Electricity Department Tender

View complete overview of Goa Electricity Department Tender

Electricity Department Tender

Works
Civil And Construction
Electrical Generators And Transformers
Electrical and Electronics
Eprocure
Opening Date4 Aug 2023
Closing Date8 Sep 2023
Tender Amount₹ 19,12,468 
Notes
Download

Costs

  • EMD

    ₹ 38,249
  • Document Cost

    ₹ 1,000
  • Tender Fee

    ₹ 3,825

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
XLPE cable armoured 3 ½ C X 185 sq.mm 1.1 KV Grade

30

40020

1334

... More
Outdoor main Switchboard for 400KVA transformer cenetr made od CRCA sheet with PU Painted and complete with all accessories and HDGI mounting channels as there are UG connections.

1

269008

269008

... More
Supply and erection of Distribution Boxes (M.S) with 400Amps MCCB & Kit-Kat fuses for 200KVA Distribution Transformers. As per drawing No.CEE/E-689 Revision No.3 alongwith 12 nos. of 400A Kitkat Porcelain fuse carrier and base with extended terminals conforming in general to drawing No.EE-II/7/2002 with 1 no. moulded case circuit breaker (MCCB), 415V, AC, 50Hz with extended terminals conforming to IS 13947-2 as amended upto date

1

63140

63140

... More
Distribution Transformer Metering Unit

1

25688

25688

... More
FRP boundary fencing

1

76667

76667

... More
Supply and erection of Modem

1

6000

6000

... More
Supply and erection of Enamelled Danger board 11000 Volts: The plate should be made from mild steel at least 1.6mm thick and vitreous enamelled white with letters, figures and convectional skull and bones in signal red color on the front side. The rear side of the plate shall be enamelled. All lettering should be centrally spaced. The corners of the plates should be rounded off. Size" 250mm x 200 mm. (as per drawing no. EE-II-3/2001, CEE/E/490)

4

992

248

... More
Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 graded granitic or basaltic stone aggregate 40 m) nominal size for foundations.

2.24

12443

5555

... More
Centering and shuttering including struttings, propping etc and removal of form work .

14.25

8022

563

... More
12mm cement plaster 1:4 (1 - cement: 4 - fine sand) for foundations.

11.82

1737

147

... More
Brick work using common burnt clay building bricks in cement mortar 1:4 (1 - cement: 4 - coarse sand) in foundation and plinth (b) with bricks of class designation 75 Kgs/sq.cm (wire cut bricks).

1.4

10382

7416

... More
Supply and spreading of 40/20mm basaltic or granitic stone aggregate in the switchyard

1.2

2704

2254

... More
Supply and erection of GI Pipe 150mm, class B

12

20172

1681

... More
Supply and erection of G.I. Nuts & Bolts 100x16mm

2.4

547

228

... More
Supply and erection of GI flat 25x5mm

45

5220

116

... More
Aluminium Crimping lug 300 sq.mm

16

1984

124

... More
Aluminium Crimping lug 95 sq.mm

4

160

40

... More
Aluminium Crimping lug 185 sq.mm

12

936

78

... More
Stringing of LT Line

-

-

-

... More
Supply and erection of RCC pole 9 mts long

8

67088

8386

... More
HDG nut bolts 100x16mm @ 0.6Kg per pair

8

1824

228

... More
Supply and erection of HDGI 4 pin 'X' arm of ISMC 75 (75 x 40mm) M.S. Channel 1.5 mtr length, Cross arm not to be welded/joined at any place, Galvanising should be hot dipped (Dimensions/specifications as per drawing no: CEE/E/705).

17

18853

1109

... More
Supply and erection of HDGI 2 pin 'X' arm of ISMC 75 (75 x 40 mm) M.S. Channel 0.75 mtr length, Cross arm not to be welded/joined at any place, (Dimensions/specifications as per drawing no: CEE/E/704).

8

4552

569

... More
Supply and stringing of GNAT' conductor 7/2.21 mm nominal aluminium area 25mm² (80 amps max. at 40° C)

1.92

48562

25293

... More
Supply and stringing of ANT' conductor 7/3.10 mm nominal aluminium area 50mm² (190 amps max. at 40° C)

1.04

50009

48086

... More
COST OF ERECTION

-

-

-

... More
Supply and erection of 400 KVA 11KV/0.4KV Distribution Transformers level II losses, Alluminium Winding, with Bimetallic Terminal Connectors, Energy Efficiency Level-II as per IS: 1180 (Part-I): 2014

1

18357

18357

... More
Supply and laying of unarmoured XLPE 1core 300sqm, cross linked polyethelene insulated, PVC sheatlthed 1 core XLPE power cable to be laid from transformer to LV panel

96

20928

218

... More
XLPE cable armoured 3 ½ C X 185 sq.mm 1.1 KV Grade

30

6840

228

... More
Outdoor main Switchboard for 400KVA transformer cenetr made od CRCA sheet with PU Painted and complete with all accessories and HDGI mounting channels as there are UG connections.

1

12500

12500

... More
Supply and erection of Distribution Boxes (M.S) with 400Amps MCCB & Kit-Kat fuses for 200KVA Distribution Transformers. As per drawing No.CEE/E-689 Revision No.3 alongwith 12 nos. of 400A Kitkat Porcelain fuse carrier and base with extended terminals conforming in general to drawing No.EE-II/7/2002 with 1 no. moulded case circuit breaker (MCCB), 415V, AC, 50Hz with extended terminals conforming to IS 13947-2 as amended upto date

1

8795

8795

... More
Removing of 200 KVA 11KV/0.4KV Distribution Transformers level II losses, Alluminium Winding, with Bimetallic Terminal Connectors, Energy Efficiency Level-II as per IS: 1180 (Part-I): 2014

1

7819

7819

... More
Dismentalling of Distribution Boxes (M.S) with 400Amps MCCB & Kit-Kat fuses for 200KVA Distribution Transformers. As per drawing No.CEE/E-689 Revision No.3 alongwith 12 nos. of 400A Kitkat Porcelain fuse carrier and base with extended terminals conforming in general to drawing No.EE-II/7/2002 with 1 no. moulded case circuit breaker (MCCB), 415V, AC, 50Hz with extended terminals conforming to IS 13947-2 as amended upto date

1

4397

4397.5

... More
Distribution Transformer Metering Unit

1

1072

1072

... More
FRP boundary fencing

1

35000

35000

... More
Supply and erection of Enamelled Danger board 11000 Volts: The plate should be made from mild steel at least 1.6mm thick and vitreous enamelled white with letters, figures and convectional skull and bones in signal red color on the front side. The rear side of the plate shall be enamelled. All lettering should be centrally spaced. The corners of the plates should be rounded off. Size" 250mm x 200 mm. (as per drawing no. EE-II-3/2001, CEE/E/490)

4

228

57

... More
Earthing complete with 2.5mts long, 40mm GI earthing pipe, class B, 20kgs each of salt and charcoal, excvation, re-filling etc.

7

17108

2444

... More
Pinth for 400kva Transformer

-

-

-

... More
Supply and erection of GI Pipe 150mm, class B

12

2184

182

... More
Supply and erection of G.I. Nuts & Bolts 100x16mm

2.4

72

30

... More
Supply and erection of GI flat 25x5mm

45

2160

48

... More
Aluminium Crimping lug 300 sq.mm

16

1616

101

... More
Aluminium Crimping lug 95 sq.mm

4

260

65

... More
Aluminium Crimping lug 185 sq.mm

12

1140

95

... More
Stringing of LT Line

-

-

-

... More
Supply and erection of RCC pole 9 mts long

8

35264

4408

... More
Supply and erection of G.I. Stay rod & plate LT/11KV line (as per drawing no. CEE/E-465 R)

4

7116

1779

... More
Supply and erection of G.I. Turn Buckle with eye bolt 11 KV (as per drawing no. CEE/E-500)

4

1068

267

... More
Supply and erection of Break insulators 8 KV (44KN): Guy strain insulators of size 90 x 65 mm. with minimum failing load of 44 KN and minimum creepage distance of 41 mm. confirming to fig 1 and designation ‘A’ of IS:5300/1969 as amended upto date. Insulators shall have markings and packing as prescribed in IS.

4

388

97

... More
Supply and erection of HDGI stay clamps for RCC Pole 9 mtr L.A., (Dimensions/specifications as per drawing no. CEE/E-524)

4

316

79

... More
HDG nut bolts 100x16mm @ 0.6Kg per pair

8

240

30

... More
HDG.I. stay wire 7/10 SWG @3.7 Kg. The Stay wire shall comply with the specific requirements of IS: 2141-1979, IS: 4826-1979 & IS: 6594-1974 or the latest versions thereof. The wires shall be of tensile grade 4 & having minimum tensile strength of 700 N/mm2 conforming to IS: 2141. HDGI stay wire standard of size 7/3.15mm (7/10SWG) wire should conform to ISS-2141/68 grade I and hot dipped galvanized as per IS 4826/1968 with up to date amendments.(Galvanising should be hot dipped Galvanised as per IS:2629/66, minimum Zinc coating of 1000 gms/sq.mtr, 140 Microns DFT), suitable for high salinity coastal areas

14.96

927

62

... More
Supply and erection of HDGI 'X' arm clamps for RCC Pole 9.00 mtr L.A., (Dimensions/specifications as per drawing no. CEE/E-524)

25

1125

45

... More
Supply and erection of HDGI 4 pin 'X' arm of ISMC 75 (75 x 40mm) M.S. Channel 1.5 mtr length, Cross arm not to be welded/joined at any place, Galvanising should be hot dipped (Dimensions/specifications as per drawing no: CEE/E/705).

17

4437

261

... More
Supply and erection of HDGI 2 pin 'X' arm of ISMC 75 (75 x 40 mm) M.S. Channel 0.75 mtr length, Cross arm not to be welded/joined at any place, (Dimensions/specifications as per drawing no: CEE/E/704).

8

1856

232

... More
Supply and erection of L.T. Pin Insulators: L. T. brown glazed porcelain pin insulators of size 100mm x 70mm conforming to type 1 fig 1 of IS:1445/1977 with amendment 2 of Feb.1981 (second revision) as amended upto date. Minimum failing load shall be 3.5kN.

45

4455

99

... More
Supply and erection of G.I. Pin for L.T.Pin Insulators: Forged G. I. Pin conforming to IS 7935/1975 as amended upto date suitable for L.T. porcelain pin insulator type 1 conforming to fig.1 of IS: 1445/77 with amendment No. 2, Feb.1981, of size 100 x 70 mm. G. I. pin shall comprise of G. I. nut and spring washer and conform to fig. No. 2 of IS: 7935/1975. Minimum failing load of pin shall be 3.5 KN.

45

3330

74

... More
Supply and erection of L.T. Shackle insulators: Brown glazed shackle insulators of size 100mm x 115mm conforming to fig.No.4 and type 2 of IS: 1445/77 as amended upto date. Minimum failing load shall be 16kN.

49

5096

104

... More
Supply and erection of Metal parts for L.T. Shackle insulators: G. I hardware suitable for L. T. shackle insulators of size 100 x 115 mm. conforming to type 2, fig. 4 of IS: 1445/77 as amended upto date. Hardware or fitting shall conform to fig. 4 of IS 7935-1975 as amended up to date, comprise of 2 G. I. strips, 2 G. I. bolts and 2 nuts with spring washers. All metal parts including nut bolts should be hot dip galvanized as per IS: 2629/66 as amended up to date. Spring washers shall be electro galvanized, (Galvanising should be hot dipped Galvanised as per IS:2629/66, minimum Zinc coating of 1000 gms/sq.mtr, 140 Microns DFT), suitable for high salinity coastal areas.

49

5096

104

... More
Supply and stringing of GNAT' conductor 7/2.21 mm nominal aluminium area 25mm² (80 amps max. at 40° C)

1.92

11871

6183

... More
Supply and stringing of ANT' conductor 7/3.10 mm nominal aluminium area 50mm² (190 amps max. at 40° C)

1.04

6899

6634



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.