Jawaharlal Nehru University Tender
If you're typing tender ID over and again or finding it difficult to go through the cumbersome government websites for looking at Delhi tenders online. We have come up with a solution i.e. we have collated every eprocurement Delhi tender on BidAssist. Also, for any queries related to an e-tender Delhi, like the bidding process, registration process, etc., the same are explained below.
Jawaharlal Nehru University - JNU Tender
Civil And Construction
Water Storage And Supply
Eprocure
Opening Date6 Sep 2024
Closing DateCancelled
Tender Amount₹ 26,65,978
Costs
EMD
₹ 53,320Document Cost
Refer DocumentsTender Fee
Refer Documents
Summary
Up-gradation Of Water Supply Pumping System Of Jnu Campus-jnu/engg./11/2024-25
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_JNU_824813_1Tender No
JNU/Engg./11/2024-25Tender Authority
Jawaharlal Nehru University ViewPurchaser Address
-Website
http://https://www.jnu.ac.in/main/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
Details_of_corrigendum_added_in_GCCN
Correction_Slip_GCC_Maintenance_Work_1_to_9
BOQ Items
150 mm dia
1
3574
3574
Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following size as required:
-
-
-
150 mm dia
1
22762
22762
Providing, installation, testing and commissioning of non-return valve of following size confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washer etc. as required:
-
-
-
150 mm dia
1
17786
17786
Supply, Laying , Testing & Commissioning of 1100 V rated aluminium conductor steel wire/ strip armored XLPE power cable of following sizes as per IS-7098 part-I in the existing masonary open duct as required.
-
-
-
3½ x 95 sq. mm Armoured Alluminium cable
50
53550
1071
Fabrication, supply, installation, testing & commissioning of floor mounted electrical power distribution cubical panel board door, outdoor type made of 2 mm CRCA sheet fully compartmentalized duly dust & vermin proof powder coated & Phosphatized with 7 tank process, complete with following switch gear mounted thereon, earthing strip, connection , interconnection , sign writing etc. suitable mounting base plate/ angle iron i/c Brick/cement concrete foundation as per site requirement etc. as required with depth upto 500 mm
1)- Incoming-
a. 400 A, 50 kA, 3-Pole, D-type Thermal magnetic release MCCB- 01 No.
2)- Busbar-
a. 800 A capacity, 4 strip aluminium bus bar - 01 Set
3)- Outgoing-
a. 200 A, 50 kA, 3-Pole, D-type Thermal magnetic release MCCB- 01 No.
b. 160 A, 50 kA, 3-Pole, D-type Thermal magnetic release MCCB- 02 No.
c. 125 A, 50 kA, 3-Pole, D-type Thermal magnetic release MCCB- 02 No.
4)- Indication lights for R,Y,B-Phase- 01 set
5)- 3-phase digital ammeter(single function meter)- 05 Nos.
6)- Multifunction digital meter- 01 No.
1
127376
127376
Supply, Installation, Testing & Commissioning of Electrical motor driven horizontal split casing (HSC) type single stage pump sets suitable for the mentioned components, capacities and specificton
a) Pump:- 140 m3/hr capacitiy at head of 65 meter , 1450 RPM capacity horizontal split casing type double stage pump having CI casing, CI impeller, CI shaft sleeve, wearing rings of CI impeller, shaft of Carbon steel-40 & mechanical seal etc as required. Suction/delivery size is (125mm x 100mm). ( Efficiency not less than 70 % at duty point)
b) Motor:- Foot mounted Copper wound squirrel cage induction motor totally enclosed fan cooled(TEFC) type of 60 HP/45 kW, 1500 RPM for operation on 415 V ± 10 % , 50 Hz, 3-phase A.C. power supply conforming to IS: 325/IS 12615:2011 and with F class insulation and coupling, coupling gaurd & f-bolts etc. as required.
c) Base Plate:- Fabrication from suitable structural M.S. channel as per manufacturer's/JNU Engineer's recommendations for mounting both pump and motor there on duly finished and painted with synthetic enamelled paint, Nut & bolts etc. for complete motor & pump set.
d) Foundation:- Suitable C.C. pump foundation as per manufacturer's design anti vibration (cushy foot) heavy duty mounting pads of approved design duly finished with cement plaster etc complete as required.
e) Priming Arrangement:- Priming Arrangement with suitable size of GI pipe, Union, Socket, elbow etc. complete as required from discharge line to pump casing including dismentalling of old existing pump sets, GI pipes, valves, foundation etc complete as required.
f) Arrengement of suitable range of Pressure gauge.
Location:- Old pump House
1
689796
689796
SITC of indoor type star-delta type starter panel suitable for 75 H.P. pump (conforms to IS 13947(Part 4) & IEC 60947-4) complete with 70 A to 100 A(AC3 duty) rating power contractor , Timer , start & stop push button , over load protection , single phase protection in 1.6 mm thick CRCA sheet with powder coated painted mounted on 50x50x6 mm size angle iron complete with earthing, connection, interconnection, sign writting etc. as requirred .
2
205162
102581
Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbow, tees, flanges, tapers, nut-bolts, gaskets etc. and fixing the pipe on the wall/celling with suitable clamp/support frame and painting with two or more coats of synthatic enamel paint of required shade complete as required:
-
-
-
100 mm dia
3
7665
2555
Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following size as required:
-
-
-
100 mm dia
1
14641
14641
Providing, installation, testing and commissioning of non-return valve of following size confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washer etc. as required:
-
-
-
100 mm dia
1
11050
11050
Supply, Installation, Testing & Commissioning of Electrical motor driven horizontal split casing casing (HSC) type single stage pump sets suitable for the mentioned components, capacities and specificton
a) Pump:- 140 m3/hr capacitiy at head of 90 meter , 2950 RPM capacity horizontal split casing type single stage pump having CI casing, Bronze impeller, CI shaft sleeve, wearing rings of CI impeller, shaft of Carbon steel-40 & mechanical seal etc as required. Suction/delivery size is (125mm x 100mm). ( Efficiency not less than 70 % at duty point)
b) Base Plate:- Fabrication from suitable structural M.S. channel as per manufacturer's/JNU Engineer's recommendations for mounting both pump and motor there on duly finished and painted with synthetic enamelled paint, Nut & bolts etc. for complete motor & pump set.
c) Foundation:- Suitable C.C. pump foundation as per manufacturer's design anti vibration (cushy foot) heavy duty mounting pads of approved design duly finished with cement plaster etc.
d) Priming Arrangement:- Priming Arrangement with suitable size of GI pipe, Union, Socket, elbow etc. complete as required from discharge line to pump casing including dismentalling of old existing pump sets, GI pipes, valves, foundation etc complete as required.
e) Arrengement of suitable range of Pressure gauge.
Location:- East gate pumping station (for water feeding from rectangular sump)
1
276889
276889