Government Of Haryana Tender
If you want to inquire about any e-tender the Haryana government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Haryana tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Haryana etender you're looking for. Read further to learn how to search and bid for etender Haryana.
Costs
EMD
₹ 13,200Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2019_HRY_103717_1Bid Award Id
ViewTender No
PWD/Electrical/162361-71Tender Authority
Government Of Haryana ViewPurchaser Address
-Website
http://https://haryana.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
10.41 Cement concrete 1:2:4 with stone aggregate 20 mm nominal size in foundation and plinth.
1.5
-
-
... More
11.2 First class brick work laid in cement sand mortar 1:6 in foundation and plinth.
6
-
-
... More
15.6 12 mm thick cement plaster 1:5.
30
-
-
... More
31.22 (Q) Earthing.
31.22(iii) Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) complete as equired.
4
-
-
... More
31.22(v) Extra for charcoal or coke and salt for G.I. Plate or copper plate earth electrode.
4
-
-
... More
31.22(xi) Pdg. and fixing 25 mm x 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode as required .
40
-
-
... More
31.26 Supply and erection of under ground cable ,loose in existing pipe or trenches complete with necessary connections . 31.26 (xxv) Ard. 25 Sq. mm 3.5 Core Cable .
50
-
-
... More
31.67 Supply and erection of mark double walled corrugated (DWC) HDPE pipe laid 1Mtr. Below ground level including diging and refilling of earth including cost of sutiable size socket/cuppler for HDPE pipe including the cost of labour and material required to complete the job in all respect upto the entire satisfaction of Engineer-in-Charge of the work. (i) HDPE pipe 63/50 mm outer dia/inner dia.
40
-
-
... More
M.R. items
NS-1
Supply, erection, testing, commissioning and installation of 62.5 KVA 3 Phase 415 Volts electric start, factory assembled, Diesel Generating Set as per I.S 4722 and or the latest I.S. specification along with instrument panel 1500 RPM complete with fuel tank and batteris and AMF panel and other standard accessories as supplied by the manufacturers complete in all respect upto the entire satisfaction of Engineer-in-Charge of the work.
(A) ENGINE Engine should be of 1500 RPM, Vertical 4 stroke 50 cycles, cold start, compressor ignition diesel engine, complete with 12 Volts electric starting arrangement capable of running 62.5 KVA continuous A.C. Power under NTP condition suitable for 10% over load for one Hr. in 12 Hrs. running, consisting all standard accessories, starting voltage 24 Volt as supplied by them manufacturers but at least including following :- Make:- Greaves Cotton / Cummins / Ruston / Kirloskar, Self Start dynamo, Flexible coupling or with close coupling with guard suitable for coupling 62.5 KVA alternator. 1 No. RPM meter. 1 No. hours meter. 1 No. standard fuel tank of capacity suitable for minimum 12 Hours run at full load with level indicator floor mounted with hoses. 1 No. Standard extra fuel filter. 1 No. Governor. 1 No. Residential type silencer with exhaust piping, insulated from inside with glass wool to suppress noise and high temperature gasket at all silencer inside joints. 1 No. fuel pump. Radiator water cooled Fly wheel to suit flexible coupling. 1 No. air cleaner assembly. Lubricant oil pump. Lubricant oil filter. Lubricant oil cooler. Mico Bosch fuel injection system. Set of standard tools 3 Nos. 3 Nos. spanners, 1 No. screw driver, 1 No. standard plier & 1 No. nose plier. (B) ENGINE INSTRUMENT PANEL 1 No. battery charger ammeter. 1 No. lubricating oil temperature gauge meter. Cut out. 12 Volts electric starting equipment with :- Starting switch with key. Starting motor 12 Volts. Battery charging dynmo meter. Safety control ( Trip ) for low lubricant oil & high water tempreature. Stop Button. Lubricant oil pressure gauge. Coolent temperature gauge. ALTERNTOR 62.5 KVA, 3 Phase, 415 Volts, 50 C/S 0.8 Power factor, 1500 RPM Self excited, self regulated, screen protected alternator brush less manufactured as per I.S 4722 and or the latest I.S specification with all standard accessories as supplied by manufacturer. Make: Crompton / Stamford / Jyoti / NGEF/ Kirloskar ARRANGEMENT Engine and alternator, as above should be fixed on suitable base frame of sturdy design made of channels with necessary reinforcement to take the load of engine and alternator and provided with 8 Nos. dunlop make antivibrating pads. AMF PANEL The AMF Panel shall be totally enclosed dead front pattern, mounted within sound proof enclosure, as per standard specification of manufacturer duly painted with synthatic paint. The panel shall be complete with all internal wiring, Cable glands, removeable side panel for easy access and locking arrangement to prevant tempering and having by pass arrangement for isolating the panel from main supply for carrying out maintenance / repair to control panel suitable automatic transfer switch suitablly rated for continous 3 Phase supply duly double throw mechanically held and electrically operated having inter locking arrangement to ensure only one position. IP rating of acoustic panel IP-54. NORMAL or "EMERGENCY" main contract shall be protected by arching contracts and operating transfer time shall not exceed fifteen seconds. All replacable contractors, coils, spring control machanisum shall be suitable for front operation / maintenance with out dio assembly / disconnecting of power source. The panel shall be provided with copper bus bars of suitable capacity duly dinned and PVC insulated. The pannel shall be suitable for following operation. OPERATION The normal or mains source shall be constantly monitored by a main voltage monitor. When main voltage fails or drops below 80% adjustable and selectable of the rated voltage or incase of two phase / single phase supply, the automatic signal to the control system shall give a starting signal to generating set. As soon as thediesel enerating set reaches its operating speed and attains its operating voltage the load shall be transferred on the generating set. Upon the return of the normal source voltage of 90% of rated voltage for a minute the switch shall retransfer the load to the normal source. The automatic control system shall reset it-self and start the engine generating set upon the failure of normal source. In the event of failure of the diesel generating set to start due to any fault, contractors / switch shall get energised without any time delay on the restoration of the normal source. If the D.G. Set fails to start and does not reach its operating speed in 25 second in three attempts the set shall automatically be disconnected and locked in isolated position. A set switch to stimulate a normal source failure shall be provided for routine testing of the transfer switch panel and D.G. set. Automatic transfer switch panel shall be provided with the following protection gear, instruments and accessories. Neutral isolation by overlapping contacts. Adjustable time delay relay for transfer and retransfer of loads of make TEKNIKA / L&T / Siemen's and Telemechanik & PIC. Engine start / stop control relays three attempt start facility & failure to start lockout of make L&T / SIEMEN's / TELEMECHANICK / TEKNIKA / PIC. Alternator contractor 3 Pole of suitable size with over load relay, short circuit and 3 Nos. HRC fuses with base for protection relay of make L&T / SIEMEN's TELEMECHANIK / TEKNIKA & HRC fuses of make L&T / GE. Auto / Manual / Test selector switches AE / IMP / VISHAL. Main contractors, L&T / SIEMEN's, GE make. One set of main supply voltage monitor to identify low voltage / complete failure and initiates necessary signal for operation of automatic control gear. Push buttons start / stop / reset / test. Selector switch for engine control On / Off ( AE / IMP / VISHAL make ). 1 No. 96 Sqmm flush mounted volt meter ( AE / IMP / VISHAL make ). 1 No. voltmeter selector switch off / mains / load / Alt.
3 Nos. 96 Sqmm flush mounted ammeter ( AE / IMP / VISHAL make ). 1 No. 96 Sqmm flush mounted frequency meter ( AE / IMP / VISHAL make ).
1 No. K.W. meter ( AE / IMP make ). 1 No. automatic cutt off device like over load relay for tripping off the D.G. Set in case of over load. 1 No. suitable size of MCCB. ON / OFF SWITCH Instrument fuses. 1 No. Voltmeter D.C. 30 Volts. 1 No. Amp. meter D.C. 30 Volts. 3 Nos. CTS of specified ratio and 15 VA burden of A.E. make. 1 No. Signal Lamp indicating "Load on D.G. Set" 1 No. signal Lamp indicating Load on mains' Over speed relay to trip the Generator on speed higher than the specified speed. 1 No. low fuel indicator L.E.D. type. 1 No. signal lamp ( Set fails to start ). 1 No. audio visual alarm and annunciation for engine safety & to indicate abnormalities in the stand by system like low fuel level, high oil temperature, high water temperature.
Earthing with copper bus bar of Suitable rating duly tinned through out the length of panel at its bottom. BATTERY AND LEADS 2 Nos. SMF / Exide / Amron make 12 Volts 25 Plate 180 AH capacity battery, with acid level indicating floater, battery stand, call and lead to take off connection. Suitable size of armourd cable for (D.G. Set 62.5 KVA) of length required for the connection and suitable cable glands for making connection from alternator to control panel. The control panel will be complete with internal wiring, necessary fuses, cable and other accessories and cost external control wiring. SOUND PROOF ENCLOSURE ( CANOPY ) The canopy of generator shall be sound proof ( Accoustic ) enclosure suitable for 62.5 KVA diesel generating set complete in all respect having following specification / features :- Fabricated as per standard specification of manufactures Stuffing done with Rock wool of 96 KG / CUM density and 100 mm thickness. Rock wool supported with Tissue paper and perforated sheets of 1.6 mm thickness having 0.5 mm holes. Residential type silencer provided to lower the noise of exhaust outlet, noise level 1.00 Mtr. 73.5 db. Canopy treated for anti rust with duco paint with primer and colour compound. Fresh air inflor and proper ventilation. Modular in construction and provided with lockable doors. The generating set with AMF panel and sound proof canopy shall be complete in all respect.
1
-
-
Evaluation Notes How It Works ?