If you're typing tender ID over and again or finding it difficult to go through the cumbersome government websites for looking at Delhi tenders online. We have come up with a solution i.e. we have collated every eprocurement Delhi tender on BidAssist. Also, for any queries related to an e-tender Delhi, like the bidding process, registration process, etc., the same are explained below.
Netaji Subhas Institute Of Technology - NSIT Tender
Electrical Goods and Equipments
Electrical and Electronics
Eprocure
Opening Date7 Mar 2024
Closing Date14 Mar 2024
Tender Amount₹ 2,65,25,279
Costs
EMD
₹ 5,30,506Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_NSIT_255648_1Bid Award Id
ViewTender No
NIT No.56/VC/2023-2024/NSUTTender Authority
Netaji Subhas Institute Of Technology ViewPurchaser Address
-Website
http://http://www.nsit.ac.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
2.3 2.4 TR
28
880684
31453
2.4 2.8 TR
10
320150
32015
2.5 3.2 TR
16
524592
32787
2.6 3.6 TR
31
1029479
33209
2.7 4.0 TR
33
1121373
33981
3 Supply,installation,testing and commissioning of following minimum capacity VRV/VRF High wall type Indoor unit equipped with washable synthetic media pre-filter,fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil,electronic expansion valve, outer cabinet,cordless remote control,drain pan,necessary accessories etc.,suitable for operationon 230V±10%,50Hz,single phase AC supply,complete as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System.The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
3.1 1.0 TR
2
39400
19700
4 Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings with suitable adjustable ring type hanger supports,jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :
4.1 6.4 mm dia (OD) (Softdrawn) with tube thickness 1.2 mm with 19 mm thick insulation
180
44100
245
4.2 9.5 mm O.D. (Soft drawn)with tube thickness 1.2mm with 19 mm thick insulation
310
102610
331
4.3 12.7 mm O.D. (Soft drawn)with tube thickness 1.2mm with 19 mm thick insulation
210
97860
466
4.4 15.86 mm O.D. (Soft drawn)with tube thickness 1.2mm with 19 mm thick insulation
290
170520
588
4.5 19 mm O.D. (Hard drawn)with tube thickness 1.2mm with 19 mm thick insulation
200
141400
707
4.6 22.2 mm dia (OD) (Harddrawn) with tube thickness 1.2 mm with 19 mm thick insulation
190
164350
865
4.7 28.58 mm dia (OD) (Harddrawn) with tube thickness 1.2 mm with 19 mm thick insulation
220
243760
1108
4.8 34.9 mm dia (OD) (Harddrawn) with tube thickness 1.62 mm with 19 mm thick insulation
190
233700
1230
4.9 41.27 mm dia (OD) (Harddrawn) with tube thickness 1.62 mm with 19 mm thick insulation
170
222530
1309
5 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete and duly insulated with 9 mm thick closed cell nitrile rubber insulation as per direction of Engineer in Charge.
5.1 25 mm nominal dia Pipes
1150
469832
408.55
5.2 32 mm nominal dia Pipes
200
100190
500.95
5.3 40 mm nominal dia Pipes
150
101152
674.35
6 Supply Installation Testing and Commissioning of control cum transmission wiring of minimum 2C x 0.75 sqmm with copper sheilded cable between indoor and outdoor units as per OEM recommendation and upto the satisfaction of engineer in-charge at site.
2850
616597
216.35
7 Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
7.1 300 mm width X 50 mm depth X 1.6 mm thickness
490
471870
963
8 Cutting holes of required size in brick masonry wall/Concrete Wall for passing of copper pipes, Drain pipes, cable removing of false ceiling and re-fixing/placing back if required etc. and making good the same etc. complete as per direction of Engineer-in-charge.(The hole shall be made by core cutter)
56
16800
300
9 Supply Installation Testing and Commissioning of Refnets/ Y-Joints/ T-Joints as per OEM recommendation and upto the satisfaction of engineer in-charge at site.
270
1755000
6500
10 Supply & fixing, testing & commissioning of double door, outdoor type IP-54 floor mounted electrical distribution panel made of 2mm thick CRCA sheet 3mm thick gland plate, with 400A aluminium busbar duly power coated complete with PCC foundation & MS angle base frame (150 mm above ground & 150 mm below ground) voltmeter ammeters, indicating lamps, selector switches, etc as reqd. comprising of the following.(Panel shall be CPRI approved) Incoming 400A 4P Adjustable MCCB 25 kA, 415 volts, 50Hz, with door interlocking with all connected accessories-1No. 1 no. 0-500 Amp. Ammeter with selector switch. 1 no. Volt meter with selector switch 0-500voIts. 3 nos. RYB Led indication lamps. Outgoing 40 / 63A 4P Adjustable MCCB 25kA - 12 Nos. 25/40A 4P MCB - 6 nos. for indoor units D.B
4
1400000
350000
11 Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
1270
88900
70
12 Supply of XLPE insulated Copper conductor, 1.1 KV grade cable of following size complete as required.
12.1 4C x 16 Sq mm, Copper Armoured
300
477594
1591.98
12.2 4C X 10 Sq mm, Copper Armoured
240
248983
1037.43
12.3 3C x 2.5sqmm, Copper Flexible for IDUs
2580
371081
143.83
13 Supply of one number XLPE insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size complete as required
13.1 3.5 C X 150 Sq. mm (Aluminium Armoured)
245
371780
1517.47
14 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.
14.1 Upto 35 sq. mm (clamped with 1mm thick saddle)
2580
116100
45
15 Laying and fixing of one number PVC insulated and PVC
sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
15.1 Upto 35 sq. mm (clamped with 1mm thick saddle)
540
29700
55
15.2 Above 95 sq. mm and upto 185 sq. mm (clamped with25/40x3mm MS flat clamp)
245
37485
153
16 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
16.1 4 X 10 sq. mm (25mm)
16
4304
269
16.2 4 X 16 sq. mm (28mm)
24
7416
309
16.3 3½ X 150 sq. mm (50mm)
8
5576
697
17 Comprehensive Annual maintenance of VRV/VRF Air conditioning system provided and installed under this contract with all parts/components i.e compressor, gas charging, fan motor etc(one year free defect liability period and thereafter paid) 17.1 For 1st Year (During defect liability period)
487
-
-
17.2 For 2nd Year
487
1363600
2800
17.3 For 3rd Year
487
1431780
2940
17.4 For 4th Year
487
1503369
3087
17.5 For 5th Year
487
1577880
3240
18 Supplying and fixing following way, single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
18.1 12 way , Double door
15
34725
2315
19 Supplying and fixing 5 amps to 32 amps, rating, 240/415 volts, 'C' Curve , miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
19.1 Single Pole
150
38400
256
19.2 Single pole and neutral
15
8985
599
20 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
20.1 2 X 10 sq. mm + 1 X 6 sq. mm earth wire
340
193800
570
21 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
6
44832
7472
22 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
180
43920
244
23 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
8
5648
706
24 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
24.1 25 mm
1930
279850
145
25 Dismantling & Buy Back of old & defective following items from NSUT as per required. (Contractor / Agency should be ensure that disposal of the old / defective wastage material should be disposed off through the autorised recycler registerd under Delhi Pollution Central Board / Central Pollution Control Board. Contractor/ Agency should also submit 'Certificate of Destruction').
25.1 1/1.5 Tr capacity Window type air conditioner
75
-262500
3500
25.2 1/1.5 Tr capacity split type air conditioner
9
-36000
4000