If you want to inquire about any e-tender the Haryana government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Haryana tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Haryana etender you're looking for. Read further to learn how to search and bid for etender Haryana.
Costs
EMD
₹ 19,300Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2019_HRY_93827_1Bid Award Id
ViewTender No
PWD/Elect-KNL/Elect-HSR/16258Tender Authority
Government Of Haryana ViewPurchaser Address
-Website
http://https://haryana.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
v) Extra for charcoal or coke and salt for G.I. Plate or copper plate earth electrode.
4
-
-
... More
xi) Pdg. and fixing 25 mm x 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode as required.
50
-
-
... More
xii) Pdg. and laying earth connections from earth electrode with 4.00 mm dia G.I. wire in 15 mm dia G.I. pipe from earth electrode as required.
40
-
-
... More
xvi) Pdg. and fixing 4.00 mm dia G.I.wire on surface or in recess for loop earthing as required.
40
-
-
... More
Under Ground Cables: Supply and erection of underground cable 1 meter below ground level covered with sand and bricks including necessary connections, digging and refilling of trenches. (HSR 31.25). xxx) 120 Sq. mm 3.5 Core Ard Cable .
80
-
-
... More
Supply and erection of underground cable, loose in existing pipe or trenches complete with necessary connections. (HSR 31.26). xxx) 120 Sq. mm 3.5 Core Ard Cable .
30
-
-
... More
Supply and erection of suitable compression type brass cable glands for underground Cable. (HSR 31.28). v) 120 Sqmm to 185 Sqmm Cable 3 to 3.5 Core
4
-
-
... More
Cement Concrete Platform:-Earth work in excavation in fundations, trenches, etc in all kinds of soils, not exceeding 2 Meter depth including dressing of bottom and sides of trenches, stacking the excavated soil, clear from the edge of excavation and subsequent filling around masonry in 15 cm layers with compaction, including disposal of all surplus soil as directed with a lead of 30 metes. (HSR 6.6).
4.95
-
-
... More
Cement lime concrete 1:8:16 with brick blast 40mm nominal size in foundation and plinth. (HSR 10.26).
1.06
-
-
... More
Cement concrete 1:2:4 with slone aggregate 20mm nominal size in foundation and plinth. (HSR 10.41)
1.21
-
-
... More
First Class bricks work laid in cement sand mortar 1:6 in foundation and plinth. (HSR 11.2).
2.26
-
-
... More
11:43 cm thick bricks wall laid in cement sand mortar 1:4 without reinforcement, in foundation and plinth. (HSR 11.47).
10.24
-
-
... More
Conglomerate floor 50 mm thick CC topping 1:2:4 (HSR 14.10).
3.06
-
-
... More
12 mm thick cement plaster 1:6 (HSR 15.7)
22.96
-
-
... More
Shed for DG Set Wrought iron and mild steel (using angles, flates, square bars, tee and chanels) ladders, grills, gratting frames, window guards, iorn doors, open able or fixed stair case or perrapet or any other type of railing, gates and tree guards etc. including cost of screws and welding rods or bolts and nuts complete fixed in position. (HSR 18.12). Chanel size (40 x 40 x 6) = 10 M X 3.5 kg Per M = 245 Kg or 2.45 QTL. Wiremess Jalli = 100 kG = 1 QTL Net & Bolts = 10 KG = 0.10 QTL Total = 2.45 + 1 + 0.10 = 3.55 QTL
3.55
-
-
... More
Non Schedule Items Supply, installation, erection commissioning and testing of 100 KVA 3 phase 415 volts water cooled electric start, factory assembled, Diesel generating set as per IS : 10002/1960 and BS 649 or the latest alongwith instrument panel and other standard accessories as supplied by the manufacturers but at least having following items /requirement/ specifications. (As per approved make) 1 No standard extra fuel filter. 1 No. Governor. 1 No. residential type silencer with exhaust piping having insulated from outside with glass wool to suppress noise and high temperature gasket at all silencer joints. 1 No. Fuel pump. Radiator. Fly wheel to suit flexible coupling 1 No. air cleaner assembly. Lubricant oil pump. Lubricant oil filter Lubricant oil cooler Mico Bosch fuel injection system. Set of standard tools. ENGINE INSTRUMENT PANEL 1 No. battery charging ammeter. 1 No. lubricating oil temperature guate meter. Cut out. 12 volts electric starting equipment with:- Starting switch with key. Starting motor 12 volts. Battery charging dyano meter. Safety control (Trip) for low lubricant oil & high water temperature. Stop button. Lubricant oil pressure gauge. Coolant temp. gauge. ALTERNATOR. 100 KVA , 3 phase, 415 volts, 50 C/S , 0. 8 power factor 1500 RPM self excited, self regulated, screen protected alternator manufactured, as per IS 13364 and BS 2613/1970 or the latest with all standard accessories as supplied by manufacturer. ARRANGEMENT Engine and alternator, as above should be fixed on suitable base frame of standard design made of channels with necessary reinforcement to take the load of engine and alternator and provided 8 Nos. Dunlop make ant vibrating pads. AMF PANEL. The automatic main failure panel shall be totally enclosed dead front pattern free floor standing type fabricated out of 14 gauge sheet steel duly painted in light grey shade of synthetic enameled paint. The panel shall be complete with all internal wiring, cable glands, removaeable side panel for easy access and locking arrangement to prevent tempering and having by pass arrangement for isolating the panel from main supply for carrying out maintenance/ repair to control panel. Suitable automatic transfer switch suitably rated for continuous 3 phase supply duly double tarcw, mechanically help and electrically operated having inter locking arrangement to ensure only one position "NORMAL" or "EMERGENCY" Main contact shall be protected by arching contacts and operating transfer time shall not exceed fifteen seconds. All replaceable contractors soils, spring control mechanism shall be suitable for front operation/ maintenance without dia assembly/ disconnecting of power source. The panel shall be provided with copper bus bars of suitable capacity duly tinned and PVC insulated. The panel shall be suitable for following OPERATION The normal or mains surce shall be constantly monitored by a main voltage monitor. When main voltage fails or drops below 80% adjustable and selectable of the rated voltage or in case of two phase/ single phase supply, the automatic control system shall give a starting single to the generator set. As soon as the diesel generator set reaches its operating speed and attains its operating voltage the load shall be automatically transferred on the generator set. Upon the return of the normal source voltage of 90% of rated voltage for a minute, the switch shall retransfer the load to the normal source. The automatic control system shall reset itself and start the engine generator set upon the failure of the normal source. In the event of failure of the diesel generator set due to faulty starting the normal contactors/ switch shall get energized without any time delay on the restoration of the normal source. If the diesel set fails to start and does not reach its operating speed in 25 second in three attempts. The set shall automatically be disconnected and locked in isolated position. A test switch to stimulate a normal source failure shall be provided for routine testing of the transfer switch, panel and D.G. Set. Automatic transfer switch panel shall be provided with the following protection gear, instruments and accessions. Neutral isolation by over lapping contacts. Adjustable time delay relay for transfer and retransfer of loads of make TEKNIKA/ L&T / Siemen's and Telemechanik & PIC Engine start/stop control relays three attempt start facility & failure to start lockout of make L&T SIEMEN'S / TELEMECHANIK/ TEKNIKA & HRC Fuses of make L&T / G.E. Altimeter contractor 3 pole of suitable size with over load relay and 3 Nos. HRC fuses with base for protection. Relay of make L&T / SIEMEN's / TELEMECHANIK/ TEKNIKA & HRC Fuses of make L&T / G.E. Auto/ Manual/ Test selector switches AE/IMP/ VISHAL. One set of main supply voltage monitor to identify low voltage/ complete failure and initiates necessary signal for operation of automatic control gear. Push buttons, start/stop/ reset/ Test Selector switch for engine control on/ off (AE/IMP/VISHAL Make.) 1 No. 96 sq mm. Digital volt meter (AE/IMP/ VISHAL Make.) 1 No. voltmeter selection switch off/mains/load/Alt. 3 Nos. 96 sq.mm Digital ammeter with selector switch (AE/IMP/VISHAL Make.) 1 No. 96 Sq. mm Digital frequency meter (AE/IMP/VISHAL Make.) 1 No. K.W.H. Meter with protection fuses (AE/IMP/HAVEL's/BHEL Make.) 1 No. K.W. meter(AE/IMP make) 1 No. Automatic cut off device against overload in addition to MCCB. 1 No. 200 Amp. MCCB ON/OFF SWITCH. Instrument fuses. 1 No. voltmeter D.C. 30 VOLTS. 1 No. Ammeter D.C. 30 VOLTS. 3 Nos. CTS of specified ratio and 15 VA burden of A.E. Make. 1 No. signal lamp load on set' 1 No signal lamp load on main 1 No signal lamp set fails to start. 1 No. audio visual alarm and annunciation for engine safety & the indicate abnormalities in the stand by system like low fuel level, high oil temperature low oil level, high water temperature. Earthing copper bus bar of size 25 mm X 5 mm duly tinned through out the length of panel its bottom. BATTERY AND LEADS 1 No. Exide make 12 volts with required leads & cells each 2 volts to have 88 AH capacity at one hour rate discharge with acid level indicating floater, battery stand, inter cells connectors with lead to take-off connections cell insulators and stand insulators, Hydrometer, theremo meter with specific gravity connection scale cell testing volt-meter and set of tools consisting rupper syringe acid resistance funnel & acid resisting tube of 2 volts capacity. The battery should be duly charged and acid filled. Battery boost charger suitable for single phase 230 volts, 50 cycles comprising AC & DC " ON "OFF" switch with HRC fuses indicating lamps, ballast double wound- (copper) main transformer, silicon rectifier stack, mocing coil Ammeter, moving coil voltmeter with selector switch, AC & DC contactors. All the components of battery charger and battery with insulated they shall be adequately rated and housed in a well ventilate-ted sheet cubical of 14 gauge with input & output terminals and suitable cable gland. 120 sq. mm/ 3. 1/2 core armoured cable of to control panel. The control panel will be complete with internal wiring necessary fuses, cable and other accessories cost of external control wiring. Length required for the connections and suitable glands for making connection from altenator to control panel. The control panel will be complete with internal wiring necessary fuses, cable and other accessories cost of external control wiring. SOUND PROOF ENCLOSURE ( CANOPY). The canopy of generator shall be sound proof (Accoustic) enclosure suitable for 100 KVA diesel generating set complete in all respect having following specifications/ features:- ( As per Specification attd.) Fabricated out of 16 SWG CRC sheets. Stuffing done with Rock wool of 96-Kg/CUM density and 100 MM thickness. Rock wool supported with Tissue paper and perforated sheets of 6 mm thickness having 5 mm holes Residential type silencer provided to lower the noise of exhaust outlet. Canopy treated with primer and Anti Rust compound & duly painted with duco paint in desired colour. Fresh air inflow and proper ventilation. Modular in constraction and provided with lockable doors. The generating set with AMF panel and sound proof canopy shall be complete in all respect upto the entire satisfaction of Engineer-in-Charge of work.
1
-
-