Municipal Corporation Tender
If you're typing tender ID over and again or finding it difficult to go through the cumbersome government websites for looking at Delhi tenders online. We have come up with a solution i.e. we have collated every eprocurement Delhi tender on BidAssist. Also, for any queries related to an e-tender Delhi, like the bidding process, registration process, etc., the same are explained below.
Municipal Corporation Tender
Electrical and Electronics
Eprocure
Opening Date6 Apr 2022
Closing Date18 Apr 2022
Tender AmountRefer Documents
Costs
EMD
₹ 38,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2022_EDMC_112172_1Bid Award Id
ViewTender No
EE(E)-I/SHN/EDMC/22-23/TC-01/1Tender Authority
Municipal Corporation ViewPurchaser Address
-Website
http://https://mcdonline.nic.in/edmcportal/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Dismantling of existing 3 nos cooling tower and changing the
following defective parts :
( a) PVC Fills - (600 mm X 300 mm X 150 mm)- 200 nos.
(b) PVC Eliminator - ( 600 X 600 X !50)- 10 nos.
(c ) PVC Header pipe 200mm 8' long - 1 no.
(d) PVC sub header pipe 63 mm 8' long - 20 nos.
(e) PVC sub header end cap 63mm - 30 nos.
(f) PVC splash cap with steel screw - 50 nos.
(g) PVC 200 mm END cap - 2 nos.
(h) PVC nozzle connection 40 mm 1' - 60 nos.
(j) Sealing compound- 20 kg
(h) FRP stiching material - 20 kg
(k) Cast aluminium fan assembly - 2 nos.
(l) Labour charges for dismantling, changing defective parts and reinstallation.
(m) Cooling tower motors -2 nos. 1
1
-
-
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect. (a) 100mm dia. (32 mm thick insulation)
10
-
-
(b) 80 mm dia (32mm thick insulation)
20
-
-
(c) 65 mm dia (32 mm thick insulation)
20
-
-
(d) 50 mm dia ( 32 mm thick insulation)
50
-
-
(e) 40 mm dia ( 32 mm thick insulation)
50
-
-
(f) 32 mm dia(19 mm thick insulation)
120
-
-
(g) 25 mm dia ( 19 mm thick insulation)
50
-
-
Descaling of condensor of 120 TR AC Plant with Vaniclean,
recirculating the same to remove the scale including changing rubber gasket of end covers including complete testing etc as required.
3
-
-
Supplying, laying, fixing, testing and commissioning of following thickness closed cell elastrometric nitrile rubber of class 'O' applied by suiatable adhesive, as per specifications and as required complete in all respect. (a) 32 mm
200
-
-
Supplying & fixing of powder coated extruded aluminium
Supply Air Grills with aluminium volume control dampers as per specifications.
4
-
-
Supplying & fixing of powder coated extruded aluminium
Return Air Grills with louvers but without volume control
dampers complete as required.
4
-
-
Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. (a) Thickness 0.80 mm sheet
4
-
-
Servicing of FCU"s installed at various locations in the hospital
i/c cleaning of filters, cleaning of choked drain lines / cleaning of coils with the help of vaniclean .
65
-
-
Repairing of Primary Chilled water pump of 7.5 HP with
changing of mechanical seal, alignment, balancing complete
testing , commissioning etc as required.
1
-
-
Repairing of Primary Chilled water pump of 5 HP with changing
of mechanical seal, alignment, balancing complete testing ,
commissioning etc as required.
1
-
-
Repairing of Defective PCB of chiller machine screw compressor of 120 TR (Carrier make) i/c complete testing , commissioning etc as required.
3
-
-
Supply & pouring of synthetic oil with viscosity grade 220 for topping up the oil level suitable for screw compressor of 120 TR (Carrier make) complete as reqd.
60
-
-
Changing of syphon of size 3/8" in pipeline i/c testing ,
commissioning complete etc as required.
24
-
-
Changing of 4" dia pressure gauges installed in existing pipeline i/c complete testing , commissioning as required.
24
-
-
Top up of R-134A refrigerant in the chilling machine i/c complete testing commissioning as required.
100
-
-
Painting of MS Pipe Line of various sizes installed at various locations applying a coat of red oxide before aplying 2 coats of paints. (a) 150 to 200 mm dia
200
-
-
(b) 65 to 100 mm dia
100
-
-
(c ) 25 to 50 mm dia
250
-
-
Supply & Fixing of Pre-filter constructed in Aluminium Frame
with HDPE mesh and supporting aluminium mesh withepoxy
sealed & filtration efficiency 99% down to 5 micron particles as reqd. in the existing opening / AHU of following size. 610 x 610 x 50 MM
10
-
-
Supply & Fixing of Hepa filter constructed in Aluminium Frame
with HDPE mesh and supporting aluminium mesh withepoxy
sealed & filtration efficiency 99% down to 5 micron particles as reqd. in the existing opening / AHU of following size. (a) 610 x 610 x 305 MM
2
-
-
(b) 610 x 305 x 305 MM
2
-
-