ON AN) with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector group DYn-11 with neutral brought out on secondry side (LV side) and having tapping at +/- 7.5% in steps of 2.5% on HV side to be changed by means of hand operated off load tap changer gear. The maximum temp rise should not exceed 45 degree celsius in oil and 55 degree Celsius in HV/LV winding when measured by resistance method after continous full load run on an ambient temperature of 40 degree Celsies. The Transformer shall be IS-1180 level 2 marked and shall comprises of the following (a) Three Nos porceian bushing suitable for 11 KV on HV side complete with copper rods, nuts and washers (b) One cable box on LT side (Secondary side) consisting of four Nos porcelain bushing with copper rods, complete with nuts and washers with cable glands (c) Oil conservator with filter type drain valve and oil level gauge d) De- hydrating breather with first time fill of dehydrating agent (Silica Gel) (e) Explosive vent, thermometer pocket on tank cover Oil level gauge, Oil drain filter valve, Lifting lugs, Oil filling hole with cap, plug with connection plate complete, Air release valve plug and four nos plain solid cast steel detachable rollers. (f) One no 100 mm dia dial type thermometer vapour pressure type, having range 0-120 Degree Celsius with metal guard having maximum perimeter temperature reading indicator with re- setting devices (g) Two earthing terminal on tank cover to facilitate fixing of 25x4 mm Gl iron earth strip for earthing of body (h) Rating plate and terminal marking plate (j) Extra bushing for neutral, out side the cable box for providing independent set of earthing for neutral.

1

-

-

... More
(k) First filling of new transformer oil, IS-335 filtered and tested. NOTE: (i) Transformer shall be painted two coats of epoxy paint (ii) Transformer shall be energy conservent for which necessary test certificate to be produced by Contractor from OEM of the transformer (iii) Pre dispatch inspection of transformer shall be carried out by rep of Accepting Officer at manufacturer premises within overall cost quoted by Contractor. Nothing extra shal be payable on this account (iv) After installation of the transformer, the same shall be tested and commissioned by SEI or rep of Accepting Officer and equipment/instruments required for testing shall be arranged by Contractor Cost of the same shall also be deemed to be included in the item rates quoted by the contractor (v) Drawing of transformer shall be approved by GE before placement of order (vi) Minimum size of plinthfor transformer shall be 4mx4m×1m (LXBXH) (vii) chain link fencing from all sides platform and aggregate upto fencing including provision of suitable size of gate with locking arrangement shall be paid in B/R schedule under respective item of work.

-

-

-

... More
S & F gang operated air break switches with vertical isolation complete with drop out fuse unit triple pole, 12 insulator type, manually operated, mounted on insulators and steel frame, with operating mechanism worked from ground level for rating 200 Amps, 11000 volts complete with GI operating pipe of heavy duty grade of suitable length complete all as directed

1

-

-

... More
S & F jumpers in red/yellow/blue colour for HT lines/connections made from aluminium conductor single core PVC insulated cable of suitable size complete including winding wires, aluminium tapes etc all as specified and directed.

300

-

-

... More
Supply and laying testing cable XLPE insulated, armoured,screened, PVC bedded, galvanised steel strip or wire armoured, electrical power cable(heavy duty) 1100 Volt grade with stranded aluminium conductor of size 630 Sqmm, 3.5 core, complete all as specified and directed. (Note :- Excavation & earth work, GI pipe for laying of cable, sand cushioning, cable protection cover shall be measured and paid for seprately under respective items of the schedule.)

300

-

-

... More
All as per srl item no 60 above, but cable size 500 Sqmm, 3.5 core

230

-

-

... More
All as per srl item no 60 above, but cable size 400 Sqmm, 3.5 core

580

-

-

... More
All as per srl item no 60 above, but cable size 70 Sqmm, 3.5 core

270

-

-

... More
All as per srl item no 60 above, but cable size 50 Sqmm, 3.5 core

590

-

-

... More
All as per srl item no 60 above, but cable size 35 Sqmm, 3.5 core

200

-

-

... More
All as per srl item no 60 above, but cable size 16 Sqmm, 4 core

30

-

-

... More
All as per srl item no 60 above, but cable size 25 Sqmm, 4 core

530

-

-

... More
All as per srl item no 60 above, but cable size 10 Sqmm, 2 core Note- Out of total qty against this description 300 RM pertains to Arboriculture Schedule in this BOQ.

820

-

-

... More
M&L sand cushioning for underground cable 8 cm below and 15 cm above the cable with clean dry river sand in trenches including spreading, levelling etc. complete all as specified and directed Note:Punned thickness only will be measured for the purpose of payment.

230.04

-

-

... More
Supply and laying reinforced precast concrete cable cover class LV type-1 flat, size 250mmx150mmx40mm as protection to LT cable complete all as specified and as directed.

17333

-

-

... More
Supply and laying reinforced precast concrete cable cover class HV type-1 flat, size 300mmx180mmx40mm as protection to HT cable complete all as specified and as directed.

1333

-

-

... More
Supply, transporting to site, erecting and fixing in truly verticle position, steel tubular swaged pole, type 410-SP-31 (8.5 metre long) complete finial taper plug, bolts, nuts, scerws as specified, CI base plate including drilling holes and painting with two coats of aluminium paint externally, providing 30cm wide alternate strips with white and black synthetic enamal paint upto 1.2m height from ground level and numbering the pole (with black and white paint), undergruound part of the pole shall be painted with black bituminous paint complete all as specified and directed. Note: Excavation, earthwork, PCC foundation shall be measured and paid separately, complete all as specified and directed. Notes:-(a) Steel tubular swaged pole should be pre-approved by Engr-in-charge. (b) Excavation, earthwork, PCC foundation shall be measured and paid separately.

12

-

-

... More
M & L for earthing complete with galvanized steel earth plate 60 cm X 60 cm X 6 mm thick buried vertically in ground to depth not less than 2.25 metres deep below ground level, with top edge of earth plate not less than 1.5 m below ground level, connected to galvanized iron earth strip of size 32mmx6mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel besides welding at all joints as shown in drawing and including excavation and earth work, GI pipe light grade 40mm bore for protection of earth wire and connected to continous earth lead on pole/test point, supplying and laying charcoal dust common salt, PGI funnel and wire mesh, 20mm dia GI pipe medium grade for watering including necessary excavation and earth work, PCC 1:2:4 type -B1 and 40 mm thick RCC M-25 (Design Mix) reinforced with TMT 8mm nominal dia @ 100 mm c/c both ways pit cover, CI frame, all as shown and specified in electrical plate No 3 of SI Part I of 1991, complete all as specified and directed by Engineer-in-Charge. Note : (i) The cost of earth lead /strip and GI pipe for protection of earth lead/strip upto 7.5m is included in the quoted rate. (ii) The cost of excavation, earth work is included in the quoted rate. (iii) Out of total quantity given against this description, 21 units pertains to external electric works and 5 units pertains to fire fighting system works.

26

-

-

... More
M & L for earthing complete with galvanized steel earth plate 60 cm X 60 cm X 6 mm thick buried vertically in ground to depth not less than 2.25 metres deep below ground level, with top edge of earth plate not less than 1.5 m below ground level, connected to galvanized earth lead wire 4.00mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel besides welding at all joints as shown in drawing and including excavation and earth work, GI pipe light grade 15mm bore for protection of earth wire and connected to continous earth lead on pole/test point, supplying and laying charcoal dust common salt, PGI funnel and wire mesh, 20mm dia GI pipe medium grade for watering including necessary excavation and earth work, PCC 1:2:4 type -B1 and 50 mm thick RCC M-25 (Design Mix) reinforced with XPM (weight not less than 3 Kg/sq m) pit cover, CI frame, all as shown and specified in electrical plate No 3 of SI Part I of 1991, complete all as specified and directed by Engineer-in-Charge. Note : (i) The cost of earth lead /strip and GI pipe for protection of earth lead/strip upto 7.5m is included in the quoted rate. (ii) The cost of excavation, earth work is included in the quoted rate. (iii) Out of total quantity given against this description, 7 units pertains to external electric works and 4 units pertains to fire internal electrification works.

11

-

-

... More
SEWAGE DISPOSAL WORKS M & L for factory made Precast reinforced concrete rectangular drain and manhole cover slab with frame of Size 1200mm x 600mm x 100mm plain surface in concrete grade of M-30 with reinforcement inside @ 8mm dia MS TMT bars both ways in Single layer with 1.2mm MS Strip at corners epoxy painted complete all as specified and directed. Note: Out of the total quantity against this item, 42 Nos pertain to Sewage Disposal Works and 100 Nos pertain to Area Drainage Works.

142

-

-

... More
M & L for factory made Precast reinforced concrete rectangular drain and manhole cover slab with frame of Size 1500mm x 600mm x 100mm plain surface in concrete grade of M-30 with reinforcement inside @ 8mm dia MS TMT bars both ways in Single layer with 1.2mm MS Strip at corners epoxy painted complete all as specified and directed.

14

-

-

... More
H.D.P.E. Double Wall Corrugated (DWC) Pipes (ISI marked) 150 mm bore SN-8 Class as per IS 16098 part-II for nonpressure Underground drainage and Sewerage applications with and including cost of special O rubber ring couples etc., laid in trenches on concrete bed to level / gradient jointing with appropriate class fitting as per manufacturer’s instructions including jointing accessories and fitting complete, all as specified and directed.

430

-

-

... More
H.D.P.E. Double Wall Corrugated (DWC) Pipes (ISI marked) 200mm bore SN-8 Class as per IS 16098 part-II for nonpressure Underground drainage and Sewerage applications with and including cost of special O rubber ring couples etc., laid in trenches on concrete bed to level / gradient jointing with appropriate class fitting as per manufacturer’s instructions including jointing accessories and fitting complete, all as specified and directed

135

-

-

... More
Cutting into existing manholes for connecting new drains, making good to pipe of 300mm and rendering, cutting out existing benching for and forming branch channel (1/2 round or 3/4 section) in cement concrete 1:2:4 type B-l smooth finished, and reforming benching as required complete all as specified and directed.

3

-

-

... More
FIRE FIGHTING , FIRE HYDRANT SYSTEM , FIRE EXTINGUISHER WORKS Supplying and fixing exhaust, Diesel engine driven pump exhaust M. S. pipe class 'C' 150 mm dia including fitting like flanges, bends, reducers, etc. 50 mm thick fibre wool insulation aluminium cladding, 21 gauge, necessary excavation, fixing of silencer connections at engine exhaust, necessary supports, back filling, cutting and making good, bird proof and weather proof flap complete all as specified and directed.( Location- In Pump Room)

18

-

-

... More
Electric Motor Driven Pump Supplying, installing, testing and commissioning of Fire authority approved Electrical driven fire pump suitable for automatic/ manual operation consisting of the following: i)Horizontal mounted End Suction type fire pump having cast iron body, bronze impeller, stainless steel shaft & capable of delivering 2280 LPM against a total head of 70 M while running at 2900 RPM complete in all respect. ii)Squirrel cage, induction motor TEFC type suitable for 415 + 10%V, 3 phase, 50 Hz, AC supply, of suitable HP rating for the above pump with synchronous speed of 2900 RPM with flexible coupling and coupling guard . iii)Common bed plate for mounting pump and motor fabricated of mild steel channel as per manufacturer's recommendation with heavy duty Anti Vibration pads (4 Nos., heavy duty). iv)Coupling and coupling guard for direct coupling of pump and motor. v)Drain Pipe with Valve (50 mm dia) vi)Main Fire Pump and Sprinkler Pump - Discharge : 2280 LPM - App. Head : 70 M (Location - Pump Room )

1

-

-

... More
Diesel Engine Driven Fire Pump [Stand by pump] (Location - Pump Room ) Supplying, installing, testing & commissioning of fire authority approved Diesel Engine driven fire pump suitable for automatic/manual operations consisting of the following: i)Horizontal mounted end suction type fire pump having cast iron body, bronze impeller, stainless steel shaft & capable of delivering 2280 LPM against a total head of 70 M while running at 1800/2300 RPM complete in all respect. ii)Radiator cooled diesel engine of suitable BHP at 1800/2300 RPM for the above pump complete with standard accessories & suitable cooling system as described in specifications. iii)Common base plate for mounting pump & engine of requisite strength manufactured out of M.S. channels as per manufacture's recommendation with heavy duty Anti Vibration pads. (Cushy foot) (6 nos., heavy duty) iv)Coupling & coupling guard for direct coupling of engine & pump. v)200 liters capacity day oil storage tank fabricated from 16 SWG thick M.S. plates. Tank shall be provided with inlet, outlet, overflow, vent, drain connections, filling connection & level indicator. Tank shall be mounted on a suitable steel structure (Painted with 2 coats of red oxide paint). Tank shall be provided with epoxy coat from inside & two or more coats of synthetic enamel paint outside over two coats of red oxide primer. vi)24 volts 180 AH lead acid battery (12 volts - 2 Nos) with boost/Trickle charger for starting the engine automatically complete as required. vii)Provision for starting of Engine automatically in case of power failure at the time of fire viii)Diesel Engine driven pump of: - Discharge: 2280 LPM - App. Head: 70 M

1

-

-

... More
Electrical Motor Driven Jockey Pump Location - Pump Room : Supplying, installing, testing and commissioning of Fire authority approved Electrical driven fire pump suitable for automatic/ manual operation consisting of the following: i)Horizontal mounted End Suction type fire pump having cast iron body, bronze impeller, stainless steel shaft & capable of delivering 180 LPM against a total head of 70 M while running at 2900 RPM complete in all respect. ii)Squirrel cage, induction motor TEFC type suitable for 415 + 10%V, 3 phase, 50 Hz, AC supply, of suitable HP rating for the above pump with synchronous speed of 2900 RPM with flexible coupling and coupling guard . iii)Common bed plate for mounting pump and motor fabricated of mild steel channel as per manufacturer's recommendation with heavy duty Anti Vibration pads (4 Nos., heavy duty). iv)Coupling and coupling guard for direct coupling of pump and motor. v)Drain Pipe with Valve (25 mm dia) vi)Jockey Pump - Discharge : 180 LPM - App. Head : 70 M

1

-

-

... More
Supply, installation, testing and commissioning of Pressure switch of approved make for Hydrant pump, jockey pump and Diesel Engine Driven pump including necessary wiring and cut off valve up to central panel & other material as described in specifications.(Location- Pump Room)

3

-

-

... More
Suppy and fix Air cushioning tank (Air vessel ) 250mm dia x 2000mm height with dished top, made of minimum 6mm thick MS Pipe /Plate complete with 20mm dia Brass air valve (Ball type) , 20mm dia stop valve, pressure gauge with brass stop cock, nipple tees elbows and all accessories complete.(Location- Pump Room)

1

-

-

... More
Supplying, fixing, testing and commissioning of heavy class MS pipe, IS : 1239 marked with all necessary fittings like tees, elbows, flanges, reducers, gaskets, nuts and bolts etc. welded or screwed joints as required including fixing the pipe with necessary structural supports (Location: Pump room).

-

-

-

... More
80 mm dia (Nominal Bore)

12

-

-

... More
100 mm dia (Nominal Bore)

12

-

-

... More
150 mm dia (Nominal Bore)

18

-

-

... More
Supplying, fixing, testing & commissioning of heavy class MS pipe, IS : 3589 marked with all necessary fittings like tees, elbows, flanges, reducers, gaskets, nuts and bolts etc. welded or screwed joints as required including fixing the pipe with necessary structural supports (for delivery/suction manifold relating to the pumps) including painting of two coats of synthetic enamel paint over two coats of red oxide primer including all civil breakages and making good the same [ Location : Pump room].

-

-

-

... More
200 mm dia (6.35 mm thick) with necessary supports etc. as required. (Nominal Bore)

6

-

-

... More
250 mm dia (6.35 mm thick) with necessary supports etc. as required. (Nominal Bore)

6

-

-

... More
Supplying, fixing, testing & commissioning of 150 mm dia 6.35 mm thick flanged end basket 300mm height of Y-type strainer made from MS body with bottom and top removable flanges with nuts, bolts etc having filteration area at least 6 times the cross sectional area of the pipe.

2

-

-

... More
Supplying, fixing, testing & commissioning of C.I. Butterfly valve conforming to IS : 13095 with flanges, nuts, bolts and washers complete for following sizes :- [PN 1.6 rating].(Location- Pump Room)

-

-

-

... More
All as per description given in Srl item no 81 above with 150 mm dia (Note- Out of total quantity given against this description 20 units pertains to fire hydrant works)

28

-

-

... More
All as per description given in Srl item no 81 above with 100 mm dia. (Note- Out of total quantity given against this description 16 units pertains to fire hydrant works)

18

-

-

... More
All as per description given in Srl item no 81 above with 80 mm dia (Note- Out of total quantity given against this description 32 units pertains to fire hydrant works)

33

-

-

... More
65 mm dia

1

-

-

... More
50 mm dia

1

-

-

... More
Supplying, fixing, testing & commissioning of dulal plate non return valce complete with nuts, bolts, and washers complete all as specified and directed.(Location- Pump Room)

-

-

-

... More
150 mm dia

3

-

-

... More
100 mm dia

2

-

-

... More
80 mm dia

1

-

-

... More
65 mm dia

1

-

-

... More
50 mm dia

1

-

-

... More
Supplying, fixing, testing & commissioning of 100 mm dia Burden type, Stainless Steel dial type pressure gauge (in Pump Room) including brass isolation valve and pipe having caliberation of 0-14 Kgs omplete all as specified and directed.

6

-

-

... More
Supply, Installation testing & commissioning of Black Mild Steel Class 'C' (Heavy Duty) pipes conforming to IS : 1239 Part-I including cutting, threading, welding & all fittings like flanges, tees, elbows, bends junctions, reducers, ball valves etc. welded or screwed joints, clamps structural steel supports (as per TAC norms) or as required/ directed at site, complete all specified and directed.

-

-

-

... More
25 mm dia (Nominal Bore)

30

-

-

... More
50 mm dia (Nominal Bore)

12

-

-

... More
65 mm dia (Nominal Bore)

12

-

-

... More
80 mm dia (Nominal Bore)

84

-

-

... More
100 mm dia (Nominal Bore)

160

-

-

... More
150 mm dia (Nominal Bore)

816

-

-

... More
Supplying & Fixing S.S. single headed ISI marked oblique pattern hydrant landing valves with 80mm dia flanged inlet & 63 mm dia female outlet complete with gun metal cap and GI chain twist release type plugh and all accessories as per IS : 5290-1983 Type A (For internal + external hydrant).

30

-

-

... More
Supplying & Fixing of 63 mm dia 15 m long non-percolating flexible hose (RRL- type A) as per IS : 636. Type A with S.S. male & female instantaneous type coupling (IS 903), complete all specified and directed.

60

-

-

... More
Supply and fix 63 mm dia Gun Metal branch pipe with 12.5 mm nozzle confirming to IS 903 , complete all specified and directed.

30

-

-

... More
Supplying & Fixing of wall mounting swinging type first aid fire hose reel with drum, hanging bracket, 36.5 Mtr. length x 20 mm dia high pressure hose reel tubing as per IS: 444 with gun metal (GM) shut off nozzle having 5 mm dia orifice. The hose reel shall be conforming to IS : 884-1985. Rate shall include 25 mm dia M.S. pipe connection from Riser to hose reel, sockets, nipples, elbows and ball valve (25 mm dia). Drum shall be fixed on adjoining wall through anchor fasteners / cement concrete block as and when required.hose reel of 20 mm dia and 30 meter length confirming to IS 8090 (For internal hydrant system)

16

-

-

... More
Supplying & Fixing of weather proof standard fire hose cabinet (900 mm x 600 mm x 300 mm deep) for yard hydrants made of 16 SWG powder coated M.S. sheet having single or double opening glazed (4.0 mm thick glass) shutter including necessary locking arrangement by allan key, stove enamelled Fire red finish with " Fire Hose" marked on front, suitable for housing 2 nos. Hose pipe, 1 No. branch pipe & nozzle spanner.

30

-

-

... More
Supply and fix MS Cabinet ( apporx 750mm x 600mm x 450 mm ) to encl fire brigade inlet connection fabricated from 16 gauge sheet with full front glass door and locking arrangement painted and mounted on masonry platform complete.

1

-

-

... More
Supply, erection, testing and commissioning of FOUR WAY fire brigade inlet connection to wet riser system which comprises of 4 No. 63 mm dia Gun metal NRV, 1 No. powder coated weather proof standard hose box suitable for accommodating the above components fabricated out of 16 SWG MS sheet with central opening, glazed front incluiding necessary fittings the word FIRE BRIGADE DRAW OFF to be painted on the box complete all as specified and directed.

1

-

-

... More
FIRE DETECTION AND ALARM SYSTEM Supply, Installation, Testing & Commissioning of Intelligent Analogue Smoke Detector with inbuilt Isolar/ Isolator Module. Programmable multiple smoke senstivity level and 5 modes of operation, the detector shall be capable of operating in heat only mode. Bi-directional in-built short circuit isolator to protect against cable faults, dual bi-colour LED's with 360 degree view of status, auto- addressable/ electronically or hard addressed, utilises fully digital communication addressable protocol with high noise rejection (For Detectors/Device without inbuilt isolator, Fault Isolator or Isolator base to be provided with each detector/device). Independently certified as complying with requirements of UL 7th Edition Standard

425

-

-

... More
Supply, Installation, Testing & Commissioning of Intelligent Analogue Heat Detector with inbuilt Isolar/ Isolator Module and two programmable thermal senstivity level, the two level corresponds to rate-of-rise (A1R) and fixed temperature class BS. Bi-directional in-built short circuit isolator to protect against cable faults, bi-colour LED's with 360 degree view of status, auto- addressable/ electronically or hard addressed, utilises fully digital communication addressable protocol with high noise rejection (For Detectors/Device without inbuilt isolator, Fault Isolator or Isolator base to be provided with each detector/device). Independently certified as complying with requirements of UL 7th Edition Standard )

32

-

-

... More
Supply, Installation, Testing & Commissioning of Intelligent Analogue addressable resettable Manual Call Point , with in-built bi-directional short circuit isolator. Bi-Colour LED for local indication of device status, single action operation, reset to normal condition using special reset key, clearly visible alarm flag in the activated state (For Detectors/Device without inbuilt isolator, Fault Isolator or Isolator base to be provided with each detector/device). Independently certified as complying with requirements of UL 7th Edition Standard.

38

-

-

... More
Supply, installation, testing & commissioning of UL approved Isolator Base/ Module fully monitored for short circuit Ability to detect short circuit conditions • Design should be for use with analog sensor. • Should have Built-in LED indication upon short circuit condition • Must contain a security locking tab for tamper protection.

25

-

-

... More
Supply, Installation, Testing & Commissioning of Addressable (SLC) loop powered Wall Sounder with inbuilt Isolar/ Isolator Module and Beacon for providing Audible and Visual Alarms in response to the output signal from the control panel , however if the OEM is supplying conventional hooter cum strobe then they should consider individual module (for addressing purpose) and EN/UL listed monitored power supply for the devices in the same cost, 32 selectable tone and adjustable sound level, maximum output volume @ 1M distance 100 dB(A), output tone frequency range 440 Hz to 2900 Hz, Visual alarm device output frequency 0.5 or 1Hz. Independently certified as complying with requirements of UL 7th Edition Standard.

38

-

-

... More
Supply, Installation, Testing & Commissioning of Intelligent Analogue Single Input/ Monitor Module with inbuilt Isolar/ Isolator Module , microprocessor controlled interface module for Flow switch monitoring and other input purposes , with in-built short circuit isolator, 360 degree view LED's for local indication of device status, auto-addressable/ electronically or hard addressed, utilises fully digital communication addressable protocol with high noise rejection (For Detectors/Device without inbuilt isolator, Fault Isolator or Isolator base to be provided with each detector/device). Independently certified as complying with requirements of UL 7th Edition Standard.

6

-

-

... More
Supply, Installation, Testing & Commissioning of Intelligent Analogue Relay Output/ Control Module with inbuilt Isolar/ Isolator Module , for control of third party/auxiliary devices using single volt-free change-over relay contact, with in-built short circuit isolator, Bi-colour LED's for local indication of device status, auto-addressable/ electronically or hard addressed, utilises fully digital communication addressable protocol with high noise rejection (For Detectors/Device without inbuilt isolator, Fault Isolator or Isolator base to be provided with each detector/device). Independently certified as complying with requirements of UL 7th Edition Standard.

5

-

-

... More
Supplying and fixing M.S. structural work fabricated from standard sections, (MS rounds, angles, channels etc.) including cutting to size, drilling welding including cost of fasteners clamps in R.C.C. structural members as directed, including two or more coats of synthetic enamel paints over one coat of primer after surface preparation including cutting and making good walls.

1000

-

-

... More
LT Panel -V(Fire Fighting Panel) Supply, install, testing and commissioning of Outdoor type LT Feeder piller box made out of 3.15 mm thick CRCA sheet totally enclosed weather dust and vermin proof as per IS , CPRI Approved with front opening suitable locking arrangement having aluminium bus bar of 240 Amp capacity for RYB and half for neutral and insulated with insulators, including connecting incoming and outgoing cables necessary PCC 1:3:6 in foundation and made out of 50 mm x 50 mm x 6 mm angle iron grouted at ground below 30 cm from ground level and 60 cm above ground. Panel shall have PLC base control with digital LED display and IP 55 protected. LT Panel comprising of the following complete all as specified and directed by Engineer-in-Charge. Note : Cost of necessary internal wiring from bus bar to ACB/MCCBs/MCBs/RCBOs/DOL Starter/Enclosure connections etc shall be deemed to be included in the unit rate. INCOMING (a) MCCB 160 Amp 4 Pole , 415 Volt 36 kA mricroprocessor based adjustable thermal and fixed magnetic type, Ics= 100% Icu=100% Icw for 1 sec with spreader-01 Nos. OUTDOOR (a) MCCB 125 Amp 4 Pole, 415 Volt 25 kA microprocessor based adjustable thermal and fixed magnetic type, Ics= 100% Icu=100% Icw for 1 sec with spreader-01 Nos. (For Eletric driven fire pump). (b) MCCB 40 Amp 4 Pole, 415 Volt 25 kA microprocessor based adjustable thermal and fixed magnetic type, Ics= 100% Icu=100% Icw for 1 sec with spreader-01 Nos. (For Eletric driven Jockey pump). (c) MCB SPN 40 Amp, 2 pole, 240 V Single phase - 1 No. (For Fire Pump House) (d)Phase indicating LED Lamp Red/Yellow/Blue - 03 Nos (e)Digital Multimeter with CT- 01 No with selector switch.

1

-

-

... More
(f) 02 x DOL starter will be complete with suitable capcity of TPN, 415 Volt, 10 kA, C Curve (Motor Duty), suitable for power contactor, ON/OFF push buttons and ON/OFF/TRIP indicating lights, selector switch for mannual/automatic operations, CT operated Digital multimeter, suitable NO & NC Potential free contacts, SMPS , DC Relays as required for Interlocking /ON-OFF on receiving of fire signal from fire control panel/Control Module, O/L relay with inbuilt single phase preventor , selector switches etc. as required. (For 01 x fire pump & 01 x Jokey pump). NOTES:- (a) Audio visual alarm & indications having disconnect/reset facility with a range of 1/2 km. Annunciator to be provided in the Fire panel with hooter and acknowledge, test and reset PBs. The indication shall come on when electrical driven pump set fails to start on pressure drop or when there is power failure during pressure drop. (b) Facility for mode of selection switch to be in auto mode and manual mode. (c) Protection failure & control cabling. (d) Automatic/mannual indication for ON/OFF/ TRIP shall be provided through potential free contact. (e) Provision of automatic/manual starting/stopping of engine shall be provided. (f) Wiring from pressure switch to starter. (g) Set of control system to make the system automatic as per functional requirements. (h) Provision for starting the diesel engine fire pump with battery charger for trickle & boost charging. The diesel engine driven fire pump shall start automatically in the event of pressure drop beyond preset limit on mains failure or failure of electrical driven pumps to start for each Diesel Engine Pump. Note- Drawing for LT Panel shall be approved by GE before placement of order by contactor.

-

-

-

... More
Supplying and applying two coat of 4 mm thick antirust protection including primer and lap of 25 mm on M.S. pipe of 150 mm dia in trenches or complete including surface preparation coating and wrapping shall be confirm to ISI 10221 including conducting Holiday Test complete all as specified and directed.

100

-

-

... More
Supplying & fixing air release valve of 25 mm dia with fittings etc. to be installed at risers complete all as specified and directed.

8

-

-

... More
Supplying and laying light duty non pressure NP-3 Class RCC pipe S/S jointed with stiff mixture in the proportion 1:2, 300 mm dia R.C.C. Hume pipe for underground hydrant pipe at road crossings including collar pieces and filling inside of pipe with sand complete as required including necessary excavation and back filling complete all as specified and directed. (For road crossing)

100

-

-

... More
Supplying & Fixing of burden type Stainless Steel dial type pressure gauge with brass isolation valve and pipe. (For each internal Fire hose cabinet) Dial Diameter : 100 mm Caliberation : 0-10 Kg/cm2

3

-

-

... More
Supply, erection, testing and commissioning of fire brigade draw out connection confirming to IS : 4038-1986 with 150 mm Non return valve/ strainer incluiding necessary fittings the word 'FIRE BRIGADE DRAW Out' to be painted on the box complete all as specified and directed.

1

-

-

... More
Supply, Installation, Testing & Commissioning of Active Network Repeater Panel (Including network card) with backlit (840 Character/240x64 pixel resolution/10" Touchscreen) graphical LCD display, incorporates function buttons for Silence, Mute, Resound, Reset and Disable/Enable. Networked for system display and control, in-built network card to network with compatible addressable panel(s) and repeater panel(s), fully on-site programmable via alphanumeric keypad or configuration software, panel housing meets min IP30 ingress protection classification finished in RAL 7035 colour complete all as specified and directed..

2

-

-

... More
Supply, Installation, Testing & Commissioning of 1-4 loop Analogue Addressable Fire Alarm Control Panel UL-10th Edidion Certified expandable via plug-in loop driver boards, loop current minimum 500mA per loop, dual flash based microprocessor, supports to connect minimum 126 devices in each loop via fully digital communication protocol, equipped with a inbuilt printer optional, white backlit display ( 840 Character/240x64 pixel resolution/10" Touchscreen) graphical LCD Display with atleast 6 lines of information, 200 zones (soft zones) per panel and 2000 zones on network, fully programmable via alphanumeric keypad or configuration software without using any king of DONGLE/LICENCE OR SPECIAL CABLE, dediacted USB and RS-232 serial port for direct or PC connection. Should support 5000 historic events and 500 fire alarm events. Panel shall be equipped with in-built multi-meter for live monitoring of loop current, earth voltage, loop voltage etc.Panel should support peer to peer networking between panels capable of networking 32 nodes on standard networking and 200 nodes on secured network.Panel housing shall meets min IP30 ingress protection classification finished in RAL 7035. The panel shall be capable of providing output for BMS/ SCADA software through optional Modbus/ Bacnet module (The System cost shall be included of all necessary cards, modules, Panel enclosure, CPU and associated accessories to complete the system design).

2

-

-

... More
Supply & fixing of copper wire 2C X 1.5 Sq.mm wire complete all as specified and directed.

1850

-

-

... More
Supplying and fixing of M.S. conduit of 20 mm dia size with all accessories , such as bend, tee and giti and screw etc complete all as specified and directed.

1500

-

-

... More
Supplying & fixing of ISI marked (IS: 2878) portable Co2 fire extinguisher of capacity 4.5 kg flat base including valve discharge hose of not less than 10mm dia. meter complete in all respect including initial fill with Co2 gas confirming to IS 307-1966 and filled to filling ratio of not more than 0.367 complete all as specified and directed.

22

-

-

... More
Supplying & fixing of ISI marked (IS: 15683) portable AFFF foam type fire extinguisher, capacity 9 liter complete all as specified and directed.

4

-

-

... More
Supplying & fixing of ISI marked (IS: 15683) portable Water mist type fire extinguisher, capacity 9 liter complete all as specified and directed.

28

-

-

... More
Supplying & fixing of ISI marked (IS: 15683) portable ABC multipurpose mono monioum phosphate powder , nitrogen pressurised type fire extinguisher, Capacity 6 kg complete all as specified and directed.

69

-

-

... More
Supplying & fixing of ISI marked (IS: 15683) portable ABC multipurpose mono monioum phosphate powder , nitrogen pressurised type fire extinguisher, Capacity 9 kg complete all as specified and directed.

8

-

-

... More
Supplying & fixing of ISI marked (IS: 13886) portable fire extinguisher, Wet Chemical type Class K Type (gas pressurized) Capacity 6 liter complete all as specified and directed.

4

-

-

... More
EMERGENCY LIGHTNING AND EXIT SIGN Supply & fixing of Addressable Combined Fire Alarm and Emergency Lighting Control Panel features 1 loop expandable up to 2 loop with loop card. The panel is compliant to BS5266, supports two lighting lines up to 127 points per line. The panel shall have event memory of 500 events, it shall have a line current of 2.5 amp. The panels shall contain a transformer installed inside the enclosure. The panel shall be networkable up to 12 panels complete all as specified and directed.

2

-

-

... More
Supply & fixing of ELS Panel Transformer 230 V with an output of 35V AC and is placed between mains and EL2 Control panel. (Approved as per BS EN 60598-2-2) ,complete all as specified and directed.

2

-

-

... More
Supply& fixing Key pad with an LCD to control, read and configure the Main ELS Control Panel, complete all as specified and directed.

2

-

-

... More
Supply & fixing of Addressable Exit Signage visible from 20 mtrs. The signage shall contains an integral long-life NiMH battery which complies with BS5266 in regards to providing 3 hours of illumination. The signage shall have dual fixing feature to mount either on ceiling or a wall. The device shall complies to BS5266 and contain range of directional lenses with ISO7010 legends. (Approved as per BS EN 60598-2-2) complete all as specified and directed.

30

-

-

... More
Supply & fix of Addressable Corridor Area LED Down The luminaries shall contain long-life NiMH batteries and latest LED technology. The light shall cast a rectangular pattern of light to illuminate corridors and escape route (Approved as per BS EN 60598-2-2 with BS EN 60598-1:2008) complete all as specified and directed.

22

-

-

... More
Supply & fixing of Addressable Open Area LED Down lighter. The luminaries shall contain long-life NiMH batteries and latest LED technology. The light shall cast circular pattern of light to illuminate open areas.(Approved as per BS EN 60598-2-2 with BS EN 60598-1:2008) with integral battery capacity of 3 hrs and bicoloured LED status indicator complete all as specified and directed.

22

-

-

... More
Supply & testing of screened and twisted single pair with 1.5 sq.mm 2 core annealed tinned multi strand copper conductor PVC Insulated flexible FRLS wire complete all as specified and directed.

1000

-

-

... More
Supply & fixing of 16 Gauge MS Conduit in size 20mm including the cost of junction box bends, elbow, sockets, Tee and GI flexible conduit to connect from ceiling to false ceiling etc laying in slab, cutting chasses and making good or surfaces mounting including all fixing hardware complete all as specified and directed.

800

-

-

... More
HEAT DETECTION TUBE Supply, install, testing & commissioning VDS Approved signal processor unit. It should have LED & LC display both as well as a 16 Relay. It shall be able to support 350 metres sensor cable length with 1 to 100 maximum sensor. The alarm triggering via differential and maximum temperature evaluation, High temperature resolution of 0.1 °C with a repeatability of ±0.1 K along the entire sensor cable length. Panel shall be Free from false alarms, caused by natural ambient temperature fluctuations, due to intelligent evaluation algorithms. Highly durable via utilisation of maintenance-free components in a modular configuration, RoHS compliant. Individual password-protected access levels for operators, maintenance and service personnel, as well as for commissioning.Operating temperature: -25 °C ...+70 °C, complete all as specified and directed.

4

-

-

... More
Supply, install, testing & Commissioning VDS approved ,Heat Sensing Cable onto which the sensors are mounted in an encapsulation at every 4 mtr interval. Complete encapsulation to protect sensors from environmental influences, Pinpoint sensor location via individual addresses, Constant sensor monitoring via control and evaluation unit Branching of cable routes via connection boxes. Cable should detect freely adjustable absolute alarm thershold & freely adjustable differential alarm thershold i.e. fixed temperature as well as rate of rise of temperature.measuring range -40°...+120° complete all as specified and directed.

200

-

-

... More
Supply, install, testing & Commissioning Connection cable 2-wire, 0.8 mm core diameter, with functional integrity E30 - E90 according to DIN 4102-12; outer sheath in HM2 compound, red, loop resistance: max. 77 Ohm connecting cable between sensor cable & controller complete all as specified and directed.

50

-

-

... More
Supply, install, testing & Commissioning Clamps One-piece, self-locking polyamide cable clamp for indoor and outdoor use Toolless locking mechanism Halogen-free according to IEC 754-2, UV resistance according to ISO 4892-2 Temperature range -30 ... +110 °C (100 pcs) complete all as specified and directed..

4

-

-

... More
Supply, install, testing & Commissioning Connection module in the housing for a sensor cable, up to four external sensors and corresponding connection lines to the control and evaluation unit; Housing material: glass-fibre reinforced polycarbonate, halogen-free, UV and weather-resistant, free of heavy metals, Protection class: IP 66 according to EN ,complete all as specified and directed.

4

-

-

... More
Supply, install, testing & commissioning configuration software specially developed for the operation and programming of the sensor control unit.Setting pre-alarms and alarm thresholds (different thresholds for different sensors possible, even within a group),Two-sensor dependency to prevent false alarms and for live temperature monitoring complete all as specified and directed.

1

-

-

... More
KITCHEN SUPPRESSION SYSTEM Supply, installation, testing & Commissioning KITCHEN SYSTEM - CORE SYSTEM KIT - class F foam based AGENT Fire detection tubing System Kitchen Cylinder( 9 L ) CE agent included not pressurized and LPCB approved/light 1. Discharge line Pipes and Fittings for 9L Kitchen system are Stainless steel single ring fitting of Ø8 mm tube to nozzle. Nozzle of Triplestar kitchen system is 1 hole type ,radius- 1/4" and material of nozzle is Stainless Fire detector tubing of Ø6mm and including all ACCESSORIES FOR SENSOR TUBE complete all as specified and directed.

4

-

-

... More
Supply, installation, testing & Commissioning LPG Gas Detector for kitchen and LPG Cylinder room.complete all accessories and panel respect at all specified and directed.

4

-

-

... More
AIR COOLING SYSTEM Supply, fixing, testing and commissioning of Horizontal draw, Double Skin sheet metal sectionalised construction Air Washer units with injected PUF in between. Complete with Pre-filter section Wiremesh type with synthetic fibre filters (1 sets of synthetic fibres) with Fine Filter (Merv 13 or Higher), fan section complete with EC type Plug fans with IE5 rated motors, outlet dampers, wet section with steel tank, 12" thick (min.) cellulose pads, water circulation pump (3-phase CM series Grundfoss with FRP cover) , water spray and circulation arrangement, quick fill, float valve (100% SS material heavy duty with SS ball and suitable drain assembly including valve, Mist eliminator section (4 fold, UV Resistant Make - BKB Extrustion) with eliminator all complete as per specifications. AWU shall be designed as per specifications and basis of design to give 95% adiabatic saturation efficiency Including flexible canvas connections made of fire resistance flexible double canvas sleeve for duct connection. Air washers shall be selected for a maximum face velocity of 500 FPM at filter section and 500 FPM at cooling media Including humidistat controller etc as listed in specifications. LED lights in Fan and Filter Section to be considered with independent limit switch. Canopy to be provided with Corrugated sheet on top of Air washer to prevent water Ingress, Airwasher base frame/legs should be SS-304 (Part of Airwasher not Seperate item) Construction features given here under:

5

-

-

... More
Notes for item here-in-above (a) Air Washer i)Outer skin = 0.63 mm pre-coated GSS, RAL Code 9003 ii)Inner skin = 0.63 mm plain SS 304 (Inside entire machine) iii)Panel = 50 ( +/- 1 ) mm thick PU Foam density 40 kg/m3 iv)Frame Work = Extruded Anodised Aluminium v)Tank = 18G SS-304 with Slope design for proper water drainage vi)Pump = 1 Nos , Grundfoss make - 3 Phase Pumps, CM Series vii)Hinges and Locks = Aluminium Die cast (Plastic material not accepted). viii)Screws & Bolts = All screws and Nut Bolts to be SS material only. Note- Capacity shall be as per OEM Specification or higher (b) Fan Section ( fans Forced Draft Type Arrangement) i)Outer skin = 0.63 mm pre-coated GSS ii)Inner skin =0.63 mm plain SS 304 iii)Panel = 25 mm thick PU Foam density 40 kg/m3 iv)Frame Work = Extruded Anodised Aluminium v)Hinges and Locks = Aluminium Die cast vi)Gaskets = EPDM vii)Dia = 560 mm Note-Capacity shall be as per OEM Specification or higher (c) Cellulose Pad Section, with Distribution pad of 50 mm thickness i)Outer skin = 0.63 mm pre-coated GSS ii)Inner skin = 0.63 mm plain SS 304, including all blankoffs iii)Pad Thk = 300 mm iv) Velocity Across Pad = 500 FPM v)Control Valves = Audco/L&T Note- Capacity shall be as per OEM Specification or higher

-

-

-

... More
(d) i)Air washer to be Forced draft type, fan installed in grid position. Ii)Inlet Louvers GI Powder Coated 18 Gauge with PPGI sheet. Iii)Filter section 600 mm width, 1200 mm height to be provided for proper removal of filters for cleaning, with hinged Door. iv)All Nut, Bolt SS, Base Frame - SS,300 mm height Legs - 20 Nos to be considered part of Air Washer. v)As described above entire inner skin & Tank in 18 Gauge SS 304 & AWU Top with with Corrugated sheet vi)Complete Wet section to be SS304 material including Celdek Pad and Delivery Chamber. vii)make up valve or automatic fill valve and 50 mm drain valve shall be part of air washer and cost seemed to be included in quoted rate. viii)Machine to be supplied with Heavy duty SS 304 legs of 300mm height, minimum 16 to 20 No legs for each Air washer to be considered part of Airwasher Supply. ix)Fan speed controller digital type to be considered with display setting and RS 485 function same to be mounted on the Electrical Panel. Note- (I)Drawing for Air Washer shall be approved by GE before placement of order by contactor. (II)Pre dispatch Inspection of Air Washer shall be carried out by the rep of Accepting officer within over all cost quoted. (III)Foundation for the equipment shall be made as per the OEM direction .The cost of the same may pls be included in the overall cost nothing will be paid extra.

-

-

-

... More
Supply, Installation, Testing Balancing & Commissioning of G.S.S rectangular/round ducting as per IS 655 - 2006 complete with gaskets, elbows, splitters, vanes, supports adjustable dampers, etc. as per approved drawings.(Factory Fabricated/Site Assembled).The price shall include necessary scaffolding required for working at required height.It is should also include duct planeum as per drawing complete all as specified and directed by engr-in-charge. (Hot dipped Galvanised with 120GSM Zinc coating)

-

-

-

... More
Thickness 1.00mm Sheet

82

-

-

... More
Thickness 0.80mm Sheet

1430

-

-

... More
Thickness 0.63mm Sheet

1170

-

-

... More
Supplying, Fixing,testing and commissioning of fire dampers in Main branch and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per MES specifications complete all specified and directed by engr-in-charge. Note- The Fire Damper should be integrated with Fire Panel.

30

-

-

... More
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.

65

-

-

... More
Supply and fixing of 25 mm thickness duly laminated aluminium foil of mat finish closed cell Nitrile rubeer(Class O) insulation on the existing duct after applyng suitable adhesive for Nitrile Rubber. The joint shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specification and as required complete all specified and directed by engr-in-charge.

3422

-

-

... More
Supply and fixing of acoustic lining of supply air duct and plenum with 15 mm thick Supply and Application of Acoustic Insulation with Engineered Nitrile Rubber open cell foam with Density 140 - 180 Kg/m3 passing Class 1 Fire Performance test as per BS 476 Part 7, Air Erosion test for 10,000 fpm air velocity as per ASTM C 1071-05 and with built-in antimicrobial protection. The material should pass Fungi Resistance Test as per DIN EN ISO 846 Method A and Bacterial Resistance Test as per DIN EN ISO 846 Method C; to be applied using manufacturer's recommended Rubber based Adhesive in a blend of solvents complete all as specified and directed by engr-in-charge.

30

-

-

... More
Supply, Installation, Testing & Commissioning of Exhaust Fan for Ventillation purpose of the air cooling,of 300mm sweep exhaust fan (metallic body) of following sizes/ sweep in the existing opening including providing and fixing suitable size 12 mm thick BWP and water proof plywood on frame work with minimun air flow of 800-1000 CFM. Scope Should also include the Supply, Installation, Testing & Commissioning of Automatic/Manual back shutter(Aluminium or as per OEM design/recommendation) for protection against dust for Exhaust Fan.Reference model for Exhaust Fan is Aero Clean Plus with Sweep 300 mm , RPM 1370 or more , CFM: 1600 m3/hr. Power Input: 72 Watts complete all specified and directed by engr-in-charge.

196

-

-

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays of size 100 mm width X 50 mm depth X 2 mm with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.complete all specified and directed by engr-in - charge. Note- The Contractor shall prepare and produce instruction, operation and maintenance manuals in English for the use, operation and the maintenance of the supplied equipment and installations and submit to the GE in (3) copies at the time of handing over. The manual shall generally consist of the following: i)Description of the project. ii)Operating instructions. iii)Maintenance instructions including procedures for preventive maintenance. iv)Schematic & control wiring diagrams. v)Commissioning Certificate.

500

-

-

... More
M & L for concealed Point wiring using approved colour coding as per IS, with stranded copper conductor 1.5 sqmm (nominal area) single core , flame retardant low smoke and low halogen FRLSH PVC insulated unsheathed, 1100 V grade conforming to IS 694 marked, multi stranded copper conductor including PVC conduit medium grade ISI marked 20mm dia with all fittings and accessories, concealed type, PVC junction boxes, modular GI metal sunken/flush boxes of thickness not less than 1.2mm of any modules from 1 to 18 Modules with Inner and outer modular cover plates and blank plates, including FRLSH flame retardant low smoke and low halogen rigid PVC insulated unsheathed stranded copper conductor 1.5 Sqmm (nominal area) single core cable as earth continuity conductor to common earth and connected to earth dolly complete all as specified and directed by Engr-in-charge. Note :- (i) Cutting/chasing of wall etc. deemed to be included in the quoted rate of this item. (ii) Modular GI metal flush/sunken Box along with modular base/front cover and blank plate are inclusive in the item rate quoted. (iii) Only switches, sockets and fan regulators shall be measured and paid separately.

-

-

-

... More
One light/exhaust/Call bell point controlled by one,one way switch/Bell push

521

-

-

... More
One socket outlet point 6 A on same board

31

-

-

... More
One socket outlet point 6 A on independent board

199

-

-

... More
One light point controlled by Two 2-way switches

7

-

-

... More
M & L concealed Point wiring using approved colour coding as per IS with stranded copper conductor 2.5 sqmm (nominal area ) single core, flame retardant low smoke and low halogen FRLSH PVC insulated unsheathed, 1100V grade conforming to IS 694 marked, multi stranded copper conductor including PVC conduit medium grade ISI marked 25mm dia with all fittings and accessories, PVC junction boxes, modular GI metal sunken/flush boxes of thickness not less than 1.2mm of any modules from 1 to 18 Modules with Inner and outer modular cover platesand blank plates, including FRLSH flame retardant low smoke and low halogen rigid PVC insulated unsheathed stranded copper conductor 2.5 Sqmm (nominal area) single core cable as earth continuity conductor to common earth and connected to earth dolly complete all as specified and directed by the Engr-in-charge. Note :- (i) Cutting/chasing of wall etc. deemed to be included in the quoted rate of this item. (ii) Modular GI metal flush/sunken Box along with modular base/front cover and blank plate are inclusive in the item rate quoted. (iii) Only switches and sockets shall be measured and paid separately.

110

-

-

... More
M & L concealed Point wiring (AC & Geyser) using approved colour coding as per IS with stranded copper conductor 4 sqmm (nominal area ) single core, flame retardant low smoke and low halogen FRLSH PVC insulated unsheathed, 1100V grade conforming to IS 694 marked, multi stranded copper conductor including PVC conduit medium grade ISI marked 25mm dia with all fittings and accessories, PVC junction boxes, including FRLSH flame retardant low smoke and low halogen rigid PVC insulated unsheathed stranded copper conductor 4 Sqmm (nominal area) single core cable as earth continuity conductor to common earth and connected to earth dolly complete all as specified and directed by the Engr-in-charge. Note :- (i) Cutting/chasing of wall etc. deemed to be included in the quoted rate of this item. (ii) Only sheet metal enclosure with socket pug top and MCB shall be measured and paid separately.

10

-

-

... More
M & L for Concealed Sub main Wiring with two run of 4.00 Sqmm (nominal cross-sectional area) FRLSH PVC insulated & unsheathed 1100 volts grade multistranded copper conductor single core cable drawn through and incl medium grade PVC conduit of adequate size and fittings and accessories concealed in walls, floors ceilings and Cutting/chasing of wall complete including one run of FRLSH PVC insulated & unsheathed single core multistranded copper conductor cable of size 4.00 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly from main DB to Sub DB /AC's earth & plug Socket. Note :- Two run of 4 Sqmm + one run of 4 Sqmm as earthing lead including PVC conduit shall be considered as one unit each of one RM.

300

-

-

... More
M & L for Concealed Sub main Wiring with two run of 6.00 Sqmm (nominal cross-sectional area) FRLSH PVC insulated & unsheathed 1100 volts grade multistranded copper conductor single core cable drawn through and incl medium grade PVC conduit of adequate size and fittings and accessories concealed in walls, floors ceilings and Cutting/chasing of wall complete including one run of FRLSH PVC insulated & unsheathed single core multistranded copper conductor cable of size 6.00 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly from main DB to Sub DB. Note :- Two run of 6 Sqmm + one run of 6 Sqmm as earthing lead including PVC conduit shall be considered as one unit each of one RM.

360

-

-

... More
M & L for Concealed Sub main Wiring with Four run of 10.00 Sqmm (nominal cross-sectional area) FRLSH PVC insulated & unsheathed 1100 volts grade multistranded copper conductor single core cable drawn through and incl medium grade PVC conduit of adequate size and fittings and accessories concealed in walls, floors ceilings and Cutting/chasing of wall complete including two run of FRLSH PVC insulated & unsheathed single core multistranded copper conductor cable of size 6.00 Sqmm green in colour as earth continuity conductor connected to common earth and earth dolly from main DB to Sub DB. Note :- Four run of 10 Sqmm + two run of 6 Sqmm as earthing lead including PVC conduit shall be considered as one unit each of one RM.

120

-

-

... More
S & F modular Switch 1 way, 6A, 1 module all as specified and as directed

960

-

-

... More
S & F modular Switch 2 way, 6A, 1 module all as specified and as directed

13

-

-

... More
S & F modular Switch 1 way 16A, 1 module all as specified and as directed

110

-

-

... More
S & F modular socket 6A, 2/3 pin combined 2 module all as specified and as directed

230

-

-

... More
S & F modular socket 6A/ 16A, 2/3 pin combined 2 module all as specified and as directed

110

-

-

... More
S & F modular bell push 6A one module

20

-

-

... More
S & F Bell Ding dong, AC, 230 V, single phase incl elct connection complete all as specified.

20

-

-

... More
S & F modular Fan Regulator step type, 2 module, suitable for BLDC fans all as specified and as directed by the Engr-in-Charge

119

-

-

... More
Material and labour for ceiling rose surface type, 65 mm x 50 mm three terminals / PVC / polycarbonate, isolated body fixed on PVC block complete all as specified and directed.

573

-

-

... More
Supply and fixing energy saving LED luminaire 600mm x 600mm, 36 watt, 220 V, AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders and LED lamps suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed.

91

-

-

... More
S&F LED bulb 12 Watt, 230 volts AC 50 Hz Retrofit B22 base complete all as specified and directed.

66

-

-

... More
M&L for Ceiling fans complete with blades, down rods and accessories, 230 V, 1200 mm sweep, five star rated with brushless direct current motor(BLDC) complete in white colour with canopy and hanging rod with all accessories incl nuts,bolts,clamps etc, complete all as specified and directed.

89

-

-

... More
M&L for Ceiling fans complete with blades, down rods and accessories, 230 V, 1400 mm sweep, five star rated with brushless direct current motor(BLDC) complete in white colour with canopy and hanging rod with all accessories incl nuts,bolts,clamps etc, complete all as specified and directed.

30

-

-

... More
S&F Exhaust fan 300 mm sweep metal body, heavy duty, Single phase AC 230/240V, with energy efficient motor, pre lubricated double ball bearing, min speed 900 rpm,copper winding complete with louvers for wall mounting incl grouting,making hole of required size in the wall and holding down bolts, nuts, washers and provision of flexible copper conductor cable 3 core from ceiling rose to exhaust fan complete all as specified and directed.

22

-

-

... More
S&F Exhaust fan 450 mm sweep metal body, heavy duty, Single phase AC 230/240V, with energy efficient motor, pre lubricated double ball bearing, min speed 900 rpm,copper winding complete with louvers for wall mounting incl grouting,making hole of required size in the wall and holding down bolts, nuts, washers and provision of flexible copper conductor cable 3 core from ceiling rose to exhaust fan complete all as specified and directed.

2

-

-

... More
S & F new generation energy saving and environmental friendly long life LED building security light 1x35 watts made up of pressure die cast alluminium housing with high power LED as light source and lense embedded PC cover having TOP OPENING separate driver compartment with IP65 protection and impact resistance of IK07, with all accessories including suitable bracket with 32mm bore light grade GI pipe bend to shape, including MS clamp of size of required size and PVC cable 1.5 Sqmm twin core from ceiling rose to light fittings complete all as specified and directed.

29

-

-

... More
S&F MCCB TPN, 40-63 A, 415 V, 16 kA, Ics=100% Icu confirms to IEC 60947-II adjustable thermal setting type complete all as specified and directed.

4

-

-

... More
S&F MCCB TPN, 100/125 A, 415 V, 16 kA, Ics=100% Icu confirms to IEC 60947-II adjustable thermal setting type complete all as specified and directed.

3

-

-

... More
M&L for concealed / wall mounted busbar chamber, 4 pole, double door, 415 volts suitable for fixing of 4 pole MCCB upto 125 Amps as incommer and incl 04 Nos of standard insulated bus bar of capacity 200 Amps all enclosed in CRCA steel sheet of minimum thickness of 2mm thick, flush/Wall mounting type, drilling holes for incoming and out going cables complete with IP-54 all as specified and directed.

2

-

-

... More
S & F RCBO - A Type 4 pole 63Amps 100mA (In accordance with IS 12640-2 & IEC 61009-1) 240 V/415 V, 50 Hz, with 10 kA short circuit capacity, RCBO is designed for use in domestic, commercial and industrial distribution systems at the most downstream circuit for ensuring protection from leakage current, short circuit & over load to the user for a particular circuit. In normal use, it is safe to use and free of threat to user as well as to environment complete all as specified and directed.

2

-

-

... More
Note: For the purpose of arriving at lumpsum amount, the amount of credit sch for buildings of Rs 84750 shall be deducted from the total quoted.

-

-

-84724.35



Evaluation Notes How It Works ?

Related Tenders

Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.