Delhi Transport Corporation Tender
If you're typing tender ID over and again or finding it difficult to go through the cumbersome government websites for looking at Delhi tenders online. We have come up with a solution i.e. we have collated every eprocurement Delhi tender on BidAssist. Also, for any queries related to an e-tender Delhi, like the bidding process, registration process, etc., the same are explained below.
Delhi Transport Corporation - DTC Tender
Civil And Construction
Civil Works Others
Eprocure
Opening Date25 Jul 2024
Closing Date5 Aug 2024
Tender Amount₹ 12,71,205
Costs
EMD
₹ 25,425Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_DTC_260058_1Bid Award Id
ViewTender No
Dy.CGM(Civil)/CED/Elect. /2024-25/05Tender Authority
Delhi Transport Corporation ViewPurchaser Address
-Website
http://http://www.dtc.nic.in/home/delhi-transport-corporation-dtc
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
100
28100
281
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
-
-
-
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
100
13700
137
4 X 2.5 sq. mm + 2 X 2.5 sq. mm earth wire
100
21500
215
Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/recessed steel/PVC conduit including dismantling as required.
-
-
-
Group C
25
11300
452
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required.
-
-
-
3 x 1.5 sq. mm
50
2500
50
3 x 2.5 sq. mm
50
3750
75
5 x 4 sq. mm
125
22750
182
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface /recess including cutting the wall and making good the same in case of recessed conduit as required.
-
-
-
25 mm
225
15525
69
Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required.
-
-
-
5/6 A switch
25
850
34
15/16 A switch
25
1875
75
3 pin 5/6 A socket outlet
25
1050
42
6 pin 15/16 A socket outlet
25
2150
86
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
50
14400
288
Supplying and fixing metal box of 180 mm X 100 mm X 60 mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 A & 15/16 A socket outlet and 15/16 A piano type switch, connections, painting etc. as required.
15
4305
287
Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required.
100
4600
46
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.
-
-
-
Group C
40
16600
415
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
-
-
-
100 A, 30kA, FPMCCB
1
5360
5360
125 A, 36kA, FPMCCB
1
5449
5449
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/ RCCB/ Isolator)
-
-
-
4 way (4 + 12), Double door
2
4396
2198
6 way (4 + 18), Double door
2
5318
2659
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
-
-
-
4 way (4 + 12), Double door
1
4502
4502
8 way (4 + 24), Double door
1
5664
5664
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
-
-
-
Single pole
60
10380
173
Triple pole
12
8400
700
Supplying and fixing following rating, four pole, (three phase and neutral), 415 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
-
-
-
63 A
4
9208
2302
Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 A, "C" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
5
12440
2488
Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required.
6
22032
3672
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 meter below ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50 mm)
3
255
85
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
80
10320
129
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required.
-
-
-
Upto 35 sq. mm
200
41200
206
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on wall surface as required.
-
-
-
Upto 35 sq. mm (clamped with 1mm thick saddle)
100
2500
25
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.
-
-
-
4 X 25 sq. mm (28mm)
10
2580
258
4 X 50 sq. mm (35 mm)
5
1790
358
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level)
including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
-
-
-
90 mm dia (OD-90 mm & ID-76 mm nominal)
100
16300
163
120 mm dia (OD-120 mm & ID-103 mm nominal)
100
22900
229
Supply of XPLE insulated PVC sheathed Armoured AL conductor cable 1.1 KV grade conforming to IS-7098 of size 4X16 sq. mm.
100
37100
371
Supply of XPLE insulated PVC sheathed Armoured AL conductor cable 1.1 KV grade conforming to IS-7098 of size 4X25 sq. mm.
100
46700
467
Supply of XPLE insulated PVC sheathed Armoured AL conductor cable 1.1 KV grade conforming to IS-7098 of size 4X50 sq. mm.
200
168000
840
Supplying & fixing of LED flood light fittings 1X100 Watt IP - 66
16
100896
6306
Supplying & fixing of LED flood light fittings 1X60 Watt IP - 66
24
100488
4187
S/I/T/C of complete LED Tube fitting 20 watt
100
38200
382
S/I/T/C of 48'' Ceiling fan High Speed
50
143500
2870
S/I/T/C of Industrial Wall mounted fan 24"
5
71240
14248
S/I/T/C of Exhaust fan 15" (1400RPM)
4
22456
5614
Dismantling and Shifting work of old/existing electric fittings in maintenance shed , workshop shed, etc as required.
1
5000
5000
Rate (DSR-2016 + Add prevailing cost index @ 31.27% On DSR-2016 rate)S. no. 1 to 25.2