Electricity Department Tender
View complete overview of Goa Electricity Department Tender
Costs
EMD
₹ 38,249Document Cost
₹ 1,000Tender Fee
₹ 3,825
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_ED_10338_1Bid Award Id
ViewTender No
tender 26(23-24)/DIV-VI/ DT 03/8/23Tender Authority
Electricity Department ViewPurchaser Address
-Website
http://eprocure.goa.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
XLPE cable armoured 3 ½ C X 185 sq.mm 1.1 KV Grade
30
40020
1334
Outdoor main Switchboard for 400KVA transformer cenetr made od CRCA sheet with PU Painted and complete with all accessories and HDGI mounting channels as there are UG connections.
1
269008
269008
Supply and erection of Distribution Boxes (M.S) with 400Amps MCCB & Kit-Kat fuses for 200KVA Distribution Transformers.
As per drawing No.CEE/E-689 Revision No.3 alongwith 12 nos. of 400A Kitkat Porcelain fuse carrier and base with extended terminals conforming in general to drawing No.EE-II/7/2002 with 1 no. moulded case circuit breaker (MCCB), 415V, AC, 50Hz with extended terminals conforming to IS 13947-2 as amended upto date
1
63140
63140
Distribution Transformer Metering Unit
1
25688
25688
FRP boundary fencing
1
76667
76667
Supply and erection of Modem
1
6000
6000
Supply and erection of Enamelled Danger board 11000 Volts:
The plate should be made from mild steel at least 1.6mm thick and vitreous enamelled white with letters, figures and convectional skull and bones in signal red color on the front side. The rear side of the plate shall be enamelled. All lettering should be centrally spaced. The corners of the plates should be rounded off.
Size" 250mm x 200 mm. (as per drawing no. EE-II-3/2001, CEE/E/490)
4
992
248
Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 graded granitic or basaltic stone aggregate 40 m) nominal size for foundations.
2.24
12443
5555
Centering and shuttering including struttings, propping etc and removal of form work .
14.25
8022
563
12mm cement plaster 1:4 (1 - cement: 4 - fine sand) for foundations.
11.82
1737
147
Brick work using common burnt clay building bricks in cement mortar 1:4 (1 - cement: 4 - coarse sand) in foundation and plinth (b) with bricks of class designation 75 Kgs/sq.cm (wire cut bricks).
1.4
10382
7416
Supply and spreading of 40/20mm basaltic or granitic stone aggregate in the switchyard
1.2
2704
2254
Supply and erection of GI Pipe 150mm, class B
12
20172
1681
Supply and erection of G.I. Nuts & Bolts 100x16mm
2.4
547
228
Supply and erection of GI flat 25x5mm
45
5220
116
Aluminium Crimping lug 300 sq.mm
16
1984
124
Aluminium Crimping lug 95 sq.mm
4
160
40
Aluminium Crimping lug 185 sq.mm
12
936
78
Stringing of LT Line
-
-
-
Supply and erection of RCC pole 9 mts long
8
67088
8386
HDG nut bolts 100x16mm @ 0.6Kg per pair
8
1824
228
Supply and erection of HDGI 4 pin 'X' arm of ISMC 75 (75 x 40mm) M.S. Channel 1.5 mtr length, Cross arm not to be welded/joined at any place, Galvanising should be hot dipped (Dimensions/specifications as per drawing no: CEE/E/705).
17
18853
1109
Supply and erection of HDGI 2 pin 'X' arm of ISMC 75 (75 x 40 mm) M.S. Channel 0.75 mtr length, Cross arm not to be welded/joined at any place, (Dimensions/specifications as per drawing no: CEE/E/704).
8
4552
569
Supply and stringing of GNAT' conductor 7/2.21 mm nominal aluminium area 25mm² (80 amps max. at 40° C)
1.92
48562
25293
Supply and stringing of ANT' conductor 7/3.10 mm nominal aluminium area 50mm² (190 amps max. at 40° C)
1.04
50009
48086
COST OF ERECTION
-
-
-
Supply and erection of 400 KVA 11KV/0.4KV Distribution Transformers level II losses, Alluminium Winding, with Bimetallic Terminal Connectors, Energy Efficiency Level-II as per IS: 1180 (Part-I): 2014
1
18357
18357
Supply and laying of unarmoured XLPE 1core 300sqm, cross linked polyethelene insulated, PVC sheatlthed 1 core XLPE power cable to be laid from transformer to LV panel
96
20928
218
XLPE cable armoured 3 ½ C X 185 sq.mm 1.1 KV Grade
30
6840
228
Outdoor main Switchboard for 400KVA transformer cenetr made od CRCA sheet with PU Painted and complete with all accessories and HDGI mounting channels as there are UG connections.
1
12500
12500
Supply and erection of Distribution Boxes (M.S) with 400Amps MCCB & Kit-Kat fuses for 200KVA Distribution Transformers.
As per drawing No.CEE/E-689 Revision No.3 alongwith 12 nos. of 400A Kitkat Porcelain fuse carrier and base with extended terminals conforming in general to drawing No.EE-II/7/2002 with 1 no. moulded case circuit breaker (MCCB), 415V, AC, 50Hz with extended terminals conforming to IS 13947-2 as amended upto date
1
8795
8795
Removing of 200 KVA 11KV/0.4KV Distribution Transformers level II losses, Alluminium Winding, with Bimetallic Terminal Connectors, Energy Efficiency Level-II as per IS: 1180 (Part-I): 2014
1
7819
7819
Dismentalling of Distribution Boxes (M.S) with 400Amps MCCB & Kit-Kat fuses for 200KVA Distribution Transformers.
As per drawing No.CEE/E-689 Revision No.3 alongwith 12 nos. of 400A Kitkat Porcelain fuse carrier and base with extended terminals conforming in general to drawing No.EE-II/7/2002 with 1 no. moulded case circuit breaker (MCCB), 415V, AC, 50Hz with extended terminals conforming to IS 13947-2 as amended upto date
1
4397
4397.5
Distribution Transformer Metering Unit
1
1072
1072
FRP boundary fencing
1
35000
35000
Supply and erection of Enamelled Danger board 11000 Volts:
The plate should be made from mild steel at least 1.6mm thick and vitreous enamelled white with letters, figures and convectional skull and bones in signal red color on the front side. The rear side of the plate shall be enamelled. All lettering should be centrally spaced. The corners of the plates should be rounded off.
Size" 250mm x 200 mm. (as per drawing no. EE-II-3/2001, CEE/E/490)
4
228
57
Earthing complete with 2.5mts long, 40mm GI earthing pipe, class B, 20kgs each of salt and charcoal, excvation, re-filling etc.
7
17108
2444
Pinth for 400kva Transformer
-
-
-
Supply and erection of GI Pipe 150mm, class B
12
2184
182
Supply and erection of G.I. Nuts & Bolts 100x16mm
2.4
72
30
Supply and erection of GI flat 25x5mm
45
2160
48
Aluminium Crimping lug 300 sq.mm
16
1616
101
Aluminium Crimping lug 95 sq.mm
4
260
65
Aluminium Crimping lug 185 sq.mm
12
1140
95
Stringing of LT Line
-
-
-
Supply and erection of RCC pole 9 mts long
8
35264
4408
Supply and erection of G.I. Stay rod & plate LT/11KV line (as per drawing no. CEE/E-465 R)
4
7116
1779
Supply and erection of G.I. Turn Buckle with eye bolt 11 KV (as per drawing no. CEE/E-500)
4
1068
267
Supply and erection of Break insulators 8 KV (44KN): Guy strain insulators of size 90 x 65 mm. with minimum failing load of 44 KN and minimum creepage distance of 41 mm. confirming to fig 1 and designation ‘A’ of IS:5300/1969 as amended upto date. Insulators shall have markings and packing as prescribed in IS.
4
388
97
Supply and erection of HDGI stay clamps for RCC Pole 9 mtr L.A., (Dimensions/specifications as per drawing no. CEE/E-524)
4
316
79
HDG nut bolts 100x16mm @ 0.6Kg per pair
8
240
30
HDG.I. stay wire 7/10 SWG @3.7 Kg. The Stay wire shall comply with the specific requirements of IS: 2141-1979, IS: 4826-1979 & IS: 6594-1974 or the latest versions thereof. The wires shall be of tensile grade 4 & having minimum tensile strength of 700 N/mm2 conforming to IS: 2141. HDGI stay wire standard of size 7/3.15mm (7/10SWG) wire should conform to ISS-2141/68 grade I and hot dipped galvanized as per IS 4826/1968 with up to date amendments.(Galvanising should be hot dipped Galvanised as per IS:2629/66, minimum Zinc coating of 1000 gms/sq.mtr, 140 Microns DFT), suitable for high salinity coastal areas
14.96
927
62
Supply and erection of HDGI 'X' arm clamps for RCC Pole 9.00 mtr L.A., (Dimensions/specifications as per drawing no. CEE/E-524)
25
1125
45
Supply and erection of HDGI 4 pin 'X' arm of ISMC 75 (75 x 40mm) M.S. Channel 1.5 mtr length, Cross arm not to be welded/joined at any place, Galvanising should be hot dipped (Dimensions/specifications as per drawing no: CEE/E/705).
17
4437
261
Supply and erection of HDGI 2 pin 'X' arm of ISMC 75 (75 x 40 mm) M.S. Channel 0.75 mtr length, Cross arm not to be welded/joined at any place, (Dimensions/specifications as per drawing no: CEE/E/704).
8
1856
232
Supply and erection of L.T. Pin Insulators: L. T. brown glazed porcelain pin insulators of size 100mm x 70mm conforming to type 1 fig 1 of IS:1445/1977 with amendment 2 of Feb.1981 (second revision) as amended upto date. Minimum failing load shall be 3.5kN.
45
4455
99
Supply and erection of G.I. Pin for L.T.Pin Insulators: Forged G. I. Pin conforming to IS 7935/1975 as amended upto date suitable for L.T. porcelain pin insulator type 1 conforming to fig.1 of IS: 1445/77 with amendment No. 2, Feb.1981, of size 100 x 70 mm. G. I. pin shall comprise of G. I. nut and spring washer and conform to fig. No. 2 of IS: 7935/1975. Minimum failing load of pin shall be 3.5 KN.
45
3330
74
Supply and erection of L.T. Shackle insulators: Brown glazed shackle insulators of size 100mm x 115mm conforming to fig.No.4 and type 2 of IS: 1445/77 as amended upto date. Minimum failing load shall be 16kN.
49
5096
104
Supply and erection of Metal parts for L.T. Shackle insulators: G. I hardware suitable for L. T. shackle insulators of size 100 x 115 mm. conforming to type 2, fig. 4 of IS: 1445/77 as amended upto date. Hardware or fitting shall conform to fig. 4 of IS 7935-1975 as amended up to date, comprise of 2 G. I. strips, 2 G. I. bolts and 2 nuts with spring washers.
All metal parts including nut bolts should be hot dip galvanized as per IS: 2629/66 as amended up to date. Spring washers shall be electro galvanized, (Galvanising should be hot dipped Galvanised as per IS:2629/66, minimum Zinc coating of 1000 gms/sq.mtr, 140 Microns DFT), suitable for high salinity coastal areas.
49
5096
104
Supply and stringing of GNAT' conductor 7/2.21 mm nominal aluminium area 25mm² (80 amps max. at 40° C)
1.92
11871
6183
Supply and stringing of ANT' conductor 7/3.10 mm nominal aluminium area 50mm² (190 amps max. at 40° C)
1.04
6899
6634