Military Engineer Services Tender
... More
The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Spl Repair Replacement Of Lt Xlpe Ug Cables Lt Panels And Street Lights At Offrs Md Accn Mall Road P1 To P29 And Mandir Marg Offrs Qtrs No P15 To 27 And Connected Allied Works Area Of Age Sldc Under Ge U Es Delhi Cantt 10 in New Delhi, Delhi, with an estimated contract value of Rs. 48,60,000. The bid opening date for this tender is 20-12-2024 and the last date for bid submission is 17-01-2025. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.
Costs
EMD
₹ 97,500Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_689500_1Bid Award Id
ViewTender No
GE ELECT/D-92/2024-25Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
... More
All as per item No.11 here-in-before but comprising of the following :- (Near 10 Mall)
INCOMING :-
(i) MCCB 4 pole , 400 Amps,50 Hz,415 Volts, 50 KA, with thermal & Magnetic release - 01 Nos (ii) Onload changeover 400 Amps -01 No (iii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No (iv) Ammeter digital type with 4 way rotary selector switch-01No (iv) CTs ratio 400/5 A ,class 1, ISI marked -01 sets of three (v) Indicating lamp- 01 set of three
(vi) Aluminium bus bar of rating 600A - set of four (vii) Rotary handle - 02 No OUTGOING :-
(i) MCCB 4 pole , 160 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 02 Nos. (ii) MCCB 4 pole , 125 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 04 Nos.
(iii) MCCB 4 pole , 100 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 04 Nos.
(iv) Rotary handle - 10 No
PLATFORM FOR PANEL :- Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. Note :-
(i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993 (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer . (iv) Energy meter is not included in the present scope of work and shall be shifted from Old LT Panel to New LT Panel. The rate for shifting is also deemed to be included in the quoted rates.
1
-
-
... More
M&L for river washed and screened, dry sand filling in trenches for cushioning of UG cables as layers of 8 cm before laying and 15 cm after laying of cables complete all as specified and directed by Engineer- in- Charge.
Note : Measurement shall be taken after punning down.
286.98
-
-
... More
All as per srl item No 5 here-in-before but using old bricks obtained under srl item No 1 complete all as specified and directed by Engineer- in- Charge.
12654
-
-
... More
M&L for removing excavated material (ie soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point complete all as specified and directed by Engineer- in- Charge.
408.95
-
-
... More
All as per item No. 11 here-in-before but comprising of the following :- (Near 28 Mall)
INCOMING :-
(i) MCCB 4 pole , 250 Amps,50 Hz,415 Volts, 50 KA, with thermal & Magnetic release - 01 Nos (ii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No (iii) Ammeter digital type with 4 way rotary selector switch-01No (iv) CTs ratio 250/5 A ,class 1, ISI marked -01 sets of three (v) Indicating lamp- 01 set of three
(vi) Aluminium bus bar of rating 600A - set of four (vii) Rotary handle - 01 No OUTGOING :-
(i) MCCB 4 pole , 160 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 01 Nos. (ii) MCCB 4 pole , 125 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 02 Nos.
(iii) MCCB 4 pole ,100 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 03 Nos.
(iv) Rotary handle - 06 No
PLATFORM FOR PANEL :- Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. Note :-
(i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993 (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer . (iv) Energy meter is not included in the present scope of work and shall be shifted from Old LT Panel to New LT Panel. The rate for shifting is also deemed to be included in the quoted rates.
1
-
-
... More
All as per item No. 11 here-in-before but comprising of the following :- (Near 23 Mandir Marg)
INCOMING :-
(i) MCCB 4 pole, 400 Amps, 50 Hz, 415 Volts, 50 KA, with thermal & Magnetic release - 01 Nos (ii) Onload changeover 400 Amps -01 No (iii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No (iv) Ammeter digital type with 4 way rotary selector switch-01No (iv) CTs ratio 400/5 A ,class 1, ISI marked -01 sets of three (v) Indicating lamp- 01 set of three
(vi) Aluminium bus bar of rating 600A - set of four (vii) Rotary handle - 02 No OUTGOING :-
(i) MCCB 4 pole, 200 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 02 Nos.
(ii) MCCB 4 pole, 160 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 02 Nos. (iii) MCCB 4 pole, 125 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 03 Nos.
(iv) MCCB 4 pole, 100 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 03 Nos.
(v) Rotary handle - 10 No
PLATFORM FOR PANEL :- Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level.
1
-
-
... More
70 Sq mm 3.5 core.
900
-
-
... More
All as per item No. 11 here-in-before but comprising of the following :- (Mall Road)
INCOMING :-
(i) ACB 4 pole, 800 Amp, 50 KA, 415 Volt AC Horizontal draw out type motorized, front operated with Micro processor based LCD protection release for adjustable over current, short circuit and earth fault protection-01 No
(ii) Voltmeter digital type with 4 way rotary selector swicth -01 No. (iii) Ammeter digital type with 4 way rotary selector switch-01 No. (iv) CTs ratio 800/5 A ,class 1, ISI marked -01 sets of three (v) Indicating lamp- 01 set of three
(vi) Aluminium bus bar of rating 1600 Amp- set of four OUGOING :-
(i) MCCB 4 pole , 400 Amps,50 Hz,415 Volts, 36 KA with microprocessor release - 03 Nos. (ii) MCCB 4 pole , 200 Amps,50 Hz,415 Volts, 36 KA with microprocessor release - 02 Nos. (iii) Rotary handle - 05 No PLATFORM FOR PANEL :- Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. Note :-
(i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer
1
-
-
... More
All as per item No.11 here-in-before but comprising of the following :- (Near Mall road circle)
INCOMING :-
(i) MCCB 4 pole , 400 Amps,50 Hz,415 Volts, 50 KA, with thermal & Magnetic release - 01 Nos (ii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No (iii) Ammeter digital type with 4 way rotary selector switch-01No (iv) CTs ratio 400/5 A ,class 1, ISI marked -01 sets of three (v) Indicating lamp- 01 set of three
(vi) Aluminium bus bar of rating 600A - set of four (vii) Rotary handle - 01 No OUTGOING :-
(i) MCCB 4 pole , 315 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 01 Nos. (ii) MCCB 4 pole , 200 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 02 Nos.
(iii) MCCB 4 pole ,125 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 02 Nos.
(iv) Rotary handle - 05 No
PLATFORM FOR PANEL :- Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. Note :-
(i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993 (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer . (iv) Energy meter is not included in the present scope of work and shall be shifted from Old LT Panel to New LT Panel. The rate for shifting is also deemed to be included in the quoted rates.
1
-
-
... More
35 Sq mm 3.5 core.
2100
-
-
... More
All as per item No. 11 here-in-before but comprising of the following :- (Near 17 Mandir Marg)
INCOMING :-
(i) MCCB 4 pole , 400 Amps,50 Hz,415 Volts, 50 KA, with thermal & Magnetic release - 01 Nos (ii) Onload changeover 400 Amps -01 No (iii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No (iv) Ammeter digital type with 4 way rotary selector switch-01No (iv) CTs ratio 400/5 A ,class 1, ISI marked -01 sets of three (v) Indicating lamp- 01 set of three
(vi) Aluminium bus bar of rating 600A - set of four (vii) Rotary handle - 02 No OUTGOING :-
(i) MCCB 4 pole , 200 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 01 Nos.
(ii) MCCB 4 pole , 160 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 02 Nos. (iii) MCCB 4 pole , 125 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 03 Nos.
(iv) MCCB 4 pole , 100 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 03 Nos.
(v) Rotary handle - 09 No
PLATFORM FOR PANEL :- Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level.
1
-
-
... More
Supply, laying, jointing, testing and commissioning in replacment of LT underground cables 1100 volts grade, PVC insulated XLPE and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-1554 marked, laid in trenches complete all as specified and directed by Engineer- in- Charge. Cables of the following sizes:-
Note Excavation, earth work, cable protection, sand fillings, cable joint shall be measured and paid separately.
-
-
-
... More
S&F of 90 Watt LED street light fittings made up of pressure die cast housing with toughened glass and individual high power LEDs with secondary optics, IP66 protection complete all as specified and directed by Engineer- in- Charge.
5
-
-
... More
Note :-
(i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993 (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer. (iv) Energy meter is not included in the present scope of work and shall be shifted from Old LT Panel to New LT Panel. The rate for shifting is also deemed to be included in the quoted rates.
-
-
-
... More
All as per item No. 11 here-in-before but comprising of the following :- (Near 28 Mall)
INCOMING :-
(i) MCCB 4 pole , 400 Amps,50 Hz,415 Volts, 50 KA, with thermal & Magnetic release - 01 Nos (ii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No (iii) Ammeter digital type with 4 way rotary selector switch-01No (iv) CTs ratio 400/5 A ,class 1, ISI marked -01 sets of three (v) Indicating lamp- 01 set of three
(vi) Aluminium bus bar of rating 600A - set of four (vii) Rotary handle - 01 No OUTGOING:-
(i) MCCB 4 pole , 250 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 01 Nos. (ii) MCCB 4 pole , 200 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 02 Nos.
(iii) MCCB 4 pole ,125 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 01 Nos.
(iv) Rotary handle - 04 No
PLATFORM FOR PANEL :- Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. Note :-
(i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993 (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer. (iv) Energy meter is not included in the present scope of work and shall be shifted from Old LT Panel to New LT Panel. The rate for shifting is also deemed to be included in the quoted rates.
1
-
-
... More
M&L for GI Tubes of size 50 mm dia light grade, galvanised, with all fitting, laid in trenches for protection of cable in road /drain crossing complete all as specified and directed by Engineer- in- Charge.
50
-
-
... More
M&L for returning filling in, including spreading, levelling, watering and well ramming soil in layers not exceeding 25 cm thick complete all as specified and directed by Engineer- in- Charge.
547.66
-
-
... More
Note :-
(i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993 (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer. (iv) Energy meter is not included in the present scope of work and shall be shifted from Old LT Panel to New LT Panel. The rate for shifting is also deemed to be included in the quoted rates.
-
-
-
... More
95 Sq mm 3.5 core.
100
-
-
... More
185 Sq mm 3.5 core.
1000
-
-
... More
PLATFORM FOR PANEL :- Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. Note :-
(i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993 (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer. (iv) Energy meter is not included in the present scope of work and shall be shifted from Old LT Panel to New LT Panel. The rate for shifting is also deemed to be included in the quoted rates.
-
-
-
... More
S&F of sub class B bricks having minimum compressive strength 75 Kg/ Sqcm laid in trenches for cable protection etc complete all as specified and directed by Engineer- in- Charge.
18981
-
-
... More
All as per item No. 11 here-in-before but comprising of the following :- (Near 16 Mall road)
INCOMING :-
(i) MCCB 4 pole , 400 Amps,50 Hz,415 Volts, 50 KA, with thermal & Magnetic release - 01 Nos (ii) Onload changeover 400 Amps -01 No (iii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No (iv) Ammeter digital type with 4 way rotary selector switch-01No (iv) CTs ratio 400/5 A ,class 1, ISI marked -01 sets of three (v) Indicating lamp- 01 set of three
(vi) Aluminium bus bar of rating 600A - set of four (vii) Rotary handle - 02 No OUTGOING :-
(i) MCCB 4 pole , 160 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 02 Nos. (ii) MCCB 4 pole , 125 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 04 Nos.
(iii) MCCB 4 pole , 100 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 04 Nos.
(iv) Rotary handle - 10 No
PLATFORM FOR PANEL :- Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. Note :-
(i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993 (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer . (iv) Energy meter is not included in the present scope of work and shall be shifted from Old LT Panel to New LT Panel. The rate for shifting is also deemed to be included in the quoted rates.
1
-
-
... More
50 Sq mm 3.5 core.
900
-
-
... More
240 Sq mm 3.5 core.
905
-
-
... More
All as per item No. 11 here-in-before but comprising of the following :- (Near Gate No :- 03 and HRC)
INCOMING :-
(i) MCCB 4 pole , 250 Amps,50 Hz,415 Volts, 50 KA, with thermal & Magnetic release - 01 Nos (ii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No (iii) Ammeter digital type with 4 way rotary selector switch-01No (iv) CTs ratio 250/5 A ,class 1, ISI marked -01 sets of three (v) Indicating lamp- 01 set of three
(vi) Aluminium bus bar of rating 400A - set of four (vii) Rotary handle - 01 No OUTGOING :-
(i) MCCB 4 pole , 100 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 02 Nos. (ii) MCCB 4 pole , 125 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 03 Nos.
(iii) Rotary handle - 05 No
PLATFORM FOR PANEL :- Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. Note :-
(i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993 (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer. (iv) Energy meter is not included in the present scope of work and shall be shifted from Old LT Panel to New LT Panel. The rate for shifting is also deemed to be included in the quoted rates.
2
-
-
... More
Note : Contractor should procure and provide 50 % of the material as listed above within 15 days of the placing of work order and shall be verified by the Engr-in-charge.
-
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements