Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_ED_13478_1Bid Award Id
ViewTender No
tender44 (23-24)/DIV-VI DT 11/1/24Tender Authority
Electricity Department ViewPurchaser Address
-Website
http://eprocure.goa.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Supply, erection, testing & commissioning of 3 core, 300 sq.mm aluminium, XLPE insulated armoured, 11KV Cable in trench
80
187040
2338
3 ½ Core XLPE Armoured cable, 1.1KV Grade 300 sq.mm
96
198240
2065
3 Core XLPE cable 11KV armoured cable 95sq.mm
15
16905
1127
H.S.11 KV Termination kit indoor 300 sq. mm XLPE 3 core
3
26520
8840
H.S.11 KV Termination kit Outdoor 300 sq. mm XLPE 3 core
1
11667
11667
H.S.11 KV Termination kit indoor 95 sq. mmXLPE 3 core
2
13462
6731
GI Flat 50x6 mm
15
3120
208
Supplying and filling of sand in plinth under floors, trenches including watering ramming consolidating, dressing, complete.
(0.2*0.45*80)
7.2
15624
2170
Supply and laying of RCC protective covers of size 600mm long x 250mm width and 50mm thick capable of bearing load of 135Kg. And covered with earth/ sand upto depth of 0.15mts. Confirming to IS 1255-1967 at non-road crossing.
133
16891
127
RCC Cable route marker.
2
1056
528
Numbering of 11KV RMU, LV Panel
2
208
104.33
Centaring and shuttering including struttings,propping etc. and removal of formwork for foundations,footings, bases for coloumns and mass concrete. (for RMU (1.1*0.96*4)= 4.25sq.mtr)
for transformer (1.5*1.27*4)= 7.62sq.mtrs)
11.87
4676
394
12mm cement plaster 1:4(1 cement:4 fine sand) (for RMU ( 0.5*0.9*4)+(1*1)=2.8sq.mtrs) (for transformer (1.3*1.3*4)+(1.4*1.4)= 8.61sq.mtrs)
11.41
2179
191
Providing and laying in position cement concrete 1:2:4 ( 1 Cement : 2 coarse sand : 4 graded granitic or basaltic stone aggregate 40 m nominal size) excluding cost of centering, shuttering and finishing: ( for RMU (1.2*1*1) = 1.2cu.mtrs) (for transformer (1.4*1.5*1.13) = 2.38cu.mtr)
3.58
21476
5999
Earthing complete with 40mm GI Pipe, 2.5 mts long alongwith 20 kgs each salt, charcoal complete.( For RMU)
8
35424
4428
HDGI flat of size 25mmx5mm for earthing ( 2X6 mtrs each for RMU
48
5568
116
300/5 LT CT ring type,measuring CT coil of rating300/5A,Class I accuracy,50Hz,660V,Burden:15VA conferming to IS2705/1992 as amended up to date.3ph,4W,Electronic Trivector Meter,LT CT operated 3X240v /5A,50Hz,class 0.5s,Category a9forDTC) with Rs232 and Optical port and compliance to BIS ICs Doc: ETD 13(6211) april,2010.Polemounted MS Box(outdoor type )Electronic Meter as per Drawing No. EE/VIII/64(REV).1.1KV Multistrand copperconductor ,XLPE insulated,armoured control cable conferming to relevent IS amended up to date and of size 4 core x 2.5sq,mm.High grade 3/4" brass gland for 4 core 2.5sqmm. cable
1
25688
25688
COST OF ERECTION
-
-
-
400 KVA 11kv/.4kv Distribution Transformers level II losses, Copper Winding, with Bimetallic Terminal Connectors, Energy Efficiency Level-II as per IS: 1180 (Part-I): 2014
1
18357
18357
Outdoor, LV Main Switchboard for 400KVA Transformer centre made of CRCA sheet with PU painted and complete with all accessories and HDGI mounting channels.
1
12500
12500
3 WAY RMU, 11KV, 630A, 21 kA 3Sec, SF6 Outdoor RMU – 2LBS + 1CB
Extensible/Non-Extensible Two (2) Motor operated load break switches (LBSs) with Manual operated earthing switches in SF6 and One (1) vacuum circuit breaker with Electrical closing and tripping along with disconnector and earthing switches SCADA Compatible and base channel. Battery charger along with batteries required for Electrical operations of RMU is in the scope of the Bidder. Each module shall consist of VPIS, FPI in LBS Module (N-1) but not less than 1 no’s per RMU. Suitable arrangement for mounting FRTU, modem or Ethernet Switch/LIU along with battery, battery charger shall be provided in RMU.
1
9720
9720
Supply, erection, testing & commissioning of 3 core, 300 sq.mm aluminium, XLPE insulated armoured, 11KV Cable in trench
80
27360
342
3 ½ Core XLPE Armoured cable, 1.1KV Grade 300 sq.mm
96
26784
279
3 Core XLPE cable 11KV armoured cable 95sq.mm
15
2985
199
H.S.11 KV Termination kit indoor 300 sq. mm XLPE 3 core
3
7644
2548
H.S.11 KV Termination kit Outdoor 300 sq. mm XLPE 3 core
1
2718
2718
H.S.11 KV Termination kit indoor 95 sq. mmXLPE 3 core
2
5076
2538
GI Flat 50x6 mm
15
720
48
Earthwork in excavation by mechanical means (hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sq.m on plan) including disposal of excavated earth lead upto 50 m and lift upto 1.5m disposed earth to be leveled and neatly dressed including providing barricading, danger lighting guarding as directed in : 1. (1.1x0.45X1) 0.495 cu.mtr per meter for cable trench. 2. (1X1X0.6) 0.6cu.mtr per RMU.
-
-
-
a) All kinds of soil (0.3*0.45*80) for 11kv Cable
10.8
5054
468
b) All types of Ordinary rock including all types of laterite rock, blasting prohibited (0.3*0.45*80) for 11kv Cable
and (1 * 1 * 0.6) for RMU
29.4
22432
763
Refilling the pipeline/foundation trenches plinth sides, foundation etc. with available excavated earth in layers not exceeding 20 cm depth consolidating each layer ramming and watering lead upto 50 M and all lifts and disposal of surplus earth as directed by Engineer in Charge.
(0.9*0.45*80)
32.4
3888
120
Supply and laying of RCC protective covers of size 600mm long x 250mm width and 50mm thick capable of bearing load of 135Kg. And covered with earth/ sand upto depth of 0.15mts. Confirming to IS 1255-1967 at non-road crossing.
133
11172
84
RCC Cable route marker.
2
512
256
Earthing complete with 40mm GI Pipe, 2.5 mts long alongwith 20 kgs each salt, charcoal complete.( For RMU)
8
21320
2665
HDGI flat of size 25mmx5mm for earthing ( 2X6 mtrs each for RMU
48
2304
48
300/5 LT CT ring type,measuring CT coil of rating300/5A,Class I accuracy,50Hz,660V,Burden:15VA conferming to IS2705/1992 as amended up to date.3ph,4W,Electronic Trivector Meter,LT CT operated 3X240v /5A,50Hz,class 0.5s,Category a9forDTC) with Rs232 and Optical port and compliance to BIS ICs Doc: ETD 13(6211) april,2010.Polemounted MS Box(outdoor type )Electronic Meter as per Drawing No. EE/VIII/64(REV).1.1KV Multistrand copperconductor ,XLPE insulated,armoured control cable conferming to relevent IS amended up to date and of size 4 core x 2.5sq,mm.High grade 3/4" brass gland for 4 core 2.5sqmm. cable
1
1072
1072