Public Works Department Tender
View complete overview of Goa PWD Tender
Costs
EMD
₹ 1,56,849Document Cost
₹ 8,000Tender Fee
₹ 6,000
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_PWD_12886_1Bid Award Id
ViewTender No
No.21/23-24/PWD/WD.X/TN-03Tender Authority
Public Works Department ViewPurchaser Address
-Website
http://eprocure.goa.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Supply, Installation, Testing and Commissioning of addressable Heat detector with fixed and rate of raise feature inlcuding mounting base with LED.. Etc. complete as required. Each detector should have 2 inbuilt Isolators as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaing opertaional availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005. Detector should monitor Electromagnetic interference and report to the panel current and average values. EMC safely for detector shall be 50 V/m. Shall be EN54/VDs/UL certification.(Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector)Make:- Bosch, detnov, gamewell, GST.
30
136350
4545
... More
Supply, Installation, Testing and Commissioning of addressable manual break glass unit (Double action) with inbuilt isolators as per NFPA 72 style 7 wiring requirements, with flexible network structures and necessary fixing arrangemengts with key complete as required. Shall be EN 54/Vds/UL Certification.Make:- Bosch, detnov, gamewell,GST.
30
175740
5858
... More
Supply, installation, testing and commissiong of stand alone loop powered detector base sounder th inbuilt isolators as per NFPA 72 style 7 wiring requirements and with 32 different tone variants selection options and adjustable sound pressure by 5 levels, the sound pressure 92.1 dB(A) with flasher having Synchronized flash rate of 1 Hz and Light intensity 2 cd,should be programmed from the panel. Shall be EN54/Vds, UL certification.Make:- Bosch, detnov, gamewell,GST.
30
357540
11918
... More
Supply, installation, testing and commissiong of Beam detector including mounting base along with interface module to direct connect to the loop, having a coverage area with a distance of min.10 m and max 100m with extra width of up to 14 m, Operating temperature range: -20 C to +55 C, Response sensitivity of 40% Vds compliant Range 50 MtrMake:- Bosch, detnov, gamewell, GST.
4
298960
74740
... More
Supply, Installation, Testing and Commissioning of MMS PVC Pipe 25 MM
7000
1060500
151.5
... More
Supply,Installation,Testing and Commissioning of Casing Caping
2000
282800
141.4
... More
Supply,Installation,Testing and Commissioning of 2 Core 1.5 Sq.mm unarmoured cable Red colour Make:-Polycab
9000
1454400
161.6
... More
Supplying and Installation of Auto Glow signage are used to mark the location of Fire Exit/Exit/Emergency Exit. Size approve as per Location. Direction of human rub/step down/step up/ramp etc.
40
37572
939.3
... More
Supplying and Installation of Fire Safety Auto Glow signage are used to mark Fire interaction/Assembly point. Size Approve as per Location.
1
1030
1030.2
... More
Fire Extinguishers
-
-
-
... More
CO2 type fire extinguishers 4.5 kg capacity with ISI valve, initial gas charge, 1 mtr long high pressure discharge braided hose, PVC horn as per IS:15683 complete with accessary & CCE cerificate with ISI mark.
2
11542
5771.14
... More
Operation ,Maintenace repair/replacement of defective parts , all other necessary repair work after completion of warranty period including availability of trained technician whenever required .Comprehensive AMC includes all electronic items such as Main fire alarm control panel, repeater panel, addressable smoke detectors, addressable heat detectors,MCP, detector base, Beam detectors along with interface base.Including refilling of fire extinguishers.
-
-
-
... More
One year warranty period (defect liability period)
-
-
-
... More
First year Annual Comprehensive maintenance @ 2% (Commensing after one year on X)
1
140572
140572.77
... More
Second year Annual Comprehensive maintenance @ 3% on X
1
210859
210859.15
... More
Third year Annual Comprehensive maintenance @ 4% on X
1
281145
281145.54
... More
Dismanteling/removing of existing fire alarm panel,smoke/Heat detectors,cables/wires and other accossories handiing over to respective officer as direction of Engineer-in -charge after making proper inventry with proper disposal of detectors complte including makin good whreever required
1
75750
75750
... More
Supression System for Server Room
-
-
-
... More
4 kg capacity clean agent, DLP assembly with automatic valve, push in connector for tube, mounting bracket, end of line adopter and low pressure switch for monitoring system.
1
42369
42369.5
... More
Linear pneumatic heat detention tube with all necessary fitting and support.
50
44945
898.9
... More
A/V alarm.
2
18180
9090