Electricity Department Tender
View complete overview of Goa Electricity Department Tender
Costs
EMD
₹ 24,41,631Document Cost
₹ 1,500Tender Fee
₹ 6,000
Summary
Work Of Bifurcation Of Existing 11kv Betalbatim And Colva Express Ug Feeders Emanating From 33/11kv Benaulim Ss To New 11kv Seraulim And 11kv Colva
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_ED_17321_1Tender No
Tender 21(2024-25)/CSCTender Authority
Electricity Department ViewPurchaser Address
-Website
http://eprocure.goa.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Supply of 3 WAY RMU 11KV, 630 Amps, Outdoor, SF6 Ring Main Unit with two Load Break Switches and one Circuit Breaker. Extensible/Non-Extensible Two (2) Motor operated load break switches (LBSs) with Manual operated earthing switches in SF6 and One (1) vacuum circuit breaker with Electrical closing and tripping along with disconnector and earthing switches SCADA Compatible and base channel. Battery charger along with batteries required for Electrical operations of RMU is in the scope of the Bidder. Each module shall consist of VPIS, FPI in LBS Module (N-1) but not less than 1 no’s per RMU. Suitable arrangement for mounting FRTU, modem or Ethernet Switch/LIU along with battery, battery charger shall be provided in RMU.
8
4520000
565000
Supply of 3 WAY RMU 11 KV, 630 amps, Outdoor, SF6 Ring Main Unit with three load break switches. Extensible/Non Extensible Three (3) Motor operated load break switches (LBSs) with Manual operated earthing switches in SF6 SCADA Compatible and base channel. Battery charger along with batteries required for Electrical operations of RMU is in the scope of the Bidder. Each module shall consist of VPIS, FPI in LBS Module (N-1) but not less than 1 no’s per RMU. Suitable arrangement for mounting FRTU , modem or Ethernet Switch/LIU along with battery, battery charger shall be provided in RMU.
9
4896000
544000
Supply of Outdoor type, heat shrinkable, three phase, end termination kit complete, for 11KV XLPE cable of size 3 x 95sq.mm .
8
81216
10152
Supply of Outdoor type, heat shrinkable, three phase, end termination kit complete, for 11KV XLPE cable of size 3 x 300sq.mm.
4
46668
11667
Supply of Indoor type, heat shrinkable, three phase, end termination kit complete, for 11KV XLPE cable of size 3 x 300sq.mm.
108
954720
8840
Supply of Indoor type, heat shrinkable, three phase, end termination kit complete, for 11KV XLPE cable of size 3 x 95sq.mm.
8
53848
6731
Supply of 11KV, three phase, Heat shrinkable, Straight Through Jointing Kit complete for XLPE cable of size 3 core 300sq.mm.
90
2660310
29559
Supply of 12 KV, 630 A ( BB - 1250A ) , 25 KA 3 Secs, 3 phase, indoor type VCB, with spring type operating mechanism, mounted on rack out type trolley, along with 3 Nos of 12 KV CT, 3 core, 400-200-/5-5 Amps, LV Compartment with Breaker control panel consisting of voltmeter, ammeter, MFM, BCPU NUMERICAL relays 61850 protocol with master and Trip Circuit supervision, LED type indication lamps, TTBs, Annunciation, 3 phase, 4 wire, DLMS energy meter with 4G modem along with Software updation in the back end system for data integration with MDM. Complete as per Technical Specification. (Outgoing)
2
2400000
1200000
Supply, Erection, Testing and Comissionig of RCC Cable route marker (400X900X100mm) (as per CEE approved drwawing) as per Technical Specifications.
300
158400
528
Supply, Laying of Warning Tapes (for entire route length) as per technical specification and drawing.
28.7
430500
15000
Supply of RCC Hume pipes for road crossings, nullah crossings, small river crossings, culverts of 250 mm inner diameter RCC pipe as per GSR 2020(Roads), alongwith required no. of collars, PCC and Masonary work as per technical specifications.
1610
1299270
807
Supply of Medium duty, HDGI Class B pipe of nominal diameter 150 mm (alongwith HDGI bends wherever required) for bridge crossing, riser pipe for 95Sq.mm & 300Sq.mm XLPE Cable etc., as per technical specifications including supporting arrangement for the pipe and 11 KV Bay.
1640
2756840
1681
Supplying & filing in plinth under floors, trenches including watering ramming consolidating, dressing, complete.
a) Sand
2128
4617760
2170
Supply of underground cable protective cover as per specification as given below: The concrete slab shall be machine made using semidry concrete that is batched in a fully automatic PLC controlled concrete batching plant & cast in a fully automatic "Vibro-Press" machine with a high vibration frequency and hydraulic pressure of 40MT, the size of the slab shall be 480mmX250mmX50mm, (+/- 2mm) & the concrete grade shall be M30 adhering to IS 456:2000 & shall have a minimum crushing strength of 30 N/mm2 (28 days strength) when tested.
64000
8640000
135
Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded granitic or basaltic stone aggregate 40 m nominal size for foundation of Ring Main Unit, Load Break Switch and 11KV Bay.
7.6
42218
5555
Centering and shutteringincluding struttings, propping etc and removal of form work for Ring Main Unit, Load Break Switch and 11 KV Bay.
25.5
14356
563
Providing of 12 mm cement plaster1:4 (1- cement: 4-fine sand ) for foundations of Ring Main Unit, Load Break Switch, and 11 KV Bay
25.63
3767
147
Laterite Masonary Works: Rubble packing with hard laterite stone under floors including watering, ramming & consolidating etc. in pipeline trenches and other foundations complete for Double circuit 33KV cable trench (0.2x0.9x1.00) i.e. 0.18 per RM
30000
11939400
397.98
Supply of G.I. earthing pipe 2500mm long, 40mm dia class B fabricated and perforated filled with homogenous mixture of 20Kgs of Charcoal, 20Kgs of salt and sand /soil complete inclusive of excavation, backfilling & spreading of excavated earth evenly with brick chamber for DSS for RMU,LBS and 11 KV Bay.
62
274536
4428
Supply and erection of HDGI flat of size 50mm x 6 mm
[Galvanising should be hot dipped Galvanised as per IS:2629/66, minimum Zinc coating of 1000 gms/sq.mtr, 140 Microns DFT, suitable for high salinity coastal areas]
580
120640
208
Cost of Erection
-
-
-
Erection, Testing and Comissioning of 3 core, 300 sq.mm. aluminium, XLPE insulated, armoured, 11KV Cable.
30000
10260000
342
Erection, Testing and Comissioning of 3 core, 95sq.mm. aluminium, XLPE armoured, 11KV Cable.
860
171140
199
Erection Testing and Comissioning of 3 WAY RMU 11KV, 630 Amps, Outdoor, SF6 Ring Main Unit with two Load Break Switches and one Circuit Breaker. Extensible/Non-Extensible Two (2) Motor operated load break switches (LBSs) with Manual operated earthing switches in SF6 and One (1) vacuum circuit breaker with Electrical closing and tripping along with disconnector and earthing switches SCADA Compatible and base channel. Battery charger along with batteries required for Electrical operations of RMU is in the scope of the Bidder. Each module shall consist of VPIS, FPI in LBS Module (N-1) but not less than 1 no’s per RMU. Suitable arrangement for mounting FRTU, modem or Ethernet Switch/LIU along with battery, battery charger shall be provided in RMU.
8
77760
9720
Erection, Testing and Comissioning of 3 WAY RMU 11 KV, 630 amps, Outdoor, SF6 Ring Main Unit with three load break switches. Extensible/Non Extensible Three (3) Motor operated load break switches (LBSs) with Manual operated earthing switches in SF6 SCADA Compatible and base channel. Battery charger along with batteries required for Electrical operations of RMU is in the scope of the Bidder. Each module shall consist of VPIS, FPI in LBS Module (N-1) but not less than 1 no’s per RMU. Suitable arrangement for mounting FRTU , modem or Ethernet Switch/LIU along with battery, battery charger shall be provided in RMU.
9
87480
9720
Erection, Testing and Comissioning of Outdoor type, heat shrinkable, three phase, end termination kit complete, for 11KV XLPE cable of size 3 x 95sq.mm .
8
21184
2648
Erection, Testing and Comissioning of Outdoor type, heat shrinkable, three phase, end termination kit complete, for 11KV XLPE cable of size 3 x 300sq.mm.
4
10872
2718
Erection, Testing and Comissioning of Indoor type, heat shrinkable, three phase, end termination kit complete, for 11KV XLPE cable of size 3 x 300sq.mm.
108
275184
2548
Erection, Testing and Comissioning of Indoor type, heat shrinkable, three phase, end termination kit complete, for 11KV XLPE cable of size 3 x 95sq.mm.
8
20304
2538
Erection, Testing & comissioning of 11KV, three phase, Heat shrinkable, Straight Through Jointing Kit complete for XLPE cable of size 3 core 300sq.mm.
90
334170
3713
Erection, Testing & comissioning of 12 KV, 630 A ( BB - 1250A ) , 25 KA 3 Secs, 3 phase, indoor type VCB, with spring type operating mechanism, mounted on rack out type trolley, along with 3 Nos of 12 KV CT, 3 core, 400-200-/5-5 Amps, LV Compartment with Breaker control panel consisting of voltmeter, ammeter, MFM, BCPU NUMERICAL relays 61850 protocol with master and Trip Circuit supervision, LED type indication lamps, TTBs, Annunciation, 3 phase, 4 wire, DLMS energy meter with 4G modem along with Software updation in the back end system for data integration with MDM. Complete as per Technical Specification. (Outgoing)
2
80000
40000
Erection, Testing and Comissionig of RCC Cable route marker (400X900X100mm) (as per CEE approved drwawing) as per Technical Specifications.
300
76800
256
Design, Supply & Erection of RCC Hume pipes for road crossings, nullah crossings, small river crossings, culverts of 250 mm inner diameter RCC pipe as per GSR 2020(Roads), alongwith required no. of collars, PCC and Masonary work as per technical specifications.
1610
408940
254
Design, Erection of Medium duty, HDGI Class B pipe of nominal diameter 150 mm (alongwith HDGI bends wherever required) for bridge crossing, riser pipe for 95Sq.mm & 300Sq.mm XLPE Cable etc., as per technical specifications including supporting arrangement for the pipe and 11 KV Bay.
1640
298480
182
Earthwork in excavation by mechanical means (hydraulic excavator/manual meansover areas (exceeding 30cm in depth, 1.5m in width as well as 10 Sq.m on plan) including disposal of excavated earth lead upto 50m and lift upto 1.5m disposed earth to be leveled and neatly dressed including providing barricading, danger lighting guarding as directed in:
a) All kinds of Soil
14500
6786000
468
Refilling the pipeline/foundation trenches plinth sides, foundation etc. with available excavated earth in layers not exceeding 20 cm depth consolidating each layer ramming & watering lead upto 50m & all lifts & disposal of surplus earth as directed by Engineer in Charge.
11684
1402080
120
Laying of underground cable protective cover as per specification as given below: The concrete slab shall be machine made using semidry concrete that is batched in a fully automatic PLC controlled concrete batching plant & cast in a fully automatic "Vibro-Press" machine with a high vibration frequency and hydraulic pressure of 40MT, the size of the slab shall be 480mmX250mmX50mm, (+/- 2mm) & the concrete grade shall be M30 adhering to IS 456:2000 & shall have a minimum crushing strength of 30 N/mm2 (28 days strength) when tested.
64000
3840000
60
Erection of G.I. earthing pipe 2500mm long, 40mm dia class B fabricated and perforated filled with homogenous mixture of 20Kgs of Charcoal, 20Kgs of salt and sand /soil complete inclusive of excavation, backfilling & spreading of excavated earth evenly with brick chamber for DSS for RMU,LBS and 11 KV Bay.
62
165230
2665
Erection of HDGI flat of size 50mm x 6 mm
580
27840
48
Laying of 11KV/LT UG cables by trenchless technology by adopting horizontal boring (HDD) . The work includes preparation of site, Boring as well as drawing of cable in in Normal soft/hard soil with minimum 8" bore size. Including supply & erection of HDPE pipe 110 mm, PN6, PE80, wall thickness 6.5mm (minimum) as per IS 4984:1995 ammendment 2016. The depth shall be 1.650m to 1.850m (1650mm-1850mm) only except at entry & exit pits where minimum depth shall be 1200mm.
1000
2800000
2800
Evaluation Notes How It Works ?