Haryana Vidyut Prasaran Nigam Limited Tender
If you want to inquire about any e-tender the Haryana government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Haryana tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Haryana etender you're looking for. Read further to learn how to search and bid for etender Haryana.
Costs
EMD
₹ 25,74,000Document Cost
₹ 11,800Tender Fee
₹ 1,180
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_HBC_292938_1Bid Award Id
ViewTender No
20237004A30B A99C 486E B788 B56E812BF6B12111HVPTender Authority
Haryana Vidyut Prasaran Nigam Limited ViewPurchaser Address
-Website
http://etenders.hry.nic.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
66 kV Isolator with E/Switch
2
-
-
66 kV Isolator without E/Switch
10
-
-
66 kV Surge Arrestor
12
-
-
66 kV CTs for Line & Bus Coupler (600-300-150/1-1-1A)
9
-
-
66 kV T/F CT (300-200-150/0.577-1-1A)
6
-
-
66 kV PT for line
6
-
-
66 kV NCT (300-200-150/1A)
2
-
-
11 kV NCT (1800-900/5A)
2
-
-
11 kV LA
6
-
-
11 kV 15 Panel Board (2000A) with one SEM on each T/F I/C Panel (including one no. bus sectionalizer panel)
2
-
-
66kV C&R Panels with SAS:
a) Bus Coupler Protection and Circuit Breaker Panel (Without Auto Reclose)
1
-
-
b) Line Protection and Circuit Breaker Panel (Without Auto Reclose)
2
-
-
c) Transformer Protection and Circuit Breaker Panel (Without Auto Reclose)
2
-
-
9000KVAR 11kV Automatically Switched Capacitor Bank along with allied equipment (controlled by one VCB)
2
-
-
220V 100AH Battery San Tubular.
1
-
-
220 V 20/30A Battery charger (SMPS).
1
-
-
220V 100AH D.C.D.B.
1
-
-
415 V LT AC Distribution Board 300 A
1
-
-
11/0.4 kV Station T/F 200 KVA
1
-
-
(a) 1.1 kV Copper Control Cable unarmoured for 66kV bays of size 7Cx4mm2, 4Cx4mm2, 2Cx4mm2,2Cx6mm2, 3Cx2.5mm2, 16Cx2.5mm2, 10Cx2.5mm2 & 7Cx2.5mm2 including junction box etc. refer Section-6 of copper & control cable & Section-7 for switchyard erection.
1
-
-
(b) Stainless steel MK (200 TB)
5
-
-
11 kV Power Cable XLPE 1C x1000mm2 for T/F to 11kV incomer with termination kit for both ends (4 runs per phase for each transformer allocating them 2 runs per phase for each 11kV I/C).
960
-
-
11 kV Power Cable XLPE 3C x 400sq mm for Capacitor Bank with termination kit for both ends
200
-
-
11 kV Power Cable XLPE 3C x 50 sq mm for station T/F with termination kit for both ends.
50
-
-
650/1100 Volts 3.5 core 240 mm2 aluminium power cable from Aux. T/F to ACDB.
1
-
-
650/1100 Volt 3.5 core 70 mm2 aluminium cable for oil filtration set.
1
-
-
650/1100 Volt 4core 16mm2 unarmoured with copper power cable for MLDB and other cable required as per contract for 66kV bays.
1
-
-
Earthing Mat Material. The earth mat will be designed/ quoted for soil resistivity of 50Wm. In case soil resistivity is more than 50Wm then the earth mat will be designed for actual soil resistivity. The payment of extra material to be used for earth mat shall be made on pro rata basis. The approximate area of earth mat to be laid is given in the corresponding columns of the substations. However, item will remain a Lot item.
1
-
-
Fire Fighting equipments as per section-6 :
i) 22.5 Kg Capacity FE CO2 type, Trolley Mounted
4
-
-
ii) 25 Kg Capacity FE DCP type, Trolley Mounted
4
-
-
iii) DCP 10 Kg Capacity, Wall mounted
4
-
-
iv) FE CO2 6.5 Kg Capacity, Wall mounted
1
-
-
v) DCP 5 Kg Capacity, Wall mounted
1
-
-
vi) Foam Type 9 Litre Capacity, Wall mounted
1
-
-
vii) Water CO2 9 Litre, Wall mounted
1
-
-
viii) Fire Buckets (12 Nos. with stand in one set)
2
-
-
Complete lightning of control room building, switch yard area, road and street as per section-7 of the specification:
a) Supply and installation of 2 fittings of 240W LED lamps with all accessories for Complete lighting of outdoor Switch yard area as per clause 16.0 of section 7 of the specifications.
14
-
-
b) Supply and installation of 35W LED tube on tubular steel poles along with the boundary wall at a distance of 30 meter as per as per clause 16.0 of section 7 of the specification
9
-
-
c) Complete lighting of road and street by providing 90W LED lamps on tubular steel poles at a distance of 15meter along the roads and streets as per as per clause 16.0 of section 7 of the specification.
9
-
-
d) Supply and installation of post top lantern 40W LED Lamps with all complete accessories at the entrance gate of sub-station.
4
-
-
e) Supply and installation of 40W LED Lamps with all complete accessories on corners of control room building.
4
-
-
Complete Substation automation system of 66/11kV substations including hardware (along with transducers) & software for 5 No. 66kV bays along with associated equipment for the bays (bay as defined in the technical specification, sec-sub-station automation system) as per technical specification. Present Description 66 kV T/F 2 Line 2 B/C 1 Note:- Signals from protection relays in 11 kV incomer would also be wired to substation automation system (SAS)
1
-
-
High wall type split AC unit of 2 Ton capacity for SCADA room & C&R Panel room (as per technical specification).
4
-
-
Computer system (SFF) with intel core i5, 9th generation processor, 8 GB RAM, 1 TB HDD, 19.5" Display with UPS.
1
-
-
Mono chrome Multi-functional printer, A-4,25PPM, Wi-Fi.
1
-
-
Testing of IUM system at NABL accredited lab.
1
-
-
Bolted type 11kV Single tension string assembly with 3 numbers Anti FOG type disc insulators (E&M strength 9000 kg) per string with all hardware accessories including ball & socket connections and tension clamp sets suitable for twin tarantulla conductor. Alternatively the bidder may quote silicon polymer composite insulator string in place of Disc Insulators
12
-
-
66 kV Bolted type single tension string assembly with 6 numbers Anti FOG type disc insulators (E&M strength 9000 kg) per string with all hardware accessories including ball & socket connection and tension clamp set suitable for single zebra conductor. Alternatively the bidder may quote silicon polymer composite insulator string in place of Disc Insulators
64
-
-
66 kV bolted type single suspension string assembly with 5 numbers Anti FOG type disc insulators (E&M strength 9000 kg) per string with all hardware accessories including ball & socket connections and suspension clamp set suitable for single zebra conductor. Alternatively the bidder may quote silicon polymer composite insulator string in place of Disc Insulators
36
-
-
Boltless C-Type Wedge connectors matching with conductor size.
1
-
-
Copper lugs glands, PVC ferrules for control cabling.
1
-
-
Fiber cleats, Aluminium clamps, bolts, nuts, washers etc., for fixing control cables in trenches.
1
-
-
Galvanized iron perforated tray with side coupler plate bolts, nuts, washers and clamps etc. of size 75x25x2 mm, 150x25x2mm, 100x25x2mm etc. & G.I. Conduits of 50mm/100mm dia from equipment to main trench as per Section-7, Switchyard erection.
1
-
-
ACSR Zebra Conductor
770
-
-
AAC Twin Tarantulla Conductor
190
-
-
7/3.15 GS Earth wire
150
-
-
Spacers for Twin Tarantulla Conductor
1
-
-
U-bolt 20mm dia.
1
-
-
Mandatory spares for hardware/ mechanical/ Electrical auxiliaries to be supplied. 10 % of the finally approved quantities for item mentioned from Sr. No. 50 to 52.
1
-
-
Item for associated structure work
A)‘Lattice type steel structure for 66kV S/Stn Greenfield, Faridabad. Supply of material, preparation of fabrication drawing, galvanizing and delivery of lattice type steel structure for tower and beams for 66/11KV switchyard fabricated from steel conforming to IS: 2062 including nuts-bolts gusset plates foundation bolts and other accessories as per drawings supplied by the owner:
Main S/Stn. tower and beam:
a)Tower type CT-4
4
-
-
b) Tower type CT-5
5
-
-
c) Tower type CT-6
3
-
-
d) Tower type CT-8
6
-
-
e) Beam type CB-6
10
-
-
f) Beam type CB-7
6
-
-
g) Tower type DT-2
2
-
-
h) Tower type DT-3
2
-
-
i) Beam type DB-2X
2
-
-
B) Equipment Structure:
a) 66 kV CT Drg. No. HTD/ST-88R
15
-
-
b) 66 kV NCT Drg. No. HTD/ST-145(if required )
2
-
-
c) 66 kV PT Drg. No. HHW/ST-66
6
-
-
d) 66 kV Surge Arrestor Drg. No. HTD/ST-89
12
-
-
e) 66 kV Isolator Drg. No. HTD/ST-87R
10
-
-
f) 66 kV L&E Switch Drg. HTD/ST-87R
2
-
-
g) 66kV Cable support structure of galvanized iron along with foundation to be designed by bidder as per site requirement/size of cable.
8
-
-
h) 11 kV NCT Drg. HTD/ST-149 (if combined structure used)/ 11 kV NCT Drg. HTD/ST-88R (if required).
2
-
-
EARTH WORK :
Earth filling with good earth (as per satisfaction of Executive Engineer/Civil Works Division), laying in layers (as per specification), dressing, including carriage, irrespective of lead, loading, unloading, watering and compaction in layers with roller including compensation of earth complete in all respect.
4300
-
-
FOUNDATIONS:
Supply of labour, T&P, material and construction of RCC footings & pedestals etc. for steel gantry and equipment structures complete in all respects as per technical specifications & drawings attached with the tender document including cost of excavation, concreting, cement, reinforcement steel, form work, grouting, holding down bolts, backfilling etc. and other items not mentioned herein but required for the completion of work.
A. GANTRY TOWERS
66kV side
i) CT-4
4
-
-
ii) CT-5
5
-
-
iii) CT-6
3
-
-
iv) CT-8
6
-
-
33kV side
i) DT-2
2
-
-
ii) DT-3
2
-
-
B. EQUIPMENT 66kV side
i) 66KV LA
12
-
-
ii) 66KV PT
6
-
-
iii) 66KV NCT
2
-
-
iv) 66kV CT
15
-
-
v) 66kV L&E & Isolator
12
-
-
11kV side
i) 11kV NCT
2
-
-
BREAKER FOUNDATION
Design, engineering, supply of labour, material, equipment & const. of foundations for breaker including all associated works PCC, RCC, structural steel, steel reinforcement & any other item not specifically mentioned herein but reqd. for completion of work as per tech. spec.
i) 66 kV Breaker Foundation
5
-
-
CABLE SUPPORT STRUCTURE FOUNDATION
Design, engineering, supply of labour, material, equipment & const. of foundations for cable support structure including all associated works PCC, RCC, structural steel, steel reinforcement & any other item not specifically mentioned herein but reqd. for completion of work as per tech. spec.
i) 66 kV Cable support structure
8
-
-
CAPACITOR BANK FOUNDATIONS
Design, Engg. & supply of labour, material & construction of foundations for following rating capacitor bank with capacitor unit (with allied equipments) & series Reactor etc. including chain link fencing 1.8M height around cap. bank complete in all respect including any other items not specifically mentioned herein but required for completion of job as per technical specification.
i) 9000KVAR 11kV Capacitor Bank
2
-
-
TRANSFORMER FOUNDATION
Design, Engg., supply of labour, material and construction of foundation for station transformer including all associated works, RCC, PCC, Reinforcement steel, misc. structural steel and other items not mentioned herein but required for the completion of work as per technical specifications.
i) 11/0.4kV 200KVA Station T/F
1
-
-
TRANSFORMER FOUNDATION
Construction of transformer foundation including all associated works, RCC, PCC, reinforcement steel, misc. structural steel and other items not mentioned herein but required for completion of work as per technical specifications & drawing attached. In case extra foundation(s) has/have to be constructed (as per approved T/F drawing) to complete the job, nothing extra would be paid on this count.
i) 25/31.5 MVA 66/11 kV T/F Foundation
2
-
-
CABLE TRENCHES
Supply of labour, material such as cement, reinforcement steel, GI angles, flats, PCC & brick pillars below cable trenches for construction of Out-Door Cable Trenches (ODCT) of required depth/ type with pre-cast RCC covers including associated works like Cable Trench Culverts crossings for roads and sump- pit-cum-pump chamber with 2HP motor of reputed make, starter, volt meter, amp-meter etc. as per foundation & trench layout plan attached, HVPNL drgs. & tech. specs. complete in all respect.
i) D-type trench
170
-
-
ii) E-type trench
55
-
-
iii) F-type trench
20
-
-
iv) H-type trench
45
-
-
v) Sump Pit Cum Pump Chamber
1
-
-
SITE SURFACING
i) Providing, supplying and laying 100mm thick PCC (1:4:8) using 20mm nominal coarse aggregates and spreading 100mm thick layer of 40mm nominal size uncrushed/crushed/ broken stone pebbles over the PCC including construction of toe wall (exposed wall plastered with cement mortar 1:5) to hold 40mm single size uncrushed/ crushed/broken stone pebbles wherever required in the bays covered under the present scope as detailed in the GELO & instructions of concerned Executive Engineer/Civil Works Division.
1400
-
-
ii) Providing, supplying & laying two layers of uncrushed/crushed/broken stone/ pebbles gravel fill. The first layer after compaction shall make min. 50mm thickness course/layer of 40mm nominal size, including dressing, rolling & compaction complete as per specs., GELO and instructions of XEN/CWD.
100
-
-
ROADS & PCC PAVEMENT
Supply of labour, material and construction of cement concrete roads and walkways/shoulders from NH/SH/etc. to Switch yard/Switch house building as per GELO/CLO as per sectional detail drawing no. HCD/SK-181 R1 and technical specification.
i) 6.0M wide
30
-
-
ii) 3.66M wide
120
-
-
iii) PCC in front and rear of parking area of SH Building as per tech. specification and drawing HCD/SK-172.
150
-
-
ROAD CULVERTS
Design, Engineering and const. of Pipe culvert(s) at suitable locations under the approach road (from main PWD/ HUDA/Municipal/Village road to the sub-station entry point) including, cost of labour, material complete in all respects as per I.R.C. Standards.
2
-
-
BOUNDARY WALL
Supply of labour, material and construction of front, C & U/C boundary walls including main gate foundations as per GELO/CLO, technical specifications. & HVPNL drg. HCD/TS-1176 R1 including excavation backfilling, lean & DPC complete in all respect.
i) 6 ft. high with GI barbed wire on angles at top.
170
-
-
ii) 4½ ft. high front wall with grill at top.
25
-
-
iii) 4½ ft. side wall with GI barbed wire
65
-
-
iv) Supply of labour, T&P, material and construction of front, side & U/C boundary walls including main gate(s) (brickwork below DPC level) as per GELO/CLO, tech. spec. & HVPNL drawings complete in all respects.
280
-
-
U/C FENCING & GATES
Providing & fixing chain link fencing including foundations, GI angle iron posts and gate(s) complete as per electrical layout & tech. spec. & as per drawing attached.
25
-
-
DRAINAGE–CUM-RAIN HARVESTING SYSTEM
Supply of labour, material for construction of recharge structure with bore well as per HVPN drawings & specs. complete in all respect. The location of recharge structure shall preferably be located on corner(s) of the substation and shall be got decided from the concerned XEN/Civil Works Division on the basis of surroundings of the substation(s). In case ground water table is less than 8m from FGL, rain harvesting well shall not be constructed (the drainage system with sump pit is to be constructed as per item mentioned below).
1
-
-
The successful bidder shall evolve design & drawing for drains, manholes with RCC covers and settlement tank including preparation of drainage layout drawing for disposal of rain water from building’s roof top & switch yard (s/stn.) area into respective bore well(s) in such a way that there shall be no ponding of water on the roof and switch yard (s/stn.). The layout so developed shall be got approved from the employer. The location of sump-pit-cum-pump chamber shall preferably be located on corner(s) of the s/stn. and shall be got decided from the concerned XEN/Civil Works Division on the basis of surroundings of the substation(s). The successful bidder will also supply labour and material for construction of sump-pit-cum-pump chamber as per HVPNL drgs. & provide one no. non clog pump(s) of 5HP of reputed make capacity with main switch, starter, volt meter, Amp. Mtr. etc. (for each sump pit) for disposal of excess water to outfall point. Any other item(s) not mentioned herein but is/are required for completion of works shall be done by the successful bidder without any extra cost to the employer.
i) Drain Section-1
100
-
-
ii) Drain Section-2
60
-
-
iii) Drain Section-3
40
-
-
iv) Road Crossing
1
-
-
v) Trench Crossing
1
-
-
vi) Sump Pit Cum Pump Chamber
1
-
-
CONTROL ROOM BUILDING
Design engineering, supply of labour, material, T&P and construction of control room building complete in all respect as per tech. specs. including exterior weather proof paint, interior emulsion, all internal services like water supply including supply & providing of 5000ltr. capacity double layer Sintex/Diplast PVC tank, Sewerage system, electrification including wiring, modular switches, maximum 20W 4ft. long LED tubes with fittings minimum 1960 lumens, ceiling/exhaust fans, Finishing, Plinth protection, closed drain around the building (i.e RCC Pipe), Indoor trenches, Soakage pit near the switch house building, connection of sewerage system to Soakage pit/Sewerage system of local authorities (as applicable), connection to main water supply system of local authority, bore (Tubewell) (as applicable) etc. & any other item not mentioned herein but required for completion of works.
3875
-
-
RCC M-20 inclusive of labour, material, shuttering, Steel reinforcement etc. complete in all respects to compensate excess quantity required to be executed due to difference in existing ground level and the formation level to be fixed after contouring or difference on account of revised drg issued at the time of construction and the tender drg.
10
-
-
Dismantling of Existing control room building, boundary wall, rcc foundations etc
Dismantling including foundations of following structure. The material whatsoever shall be the property of the successful bidder. The dismantled material shall not be allowed for reuse at any of the sub-stations; however, HVPNL may allow use of bricks for brick ballast purpose only. Dismantling of Existing control room building, boundary wall, rcc foundations and other structures
Note:- This item is dismantlement item, hence recoverable amount against the dismantlement of Existing control room building, boundary wall, rcc foundations etc. has been freezed for this price bid.
1
-665537
-