Haryana Power Generation Corporation Limited Tender
If you want to inquire about any e-tender the Haryana government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Haryana tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Haryana etender you're looking for. Read further to learn how to search and bid for etender Haryana.
Costs
EMD
₹ 1,27,500Document Cost
₹ 1,180Tender Fee
₹ 1,180
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_HBC_389376_1Bid Award Id
ViewTender No
20246D3DB42C 20AF 4E54 85E8 F5151ACD6767712PGCTender Authority
Haryana Power Generation Corporation Limited ViewPurchaser Address
-Website
http://www.hpgcl.org.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
Providing New Insulation with refixing of old cladding in Boiler Furnace Wind Box and APH Area. Insulation (Type: Rock Wool Felt, Thickness-200mm) Netting: GI, Cladding (Old Corrugated sheet)
150
-
-
Providing New Insulation with New Cladding in Boiler Furnace Wind Box and APH Area. Insulation (Type: Rock Wool Felt, Thickness-190 mm) Netting: GI, Cladding (Corrugated Al. Sheet, Thickness: 1.2 mm)
100
-
-
Providing New Insulation with refixing of old cladding in Drum DownComers pipers 24 to 80 m elevation, ring header including man holes of ring header at 9 meter elevation, main steam to PRDS line, main steam line and ID fan area. Insulation (Type: Rock Wool Felt, Thickness-150 mm) Netting: GI, Cladding (Old plain sheet)
50
-
-
Providing New Insulation with new cladding in Drum Down-Comers pipers 24 to 80 m elevation, ring header including man holes of ring header at 9 meter elevation, main steam to PRDS line, main steam line and ID fan area. Insulation (Type: Rock Wool Felt, Thickness-150 mm) Netting: GI, Cladding (Al. Sheet, Thickness: 0.56 mm)
50
-
-
Providing New Insulation with refixing of old Cladding in Bottom of Zpanel at 9 meter elevation and ESP Hopper area. Insulation (Type: Rock Wool Felt, Thickness-150 mm) Netting: GI, Cladding (Old Corrugated sheet)
100
-
-
Providing New Insulation with new cladding in Bottom of Z-panel at 9 meter elevation and ESP Hopper area. Insulation (Type: Rock Wool Felt, Thickness-190 mm) Netting: GI, Cladding (Corrugated Al. Sheet, Thickness: 1.2 mm)
100
-
-
Providing New Insulation with new cladding in Fuel Oil Lines/after Vent/Drain line valve i.e. Drum Vent, CBD Drain (Left and Right) and Vent, LTSH Drain line and Ring Header Drain Valve area. Insulation (Type: Rock Wool Felt, Thickness-50 mm) Netting: GI, Cladding (Al. Sheet, Thickness: 0.56 mm)
50
-
-
Filling Inside Cover Plates. Providing only new Insulation in Burner Panel area. Insulation (Type: Rock Wool Felt, Thickness-120 mm) Netting: GI.
500
-
-
Providing New Insulation with New Cladding in Vent/Drain i.e. Drum Vent, CBD Drain (Left and Right), SH Spray Line and Vent, LTSH Drain line and Ring Header Drain Valve area. Insulation (Type: Rock Wool Felt, Thickness-100 mm) Netting: GI. Cladding (Al. Sheet, Thickness: 0.56 mm)
100
-
-
Providing New Insulation with New Cladding in Primary and secondary Hot Air Duct at, 6 M to 30 M elevation area. Insulation (Type: Rock Wool Felt, Thickness-170 mm) Netting: GI. Cladding (Corrugated Al. Sheet Thickness: 1.2 mm)
450
-
-
Providing New Insulation with refixing of old cladding in Primary and secondary Hot Air Duct at , 6 M to 30 M elevation area. Insulation (Type: Rock Wool Felt, Thickness-170 mm) Netting: GI. Cladding (Old Corrugated Sheet)
100
-
-
Providing New Insulation with New Cladding in Flue Gas Duct area. Insulation (Type: Rock Wool Felt, Thickness-40 mm) Netting: GI. Cladding (Corrugated Al. Sheet Thickness-1.2 mm )
500
-
-
Providing New Insulation with refixing of old cladding in Flue Gas Duct area. Insulation (Type: Rock Wool Felt, Thickness-40 mm) Netting: GI. Cladding (Old Corrugated Sheet)
600
-
-
Providing New Cladding sheet on existing insulation in any area boiler/ hot duct/cold duct/wind box/ ESP hopper /ESP duct. Cladding (Corrugated Sheet Al Thickness: 1.2 mm)
100
-
-
Providing New Cladding sheet on existing insulation in Any area line of vent/drain/main steam line/ bottom Ring Header line. Cladding (Al. Sheet Thickness: 0.56 mm)
50
-
-
Refixing of Old cladding Sheet in any of the area pertaining to Boiler and its auxiliaries. Cladding (Old Corrugated/ plain sheet)
200
-
-
Thermal Insulation works pertaining to Turbine and its auxiliaries
-
-
-
Alumina silicate fibre block insulation with bottom plaster, Thickness: 70x3mm, Area: HIP turbine (Cylinder cover) Main Turbine Site.
40
-
-
Alumina silicate fibre block type insulation with bottom plaster, Thickness: 60x3mm, Area: HIP turbine (Cylinder base) Main Turbine Site
40
-
-
Alumina silicate fibre type insulation , Thickness: 80x2mm, Area: steam inlet sleeve, HIP turbine Main Turbine Site
12
-
-
Alumina silicate fibre type, Thickness: 40x2mm, Area: Dum Ring balance piping, HIP turbine Main Turbine Site.
20
-
-
Alumina silicate fibre block type insulation with bottom plaster, Thickness: 80x2mm, Area: MSV body Main Turbine Site
38
-
-
Alumina silicate fibre pipe type insulation with bottom plaster, Thickness: F340x70 and F480x50, Area: GV piping and flanges Main Turbine Site
60
-
-
Alumina silicate fibre block type insulation with bottom plaster, Thickness: 80x2mm, Area: RSV and RIV body and cover Main Turbine Site
25
-
-
Alumina silicate fibre pipe type insulation with bottom plaster, Thickness: 80x2mm, Area: RSV piping and flanges Main Turbine Site
45
-
-
Alumina silicate fibre block type insulation, Thickness: 60 +40mm, Area: cross-over piping and flanges Main Turbine Site
100
-
-
Alumina silicate Felt, Insulation Thickness-160 mm for TDBFP in r/o TGM-I, RGTPP
40
-
-
Alumina silicate Felt ,Thickness 120 mm in r/o TGM-I, RGTPP
30
-
-
Alumina silicate Felt ,Thickness 100 mm in r/o TGM-I, RGTPP
40
-
-
Alumina silicate Felt ,Thickness 50 mm in r/o TGM-I, RGTPP
30
-
-
Rock Wool felt ,Insulation Thickness 160 mm in r/o TGM-I, RGTPP
40
-
-
Rock Wool felt ,Insulation Thickness120 mm in r/o TGM-I, RGTPP
40
-
-
Rock Wool felt,Insulation Thickness 100 mm in r/o TGM-I, RGTPP
120
-
-
Rock Wool felt ,Insulation Thickness 80 mm in r/o TGM-I, RGTPP
100
-
-
Rock Wool felt , Insulation Thickness 50 mm in r/o TGM-I, RGTPP
100
-
-
Cladding in r/o TGM-I, RGTPP
150
-
-
Evaluation Notes How It Works ?
Potential Partner