If you're typing tender ID over and again or finding it difficult to go through the cumbersome government websites for looking at Delhi tenders online. We have come up with a solution i.e. we have collated every eprocurement Delhi tender on BidAssist. Also, for any queries related to an e-tender Delhi, like the bidding process, registration process, etc., the same are explained below.
Indian Institute Of Technology - IIT Tender
Security and Emergency Services
Eprocure
Opening Date6 Feb 2024
Closing Date15 Feb 2024
Tender Amount₹ 2,82,88,100
Costs
EMD
₹ 5,65,762Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_IIT_794089_1Bid Award Id
ViewTender No
IITD/WORKS(SP-4534)/2023Tender Authority
Indian Institute Of Technology ViewPurchaser Address
-Website
http://eprocure.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
S/I/T/C of Addressable Fire Detection-cum-Alarm and Public Address System in Academic Blocks, Computer Service Center and Mathematics Department at IIT Delhi.
BOQ Items
Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required.
100
-
-
Supplying, installation, testing & commissioning of addressable strobe complete as required.
100
-
-
Supplying, installation, testing & commissioning of addressable phone control module complete as required.
30
-
-
Supplying, installation, testing & commissioning of fire fighter phone jack complete as required.
30
-
-
Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required.
550
-
-
Supplying, installation, testing & commissioning of fault isolator complete with base as required.
120
-
-
Supplying, installation, testing & commissioning of addressable beam detector with short circuit isolator (inbuilt or seperate) complete with emitter and receiver including connections with remote test features etc complete as required.
3
-
-
Supplying, installation, testing & commissioning of 6 inches dia, 2 watts, 70/100 volts ceiling speaker complete as required.
200
-
-
Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required.
90
-
-
Supplying, installation, testing & commisssioning of intelligent addressable multi criteria (Smoke + Heat + CO + IR) detector including suitable photo detector complete with base as required.
6
-
-
Supplying, installation, testing & commissioning of intelligent addressable High Sensitivity Photo Detector with sensitivity level of 0.02% to 2% Obs/Feet. The detector shall have the parabolic amplifier to focus the light beam to a very small volume near the receiving photo sensor at the incipient stage of fire- when the smoke particles are lesser than 0.3 microns intrudes inside the detection chamber & shall have better response time at much earlier stage of fire.. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches.
15
-
-
Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required.
1
-
-
Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required.
1
-
-
Supplying, installation, testing & commissioning of intelligent interface unit BACnet/ Modbus protocol i.e. supplying ommunication links between building management system and fire alarm control panel complete as required.
1
-
-
Supplying, installation, testing & commissioning of exit point directional sound speaker with voice and integral audio amplifier with selectable sound pulse patterns complete as required.
10
-
-
Supplying, installation, testing & commissioning of addressable fire control module complete as required.
40
-
-
Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
20000
-
-
PSupplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required.
-
-
-
Speaker cable Single pair, 2-core, 1.5 sqmm
4500
-
-
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
-
-
-
20mm dia
2340
-
-
Supplying, installing, testing and commissioning approved make Microprocessor based Multi-loop, Networkable Addressable Fire Alarm Control Panel with minimum 600 characters LCD display, 4000 trouble events including 1000 alarm log history events, Self Programmable alphanumeric keypad for programming. The panel should be equipped with sufficient number of loops & each loop shall have a capacity of minimum 125 detectors & 125 other devices excluding 20% spare. The panel shall work in degrade mode in case of CPU failure, Products not having this feature may offer Redundant CPU. Four access levels, flash EPROM, 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and 30 mins in alarm condition with the charging capacity of 200AH. The panel shall be capable of self programing without any dependancy on dongle or programming software. Quoted rate shall include supply of necessary software & hardware for programming the panel with all necessary licence. Panel shall have Modbus/ Bacnet over IP protocol for future integration with BMS. However, for present arrangement FA system will be standalone with 24x7 monitoring. The panel shall be capable for remote accessibility on a mobile app through cloud platform/solution. Complied to meet UL864, 10th Edition and FM Approved.
-
-
-
Ten Loop Panel
3
-
-
Two Loop Panel
2
-
-
Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V rms operating at 240 Volt AC Supply complete as required.
5
-
-
Supplying, installation, testing & commissioning of Talk Back ( Two Way Communication ) Fire Fighter telephone Control Panel and will be of same make of FAS Panel and seamlessly integrated. The panel shall be seamlessly Integrated to 8 channel Digital Voice Evacuation System Controller capable of broadcasting Evacuation Messages on same peer-to-peer Network and 2 ways Communication Fire Fighters System. The Fire Fighters Telephone System shall be capable of having minimum 30 Telephones in conference in multiple FFT Risers.
1
-
-
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.
-
-
-
1 run of cable
900
-
-
Sub Head 2 :- (AMC) Supplementry agreement shall be formed.
Routine, preventive and breakdown maintenance & round the clock x 7 days monitoring of installed Fire Detection & Alarm system by deputing skilled technical [minimum ITI Electrical / Electronics / Instrumentation passed] person[s] who shall be vigilant and be available round the clock x 7 days etc. as required. [N.B. - [a] Materials, if any, required due to fault / malfunction of the system beyond DLP to be given by the Institute & to be replaced by the contractor [b] Attendance of deputed staff shall be maintained through manual as well as biometric machine to be kept in the fire control room [c] any shortfall of attendance of staff will affect the billing proportionately [d] Latest Labour regulation shall be complied strictly]. 1st Year : Free of Cost [ Totally Comprehensive] 1 Job means for a period of 01 month
-
-
-
2nd year
12
-
-
3rd year
12
-
-
4th year
12
-
-
5th year
12
-
-
6th year
12
-
-