Military Engineer Services Tender
... More
The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Spl Repair To Central Ac Plant And Repair Replacement Of Ber Cooling Appliances At Af Stn Vadsar in Gandhinagar, Gujarat, with an estimated contract value of Rs. 42,93,000. The bid opening date for this tender is 29-10-2026 and the last date for bid submission is 19-11-2026. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.
Military Engineer Services - MES Tender - Gujarat Tender
Opening Date29 Oct 2026
Closing Soon19 Nov 2026
Tender Amount₹ 42,93,000
Costs
EMD
₹ 85,860Document Cost
₹ 500Tender Fee
Refer Documents
Description
Spl Repair To Central Ac Plant And Repair Replacement Of Ber Cooling Appliances At Af Stn Vadsar
Contact
Tender Id
2026_MES_796257_1Tender No
8517/26-27/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
... More
Supply and fixing in replacement of Low pressure transducer switch (LP Switch) as per existing make & model complete all as specified and directed by Engr-in-Charge.
2
-
-
... More
Supply and fixing in replacement of High pressure transducer switch (HP Switch) as per existing make & model complete all as specified and directed by Engr-in-Charge.
2
-
-
... More
Material & Labour for charging of refrigerant gas R-407c including opening and re-assembling of connected acessories of central AC plant of capacity 85 TR, complete all as specified and directed by Engr-in-Charge.
120
-
-
... More
Supply and fixing in replacement of cooling tower finges as per existing make & model complete all as specified and directed by Engr-in-Charge.
300
-
-
... More
Material & Labour for descaling of complete condenser units for central AC plants (AC Plant Make- voltas) of capacity 85 TR by means of adding descaling chemical solution (HCL) or equivalent as per requirements and running the plant pump continuously till all the scale of pipes/shell are removed including removing side covers of condenser and cleaning the water tubes by means of nylon brushes till the scaling is removed and re fixing of covers including replacement of neoprene rubber gasket and refixing pipe connection etc. complete all as specified and directed by Engr-in-Charge.
Note:- Descaling shall be carried out in supervision of Engineer from authorised agency of OEM complete all as specified and directed by Engr-in-Charge.
3
-
-
... More
Supply, fabricate and erect PGI Air duct made out of 22 gauge PGI sheet including necessary support, jointing with suitable size MS Angle/flat iron and 3mm thick rubber packing, drilling and necessary GI nuts, bolts & washers all as specified and directed, from ground level to upto 50ft height complete all as specified and directed by Engr-in-Charge.
70
-
-
... More
Supply, fabricate and erect PGI Air duct made out of 24 gauge(Duct) PGI sheet including necessary support, jointing with suitable size MS Angle/flat iron and 3mm thick rubber packing, drilling and necessary GI nuts, bolts & washers all as specified and directed, from ground level to upto 50ft height complete all as specified and directed by Engr-in-Charge.
70
-
-
... More
Supply, fabricated and erect PGI Air duct made out of 20 gauge(For AHU ) PGI sheet including necessary support, jointing with suitable size MS Angle/flat iron and 3mm thick rubber packing, drilling and necessary GI nuts, bolts & washers all as specified and directed, from ground level to upto 50ft height complete all as specified and directed by Engr-in-Charge.
75
-
-
... More
Material & Labour for insulation to supply air duct with 25 mm thick rockwool/mineral wool slab covered with chicken wiremesh tissue paper and 24/26gauge aluminium sheet cladding work including taking down old unsv insulation complete all as specified and directed by Engr-in-Charge.
40
-
-
... More
Material & Labour for insulation to supply air duct for OT AHUS with 20 mm thick armafex insulation covered with armaflex insulation using SR 505 fevicol solution complete all as specified and directed by Engr-in-Charge.
40
-
-
... More
Material & Labour for insulation to 3x85 TR chillar unit with 25 mm thick armafex insulation covered with armaflex insulation using SR 505 fevicol solution complete all as specified and directed by Engr-in-Charge.
24
-
-
... More
Supply & Fixing in replacement of aluminium powder coated supply air diffuser minimum 22 gauge with volume control damper including taking down old unsv diffuser complete all as specified and directed by Engr-in-Charge.
4
-
-
... More
Supply & Fixing in replacement of aluminium powder coated return air linear diffuser minium 22 gauge complete all as specified and directed by Engr-in-Charge.
4
-
-
... More
Supply & Fixing in replacement butter fly valve of dia 100mm suitable for condensing /chiller water line with ISI marked including jointing with proper gasket, nuts, bolts & washer complete all as specified and directed by Engr-in-Charge.
2
-
-
... More
Supply & Fixing in replacement butter fly valve of dia 150 mm suitable for condensing / chiller water line with ISI marked including jointing with proper gasket, nuts, bolts & washer complete all as specified and directed by Engr-in-Charge.
4
-
-
... More
Supply & Fixing in replacement NRV of dia 150 mm suitable for condensing /chiller water line with ISI marked including jointing with proper gasket, nuts, bolts & washer complete all as specified and directed by Engr-in-Charge.
4
-
-
... More
S & F of water pressure gauge 4" dial type with cock 0-14 Kg/Sqmtr complete all as specified and directed by Engr-in-Charge.
4
-
-
... More
S & F of refrigerant pressure gauge 4" dial type with cock 30 to 150 PSI complete all as specified and directed by Engr-in-Charge.
2
-
-
... More
S & F of refrigerant Temp. gauge 4" dial type cock 0C to 50 Ccomplete all as specified and directed by Engr-in-Charge.
2
-
-
... More
Servicing and de-scaling of FRP cooling tower induced draft counter flow of dimension 2855x3100x3850mm of Central AC plants (AC Plant Make - voltas) of capacity 85 TR complete with chemical solution as recommended by manufacturer with rods and wire brushes complete all as specified and directed by Engr-in-Charge.
1
-
-
... More
Supply, install, testing and commissioning of high wall split type air conditioner unit indoor/outdoor complete with cordless remote control unit and within built air ioniser and plasma filter for better indoor quality and EER 5.2 of cap 1.5 TR 5 star rating including stand and PVC drain pipe of Aprox 10 mtr long complete incl taking down old insv AC complete all as specified and directed by Engr-in-Charge.
14
-
-
... More
Supply, install, testing and commissioning of high wall split type air conditioner unit indoor/outdoor complete with cordless remote control unit and within built air ioniser and plasma filter for better indoor quality and EER 5.2 of cap 2.0 TR 5 star rating including stand and PVC drain pipe of Aprox 10 mtr long complete incl taking down old insv AC complete all as specified and directed by Engr-in-Charge.
8
-
-
... More
M & L for concealed sub main wiring complete with PVC insulated FRLSH cable of 2 run of single core 04 Sqmm 1100 volts grade with unseathead multistranded copper coductor (for phase and neutral) drawn through and including PVC med grade conduit with accessories and 1 run of 4 sqmm 1100 volts grade with unseathead multistranded FRLSH copper coductor (for earthing) complete all as specified and directed by Engr-in-Charge. Note :- (a) two run of 4 Sqmm multistranded FRLSH copper conductor and one run of 4 Sqmm multistranded FRLSH copper conductor and one run of 20 mm dia med grade PVC conduit shall be measured adn paid as one run length. Colour coding for wiring shall be followed as per direction of Engr-in-Charge.
(b) The rate quoted by contractor shall be included for chess cutting of the existing wall/surface for concealed wiring and making good the disturbed surfaces to match with the existing wall/surfaces
185
-
-
... More
S & F of single pole and neutral enclosure with a two pin and earth plug socket complete with one single pole MCB of 20 Amp capacity complete all as specified and directed by Engr-in-Charge. Make:- Legrand/L&T/Havells or equivalent as approved by GE.
23
-
-