Goa State Urban Development Agency Tender
View complete overview of Goa GSUDA Tender
Costs
EMD
₹ 8,44,696Document Cost
₹ 15,000Tender Fee
₹ 6,000
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_GSUDA_13675_1Bid Award Id
ViewTender No
43/3/GSUDA/Etender/44/2062 dt 16/01/2024Tender Authority
Goa State Urban Development Agency ViewPurchaser Address
-Website
http://eprocure.goa.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Design, Supply of 500W,IP 66 LED flood light to achieve average pitch horizontal illumination of 776 lux and vertical pitch 845 lux luminaire having housing and trim made of pressure die cast corrosion resistant alluminium alloy with heat dissipating fins design for excellent thermal management, Cover Glass- heat resistant toughened clear glass, Light Source - High power LED SMD type Color temp. White light 5700ºK ±300ºK
and CRI 70 , MCPCB Construction, LPW 100 /120, Optical Lens- Polycarbonate high performance type narrow, medium, wide (other options as per project needs) , Ingress protection - Flood light IP66, Driver enclosure IP65 . incl. connections etc. as required of make Transrail/Wipro/Philips/GE/Atilite).
114
9700146
85089
Supply of armoured PVC insulated PVC sheathed aluminum conductor cable of 1.1 kv grade with ISI mark conforming to IS:1554(Part I), IS:7098(Part II) with latest amendments of following size. (1) 4 ore 16 sq.mm
200
74400
372
Supply of armoured PVC insulated PVC sheathed aluminum conductor cable of 1.1 kv grade with ISI mark conforming to IS:1554(Part I), IS:7098(Part II) with latest amendments of following size. (2) 3.5core 35 sq.mm
2000
1028000
514
Supply of armoured PVC insulated PVC sheathed aluminum conductor cable of 1.1 kv grade with ISI mark conforming to IS:1554(Part I), IS:7098(Part II) with latest amendments of following size. (3) 3.5core 50 sq.mm
1500
1021500
681
Supply of armoured PVC insulated PVC sheathed aluminum conductor cable of 1.1 kv grade with ISI mark conforming to IS:1554(Part I), IS:7098(Part II) with latest amendments of following size. (4) 3.5core 95 sq.mm
900
1080000
1200
Supply of armoured PVC insulated PVC sheathed aluminum conductor cable of 1.1 kv grade with ISI mark conforming to IS:1554(Part I), IS:7098(Part II) with latest amendments of following size. (6) 3.5core 185 sq.mm
400
875600
2189
Supply of armoured PVC insulated PVC sheathed aluminum conductor cable of 1.1 kv grade with ISI mark conforming to IS:1554(Part I), IS:7098(Part II) with latest amendments of following size. (7) 3.5core 300 sq.mm
300
973500
3245
Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size exceeding 25 sq.mm direct in ground including excavation in the form of a trench as per Cable Trench Drawing provided by the Engineer-Incharge,sand cushioning with screened sand bed of 20mm thick , protective covering with bricks placed lenghtwise on top of cable all over the run and backfilling the excavated earth without stones or hard material and making the surface proper with 15 cm crown on the top complete as required.
5300
3975000
750
Supply and making cable end terminations with brass compression gland and aluminium lugs for following sizes of PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1KV grade, complete as required. (1) 4 core 16 sq.mm
20
8000
400
Supply and making cable end terminations with brass compression gland and aluminium lugs for following sizes of PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1KV grade, complete as required. (2) 3.5core 35 sq.mm
30
19500
650
Supply and making cable end terminations with brass compression gland and aluminium lugs for following sizes of PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1KV grade, complete as required. (3) 3.5core 50 sq.mm
24
20400
850
Supply and making cable end terminations with brass compression gland and aluminium lugs for following sizes of PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1KV grade, complete as required. (4) 3.5core 95 sq.mm
8
9600
1200
Supply and making cable end terminations with brass compression gland and aluminium lugs for following sizes of PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1KV grade, complete as required. (6) 3.5core 185 sq.mm
12
21600
1800
Supply and making cable end terminations with brass compression gland and aluminium lugs for following sizes of PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1KV grade, complete as required. (7) 3.5core 300 sq.mm
10
21000
2100
Supply of 4 core armoured PVC insulated PVC sheathed copper conductor cable of 1.1 kv grade with ISI mark conforming to IS:1554(Part I), IS:7098(Part II) with latest amendments of following size. (1) 4core 1.5 sq.mm
200
46400
232
Supply of 4 core armoured PVC insulated PVC sheathed copper conductor cable of 1.1 kv grade with ISI mark conforming to IS:1554(Part I), IS:7098(Part II) with latest amendments of following size. (2) 4core 2.5 sq.mm
200
65400
327
Supply and Laying of PVC flexible cable of 3C X 2.5Sq.mm 1.1KV grade for laying inside the pole.
3500
945000
270
Supply and making cable end terminations with brass compression gland and aluminium lugs for following sizes of 4 core PVC insulated PVC sheathed/XLPE copper conductor cable of 1.1KV grade, complete as required. (1) 4core 1.5 sq.mm
20
6700
335
Supply and making cable end terminations with brass compression gland and aluminium lugs for following sizes of 4 core PVC insulated PVC sheathed/XLPE copper conductor cable of 1.1KV grade, complete as required. (2) 4core 2.5 sq.mm
25
8750
350
Providing & fixing G.I. pipes complete with G.I. fittings including trenching and re-filling etc. as reqd. ( external work) 50 mm nominal bore.
48
13920
290
Providing & fixing G.I. pipes complete with G.I. fittings including trenching and re-filling etc. as reqd. ( external work) 100mm nominal bore
60
51000
850
Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories and providing special protective masonry chamber as per enclosed drawing ( to be paid extra) (but without charcoal or coke and salt) as required as per the Earthing Drawing provided by the Engineer-Incharge.The scope of work includes the following: a) Excavation of pit of size 1.0x1.0x 3.0 mtrs(min) and disposal of excavated soil. c)Watering GI pipe, 20mm, Class B, with funnel as per specs. d) Charcoal/salt as per specs ( paid seperately). e) Refilling the pit of size 1.0x1.0x 3.0 mtrs(min) with soft black agriculture soil of minimum resistivity i/c transportation. f) Testing of earth value with earth megger and certifications of its value. Aluminium tag with embossed earthing value to be attached to the pipe.g)watering arrangement(plumbing will be paid seperately).
24
250800
10450
Extra for using salt & charcoal for pipe earth electrode as required.
24
41520
1730
Providing and laying 25 mm x 5 mm G.I.strip on surface or in recess for connections etc. as required
150
43500
290
Supply, Installation, Testing & Commissioning of outdoor type compartmentalize feeder pillar with double door and locking facility fabricated with 16swg CRCA M.S. sheet duly degreased,derusted,powder coated with interconnections with copper wiring,glanding,lugging,earthing stud etc. suitable for 440 volts, 3phase, 4wire, 50Hz AC supply ,mounted on stand fabricated with M.S. angles of size 35mmx35mmx6mm comprising of following: 1) 100 Amps TP MCCB as incomer of approved make - 1 No. 2) Indicating lamp set RYB with control fuses - 1 set 3) 60 Amps 3 pole contactor L&T/siemens make - 4 No. 4) Single dial timer of make:GIC with MCB - 4 No 5) Power tool control with 2 Nos 9A contactors and raise lower push button 6) Neutral link, 20A, - 1No.
6
584400
97400
Earthwork in excavation by mechanical means(hydraulic excavator/manual in foundation pipeline trenches drain not exceeding 1.5m in width 10 sq.m on plan including dressing of sides, ramming of bottoms lift upto 1.5 m including getting out the excavated soil and disposal of surplus soil as directed within a lead of 50 m. a) All types of ordinary rock including all types of laterite rock,blasting prohibited
120
84000
700
Rubble packing with hard laterite stone under floors including watering ramming and consoldating etc in pipeline trenches and other foundations complete
30
40500
1350
Providing and laying cement concrete 1:3:6 (1 cement:3 coarse sand: 6 graded granitic or basaltic stone aggrt. 40 mm nominal size) excluding cost of centering ,shuttering and finishing: a) All work upto plinth level
20
116000
5800
Providing and laying in position ready mixed concrete (RMC) with usage of Fly Ash as per IS 3812 and IS 456-2000 manufactured in fully automatic batching plant and transported to site of work in transit mixer for a lead upto 10kms having continious agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work including pumping of R.M.C., from the transit mixer to the site of laying, excluding the cost of centering, shuttering, finishing and reinforcement including the cost of admixtures in recommended porportions as per IS : 9103 to accelerate/retard setting of concrete, improve workability without imparing strength and durability as per the directions of the engineer- in-charge. All works upto floor V level M-30grade of concrete
130
1209000
9300
Centering and shuttering i/c strutting, proping etc. and removal of form for . b) Vertical surfaces such as retaining walls,return walls,walls (any thickness) including attached pilasters, buttresses,plinth and string courses,fillets etc
230
111550
485
Providing Mild steel reinforcement conforming to IS- 1786 of 1986 for RCC work incl. bending, binding and placing in position in all the floors along with the factory made precast concrete cover blocks of specified sizes whose comprehensive strengh is not less than that of surrounding concrete in the structural member
5000
725000
145
Supply installtaion testing and commissioning of 180kva 3phase Diesel Generating Set with multi inline cyclinder coupled to 3phase Alternator.
1.0 DIESEL ENGINE: Engine shall be Mahindra (mpower)/ Volvo Eicher/ Perkins capable of developing required power at 1500 rpm & compact
with large reserve power and stable in operation with excellent speed regulation confirming to Governing
performance in accordance with BS-5514.
The engine selected above provides optimal fuel economy, low noise, low maintenance and long life
meeting the Emission standards.
The engine shall be complete with the following:
Flywheel, Lift Eyelets, Crank Case Ventilation & Engine Mountings
Engine driven Lub. Oil Pump, Strainer, Oil Filters, Oil Dip- Stick & Drain Plug.
Fuel Injection Pump, Speed Governor, Fuel Filters and Fuel Pipes.
Air Filters & Exhaust arrangement.
Radiator, Engine driven Coolant Pump, Thermostate, Engine driven Radiator Fan, and Integral piping.
DC Electric Starter Motor, Battery Charging DC Alternator, Switches, Sensors & its Engine wiring. 2.0 A.C. Alternatur:
A.C. Generator of suitable rating shall be Leroy Somer make Industrial, Brushless type, Synchronous, self excited, self regulated type fitted with AVR for voltage regulation of +/-1%. A.C. Generatorshall be with Class of Insulation ‘H’, Screen Protected drip proof having enclosure as per IP-23 and horizontal foot mounted single bearing type confirming to BS-5000, IS4722. ACOUSTIC ENCLOSURE
DPK/Supernova Acoustic Enclosures are thoughtfully crafted, art-piece. The design of the Enclosure is with natural air circulation without loss of any power for ventilation fan. Each DG Set with Enclosure undergoes strict quality checks and testing to achieve high-end performance. Supernova Acoustic Enclosure with other accessories meets the detailed specifications/ scope of supply as under:
The Enclosure enables reduction of 25dbA, thus at 1mtr. Distance under free field condition, it measures 75 dbA.
1
2140000
2140000
Two years maintaince package inclduing minor breakdown and oil change servicing for entire 2 years 180kva Diesel Generating Set
1
220000
220000
Supply and laying of 11KV 3C X 300 sqmm HT cable.Polycab make.
70
283850
4055
H.T.11 KV Termination kit indoor of Raychem make.
7
72947
10421
H.T.11 KV Termination kit outdoor Raychem make.
1
13579
13579
RCC pole 11.0 mtr long
2
49942
24971
11KV GOAB switch 200amps
1
27524
27524
11KV HG Fuse 200amps
1
13818
13818
Supply and fixing of 9KV Lighting arrestor
3
9621
3207
HDGI Structure Material
120
25920
216
HDG 11 KV 'V' shape cross arm with HDG clamps and HDG nut bolts etc. for 11 mtrs long RCC pole
2
4778
2389
HDG top fitting cross arm of channel ISMC 75x40x6 mm 0.7 mtrs long along with HDG clamps & HDG nut bolts etc for 11 mtrs along RCC pole
2
3258
1629
11 KV pin insulator with HDG pin
6
5070
845
ACSR Weasel Conductor 6/1/2.59 (nominal aluminium area 30 mm') (139 amp max at 45 C) for jointing and jumpering
0.1
4051
40519
Supply of 11KV Metering cubicle fabricated in CRCA Sheets. The Panel shall be powder coated and it will be totally dust and Vermin proof with busbar,wiring and base frame. lt will consist of:-
o 11KVCT's 25l5A Cls-0.5s, STC-13.1 :3Nos
o 11KVPT's 50VA :3Nos
o HT Trivector Meter DLMS :1No
o Modem:1No CT's & PT'S are MRT tested and are approved by Electricity department
Pragati make.
2
766000
383000
Providind and making Chemical Earthing 3mtr deep with copper bonded earthing rod dia 17mm x 3 mtr length with 25kg x 2 nos BFC bag with Frp square earth pit cover of 300 x 300 mm
16
320000
20000
Providing & Fixing 50x5 mm GI strip for neutral connection earthing
10
4100
410
Providing & Fixing 25x5 mm GI strip for body earthing
60
16500
275
Supply and erection of Non extensible load break switch 400 A,switchgear with oil type as approved by GED for isolation and protection of transformer (100 - 800 KVA). The load break switch will be having protection system mechanism and plunger type HRC bottle type fuses with an fault tripping arrangement.Type: NEFS with 2 sets of Terminal protector boots and transportation.
Make: Lucy Electric
1
373500
373500
GI chain link fencing for Transformer substation
1
118000
118000
Providing and spreading of metal in substation area including labour cost.
1
13000
13000
Providind and making Thermal Insul coating for 2nos of HT metering units
1
223000
223000
Providing and laying of 1x70 sqmm copper flexible cable for neutral connection of D.G set
12
19200
1600
Supply, erection, testing and commissioning of Main panel board. Panel shall be frabricated from 2/1.5 mm thick CRCA sheet, with rubber gasket on door and power coated with seimens gray shade. Panel will be provided with 800A(80x10mm) for phase & 80 x 6neutral AL. bus bar and 40mmx5mm AL strip. Base channel 75x40x5 shall be provided.
Control wire - PVC insulated 1100v copper 1sqmm 2.5sqmm.
Power wiring - PVC insulated 1100v copper 35sqmm/25sqmm/16sqmm/6sqmm. Panel consisting of:
Incomer: 800A ACB 4P 50KA TM MDO - 1NOS - L&T Make
250A MCCB TP 36 KA TM WITH ROH - 1NOS - L&T Make
400A MCCB TP 36 KA TM WITH ROH - 1NOS - L&T Make
RYB LAMP 240V AC - 3 sets - L&T Make
VIF METER /5 - 3NOS - Elmasure/ L&T Make
ELR WITH CB CT - 1NO - PROK Make
SP MCB 6A 10 KA - 10NOS - L&T Make
CT 800/5 15 VA - 3NOS - Lotlikar Make
CT 250/5 15 VA - 3NOS - Lotlikar Make
CT 400/5 15 VA - 3NOS - Lotlikar Make
Outgoing:
400A 4P MANUEL - 1NOS - L&T / C&S Make
100A MCCB TP 25 KA TM WITH ROH - 6NOS - L&T Make
63A 3P MCB 10 KA - 16NOS - L&T Make
250A 4P MANUEL - 1NOS - L&T / C&S Make
100A MCCB TP 25 KA TM WITH ROH - 4NOS - L&T Make
63A 3P MCB 10 KA - 4NOS - L&T Make
1
1465000
1465000
400 KVA, 11/0.433 KV, Oil Cooled, Copper Wound Transformer. Off Circuit Tap Changer
HV & LV side cable box
As per BIS 1180, level 2
Approved by Goa Electricity department
Make: SVT make
Including
M.R.T testing at Margao, Handling Charges & Transportation to the site, unloading etc complete.
1
1500000
1500000
Evaluation Notes How It Works ?