Opening Date6 Jan 2024
Closing Date20 Jan 2024
Tender Amount₹ 2,96,78,373 
Notes
Download

Costs

  • EMD

    ₹ 5,93,567
  • Document Cost

    ₹ 1,500
  • Tender Fee

    ₹ 6,000

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Providing of Cement concrete in the ratio 1:2:4(1 cement: 2 Sand, 4 graded granite/basaltic, aggregate 20mm nominal size) including cost of centering, shuttering & muffing 0.4mts above the ground & properly curved

13.2

73326

5555

... More
Supply of Cross Arm Channel 4Pin .The cross arms shall be made of M.S. channel of ISMC-75 vide table 2 of IS: 8081 1964 . The cross arms shall be without any joints. The cross arms shall be hot dipped galvanized generally conforming to IS - 2633/72. The length of the 4pin cross arm shall be 1110mm with 4 holes of 22 dia each on each flange section. In addition 2 holes of size 18mm x 40mm slotted holes shall be provided on the cross arm for clamping arrangement to the pole. The length of the 4pin side cross arm shall be 1410mm with 4 holes of 22 dia each on each flange section. In addition 2 holes of size 18mm x 40mm slotted holes shall be provided on the cross arm 40 mm from the left edge of the X-arm for clamping arrangement to the pole & two holes of size 17mm dia at 355mm & 660mm from the slotted hole for arrangement to fix angle support. The angle support shall be of ISA 50x50x6mm G.I. with 17 mm dia holes at the two ends. The other end of the angle shall be clamps utilizing suitable G. I. stay clamps of length 312mm end to end

990

1097910

1109

... More
Supply of Cross Arm Channel 2Pin .The cross arms shall be made of M.S. channel of ISMC-75 vide table 2 of IS: 8081 1964 . The cross arms shall be without any joints. The cross arms shall be hot dipped galvanized generally conforming to IS - 2633/72. The length of the 4pin cross arm shall be 1110mm with 4 holes of 22 dia each on each flange section. In addition 2 holes of size 18mm x 40mm slotted holes shall be provided on the cross arm for clamping arrangement to the pole. The length of the 4pin side cross arm shall be 1410mm with 4 holes of 22 dia each on each flange section. In addition 2 holes of size 18mm x 40mm slotted holes shall be provided on the cross arm 40 mm from the left edge of the X-arm for clamping arrangement to the pole & two holes of size 17mm dia at 355mm & 660mm from the slotted hole for arrangement to fix angle support. The angle support shall be of ISA 50x50x6mm G.I. with 17 mm dia holes at the two ends. The other end of the angle shall be clamps utilizing suitable G. I. stay clamps of length 312mm end to end

791

450079

569

... More
Supply of 11 KV V shape cross arm.Cross arms shall be made of HDGI channel of size ISMC 75X40X7.3mm. hot dip galvanizing generally conforming to IS – 2633/72 . The cross arm shall not be welded/joined at any place except as specified

11

16159

1469

... More
Supply of Cut point Channel 1.3 mtr long.Cross arms shall be made of HDGI channel of size ISMC 75X40X7.3mm. hot dip galvanizing generally conforming to IS – 2633/72 . The cross arm shall not be welded/joined at any place except as specified

11

21549

1959

... More
Supply of HDGI Top fitting for 11KV. Hot dip galvanizing generally conforming to IS – 2633/72

11

1991

181

... More
Supply of HDGI Top fitting cross arm ISMC channel,75x40mm,0.7mts long. Hot dip galvanizing generally conforming to IS – 2633/72

11

9009

819

... More
Supply of Guard cross arm 1.5 mtr long.Cross arms shall be made of HDGI channel of size ISMC 75X40. hot dip galvanizing generally conforming to IS – 2633/72 . The cross arm shall not be welded/joined at any place except as specified

22

48312

2196

... More
Supply of GI Xarm clamp LA for 9.0mts pole.shall be hot dipped galvanized generally conforming to IS - 2633/72

477

126882

266

... More
Supply of GI Xarm clamp SA for 9.0mts pole.shall be hot dipped galvanized generally conforming to IS - 2633/73

310

82460

266

... More
Supply of GI stay clamp LA for 9.0mts pole.shall be hot dipped galvanized generally conforming to IS - 2633/73

110

54010

491

... More
Supply of GI Xarm clamp LA for 7.5mts pole.shall be hot dipped galvanized generally conforming to IS - 2633/74

1243

228712

184

... More
Supply of GI Xarm clamp SA for 7.5mts pole.shall be hot dipped galvanized generally conforming to IS - 2633/75

7

1288

184

... More
Supply of 11 KV Pin Insulator with H.D.G.I. Pin 11 KV brown glazed porcelain pin insulator with minimum failing load of 5 KN and the Minimum creepage distance of 320 mm conforming to IS 731-1971 as amended upto date.Insulators shall be marked and packed as per IS

33

22869

693

... More
Supply of 11 KV Disc Insulators 45KN with H.D.G.I. Metal parts.11 KV disc insulators ball and socket type, type ‘A’ porcelain brown glazed duly cemented at factory with MCI socket cap, forged steel ball pin and supplied with Phosphor bronze “W” split pin as per IS 731-1971 as amended upto date. Pin ball diameter 16 mm. Minimum Creepage distance 320 mm. Ferrous parts shall be galvanized as per relevant IS

33

78045

2365

... More
Supply of LT pin insulator with GI pin

3545

932335

263

... More
Supply of Insulator -(LT) Shackle .L.T. brown glazed shackle insulators of size 100mm x 115mm conforming to fig.No.4 and type 2 of IS: 1445/77 as amended upto date. Minimum failing load shall be 16kN. Insulators shall have marking and packing as prescribed in IS

2492

927024

372

... More
Supply of ACSR 'WEASEL' of size ( 6/1/2.59mm) for earthing and jumpering .Packing and marking of drum will be as per IS:Conductor length shall be 1500 mtr. with tolerance of +/- 5%

2.75

91874

33409

... More
Supply of conductor-AA ANT, 2. 7/3.10 mm .

102

4904772

48086

... More
Supply of conductor -AA GNAT,1. 7/2.21 mm,

128.32

3245597

25293

... More
Supply of Anticlimbing device(barbed wire).Hot dip galvanized steel barbed wire type 4 conforming to IS:278/1962 as amended upto date and galvanization conforming to IS:4826/1979as amended upto date

22

3190

145

... More
Supply of Enamelled danger board of size 250mm x 200mm

22

5456

248

... More
Supply of Earthing complete with 2.5mts long, 40mm GI earthing pipe, class B, 20kgs each of salt and charcoal, excvation, re-filling etc.Earthing pipe made of Hot Dip galvanized steel tube of heavy class, 40mm nominal bore conforming to IS 1239 Part 1 1990 as amended upto date and Hot Dip zinc coating shall conform to IS 4736-1968 as amended upto date

66

292248

4428

... More
Supply of Stay set complete for 9.0 mts RCC Pole.HDGI Stay Sets Complete Comprising of stay rod with plate, HDGI stay wire of size 7/10swg, Break insulator of 15KV/8KV,HDGI turn buckle with eye bolt, suitable HDGI stay clamps, HDGI nut bolts, . The Stay wire shall comply with the specific requirements of IS: 2141-1979, IS: 4826-1979 & IS: 6594-1974 or the latest versions thereof and also as per the specifications enclosed.

176

752400

4275

... More
Supply of Stay set complete for 7.5 mts RCC Pole.HDGI Stay Sets Complete Comprising of stay rod with plate, HDGI stay wire of size 7/10swg, Break insulator of 15KV/8KV,HDGI turn buckle with eye bolt, suitable HDGI stay clamps, HDGI nut bolts, . The Stay wire shall comply with the specific requirements of IS: 2141-1979, IS: 4826-1979 & IS: 6594-1974 or the latest versions thereof and also as per the specifications enclosed.

232

922664

3977

... More
Supply of HDGI Structure Materials. shall be hot dipped galvanized

3014

509366

169

... More
Supply of 11 KV GOAB switch with 200 A.12 KV rated voltage GOAB switches tilting type, outdoor, manually operated, triple pole, single break, conforming to IS: 9921-Part1 to V as amended upto date and detailed specifications enclosed herewith. Each set shall comprise of six pedestal and three tilting post insulators. Insulator should be factory cemented by the manufactures of the insulators and have minimum 320mm creepage distance and AB switches contacts shall be of copper/copper alloy

11

258885

23535

... More
Supply of 11 KV HG fuse,200A, Horn gap type fuse I.TECHNICAL PARTICULARS: 1. Highest System voltage : 12 KV (R.M.S) 2. Impulse voltage withstand voltage : 75 KV (Peak) 3. One minute power frequency withstand voltage : 35 KV (R.M.S.) 4. Continuous current rating of the unit : 200 Amps

11

114950

10450

... More
Supplyof 9 KV, 5A Lightning Arrestor, pole mounted.9 KV, 5 KA nominal discharge current Metal Oxide gapless distribution class lightning arrestor conforming to IEC-60099-4 and IS 3070 Part 3 1993 as amended upto date suitable for 11 KV 50 HZ effectively earthed neutral system with necessary mounting arrangements and connector suitable to connect ACSR conductor upto overall diameter 12.30 mm.The marking of the Lightning Arrestors shall be as per IS

33

100089

3033

... More
Supply of MS Distribution box complete.M. S. distribution box MCCB of 400 Amps capacity Kit Kat Porcelain fuse carrier and base with extended terminals.

11

532257

48387

... More
Supply of HDGI nuts & bolts.G.I. Hexagonal head bolts and hexagonal nuts conforming to IS 1363 part 1 to 3 1992 as amended upto date.The bolts and nuts shall be hot dip galvanized as per IS: 2629-1985 as amended upto date

1004

228912

228

... More
Supply of XLPE unarmoured cable 1 core 240 sq.mm.The unarmoured cable shall be of 1 core and of sizes as required i.e.185Sq.mm that shall be suitably terminated at both the ends with appropriate sizes of Aluminum lugs duly crimped using a crimping tool. Appropriate sizes of G.I / Brass nut / bolts / washers shall be used for firmly connecting the same to the MCCB’s/Transformer L.T. Bushings/Outgoing LT feeder

120

43920

366

... More
Supply of XLPE unarmoured cable 1 core 120 sq.mm.The unarmoured cable shall be of 1core and of sizes as required i.e.120 Sq.mm that shall be suitably terminated at both the ends with appropriate sizes of Aluminum lugs duly crimped using a crimping tool. Appropriate sizes of G.I / Brass nut / bolts / washers shall be used for firmly connecting the same to the MCCB’s/Transformer L.T. Bushings/Outgoing LT feeder

600

98400

164

... More
Supply of XLPE unarmoured cable 1 core 95 sq.mm(For Neutral).The unarmoured cable shall be of 1core and of sizes as required i.e.120 Sq.mm that shall be suitably terminated at both the ends with appropriate sizes of Aluminum lugs duly crimped using a crimping tool. Appropriate sizes of G.I / Brass nut / bolts / washers shall be used for firmly connecting the same to the MCCB’s/Transformer L.T. Bushings/Outgoing LT feeder

560

71680

128

... More
Supply of Aluminum crimping lugs shall conform to IS: 8309-1976 as amended upto date. Lugs shall be made of aluminium of grade 1E of IS 5082-1969 suitable for aluminium cables of following sizes: 1)240Sq.mm

24

2256

94

... More
Supply of Aluminum crimping lugs shall conform to IS: 8309-1976 as amended upto date. Lugs shall be made of aluminium of grade 1E of IS 5082-1969 suitable for aluminium cables of following sizes: 1. 120 Sq.mm.

120

6480

54

... More
Supply of Aluminum crimping lugs shall conform to IS: 8309-1976 as amended upto date. Lugs shall be made of aluminium of grade 1E of IS 5082-1969 suitable for aluminium cables of following sizes: 1. 95Sq.mm.

112

4480

40

... More
Supply of Aluminum crimping lugs shall conform to IS: 8309-1976 as amended upto date. Lugs shall be made of aluminium of grade 1E of IS 5082-1969 suitable for aluminium cables of following sizes: 1. 70Sq.mm.

110

3740

34

... More
Supply of FRP Fencing complete with Gate around every distribution sub-station containing RMU, one distribution transformer and one LV switchboard including danger plate (Size  4Mx3Mx2M) with Concreting for FRP Fencing supports with plinth (0.3x0.3x0.5) Cu.m. x 12 nos. Each ratio 1:3:6

1

76667

76667

... More
Erection Cost

-

-

-

... More
Erection of 9 mts. long RCC poles .The poles should be as per drawing approved by CEE and conforming to IS standards as amended upto date. The Component used for pole shall conform to following IS amended upto date.

185

815480

4408

... More
Erection of 7.5mts. long RCC poles .The poles should be as per drawing approved by CEE and conforming to IS standards as amended upto date. The Component used for pole shall conform to following IS amended upto date.

330

1217370

3689

... More
Fixing of Cross Arm Channel 4Pin .The cross arms shall be made of M.S. channel of ISMC-75 vide table 2 of IS: 8081 1964 . The cross arms shall be without any joints. The cross arms shall be hot dipped galvanized generally conforming to IS - 2633/72. The length of the 4pin cross arm shall be 1110mm with 4 holes of 22 dia each on each flange section. In addition 2 holes of size 18mm x 40mm slotted holes shall be provided on the cross arm for clamping arrangement to the pole. The length of the 4pin side cross arm shall be 1410mm with 4 holes of 22 dia each on each flange section. In addition 2 holes of size 18mm x 40mm slotted holes shall be provided on the cross arm 40 mm from the left edge of the X-arm for clamping arrangement to the pole & two holes of size 17mm dia at 355mm & 660mm from the slotted hole for arrangement to fix angle support. The angle support shall be of ISA 50x50x6mm G.I. with 17 mm dia holes at the two ends. The other end of the angle shall be clamps utilizing suitable G. I. stay clamps of length 312mm end to end

990

258390

261

... More
Fixing of Cross Arm Channel 2Pin .The cross arms shall be made of M.S. channel of ISMC-75 vide table 2 of IS: 8081 1964 . The cross arms shall be without any joints. The cross arms shall be hot dipped galvanized generally conforming to IS - 2633/72. The length of the 4pin cross arm shall be 1110mm with 4 holes of 22 dia each on each flange section. In addition 2 holes of size 18mm x 40mm slotted holes shall be provided on the cross arm for clamping arrangement to the pole. The length of the 4pin side cross arm shall be 1410mm with 4 holes of 22 dia each on each flange section. In addition 2 holes of size 18mm x 40mm slotted holes shall be provided on the cross arm 40 mm from the left edge of the X-arm for clamping arrangement to the pole & two holes of size 17mm dia at 355mm & 660mm from the slotted hole for arrangement to fix angle support. The angle support shall be of ISA 50x50x6mm G.I. with 17 mm dia holes at the two ends. The other end of the angle shall be clamps utilizing suitable G. I. stay clamps of length 312mm end to end

791

183512

232

... More
Fixing of 11 KV V shape cross arm.Cross arms shall be made of HDGI channel of size ISMC 75X40X7.3mm. hot dip galvanizing generally conforming to IS – 2633/72 . The cross arm shall not be welded/joined at any place except as specified

11

3718

338

... More
Fixing of Cut point Channel 1.3 mtr long.Cross arms shall be made of HDGI channel of size ISMC 75X40X7.3mm. hot dip galvanizing generally conforming to IS – 2633/72 . The cross arm shall not be welded/joined at any place except as specified

11

5412

492

... More
Fixing of HDGI Top fitting for 11KV. Hot dip galvanizing generally conforming to IS – 2633/72

11

682

62

... More
Fixing of HDGI Top fitting cross arm ISMC channel,75x40mm,0.7mts long. Hot dip galvanizing generally conforming to IS – 2633/72

11

2508

228

... More
Fixing of Guard cross arm 1.5 mtr long.Cross arms shall be made of HDGI channel of size ISMC 75X40. hot dip galvanizing generally conforming to IS – 2633/72 . The cross arm shall not be welded/joined at any place except as specified

22

12012

546

... More
Fixing of GI Xarm clamp LA for 9.0mts pole.shall be hot dipped galvanized generally conforming to IS - 2633/72

477

21465

45

... More
Fixing of GI Xarm clamp SA for 9.0mts pole.shall be hot dipped galvanized generally conforming to IS - 2633/73

310

13950

45

... More
Fixing of GI stay clamp LA for 9.0mts pole.shall be hot dipped galvanized generally conforming to IS - 2633/73

110

8690

79

... More
Fixing of GI Xarm clamp LA for 7.5mts pole.shall be hot dipped galvanized generally conforming to IS - 2633/74

1243

39776

32

... More
Fixing of GI Xarm clamp SA for 7.5mts pole.shall be hot dipped galvanized generally conforming to IS - 2633/75

7

224

32

... More
Fixing of 11 KV Pin Insulator with H.D.G.I. Pin 11 KV brown glazed porcelain pin insulator with minimum failing load of 5 KN and the Minimum creepage distance of 320 mm conforming to IS 731-1971 as amended upto date.Insulators shall be marked and packed as per IS

33

5016

152

... More
Fixing of 11 KV Disc Insulators 45KN with H.D.G.I. Metal parts.11 KV disc insulators ball and socket type, type ‘A’ porcelain brown glazed duly cemented at factory with MCI socket cap, forged steel ball pin and supplied with Phosphor bronze “W” split pin as per IS 731-1971 as amended upto date. Pin ball diameter 16 mm. Minimum Creepage distance 320 mm. Ferrous parts shall be galvanized as per relevant IS

33

10956

332

... More
Erection of LT pin insulator with GI pin

3545

613285

173

... More
Fixing of Insulator -(LT) Shackle .L.T. brown glazed shackle insulators of size 100mm x 115mm conforming to fig.No.4 and type 2 of IS: 1445/77 as amended upto date. Minimum failing load shall be 16kN. Insulators shall have marking and packing as prescribed in IS

2492

518336

208

... More
Stringing of ACSR 'WEASEL' of size ( 6/1/2.59mm) for earthing and jumpering .Packing and marking of drum will be as per IS:Conductor length shall be 1500 mtr. with tolerance of +/- 5%

2.75

19552

7110

... More
Stringing of conductor-AA ANT, 2. 7/3.10 mm .

102

676668

6634

... More
Stringing of conductor -AA GNAT,1. 7/2.21 mm,

128.32

793402

6183

... More
Fixing of Anticlimbing device(barbed wire).Hot dip galvanized steel barbed wire type 4 conforming to IS:278/1962 as amended upto date and galvanization conforming to IS:4826/1979as amended upto date

22

1012

46

... More
Fixing of Enamelled danger board of size 250mm x 200mm

22

1254

57

... More
ErectionEarthing complete with 2.5mts long, 40mm GI earthing pipe, class B, 20kgs each of salt and charcoal, excvation, re-filling etc.Earthing pipe made of Hot Dip galvanized steel tube of heavy class, 40mm nominal bore conforming to IS 1239 Part 1 1990 as amended upto date and Hot Dip zinc coating shall conform to IS 4736-1968 as amended upto date

66

175890

2665

... More
Erection of Stay set complete for 9.0 mts RCC Pole.HDGI Stay Sets Complete Comprising of stay rod with plate, HDGI stay wire of size 7/10swg, Break insulator of 15KV/8KV,HDGI turn buckle with eye bolt, suitable HDGI stay clamps, HDGI nut bolts, conforming to drawings approved. The Stay wire shall comply with the specific requirements of IS: 2141-1979, IS: 4826-1979 & IS: 6594-1974 or the latest versions thereof and also as per the specifications enclosed.

176

431904

2454

... More
Erection of Stay set complete for 7.5 mts RCC Pole.HDGI Stay Sets Complete Comprising of stay rod with plate, HDGI stay wire of size 7/10swg, Break insulator of 15KV/8KV,HDGI turn buckle with eye bolt, suitable HDGI stay clamps, HDGI nut bolts, conforming to drawings approved. The Stay wire shall comply with the specific requirements of IS: 2141-1979, IS: 4826-1979 & IS: 6594-1974 or the latest versions thereof and also as per the specifications enclosed.

232

554944

2392

... More
Providing of HDGI Structure Materials. shall be hot dipped galvanized

3014

141658

47

... More
Erection of 11 KV GOAB switch with 200 A.12 KV rated voltage GOAB switches tilting type, outdoor, manually operated, triple pole, single break, conforming to IS: 9921-Part1 to V as amended upto date and detailed specifications enclosed herewith. Each set shall comprise of six pedestal and three tilting post insulators. Insulator should be factory cemented by the manufactures of the insulators and have minimum 320mm creepage distance and AB switches contacts shall be of copper/copper alloy

11

43681

3971

... More
Fixing of 11 KV HG fuse,200A, Horn gap type fuse I.TECHNICAL PARTICULARS: 1. Highest System voltage : 12 KV (R.M.S) 2. Impulse voltage withstand voltage : 75 KV (Peak) 3. One minute power frequency withstand voltage : 35 KV (R.M.S.) 4. Continuous current rating of the unit : 200 Amps

11

37048

3368

... More
Erection of 9 KV, 5A Lightning Arrestor, pole mounted.9 KV, 5 KA nominal discharge current Metal Oxide gapless distribution class lightning arrestor conforming to IEC-60099-4 and IS 3070 Part 3 1993 as amended upto date suitable for 11 KV 50 HZ effectively earthed neutral system with necessary mounting arrangements and connector suitable to connect ACSR conductor upto overall diameter 12.30 mm.The marking of the Lightning Arrestors shall be as per IS

33

5742

174

... More
Erection of MS Distribution box complete.M. S. distribution box MCCB of 400 Amps capacity Kit Kat Porcelain fuse carrier and base with extended terminals.

11

51557

4687

... More
Removing & re-erection of 200KVA Distribution Transformer

3

70371

23457

... More
Removing & re-erection of 100KVA Distribution Transformer

8

132204

16525.5

... More
Removing & re-erection of Distribution Transformer Metering Unit, with DLMS protocol energy meter

11

17688

1608

... More
Providing of HDGI nuts & bolts.G.I. Hexagonal head bolts and hexagonal nuts conforming to IS 1363 part 1 to 3 1992 as amended upto date.The bolts and nuts shall be hot dip galvanized as per IS: 2629-1985 as amended upto date

1004

30120

30

... More
Erection of XLPE unarmoured cable 1 core 240 sq.mm.The unarmoured cable shall be of 1 core and of sizes as required i.e.185Sq.mm that shall be suitably terminated at both the ends with appropriate sizes of Aluminum lugs duly crimped using a crimping tool. Appropriate sizes of G.I / Brass nut / bolts / washers shall be used for firmly connecting the same to the MCCB’s/Transformer L.T. Bushings/Outgoing LT feeder

120

24000

200

... More
Erection of XLPE unarmoured cable 1 core 120 sq.mm.The unarmoured cable shall be of 1core and of sizes as required i.e.120 Sq.mm that shall be suitably terminated at both the ends with appropriate sizes of Aluminum lugs duly crimped using a crimping tool. Appropriate sizes of G.I / Brass nut / bolts / washers shall be used for firmly connecting the same to the MCCB’s/Transformer L.T. Bushings/Outgoing LT feeder

600

57000

95

... More
Erection of XLPE unarmoured cable 1 core 95 sq.mm(for Neutral).The unarmoured cable shall be of 1core and of sizes as required i.e.120 Sq.mm that shall be suitably terminated at both the ends with appropriate sizes of Aluminum lugs duly crimped using a crimping tool. Appropriate sizes of G.I / Brass nut / bolts / washers shall be used for firmly connecting the same to the MCCB’s/Transformer L.T. Bushings/Outgoing LT feeder

560

50960

91

... More
Providing of Aluminum crimping lugs shall conform to IS: 8309-1976 as amended upto date. Lugs shall be made of aluminium of grade 1E of IS 5082-1969 suitable for aluminium cables of following sizes: 1)240Sq.mm

24

2424

101

... More
Providing of Aluminum crimping lugs shall conform to IS: 8309-1976 as amended upto date. Lugs shall be made of aluminium of grade 1E of IS 5082-1969 suitable for aluminium cables of following sizes: 1. 120 Sq.mm.

120

10560

88

... More
Providing of Aluminum crimping lugs shall conform to IS: 8309-1976 as amended upto date. Lugs shall be made of aluminium of grade 1E of IS 5082-1969 suitable for aluminium cables of following sizes: 1. 95Sq.mm.

112

7280

65

... More
Providing of Aluminum crimping lugs shall conform to IS: 8309-1976 as amended upto date. Lugs shall be made of aluminium of grade 1E of IS 5082-1969 suitable for aluminium cables of following sizes: 1. 70Sq.mm.

110

6490

59

... More
Removing of Rail poles 90 lb/yd 11 mtr long

8

61876

7734.5

... More
Removing of RCC poles 9 mtr long

69

152076

2204

... More
Removing of RCC poles 7.5 mtr long

330

608685

1844.5

... More
Removing of 4 pin cross arm

989

129064

130.5

... More
Removing of 2 pin cross arm

790

91640

116

... More
Removing of HDGI 11KV V shape X-arm

11

1859

169

... More
Removing of cut point channel 1.3 mtr long

11

2706

246

... More
Removing of Top fitting for 11KV

11

341

31

... More
Removing of HDGI Top Fitting cross arm ISMC Channel, 75x40mm,0.7mtrs long

11

1254

114

... More
Removing of Shackle insulator with metal parts

2486

258544

104

... More
Removing of Pin insulator with GI Pin

3545

306642

86.5

... More
Removing & restringing of ACSR of weasel conductor

1.65

17597

10665

... More
Removing AA ANT conductor

102

338334

3317

... More
Removing AA GNAT conductor

128.32

396701

3091.5

... More
Removing of old Rail pole DP structure materials

3014

70829

23.5

... More
Removing of 11 KV GOAB switch 200A

11

21840

1985.5

... More
Removing 11 KV HG fuse set 200A

11

18524

1684

... More
Removing of 11kv Disc insulators with metal parts 45KN

33

5478

166

... More
Removing of MS Distribution Box

11

60593

5508.5

... More
Removing of lightning arrestor

33

2871

87

... More
Removing XLPE armoured cable 3 1/2 core 240sq.mm.

30

4080

136

... More
Removing XLPE armoured cable 3 1/2 core 120sq.mm.

150

13200

88

... More
Removing XLPE armoured cable 31/2 core 95sq.mm.

140

10430

74.5

... More
Providing of FRP Fencing complete with Gate around every distribution sub-station containing RMU, one distribution transformer and one LV switchboard including danger plate (Size  4Mx3Mx2M) with Concreting for FRP Fencing supports with plinth (0.3x0.3x0.5) Cu.m. x 12 nos. Each ratio 1:3:6

1

25000

25000



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.