Electricity Department Tender

Take tender evaluation notes for Goa Electricity Department Tender

Electricity Department Tender

Works
Electrical Generators And Transformers
Electrical and Electronics
Eprocure
Opening Date22 Nov 2023
Closing Date6 Jan 2024
Tender Amount₹ 20,30,273 
Notes
Download

Costs

  • EMD

    ₹ 40,605
  • Document Cost

    ₹ 500
  • Tender Fee

    ₹ 4,061

Summary

Work Of Erection Of 100kva Distribution Transformer Centers At Baddem In V.p. Cotigao Under The Jurisdiction Of Sub-div-iii, Canacona Under Div-xvi, Margao.

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Supply of ACSR ' RACOON conductor of size 6/1/2.59mm. The stringing rate includes transportation, jointing, jumpering with aluminium tape etc. 3.31 Kms of the conductor shall be used for stringing of 11 KV line, 0.28Kms for providing guarding and 0.25 Kms shall be used for jumpering on DP. The remaining 0.4 Kms of conductor shall be used for earthing of transformer centre which includes crimping of lugs and terminating the conductor to all the equipments of the DP with the lugs of appropriate size. The conductor shall be as per technical specification.

0.12

10379

86496

... More
Erection 185sq.mm of single cores XLPE unarmoured Al conductor 1.1KV grade power cable as per Technical Specification and as per IS:7098 (Part-I/1988) with latest ammendment carrying ISI mark.

240

40800

170

... More
Erection of 11KV 3 phase outdoor terminating kit including sockets at 11KV end of DT to be used with cables as per - 95sq.mm. including connection of cable armouring and screen to grounding system.

1

2648

2648

... More
Erection of G.I. earthing pipe 2500mm long, 40mm dia class B fabricated and perforated filled with homogenous mixture of 20Kgs of Charcoal, 20Kgs of salt and sand /soil inclusive of excavation, backfilling & spreading of excavated earth evenly as per Drg No. CEE/E-829. The work includes excavation of pit in any type of soil classified under Soft Strata of Annexure A of CPWD-8.

6

14664

2444

... More
The 2pin cross arm shall be of 510mmlength & provided with a total of 4 holes of 22mm dia on each flange section. In addition two slotted holes of size 18 x 40 mm shall be provided on the cross arm for clamping arrangement to the pole. The 2pin side cross arm shall be of 800mm length & provided with a total of 4 holes of22mm dia on each flange section. In addition two slotted holes of size 18 x 40mm shall be provided on the left end of the cross arm for clamping arrangement to the pole. The cross arms shall be fitted vertically onto the top end of the poles, at a height conforming to the relevant I.E. rules & utilizing suitable size of HDGI clamps & HDGI washers, HDGI nut bolts.

42

9744

232

... More
Supply of AAC" GNAT" size 7/2.21mm conductor for neutral, streetlight and jumpering as well as guarding.Hard drawn stranded aluminum conductor & conforming to IS: 398(Pt-I/76) with amendment no.1,2 & 3 & of size 7/2.21mm aluminum, (nominal aluminum area 25mm2) "GNAT". Regarding packing of the drum should be conforming as per IS: 1778/80 with amendment no. 1. The conductor shall be wound with protective wrapping (Cl. 5.1) & also protective lagging (Cl. 5.2 of ISS). The wires shall be smooth & free from all imperfections, such as spills & splits. No joints shall be permitted in any wire.

3.95

99907

25293

... More
Erection of 100KVA, 11/0.433KV 3 PH. Aluminium Wound Distribution Transformer level-II

1

11017

11017

... More
COST OF MATERIAL

-

-

-

... More
Supply HDGI G.I. Hexagonal head bolts and hexagonal nuts conforming to IS 1363 part I to III 1992 as amended upto date of the size 3 ½" x 5/8" or 4" x 5/8",6"x5/8", 8"x5/8"

90

20520

228

... More
Supply of AAC ' ANT ' conductor of size 7/3.14mm. The stringing rate includes transportation, jointing, etc. 7.44 Kms of conductor shall be strung as phases for LT line. The conductor shall be comply to the technical specification.

4.7

226004

48086

... More
Supply of 11.00 meters long R.C.C. Pole as per drawing No.CEE/E-698 Rev-2 and conforming to IS 785-1998 as amended upto date. The Component used for pole shall conform to following IS amended upto date. Ordinary Port land cement 53 grade : IS 12269 Aggregate : IS 383-1970 Torsteel : IS 1786-7985 MS bar : IS 432 P 1&2-1982 Erection includes transpotation, dragging of pole to the site of pit, clearing of bushes etc and excavation of pit of Size 0.60 x 0.60 x 1.5 mts in any type of soil and back filling the pit after erection of the pole in pit by rubble and excavated soil as shown in the Drg No. EE/IV/LT9.0RCC. ( Rubble is dealt seperately )

2

32742

16371

... More
Stringing of AAC" GNAT" size 7/2.21mm conductor for neutral, streetlight and jumpering as well as guarding.Hard drawn stranded aluminum conductor & conforming to IS: 398(Pt-I/76) with amendment no.1,2 & 3 & of size 7/2.21mm aluminum, (nominal aluminum area 25mm2) "GNAT". Regarding packing of the drum should be conforming as per IS: 1778/80 with amendment no. 1. The conductor shall be wound with protective wrapping (Cl. 5.1) & also protective lagging (Cl. 5.2 of ISS). The wires shall be smooth & free from all imperfections, such as spills & splits. No joints shall be permitted in any wire.

3.95

24422

6183

... More
Supply of HDGI stay rod with plate complete for for 7.5 m long RCC pole as per technical specification. ( Rubble is dealt seperately)

40

162724

4068.1

... More
Erection of HDGI stay rod with plate complete for 11 mts. Long RCC pole as per technical specification ( Rubble is dealt seperately)

2

5071

2535.5

... More
Supply of 11KV 3 phase outdoor terminating kit including sockets at 11KV end of DT to be used with cables as per - 95sq.mm. including connection of cable armouring and screen to grounding system.

1

10152

10152

... More
Fixing of Anticlimbing device made out of G.I. barbed wire of size 8SWG.

2

350

175

... More
Erection of 7.5 meters long R.C.C. Pole as per drawing No.CEE/E-698 Rev-2 and conforming to IS 785-1998 as amended upto date. The Component used for pole shall conform to following IS amended upto date. Ordinary Port land cement 53 grade : IS 12269 Aggregate : IS 383-1970 Torsteel : IS 1786-7985 MS bar : IS 432 P 1&2-1982 Erection includes transpotation, dragging of pole to the site of pit, clearing of bushes etc and excavation of pit of Size 0.60 x 0.60 x 1.5 mts in any type of soil and back filling the pit after erection of the pole in pit by rubble and excavated soil as shown in the Drg No. EE/IV/LT9.0RCC. ( Rubble is dealt seperately )

41

151249

3689

... More
Supply and transportation of 12 KV rated voltage GOAB switches tilting type, outdoor, manually operated, triple pole, single break, conforming to IS: 9921-Part1 to V as amended upto date and detailed specifications. Each set shall comprise of six pedestal and three tilting post insulators. Insulator should be factory cemented by the manufactures of the insulators and have minimum 320mm creepage distance and AB switches contacts shall be of copper/copper alloy. The AB switch shall be of current rating 200 A. The isolators shall be as per technical specification.

1

23535

23535

... More
Supply, testing and commissioning of 100KVA, 11/0.433KV 3 PH. Aluminium Wound Distribution Transformer level-II

1

148333

148333

... More
Supply and commissioning of MS Distribution Box alongwith 12nos. 200A Kit Kat fuse and MCCB of 400Amps, 415 Volts. The box shall be fabricated with MS sheet 12 gauge with overlapping rain proof slit ventilators on both sides of the distribution box with wire mesh to prevent entry of insects with pin head door hinges locking arrangement and shall have required number of bus bars made out of Aluminium strips of size 40 x 10mm for connecting MCCB, fuses and cables (for 4 feeder arrangement) & other accessories. The box shall also have 'magnetic hold' arrangement to ensure that the box doors always remains in 'closed' positiion when shut even without latching.

1

63140

63140

... More
Supply & Erection 185sq.mm of single cores XLPE unarmoured Al conductor 1.1KV grade power cable as per Technical Specification and as per IS:7098 (Part-I/1988) with latest ammendment carrying ISI mark.

240

58800

245

... More
Providing of Low Tension metering to the DTC by Suplying, Installing and commissioning of following Materials: a] Epoxy resin Cast L.T. CT coil of 300/5A, Class-0.5s, 50Hz,660V, Burden 15VA conforming to IS-2705 / 1992 as amended upto date (3 Nos) b] Electronic 3Phase,4wire ,Trivector Meter ,LT CT operated 3x240V,-/5A,50Hz, class 0.5s, Category "A" (DLMS COSEM Protocol) for DTC with RS 232 Optical port and complience to BIS ICS Doc: ETD 13(6211) and latest. (1 No) c] 1.1KV multistand copper conductor 2.5sq.mm, XLPE insulated, armoured control cable conforming to relevant IS amended upto date.( 15 Mtr) d] Pole mounted M.S Box ( outdoor type) for Electronic Meter as Drawing No.EE/VIII/64(REV) (1 No) e] Al. L shape flat 40mm suitable for mounting on bushing rod and brass lug (3 Nos)

1

1656

1656

... More
Supply of GI 4 pin LT cross arm channel typeThe 4pin cross arm shall be of 510mmlength & provided with a total of 4 holes of 22mm dia on each flange section. In addition two slotted holes of size 18 x 40 mm shall be provided on the cross arm for clamping arrangement to the pole. The 2pin side cross arm shall be of 800mm length & provided with a total of 4 holes of22mm dia on each flange section. In addition two slotted holes of size 18 x 40mm shall be provided on the left end of the cross arm for clamping arrangement to the pole. The cross arms shall be fitted vertically onto the top end of the poles, at a height conforming to the relevant I.E. rules & utilizing suitable size of HDGI clamps & HDGI washers, HDGI nut bolts.

73

80957

1109

... More
Supply, fabrication and transportation of Hot dip galvanised DP structure material consisting of the following: a] Transformer bed channel ISMC of size 100 x 50 mm, 2.74 mts long, 2 pieces alongwith transformer belting angle ISA of size 50 x 50 mm, 2740mm long, 2 pieces alongwith side supports as per Drg No. EE/IV/DP/Bed-Ch for transformer. b] GOAB switch mounting channel ISMC of size 75 x 40 mm, 2740mm mts long, 2 pieces alongwith side supports as per Drg No. EE/IV/DP/GOAB CH for each GOAB switch. c] HG fuse mounting channel ISMC of size 75 x 40 mm, 2740mm mts long, 2 pieces alongwith Lightening Arrestors mounting angles ISA of size 50 x 50 mm, 2.74 mts long alongwith side supports as per Drg No EE/IV/DP/GOAB/HG-CH for HG fuse set. d] Intake Channel ISMC for mounting Disc Insulators of size 100 x 50 mm, 1 piece as per Drg No. Drg No. EE/IV/DP/INTAKE-CH . The work shall include all fabrication, drilling of holes, welding, cutting etc. The hot dip galvanisation shall be done only after fabrication work is completed.

274

46306

169

... More
Supply of 7.5 meters long R.C.C. Pole as per drawing No.CEE/E-698 Rev-2 and conforming to IS 785-1998 as amended upto date. The Component used for pole shall conform to following IS amended upto date. Ordinary Port land cement 53 grade : IS 12269 Aggregate : IS 383-1970 Torsteel : IS 1786-7985 MS bar : IS 432 P 1&2-1982 Erection includes transpotation, dragging of pole to the site of pit, clearing of bushes etc and excavation of pit of Size 0.60 x 0.60 x 1.5 mts in any type of soil and back filling the pit after erection of the pole in pit by rubble and excavated soil as shown in the Drg No. EE/IV/LT9.0RCC. ( Rubble is dealt seperately )

41

249772

6092

... More
Supply of 11KV 3 phase indoor terminating kit including sockets at RMU to be used with cables - 95sq.mm including connection of cable armouring and screen to grounding system.

1

6731

6731

... More
Supply of HDGI stay rod with plate complete for 11 mts. Long RCC pole as per technical specification ( Rubble is dealt seperately)

2

9227

4613.57

... More
Supply of 11 KV H.G. Fuse (set of three HG fuses) units 200 Amp as specified in DRg No CEE/E-786

1

10450

10450

... More
The 2pin cross arm shall be of 510mmlength & provided with a total of 4 holes of 22mm dia on each flange section. In addition two slotted holes of size 18 x 40 mm shall be provided on the cross arm for clamping arrangement to the pole. The 2pin side cross arm shall be of 800mm length & provided with a total of 4 holes of22mm dia on each flange section. In addition two slotted holes of size 18 x 40mm shall be provided on the left end of the cross arm for clamping arrangement to the pole. The cross arms shall be fitted vertically onto the top end of the poles, at a height conforming to the relevant I.E. rules & utilizing suitable size of HDGI clamps & HDGI washers, HDGI nut bolts.

42

23898

569

... More
Stringing of AAC ' ANT ' conductor of size 7/3.14mm. The stringing rate includes transportation, jointing, etc. 7.44 Kms of conductor shall be strung as phases for LT line. The conductor shall be comply to the technical specification.

4.7

31179

6634

... More
Fixing of a) L.T. brown glazed shackle insulators of size 100mm x 115mm conforming to fig.No.4 and type 2 of IS: 1445/77 as amended upto date. Minimum failing load shall be 16kN & b) G. I hardware suitable for L. T. shackle insulators of size 100 x 115 mm. conforming to type 2, fig. 4 of IS: 1445/77 as amended upto date. Hardware or fitting shall conform to fig. 4 of IS 7935-1975 as amended up to date, comprise of 2 G. I. strips, 2 G. I. bolts and 2 nuts with spring washers.

172

35776

208

... More
Erection and commissioning of MS Distribution Box alongwith 12nos. 200A Kit Kat fuse and MCCB of 400Amps, 415 Volts. The box shall be fabricated with MS sheet 12 gauge with overlapping rain proof slit ventilators on both sides of the distribution box with wire mesh to prevent entry of insects with pin head door hinges locking arrangement and shall have required number of bus bars made out of Aluminium strips of size 40 x 10mm for connecting MCCB, fuses and cables (for 4 feeder arrangement) & other accessories. The box shall also have 'magnetic hold' arrangement to ensure that the box doors always remains in 'closed' positiion when shut even without latching.

1

8795

8795

... More
Erection of Enamelled danger board

2

114

57

... More
Supply of Anticlimbing device made out of G.I. barbed wire of size 8SWG.

2

290

145

... More
Fixing of HDGI L.A./S.A. cross arm clamps suitable for 7.5 RCC pole as per Drg No. CEE/E-524.

113

3616

32

... More
Fixing of 11 KV H.G. Fuse (set of three HG fuses) units 200 Amp as specified in DRg No CEE/E-786

1

3368

3368

... More
Erection of a) 11 KV brown glazed porcelain Pin Insulator with minimum failing load of 5 KN and the Minimum creepage distance of 320 mm conforming to IS 731-1971 as amended upto date & b) Forged G. I. Pin conforming to IS 2486 part 1 & 2 as amended upto date suitable for 11 KV glazed porcelain pin insulators conforming to IS: 731/71 as amended upto date. G. I pin shall conform to reference S-165 N fig. 5 of IS: 2486/ (part-II)/74 as amended upto date. Dimensions ‘X’ in said fig. shall be 150 mm (screwed 100 mm). Pin shall be supplied along with one suitable G. I. hexagonal nut and G. I. spring washer. Minimum failing load of pin shall be 10 KN. HT Porcelain insulator.

3

456

152

... More
Supply and Crimping of Alluminium Crimping lug 185 sq.mmAluminum crimping lugs shall conform to IS: 8309-1976 as amended upto date. Lugs shall be made of aluminum of grade 1E of IS 5082-1969 suitable for aluminum cables of size 95/150 sq. mm. The cost of Aluminum lugs are inclusive in Supply, Erection, Testing, Commissioning of Single Core XLPE unarmored LT Power Cable/ACSR Conductor. Tests as per IS shall be carried out at manufacturers work and test reports shall be furnished before supply of materials. The work involves supply and fixing of cable glands and cable lugs as per cable sizes mentioned in the Bidding Schedule. While fixing of glands to the switchgear / Transformer or distribution box panel, sufficient care shall be taken. These cable glands shall be fixed face to face. Skilled and experience electrician shall be used in carrying out this job in systematic manner.

24

1872

78

... More
Erection of HDGI stay rod with plate complete for for 7.5 m long RCC pole as per technical specification. ( Rubble is dealt seperately)

40

96120

2403

... More
Supply of a) 11 KV brown glazed porcelain Pin Insulator with minimum failing load of 5 KN and the Minimum creepage distance of 320 mm conforming to IS 731-1971 as amended upto date & b) Forged G. I. Pin conforming to IS 2486 part 1 & 2 as amended upto date suitable for 11 KV glazed porcelain pin insulators conforming to IS: 731/71 as amended upto date. G. I pin shall conform to reference S-165 N fig. 5 of IS: 2486/ (part-II)/74 as amended upto date. Dimensions ‘X’ in said fig. shall be 150 mm (screwed 100 mm). Pin shall be supplied along with one suitable G. I. hexagonal nut and G. I. spring washer. Minimum failing load of pin shall be 10 KN. HT Porcelain insulator.

3

2079

693

... More
Supply of 9 KV, 5 KA nominal discharge current Metal Oxide gapless distribution class lightning arrestor conforming to IEC-60049-4 and IS 3070 Part 3 1993 as amended upto date suitable for 11 KV 50 HZ effectively earthed neutral system with necessary mounting arrangements and connector suitable to connect ACSR conductor upto overall diameter 12.30 mm.

3

9099

3033

... More
Supply of HDGI S.A./L.A. cross arm clamps for 11 mts. Long RCC pole as per DRG No. EE-II/20/2008

14

5796

414

... More
Laying of 11KV, 3 core, 95sq.mm, Al conductor, XLPE, insulated, armoured cable (from the RMU to the transformer)

22

4378

199

... More
Erection of 11.00 meters long R.C.C. Pole as per drawing No.CEE/E-698 Rev-2 and conforming to IS 785-1998 as amended upto date. The Component used for pole shall conform to following IS amended upto date. Ordinary Port land cement 53 grade : IS 12269 Aggregate : IS 383-1970 Torsteel : IS 1786-7985 MS bar : IS 432 P 1&2-1982 Erection includes transpotation, dragging of pole to the site of pit, clearing of bushes etc and excavation of pit of Size 0.60 x 0.60 x 1.5 mts in any type of soil and back filling the pit after erection of the pole in pit by rubble and excavated soil as shown in the Drg No. EE/IV/LT9.0RCC. ( Rubble is dealt seperately )

2

17200

8600

... More
COST OF ERECTION

-

-

-

... More
Fixing of a) L.T. brown glazed porcelain pin insulators of size 100mm x 70mm conforming to type 1 fig 1 of IS:1445/1977 with amendment 2 of Feb.1981 (second revision) as amended upto date. Minimum failing load shall be 3.5kN & b) Forged G. I. Pin conforming to IS 7935/1975 as amended upto date suitable for L.T. porcelain pin insulator type 1 conforming to fig.1 of IS: 1445/77 with amendment No. 2, Feb.1981, of size 100 x 70 mm. G. I. pin shall comprise of G. I. nut and spring washer and conform to fig. No. 2 of IS: 7935/1975. Minimum failing load of pin shall be 3.5 KN.

153

26469

173

... More
Fixing of HDGI S.A./L.A. cross arm clamps for 11 mts. Long RCC pole as per DRG No. EE-II/20/2008

14

910

65

... More
Supply and fixing HDGI G.I. Hexagonal head bolts and hexagonal nuts conforming to IS 1363 part I to III 1992 as amended upto date of the size 3 ½" x 5/8" or 4" x 5/8",6"x5/8", 8"x5/8"

90

2700

30

... More
Providing of Low Tension metering to the DTC by Suplying, Installing and commissioning of following Materials: a] Epoxy resin Cast L.T. CT coil of 300/5A, Class-0.5s, 50Hz,660V, Burden 15VA conforming to IS-2705 / 1992 as amended upto date (3 Nos) b] Electronic 3Phase,4wire ,Trivector Meter ,LT CT operated 3x240V,-/5A,50Hz, class 0.5s, Category "A" (DLMS COSEM Protocol) for DTC with RS 232 Optical port and complience to BIS ICS Doc: ETD 13(6211) and latest. (1 No) c] 1.1KV multistand copper conductor 2.5sq.mm, XLPE insulated, armoured control cable conforming to relevant IS amended upto date.( 15 Mtr) d] Pole mounted M.S Box ( outdoor type) for Electronic Meter as Drawing No.EE/VIII/64(REV) (1 No) e] Al. L shape flat 40mm suitable for mounting on bushing rod and brass lug (3 Nos)

1

25688

25688

... More
Supply of HDGI L.A./S.A. cross arm clamps suitable for 7.5 RCC pole as per Drg No. CEE/E-524.

113

20792

184

... More
Erection of 12 KV rated voltage GOAB switches tilting type, outdoor, manually operated, triple pole, single break, conforming to IS: 9921-Part1 to V as amended upto date and detailed specifications. Each set shall comprise of six pedestal and three tilting post insulators. Insulator should be factory cemented by the manufactures of the insulators and have minimum 320mm creepage distance and AB switches contacts shall be of copper/copper alloy. The AB switch shall be of current rating 200 A. The isolators shall be as per technical specification.

1

3971

3971

... More
Supply of G.I. earthing pipe 2500mm long, 40mm dia class B fabricated and perforated filled with homogenous mixture of 20Kgs of Charcoal, 20Kgs of salt and sand /soil inclusive of excavation, backfilling & spreading of excavated earth evenly as per Drg No. CEE/E-829. The work includes excavation of pit in any type of soil classified under Soft Strata of Annexure A of CPWD-8.

6

16380

2730

... More
Supply of 11KV, 3 core, 95sq.mm, Al conductor, XLPE, insulated, armoured cable (from the RMU to the transformer)

22

24794

1127

... More
Fixing of 9 KV, 5 KA nominal discharge current Metal Oxide gapless distribution class lightning arrestor conforming to IEC-60049-4 and IS 3070 Part 3 1993 as amended upto date suitable for 11 KV 50 HZ effectively earthed neutral system with necessary mounting arrangements and connector suitable to connect ACSR conductor upto overall diameter 12.30 mm.

3

522

174

... More
Supply and erection of 11KV 3 phase indoor terminating kit including sockets at RMU to be used with cables - 95sq.mm including connection of cable armouring and screen to grounding system.

1

2538

2538

... More
Supply of a) L.T. brown glazed porcelain pin insulators of size 100mm x 70mm conforming to type 1 fig 1 of IS:1445/1977 with amendment 2 of Feb.1981 (second revision) as amended upto date. Minimum failing load shall be 3.5kN & b) Forged G. I. Pin conforming to IS 7935/1975 as amended upto date suitable for L.T. porcelain pin insulator type 1 conforming to fig.1 of IS: 1445/77 with amendment No. 2, Feb.1981, of size 100 x 70 mm. G. I. pin shall comprise of G. I. nut and spring washer and conform to fig. No. 2 of IS: 7935/1975. Minimum failing load of pin shall be 3.5 KN.

153

40239

263

... More
Supply of a) L.T. brown glazed shackle insulators of size 100mm x 115mm conforming to fig.No.4 and type 2 of IS: 1445/77 as amended upto date. Minimum failing load shall be 16kN & b) G. I hardware suitable for L. T. shackle insulators of size 100 x 115 mm. conforming to type 2, fig. 4 of IS: 1445/77 as amended upto date. Hardware or fitting shall conform to fig. 4 of IS 7935-1975 as amended up to date, comprise of 2 G. I. strips, 2 G. I. bolts and 2 nuts with spring washers.

172

63984

372

... More
Supply of Enamelled danger board

2

496

248

... More
Stringing of ACSR ' RACOON conductor of size 6/1/2.59mm. The stringing rate includes transportation, jointing, jumpering with aluminium tape etc. 3.31 Kms of the conductor shall be used for stringing of 11 KV line, 0.28Kms for providing guarding and 0.25 Kms shall be used for jumpering on DP. The remaining 0.4 Kms of conductor shall be used for earthing of transformer centre which includes crimping of lugs and terminating the conductor to all the equipments of the DP with the lugs of appropriate size. The conductor shall be as per technical specification.

0.12

1240

10334



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.