Electricity Department Tender

View complete overview of Goa Electricity Department Tender

Electricity Department Tender

Works
Electrical and Electronics
Eprocure
Opening Date2 Feb 2024
Closing Date20 Feb 2024
Tender Amount₹ 6,42,659 
Notes
Download

Costs

  • EMD

    ₹ 12,853
  • Document Cost

    ₹ 500
  • Tender Fee

    ₹ 1,285

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Supply of MS Distribution box as per drg No. CEE/E-689 Revision No. 3 along with MCCB 400 A, Bus bar made out of Aluminium strips 40 x 10 mm,aluminium 'J' type fuse links (Set of 3) for 4 feeder arrangement with 1 no of moulded case circuit breaker (MCCB) of 200A, 415V, AC 50 Hz for 200 KVA Distribution Transformer centre

1

48387

48387

... More
Supply of Single core XLPE Insulated PVC Sheathed cable 185sqmm 1.1kV grade

40

9800

245

... More
Supply of Three and half core armoured XLPE cable of size 95 Sq.mm cross linked polyethelene insulated, PVC shealthed 3.5 core 95 sqmm cable with galvanized steel strip armoured aluminium cable of 1100 volts grade suitable for 3 phase earthed system and conforming to IS: 7098 (Part-I)/1988 as amended upto date.

24

17616

734

... More
Supply of 11 KV , 200 A Horn gap fuse unit (Set of three) shall be as per enclosed drg No. CEE/E-786. Revision 3 and detailed specifications enclosed herewith.

1

10450

10450

... More
Supply of 9 KV, 5 KA nominal discharge current metal oxide gapless distribution class Lightning arrestor conforming to IEC-600994-4 and IS: 3070 part 3 1993 as amended upto date suitable for 11 KV 50 HZ effectively earthed neutral system with necessary mounting arragements and connector suitable to connect ASCR conductor upto overall diameter 12.30 mm

3

9099

3033

... More
Supply of HDGI structure material for DP. Each trasformer centre DP consist of HDGI structure material as follows: a) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for incoming line & installation of disc insulators b) GI channel ISMC75x40x7.3mm 2.75mtrs long 2 pieces for GOAB switch c) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for HG fuses d) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for installation of lightening arrestor e) GI channel ISMC 100x50x7.3mm 2.75 mtrs long 2 pieces for installation of Trasformer f) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for side support of trasformer g) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 4 pieces for installation of any other items h) GI channel ISMC 100x40x7.3mm 0.52 mtrs long 2 pieces for installation of Transformer base channel

274

46306

169

... More
Supply of Earthing complete with 40mm GI Pipe, 2.5 mts long alongwith 20 kgs each salt, charcoal complete.

6

16380

2730

... More
Supply of Enamelled danger boards 11000 Volts as per drg no. CEE/E-490

4

992

248

... More
Supply of HDGI L.T. 2 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-491 for 9 mtr Rcc pole

3

1707

569

... More
Supply of HDGI L.T. 4 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-491 for 9mtr Rcc pole

6

6654

1109

... More
Supply of X-arms clamps SA/LA of 9mtrs pole

21

5586

266

... More
Supply of L.T. brown glazed porcelain pin insulators of size 100mmx70mm conforming to type 1 fig 1 of IS: 1445/1977 with amendment 2 of Feb 1981 (second revision) as amended upto date. Minimum failing load shall be 3.5 KN with Forged GI pin conforming to IS 7935/1975 as amended upto date suitable for LT porcelain pin insulator type 1 conforming to fig 1 of IS: 1445/77 with amendment no 2 feb 1981, of size 100 x 70 mm. GI pin shall comprise of GI nut and spring washer and conform to fig No 2 of IS: 7935/1975. Minimum failing load of pin shall be 3.5 KN

20

5260

263

... More
Supply of LT brown glazed shackle Insulator of size 100 mm x 115 mm conforming to fig No. 4 and type 2 fo IS: 1445/77 as amended upto date. Minimum failing load shall be 16 KN with GI hardware suitable for LT shackle insulator of size 100 x 115 mm conforming to type 2 fig 4 of IS: 1445/77 as amended upto date. Hardware or fitting shall conform to fig 4 of IS: 7935-1975 as amended upto date comprise fo 2 GI strips, 2 GI bolts and 2 nuts with spring washers.

10

3720

372

... More
Supply of Stay clamp for 9 mtr Rcc Pole

4

1964

491

... More
Supply of HDGI Cut point channel 75X40X 6mm,1.3 mts long (8.84kgs)

4

7836

1959

... More
Supply of HDGI 11KV "V" shape cross arm of channel ISMC 75 x 40 x 7.3mm as per gdr. No. CEE/E-408-R1

4

5876

1469

... More
Supply of 11 Disc Insulators ball and socket type, A porcelain brown glazed duly cemented at factory with MCI socket cap, forged steel ball pin and supplied with Phosphor bronze "W" split pin as per IS 731-1971 as amended upto date. Minimum failing load 45 KN Pin ball diameter 16 mm. Minimum Creepage distance 320 mm with 2 bolted type hardware fitting 70KN suitable for 11 KV ball and socket type disc insulators of 16 mm pin, failing load of 70 KN and suitable for ACSR conductor of size upto 18 mm diameter. The metal parts shall be as per drg No CC/E-482-Rev-2 Benclosed and conform to IS-2486 part 1-1993, 2486 Part-2-1989 as amended upto date.

21

60606

2886

... More
Supply of HDGI Top fitting X-arm channel 75X40,0.7mts long(4.74kgs)

4

3276

819

... More
Supply of 11 KV brown glazed porcelain Pin Insulator with minimum failing load of 5 KN and the minimum creepage distance of 320mm conforming to IS 731-1971 as amended upto date. And forged GI pin conforming to IS 2486 part 1 & 2 as amended upto date suitable for 11 KV glazed porcelain pin insulators conforming to IS 731/71 as amended upto date. GI pin shall conform to reference S-165 N fig 5 of IS 2486/(part-II)/74 as amended upto date. Dimension X in said fig shall be 150mm (screwed 100mm). Pin shall be supplied along with one suitable GI hexagonal nut and GI spring washer. Minimum failing load of pin shall be 10 KN.

12

8316

693

... More
Supply of HDGI Nut bolts 65X100mm

9.6

2188

228

... More
Supply of Stay set complete for 9.0 mtr RCC pole

6

26199

4366.54

... More
Supply of AAC conductor hard drawn stranded all aluminium conductor conforming IS 398(Part-1/96) as amended upto date of following sizes 7/3.10 mm ANT conductor for phases

0.1

4808

48086

... More
Supply of AAC conductor hard drawn stranded all aluminium conductor conforming IS 398(Part-1/96) as amended upto date of following sizes 7/2.21 mm GNAT conductor for double neutral & guadings.

0.1

2529

25293

... More
Supply of ACSR 'Weasel' conductor confirming ISI specification IS: 398 (part-1/96) as amended upto date of following sizes 6/1/2.59 mm for guarding

0.6

20045

33409

... More
Cost of Erection

-

-

-

... More
Erection of RCC pole 9.0 mtr as per the drawing No.CEE/E-698, REV-1 as per annexure confirming to IS 785-1998 as amended upto date. The component used for pole shall conform to following IS amended up to date. 1) Ordinary Port land cement 53 grade IS 12269 2) Aggregate IS 383-1970 3) Torsteel IS 1786-7985 4) MS bar IS 432 p 1 & 2-1982

10

44080

4408

... More
Erection of 11 KV rated voltange GOAB switches tilting type, outdoor, manually operated, triple pole, single break, conforming to IS: 9921-Part 1 to V as amended up to date and detailed specification eclosed herewith. Each set shall comprise of six pedestal and three tilting post insulators. Insulator should be factory cemented by the manufacturer of the insulators and have minimum 320 mm creepage distance and AB switchs contacts shall be of copper/ copper alloy. The AB switch shall be of following current rating: 200 A

1

3971

3971

... More
Erection of MS Distribution box as per drg No. CEE/E-689 Revision No. 3 along with MCCB 400 A, Bus bar made out of Aluminium strips 40 x 10 mm,aluminium 'J' type fuse links (Set of 3) for 4 feeder arrangement with 1 no of moulded case circuit breaker (MCCB) of 200A, 415V, AC 50 Hz for 200 KVA Distribution Transformer centre

1

4687

4687

... More
Erection of Single core XLPE Insulated PVC Sheathed cable 185sqmm 1.1kV grade

40

7360

184

... More
Erection of Three and half core armoured XLPE cable of size 95 Sq.mm cross linked polyethelene insulated, PVC shealthed 3.5 core 95 sqmm cable with galvanized steel strip armoured aluminium cable of 1100 volts grade suitable for 3 phase earthed system and conforming to IS: 7098 (Part-I)/1988 as amended upto date.

24

3576

149

... More
Erection of 11 KV , 200 A Horn gap fuse unit (Set of three) shall be as per enclosed drg No. CEE/E-786. Revision 3 and detailed specifications enclosed herewith.

1

3368

3368

... More
Erection of 9 KV, 5 KA nominal discharge current metal oxide gapless distribution class Lightning arrestor conforming to IEC-600994-4 and IS: 3070 part 3 1993 as amended upto date suitable for 11 KV 50 HZ effectively earthed neutral system with necessary mounting arragements and connector suitable to connect ASCR conductor upto overall diameter 12.30 mm

3

522

174

... More
Erection of HDGI structure material for DP. Each trasformer centre DP consist of HDGI structure material as follows: a) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for incoming line & installation of disc insulators b) GI channel ISMC75x40x7.3mm 2.75mtrs long 2 pieces for GOAB switch c) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for HG fuses d) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for installation of lightening arrestor e) GI channel ISMC 100x50x7.3mm 2.75 mtrs long 2 pieces for installation of Trasformer f) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for side support of trasformer g) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 4 pieces for installation of any other items h) GI channel ISMC 100x40x7.3mm 0.52 mtrs long 2 pieces for installation of Transformer base channel

274

12878

47

... More
Erection of Earthing complete with 40mm GI Pipe, 2.5 mts long alongwith 20 kgs each salt, charcoal complete.

6

14664

2444

... More
Erection of Enamelled danger boards 11000 Volts as per drg no. CEE/E-490

4

228

57

... More
Erection of HDGI L.T. 2 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-491 for 9 mtr Rcc pole

3

696

232

... More
Erection of HDGI L.T. 4 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-491 for 9mtr Rcc pole

6

1566

261

... More
Erection of X-arms clamps SA/LA of 9mtrs pole

21

945

45

... More
Erection of L.T. brown glazed porcelain pin insulators of size 100mmx70mm conforming to type 1 fig 1 of IS: 1445/1977 with amendment 2 of Feb 1981 (second revision) as amended upto date. Minimum failing load shall be 3.5 KN with Forged GI pin conforming to IS 7935/1975 as amended upto date suitable for LT porcelain pin insulator type 1 conforming to fig 1 of IS: 1445/77 with amendment no 2 feb 1981, of size 100 x 70 mm. GI pin shall comprise of GI nut and spring washer and conform to fig No 2 of IS: 7935/1975. Minimum failing load of pin shall be 3.5 KN

20

3460

173

... More
Erection of LT brown glazed shackle Insulator of size 100 mm x 115 mm conforming to fig No. 4 and type 2 fo IS: 1445/77 as amended upto date. Minimum failing load shall be 16 KN with GI hardware suitable for LT shackle insulator of size 100 x 115 mm conforming to type 2 fig 4 of IS: 1445/77 as amended upto date. Hardware or fitting shall conform to fig 4 of IS: 7935-1975 as amended upto date comprise fo 2 GI strips, 2 GI bolts and 2 nuts with spring washers.

10

2080

208

... More
Erection of Stay clamp for 9 mtr Rcc Pole

4

316

79

... More
Erection of HDGI Cut point channel 75X40X 6mm,1.3 mts long (8.84kgs)

4

1968

492

... More
Erection of HDGI 11KV "V" shape cross arm of channel ISMC 75 x 40 x 7.3mm as per gdr. No. CEE/E-408-R1

4

1352

338

... More
Erection of 11 Disc Insulators ball and socket type, A porcelain brown glazed duly cemented at factory with MCI socket cap, forged steel ball pin and supplied with Phosphor bronze "W" split pin as per IS 731-1971 as amended upto date. Minimum failing load 45 KN Pin ball diameter 16 mm. Minimum Creepage distance 320 mm with 2 bolted type hardware fitting 70KN suitable for 11 KV ball and socket type disc insulators of 16 mm pin, failing load of 70 KN and suitable for ACSR conductor of size upto 18 mm diameter. The metal parts shall be as per drg No CC/E-482-Rev-2 Benclosed and conform to IS-2486 part 1-1993, 2486 Part-2-1989 as amended upto date.

21

7875

375

... More
Erection of HDGI Top fitting X-arm channel 75X40,0.7mts long(4.74kgs)

4

912

228

... More
Erection of 11 KV brown glazed porcelain Pin Insulator with minimum failing load of 5 KN and the minimum creepage distance of 320mm conforming to IS 731-1971 as amended upto date. And forged GI pin conforming to IS 2486 part 1 & 2 as amended upto date suitable for 11 KV glazed porcelain pin insulators conforming to IS 731/71 as amended upto date. GI pin shall conform to reference S-165 N fig 5 of IS 2486/(part-II)/74 as amended upto date. Dimension X in said fig shall be 150mm (screwed 100mm). Pin shall be supplied along with one suitable GI hexagonal nut and GI spring washer. Minimum failing load of pin shall be 10 KN.

12

1824

152

... More
Erection of HDGI Nut bolts 65X100mm

9.6

288

30

... More
Erection of Stay set complete for 9.0 mtr RCC pole

6

14795

2465.88

... More
Erection of AAC conductor hard drawn stranded all aluminium conductor conforming IS 398(Part-1/96) as amended upto date of following sizes 7/3.10 mm ANT conductor for phases

0.1

663

6634

... More
Erection of AAC conductor hard drawn stranded all aluminium conductor conforming IS 398(Part-1/96) as amended upto date of following sizes 7/2.21 mm GNAT conductor for double neutral & guadings.

0.1

618

6183

... More
Erection of ACSR 'Weasel' conductor confirming ISI specification IS: 398 (part-1/96) as amended upto date of following sizes 6/1/2.59 mm for guarding

0.6

4266

7110

... More
Removing & Re-stringing of ANT conductor

0.24

2388

9951

... More
Removing & Re-stringing of GNAT conductor

0.12

1112

9274.5

... More
Removing & Re-stringing of Weasel Conductor

0.24

2559

10665

... More
Removing rehoisting of Transformer 200KVA

1

23457

23457

... More
Removing of 11KV Disc Insulator

9

1687

187.5

... More
Removing of 2 pin x-arm

1

116

116

... More
Removing of 4 pin x-arm

2

261

130.5

... More
Removing of LT shackle insulator with M.P

10

1040

104

... More
Removing of Stay clamp

1

39

39.5

... More
Removing of Cut point channel

1

246

246

... More
Removing of 11 KV Vshape X arm

1

169

169

... More
Removing of Top fitting

1

45

45.5

... More
Removing of 11 KV Pin insulators

3

228

76

... More
Removing of GOAB Switch 200amp

1

1985

1985.5

... More
Removing of Lightening arrestor

3

261

87

... More
Removing of HG fuse unit

1

1684

1684

... More
Removing of Distribution Box

1

4397

4397.5

... More
Removing of XLPE cable 3.5C X 240 sqmm

12

1632

136

... More
Removing of XLPE cable 3.5C X 95 sqmm

24

1788

74.5

... More
Removing of RCC pole 9 mtr long

1

2204

2204

... More
Removing of Rail Pole 90LB

2

21050

10525

... More
Removing of structural material

100

2350

23.5



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.